DIVISION 23 SECTION 23 08 00 COMMISSIONING OF HVAC SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification Sections, apply to this Section. B. ASHRAE Guideline 1-2007, HVAC&R Technical Requirements for the Commissioning Process C. OPR and BoD documentation are included by reference for information only. 1.2 SUMMARY A. This Section includes general requirements that apply to implementation of the commissioning process without regard to specific systems, assemblies, and components. B. Related Sections include the following: 1. Division 01 Section 01 91 00 Commissioning General Requirements for general commissioning process activities. 2. Division 23 Mechanical 3. Division 28 Electronic Safety and Security for interaction with fire alarm systems 1.3 DEFINITIONS A. Commissioning Plan: A document, prepared by CxA, that outlines the organization, schedule, allocation of resources, and documentation requirements of the commissioning process. B. CxA: Commissioning Authority. C. Quality Assurance: A program for the systematic monitoring and evaluation of the various aspects of a system, assembly, or component to ensure that standards of quality are being met. This is the responsibility of the CxA. D. Quality Control: A system for ensuring the maintenance of proper standards in systems, assemblies, and components. This is the responsibility of the Contractor. E. Official: State or Local official having jurisdiction over the HVAC&R systems F. Systems, Assemblies, Equipment, and Components: Where these terms are used together or separately, they shall mean “as-built” systems, assemblies, equipment, and components. Buley Library Renovations SCSU, New Haven, CT Project No: BI-RS-2258 Phase 2 23 08 00/ 1 of 10 9-20-2013 Bid Specification DIVISION 23 SECTION 23 08 00 COMMISSIONING OF HVAC SYSTEMS PART 2 - PRODUCTS (NOT USED) PART 3 - EXECUTION 3.1 CONSTRUCTION CHECKLISTS A. The CxA shall provide Construction Checklists to the Contractors for execution that will indicate expected Quality Control features required for a highest-quality installation. The contractor shall complete the checklists as construction progresses and return them to the CxA as indicated in Section 01 9113 Commissioning General Requirements. B. Checklists for this section will include: 1. Air Handling Units 2. Humidifiers 3. Exhaust fans 4. Return fans 5. All variable air volume (VAV) terminal units and associated reheat coils 6. Chillers and pumps 7. Chilled water system 8. Cooling Towers and condenser water pumps, etc. 9. Hot Water pumps 10. Hot water system 11. Computer room air conditioning units and associated split system condensers 12. Unit heaters, cabinet unit heaters, etc. 13. Testing Adjusting and Balancing (TAB) 14. Building automation system and Direct Digital Controls and system interlocks 15. Existing equipment with control modifications 16. Ductwork systems 17. Piping Systems 18. Terminal heating units ( unit heaters, reheat coils, fintube, radiant ceiling panels) 19. Additional Items to be added as required C. A sample installation checklist is included to show the typical scope and rigor of the process. 3.2 PREREQUISITES TO TESTING A. Prior to the testing of these systems or assemblies, the Contractor shall certify that: 1. The system or assembly is completely installed, functional, and documented through checklists. 2. Work performed by other trades, but essential for this system or assembly’s operation, is complete (e.g., electrical components are wired and power is provided) 3. All contractor-performed start-up procedures and tests are complete and documented. 4. Preliminary trending data provided to verify actual system operation. 5. The system or assembly is ready for the Owner to take beneficial use. Buley Library Renovations SCSU, New Haven, CT Project No: BI-RS-2258 Phase 2 23 08 00/ 2 of 10 9-20-2013 Bid Specification DIVISION 23 SECTION 23 08 00 COMMISSIONING OF HVAC SYSTEMS 3.3 SYSTEM OR ASSEMBLY TEST REQUIREMENTS A. The CxA will provide Functional Performance Test procedures to the Contractor for execution for the following specific systems, assemblies, and components: 1. Air Handling Units 2. Humidifiers 3. Exhaust fans 4. Return fans 5. All variable air volume (VAV) terminal units and associated reheat coils 6. Chillers and pumps 7. Chilled water system 8. Cooling Towers and condenser water pumps, etc. 9. Hot Water pumps 10. Hot water system 11. Computer room air conditioning units and associated split system condensers 12. Unit heaters, cabinet unit heaters, etc. 13. Testing Adjusting and Balancing (TAB) 14. Building automation system and Direct Digital Controls and system interlocks 15. Existing equipment with control modifications 16. Additional Items to be added as required B. Acceptance criteria and test details will be in accordance with the related sections including the following: 1. Division 01 Section 01 91 00 Commissioning General Requirements for general commissioning process activities. 