21 00 00

advertisement
SECTION 21 00 00 - FIRE SUPPRESSION
PART 1 - GENERAL
1.1
RELATED DOCUMENTS
A.
1.2
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
SUMMARY
A.
This section is intended to describe the fire protection equipment and devices for the fire
suppression work.
B.
This section includes the following:
1.
2.
3.
4.
5.
6.
C.
Related sections include the following:
1.
2.
3.
4.
5.
1.3
Applicable requirements of Section 22 05 00, Basic Materials and Methods.
Combination wet standpipe /
Preaction sprinkler system, including piping, alarm valve, deluge valve, air compressor,
sprinkler heads, valves, accessories.
Clean agent fire extinguishing system.
Through-penetration fire-stop systems at penetrations through floors and fire or smoke
rated walls or partitions will be provided by Contractor for Division 07. Refer to Section
22 05 00 for work in this section.
Miscellaneous fire protection accessories.
All applicable sections of Division 1
Division 7: Sealants
Section [22 05 00: Basic Materials and Equipment
Section 22 05 48: Vibration Isolation and Seismic Restraints
Section 22 05 13: Electrical Requirements for Plumbing Equipment
REFERENCES
STANDARDS
A.
AND
REQUIREMENTS
OF
REGULATORY
AGENCIES
AND
Codes and Standards: The fire protection equipment and installation shall conform to the
requirements of all applicable codes, rules, regulations and standards, including, but not limited
to, the following:
1.
2.
3.
4.
International Building Code, 2006 New Jersey edition
NFPA 13 - Standard for the Installation of Sprinkler Systems
NFPA 14 - Standard for the Installation of Standpipe and Hose Systems
NFPA 20 - Standard for the Installation of Centrifugal Fire Pumps
21 00 00 - 1 of 31
Construction Documents
20080548
H2410
5.
6.
7.
8.
9.
10.
NFPA 24 - Standard for the Installation of Private Fire Service Mains and Their
Appurtenances
NFPA 25 - Standard for the Inspection, Testing and Maintenance of Water-Based Fire
Protection Systems
NFPA 70 - National Electrical Code
NFPA 72 - National Fire Alarm Code
NFPA 75 - Protection of Information Technology Equipment
NFPA 2001 - Standard on Clean Agent Fire Extinguishing Systems
B.
NEMA MG-1: Motors and Generators
C.
NEMA ICS-6: Enclosures for Industrial Control and Systems
D.
NICET: National Institute for Certification in Engineering Technologies
E.
UL 448: Pumps for Fire Protection Service
1.4
SUBMITTALS
A.
Provide submittals in accordance with Article 2.1 of this section and in accordance with Section
01 33 00, Submittal Procedures, in sufficient detail to verify full compliance with the
requirements of the contract documents.
B.
Before starting work, submit Contractor's documentation as specified in the Quality Assurance
article of this section.
C.
Submit data sheets for all products listed in this section. Where data sheets include information
on multiple sizes or types of materials, clearly indicate which item is being submitted for
review.
D.
Submit reflected ceiling plans showing proposed location of sprinkler and clean agent heads
and/or nozzles, and actuating devices, with respect to ceiling lights, diffusers, ceiling grid
framing members, etc. Be responsible for verifying that spacing of heads located near surface
mounted and/or suspended lighting fixtures, HVAC diffusers and any other obstruction
complies with applicable NFPA requirements.
E.
After review of reflected ceiling plan, prepare working plans of installation. Include size of all
piping, method of anchoring and hanging pipe, location and type of valves, position, type and
temperature ratings of sprinkler heads, material and equipment list indicating manufacturers'
names and types, structural, mechanical, electrical and architectural coordinating information,
and the various other items pertinent to the complete installation of the systems. Indicate
seismic restraint locations and details when seismic restraint requirements are specified.
F.
Provide Clean Agent Extinguishing System submittals as specified in this section.
G.
Working plans shall comply with the requirements of applicable NFPA standard, shall be
prepared at a scale of not less than 1/8" = 1'-0" and shall bear either the seal of a registered
professional engineer experienced in fire protection system design or copy of NICET
certification for the responsible design professional prior to submission to authority having
21 00 00 - 2 of 31
Construction Documents
20080548
H2410
jurisdiction. Designer NICET or professional engineering qualifications must meet or exceed
the requirements of the Authority Having Jurisdiction.
H.
Obtain approval and stamp from all authorities having jurisdiction of working plans, andclean
agent extinguishing system design documentation as specified in this Section, and sprinkler
system hydraulic calculations and submit 6 copies of the approved and stamped plans and
system design calculations cover summary sheet only bearing PE seal or NICET certification to
Architect for review before starting any work.
I.
Architect will review working plans for compliance and conformance with Contract Documents
only and not for adequacy of system design. Architectural review does not relieve Contractor of
full responsibility for system design.
J.
Where the Contractor must revise and resubmit, the revised submittal shall be accompanied by a
written response to all previous submittal comments. Failure to provide written response to
previous comments shall be cause for rejection of the submittal.
1.5
WARRANTY AND CONTRACT CLOSEOUT
A.
Comply with warranty and closeout requirements specified in Division 00.
B.
Warranty: Refer to BIDDING AND CONTRACT REQUIREMENTS and to DIVISION 1 GENERAL REQUIREMENTS.
C.
Contract Closeout
1.
2.
Include information for all products specified in this section in the operating and
maintenance manual.
Provide the following as specified in this section:
a.
b.
c.
d.
e.
f.
g.
1.6
Inspection certificates
Test reports
Inspection agreement
Portable electric heating device for testing heat responsive units of preaction and
clean agent system
Clean agent extinguishing systems acceptance test reports, operation training, asbuilt drawings, operation and maintenance manuals.
Manufacturer's startup and test certificate for fire protection pump and associated
equipment.
"As-built" drawings to be in AutoCAD and PDF format.
SEISMIC REQUIREMENTS
A.
Seismic Design
1.
All new and existing-repalced fire suppression systems (equipment and piping) shall be
provided with seismic restraints in accordance with the requirements of the 2006
International Building Code, Chapter 16 and Division 22 Section “Vibration Isolation and
Seismic Restraints for Plumbing Systems”.
21 00 00 - 3 of 31
Construction Documents
20080548
H2410
2.
3.
Refer to Structural Drawings for seismic criteria to be used for this project.
Use a component Importance Factor, Ip, of 1.5 for all life safety systems required to
function during and after an earthquake; including, but not limited to:
a.
b.
c.
d.
4.
Use a component Importance Factor, Ip, of 1.5 for all systems and components required
for continuous operation of the facility or whose failure could impair the continued
operation of the building, including:
a.
b.
5.
6.
7.
8.
9.
1.7
Wet, dry, preaction, deluge sprinkler systems.
Standpipe systems.
Clean gas suppression system.
Fire pump.
Piping.
Suspended equipment.
Employ a Professional Engineer registered in the jurisdiction for which the project is
located to design all restraints necessary to meet the seismic requirements. Said Engineer
shall sign and seal all drawings and calculations prepared for this purpose.
Prior to first Application for Payment, provide a complete listing of all components and
elements that are to be seismically restrained and/or braced.
It is the entire responsibility of the equipment manufacturer to design their equipment so
that the strength and anchorage of the components of the equipment exceeds the force
level used to restrain and anchor equipment itself to the supporting structure. Factory
manufactured and/or field or shop fabricated equipment shall be designed to safely accept
and resist, at its points of anchorage or suspension without failure or permanent
displacement of the equipment, earthquake generated external forces required by the
code.
The preparation and submittal of product data and shop drawings to the Architect for
review shall constitute a representation by the manufacturer, contractor and vendor that
all components comply with the above requirements.
The functional and physical interrelationship of components and their effect on each
other shall be installed so that failure of an essential or nonessential architectural,
mechanical, electrical component shall not cause the failure of nearby essential
architectural, mechanical, or electrical components.
QUALITY ASSURANCE
A.
Sprinkler equipment and installation in accordance with recommendations of Owner's
Underwriters and requirements of local Fire authority having jurisdiction.
B.
Equipment and installation to meet requirements of:
1.
2.
3.
C.
National Fire Protection Association
Insurer: Marsh USA, Inc.
Local and State codes and regulations.
Manufacturers: All products and materials utilized in the fire protection systems shall be listed
for fire protection service by Underwriters' Laboratories (UL) and approved for fire protection
21 00 00 - 4 of 31
Construction Documents
20080548
H2410
service by Factory Mutual (FM). Factory Mutual approval is required when the Factory Mutual
Engineering Division is included in the paragraph above.
D.
Contractor
1.
2.
3.
1.8
The Fire Protection Contractor for the fire protection system shall be qualified for the
work specified herein, regularly engaged in the installation of automatic fire suppression
systems and equipment.
