INSTALLATION AND MAINTENANCE INSTRUCTIONS SpectrAlert Ceiling Mount Series Strobes, and Horn/Strobes A Division of Pittway 3825 Ohio Avenue, St. Charles, Illinois 60174 1-800-SENSOR2, FAX: 630-377-6495 For use with the following models: www.systemsensor.com Strobes: 24 volt: SC2415W, SC241575W, SC2430W, SC2475W, SC2495W, SC24115W, SC24177W Horn/Strobes: 24 volt: PC2415W, PC241575W, PC2430W, PC2475W, PC2495W, PC24115W, PC24177W Remove suffix “W” for red models. Add suffix “P” for models with plain housing. The Products to which this manual applies may be covered by one or more of the following U.S. Patent numbers: 5,914,665; 5,850,178; 5,598,139; 6,049,446; 6,057,778; D424465 Specifications Mechanical Input Terminals: Overall Dimensions: Operating Temperature: Electrical Voltage Range: 15 candela through 115 candela Strobes & Horn/Strobes: (with MDL module): 177 candela models only Strobes & Horn/Strobes: (with MDL module): 12 to 18 AWG (3.31 to 0.82 mm2) 6.8″ diameter (173 mm) 32° F to 120° F (0° C to 49° C) DC or Full-Wave Rectified models 16 to 33 volts DC or Full Wave Rectified 17 to 33 volts DC or Full Wave Rectified 16 to 33 volts DC; 20 to 33 volts Full Wave Rectified 17 to 33 volts DC; 21 to 33 volts Full Wave Rectified NOTE: Horn/Strobes units will operate on walk tests with on-time durations of 1 sec. or greater. Flash Rate: 1 Flash Per Second Light Output: Models with 15 only in the model number are listed at 15 candela. Models with 1575 are listed at 15 candela per UL 1971 but will provide 75 candela on axis (straight down). Models with 30, 75, 95, 115, 177 are for that candela. Sound Output: Sound output levels are established at Underwriters Laboratories in their reverberant room. Always use the sound output specified as UL Reverberant Room when comparing products. Listings: UL S5512 Strobe, UL S4011 (Combo) Note: Strobes have a 16–33 Volt Operating Range Limit. Do not exceed the maximum number of 70 strobe lights when connecting the MDL Sync module zone with a maximum line impedance of 4 Ohms per loop. General Description all the device currents do not exceed the current capability of the panel. Calculations are based on using the device current found in the subsequent charts and must be the current specified for the type of panel power supply used. The SpectrAlert ceiling mount series notification appliances are designed to meet the requirements of most agencies governing these devices, including: NFPA, The National Fire Alarm Code, UL, FM, CSFM, MEA. Also, check with your local Authority Having Jurisdiction for other codes or standards that may apply. Wire Sizes The designer must be sure that the last device on the circuit has sufficient voltage to operate the device within its rated voltage. When calculating the voltage available to the last device, it is necessary to consider the voltage drop due to the resistance of the wire. The thicker the wire, the less the voltage drop. Generally, for purposes of determining the wire size necessary for the system, it is best to consider all of the devices as “lumped” on the end of the supply circuit (simulates “worst case”). The SpectrAlert ceiling mount series can be installed in systems using 24volt panels having DC or full-wave rectified (FWR) power supplies. The series can also be installed in systems requiring synchronization (module MDL required) or systems that do not require synchronization (no module required). NOTICE: This manual shall be left with the owner/user of this equipment. Typical wire size resistance: 18 AWG solid: Approximately 16 AWG solid: Approximately 14 AWG solid: Approximately 12 AWG solid: Approximately Fire Alarm System Considerations Temporal and Non-Temporal Coded Signals: The American National Standards Institute and the National Fire Alarm Code require that all horns used for