Images depicted herein are for demonstration purposes. Each facility is different, and user needs may vary. Adjust accordingly, based on equipment value and/or downtime expenses. IEEE C62.41.2-2002 Category C IEEE: Category C - Service Entrance Exposure NEC 285 & NRTL: SPD Type 1, 2, or equivalent Type 4 N&G Bonded (i.e., L-N and L-G are same) (Per Phase generally considered Sum of L-N plus L-G) Gen Set Load Side Surge Current kA ratings for all Categories are subjective. Consult SPD mfg for specific recommendations IEEE C62.41.2-2002 Category B ATS / STS Type 1 or 2 SPD Load side of the Switch protects Service and Gen Set Distribution Indoor HVAC (VFD) Distribution Type 1 or 2 SPD Type 1 or 2 SPD Type 1 or 2 SPD MCC Indoor L-N and L-G are different – need L-N, L-G, and N-G (Per Phase generally considered Sum of L-N plus L-G) UL 96A Lightning Protection System SPDs at Service Entrances require 20kA I-n and UL Mark Type 1 or 2 SPD NEC 285 & NRTL: SPD Type 1, 2, or equivalent Type 4 Historical kA Ratings: Per Phase: 300kA to 100kA per phase Per Mode: 150kA to 50kA per mode ANSI/UL 1449 - Surge Protective Devices UL 1283 – EMI/RFI Filtering ANSI/IEEE C62.41.1-2002 – Guide on Surge Environment ANSI/IEEE C62.41.2-2002 – Characterization of Surges ANSI/IEEE C62.45-2002 - Testing IEEE C62.62-2010 - Testing IEEE C62.72-2007 – Application Guide Service Entrance IEEE: Category B - External remnant or Internally Induced Require appropriate SCCR ratings Relevant SPD Standards (1000V and Less): Line Side Higher available fault currents require appropriate SCCR ratings Historical kA ratings: Per Phase: 400kA to 200kA per phase Per Mode: 200kA to 100kA per mode Line side requires Type 1 SPD per NEC 285 & UL 1449 Type 1 SPD Equipment installed outside of the building could increase exposure level to Category C. Consider effects of Ground Potential Rises from direct lightning strikes to earth Wind or PV Generation Type 1 or 2 SPD Outdoor Type 1 or 2 SPD Busway Outdoor Lighting Type 1 or 2 SPD Outdoor HVAC (VFD) Type 1 or 2 SPD Type 1 or 2 SPD Type 1 or 2 SPD Protect both ends of the bus way against reflections Establishes a new reference to ground, like a service entrance. L-N only may be sufficient IEEE: Category A, maybe B, maybe C if outdoor loads are connected IEEE C62.41.2-2002 Category A Branch Type 3 SPD Branch NEC 285 & NRTL: SPD Type 1, 2, or equivalent Type 4. Could be Type3. L-N and L-G are different – need L-N, L-G, and N-G “Pre” SPD (Type 1) Indoor Lighting Type 1 or 2 SPD Separately Derived System Small or Office Equipment Type 1 or 2 SPD Branch Require appropriate SCCR ratings Historical kA Ratings; Per Phase: 160kA to 100kA per phase Per Mode: 80kA to 50kA per mode UPS (or PDU, PDM) Type 1 or 2 SPD Computers or Servers Revision Date: April 14, 2014 Branch Outdoor “Post” SPD (Per Phase generally considered Sum of L-N plus L-G) Type 1 or 2 SPD Indoor Outdoor Lighting Type 1 or 2 SPD Outdoor Equipment Type 1 or 2 SPD Equipment installed outside of the building could increase exposure level to Category C. Consider effects of Ground Potential Rises from direct lightning strikes to earth Equipment Type 1 or 2 SPD Series SPD Equipment Series or two-port SPDs may disconnect downstream loads at end of life