1 Webinar: The Basics and Benefits of Commissioning Erik Jeannette, PE Architectural Energy Corporation Boulder, Colorado www.archenergy.com © Architectural Energy Corporation Who am I? • Erik Jeannette, P.E. – – – – Controls and building energy efficiency expert ASHRAE controls research Controls engineer with Comfort Systems USA Business Team Leader and Commissioning Engineer - Architectural Energy Corporation © Architectural Energy Corporation 2 Webcast Outline • • • • • • Section 1: What is Commissioning? Section 2: Commissioning Section 3: Retro-commissioning Section 4: Case Studies Section 5: Costs and Benefits Section 6: Resources © Architectural Energy Corporation 3 Commissioning Definition • Commissioning is a systematic process of ensuring that all building or facility systems perform in accordance with the design documentation and intent, and in accordance with the owner’s operational needs. © Architectural Energy Corporation 4 Commissioning Definitions • Commissioning: – Process applied to new construction or major building renovation • Retro-commissioning: – Performed on facilities that have been in service and never commissioned • Re-commissioning: – Facility has previously been commissioned and is in need of a “tune-up” • Continuous commissioning: – On-going program of structured commissioning throughout the lifetime of a building © Architectural Energy Corporation 5 Webcast Outline • • • • • • Section 1: What is Commissioning? Section 2: Commissioning Section 3: Retro-commissioning Section 4: Case Studies Section 5: Costs and Benefits Section 6: Resources © Architectural Energy Corporation 6 Commissioning for New Construction • Typical Commissioning Team Members – – – – – – – Commissioning Provider (CX Agent) Owner’s Representative (PM) Architect and Design Engineers (A/E) General Contractor (GC) Mechanical Sub-contractor (MC) Electrical Sub-contractor (MC) Specialty Sub-contractors (Controls, TAB, Security, Elevator, etc.) – Operations and Maintenance Staff – Equipment Suppliers © Architectural Energy Corporation 7 Commissioning Process Design Phase Design Intent, CX Plan, Specifications Review submittals, Prepare checklists and Testing Plans © Architectural Energy Corporation Construction Phase Verify Installation, Start-Up and Component Testing Acceptance Phase Functional Testing, Resolve Deficiencies, Review O&M 8 Warranty Phase Diagnostic Monitoring, CX Report, O+M Staff Training, Seasonal Testing Commissioning Goals • All systems working as intended to achieve: – Occupant satisfaction and safety • All building systems performing reliably and safely • Improved comfort and indoor air quality – Cost savings • Energy, equipment maintenance, and equipment replacement – Smoother construction process • Avoided construction problems, quicker final acceptance, and reduced warranty callbacks © Architectural Energy Corporation 9 Commissioning Objectives • Ensure the facility meets performance requirements • Provide a safe and healthy environment • Provide optimum energy performance • Provide a facility that can be efficiently operated and maintained • Provide complete orientation and training to facility staff • Provide improved documentation of building systems © Architectural Energy Corporation 10 What should be Commissioned? • Whole-building commissioning – all major building systems: HVAC, electrical, controls, security, life safety, envelope, communications, movement, process equipment, etc. • Targeted systems – – – – HVAC equipment, controls Lighting controls - Electrical Building envelope - Security, Life Safety Kitchen Equipment - Plumbing, Irrigation © Architectural Energy Corporation 11 Design Phase Commissioning • Early intervention is better than later – Every building is a prototype – Every project will have design and construction issues – It will always cost less to fix a problem during design then during construction or occupancy – The more eyes on the job, the better © Architectural Energy Corporation 12 Design Phase Commissioning 13 The cost versus potential impact ratio of the commissioning effort can be expressed as the “X” Factor: Design Phase Construction Phase Acceptance Phase Impact Potential A C B Commissioning Cost/Impact Low Cost High Impact © Architectural Energy Corporation Cost vs. Impact High Cost Equal Low Impact Construction Phase Commissioning • Job-Site Observation – Job-site visits to check installation practices and catch problems early – During early system construction, repeated mistakes can be identified and corrected before they become widespread – Digital photos help to track progress and can be sent to