The Fire Protection Contractor shall have a minimum of five years experience in the
installation of fire suppression systems. Upon request, documentation shall be submitted
to show that the Fire Protection Contractor has provided similar systems to those
specified herein. Documentation on at least 3 similar systems shall be provided including
the system size and the name of a contact person at the facility.
Documentation shall be provided to show that all fire protection systems is designed by
an employee with a Level III or Level IV NICET (National Institute for Certification in
Engineering Technologies) certification in automatic fire suppression system layout. If
such a certified individual is not employed, adequate documentation shall be provided to
show comparable training and experience of the designer.
DESIGN BASIS
A.
Drawings indicate areas to be protected by Fire Protection Systems and show location of main
water supply and risers. Drawings are diagrammatic and not necessarily complete and work is
not limited to that shown. Design, arrangement, size and location of risers, feed mains, cross
mains, branch lines and drains and spacing, number and types of heads must conform with
requirements of Authorities, Standards, and Codes for the hazards and applicable occupancies.
B.
Number and Location of Sprinkler Heads
1.
2.
3.
C.
Where head location is not shown on the drawings, provide coordinated layout with the
ceiling plan. Locate heads in the center of ceiling tiles.
Where head locations are shown on the drawings, provide at the locations shown as a
minimum. If additional heads are required to conform with requirements of authorities,
standards and codes for the hazard and application, coordinate head layout with Architect
before preparing submittals.
Provide all additional sprinklers required for a complete sprinkler system installation in
compliance with NFPA 13. Additional sprinklers in excess of quantities indicated on
drawings shall be provided at no additional cost when required to comply with NFPA 13
(13R) obstruction, location and spacing requirements.
Sprinkler system shall be hydraulically designed in accordance with the following criteria:
1.
All mechanical rooms, electrical equipment storage rooms and similar areas:
a.
b.
2.
Minimum design density of 0.19 gpm per square foot over the hydraulically most
remote 2,600 square feet.
Maximum protection area per sprinkler of 130 square feet.
All Mechanical Room spaces and similar Ordinary Hazard Group I hazard areas.
21 00 00 - 5 of 31
Construction Documents
20080548
H2410
a.
b.
Minimum design density of 0.15 gpm per square foot over the hydraulically most
remote 1,950 square feet.
Maximum protection area per sprinkler of 130 square feet.
D.
Include a total hose stream demand of 250 gpm in the hydraulic calculations, including inside
and outside hose.
E.
For purposes of bidding, the contractor shall use the following water supply at the fire pump
discharge:
Flow, gpm
0
1,330
Pressure, psi
107 (Pump churn)
78
F.
The contractor shall perform or have the water authority perform an additional flow test prior to
the system design. In any case, where multiple water supply curves are available, the contractor
shall use the lowest available normal operation curve as the basis of design.
G.
Sprinkler system water velocity shall not exceed 20 feet per second.
H.
The combined sprinkler and hose stream system demand pressure shall include at minimum ten
(10) psig safety factor.
I.
Where there is a conflict between the drawings or specifications and any referenced standard,
include the item of greater cost in the work and bring such conflict to the attention of the
Architect for resolution.
1.9
INSPECTIONS
A.
1.10
A.
1.11
A.
Arrange and pay for all inspections, approvals, examinations and tests required by authorities
having jurisdiction as necessary to obtain complete and final acceptance of Fire Protection
Systems. Deliver certificates of all such inspections, approvals and tests to Architect and
Owner's representative after completion of the installation.
TESTS
Test fire protection systems as specified in [22 05 00, Basic Materials and Methods, as specified
in Part 3 of this section, and as required by applicable NFPA reference standard. Conduct tests
in presence of a representative of the fire insurance rating organization. Pay expenses in
connection with performing tests.
INSPECTION SERVICE
After completion of work and at the start of the warranty year, execute an "Inspection
Agreement" with the Owner without additional cost to the Owner that includes provision of
21 00 00 - 6 of 31
Construction Documents
20080548
H2410
inspection, testing and maintenance of all fire protection equipment in accordance with the
quarterly requirements of NFPA 25 and/or other appropriate reference standards. The
agreement shall cover four site visits by the contractor scheduled on a quarterly basis as agreed
by the Owner.
B.
1.12
After each inspection, submit to the Owner, insurance carrier and authority having jurisdiction
as directed by the Owner, a "Report of Inspection" on a standard form similar to those provided
in Appendix B of NFPA 25.
SEISMIC DESIGN
A.
Refer to Section 22 05 00, Article 1.10.
B.
Coordinate ceiling penetrations with ceiling installer to provide minimum clearance
requirements around sprinkler penetration per seismic requirements.
PART 2 - PRODUCTS
2.1
ACCEPTABLE MANUFACTURERS
A.
Subject to compliance with requirements, provide products of the following manufacture:
1.
Air Compressor
a.
b.
c.
d.
2.
Alarm Bell
a.
3.
Ames
Cla-Val
Conbraco
Febco
Hersey
Watts
Zurn
Clean Agent Extinguisher System
a.
5.
Potter Electric Signal Co.
Backflow Preventer (Double Check) (Detector Double Check)
a.
b.
c.
d.
e.
f.
g.
4.
General Air Products
Viking
Gast
Reliable
Dupont
Fire Extinguisher
21 00 00 - 7 of 31
Construction Documents
20080548
H2410
a.
b.
c.
6.
Fire Hose and Valve Cabinets
a.
b.
c.
d.
e.
7.
b.
General: Unless otherwise specified, any United States manufacturer whose products
comply with the reference standards. Submittals are not required where a
manufacturer is not specified.
Basic Piping and Fitting Materials and Accessories not Specified in this Section:
Refer to Section 22 05 00 and NFPA references.
Sprinkler Heads
a.
b.
c.
d.
e.
11.
Notifier
Potter Electric Signal Co.
Pipe and Fitting Materials
a.
10.
Crane
Tyco Fire and Building Products
Jenkins
Kennedy
Milwaukee
Mueller Co.
Stockham
Victaulic Company of America
Walworth
Anvil
Nibco
Monitor, Switches
a.
b.
9.
Allenco
Elkhart Brass Mfg. Co.
Potter-Roemer, Inc.
Sierra Standard Fire Equipment Co.
Croker
Fire Protection System Valves, Type FPSV
a.
b.
c.
d.
e.
f.
g.
h.
i.
j.
k.
8.
Ansul
Kidde, Inc.
Fyr-Fyter
Tyco Fire and Building Products
Reliable Automatic Sprinkler Co., Inc.
The Viking Corporation
Flexhead
Victaulic Company of America
Sprinkler Valve Assemblies Preaction)
a.
b.
Tyco Fire and Building Products
Victaulic Company of America
21 00 00 - 8 of 31
Construction Documents
20080548
H2410
c.
d.
2.2
Reliable Automatic Sprinkler Co., Inc.
The Viking Corporation
AIR COMPRESSOR
A.
For preaction sprinkler system, provide air compressor mounted on a concrete pad near
preaction valve riser pipe valve.
B.
Size compressor to suit the requirements of the system and include an automatic starting device,
air pressure maintenance device, necessary electrical accessories, trim and piping connections.
Provide adjustable type pressure control for cut in and cutout points as well as range adjustment.
C.
Air compressors shall be General Air Products, Reliable, Viking or equal. Air compressor shall
be UL Listed for sprinkler service. Air compressors shall be tank mounted type when an
accelerator is required on sprinkler system, and otherwise required by NFPA 13.
1.
2.
3.
4.
5.
6.
7.
[215 gallon max.] #OL215 33AC 2.60 cfm 1/3 hp 120V, single phase
[335 gallon max.] #OL335 50AC 4.50 cfm 1/2 hp 120V, single phase
[620 gallon max.] #LT620 150 7.60 cfm 1 hp [208] [460]V, 3 phase
[900 gallon max.] #LT900 150 11.00 cfm 1-1/2 hp [208] [460]V, 3 phase
[1220 gallon max.] #LT1220 200B 14.80 cfm 2 hp [208] [460]V, 3 phase
[2000 gallon max.] #LT2000 300B 24.40 cfm 3 hp [208] [460]V, 3 phase
[2500 gallon max.] #LT2500 500B 30.20 cfm 5 hp [208] [460]V, 3 phase
D.
Air compressor for dry pipe or preaction piping systems subject to freezing conditions shall be
equipped with a UL listed FM approved dual tower regenerative desiccant dryer with a
coalescing prefilter capable of providing -20o F dewpoint air.
E.
Install a relief valve between the gas supply and the sprinkler system arranged to relieve at 5 psi
(0.3 bar) above the maximum recommended gas pressure maintained within the sprinkler
system. Install a check valve on the connection between the gas supply and the pre-action
sprinkler system.
2.3
FIRE EXTINGUISHER
A.
2.4
Fire extinguisher(s) will be provided under Division 10.
FIRE DEPARTMENT VALVE CABINETS
A.