2. Division 23 Mechanical 3. Division 28 Electronic Safety and Security. C. A sample functional performance test is included to show the typical scope and rigor of the process. 3.4 TEST REPORTS A. 3.5 Provide copies of all reports required in the listed reference sections (see Section 1.02 SUMMARY above for the sections) for review. SAMPLE FORMS Buley Library Renovations SCSU, New Haven, CT Project No: BI-RS-2258 Phase 2 23 08 00/ 3 of 10 9-20-2013 Bid Specification DIVISION 23 SECTION 23 08 00 COMMISSIONING OF HVAC SYSTEMS Installation Checklist Roof Top Unit # _______________Serving Room/Area/Floor __________________ Model Verification Specified Submitted Installed Manufacturer Model Number Serial Number Inlet Size Cool CFM / Heat CFM Installation Checks ID Description Pass / Fail 1 Verify the unit has been installed on a roof curb. Entire length and width under base shall be sealed for additional water management protection. (15500 2.42D) 2 The piping cabinet shall have removable panels or optional access door of the same construction as unit door. (15500 2.42H) 3 Verify view windows are provided for all fan section access doors and is made of tempered glass. (15500 2.42K) 4 Verify that a factory mounted light fixtures are provided in all sections of the unit that have access doors. Provide individual light switches installed adjacent to access doors. (15500 2.42L) 5 Coils shall be removable by unbolting the wall panels in the coil section. Connections shall be clearly labeled on the outside of units. (15500 2.42O) 6 7 Verify filter section shall have filter racks, an access door for filter removal and block offs as required to prevent air bypass around filters. Units shall be supplied with 4” flat and 12” cartridge bag filters. (155500 2.42P) Verify factory wired disconnect switches for each fan (VSDs are to be mounted in the building not within the rooftop unit). Also provide factory wired lights and GFI receptacles (two per unit). (15500 2.42V) 8 Provide smoke rated damper assembly for both supply and return air openings for RTU-1, 7 and 9. (15500 2.42W) 9 Provide isolation damper assemblies for both supply and return air openings for all rooftop units except RTU-1, 7 and 9. (15500 2.42X) 10 11 Comments Verify the following piping components have been installed in the direction of flow for the CW/HW supply: (M4-2-0) a. Thermometer b. Butterfly Valve c. Strainer with hose end drain valve with cap and chain. d. Union e. ¾” Hose end drain valve with cap and drain. Verify the following piping components have been installed in the direction of flow for the CW/HW return: (M4-2-0) a. Automatic Air Vent b. Union c. 2-Way Control Valve d. Union e. Butterfly Valve with Memory Stop f. Thermometer Approvals (only one required) Name (printed neatly) Signature Contractor/Manuf. Rep. Engineer Construction Administrator Commissioning Agent Buley Library Renovations SCSU, New Haven, CT Project No: BI-RS-2258 Phase 2 23 08 00/ 4 of 10 9-20-2013 Bid Specification Date DIVISION 23 SECTION 23 08 00 COMMISSIONING OF HVAC SYSTEMS Sample Functional Performance Test Heat Recovery Rooftop Unit – ERV-2 1. Participants Name/Representing / / / Party filling out this form Participation (Testing, Witness, etc) Date of test 2. Prerequisite Checklist a. A completed and approved balancing report has been provided. b. An as-built version of the controls submittal has been provided. c. The controls contractor has certified that their internal commissioning is complete and the project is ready for third-party verification. CC initials: ________. Date: ________. d. The general contractor has certified that the construction is substantially complete and ready for thirdparty verification. GC initials: ________. Date: ________. e. Record all values for setpoints, control parameters, limits, delays, lockouts, schedules, etc., that have been changed to accommodate testing: Parameter Occupied space temperature heating setpoint