CopperLogic Control molded case circuit breaker catalog This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com cPRO line molded case circuit breakers molded case switches F-series (15 – 225 Amps) General Description........................................................................... 6 Single Pole Breakers........................................................................... 9 Two Pole Breakers............................................................................... 10 Three Pole Breakers............................................................................ 13 Molded Case Switches....................................................................... 16 Field-Installable Accessories............................................................ 22 Trip Curves............................................................................................ 28 Technical Data.................................................................................... 41 Dimensions.......................................................................................... 45 K-series (70 – 400 Amps) General Description........................................................................... 48 Two Pole Thermal-Magnetic Breakers........................................... 50 Three Pole Thermal-Magnetic Breakers........................................ 54 Electronic Trip Breakers..................................................................... 58 100% Rated Electronic Trip Breakers.............................................. 67 Molded Case Switches....................................................................... 70 Accessories........................................................................................... 71 Trip Curves............................................................................................ 79 Technical Data.................................................................................... 96 Dimensions.......................................................................................... 100 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com Control with CopperLogic molded case circuit breakers This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com cPRO molded case circuit breakers & switches circuit and personnel protection Circuit breakers continue to offer a safe and reusable alternative to fuses for superior short circuit protection. In addition to being a “greener” solution by producing less waste, most circuit breakers provide additional types of protection and features simply not found with fuses. R Circuit breakers also reduce downtime and increase safety. A simple flip of a switch can restore continuity, where fuses require additional time and can be dangerous to replace. Unlike fuses, which are “sacrificial overcurrent devices,” CopperLogic’s cPRO circuit breakers are designed with high current withstand capabilities and sophisticated arc quenching techniques for many years of reliable use. CopperLogic’s Molded Case Circuit Breakers provide circuit protection for low voltage distribution systems. The cPRO series ranges from 15 – 400 amperes, and includes thermal-magnetic breakers, electronic trip breakers and molded case switches. >15 to 400 amperes > Meets NEMA design standards >Multiple switching capacity options >Thermal-magnetic and electronic trip breakers available >Molded case switches available cPRO breakers offer protection of cable and exceed the requirements of the NEC for branch circuit protection and UL 1087 for use as a disconnecting means. Reverse loop contact design provides for current limiting performance and higher interrupting ratings within compact breaker sizes. Quenches Arc Flashes Arc flashes take only milliseconds