Product Information Speaker/StrobeCombination Low Profile, Field Selectable Candela 13-487, 13-489 Overview GE Interlogix offers the low profile fire alarm speaker/strobe which is designed to generate attention grabbing tones and voice commands for emergency signaling evacuation applications. These highly efficient low profile speakers are available with field selectable taps from 1/4W – 2 Watts. The low profile speakers are available with input voltage of 25 Vrms and can be installed on a standard 4” x 4” x 1 1/2” electrical backbox without the need for an extension ring. This speaker/strobe series is designed with a new strobe. The strobe features a unique candela intensity field selector switch for switching the candela output from 15/75 to 30/120 cd. The strobe housing is clearly labeled with “FIRE” lettering and is polarized for connecting to supervised fire alarm circuits. The strobe is designed with a xenon flashtube and provides a candela intensity field selector switch for maximum performance. The speaker/strobe series is available in red or white housing 15/75 to 30/120 cd. and 110 cd models. The strobe can be synchronized by using the 13-472 sync module to comply with NFPA recommendations concerning photosensitive epilepsy when installing 2 or more visual appliances within the field of view. The strobe signals are listed for indoor use, ceiling and wall mount, under UL 1971 standard. Architectural The fire alarm speaker is approved for fire alarm signaling use and capable of reproducing alarm tones or voice commands on Engineering Specifications 25Vrms. Speakers provide incremental tap settings of 1/4, 1/2, 1, Standard Features UL listed for Wall or Ceiling mount. Frequency range 400 Hz — 4000 Hz. Integral blocking capacitor for line supervision. Strobes are available in 15/75 — 30/120 and 110 Candela Intensity. 24VDC polarized models and 2 watts and are selected by means of a jumper wire. The speaker has a frequency range of 400 to 4000 Hz and has an operating temperature between 14°F and 140°F. The speaker produces a UL sound pressure level at 10 feet up to 84dB. The strobe is listed under UL 1971 standard for signaling devices for the hearing impaired and is approved for fire protective service. The candela output is field selectable, having a dual setting of Designed to meet or exceed NFPA / ANSI Standards and ADA Accessibility Guidelines. UL listed for fire protective service. Field selectable taps from 1/ 4W — 2 Watts. Screw terminals capacity up to 12 AWG. 15/75 to 30/120 cd output. The signaling strobe operates on 24VDC from a non-coded regulated DC supply or full-wave rectified, unfiltered supply. The signaling strobe is designed to produce a signal flash of one flash per second (1 Hz) with continuously applied minimum voltage. The 13-487 and 13-489 is capable of wall or ceiling mounting. The visual signaling devices are to be installed in all non-sleeping/corridor and sleeping areas as per plans and specifications. Polarized strobes with wide listed voltage ranges using filtered DC or unfiltered FWR input voltage. Meets ADA guidelines for minimum one flash per/sec (1Hz) All models mount to 4” x 4” x 11/ 2” square back box Speaker Strobe Combination Low Profile, Field Selectable Candela 13-487, 13-489 Dimensions Specifications Rated Input Voltage Input Power Impedance Sound Pressure Level Frequency Response Low frequency Cut Off Operating Temp. Range 25V 1/4W, 1/2W, 1W, 2W 2.5K, 1250, 620, 310 Ω 75, 78, 81, 84dB/10ft 400 — 4000Hz 200Hz 14°F - 140°F (-10°C – +60°C) 2.28" 58mm Round 3.97" 101mm 3.97" 101mm 2.69" 68mm 3.38" 85.7mm 2.69" 68mm 3.38" 85.7mm 0.59" 15mm 7.25" 184mm 2.28" 58mm Square 1.25" 32mm 0.59" 15mm 5.5" 140mm 1.25" 32mm Strobe – only current draw Average Current (mA) 24 volt models 19.2V Candela 24V Peak Current (mA) 24 volt models 26.4V 19.2V DC FWR DC FWR DC FWR Candela In-Rush Current (mA) 24 volt models 24V 26.4V 19.2V DC FWR DC FWR DC FWR Candela 24V 26.4V DC FWR DC FWR DC FWR 15/75 30/120 105 144 132 184 86 114 111 132 79 104 107 125 15/75 30/120 189 213 225 245 154 175 220 235 140 163 220 235 15/75 30/120 232 236 260 264 248 252 280 255 288 350 260 293 110 202 297 200 292 198 289 110 308 370 320 369 320 394 110 357 132 101 189 129 517 The strobes and synch module are listed for indoor use with a temperature operating range of 32°F – 120°F ( 0°C – 49°C). ADA MEA Approved Ordering Information Model 13-487 13-489 Voltage Rating Strobe Candela Rating Sync W/SMS1-33A Module 25VRMS 15/75, 30/120 Yes Yes 25VRMS 15/75, 30/120 Selectable Wattage Flash Rate/Min. Grille Type 14 1 2 / , / , 1, 2 / , / , 1, 2 60 Square Red 14 1 2 60 Round White Color