Occupied space temperature cooling setpoint Frost Control temperature alarm setpoint Occupied/Unoccupied mode Occupied Space Humidity Setpoint Pre-Test Values Returned to Pre-Test Values √ Parameter Pre-Test Values Returned to Pre-Test Values √ Unoccupied space temperature heating setpoint Unoccupied space temperature cooling setpoint Occupied low space temperature alarm setpoint Occupancy Schedule Low Limit Switch SP Buley Library Renovations SCSU, New Haven, CT Project No: BI-RS-2258 Phase 2 23 08 00/ 5 of 10 9-20-2013 Bid Specification DIVISION 23 SECTION 23 08 00 COMMISSIONING OF HVAC SYSTEMS 3. Sensor Calibration Checks. The sensors listed below are to be checked for calibration and adequate location. Sensor Locati on OK1 BAS Value Measure d Value Pas s Y/N Sensor Locatio n 1 OK BAS Value Measure d Value Pas s Y/N Outside air temperature Y/N Y/N WDAT (CLT) - avg Y/N Y/N Space temperature Y/N Y/N DAT - avg. Y/N Y/N Discharge Y/N Air Humidity 1 Sensor location is appropriate and away from causes of erratic operation. Comments: Y/N RAT - avg. Y/N Y/N 4. Device Calibration Checks. The actuators or devices listed below are to be checked for proper operation and/or calibration. Device or Actuator Procedure / State BAS Value Site Observation Pass Y/N Outside air damper / actuator 1. Observe OA damper modulating in unison with RA and EA damper. Y/N Exhaust air damper / actuator 1. Observe EA damper modulating in unison with RA and OA damper. Y/N Stop Y/N Start Y/N Exhaust air fan status Return air damper / actuator Supply air fan and status Electric Duct Heat Heat Recovery Wheel H/C Valve Low Limit Switch 1. Observe during outside air damper testing. Return air damper should operate inversely with the outside air damper. 1. Stop /Status Y/N 2. Start /Status Y/N Y/N 1. Off Y/N 2. On Y/N Stop Y/N Start Y/N Fail Position 50 % Open 100 % Open Trip Y/N Y/N 5. Notes Buley Library Renovations SCSU, New Haven, CT Project No: BI-RS-2258 Phase 2 23 08 00/ 6 of 10 9-20-2013 Bid Specification DIVISION 23 SECTION 23 08 00 COMMISSIONING OF HVAC SYSTEMS 6. Functional Testing Record Seq. ID Mode ID 1. 2. 1 UNOCCUPIED MODE (Vacation Periods Only) 3. Test Procedure (including special conditions) Command the unit to the unoccupied mode through the BAS. When the unit is in the unoccupied mode command the unoccupied space temperature heating setpoint to 5°F above the current average space temperature. When the unit is in the unoccupied mode command the unoccupied space temperature heating setpoint to 5°F below the current average space temperature. Expected Response 1. The outside air dampers will be closed. The return air damper will be open 100%. Observe fail position of DTW (HCV) valve. The heating unit will cycle to the unoccupied set point of 60deg (adj). The supply air fan will be off. This is the “shutdown” mode for the unit. 2. The outside air dampers will remain closed. The return air damper will remain open. The supply air fan will be on. The heating module will start. 3. The heating module will be deenergized. The supply air fan will stop. The unit will return to shutdown mode. 1. The supply air fan will start. The outside, return and exhaust air dampers will modulate to maintain a minimum discharge air temperature setpoint of 53° F at sensor CLT. Heat wheel speed will control at this setpoint. 2. The supply air fan will remain on line. The outside, return and exhaust air dampers will continue modulating. The DTW (HCV) will modulate to heat the space until the setpoint is satisfied. Discharge air temperature is limited to 55 to 80 Deg F. Pass Y/N Y/N Note: This may not be set up, as no sequence was provided. 3 OCCUPIED MODE HEATING (SYSTEM INDEXED TO HEAT) 1. Command the unit to occupied mode. 2. When the unit is in the occupied mode adjust the space temperature heating setpoint to 5°F above the current space temperature. Note: If system is not indexed to heating mode DTW (HCV) valve will remain closed. Buley Library Renovations SCSU, New Haven, CT Project No: BI-RS-2258 Phase 2 23 08 00/ 7 of 10 9-20-2013 Bid Specification Y/N Notes DIVISION 23 SECTION 23 08 00 COMMISSIONING OF HVAC SYSTEMS Seq. ID Mode ID 1. 2. 4 OCCUPIED MODE ECONOMIZER (COOLING MODE INDEXED) 3. 