Provide where indicated on drawings fire department valve cabinets. Mount fire department
standpipe valves in valve cabinet. Valve cabinets for nonpressure regulating type angle hose
valves shall be Potter-Roemer or equal recessed type #1810 with Suffix-F flush solid metal
door.
B.
C.
Cabinet shall be 20 gauge steel for box frame and tubular door. Continuous steel hinge shall be
provided. All surfaces shall have a recoatable white polyester finish. Door and frame shall
21 00 00 - 9 of 31
Construction Documents
20080548
H2410
have white polyesterfinish. Provide equipment identification with contrasting colored lettering
not less than 2-in in height.
2.5
MONITOR SWITCHES
A.
Provide supervisory switch on each system control valve(s). The mechanism shall be contained
in a weatherproof, die cast aluminum housing, which shall provide a 3/4 inch tapped conduit
entrance and incorporate the necessary facilities for attachment to the valve. Switch housing
shall have a minimum rated capacity of 1 amp at 125V AC and 1/4 amp at 24V DC. The entire
installed assembly shall be tamperproof and arranged to cause a switch operation if the housing
cover is removed or if the unit is removed from its mounting. Valve supervisory switches shall
be designed for valve mounting either vertically or horizontally. Said switches shall be
normally closed type capable of detecting any motion from the valve full open position.
B.
High/low air pressure supervisory switches shall be provided for and the preaction sprinkler
systems. Device shall provide output signal to the fire alarm system when air pressure drops
fifty percent below normal system pressure or rises 10 psi above normal system pressure.
2.6
PIPE AND FITTINGS
A.
General
1.
2.
B.
Pipe and fitting materials and joint types are specified in the following "Piping Class"
paragraphs. Application material and joint type which will be permitted for specific
services are specified hereinafter in the Article titled "Piping System Requirements".
Where more than one Piping Class is listed under "Piping System Requirements" for a
service, use any of listed classes, unless otherwise specified or indicated, but systems'
materials must be consistent throughout the work.
Pipe and fittings shall conform to the latest issue of the standards referred to hereinafter.
Each length of pipe and each fitting shall be marked with the manufacturer's name brand
and specification code designation to which it belongs.
Piping Class S8
ITEM
LIMITS
DESCRIPTION
PIPE
6 inch & smaller
Steel pipe Schedule 40, nipples, Schedule 80,
black, except preactionsystem
piping to be internally galvanized; threadable
lightwall steel
with a corrosion resistance rating equal to
Schedule 40 is also acceptable (Allied Dynathread
or equal)
8 inch & larger
Steel pipe Schedule 30
21 00 00 - 10 of 31
Construction Documents
20080548
H2410
JOINTS
2 inch & smaller
Screwed or welded
Welded or grooved mechanical
FITTINGS
2-1/2 inch &
larger
2 inch & smaller
Butt weld steel or steel grooved type
UNIONS
2-1/2 inch &
Larger
2 inch and smaller
2-1/2 inch
and larger
All sizes
Companion flanges
Class 150 malleable iron threaded or socket welded
Class 250 threaded, Class 3000 socket welded
FLANGES
Class 150 forged steel
Reference Standards
1.
Steel Pipe: ASTM A 53, Grade B black carbon steel. ASTM A 135 for Dynathread
2.
Malleable Iron Threaded Fittings: ASTM A 197 black malleable iron. ANSI B16.3
Classes 150 and 300 banded, with ANSI B2.1 standard taper pipe threads.
3.
Welded Fittings for Black Steel Pipe: 2 inch and smaller - Class 3000 forged steel socket
welded fittings, ASTM A 105 and ANSI B16.11; 2-1/2 inch and larger - ASTM A 234,
Grade A and ANSI B16.9. All elbows long radius.
4.
Flanges for Welded Black Steel Pipe: Forged steel, ASTM A 181 Class 60, ANSI B16.5
for Classes 150 and 300.
5.
Galvanized Pipe and Fittings: Same as black steel and malleable iron specified above
except coated with ASTM B 6 slab zinc inside and outside by the hot-dip process.
2.7
PIPING SYSTEM REQUIREMENTS
A.
Fire Protection
Service
Valve
Pipe
Type/Class Class
Fire Protection Water
1. Underground
FPSV*
DI1*
2. Above Ground
FPSV**
S8**,
*
*
*Comply with NFPA 24 and local Code requirements
**Comply with NFPA 13 and applicable Building Code, except plastic
piping not allowed
Clean Agent Extinguishing System
*Comply with NFPA 2001 and applicable Building Code
21 00 00 - 11 of 31
Construction Documents
20080548
H2410
2.8
PREACTION SPRINKLER SYSTEM
A.
2.9
Provide approved type automatic sprinkler preaction system consisting of closed sprinkler heads
properly spaced to cover the areas protected, including electrically operated deluge valves
actuated by properly spaced electric smoke and heat type detector heads and manual electric
releases. Preaction release shall be via the building EST 3 fire alarm system. Automatically
maintain supervisory air pressure, air compressor and air trim piping. System shall be in full
accordance with the requirements of the National Fire Protection Association, and shall be
Underwriters Laboratory listed, FM approved. Automatic preaction sprinkler system shall be
provided for areas indicated on drawings. System shall be similar to Viking single interlocked
electrically released system.
SPRINKLER HEADS
A.
Provide sprinklers as shown or specified, and finished as follows:
1.
2.
Quick response upright type with bronze finish.
Quick response semi-recessed with white finish dry pendant.
B.
All sprinkler heads shall be the product of a single manufacturer.
C.
Sprinklers in finished areas attached to concealed piping shall be pendent or sidewall type with
chrome or factory painted finish and escutcheon or cover plate as specified.
D.
Sprinklers in unfinished areas connected to exposed piping shall be upright, pendent or sidewall
type with bronze finish unless specified otherwise.
E.
Sprinklers for light hazard occupancies shall be quick response type where required by code.
2.10
A.
VALVES
General
1.
2.
Valves are specified by Valve Type and, for some services, several valve types are grouped
by "Valve Class" in this section. Application is stated in the "Piping System Requirements".
Where more than one Valve Type or Valve Class is listed for a service, use any of the listed
Types or Classes, unless otherwise specified or indicated, but selection must be consistent
throughout the work.
Valve packing shall not contain asbestos.
B.
Refer to Section 22 05 00 for basic valves not specified in this section.
C.
Type FPSV, Fire Protection System Valves: Class 175 WWP, UL and FM listed for fire
protection service.
D.
Type FPSV, Fire Protection System Valves: Class 175 WWP, UL and FM listed for fire
protection service, equivalent to listed figure numbers. Stockham figure numbers are listed
except where noted otherwise.
21 00 00 - 12 of 31
Construction Documents
20080548
H2410
1.
2.
3.
4.
5.
6.
7.
8.
9.
2.11
Gate Valves 2 Inch and Smaller: Bronze, screw ends, solid disc, OS&Y. B-133.
Butterfly Valves 2 Inch and Smaller: Bronze, screwed ends, stainless steel disc and stem
with built-in supervisory control switch, Milwaukee Model BB-SCS01.
Gate Valves 2-1/2 Inch and Larger: Flanged, iron body, bronze trim, solid disc, OS&Y.
G-634.
Butterfly Valves 2-1/2 Inch and Larger: Lug body, cast iron body, EPDM seat,
aluminum-bronze disc, supervisory switch, Kennedy Model 911LE.
Check Valves 2-1/2 Inch and Larger: Horizontal swing type, iron body, bronze mounted,
composition disc, equipped with ball drip connection. Flanged, G-940. Threaded, G938.
Fire Department Valves at Standpipes: 2-1/2 inch 300 pound brass angle hose valve with
red handwheel complete with hose coupling, cap and chain, complying with local fire
department requirements.
Ball Valves 2 Inch Through 3 Inch: Ductile iron, grooved end, stainless steel ball, TFE
seat, built-in supervisory control switch, Victaulic Series 727.
Butterfly Valves 4 Inch Through 8 Inch: Ductile iron, grooved ends, ductile iron disc
with EPDM disc coating, built-in supervisory control switch, Victaulic Series 708.
Check Valves 4 Inch Through 8 Inch: Ductile iron, grooved ends, center lug, seat
integrally bonded to discs and replaceable, Victaulic Series 714.
WATER FLOW SWITCHES
A.
Provide in wet pipe sprinkler system, flow switch of paddle type with two (2) sets of Form "C"
single pole double throw (SPDT) contacts, suitable for maximum 120 volt AC or 24 volt DC
electrical service. Paddle type switches shall have a sensitivity setting to signal any flow of
water that equals or exceeds the discharge from the smallest orifice sprinkler head attached to
the system. Flow switch shall have an adjustable retard feature.
B.
Provide in dry pipe, preaction and deluge systems, a pressure type waterflow switch where
indicated. Switch shall be provided with two (2) sets of Form "C" contacts suitable for 120V
AC or 24V DC service.
2.12
A.