to compromise expensive equipment and create an extremely dangerous environment to personnel. CopperLogic’s cPRO molded case breakers significantly outperform the calculations listed in IEEE Standard 1584-2002, Guide for Performing Arc Flash Hazard Calculations. Applications • Machine Tool Control Panels and Motor Control Centers • Panelboards - as both main and branch circuit protection devices • Feeder Pillars - in distribution systems to provide main and branch circuit protection (app photo) • Switchgear - in distribution systems to provide circuit protection up to 400 amperes • Enclosed Circuit Breaker Disconnects - completely assembled in enclosures to meet specific customer requirements This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com 3 CopperLogic’s catalog numbering system for molded case circuit breakers and other devices follows a logical system. Device attributes can be determined by the following nomenclature. Dashes (–) are used to separate device attributes and should always be included when ordering. TM 3 – K4 M S Continuous Rating Device Type S 80% Continuous Rating C 100% Continuous Rating TM Thermal-Magnetic Circuit Breaker ET Electronic Trip Circuit Breaker MF Circuit Breaker Frame Only (no trip module) CS Molded Case Switch Breaking Capacity L Low Breaking Capacity M Medium Breaking Capacity H High Breaking Capacity Number of Poles 1 Single Pole 2 Two Poles 3 Three Poles Frame Size F K K2 K4 F-series (to 225A) K-series (without trip module) K-series (to 250A) K-series (to 400A) This page for reference only. Please turn to the appropriate pages to determine the exact device and/or accessories required for your application. 4 copperLogic.com This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 CPRO-CAT-1109 www.barr-thorp.com cPRO Nomenclature Molded Case Circuit Breakers and Molded Case Switches – 200 B – L S Frame Window Option Trip/Frame Rating 15 ↓ 400 S Maximum Continuous Amp Rating (blank) Without window Terminals Trip Module Type A B E F G H VISA-window option for viewing main power contacts Line and Load side Terminals ship as standard with assembled breakers. L Other options available; contact your CopperLogic representative. Fixed Thermal, Fixed Magnetic Fixed Thermal, Adjustable Magnetic Electronic Trip, I 2t response Electronic Trip, flat response (blank) Electronic Trip, I 2t with ground fault Without terminals (for Frame Only and K-series Molded Case Switches) Electronic Trip, flat with ground fault No trip module (for Frame Only and Molded Case Switches) (blank) CPRO-CAT-1109 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 copperLogic.com www.barr-thorp.com 5 cPRO F-series Factory complete breakers to 225 amps cPRO F-series breakers offer compact control with many built-in accessory options. Factory assembly means your breaker is ready-to-go from the box… saving time and reducing installation costs. F-series molded case switches are 100% rated devices, eliminating the need for “sizing up” to match your application requirements. R Versatile protection in a small footprint The F-series provides economical solutions from 15 to 225 amps at 600 V AC and 250 V DC. Three levels of breaking capacities are provided to a maximum of 200kA (@240V AC). Industrial applications of 600V and 480V are protected to a maximum of 35kA and 100kA respectively. F-series circuit breakers and molded case switches meet an array of requirements for use in many kinds of applications. In addition to standard three pole circuit protection, one and two pole breakers are available for single phase motors and other applications including lighting, heating, transformer and branch circuit protection for single phase receptacles. Breakers are also suitable for use with refrigerant motor-compressors (HACR rated) and back-fed mains (factory sealed and approved for reverse feed). All circuit breakers 15 through 30 amperes are also suitable for use with HID (high intensity discharge) lighting circuits (480V max). F-series three pole breakers occupy a small footprint of just 6” x 41∕8”. >15 – 225 amperes >Suitable for reverse feed use Interrupting Capacity [kA] 200 240V AC (for two and three pole breakers) >Factory-installed options allow breakers to 480V AC 600V AC be ready-to-go from the box > Listed in accordance with CSA C22.2 No. 5 and UL 489 250V DC 100 100 65 35 35 25 22 22 High Breaking Capacity 65 Medium Breaking Capacity Low Breaking Capacity 6 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 18 10 www.barr-thorp.com You’ve got connections Turn it On All breakers are manufactured to accept compression lugs, however line and load side box terminals are preinstalled and come standard with every F-series breaker. If desired, you can also choose line side only or load side only box terminals (or none) by special order. Multi-wire connectors are also available that allow you to distribute the load from the breaker to multiple devices without the use of separate distribution terminal blocks. In addition, a control wire terminal kit can be used to tap off the main power terminal, which can eliminate the need for additional panel wiring. Safety you can see CopperLogic breakers offer optional viewing windows in the breaker frame that allow you to see the position of the main power contacts in toggle operated applications. This is a requirement in the mining industry and certain utilities. If a pole is welded closed, one glance at the window can prevent serious injury. In addition, accessories such as terminal shields and end covers provide touch-safe protection. The cPRO F-series also includes two and three-pole Molded Case Switches that offer up to 225A switching capabilities in applications to 600V AC and 250V DC. Molded case switches are constructed of circuit breaker components and include a fixed magnetic trip to increase the short circuit withstand rating (65kA @480V) and to protect the switch itself. They are also listed for reverse feed use and are 100% rated devices. A Shunt Trip is also available for these Switches, a feature not offered by many other manufacturers. Factory Installed Options Include: • Line and Load Terminals • Built-in Frame Window • Alarm Lockout Switch • Auxiliary Switch • Alarm and Auxiliary Combination Switch • Shunt Trip • Undervoltage Trip Remote electrical operator Two types of devices are available for remote operation and reset. The first has a solenoid mechanism that trips the breaker in as little as 80ms. The other type has built-in electric motor that physically moves the breaker toggle in three seconds. Through-the-door & Flange Mounted Operators All operators include a lock-out mechanism for up to three padlocks that prevent the handle from being turned to the ON position. Door interlocks also prevent the enclosure door from being opened while the handle is in the ON position (defeat mechanisms are included). Flange handle can be mounted up to 10 ft. away from the breaker. Standard handles are rated NEMA 1 and 12 - available in black and red Ergonomic handles are rated NEMA 1, 12, 3R, 4 and 4X Flange handles are rated NEMA 1, 12, 3R, 4 and 4X This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com 7 cPRO Molded Case Circuit Breakers Notes 8 copperLogic.com This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 CPRO-CAT-1109 www.barr-thorp.com cPRO Molded Case Circuit Breakers Thermal-Magnetic Single Pole, F-series > For single pole applications to 150A @347V > Protection for single-phase motors, transformers and branch circuits > UL and CSA approved