Chapter Electrical 22 Electrical Plant Bulks General Plant Electrical Bulks .......................................................... 22-3 Substation Electrical Plant Bulks ..................................................... 22-9 Schematic of Project Site Transmission Line Hook-Up .............. 22-13 Wire Sizes US Country Base .............................................................................. 22-14 UK and JP Country Bases ................................................................ 22-14 Electrical Class/Division NEC ................................................................................................... 22-15 IEC ................................................................................................... 22-16 G3 © ICARUS Corporation, 1998. 22-2 ICARUS Reference © ICARUS Corporation, 1998. G3 Chapter 22: Electrical 22-3 Electrical Plant Bulks Electrical plant bulks are divided into two categories, general and substation plant bulks. A description of each follows. General Electrical Plant Bulks General electrical plant bulks include cables, trays, grounding, lighting and tracing. 1 Description Type Electrical cable runs: wire, armored, multi-core ELEC-CABLE Material Selection: ARMOR W-C W-NC W-TR M-C M-NC M-TR LARM - Armored multi-core cable - Single wires in conduit, includes conduit - Single wires in conduit (less conduit) - Single wires in tray (less tray) - Multi-core in conduit, includes conduit - Multi-core in conduit (less conduit) - Multi-core cable in tray (less tray) - Lead covered armored cable Voltage: 600 5000 15000 600 3300 11000 - 600 V at 60 HZ - 5000 V at 60 HZ - 15000 V at 60 HZ - 600 V at 50 HZ - 3300 V at 50 HZ - 11000 at 50 HZ Cable Size: Default: US: single wires in conduit, else multi-core cable in tray without tray. See “Wire Sizes” later in this chapter. Conduit Material: Default: *GALV* GALV - Galvanized rigid steel conduit EMT - Electrical mechanical tubing AL - Aluminum PVC - PVC plastic conduit PBON - PVC coated rigid steel (plasti-bond) PVCA - PVC coated aluminum FRE - Fiberglass 2 Rigid conduit, galvanized steel, couplings, fittings and seals Material Selection: Default: *GALV* GALV - Galvanized rigid steel conduit EMT - Electrical mechanical tubing AL - Aluminum PVC - PVC plastic conduit PBON - PVC coated rigid steel (plasti-bond) PVCA - PVC coated aluminum FRE - Fiberglass Diameter: Range: 0.5 - 6.0 INCHES [15 - 150 MM] Number of Elbows: Default: *0* No. of Fittings: Default: *0* No. of Conduit Seals: Default: *0* G3 © ICARUS Corporation, 1998. CONDUIT 22-4 ICARUS Reference Electrical Plant Bulks - General Electrical Plant Bulks continued 3 Description Type Electrical cable tray ELEC-TRAY Material Selection: *GALV*, FBRGL, SS, AL No. of 90 DEG bends: *0* Type: *L*, T, C, B Width: Range: 6 - 36 INCHES [150 - 910 MM]; Default: *18* INCHES [*450* MM] 4 Electrical tracing of existing equipment Electrical tracing of equipment; item of equipment and its insulation are assumed specified elsewhere in the project. EQPT-TRACE Heating Cable Type: Use P series cable for process manten., A or P series cable for ambient control. 3A - 3 W/FT [10 W/M] Chemelex BTV2-CT cable 5A - 5 W/FT [16 W/M] Chemelex BTV2-CT cable 8A - 8 W/FT [26 W/M] Chemelex BTV2-CT cable 10A - 10 W/FT [33 W/M] Chemelex BTV2-CT cable 5P - 5 W/FT [16 W/M] Chemelex XTV2-CT cable 10P - 10 W/FT [33 W/M] Chemelex XTV2-CT cable 15P - 15 W/FT [49 W/M] Chemelex XTV2-CT cable 20P - 20 W/FT [65 W/M] Chemelex XTV2-CT calbe Distance to Panel: If the distance to the panel board is not specified, the system defaults to the value defined for Area Electrical Specifications. Thermostat Control: Default: *E-AMB* E-AMB - Electric tracing/ambient temperature control Single thermostat, control of electrical tracer based upon low ambient temperature specified for General Area Specifications. E-PRO - Electric tracing/process temperature control Multiple thermostated circuits, control of electrical tracer based upon low ambient temperature specified for General Area Specifications. 