CLEAN AGENT EXTINGUISHING SYSTEM
Codes and Standards
1.
Applicable Publications: The following publications of the issues listed below, but referred
to thereafter by basic designation only, form a part of this specification to the extent
indicated by the references thereto.
a.
b.
c.
d.
e.
f.
NFPA No. 2001 - Clean Agent Fire Extinguishing Systems
NFPA No. 70 - National Electrical Code
NFPA No. 72 - National Fire Alarm Code
Factory Mutual Approval Guide
Requirements of the Authority Having Jurisdiction (AHJ)
Fike ECARO-25 Design, Installation, and Maintenance Manual
21 00 00 - 13 of 31
Construction Documents
20080548
H2410
g.
The standards listed, as well as all other applicable codes and standards shall be
used as "minimum" design standards. Also to be considered are the requirements
of the "Authority Having Jurisdiction" and good engineering practices.
B.
SCOPE: This specification outlines the requirements for a “Total Flood” ECARO-25 TM
Clean Agent Fire Suppression System utilizing DuPontTM FE-25TM as the fire extinguishing
agent. The work described in this specification includes all engineering, labor, materials,
equipment and services necessary, and required, to complete and test the suppression system.
The system shall be supplied and installed by the local authorized distributor: Suppression
Systems, Inc., 1-800-360-0687.
C.
GENERAL: Supply and install an Automatic Fire Detection and Clean Agent Fire
Extinguishing System. The total system shall be supplied and manufactured by a single source.
Model numbers hereafter described are as manufactured and distributed by Fike Protection
Systems, A Division of Fike Corporation, 704 South Tenth Street, Blue Springs, Missouri,
64015, (816)229-3405. Fike equipment is used to indicate the type and style of equipment
required. Equal equipment can be considered if it is submitted for approval in advance and
meets the engineering qualifications in design and intent. System shall be supplied and installed
by the local authorized distributor: Suppression Systems Inc., 800-360-0687.
All equipment shall perform as a part of a single system. The system design shall conform to all
standards as described in the National Fire Protection Association Pamphlet 2001 - "Clean Agent
Fire Extinguishing Systems" - Latest Edition. These standards shall be used as a minimum design
standard. Also considered are the requirements of the "Authority Having Jurisdiction" and good
engineering practices. All components shall be listed by Underwriters Laboratories (UL) and/or
Factory Mutual (FM).
1.
INSTALLER:
a.
b.
c.
d.
e.
f.
g.
The installing contractor shall be trained by the supplier to design, install, test and
maintain the ECARO-25 Suppression Systems.
The installing contractor shall be an experienced firm regularly engaged in the
installation of automatic Clean Agent, or similar, fire suppression systems in strict
accordance with all applicable standards.
The installing contractor must have a minimum of five (5) years experience in the
design, installation and testing of Clean Agent, or similar, fire suppression
systems. A list of systems of a similar nature and scope shall be provided on
request.
The installing contractor shall show evidence that the company carries sufficient
liability and completed operations insurance policy. These limits shall supersede
limits required in the general conditions of the specifications.
The installing contractor shall maintain, or have access to, a Clean Agent
recharging station. The installing contractor shall provide proof of his ability to
recharge the largest Clean Agent system within 24 hours after a discharge. Include
the amount of bulk agent storage available.
The installing contractor shall be an authorized stocking distributor of the Clean
Agent system equipment so that immediate replacement parts are available from
inventory.
The installing contractor shall show proof of emergency service available on a
twenty-four hour, seven-day-a-week basis.
21 00 00 - 14 of 31
Construction Documents
20080548
H2410
h.
2.
The installing contractor shall have a Nicet Level IV certified Engineer on their
staff.
SUBMITTALS:
a.
The installing contractor shall submit the following design information and
drawings for approval prior to starting work on this project:
1)
2)
3)
4)
5)
6)
7)
8)
9)
b.
D.
Field installation layout drawings having a scale of not less than 1:1000m
detailing the location of all agent storage tanks, pipe runs including pipe
sizes and lengths, control panel(s), detectors, manual pull stations, abort
stations, audible and visual alarms, etc.
Auxiliary details and information such as maintenance panels, door holders,
special sealing requirements and equipment shutdowns.
Separate layouts, or drawings, shall be provided for each level, ( i.e.; room,
underfloor, and above ceiling) and for mechanical and electrical work.
A separate layout or drawing, shall show isometric details of agent storage
containers, mounting details and proposed pipe runs and sizes.
Electrical layout drawings shall show the location of all devices and include
point-to-point conduit runs and a description of the method(s) used for
detector mounting.
Provide an internal control panel wiring diagram which shall include power
supply requirements and field wiring termination points.
Complete hydraulic flow calculations, from Fike’s FM Approved ECARO25 Flow Calculation Program, shall be provided for all engineered Clean
Agent systems. The individual sections of pipe and each fitting to be used,
as shown on the isometrics, must be identified and included in the
calculation. Total agent discharge time must be shown and detailed by zone.
Provide calculations for the battery stand-by power supply taking into
consideration the power requirements of all alarms, initiating devices and
auxiliary components under full load conditions.
A complete sequence of operation shall be submitted detailing all alarm
devices, shutdown functions, remote signaling, damper operation, time
delay and agent discharge for each zone or system.
Submit drawings, calculations and system component data sheets for approval to
the local Fire Prevention Agency, owners Insurance Underwriter and all other
Authorities Having Jurisdiction before starting installation. Submit approved plans
to the Architect/Engineer for record.
SCOPE:
1.
System Components: This specification covers the requirement for Engineered Automatic
Fire Detection and Fixed Fire Suppression System(s) using FE-25 as the extinguishing
agent:
a.
b.
Detection of products of combustion and fire shall be by devices listed by UL
and/or FM.
Alarm signals and systems supervision shall be by a control panel with battery
standby listed by UL and/or FM.
21 00 00 - 15 of 31
Construction Documents
20080548
H2410
c.
d.
2.
System Consideration and Requirements: In order to insure system effectiveness and owner
satisfaction, the contractor shall supply and install all specified equipment and accessories
for a complete, electrically supervised system as described and shown on the plans.
a.
E.
Release of FE-25 extinguishing agent shall be accomplished by an electrical signal
for the control panel and shall be in accordance with the requirements set forth in
NFPA 2001.
Extinguishing agent storage containers and nozzles shall be listed by UL and/or
FM.
System Drawings: The contractor shall specifically prepare plans which are to an
indicated scale with lettering no smaller than one-eight inch (⅛") and easily
reproducible. These plans will show the quantity, location and marking of all
systems components. Included shall be a description and routing of all piping.
Flow calculations shall be included per current edition of NFPA 2001. Care
should be taken to locate all agent storage containers as close to the protected area
as possible to minimize the time required for the extinguishing agent to reach the
fire. Container design shall permit on-site and in-place reconditioning and
refilling.
SYSTEM COMPONENTS:
1.
Control Equipment:
a.
b.
c.
d.
e.
f.
g.
The control panel shall be a SHP PRO (Single Hazard Panel) Control System, P/N
10-063-X-X-X, manufactured by Fike Protection Systems, Blue Springs, MO.
The SHP PRO Control System, and its components, shall be UL listed and FM
approved for releasing service and be suitable for Deluge Pre-action sprinkler
service.
The SHP PRO Control System shall perform all functions necessary to operate the
system detection, actuation and auxiliary functions, as outlined.
The SHP PRO Control System shall be capable of providing 7AH to 40AH battery
standby power supplies.
The SHP PRO Control System shall be microprocessor based with hardware and
software integration designed to guarantee reliability.
The SHP PRO Control System shall support Cross Zone, Sequential, Single
Detector Release and Manual Release detection/actuation methods.
The SHP PRO Control System shall provide the following capabilities and
functions:
1)
2)
3)
4)
5)
6)
7)
Three (3) Class B (Style Y) indicating appliance circuits rated for 2.0 amps
@ 24 VDC.
Four (4) Class B (Style A) initiating circuits
Optional Class A (Style D) module for initiating circuits
Eight (10) Status LEDs plus alpha-numeric display for troubleshooting: AC
normal; alarm; pre-discharge; release; supervisory; trouble;panel silenced,
abort,, release disabled, ground fault.
Programmable pre-discharge and discharge timers
Resettable and continuous auxiliary output power
Five (5) optional Abort types
21 00 00 - 16 of 31
Construction Documents
20080548
H2410
8)
9)
10)
11)
12)
13)
14)
2.
F.
Intelligent Transistor protection to prevent noise spikes and microprocessor
failure from inadvertently activating release outputs
A dedicated Disable switch for outputs
Three (3) dedicated Form C contacts configured for Alarm, Supervisory,
and trouble rated at 2.0A each. In addition up to 8 additional relay contacts,
programmable for alarm, trouble, pre-discharge, discharge, abort,
supervisory or waterflow functions, depending on panel configuration, rated
at 2.0A each utilizing CRM$ relay module. (P/N 10-2204)
Three (3) Form “C” relays, rated at 5 amps, are provided on the SHP PRO
panel board. Installation of the optional CRM4 Relay Module (P/N 102204) will provide four (4) additional 2 amp relays.