for switching duty to 20A > Factory installed options allows for quicker installation time > HACR rated allows for use with refrigerant motor compressors > Factory sealed and approved for reverse feed use with back-fed mains Thermal-Magnetic Single Pole Circuit Breakers with Non-Interchangeable Fixed Thermal, Fixed Magnetic Trip Module ➊➋➌ Continuous Amp Rating @ 40° C (104° F) Maximum Operating Voltage Low Breaking Capacity 18 kAIC @ 347 V AC 35 kAIC @ 277 V AC 10 kAIC @ 125 V DC ➍ AC DC Catalog Number Price 15 347 125 TM1-FLS-15A-L ➎ 581 20 347 125 TM1-FLS-20A-L ➎ 581 25 347 125 TM1-FLS-25A-L 581 30 347 125 TM1-FLS-30A-L 581 35 347 125 TM1-FLS-35A-L 581 40 347 125 TM1-FLS-40A-L 581 45 347 125 TM1-FLS-45A-L 581 50 347 125 TM1-FLS-50A-L 581 60 347 125 TM1-FLS-60A-L 581 70 347 125 TM1-FLS-70A-L 653 80 347 125 TM1-FLS-80A-L 653 90 347 125 TM1-FLS-90A-L 653 100 347 125 TM1-FLS-100A-L 653 110 347 125 TM1-FLS-110A-L 1447 125 347 125 TM1-FLS-125A-L 1447 150 347 125 TM1-FLS-150A-L 1930 ➊ Line and Load side terminals ship with breaker as standard. Other options are available; contact your CopperLogic representative. Ordering Instructions 1 2 ➋ A VISA-window to view main power contacts is available. If desired, add “S” to end of main breaker catalog number, and add $950 to price. For toggle style operators only. Locate the desired main circuit breaker. Order field-installable accessories separately on pages 22 – 27. ➌ Mounting hardware not included. Order base mounting hardware separately on page 27. ➍ DC ratings apply to substantially non-inductive circuits. Time constant is 3ms minimum at 10kA and 8ms minimum at 22kA. ➎ UL and CSA listed for SWD (switching duty) lighting applications. CPRO-CAT-1109 Discount Code B30 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 copperLogic.com www.barr-thorp.com 9 > For two pole applications to 225A @600V > Protection for single-phase motors, transformers and branch circuits > Factory installed options allows for quicker installation time > HACR rated allows for use with refrigerant motor compressors > Factory sealed and approved for reverse feed use with back-fed mains Thermal-Magnetic Two Pole Circuit Breakers with Non-Interchangeable Fixed Thermal, Fixed Magnetic Trip Module ➊➋➌ Step 1: Select Main Breaker Continuous Amp Rating @ 40° C (104° F) Maximum Operating Voltage Low Breaking Capacity 18 kAIC @ 600 V AC 35 kAIC @ 480 V AC 65 kAIC @ 240 V AC 10 kAIC @ 250 V DC ➍ Price Medium Breaking Capacity 25 kAIC @ 600 V AC 65 kAIC @ 480 V AC 100 kAIC @ 240 V AC 22 kAIC @ 250 V DC ➍ AC DC Catalog Number Catalog Number Price Catalog Number Price 15 600 250 TM2-FLS-15A-L 774 TM2-FMS-15A-L 1379 TM2-FHS-15A-L 1525 20 600 250 TM2-FLS-20A-L 774 TM2-FMS-20A-L 1379 TM2-FHS-20A-L 1525 25 600 250 TM2-FLS-25A-L 774 TM2-FMS-25A-L 1379 TM2-FHS-25A-L 1525 30 600 250 TM2-FLS-30A-L 774 TM2-FMS-30A-L 1379 TM2-FHS-30A-L 1525 35 600 250 TM2-FLS-35A-L 774 TM2-FMS-35A-L 1379 TM2-FHS-35A-L 1525 40 600 250 TM2-FLS-40A-L 774 TM2-FMS-40A-L 1379 TM2-FHS-40A-L 1525 45 600 250 TM2-FLS-45A-L 774 TM2-FMS-45A-L 1379 TM2-FHS-45A-L 1525 50 600 250 TM2-FLS-50A-L 774 TM2-FMS-50A-L 1379 TM2-FHS-50A-L 1525 60 600 250 TM2-FLS-60A-L 774 TM2-FMS-60A-L 1379 TM2-FHS-60A-L 1525 70 600 250 TM2-FLS-70A-L 798 TM2-FMS-70A-L 1742 TM2-FHS-70A-L 1851 80 600 250 TM2-FLS-80A-L 798 TM2-FMS-80A-L 1742 TM2-FHS-80A-L 1851 1851 90 600 250 TM2-FLS-90A-L 798 TM2-FMS-90A-L 1742 TM2-FHS-90A-L 100 600 250 TM2-FLS-100A-L 798 TM2-FMS-100A-L 1742 TM2-FHS-100A-L 1851 110 600 250 TM2-FLS-110A-L 1696 TM2-FMS-110A-L 3509 TM2-FHS-110A-L 4035 125 600 250 TM2-FLS-125A-L 1696 TM2-FMS-125A-L 3509 TM2-FHS-125A-L 4035 150 600 250 TM2-FLS-150A-L 1696 TM2-FMS-150A-L 4254 TM2-FHS-150A-L 4956 175 600 250 TM2-FLS-175A-L 1696 TM2-FMS-175A-L 4430 TM2-FHS-175A-L 