building evacuation installed after July 1, 1996, must produce Temporal Coded Signals. /2 Sec. On 1 /2 Sec. Off 1 /2 Sec. On 1 /2 Sec. Off 1 /2 Sec. On 11/2 Sec. Off ft. ft. ft. ft. The same number of devices using 12 AWG wire will produce only 2 volts drop. The same devices using 18 AWG wire will produce 8 volts drop. Consult your panel manufacturer’s specifications, as well as SpectrAlert’s operating voltage range to determine acceptable voltage drop. Repeats Power Supply Considerations Note: If class “A” wiring is installed, the wire length may be up to 4 times the single wire length in this calculation. Panels typically supply DC filtered voltage or FWR (full-wave rectified) voltage. The system design engineer must calculate the number of units used in a zone based on the type of panel supply. Be certain the sum of D900-22-00 ohms/1,000 ohms/1,000 ohms/1,000 ohms/1,000 Example: Assume you have 10 devices on a zone and each requires 50 mA average and 2000 Ft. of 14 AWG wiring (total length=outgoing +return). The voltage at the end of the loop is 0.050 amps per device x 10 devices x 3 ohms/1,000 ft. x 2000 ft =3 volts drop. Signals other than those used for evacuation purposes do not have to produce the Temporal Coded Signal. Temporal coding is accomplished by interrupting a steady sound in the following manner: 1 8 5 3 2 1 I56-1453-006R Figure 1A: Current Draw Measurements (Average Mean Method) NOTE: The SC24177 and PC24177 strobes were only tested at the 20-33 Volt-FWR limits and 16-33 Volt DC limits, all other SC and PC strobes were only tested at the 16-33 Volt-FWR/DC limits. This does not include the 80% low end or 110% high end voltage limits. Ceiling Mount Horn/Strobe 15 cd: Ceiling Mount Strobe Only: Average Mean Current (mA) 24V Models 16V 20V 24V 33V Candela 15 15/75 30 75 95 115 177 Peak Current (mA) 24V Models 16V 20V 24V 33V DC FWR FWR DC FWR DC FWR DC FWR FWR DC FWR DC FWR DC FWR FWR 63 81 119 179 278 290 453 79 94 109 167 231 232 55 62 79 140 173 230 300 41 47 56 101 122 156 208 51 62 73 126 163 212 241 164 174 238 418 540 644 952 232 238 288 436 562 668 242 258 318 462 560 712 1104 170 168 218 384 518 576 872 224 228 298 486 552 728 1184 91 91 94 99 92 81 79 118 115 116 118 115 108 48 56 68 127 153 191 338 291 170 172 226 398 534 612 1092 912 Ceiling Mount Horn/Strobe 1575 cd: Tone Electromech. High/Low Volume High Low 3000 Hz High Interrupt. Low Temp /Non Temp Non Temp Non Temp Non Temp Non High/Low Volume High Low 3000 Hz High Interrupt. Low Temp /Non Temp Non Temp Non Temp Non Temp Non DC FWR DC FWR DC FWR 90 90 83 83 115 115 84 84 88 88 77 77 139 139 78 78 79 96 76 79 96 76 70 81 65 70 81 65 83 101 82 83 101 82 72 84 69 72 84 69 105 105 88 88 110 110 92 92 Tone Electromech. 238 238 231 231 278 278 232 232 FWR 222 222 211 211 225 225 212 212 FWR DC FWR 133 134 137 133 132 118 148 126 177 179 179 177 176 175 170 188 182 184 186 187 174 171 252 237 244 238 244 249 234 3000 Hz High Interrupt. Low 207 207 192 192 212 212 195 195 DC 151 151 140 140 157 157 144 144 FWR 206 206 189 189 211 211 193 193 Tone Electromech. High/Low Volume High Low 3000 Hz High Interrupt. Low Tone Electromech. Temp /Non Temp Non Temp Non Temp Non Temp Non 3000 Hz High Interrupt. Low Temp /Non Temp Non Temp Non Temp Non Temp Non Average Mean Current (mA) 24V Models 16V 24V 33V DC FWR 78 78 71 71 91 91 72 72 80 80 69 69 94 94 70 70 DC FWR DC FWR 71 71 62 62 75 75 64 64 70 70 59 59 76 76 63 63 94 94 77 77 99 99 81 81 89 89 74 74 94 94 77 77 Ceiling Mount Horn/Strobe 75 cd: DC FWR DC FWR DC FWR 110 110 103 103 125 125 104 104 105 105 94 94 108 108 95 95 91 91 82 82 95 95 84 84 85 85 74 74 91 91 78 78 116 116 99 99 121 121 103 103 113 113 98 98 118 118 101 101 Tone Electromech. 