Multiple input power source - 120 VAC or 240 VAC @ 50/60 Hz
4.0 amp @ 24 VDC power supply to operate high current draw horns and
strobes.
Available in either Red or Gray finish
Electrical Installation: Wiring for the detection system, the extinguishing system, and
damper trip or releases shall be run in accordance with the one-line diagram schematic
diagrams provided by the specification. Wiring must be conduit. Use 14 AWG
MINIMUM, 600 volt, 105 C, UL listed wire. Make wire runs continuous unless unusually
long runs make splices unavoidable. Splices must be soldered; wire nuts are not acceptable.
NOTE: The 115 volt 60 Hz single phase power input line must be in separate conduit and
connected to the main building line through a separate 15 amp circuit dedicated to the
extinguishing system.
SYSTEM DESCRIPTION AND OPERATION:
1.
2.
3.
4.
5.
6.
The system shall be a Total Flood ECARO-25 Suppression System. System shall be
supplied by Suppression Systems, Inc., 800-360-0687.
The ECARO-25 system shall provide a minimum design concentration of 8.0%, by
volume, in all areas and/or protected spaces, at the minimum anticipated temperature
within the protected area. System design shall not exceed the PBPK molding maximum
exposure limit concentration level of 11.5%, by volume, unless provisions for room
evacuation, before agent release, are provided. All personnel should be able to leave the
protected space prior to the discharge or at least within 5 minutes of the commencement
of discharge. In the event Fike’s Maximized Piping System is implemented, a minimum
design concentration of 8.0%, by volume, shall be utilized.
The system shall be complete in all ways. It shall include all mechanical and electrical
installation, all detection and control equipment, agent storage containers, ECARO-25
agent, system actuation equipment, discharge nozzles, pipe and fittings, manual release
and abort stations, audible and visual alarm devices, auxiliary devices and controls,
shutdowns, alarm interface, caution/ advisory signs, functional checkout and testing,
training and all other operations necessary for a functional ECARO-25 Clean Agent
Suppression System.
Provide two (2) inspections during the first year of service. Inspections shall be made at
6 month intervals commencing when the system is first placed into normal service.
The general contractor shall be responsible for sealing and securing the protected spaces
against agent loss and/or leakage during the 10 minute "hold" period.
The system(s) shall be actuated by a combination of ionization and/or photoelectric
detectors installed at a maximum spacing of 250 sq. ft.(23.2 sq. mtr.) per detector, in both
21 00 00 - 17 of 31
Construction Documents
20080548
H2410
7.
8.
the room, underfloor and above ceiling protected spaces. If the airflow is one air change
per minute, photoelectric detectors only shall be installed at a spacing not to exceed 125
sq. ft. (11.6 sq. mtr.) per detector.
Detectors shall be wired in Sequential Detection method of operation, standard CrossZoned detection, or single detector release. No other detection / wiring arrangements will
be acceptable.
Automatic operation of each protected area shall be as follows:
a.
Actuation of one (1) detector, within the system, shall:
1)
2)
3)
Illuminate the "ALARM" lamp on the control panel face.
Energize an alarm bell and/or an optional visual indicator.
Transfer sets of 5 Amp rated auxiliary contacts which can perform auxiliary
system functions such as:
a)
b)
c)
b.
Actuation of a 2nd detector, within the system, shall:
1)
2)
3)
4)
5)
c.
4)
e.
G.
Illuminate the "PRE-DISCHARGE" lamp on the control panel face.
Energize a pre-discharge horn or horn/strobe device.
Shut down the HVAC system and/or close dampers.
Start time-delay sequence (not to exceed 60 seconds).
System abort sequence is enabled at this time.
After completion of the time-delay sequence, the ECARO-25 Clean Agent system
shall discharge and the following shall occur:
1)
2)
3)
d.
Operate door holder/closures on access doors. (By others)
Transmit a signal to a fire alarm system. (By others)
Shutdown HVAC equipment. (By others)
Illuminate a "SYSTEM FIRED" lamp on the control panel face.
Shutdown of all power to high-voltage equipment
Energize a visual indicator(s) outside the hazard in which the discharge
occurred.
Energize a "System Fired" audible device.
The system shall be capable of being actuated by manual discharge devices located
at each hazard exit. Operation of a manual device shall duplicate the sequence
description above except that the time delay and abort functions SHALL be
bypassed. The manual discharge station shall be of the electrical actuation type
and shall be supervised at the main control panel.
The system shall be capable of providing a “PRE-ALARM” feature that can give
advanced warning of a possible alarm condition.
MATERIALS AND EQUIPMENT:
1.
GENERAL REQUIREMENTS: The ECARO-25 Clean Agent System materials and
equipment shall be standard products of the supplier's latest design and suitable to
perform the functions intended. When one or more pieces of equipment must perform
the same function(s), they shall be duplicates produced by one manufacturer
21 00 00 - 18 of 31
Construction Documents
20080548
H2410
2.
ECARO-25 AGENT STORAGE AND DISTRIBUTION: Each system shall have its own
supply of clean agent.
a.
b.
c.
d.
e.
f.
g.
h.
The system design can be modular, central storage, or a combination of both
design criteria utilizing a fast acting rupture disc valve. The valve shall contain a
scored, non-fragmenting, rupture disc to provide immediate total discharge of the
ECARO-25 agent.
Systems shall be designed in accordance with the manufacturer's guidelines.
Each supply shall be located within the hazard area, or as near as possible, to
reduce the amount of pipe and fittings required to install the system.
The clean agent shall be stored in FIKE Series Agent Storage Containers.
Containers shall be super-pressurized, with dry Nitrogen, to an operating pressure
of 360 psi @ 70 F (25 bar @ 21 C). Containers shall be of high-strength alloy
steel construction and conform to NFPA 2001.
Containers shall be actuated by parallel wired Gas Cartridge Actuators through a
Fike Agent Release Module (ARM), located at each agent container.
Each container shall have a pressure gauge and low pressure switch to provide
visual and electrical supervision of the container pressure. The low pressure
switch shall be wired to the control panel to provide an audible and visual
"Trouble" alarm in the event the container pressure drops below 288 psi (19 bar).
The pressure gauge shall be color coded to provide an easy, visual indication of
container pressure.
Each container shall have a pressure relief provision that automatically operated
when the internal temperature exceed 150 F (66 C).
Engineered discharge nozzles shall be provided, within the manufacturer's
guidelines, to distribute the ECARO-25 agent throughout the protected spaces.
The nozzles shall be FIKE designed to provide proper agent quantity and
distribution.
1)
i.
Although distribution piping modifications will not occur and/or be at a minimum,
distribution piping, and fittings, shall be installed or retained in accordance with
the manufacturer's requirements, NFPA 2001 and approved piping standards and
guidelines. All distribution piping shall be installed by qualified individuals using
good, accepted practices and quality procedures. All piping shall be adequately
supported and anchored at all directional changes and nozzle locations.
1)
2)
H.
Nozzles shall be available in NPT sizes ¼” – 3” (8mm- 80mm). Each size
shall be available in 180 and 360 distribution patterns.
All piping shall be reamed, blown clear and swabbed with suitable solvents
to remove burrs, mill varnish and cutting oils before assembly.
All pipe threads shall be sealed with Teflon tape pipe sealant applied to the
male thread ONLY.
ELECTRICAL REQUIREMENTS
1.
2.
CONTROL PANEL: The Control Panel must be a listed and approved device that has a
releasing circuit.
DETECTORS: The detectors shall be spaced and installed in accordance with the
manufacturer's specifications and the guidelines of NFPA No. 72 - current edition.
21 00 00 - 19 of 31
Construction Documents
20080548
H2410
a.
Detection Devices:
1)
2)
3)
The products of combustion detectors - ionization type, shall be Fike. The
detector shall utilize solid state circuitry and be of the dual chamber
configuration. One (1) chamber shall be open to sense particles of
combustion while the other will be used as a reference chamber of stability.
The unit shall be designed so as to be unaffected by RF energy from 1kHz
through 100 mHz. The detectors shall also be unaffected by air velocities
up to 3000 FPM.
The ionization type detector shall utilize a standard base so that it may
readily be interchanged, without any modifications, with photoelectric or
thermal type detectors. The detector head shall house an alarm LED that
pulsates while the detector is in the normal standby condition and lights
steadily upon sensing an alarm condition. The detector shall be equipped to
provide a remote annunciator which will duplicate LED indication. The
detector head shall be equipped with a means of securing the head to the
base in such a fashion that the head may not readily be tampered with or
removed.
The products of combustion detectors - photoelectric type, shall be Fike.