5219 200 600 250 TM2-FLS-200A-L 1696 TM2-FMS-200A-L 4430 TM2-FHS-200A-L 5219 225 600 250 TM2-FLS-225A-L 1696 TM2-FMS-225A-L 4430 TM2-FHS-225A-L 5219 ➊ Line and Load side terminals ship with breaker as standard. Other options are available; contact your CopperLogic representative. Ordering Instructions 1 2 3 High Breaking Capacity 35 kAIC @ 600 V AC 100 kAIC @ 480 V AC 200 kAIC @ 240 V AC 22 kAIC @ 250 V DC ➍ ➋ A VISA-window to view main power contacts is available. If desired, add “S” to end of main breaker catalog number, and add $950 to price. For toggle style operators only. Locate the desired main circuit breaker. Choose an optional right pole accessory on next page. Order field-installable accessories separately on pages 22 – 27. 10 copperLogic.com ➌ Mounting hardware not included. Order base mounting hardware separately on page 27. ➍ DC ratings apply to substantially non-inductive circuits. Time constant is 3ms minimum at 10kA and 8ms minimum at 22kA. ➎ Internal accessories must be factory installed to maintain UL/CSA approval with F-series cPRO circuit breakers and molded case switches. Discount Code B30 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 CPRO-CAT-1109 www.barr-thorp.com cPRO Molded Case Circuit Breakers Thermal-Magnetic Two Pole, F-series Internal Accessories for Factory Installation ➎ - Right Pole mounted options Step 2: Select Optional Right Pole Accessory (Choose One) Factory Installation Code Installed Accessories Description For use with… Schematic (add to catalog Operating Voltage number as suffix) Price Adder Alarm Lockout Switch For remote indication of trip operation. Switch resets when circuit breaker resets. 18 inch pigtail leads, 18 AWG / 0.8 mm2 Installed on right pole, leads exit on rear of breaker Make 1 NO & 1 NC +B06F 337 2 NO & 2 NC +B13F 337 1 NO & 1 NC +A06F 337 2 NO & 2 NC +A13F 337 1 NO & 1 NC for Auxilary and 1 NO & 1 NC for Alarm +C05F 337 12 – 24 V AC 12 – 24 V DC +S18F 589 48 – 127 V AC 48 – 60 V DC +S22F 589 208 – 380 V AC 110 – 127 V DC +S26F 589 415 – 600 V AC 220 – 250 V DC +S30F 589 12 V AC 12 V DC 24 V AC 24 V DC +U50F +U78F +U54F +U82F 592 592 592 592 48 V AC 48 V DC +U86F 592 60 V AC 60 V DC +U102F 592 110 – 127 V AC 110 – 127 V DC 208 – 240 V AC 220 – 250 V DC 380 – 480 V AC 525 – 600 V AC +U62F +U90F +U66F +U94F +U70F +U74F 592 592 592 592 592 592 Two pole F-series Break Auxiliary Switch For remote indication of circuit breaker status. 18 inch pigtail leads, 18 AWG / 0.8 mm2 Installed on right pole, leads exit on rear of breaker a Two pole F-series b Alarm and Auxiliary Switch Combination 18 inch pigtail leads, 18 AWG / 0.8 mm2 Installed on right pole, leads exit on rear of breaker a Two pole F-series b Shunt Trip Provides remote trip Intermittent duty 18 inch pigtail leads, 18 AWG / 0.8 mm2 Installed on right pole, leads exit on rear of breaker Two pole F-series Three pole F-series ST a Undervoltage Trip Monitors power feed to circuit breaker or switch. Trips circuit breaker or switch when voltage drops below threshold. 18 inch pigtail leads, 18 AWG / 0.8 mm2 Installed on right pole, leads exit on rear of breaker CPRO-CAT-1109 Two pole F-series Three pole F-series UV Discount Code B30 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 copperLogic.com www.barr-thorp.com 11 cPRO Molded Case Circuit Breakers Notes 12 copperLogic.com This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 CPRO-CAT-1109 www.barr-thorp.com cPRO Molded Case Circuit Breakers Thermal-Magnetic Three Pole, F-series > For three pole applications to 225A @600V > Protection for three-phase motors, transformers and branch circuits > Factory installed options allows for quicker installation time > HACR rated allows for use with refrigerant motor compressors > Factory sealed