3000 Hz High Interrupt. Low Temp /Non Temp Non Temp Non Temp Non Temp Non Average Mean Current (mA) 24V Models 16V 24V 33V DC FWR DC FWR DC FWR 194 194 187 187 197 197 188 188 168 168 157 157 188 188 158 158 150 150 141 141 154 154 143 143 130 130 119 119 136 136 123 123 169 169 152 152 174 174 156 156 174 174 159 159 179 179 162 162 Ceiling Mount Horn/Strobe 177 cd: DC FWR DC FWR DC FWR 305 305 298 298 308 308 299 299 256 256 245 245 259 259 246 246 214 214 205 205 218 218 207 207 185 185 174 174 191 191 178 178 255 255 238 238 260 260 242 242 264 264 249 249 269 269 252 252 High/Low Volume High Low Average Mean Current (mA) 24V Models 16V 24V 33V Temp /Non Temp Non Temp Non Temp Non Temp Non High/Low Volume High Low Average Mean Current (mA) 24V Models 16V 24V 33V Ceiling Mount Horn/Strobe 115 cd: DC FWR 176 176 167 167 180 180 169 169 High/Low Volume High Low Average Mean Current (mA) 24V Models 16V 24V 33V DC DC Ceiling Mount Horn/Strobe 30 cd: Average Mean Current (mA) 24V Models 16V 24V 33V Ceiling Mount Horn/Strobe 95 cd: Tone Electromech. In Rush Current (mA) 24V Models 33V 16V 20V 24V Tone Electromech. High/Low Volume High Low 3000 Hz High Interrupt. Low Temp /Non Temp Non Temp Non Temp Non Temp Non Average Mean Current (mA) 24V Models 16V 20V 24V 33V DC FWR DC FWR DC FWR 468 468 461 461 471 471 462 462 367 367 354 354 371 371 356 356 314 314 305 305 318 318 307 307 237 237 226 226 243 243 230 230 284 284 267 267 289 289 271 271 334 334 319 319 339 339 322 322 Figure 1B: Current Draw Measurements (Average RMS Method) NOTE: The SC24177 and PC24177 strobes were only tested at the 20-33 Volt-FWR limits and 16-33 Volt DC limits, all other SC and PC strobes were only tested at the 16-33 Volt-FWR/DC limits. This does not include the 80% low end or 110% high end voltage limits. Ceiling Mount Horn/Strobe 15 cd: Ceiling Mount Strobe Only: Average RMS Current (mA) 24V Models 20V 24V 16V 33V Candela 15 15/75 30 75 95 115 177 DC FWR FWR DC FWR DC FWR 74 86 112 209 269 336 521 71 81 103 178 242 300 74 81 98 168 208 268 370 54 62 78 143 180 218 315 74 86 99 154 204 248 327 61 71 90 167 213 257 412 394 Tone Electromech. Low 3000 Hz High Interrupt. Low Ceiling Mount Horn/Strobe 1575 cd: Tone Electromech. High/Low Volume High Low 3000 Hz High Interrupt. Low Temp /Non Temp Non Temp Non Temp Non Temp Non DC FWR DC FWR DC FWR 101 101 94 94 104 104 95 95 105 105 94 94 108 108 95 95 94 94 85 85 98 98 87 87 91 91 80 80 97 97 84 84 129 129 112 112 134 134 116 116 Tone Electromech. Low 3000 Hz High Interrupt. Low D900-22-00 Temp /Non Temp Non Temp Non Temp Non Temp Non Low 3000 Hz High Interrupt. Low Average RMS Current (mA) 24V Models 16V 24V 33V Temp /Non Temp Non Temp Non Temp Non Temp Non DC FWR DC FWR DC FWR 127 127 120 120 130 130 121 121 127 127 116 116 130 130 117 117 113 113 104 104 117 117 106 106 107 107 96 96 113 113 100 100 142 142 125 125 147 147 129 129 132 132 117 117 137 137 120 120 Average RMS Current (mA) 24V Models 16V 24V 33V DC FWR DC FWR DC FWR 284 284 277 277 287 287 278 278 266 266 255 255 269 269 256 256 236 236 227 227 240 240 229 229 209 209 198 198 215 215 202 202 247 247 230 230 252 252 234 234 242 242 227 227 247 247 230 230 Tone Electromech. High/Low Volume High Low 3000 Hz High Interrupt. Low Tone Electromech. 2 DC FWR DC FWR DC FWR 351 351 344 344 354 354 345 345 324 324 313 313 327 327 314 314 280 280 271 271 284 284 273 273 247 247 236 236 253 253 240 240 291 291 274 274 296 296 278 278 302 302 287 287 307 307 290 290 High/Low Volume High Low 3000 Hz High Interrupt. Low Average RMS Current (mA) 24V Models 16V 24V 33V Temp /Non Temp Non Temp Non Temp Non Temp Non DC FWR 89 89 82 82 92 92 83 83 95 95 84 84 98 98 85 85 DC FWR DC FWR 84 84 75 75 88 88 77 77 83 83 72 72 89 89 76 76 117 117 100 100 122 122 104 104 108 108 93 93 113 113 96 96 Temp /Non Temp Non Temp Non Temp Non Temp Non Average RMS Current (mA) 24V Models 16V 24V 33V DC FWR DC FWR DC FWR 224 224 