design team for immediate response to items in question © Architectural Energy Corporation 14 Construction Phase Commissioning • Equipment Start-Up – Document completion of and adherence to manufacturer’s start-up recommendations – Typically asking contractors to document what they already do – Provide engineering expertise during start-up – Aid in integrating vendors and contractors to workout details © Architectural Energy Corporation 15 Acceptance Phase Commissioning • Functional performance tests – Often referred to as the “commissioning” phase in a project schedule – Verifies the intended operation of individual components and associated controls under various conditions and modes of operation – Test plans prepared to verify the complete sequence of operations – Testing from components to systems © Architectural Energy Corporation 16 HVAC Pre-Functional Issues Sometimes the obvious is missed... © Architectural Energy Corporation 17 HVAC Pre-Functional Issues © Architectural Energy Corporation 18 HVAC Functional Performance Issues • Example, Municipal Office Building: – Programming error prevented morning warm-up cycle on RTU, – causing winter warm-up to be done by electric reheat. © Architectural Energy Corporation 19 HVAC Functional Performance Issues • Example, packaged RTU: winter night setback mode – the outside air damper was open to 40% minimum position, – when it should be closed. © Architectural Energy Corporation 20 HVAC Short-Term Diagnostic Testing Issues • Scheduling: equipment found on at night or weekends • System operation above or below setpoint • Excessive cycling of equipment • Malfunctioning controls (economizers, reset schedules) • Controls permanently overridden • Simultaneous heating and cooling © Architectural Energy Corporation 21 Warranty Phase Commissioning • Warranty period / seasonal testing – Seasonal variation in operations or control strategies may require additional testing during the opposite season to verify performance – Depends on season during functional performance testing – Review operation before warranty period expires © Architectural Energy Corporation 22 Webcast Outline • • • • • • Section 1: What is Commissioning? Section 2: Commissioning Section 3: Retro-commissioning Section 4: Case Studies Section 5: Costs and Benefits Section 6: Resources © Architectural Energy Corporation 23 Where to Start? • Retrofit or Retro-commission? – Is the equipment efficient? – Is the equipment appropriate for the loads? – Is it optimally controlled? • Need a benchmark • What is EUI? – Energy Utilization Index • Btu/sf/year • kWh/sf/year • W/sf © Architectural Energy Corporation 24 Where to Start? • Energy Utilization Index © Architectural Energy Corporation 25 Where to Start? © Architectural Energy Corporation 26 Where to Start? • How about comfort and maintenance? – Is the facility staff chasing comfort problems? – Does “putting out fires” lead to no time for routine maintenance? • Comfort – Poor comfort control excessive energy use – Poor comfort something is not right © Architectural Energy Corporation 27 Where to Start? • Retrofit – If equipment is past its life – If lighting is incandescent or T-12 – If building use is dramatically different than the original design – If controls are not maintainable – If large AHUs run because there is a new computer room • Mis-match of equipment to load and use © Architectural Energy Corporation 28 Where to Start? • Retro-commission – – – – – – – Controls tune-up Existing controls are useful Existing controls are not optimized Control programs have been “butchered” Sensor calibration is a concern Actuators are failing Sequences are inefficient © Architectural Energy Corporation 29 Retro-commission vs. Retrofit • Retro-commission – Lower cost – Fast payback • Retrofit – Higher cost – Longer payback – Savings are more persistent © Architectural Energy Corporation 30 How to Decide • Retrofit and retro-commissioning can happen together • Mechanical problems should not be fixed with more controls • Mechanical problems fixed with mechanical design • Control problems fixed with retrocommissioning • Apply whichever is appropriate © Architectural Energy Corporation 31 Retro-commissioning Process Planning Prepare RCx Plan, Preliminary Investigation © Architectural Energy Corporation Investigation Detailed Analysis, Short-Term Monitoring, Payback Analysis Implementation Measures Get Implemented 32 Verification Occupancy Perform Functional Testing, Resolve Deficiencies Staff Training, Define Seasonal Testing, Measurement And Verification Retro-commissioning Process • Who does the work? • Retro-commissioning