5 Electrical tracing of existing piping run Electrical tracing of piping; piping is assumed specified elsewhere. This item also provides insulation of the same size, or one size larger than pipe diameter for pipe diameters of 8 INCHES [200 MM] or smaller. PIPE-TRACE Traced Pipe Length: The pipe being traced is not included, but must be specified elsewhere. Traced Pipe Diameter: The pipe being traced is not included, but must be specified elsewhere. Maintenance Temp.: Process temperature to be maintained. Max: 250 DEG F [120 DEG C] over ambient. Thermostat Control: Default: *E-AMB* E-AMB - Electric tracing/ambient temperature control Single thermostat, control of electrical tracer based upon low ambient temperature specified for General Area Specifications. E-PRO - Electric tracing/process temperature control Multiple thermostated circuits, control of electrical tracer based upon low ambient temperature specified for General Area Specifications. Distance to Panel: Distance -pipe to local panel, feeder run to individual tracers determined by system. Length: Total length of tracer segments, default based on pipe length and diameter. © ICARUS Corporation, 1998. G3 Chapter 22: Electrical 22-5 Electrical Plant Bulks - General Electrical Plant Bulks continued 6 Description Type Ground grid A system of buried cable and rods provide a grid work for grounding equipment, buildings and structures. GRND-GRID Wire options: AWG (US only): 6, 2, 1/0, 2/0, 4/0; MM2: 16, 35, 50, 70, 95, 120. Default: *2* AWG [*35* MM2] Rod Types: *STD*, EL-L, EL-S. Includes direct-buried grid cable brazed to each ground rod. The default rod type, STD, includes manually-driven ¾ INCH x 10 FEET [3.05 METER] copper-clad ground rods with studs, clamps, etc. The electrolytic rod types, EL-L (3 FEET vertical x 10 FEET horizontal [0.91 x 3.05 METER]) and EL-S (straight 10 FEET length [3.05 M]), include pipe with weep holes, electrolytic filling material, special conductive backfill material, and protective cover. If the number of ground rods is not specified, 4 rods are generated for the first 1-199 FEET [0.3-60.6 METER] of grid cable, then 1 rod for each 200 FEET [61 METER] thereafter. For example, a 10 FEET [3.05 METER] length generates 4 rods, a 200 FEET [61 METER] length generates 5, and 1,000 FEET [305 METER] generates 9. Does not include trenching and backfill. Ground Grid diagram and rod types: G3 © ICARUS Corporation, 1998. 22-6 ICARUS Reference Electrical Plant Bulks - General Electrical Plant Bulks continued 7 Description Type Area lighting: includes poles, lights and cable Flood: 400 - 1000 W; Default: *400* Other: 100 - 400 W; Default: *175* AREA-LIGHT Fixture Type: Default: Mercury vapor/explosion proof FL1 FL2 FL1E FL2E MVPE MVPV MVCE MVCV MVF SVPE SVPV SVCE SVCV SVF INPE INPV INCE INCV MHV - Fluorescent - 1 bulb - Fluorescent - 2 bulbs - Fluorescent - 1 bulb, explosion proof - Fluorescent - 1 bulbs, explosion proof - Mercury vapor/explosion proof - Mercury vapor/vaportite - Mercury vapor/ceiling/explosion proof - Mercury vapor/ceiling vaportite - Mercury vapor/flood - Sodium vapor/explosion proof - Sodium vapor/vaportite - Sodium vapor/ceiling/explosion proof - Sodium vapor/ceiling/vaportite - Sodium vapor/flood - Incandescent/explosion proof - Incandescent/vaportite - Incandescent/ceiling/explosion proof - Incandescent/ceiling/vaportite - Mercury halide flood Length/Cable Runs: Cable run length from lighting panel. Power per Light: Range: 100 - 1,000 W. Flood: Default: *400 W*, Min: 400 W; Other: Default: 175 W; Max: 400 W. Number of Poles: Default: *0*. Pole Height: Default: *20* FEET [*6.0* M]. No. Basic Receptacle: Default: *0*. No. Weld Receptacle: Default: *0*. Wiring System: Default: *3 wire system* 2 - 2 conductor system 3 - 3 conductor system 4 - 4 conductor system Wiring Size: Default: US: *12 AWG*, else: 2.5 MM2. 