217 217 227 227 218 218 197 197 180 180 202 202 184 184 202 202 191 191 205 205 192 192 190 190 181 181 194 194 183 183 202 202 187 187 207 207 190 190 172 172 161 161 178 178 165 165 Ceiling Mount Horn/Strobe 177 cd: Ceiling Mount Horn/Strobe 115 cd: Ceiling Mount Horn/Strobe 95 cd: High/Low Volume High Tone Electromech. High/Low Volume High Temp /Non Temp Non Temp Non Temp Non Temp Non Ceiling Mount Horn/Strobe 75 cd: Ceiling Mount Horn/Strobe 30 cd: Average RMS Current (mA) 24V Models 16V 24V 33V 115 115 100 100 120 120 103 103 High/Low Volume High Average RMS Current (mA) 24V Models 16V 24V 33V Tone Electromech. High/Low Volume High Low 3000 Hz High Interrupt. Low Temp /Non Temp Non Temp Non Temp Non Temp Non Average RMS Current (mA) 24V Models 16V 20V 24V 33V DC FWR DC FWR DC FWR 536 536 529 529 539 539 530 530 441 441 428 428 445 445 430 430 417 417 408 408 421 421 410 410 344 344 333 333 350 350 337 337 370 370 353 353 375 375 357 357 404 404 389 389 409 409 392 392 I56-1453-006R Figure 1C: Sound Pressure Measurements Sound Output Guide Temporal Low Volume Electromechanical 3000 Hz Interrupted High Volume Electromechanical 3000 Hz Interrupted NonLow Volume Electromechanical Temporal 3000 Hz Interrupted High Volume Electromechanical 3000 Hz Interrupted Figure 1D: Positioning for Maximum Brightness NOTE: For maximum brightness, unit must be mounted with flash angles as shown. Sound pressure dBA @10 ft./volts DC 16 24 33 75 75 79 75 75 79 79 82 82 79 82 82 75 82 82 79 82 85 82 85 85 82 85 85 Horn Selections The horns on SpectAlert horn/strobe combo units are factory set for high volume, temporal code, and electromechanical tone. Tones: Electromechanical or 3kHz tones may be field-selected using the dipswitch selector (See Figs. 2B and 3B for dipswitch location). NOTE: When powered from FWR supply, tones will be modulated(turned on and off) by 120Hz causing the tones to sound diferent from DC power. Temp/Non-Temp: Temporal coding or Non-Temporal coding can also be fieldselected using the dipswitch. High/Low Volume: High or low volume may also be field-selected using the dipswitch. Figure 3A. Any combination of models powered by a 4-wire circuit to provide independent horn and strobe operation (Remove factory installed jumpers, see Figure 3B): NOTE: Strobes must be powered continuously for horn operation. (+) (+) System Operation: Non-Synchronized Devices (+) (+) H O R N H O R N H O R N E O L (—) Figure 2A. Any combination of models powered by a 2-wire circuit: (+) HORN HORN/STROBE STROBE ONLY (+) (+) (+) (+) E O L (–) (–) (—) (–) (–) C O M B O C O M B O NOTE: Supply power must be continous for proper operation. (+) (+) S T R O B E (+) S T R O B E S T R O B E E O L Figure 2B: Horns and strobes powered in tandem: Figure 3B: Horns and strobes powered independently (Horn operated on coded power supply): NOTE: Supply power must be continuous for proper operation. NOTE: Strobes must be powered continuously for horn operation. FROM FACP, MODULE OR PREVIOUS DEVICE FACTORY INSTALLED SHORTING BAR _ + HORNS STROBES FACTORY INSTALLED JUMPER REMOVED _+ _ + STROBE + STROBE + HORN + DIP SWITCH HORN + STROBE - STROBE - HORN - HORN - _+ _ + TO NEXT TO NEXT HORN STROBE OR EOL OR EOL TO NEXT DEVICE OR EOL D900-22-00 _ + 3 Break wire as shown for supervision of connection. DO NOT allow stripped wire leads to extend beyond switch housing. DO NOT loop wires. I56-1453-006R Mounting Diagrams: Strobe or Horn/Strobe with universal mounting plate: Screw types used for mounting: A = #8 plastite B = 8-32 x 3/4 pan head 1. Mount adapter plate to back box with screws B. 2. Complete field wiring. 3. Secure unit to plate with screws A. Strobe or Horn/Strobe surface mount: 1. Mount adapter plate and back box skirt to back box with screws B. 2. Complete field wiring. 