The detector shall utilize solid state circuitry, a pulsed, infrared LED light
source, and a silicon photo diode receiving element. The receiving element
will normally not sense any light from the LED source. When smoke
particles enter the sensing chamber, the light source shall be reflected to the
sensing element. Comparative circuitry shall be incorporated so as to
discriminate between a valid "fire" signal and an intermittent "non-fire"
source. The entrance to the sensing chamber shall be surrounded by a fine
stainless steel mesh so as to prevent ready entry by insects, lint or dust. Unit
shall be dew proof and uninfluenced by high air velocity. The photoelectric
type detector shall utilize a standard base so that it may readily be
interchanged, without any modifications, with ionization or thermal type
detectors. The detector head shall house an alarm LED that pulsates while
the detector is in the normal standby condition and lights steadily upon
sensing an alarm condition. The detector shall be equipped to provide a
remote annunciator which will duplicate LED indication. The detector head
shall be equipped with a means of securing the head to the base in such a
fashion that the head may not readily be tampered with or removed.
The detector head shall be removable from its base for cleaning, service, or
replacement. The detector shall be capable of having its calibration checked
or adjusted in the field via the standard detector sensitivity monitor. This
same monitor shall be capable of checking ionization and photoelectric type
detectors. A detector may have sensitivity tested either in place as it is
exposed to the environment or in a calibrated smoke chamber to give a
reading of sensitivity which can be referenced against other like detectors
under known conditions. The detectors shall be FM approved, ULC listed
and UL listed to UL Standard 268.
21 00 00 - 20 of 31
Construction Documents
20080548
H2410
4)
3.
MANUAL RELEASE (Electric): The electric manual release switch shall be a dual action
device which provides a means of manually discharging the ECARO-25 Clean Agent
Suppression System.
a.
b.
c.
d.
4.
c.
Alarm bells (p/n MBA-6-24) shall be located as indicated on the drawings.
Pre-discharge horn/strobe combination units (p/n GEC3-24-WR) shall be located
as indicated on the drawings.
A Strobe device (p/n RSSWP2475) shall be placed outside, and above, each exit
door from the protected space. Provide an advisory sign, Fike P/N 02-10313, at
each light location.
CAUTION and ADVISORY SIGNS: Provide signs, as required, to comply with NFPA
2001 and the recommendations of the ECARO-25 equipment supplier:
a.
b.
c.
7.
"Locking" or "Keyed" abort stations shall not be permitted.
The (optional) Abort Station shall be located adjacent to each manual station.
AUDIBLE and VISUAL ALARMS: Alarm audible and visual signal devices shall operate
from the Control Panel.
a.
b.
6.
The Manual Release switch shall be a Fike P/N 10-1638 or a Manual Pull station,
P/N 02-3710.
An electrical Manual Release switch or Manual Pull station shall be a dual action
device requiring two distinct operations to initiate a system actuation.
Manual actuation shall bypass the time delay and abort functions, shall cause the
system to discharge and shall cause all release and shutdown devices to operate in
the same manner as if the system had operated automatically.
A Manual Release or Manual Pull switch shall be located at each exit from the
protected hazard and shall have an advisory sign, Fike P/N 02-10312, provided at
each location.
ABORT STATION: The optional Abort Station shall be the "Dead Man" type and shall
be located next to each manual switch.
a.
b.
5.
Detector Orientation: All ceiling mounted detectors will be oriented so as to
allow, if possible, the viewing of the detectors alarm lamp from the control
panel location.
Entrance sign: (1) required at each entrance to a protected space. (Fike P/N 0210314)
Manual Discharge sign: (1) required at each manual discharge station. (Fike P/N
02-10312)
Flashing Light sign: (1) required at each flashing light over each exit from a
protected space. (Fike P/N 02-10319 or 02-10313)
SYSTEM and CONTROL WIRING: All system wiring shall be furnished and installed by
the contractor.
21 00 00 - 21 of 31
Construction Documents
20080548
H2410
a.
b.
c.
d.
e.
8.
All wiring shall be installed in electrical metallic tubing (EMT), or conduit, and
must be installed and kept separate from all other building wiring.
All system components shall be securely supported independent of the wiring.
Runs of conduit and wiring shall be straight, neatly arranged, properly supported,
and installed parallel and perpendicular to walls and partitions.
The sizes of the conductors shall be those specified by the manufacturer. Color
coded wire shall be used. All wires shall be tagged at all junction points and shall
be free from shorts, earth connections (unless so noted on the system drawings),
and crosses between conductors. Final terminations between the Control Panel and
the system field wiring shall be made under the direct supervision of a factory
trained representative.
All wiring shall be installed by qualified individuals, in a neat and workmanlike
manner, to conform to the National Electrical Code, Article 725 and Article 760,
except as otherwise permitted for limited energy circuits, as described in NFPA 72
-current edition. Wiring installation shall meet all local, state, province and/or
country codes.
The complete system electrical installation, and all auxiliary components, shall be
connected to earth ground in accordance with the National Electrical Code.
SYSTEM INSPECTION and CHECKOUT: After the system installation has been
completed, the entire system shall be checked out, inspected and functionally tested by
qualified, trained personnel, in accordance with the manufacturer's
recommended
procedures and NFPA standards.
a.
b.
c.
All containers and distribution piping shall be checked for proper mounting and
installation.
All electrical wiring shall be tested for proper connection, continuity and resistance
to earth.
The complete system shall be functionally tested, in the presence of the owner or
his representative, and all functions, including system and equipment interlocks,
must be operational at least five (5) days prior to the final acceptance tests.
1)
2)
3)
9.
10.
Each detector shall be tested in accordance with the manufacturers
recommended procedures, and test values recorded.
All system and equipment interlocks, such as door release devices, audible
and visual devices, equipment shutdowns, local and remote alarms, etc. shall
function as required and designed.
Each Control Panel circuit shall be tested for trouble by inducing a trouble
condition into the system.
TRAINING REQUIREMENTS: Prior to final acceptance, the installing contractor shall
provide operational training to each shift of the owners personnel. Each training session
shall include Control Panel operation, manual and (optional) abort functions, trouble
procedures, supervisory procedures, auxiliary functions and emergency procedures.
OPERATION and MAINTENANCE: Prior to final acceptance, the installing contractor
shall provide complete operation and maintenance instruction manuals, four (4) copies
for each system, to the owner. All aspects of system operation and maintenance shall be
detailed, including piping isometrics, wiring diagrams of all circuits, a written description
of the system design, sequence of operation and drawing(s) illustrating control logic and
21 00 00 - 22 of 31
Construction Documents
20080548
H2410
11.
12.
equipment used in the system. Checklists and procedures for emergency situations,
troubleshooting techniques, maintenance operations and procedures shall be included in
the manual.
AS-BUILT DRAWINGS: Upon completion of each system, the installing contractor
shall provide four (4) copies of system "As-Built" drawings to the owner. The drawings
shall show actual installation details including all equipment locations (i.e.: control
panel(s), agent container(s), detectors, alarms, manuals and aborts, etc.) as well as piping
and conduit routing details. Show all room or facilities modifications, including door
and/or damper installations completed. One (1) copy of reproducible engineering
drawings shall be provided reflecting all actual installation details.
ACCEPTANCE TESTS:
a.
b.
c.
d.
e.
13.
At the time "As-Built" drawings and maintenance/operations manuals are
submitted, the installing contractor shall submit a "Test Plan" describing
procedures to be used to test the control system(s). The Test Plan shall include a
step-by-step description of all tests to be performed and shall indicate the type
and location of test apparatus to be employed. The tests shall demonstrate that
the operational and installation requirements of this specification have been met.
All tests shall be conducted in the presence of the owner and shall not be
conducted until the Test Plan has been approved.
The tests shall demonstrate that the entire control system functions as designed and
intended. All circuits shall be tested: automatic actuation, solenoid and manual
actuation, HVAC and power shutdowns, audible and visual alarm devices and
manual override of abort functions. Supervision of all panel circuits, including AC
power and battery power supplies, shall be tested and qualified.
A room pressurization test shall be conducted, in each protected space, to
determine the presence of openings, which would affect the agent concentration
levels. The test(s) shall be conducted using the Retro-Tec Corp. Door Fan system,
or equivalent, with integrated computer program. All testing shall be in accordance
with NFPA 2001.
If room pressurization testing are required and have indicated openings exist which
would result in leakage and/or loss of the extinguishing agent, the installing
contractor shall be responsible for coordinating the proper sealing of the protected
space(s) by the general contractor or his sub-contractor or agent. The general
contractor shall be responsible for adequately sealing all protected space(s) against
agent loss or leakage. The installing contractor shall inspect all work to ascertain
that the protected space(s) have been adequately and properly sealed.
Upon acceptance by the owner, the completed system(s) shall be placed into
service.
SYSTEM INSPECTIONS:
a.
b.