and approved for reverse feed use with back-fed mains Thermal-Magnetic Three Pole Circuit Breakers with Non-Interchangeable Fixed Thermal, Fixed Magnetic Trip Module ➊➋➌ Step 1: Select Main Breaker Continuous Amp Rating @ 40° C (104° F) Maximum Operating Voltage Low Breaking Capacity 18 kAIC @ 600 V AC 35 kAIC @ 480 V AC 65 kAIC @ 240 V AC 10 kAIC @ 250 V DC ➍ Price Medium Breaking Capacity 25 kAIC @ 600 V AC 65 kAIC @ 480 V AC 100 kAIC @ 240 V AC 22 kAIC @ 250 V DC ➍ AC DC Catalog Number Catalog Number Price Catalog Number Price 15 600 250 TM3-FLS-15A-L 816 TM3-FMS-15A-L 1557 TM3-FHS-15A-L 2102 20 600 250 TM3-FLS-20A-L 816 TM3-FMS-20A-L 1557 TM3-FHS-20A-L 2102 25 600 250 TM3-FLS-25A-L 816 TM3-FMS-25A-L 1557 TM3-FHS-25A-L 2102 30 600 250 TM3-FLS-30A-L 816 TM3-FMS-30A-L 1557 TM3-FHS-30A-L 2102 35 600 250 TM3-FLS-35A-L 816 TM3-FMS-35A-L 1557 TM3-FHS-35A-L 2102 40 600 250 TM3-FLS-40A-L 816 TM3-FMS-40A-L 1557 TM3-FHS-40A-L 2102 45 600 250 TM3-FLS-45A-L 816 TM3-FMS-45A-L 1557 TM3-FHS-45A-L 2102 50 600 250 TM3-FLS-50A-L 816 TM3-FMS-50A-L 1557 TM3-FHS-50A-L 2102 60 600 250 TM3-FLS-60A-L 816 TM3-FMS-60A-L 1557 TM3-FHS-60A-L 2102 70 600 250 TM3-FLS-70A-L 816 TM3-FMS-70A-L 1692 TM3-FHS-70A-L 2272 80 600 250 TM3-FLS-80A-L 816 TM3-FMS-80A-L 1692 TM3-FHS-80A-L 2272 2863 90 600 250 TM3-FLS-90A-L 816 TM3-FMS-90A-L 1899 TM3-FHS-90A-L 100 600 250 TM3-FLS-100A-L 816 TM3-FMS-100A-L 2142 TM3-FHS-100A-L 2863 110 600 250 TM3-FLS-110A-L 1785 TM3-FMS-110A-L 3132 TM3-FHS-110A-L 4475 125 600 250 TM3-FLS-125A-L 1785 TM3-FMS-125A-L 3132 TM3-FHS-125A-L 4475 150 600 250 TM3-FLS-150A-L 1785 TM3-FMS-150A-L 3262 TM3-FHS-150A-L 5173 175 600 250 TM3-FLS-175A-L 1785 TM3-FMS-175A-L 4092 TM3-FHS-175A-L 5173 200 600 250 TM3-FLS-200A-L 1785 TM3-FMS-200A-L 5000 TM3-FHS-200A-L 6091 225 600 250 TM3-FLS-225A-L 1785 TM3-FMS-225A-L 5444 TM3-FHS-225A-L 6712 Ordering Instructions 1 2 3 4 High Breaking Capacity 35 kAIC @ 600 V AC 100 kAIC @ 480 V AC 200 kAIC @ 240 V AC 22 kAIC @ 250 V DC ➍ CPRO-CAT-1109 See next page for Step 2. ➊ Line and Load side terminals ship with breaker as standard. Other options are available; contact your CopperLogic representative. Locate the desired main circuit breaker. Choose an optional left pole accessory on next page. Choose an optional right pole accessory on page 15. Order field-installable accessories separately on pages 22 – 27. ➋ A VISA-window to view main power contacts is available. If desired, add “S” to end of main breaker catalog number, and add $950 to price. For toggle style operators only. ➌ Mounting hardware not included. Order base mounting hardware separately on page 27. ➍ DC ratings apply to substantially non-inductive circuits. Time constant is 3ms minimum at 10kA and 8ms minimum at 22kA. Discount Code B30 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 copperLogic.com www.barr-thorp.com 13 Accessories F-series Factory Installation Options Internal Accessories for Factory Installation ➊ - Left Pole mounted options ➋ Step 2: Select Optional Left Pole Accessory (Choose One) Factory Installation Code Installed Accessories Description For use with… Schematic Price Adder Contacts (add to catalog number as suffix) 1 NO & 1 NC +B02F 337 2 NO & 2 NC +B10F 337 1 NO & 1 NC +A02F 337 2 NO & 2 NC +A10F 337 1 NO & 1 NC for Auxilary and 1 NO & 1 NC for Alarm +C02F 337 Alarm Lockout Switch For remote indication of trip operation. Switch resets when circuit breaker resets. 18 inch pigtail leads, 18 AWG / 0.8 mm2 Installed on left pole, leads exit on rear of breaker Make Three pole F-series Break Auxiliary Switch For remote indication of circuit breaker status. 