3. Secure unit to skirt with screws A. 4x4x11⁄2 BBSCW (white) BBSC (red) B B A A Please refer to insert for the Limitations of Fire Alarm Systems WARNING The Limitations of Ceiling Mount Horn/Strobes The horn and/or strobe will not work without power. The horn/strobe gets its power from the fire/security panel monitoring the alarm system. If power is cut off for any reason, the horn/strobe will not provide the desired audio or visual warning. The horn may not be heard. The loudness of the horn meets (or exceeds) current Underwriters Laboratories’ standards. However, the horn may not alert a sound sleeper or one who has recently used drugs or has been drinking alcoholic beverages. The horn may not be heard if it is placed on a different floor from the person in hazard or if placed too far away to be heard over the ambient noise such as traffic, air conditioners, machinery or music appliances that may prevent alert persons from hearing the alarm. The horn may not be heard by persons who are hearing impaired. NOTE: Strobes must be powered continuously for horn operation. The signal strobe may not be seen. The electronic visual warning signal uses an extremely reliable xenon flash tube. It flashes at least once every second. The strobe must not be installed in direct sunlight or areas of high light intensity (over 60 foot candles) where the visual flash might be disregarded or not seen. The strobe may not be seen by the visually impaired. The signal strobe may cause seizures. Individuals who have positive photic response to visual stimuli with seizures, such as persons with epilepsy, should avoid prolonged exposure to environments in which strobe signals, including this strobe, are activated. The signal strobe cannot operate from coded power supplies. Coded power supplies produce interrupted power. The strobe must have an uninterrupted source of power in order to operate correctly. System Sensor recommends that the horn and signal strobe always be used in combination so that the risks from any of the above limitations are minimized. Three-Year Limited Warranty System Sensor warrants its enclosed horn. strobe, or horn/strobe to be Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. free from defects in materials and workmanship under normal use and Please include a note describing the malfunction and suspected cause of service for a period of three years from date of manufacture. System failure. The Company shall not be obligated to repair or replace units Sensor makes no other express warranty for this horn, strobe, or which are found to be defective because of damage, unreasonable use, horn/strobe. No agent, representative, dealer, or employee of the modifications, or alterations occurring after the date of manufacture. In no Company has the authority to increase or alter the obligations or limitacase shall the Company be liable for any consequential or incidental damtions of this Warranty. The Company’s obligation of this Warranty shall be ages for breach of this or any other Warranty, expressed or implied whatlimited to the repair or replacement of any part of the horn, strobe, or soever, even if the loss or damage is caused by the Company’s negligence horn/strobe which is found to be defective in materials or workmanship or fault. Some states do not allow the exclusion or limitation of incidental under normal use and service during the three year period commencing or consequential damages, so the above limitation or exclusion may not with the date of manufacture. After phoning System Sensor’s toll free apply to you. This Warranty gives you specific legal rights, and you may number 800-SENSOR2 (736-7672) for a Return Authorization number, also have other rights which vary from state to state. send defective units postage prepaid to: System Sensor, Repair D900-22-00 4 I56-1453-006R © 2000 System Sensor