The installing contractor shall provide two (2) inspections of each system, installed
under this contract, during the one-year warranty period. The first inspection shall
be at the six month interval, and the second inspection at the 12 month interval,
after system acceptance. Inspections shall be conducted in accordance with the
manufacturer's guidelines, and the recommendations of NFPA 2001.
Documents certifying satisfactory system(s) operation shall be submitted to the
owner upon completion of each inspection.
21 00 00 - 23 of 31
Construction Documents
20080548
H2410
14.
WARRANTY: All FIKE system components furnished, and installed under this contract,
shall be guaranteed against defects in design, materials and workmanship for the full
warranty period which is standard with the manufacturer, but in no case less than one (1)
year from the date of system acceptance.
PART 3 - EXECUTION
3.1
GENERAL INSTALLATION REQUIREMENTS
A.
Refer to Section 22 05 00 for basic requirements.
B.
Manufacturers' Supervision/Inspection: Contractor shall be fully responsible for properly
making arrangements for and coordinating with the manufacturer to provide the specified
manufacturer's supervision/inspection services and manufacturer's written certification as
specified in Part 1 of this section, and shall at his own expense make any
corrections/modifications to his installation work as required by the manufacturer.
C.
Protection of Underground Piping
1.
2.
3.
Protect black or galvanized steel piping installed below grade with one shop coat of
"Bitumastic 50", one field coat of "Bitumastic" primer and one field coat of "Bitumastic 50"
enamel applied hot.
Protect underground ductile iron fire protection water main piping with a loose
encasement of eight mills thick tube or sheet polyethylene.
In lieu of the above and where working temperature permits, piping may be machine
wrapped with polyvinyl chloride backed tape with a pressure sensitive adhesive, 3M Co.
"Scotchrap No. 51" or approved equal, of not less than 20 mil thickness. Prime pipe
before installation of tape. Apply primer and tape in strict accordance with
manufacturer's instructions. Do not apply tape until after piping tests have been
completed.
D.
Provide pressure gauges where shown and as required by authorities having jurisdiction.
E.
Provide suitable means to permit free movement resulting from contraction and expansion.
F.
Install sprinkler heads in all spaces including electrical and elevator machine rooms, elevator
shafts, stairways and any open or closed areas that may require protection such as under
combustible raised floors or stages and areas above and below ducts, etc., in accordance with
NFPA 13. Arrange heads to clear all construction features, lights, ducts, piping, etc. Provide all
sprinklers as may be required to provide a complete sprinkler system in all areas designed as
having a sprinkler system.
G.
No piping foreign to electrical equipment is permitted to be installed in, enter, or pass through
electrical equipment rooms, elevator machine rooms or similar areas. Only sprinkler branch
piping with sprinkler heads serving such areas as previously listed may be installed. Piping and
sprinkler heads are not permitted to be installed directly over any equipment, panels, etc., within
this space.
21 00 00 - 24 of 31
Construction Documents
20080548
H2410
H.
Provide each controlling valve with an approved lettered sign, as specified in Section 22 05 00,
Basic Materials and Methods.
I.
Protect sprinkler piping system from earthquake damage in accordance with the requirements of
NFPA 13.
J.
Provide seismic restraints for equipment as specified in Section 22 05 00.
K.
This Contractor shall coordinate locations of fire protection system piping with respect to fresh
air intake louvers. Routing of piping directly in front of such louvers shall be avoided due to
potential freezing conditions. Refer to mechanical drawings for exact locations for all louvers.
All louvers shall be shown on shop drawing submittals.
L.
The Contractor shall be responsible for coordinating all fire protection equipment locations with
the locations of all lighting fixtures, HVAC diffusers, ceiling architectural features and
structural members. The Contractor is responsible for coordinating the locations of all fire
protection piping and equipment with all other trades to prevent obstructions to the required
sprinkler discharge pattern and to prevent conflicts with location of piping above finished
ceilings.
M.
Sprinkler heads shall be installed in a symmetrical and orderly fashion.
N.
A maximum tolerance of (+) 1/2 inch between two adjacent sprinkler heads and 3/4 inch overall
for sprinkler heads aligned parallel and perpendicular to branch lines shall be provided.
O.
Sprinkler heads shall be located in the center of all ceiling tiles.
P.
Piping shall be located so as to avoid areas where sprinkler or standpipe piping may have the
potential for freezing.
3.2
CLEAN AGENT EXTINGUISHING SYSTEM
A.
General
1.
2.
3.
4.
B.
Provide Clean Agent, fixed pipe, total flooding, fire extinguishing system for protection of
Data Center.
Design and installation in full accordance with requirements of: latest issue NFPA 2001,
local authority having jurisdiction and manufacturer's recommendations.
System preengineered and UL listed. System designed and installed in accordance with
limits and guidelines depicted in manufacturer's design manual and operation and
maintenance manual.
All design and installation shall be accomplished by an experienced firm regularly
engaged in the installation, maintenance and servicing of automatic fire detection and
Clean Agent Extinguishing Systems in accordance with the appropriate NFPA standards.
Clean Agent Supply Equipment
1.
Storage Cylinders
a.
Mount where indicated on plans.
21 00 00 - 25 of 31
Construction Documents
20080548
H2410
b.
c.
2.
3.
4.
5.
6.
7.
C.
Mount securely in an upright position. Provide seismic restraints when seismic
restraints are required for fire suppression system.
Locate where shown on Drawings.
Discharge Nozzles: UL listed for specific Clean Agent, with either 180o or 360o flat fanshaped discharge pattern and range in orifice sizes to suit application
Power Shutdown and Alarm: Detection system shall include contacts for shutdown
circuit which will power down air handling fans and computer equipment, and close
doors and fire/smoke dampers to prepare for Clean Agent discharge. A 3 pole, double
throw, pressure switch that will activate upon Clean Agent discharge shall be installed
and wired across the 2 detection zones such that any method of Clean Agent release will
sound alarm, shut down air handling equipment and computer equipment, and release all
magnetic door holdersand fire/smoke dampers.
Functional Test: System design shall incorporate capability of fully testing all electrical
detection, discharge control, abort, power shutdown, air conditioning shutoff, fire/smoke
damper and door closer circuits without discharge of clean agent and without
disconnecting clean agent supply from the system.
Battery Backup Power System: Provide battery backup of entire Clean Agent system,
including detection, alarm, actuation and supervisory systems, be designed such that upon
main power failure, backup power automatically services system with no delay or
interruption of any kind. Battery system must be capable of powering system for a period
of not less than 24 hours in a normal standby condition, at the end of which time it shall
be capable of operating entire system in a full alarm condition for a period of not less
than 10 minutes. Trouble horn and light shall be activated to indicate that the system is
operating on battery power.
Magnetic Door Holders: Magnetic door holders for releasing doors with customer
furnished self-closing hardware shall be installed on the floor. Upon actuation of firstzone detectors or manual discharge of the Clean Agent, magnetic door holders shall
deactivate and release doors.
Automatic Fire/Smoke Damper(s): Provide releasing device for automatic fire/smoke
damper(s) in air conditioning ductwork servicing hazard areas separated by fire and
smoke rated walls. Activation of fire/smoke dampers shall occur as described
hereinbefore.
Design Documentation
1.
Upon completion of the clean gas suppression system design, and prior to any installation
work, this contractor shall submit 4 copies of system design to authority having jurisdiction,
for approval. Documentation shall include, but not be limited to, the following:
a.
Clean Agent Quantity Requirements for Each Hazard Area:
1)
2)
3)
4)
5)
6)
b.
Dimensions and volume.
Design temperature.
Clean Agent volume factor.
Clean Agent required.
Size and fill weight of Clean Agent cylinders.
Clean Agent volumetric concentration.
Pipe and Nozzle Calculations for Each Hazard Area:
21 00 00 - 26 of 31
Construction Documents
20080548
H2410
1)
2)
3)
4)
5)
c.
d.
e.
f.
g.
2.
D.
Detection System Design: Drawings to illustrate detector zoning and placement
within the hazard area.
System Control Unit Design: Schematics for entire system control unit including
circuit diagrams for detectors, cylinder control head[s], manual pull stations, abort
circuits, audio and visual alarms, and door and fire damper releases.
Working Drawings: Complete drawings of the proposed system showing locations
of discharge nozzles, Clean Agent storage containers, electrical control panel[s],
manual release station[s], abort switches, audio and visual alarms, and door and
fire damper releases. Working drawings are to be fully coordinated with other
trades with respect to lighting, ductwork, diffusers and any other item or piece of
equipment.
Descriptive Data: All components.
Additional information that may be required by manufacturer and/or authority
having jurisdiction.
After approval of Authority having jurisdiction, transmit required copies of approved
Drawings to Architect for review. Construction shall not commence until drawings are
reviewed by Architect.
Clean Agent System Installation
1.
2.
Mechanical Requirements: Comply with NFPA 2001.
Electrical Requirements
a.
b.
c.
d.
E.
Discharge time.
Flow rate per nozzle.
Type of nozzle.