14- 14 AWG - US only 12- 12 AWG - US only 10- 10 AWG - US only 1.5 - 1.5 MM2 - other bases 2.5 - 2.5 MM2 - other bases 4 - 4 MM2 - other bases Wire Placement: Default: *ABOVE* ABOVE - Above-grade BURIED - Buried Wire Type: ARMOR W-C W-NC W-TR M-C M-NC M-TR - Armored multi-core cable - Single wires in conduit, includes conduit - Single wires in conduit (less conduit) - Single wires in tray (less tray) - Multi-core in conduit, includes conduit - Multi-core in conduit (less conduit) - Multi-core cable in tray (less tray) Support type: *PENDT*, BRAKT, STAND, POLE. © ICARUS Corporation, 1998. G3 Chapter 22: Electrical 22-7 Electrical Plant Bulks - General Electrical Plant Bulks continued Description 8 Electrical control cable runs (LV) Type CTRL-CABLE Material Selection: ARMOR W-C W-NC W-TR M-C M-NC M-TR LARM - Armored multi-core cable - Single wires in conduit, includes conduit - Single wires in conduit (less conduit) - Single wires in tray (less tray) - Multi-core in conduit, includes conduit - Multi-core in conduit (less conduit) - Multi-core cable in tray (less tray) - Lead covered armored cable No. of Conductors: Range: 3 - 37 Conduit Material: Default: *GALV* GALV - Galvanized rigid steel conduit EMT - Electrical mechanical tubing AL - Aluminum PVC - PVC plastic conduit PBON - PVC coated rigid steel (plasti-bond) PVCA - PVC coated aluminum FRE - Fiberglass Cable Size: *14*, 12, 10 AWG; *1.5*, 2.5, 4.0 MM2. 9 Group of anodes in deep well A group of anodes in a deep well with connecting leads to an adjacent junction box. DEEP-ANODE Capacity: Based on five amps per anode. Depth: Depth should be based on the local soil conditions. The depth is 100 FEET [30 M] plus 7 FEET [2 M] per anode (5 amps per anode). Well Casing Symbol: Default: *NONE* NONE - No well casing CASED - Cased well 10 Individual galvanic anode An individual galvanic anode for road crossings, etc. GALV-ANODE Length/Cable Runs: Default: *40* FEET [*12* M] 11 Group of anodes in shallow surface bed A shallow surface anode bed consisting of anodes with underground leads to an adjacent junction box. Type of Anode: A B C D - Drilled hole, native backfill - Drilled hole, coke breeze backfill - Trench, coke breeze backfill - Trench, native backfill No. Anodes per Bed: *10* Spacing: Anode spacing is the center-to-center distance. Default: *8* FEET [*2.5* M] G3 © ICARUS Corporation, 1998. SURF-ANODE 22-8 ICARUS Reference Electrical Plant Bulks - General Electrical Plant Bulks continued Description Type 12 Potential measurement test station Enter number of test stations per location. POT-TEST 13 Transformer/rectifier 480 V/60 HZ [415 V/50 HZ] 3 phase input D.C. Output: 50 V/50 A or 100 V/100 A RECTIFIER Power pole line must be specified separately. Current: Range: 50 - 100 A Length/Cable Runs: Default: *500* FEET [*150* M] 14 Solar panel with storage batteries Solar panels, adjacent storage batteries, control center, supporting structure, fencing and cable to a junction box. SOLAR-PANL Length/Cable Runs: Default: *500* FEET [*150* M] 15 Emergency light with battery Provides short-term, local lighting for personnel in case of an electric power failure. Indoor, general-purpose type includes selection of light types, 6V battery, batteryrecharger, power cable with plug for local outlet, and mounting bracket. EMER-LIGHT Type: HEPS, HEPR, LEPS, LEPR, STDS, STDR Number of bulbs: *1*, 2 16 Underground cable duct Type: *TILE*, ENVEL, CONC, PRCST CABLE