provider generally does not make program changes or install or repair equipment • Retro-commissioning provider subcontracts • Owner hires directly, Retro-commissioning manages work © Architectural Energy Corporation 33 Retro-commissioning Process • Short-Term Monitoring • Data collection of existing equipment operation • Used to understand existing control strategies • Use Building automation system or dataloggers © Architectural Energy Corporation 34 Short-Term Monitoring © Architectural Energy Corporation 35 Retro-commissioning Opportunities • • • • • • • • • • • Scheduling and optimum start/stop Fixed system setpoints vs. variable Failing control hardware Economizers Balance valves on large pumps VAV box scheduling Rewrite and reprogram sequences Outside air control Return fan control Lighting Control Demand Control © Architectural Energy Corporation 36 Scheduling • Still the most powerful EMS tool • One of the biggest sources of energy waste – Schedules creep longer and longer © Architectural Energy Corporation 37 Optimum Start • One of the oldest EMS strategies • Many ways to accomplish it • Basically takes into account OAT, Zone Temp & recovery ability of HVAC equipment • Starts the equipment just early enough to meet setpoint at the beginning of occupancy • Adaptive Learning or not? © Architectural Energy Corporation 38 Optimum Start • Applicable to Air Handlers or zones – Zones or AHU send request to central plants to operate if needed • Decide if you want optimum start heating or cooling or both • Keep outdoor air dampers closed during a morning warm-up optimum start period • Specify a maximum “look-ahead window” of X hours © Architectural Energy Corporation 39 Optimum Stop • Stops the facility systems prior to scheduled stop time to let the building “coast” to the end • Use the mass of the building and comfort delivery systems to maintain comfort without heating or cooling • Especially good for electric heat • Optimum stop ~30 to 45 minutes early • Don’t turn the air off!! – may depend on occupants © Architectural Energy Corporation 40 Fixed or Variable Setpoints • Fixed setpoints are rarely efficient • Central plant and AHU setpoints to match the building load • 55F AHU discharge air is for design days • 44F chilled water is not always necessary • Setpoints should self-adjust – Provide only enough cooling to meet the load – Maximize return air heating – Minimize air duct losses © Architectural Energy Corporation 41 Fixed or Variable Setpoints • Heating Water Plant – If occupied, enable ~60F outdoor temp – If all AHU are off, enable at ~50F • Reduce heating plant runtime – less energy – less maintenance – Close the hot water valves! • Coil radiative losses can be extensive • Compromise with maintenance and control MAT to 50F © Architectural Energy Corporation 42 Fixed or Variable Setpoints • A reset dynamically adjusts a setpoint based on another variable – Used to match a setpoint to the process load – Good -Can be a linear fixed slope between 2 conditions OAT AHU DAT 90F 55F 20F 65F – Better -Can use a PID to determine the setpoint based on 1 condition and 1 target number • Self-adjusts to find the best setpoint for the current conditions © Architectural Energy Corporation 43 Fixed or Variable Setpoints • Monitor VAV dampers and valves for AHU setpoints • Monitor AHU valves for central plant setpoints • Use “request for heating” or “cooling” – Enable plants on load request, not OAT © Architectural Energy Corporation 44 Fixed or Variable Setpoints • What to reset…. – – – – – – – – Zone setpoint Duct static pressure setpoint Discharge air temperature setpoint Supply water temperature Condenser water temperature setpoint Heat Pump condenser water temperature Building static pressure setpoint Lighting level • Need to be careful not to have too many resets on one system! © Architectural Energy Corporation 45 Failing Control Hardware • Broken actuators & linkages & leaky valves – Pneumatic actuator diaphragms – Linkages come loose – Globe valve and zone valves can leak • Sensor calibration – Key sensors need regular calibration • Outside air temp and humidity • Supply air and water temps © Architectural Energy Corporation 46 Economizers • Packaged RTU economizers – Very high failure rate after couple years – Cheap damper connection – Failed sensor, actuator or binding damper • All economizers – Disable economizer mode too early – Many economizing hours lost – Humidity sensors and enthalpy switchover © Architectural Energy Corporation 47 Balance Valves • Balance valves on large pumps – 15% open valve restricts flow 85% – Open valve, change