HUMIDITY 3% Humidity Transmitter & Optional Temperature Transmitters HD31K, HO31K, HW31K DESCRIPTION The Kele Models HW31K, HD31K, and HO31K 3% humidity transmitters are specifically designed for use in HVAC/BAS applications. These instruments measure relative humidity from 0% to 100%. The standard two-wire, 4-20 mA output provides low-cost humidity monitoring for building control. The RH transmitters are available with thermistor or RTD temperature sensors. They are available in room, duct, and OSA mounting styles. OPERATION HD31K The transmitter converts the relative humidity into a 4-20 mA signal with 3% accuracy. The optional temperature sensors, thermistor or RTD, offer direct connections to most automation systems. HW31K 9 HO31K FEATURES HUMIDITY • • • • OPTIONS: 0% to 100% RH measurement 3% accuracy (5% to 90% RH) Two-wire, 4-20 mA output White plastic design • Temperature thermistor • Temperature RTD SPECIFICATIONS Accuracy Thermal Effect Stability Supply Voltage Signal Output Maximum Output Impedance Measurement Range RH Temperature Sensor Protection 532 3% RH @ 73°F (23°C) from 5% to 90%; (0-5% & 90%-100%) add 4% 0.07% per °F typically <±1% drift per year 9.5-28 VDC RH: 4-20 mA Temperature: 4-20 mA optional thermistor, RTD 725Ω @ 24VDC (Supply voltage - 9.5V) / 0.02) Operating Humidity 0-100% RH non-condensing Operating Temperature-20° to 158°F (-29° to 70°C) Enclosure Rating White plastic Wiring Terminations Screw terminals for loop termination Weight Room 0.3 lb (0.09 Kg) Duct 0.58 lb (0.26 Kg) OSA 0.72 lb (0.33 Kg) Approvals RoHs Warranty 1 year 0-100% -20° to 140°F (29° to 60°C) (see ordering information) Sintered filter (duct and OSA) 888-397-5353 USA kele.com When you need it right, right now, call Kele. March 2014 HUMIDITY 3% Humidity Transmitter & Optional Temperature Transmitters HD31K, HO31K, HW31K DIMENSIONS 3.25 (8.26) in (cm) 2.5 (6.35) 0.75 (1.91) 2.3 (5.84) 4.50 (11.43) 0.88 (2.24) 4.87 (12.38) 1.20 (3.05) Front View Side View 5.5 (13.98) Mounting Tabs Gasket Correct position for mounting outdoor air sensor .75 (1.91) HW31K HD31K MOUNTING HO31K WIRING FOR ROOM UNIT MOUNTING OSA SENSOR The transmitter should be mounted preferably on the north side (Northern Hemisphere) of a building under the eave, not above windows or doors. The transmitter should be mounted vertically with the sensor slots pointing down. Power Supply 24 VDC Cover Hooks 0.75 (1.90) 4.75 (12.07) 1/2" Conduit Hole 1/8" NPT 2.75 (7.0) Wire-way hole RH RH North Top Screw Not Used HUMIDITY Room, Duct, OSA (RH or RH-T) Duct and OSA ORDERING INFORMATION MODEL HW31K HD31K HO31K DESCRIPTION 3% room-mount humidity transmitter, 4-20 mA output 3% duct-mount humidity transmitter, 4-20 mA output 3% OSA-mount humidity transmitter, 4-20 mA output OPTIONS (temperature sensor or transmitter) -No temperature sensor T3 10,000 thermistor @ 77 F (25 C), Type III T11K 10,000 thermistor @ 77 F (25 C), Type III, with 11K shunt T21 2252Ω thermistor @ 77˚F (25˚C), Type II T22 3000Ω thermistor @ 77˚F (25˚C), Type II T24 10,000 thermistor @ 77 F (25 C), Type II T27 100,000Ω thermistor @ 77˚F (25˚C), Type II T42 20,000Ω thermistor @ 77˚F (25˚C), Type IV T63 1000Ω nickel RTD @ 70˚F (26˚C), Type III T81 100Ω RTD @ 32˚F (0˚C), 385 platinum curve T85 1000 @ 32˚F (0˚C), 385 platinum RTD T91 1000 @ 32˚F (0˚C), 375 platinum RTD HD31K T3 DCPA-1.2 DCP-1.5-W March 2014 24 V V+ Optional Thermistor or RTD Temperature Sensor Board Hooks 9Power Humidity 4-20 mA signal V+ Cover Securing Screws and Back Plate 8.38 (21.29) Example: HD31K-T3 Duct-mount humidity transmitter with 10 kΩ Type III temperature sensor RELATED PRODUCTSPAGE Power supply, 120 VAC IN to 24 VAC/24 VDC OUT 994 Power supply, 24 VAC IN to 24 VDC OUT 995 WE MAKE IT EASY. kele.com 888-397-5353 USA 533