DUCT © ICARUS Corporation, 1998. G3 Chapter 22: Electrical 22-9 Substation Electrical Plant Bulks Substation electrical plant bulks include transformers, breakers, transmission lines and bus. 1 Description Type Bus duct BUS-DUCT Continuous Current: Max: 3,000 A Voltage: *600* 5000 15000 600 3300 11000 - 600 V at 60 HZ. - 5000 V at 60 HZ. - 15000 V at 60 HZ. - 600 V at 50 HZ. - 3300 V at 50 HZ. - 11000 V at 50 HZ. Number of Elbows: Default: 1 per 20 FEET [6 M] Termination Type: *NONE* NONE - No terminations TRANS - Transformer termination only SWGR - Switchgear termination only BOTH - Switchgear and transformer termination 2 Electrical transformer: 1 or 2 tap TRANSFORM Rated load: Range: 10 - 100,000 KVA Type: *DRY*, OIL 3 Oil circuit breakers OIL-C-BRKR Rated voltage: Range: 11 - 400 KV Continuous Current: Max: 5 KA 4 Disconnect switches DISCNCT-SW Voltage: Range: 4 - 230 KV 5 Overhead transmission line: cables, structures, guys, grounds See “Schematic of Project Site Transmission Line Hook-Up,” page 22-13. POLE-LINE Wire size: See “Wire Sizes” later in this chapter. 6 Steel for substation structure G3 © ICARUS Corporation, 1998. SUBSTN-STL 22-10 ICARUS Reference Electrical Plant Bulks - Substation Electrical Plant Bulks continued 7 Description Type Circuit breakers: main, feeder, tie-breakers BREAKER Continuous Current: Max: 3,000 A Voltage: through the maximum HV. Interrupt Capacity: LV: 25 - 70 MVA; MV: 250 - 350 MVA; HV: 500 - 1000 MVA Breaker type: Defualt: *FEED* FEED - Feeder breaker MAIN - Main breaker TIE - Tie breaker Type: *AIR*, SF6, VAC 8 Motor control center Floor-mounted assemblies of one or more enclosed vertical sections principally containing combination motor control/overload protection units (starters). MCC Range: LV: 0.5 - 400 HP [0.33 - 300 KW] MV: 200 - 1000 HP [150 - 3000 KW] Voltage: LV or MV Type: *S*, I The MCCs described below are intended for inside use (i.e., are not for outside use local to the motors). They are unaffected by the electrical class/zone specifications covered later in this chapter. The “intelligent” MCCs provide more sophisticated electronic control and communication to a control center. The cost for upstream items are not included (e.g., supply bus duct/cable; switchgear [feeder breakers, metering, substation disconnect switch, main breaker]; and substation transformer). There are two types of MCC available in the system (see diagram below)- those which supply electric motors driven at low voltage (MCC-LV: COA 733) and those driven at mid-voltage (MCC-MV: COA 744). The MCC-LV may contain starters for motors and as well as circuit breakers for other small electrical loads (LIGHTING TRANS. BRKR- to supply panelboards feeding lights, electric tracing, control center hardware). The MCC-MV contains only starters for motors. The MCC-LV is a 12-NEMA space cabinet; the MCC-MV is a 3-NEMA space cabinet. This item is specified by the HP [KW] rating of the motor being supplied- this permits the system to select an appropriately sized starter (see table below). The resulting cost includes both the cost of the starter as well as the cost for the fraction of the cabinet occupied by the starter. For example, assume that you specify a 20 HP [15 KW] rating- the reported cost for the MCC-LV is the cost of the 3-space starter plus three-twelfths of the whole cost of the cabinet. Specifying four such items would, in effect, completely account for the cost of one 12-space MCC-LV containing four 3-space starters. - Continued - © ICARUS Corporation, 1998. G3 Chapter 22: Electrical 22-11 Electrical Plant Bulks - Substation Electrical Plant Bulks continued Description Type Motor Size Voltage Starter Size (spaces) < = 10 HP [< = 7.5 KW] LV 2 20–50 HP [15–37.4 KW] LV 3 (lighting transformer breaker) 60-100 