Pipe sizes.
Nozzle thread and orifice sizes.
Field wiring between the releasing control panel and the equipment shutdown devices
will be provided by Division 26.
Comply with NFPA 70 and Division 26. Equipment and materials UL approved
wherever their standards have been established.
This Contractor's Responsibility: This Contractor shall be responsible for
providing the control panel and control wiring for detectors, alarms, abort stations,
manual pull stations and providing contacts for building alarm system, air
conditioning and computer equipment shutdown devices, voltage trips and circuit
breakers, door and fire/smoke damper releases and other auxiliary devices as
required.
Wiring: New wiring, including control circuitry, to be insulated copper conductors
installed in metal conduit, except that in limited energy circuits listed limited
energy cable may be used without placement in metal conduit.
Additional Requirements
1.
Acceptance Test
a.
Upon completion of the systems installation, perform a complete acceptance test in
presence of Owner's representative. Conduct tests by experienced personnel
21 00 00 - 27 of 31
Construction Documents
20080548
H2410
b.
according to the manufacturer's recommended methods and procedures required by
insurance rating authority having jurisdiction.
Simultaneously or separately test the following:
1)
2)
3)
4)
5)
6)
7)
8)
c.
d.
2.
3.
4.
3.3
Fire/Smoke damper/door closers.
Audible and visual alarms.
Abort and manual pull stations.
Actuator circuits.
Air handling and computer equipment shutdown.
All detection zones.
Room integrity (via pressurization test)
All control panel functions.
Ventilation of Spaces After Testing: Be responsible for and provide ventilation
using temporary and permanent systems as required to assure that all spaces
associated with discharge test are evacuated of test material in a manner that
precludes any unsafe human contact with test material.
Provide written report of test results.
Training Requirements: Prior to final acceptance, provide 8 (eight) hours operation and
maintenance training to Owner's personnel. Include computer emergency procedures, abort
functions, system control panel operation, troubleshooting procedures and unique
maintenance and safety requirements. Coordinate dates and times of training period not less
than 2 weeks prior to session.
Equipment Instruction Plates: Provide engraved instruction plates detailing emergency
procedures at each hazard area manual discharge station, and abort switch station.
As-Built Drawings: Provide 3 copies of As-Built Drawings showing actual installation
details. Show all equipment locations as well as exact pipe and conduit routing details
and agent storage position. Illustrate all facilities modifications.
COMBINATION WET STANDPIPE-SPRINKLER SYSTEM
A.
Provide combination wet standpipe-sprinkler system complete with piping, fittings, valves,
sprinklers, fire department valves, fire department valve cabinet, water flow switches, and
accessories.
B.
Provide water to sprinklers from wet standpipes. Install monitored isolation valve, flow switch,
drain and test valves in each sprinkler system as it connects to wet standpipe. Provide drain
riser to receive discharge unless noted otherwise.
C.
Provide full size check valve in Siamese fire department inlet connection line located as near as
practicable to point where it joins the system. Install 3/4 inch automatic ball drip between
check valve and fire department connection to prevent freezing. Pipe ball drip to outside.
D.
Where more than one standpipe is required, interconnect all standpipes and provide shutoff
valve at base of each standpipe.
E.
During construction, make one standpipe outlet available on each floor without delay, for fire
department use.
21 00 00 - 28 of 31
Construction Documents
20080548
H2410
F.
Where static pressure exceeds 175 psi at hose station, provide pressure reducing valve to
prevent static and residual pressure on hose exceeding 100 psi for 1-1/2 inch valves and 175 psi
for 2-1/2 inch valves. Where residual pressure exceeds 100 psi at a 1-1/2 inch hose station,
provide a pressure restricting disc or pressure reducing valve to reduce residual pressure to 100
psi.
G.
Provide 2-way standpipe roof manifold outlets with hose valves, caps and chains on roof.
Provide manifold supply with indicating valve, tamper switch and automatic ball drip. Locate
supply valve as close to roof access as practical unless indicated otherwise.
H.
Run piping concealed above ceilings where they exist. Expose only heads.
I.
Protect sprinkler heads against mechanical injury with standard guards.
J.
Provide sprinkler heads of rating higher than ordinary, where required and approved by
authorities having jurisdiction.
K.
Install sprinkler head guards where heads are low enough to be subject to possible damage as
required or directed.
L.
Seal sleeves of pipes passing through ceiling air plenum space walls or the roof above airtight in
a manner similar to that specified for watertight sleeves.
M.
Do not allow pipe hangers to pierce ductwork under any circumstances without prior approval
of Architect.
N.
Coordinate installation with electrical work for fire alarm system.
O.
Provide on wall near sprinkler alarm valve cabinet(s) containing 12 extra sprinkler heads for
each type and wrenches suitable for each head type.
P.
Install inspectors test pipes and connections at points as required and approved by authorities
having jurisdiction, and so that flow of water will be visible.
Q.
Grade piping for complete drainage. Provide drain pipes with approved valves and run to an
accessible place for discharge. Install auxiliary drain connections pipes at any low points in
systems in accordance with NFPA 13 or other applicable standard.
R.
Provide system, auxiliary, test and water motor alarm drain lines with valves and pipe to
discharge over approved drains or discharge through exterior walls not more than 6 inches
above grade as indicated or as required, visible from drain valves, so located that they will not
cause water damage to persons or property.
S.
Show required test pipes and drains on shop drawing plans.
T.
Provide pressure gauge at highest most remote hose station.
21 00 00 - 29 of 31
Construction Documents
20080548
H2410
3.4
CONNECTIONS TO EXISTING SYSTEM
A.
Extend new system from existing system. Make necessary alterations to existing systems as
required and as shown. Match new materials in altered systems with existing materials, unless
otherwise indicated.
B.
Be responsible for and repair any leaks developing in existing piping and for damage to existing
work due to failure to take proper precautions when making alterations and testing the system.
C.
Refer to Section 22 05 00 for additional instructions in connections with alteration work.
3.5
INTERFACING WITH ELECTRICAL WORK
A.
Refer to Section 22 05 00, Electrical Equipment and Wiring, for requirements regarding motors,
starters, and wiring.
B.
Power wiring will be provided under Division 26, Electrical, to the following:
1.
2.
3.
4.
5.
6.
C.
Preaction system air compressor alarm bell and switches
Preaction system releasing module
Clean Agent Extinguishing System control panel
Supervisory alarm system control panel
Alarm bell[s]
Air compressor
Signal wiring for the connection of the following systems to the fire alarm system will be
provided under Division 26, Electrical:
1.
Preaction System
a.
b.
c.
2.
Clean Agent Extinguishing System
a.
b.
c.
3.6
Panel trouble
Waterflow alarm via pressure switch
Electric alarm bell
Panel trouble
Predischarge alarm switch
Discharge alarm switch
MONITOR SWITCH
A.
Mount switch so that it will not interfere with operation of shutoff valve. Adjust switch to
operate with one revolution of hand-wheel from its normal full open position. Closing of valve
shall transmit alarm to annunciator panel and restoration of valve to normal open position shall
restore circuit to normal operation. Attempts to remove unit from its mounting or tampering
21 00 00 - 30 of 31
Construction Documents
20080548
H2410
with cover of housing shall transmit signal to annunciator panel and restoration of switch to its
mounting position, or replacing cover on housing shall restore circuit to normal operation.
3.7
PREACTION SPRINKLER SYSTEM
A.
Provide complete system with, deluge valve, sprinkler heads, pipe, fittings and hangers, air
compressor, valves, alarms, accessories, wiring and heat actuating devices required to operate
the system valve automatically. Release to be via building fire alarm system.
B.
Install in accordance with NFPA provisions and similar to that specified for wet sprinkler
system.
C.
The single interlock preaction system shall utilize a deluge valve which is tripped by the
actuation of a solenoid valve from the operation of the detection system. This puts water in the
system piping prior to fusing of the sprinklers. The system piping is pressurized with air for
supervisory purposes. If the system piping or a sprinkler head is broken, the pressure will be
reduced and a trouble alarm will sound at panel with optional trouble alarm being sent to alarm
service.
3.8
TESTING OF PIPING SYSTEMS
A.
Refer to Testing of Piping Systems, General, in Section 22 05 00.
B.
Water Fire Protection System: Test as required by applicable NFPA standards. Test
hydrostatically to 200 psig or 50 pounds over static head on system, whichever is greater.
Maintain pressure for 2 hours without leakage.
C.
Clean Agent Extinguishing System: Test pneumatically at pressure equivalent to 150% of
Clean Agent system design pressure at 130o F. Maintain pressure for 2 hours without leakage.
D.
Unless otherwise required by Code, new branch piping connected to existing systems may be
tested at normal operating pressure, provided new piping does not exceed 75 feet, or does not
include more than 20 fittings.
END OF SECTION 21 00 00
21 00 00 - 31 of 31
Construction Documents
20080548
H2410
Download