5 HEAT RECOVERY MODE Test Procedure (including special conditions) Note: May not apply not specified in sequence of operation. When the unit is in the occupied mode override the outside air temperature to 48°F. Command the space temperature occupied cooling setpoint to 5°F above the current space temperature and the occupied heating setpoint to 5°F below the current space temperature. Command the mixed air temperature setpoint to 5°F below the current mixed air temperature. Command the mixed air temperature setpoint to 5°F above the current mixed air temperature. Expected Response 1. The supply air fan will remain on. The outside, return and exhaust air dampers will modulate to provide more outside air, in a direct action control algorithm, to maintain the mixed air temperature setpoint of 55 degrees. If the cooling setpoint is not met then the DWT (HCV) valve will modulate open to met space setpoint. 2. The supply air fan will remain on. The outside, return and relief air dampers will modulate to provide less outside air, in a direct action control algorithm, to maintain the mixed air temperature setpoint. Pass Y/N Y/N Command the mixed air temperature setpoint to 5°F above the current mixed air temperature. 1. Normal operation 1. The heat recovery wheel is rotating with the exhaust air passing thru the wheel and the OA passing thru the wheel to warm air or cool air. No air is bypassing wheel Buley Library Renovations SCSU, New Haven, CT Project No: BI-RS-2258 Phase 2 23 08 00/ 8 of 10 9-20-2013 Bid Specification Y/N Notes DIVISION 23 SECTION 23 08 00 COMMISSIONING OF HVAC SYSTEMS Seq. ID 6. Test Procedure (including special conditions) Mode ID OCCUPIED DEHUMIDIFICATION (COOLING MODE INDEXED ONLY) 1. With system indexed to cooling and the system is in occupied mode lower space humidity setpoint (62%) 10% lower. OCCUPIED COOLING (COOLING MODE INDEXED) Pass Y/N 1. DTW (HCV) will modulate and electric heater will stage on and off to maintain space setpoint. This is the only function of the electric heater. Y/N Return to normal. 2. DTW valve will return to normal control and the electric heater will stage off. 1. With the system in occupied mode, lower space temperature setpoint (75) as sensed by TR, 5 Deg F. lower than current space temperature. 1. The heat wheel increase speed to shed return air heat and the DWT (HCV) valve will modulate open to maintain new space setpoint. DAT shall never drop below 55 Deg. F. Allow time for control to stabilize. 2. 7. Expected Response Y/N 2. Return to normal. 1. With the unit running, raise the frost control setpoint as sensed at TF, 5 Deg F higher than current exhaust air temperature. 8. FROST CONTROL 1. Observe heat wheel slow to raise exhaust air temperature to high setpoint. 2. Observe low exhaust air alarm at BAS. Y/N 2. Reset alarm time delay for exhaust air temperature to 2 minutes. 3. Return all to normal. 9. FREEZE STAT ALARM AND SHUTDOWN 1. With the unit running in the occupied mode, trip the low limit thermostat located upstream of the HC coil. 2. Manually reset the freeze alarm at the BAS. 10 8 DIRTY AIR FILTER ALARM SUPPLY AIR FAN ALARM AND SHUTDOWN 1. With the unit operating, decrease the dirty filter alarm delay time to 2 minutes, and then gently pump up the high side of the filter DP. 2. Return to normal. 1. With the unit running in the occupied mode, stop the supply air fan by turning it off at its starter. 1. The unit will shut down, and all dampers will go to their fail state, and DTW (HCV) valve will fail open to the coil. The BAS will indicate a freeze alarm. Y/N 2. The unit will start in occupied mode. 1. Check that the BAS alarms. Y/N 1. The unit will go to its shutdown mode. The BAS will indicate a supply air fan status alarm. Y/N Buley Library Renovations SCSU, New Haven, CT Project No: BI-RS-2258 Phase 2 23 08 00/ 9 of 10 9-20-2013 Bid Specification Notes DIVISION 23 SECTION 23 08 00 COMMISSIONING OF HVAC SYSTEMS Seq. ID Mode ID 9 EXHAUST FAN SHUTDOWN 11 TRENDS Test Procedure (including special conditions) 1. With the unit running in the occupied mode, stop the exhaust fan by turning it off at its starter. Set the following points for 15 minute trend samples and review in 48 hours: Expected Response Pass Y/N 1. The unit will go to its shutdown mode. The BAS will indicate an exhaust fan status alarm. Y/N Trend Data Y/N 1. Space temperature. 2. Supply air fan status. 3. Exhaust air fan status 4. Mixed air temperature. 5. Outside air temperature. 6. Mixed air damper position 7. Room Humidity 8. Supply Air Temperature -- END OF TEST -- END OF SECTION Buley Library Renovations SCSU, New Haven, CT Project No: BI-RS-2258 Phase 2 23 08 00/ 10 of 10 9-20-2013 Bid Specification Notes