HP [44.7-75 KW] LV 5 125-200 HP [95-150 KW] LV 6 250-400 HP [180-300 KW] LV 9 200-400 HP [150-300 KW] MV 1 MV 3 450-4,000 HP [335-3,150 KW] Medium Voltage (MV) and Low Voltage (LV) Motor Control Centers (MCC): 9 Switch board SWITCH-BRD Continuous current: 600-4000 A Voltage: 3-13.8 KV Interrupt capacity: *25*-40 KA Type: VCB, VCS1, VCS2, VCS3 10 AC/DC Transformer AC-DC-TRAN Rating: 30-300 ampere-hours 11 Package transformer with panel Rated load: 50-800 KVA Primary voltage: 3000-13800 V No. of phases: 1 or *3* G3 © ICARUS Corporation, 1998. PKG-TRANSF 22-12 ICARUS Reference Electrical Plant Bulks - Substation Electrical Plant Bulks continued 13 Description Type Emergency diesel generator EM-PWR-SET Rated power: 5 - 1500 KVA 14 Uninterrupted power supply UPS Rated load: 2-300 KVA. Type: *STD*, MULT. 15 Power factor connection capacitor PF-CORRECT Capacity: 24-2500 KVAR. Voltage: LV, MV. © ICARUS Corporation, 1998. G3 Chapter 22: Electrical 22-13 Schematic of Project Site Transmission Line Hook-Up* Power from National or Local Power Supply Grid Overhead Transmission Line * not to scale G3 © ICARUS Corporation, 1998. Steel for Substation Structure Oil Circuit Breaker Power to Main and Unit Substations 22-14 ICARUS Reference Wire Sizes Wire sizes must be chosen from one of the following tables: US Country Base US Country Base or AWG Wire Units Wire Size Symbols (gauge sizes) LV MV HV 14 12 10 8 6 4 2 1 1/0 2/0 4/0 250 350 500 750 ............. (AWG) ............. 1000 1250 1500 1750 2000 ..... (KCMIL) ..... UK and JP Country Bases UK and JP Country Base or MM2 Wire Units Wire Size Symbols (MM2 sizes) LV MV HV 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630 800 1000 ............................... (MM2) ................................. © ICARUS Corporation, 1998. G3 Chapter 22: Electrical 22-15 Electrical Class/Division National Electrical Code (NEC). Electrical Class and Division Symbol Cable Type Single Core or Multi-Core Wire In Tray Single Core or Multi-Core Wire In Conduit Armored Cable Flammable Gasses or Vapors 11 Highly inflammable gasses and/or vapors. Hazardous atmospheres exist continuously or can occur during course of normal operation for this area. Explosion-proof. — + — 12 Flammable liquids are handled and processed in this area, but they are normally confined. — + + Combustible Dust 21 Dust is suspended in air continuously or during course of normal operation for this area. — + — 22 Suspension of dust is not likely in this area, but deposits of dust can occur and be ignited by sparks. — + + Combustible Fibers or Particles 31 Locations exist in this area in which ignitable fibers are handled or used. — + + 32 Locations exist in this area in which easily ignitable fibers are stored. — + + + + + General Purpose GP Non-hazardous conditions. + Indicates cable type consistent with electrical class and division. — Indicates cable type inconsistent with electrical class and division. G3 © ICARUS Corporation, 1998. 22-16 ICARUS Reference International Electrical Code (IEC). Electrical Zone Cable Type Single Core or Multi-Core Wire In Tray Single Core or Multi-Core Wire In Conduit Armored Cable 0 Explosive gas/air mixture is constantly present or is present for long periods. — + + 1 Explosive gas/air mixture is likely to occur under normal operating conditions. — + + 2 Explosive gas/air mixture is unlikely to occur under normal operating conditions. If it does occur, it will be of short duration. + + + GP Non-hazardous conditions. + + + + Indicates cable type consistent with electrical class and division. — Indicates cable type inconsistent with electrical class and division, WARNing message will be issued in the SCAN report. © ICARUS Corporation, 1998. G3 Chapter 22: Electrical 22-17 G3 © ICARUS Corporation, 1998.