18 inch pigtail leads, 18 AWG / 0.8 mm2 Installed on left pole, leads exit on rear of breaker a Three pole F-series b Alarm and Auxiliary Switch Combination 18 inch pigtail leads, 18 AWG / 0.8 mm2 Installed on left pole, leads exit on rear of breaker a Three pole F-series b Ordering Instructions 1 2 3 4 Locate the desired main circuit breaker from previous page. Choose an optional left pole accessory on this page. Choose an optional right pole accessory on next page. Order field-installable accessories separately on pages 22 – 27. 14 copperLogic.com ➊ Internal accessories must be factory installed to maintain UL/CSA approval with F-series cPRO circuit breakers and molded case switches. ➋ Popular configurations shown. Additional configurations including lead exit and pole mounting locations are available, contact your CopperLogic representative. Discount Code B30 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 CPRO-CAT-1109 www.barr-thorp.com Accessories F-series Factory Installation Options Internal Accessories for Factory Installation ➊ - Right Pole mounted options ➋ Step 3: Select Optional Right Pole Accessory (Choose One) Factory Installation Code Installed Accessories Description For use with… Schematic (add to catalog Operating Voltage number as suffix) Price Adder Shunt Trip Provides remote trip Intermittent duty 18 inch pigtail leads, 18 AWG / 0.8 mm2 Installed on right pole, leads exit on rear of breaker Two pole F-series Three pole F-series ST a 12 – 24 V AC 12 – 24 V DC +S18F 589 48 – 127 V AC 48 – 60 V DC +S22F 589 208 – 380 V AC 110 – 127 V DC +S26F 589 415 – 600 V AC 220 – 250 V DC +S30F 589 12 V AC 12 V DC 24 V AC 24 V DC +U50F +U78F +U54F +U82F 592 592 592 592 48 V AC 48 V DC +U86F 592 60 V AC 60 V DC +U102F 592 110 – 127 V AC 110 – 127 V DC 208 – 240 V AC 220 – 250 V DC 380 – 480 V AC 525 – 600 V AC +U62F +U90F +U66F +U94F +U70F +U74F 592 592 592 592 592 592 Undervoltage Trip Monitors power feed to circuit breaker or switch. Trips circuit breaker or switch when voltage drops below threshold. 18 inch pigtail leads, 18 AWG / 0.8 mm2 Installed on right pole, leads exit on rear of breaker Two pole F-series Three pole F-series UV Ordering Instructions 1 2 3 4 CPRO-CAT-1109 Locate the desired main circuit breaker from page 13. Choose an optional left pole accessory on previous page. Choose an optional right pole accessory on this page. Order field-installable accessories separately on pages 22 – 27. ➊ Internal accessories must be factory installed to maintain UL/CSA approval with F-series cPRO circuit breakers and molded case switches. ➋ Popular configurations shown. Additional configurations including lead exit and pole mounting locations are available, contact your CopperLogic representative. Discount Code B30 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 copperLogic.com www.barr-thorp.com 15 > For two pole, single-phase motor disconnecting and switching to 225A > 100% Rated device prevents need to select a larger switch size > Built-in fixed instantaneous trip opens above 1800 Amps > Factory installed options allows for quicker installation time > HACR rated allows for use with refrigerant motor compressors Two Pole Molded Case Switches ➊➋➌➍ Step 1: Select Main Switch Maximum Operating Voltage Medium Short-circuit Withstand Rating 25 kAIC @ 600 V AC 65 kAIC @ 480 V AC 100 kAIC @ 240 V AC 22 kAIC @ 250 V DC Low Short-circuit Withstand Rating 18 kAIC @ 600 V AC 25 kAIC @ 480 V AC 65 kAIC @ 240 V AC 10 kAIC @ 250 V DC Continuous Amp Rating @ 40° C (104° F) AC DC Catalog Number Price Catalog Number Price 100 600 250 CS2-FLC-100-L 1360 CS2-FMC-100-L 1842 150 600 250 CS2-FLC-150-L 2193 CS2-FMC-150-L 2500 225 600 250 CS2-FLC-225-L 2917 CS2-FMC-225-L 3246 ➊ Line and Load side terminals ship with molded case switch as standard. Other options are available; contact your CopperLogic representative. Ordering Instructions 1 2 3 ➋ A VISA-window to view main power contacts is available. If desired, add “S” to end of main switch catalog number, and add $950 to price. For toggle style operators only. Locate the desired main molded case switch. Choose an optional right pole accessory on next page. Order field-installable accessories separately on pages 22 – 27. 