impeller size – Reduce HP and losses • Example: – 30HP pump – Balance valve 65% open – Save 3kW and 3800 kWh = ~$150/yr © Architectural Energy Corporation 48 VAV Box Scheduling • Zone scheduling • VAV box minimum airflow: min to zero – Occupied box = minimum airflow – Unoccupied box = zero airflow • Turn off AHU – Use occupancy override buttons – Only the occupied zones get airflow – 80% of the building is unoccupied at 5PM © Architectural Energy Corporation 49 Rewrite and Reprogram Sequences • Are the original sequences optimized? • Or are they designed for the worst-case scenario? • Re-commission instead of retrocommissioning • Sequences should have: – – – – – Optimum start/stop Variable setpoints System setpoints that match the loads Proper economizer switchover Optimized plant control © Architectural Energy Corporation 50 Minimum Outside Air • How to measure (air flow, calculate, etc) • How much is needed • Variable air Volume challenges – ASHRAE 62 requires OA CFM maintain as supply air varies, or set OA at min supply CFM • Drop the setting when 90% of the occupants leave at 5:30PM – But keep building pressure positive! © Architectural Energy Corporation 51 Minimum Outside Air • OA need based on CO2 concentration – “Demand Controlled Ventilation” • 2005 Title 24 Code – Section 121 – CO2 Sensor in each room that has a design occupancy >= 25 people per 1000SF • With a few exceptions… • 600 ppm above ambient © Architectural Energy Corporation 52 Lighting Control • Parking lot lights – Timeclock – Astronomical clock – Photocell • Interior lights – Schedule with DDC – Occupancy sensors – Photocell on/off © Architectural Energy Corporation 53 Demand Control • Electrical demand control and load shedding • Turn off equipment or adjust setpoints – – – – DX lockout Increase CHW setpoint Lobby lights Zone setpoint reset • Measure building kW • Keep the building below kW setpoint © Architectural Energy Corporation 54 Compressor Operation • Packaged RTU DX systems • Y1 and Y2 with 3 or more compressors © Architectural Energy Corporation 55 Compressor Operation • Case Study- Park Meadows Mall – 4 compressors, with 2 output signals – Convert to 4 cooling signals – Reduce short-cycling – Allow for demand control – Reduce peak demand – Savings • 65kW, and 85,439 kWh/Summer • ~$10,000 per summer © Architectural Energy Corporation 56 Compressor Operation © Architectural Energy Corporation 57 Strategies in Order of Energy Savings • • • • • • • • • Scheduling Optimum Start Optimum Stop Minimum Outside air control and economizers Setpoint resets Demand Limiting Load Based Control Return fan control Balance valves and impellers © Architectural Energy Corporation 58 Webcast Outline • • • • • • Section 1: What is Commissioning? Section 2: Commissioning Section 3: Retro-commissioning Section 4: Case Studies Section 5: Costs and Benefits Section 6: Resources © Architectural Energy Corporation 59 Case Study: Century Middle School • 116,000 SF, 4-year old School – Highest Energy Utilization Index in district – Large number of comfort complaints – Reduced natural gas use by 48% – Reduced electrical energy use by 22% © Architectural Energy Corporation 60 Case Study: Century Middle School • Mechanical System Description – – – – – – Chiller Plant with Cooling Tower Boiler Plant 8 Constant Volume Air Handlers 83 Reheat Coils Crawl Space relief fans for pressure control New CSI DDC system © Architectural Energy Corporation 61 Case Study: Century Middle School Retro-commissioning Plan • Identify control problems – Develop plan to repair or replace control equipment • Many pneumatic actuators found disconnected • Pneumatic transducers incorrectly calibrated • Identify comfort problems • Identify occupancy patterns – Match Equipment Schedules with Use • Short-term monitored data collection and analysis © Architectural Energy Corporation 62 Case Study: Century Middle School • Short-term Monitoring - HVAC Energy Data © Architectural Energy Corporation 63 Case Study: Century Middle School • Short-term Monitoring - Lighting Energy Data (Occupancy Indicator) © Architectural Energy Corporation 64 Case Study: Century Middle School • Short-term Monitoring Revealed – All AHU discharge air resets “broke” • 55F air temp at all times because the reset was to return air temperature – All AHU overheat every night • Hot Water valves control to 100F discharge air; Sensor is 15’ away from coil • Major loss of boiler energy during unoccupied hours – Hot water supply temperature reset “broke” • Programming errors • Boiler limit controllers fighting with DDC control © Architectural Energy Corporation 65 Case Study: Century Middle School © Architectural Energy Corporation 66 Case Study: Century Middle School $65,000 of Natural Gas Savings From Dec ‘01 to Feb ‘03 © Architectural Energy Corporation 67 Case Study: Niver Creek Middle School • 105,000SF, 30-year old School – 15 Multi-Zone DX Rooftop Units – 1 Variable Volume Unit – Boiler Plant © Architectural Energy Corporation 68 Case Study: Niver Creek Middle School • Overall Project Scope – Replace old DDC system with new (450 points) – Replace 4 multizone roof top units with new – Re-balance all air and water systems • Commissioning Scope – Perform existing mechanical evaluation to determine project scope – Re-write all equipment sequences • Include setpoint resets to minimize energy use – Commission all existing and new HVAC equipment © Architectural Energy Corporation 69 Case Study Energy Results: kWh © Architectural Energy Corporation 70 Case Study Energy Results: Gas © Architectural Energy Corporation 71 Webcast Outline • • • • • • Section 1: What is Commissioning? Section 2: Commissioning Section 3: Retro-commissioning Section 4: Case Studies Section 5: Costs and Benefits Section 6: Resources © Architectural Energy Corporation 72 Commissioning Costs • Typical cost: $0.50 to $2.00 per SF • Typical energy savings: 6 to 12 percent • Median payback: ~ 5 years (from energy savings) • Other cost estimate methods: – .5 to 2 percent of total construction cost – 2 to 4 percent of equipment/installation cost of systems to be commissioned (i.e. mechanical system cost, electrical system cost) Data from proceedings of 1997 National Conference on Building Commissioning/Oregon Office of Energy Cost-effectiveness of Commercial Buildings Commissioning – A Meta-Analysis of Energy and Non-Energy Impacts in Existing Buildings and New Construction in the United States, LBNL, PECI, Energy Systems Lab – TAMU, 2004 © Architectural Energy Corporation 73 Retro-commissioning Costs • Typical fees: $0.20 to $0.90 per SF • Typical implementation cost: – Office buildings - $0.20 to $0.50 per SF – Labs and hospitals are more costly • Typical energy savings: 7 to 30 percent • Median payback: > .7 years Data from proceedings of 1997 National Conference on Building Commissioning/Oregon Office of Energy Cost-effectiveness of Commercial Buildings Commissioning – A Meta-Analysis of Energy and Non-Energy Impacts in Existing Buildings and New Construction in the United States, LBNL, PECI, Energy Systems Lab – TAMU, 2004 © Architectural Energy Corporation 74 Commissioning Benefits • Consider the potential costs of not commissioning: – – – – – – – Professional liability claims Owner litigation exposure Unhappy owner Unhappy building occupants Unhappy O+M staff Higher energy costs Continuing callbacks to solve problems and warranty claims © Architectural Energy Corporation 75 Webcast Outline • • • • Section 1: What is Commissioning? Section 2: The Commissioning Process Section 3: Commissioning Case Studies Section 4: Commissioning Costs and Benefits • Section 5: Resources © Architectural Energy Corporation 76 Commissioning Resources • Building Commissioning Association web site – http://www.bcxa.org • PECI (Portland Energy Conservation, Inc.) – http://www.peci.org • ASHRAE Guidelines 0 & 1 – http://www.ashrae.org • California Commissioning Collaborative – http://www.cacx.org © Architectural Energy Corporation 77 Energy Design Resources • www.energydesignresources.com • Commissioning Guidelines and Design Brief • Commissioning Assistant On-line software • Technical Design Briefs and Guidelines • Case Studies • Software tools (Skycalc, SPOT, eQuest) © Architectural Energy Corporation 78 Savings By Design Program • www.savingsbydesign.com • Set guidelines for exceeding T-24 standards • Design assistance • Incentives for owner ($150k max) • Incentives for design team ($50k max) • Design approaches: System and whole building © Architectural Energy Corporation 79 Energy Efficiency Resources • • • • www.pge.com/biz New construction design assistance Cash incentives Customized energy efficiency/demand response incentives • Energy efficiency equipment rebates • Self generation incentives and rates • Education and training © Architectural Energy Corporation 80 Energy Efficiency Resources 81 • www.smud.org/commercial/saving/incentives. html • www.sdge.com/business/bus_energy_efficiency .shtml • www.sce.com/RebatesandSavings/ • www.socalgas.com/energyefficiency/ © Architectural Energy Corporation 82 Thank you for participating in this Webinar Erik Jeannette, PE Architectural Energy Corporation Boulder, Colorado www.archenergy.com © Architectural Energy Corporation