16 copperLogic.com ➌ Molded case switches are supplied with a fixed instantaneous trip that opens above 1800A. ➍ Mounting hardware not included. Order base mounting hardware separately on page 27. ➎ Internal accessories must be factory installed to maintain UL/CSA approval with F-series cPRO circuit breakers and molded case switches. Discount Code B30 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 CPRO-CAT-1109 www.barr-thorp.com cPRO Molded Case Switches Molded Case Switches, Two pole, F-series Internal Accessories for Factory Installation ➎ - Right Pole mounted options Step 2: Select Optional Right Pole Accessory (Choose One) Factory Installation Code Installed Accessories Description For use with… Schematic (add to catalog Operating Voltage number as suffix) Price Adder Alarm Lockout Switch For remote indication of trip operation. Switch resets when circuit breaker resets. 18 inch pigtail leads, 18 AWG / 0.8 mm2 Installed on right pole, leads exit on rear of breaker Make 1 NO & 1 NC +B06F 337 2 NO & 2 NC +B13F 337 1 NO & 1 NC +A06F 337 2 NO & 2 NC +A13F 337 1 NO & 1 NC for Auxilary and 1 NO & 1 NC for Alarm +C05F 337 12 – 24 V AC 12 – 24 V DC +S18F 589 48 – 127 V AC 48 – 60 V DC +S22F 589 208 – 380 V AC 110 – 127 V DC +S26F 589 415 – 600 V AC 220 – 250 V DC +S30F 589 12 V AC 12 V DC 24 V AC 24 V DC +U50F +U78F +U54F +U82F 592 592 592 592 48 V AC 48 V DC +U86F 592 60 V AC 60 V DC +U102F 592 110 – 127 V AC 110 – 127 V DC 208 – 240 V AC 220 – 250 V DC 380 – 480 V AC 525 – 600 V AC +U62F +U90F +U66F +U94F +U70F +U74F 592 592 592 592 592 592 Two pole F-series Break Auxiliary Switch For remote indication of circuit breaker status. 18 inch pigtail leads, 18 AWG / 0.8 mm2 Installed on right pole, leads exit on rear of breaker a Two pole F-series b Alarm and Auxiliary Switch Combination 18 inch pigtail leads, 18 AWG / 0.8 mm2 Installed on right pole, leads exit on rear of breaker a Two pole F-series b Shunt Trip Provides remote trip Intermittent duty 18 inch pigtail leads, 18 AWG / 0.8 mm2 Installed on right pole, leads exit on rear of breaker Two pole F-series Three pole F-series ST a Undervoltage Trip Monitors power feed to circuit breaker or switch. Trips circuit breaker or switch when voltage drops below threshold. 18 inch pigtail leads, 18 AWG / 0.8 mm2 Installed on right pole, leads exit on rear of breaker CPRO-CAT-1109 Two pole F-series Three pole F-series UV Discount Code B30 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 copperLogic.com www.barr-thorp.com 17 cPRO Molded Case Circuit Breakers Notes 18 copperLogic.com This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 CPRO-CAT-1109 www.barr-thorp.com cPRO Molded Case Switches Molded Case Switches, Three pole, F-series > For three pole, three-phase motor disconnecting and switching to 225A > 100% Rated device prevents need to select a larger switch size > Built-in fixed instantaneous trip opens above 1800 Amps > Factory installed options allows for quicker installation time > HACR rated allows for use with refrigerant motor compressors Three Pole Molded Case Switches ➊➋➌➍ Step 1: Select Main Switch Maximum Operating Voltage Medium Short-circuit Withstand Rating 25 kAIC @ 600 V AC 65 kAIC @ 480 V AC 100 kAIC @ 240 V AC 22 kAIC @ 250 V DC Low Short-circuit Withstand Rating 18 kAIC @ 600 V AC 25 kAIC @ 480 V AC 65 kAIC @ 240 V AC 10 kAIC @ 250 V DC Continuous Amp Rating @ 40° C (104° F) AC DC Catalog Number Price Catalog Number Price 100 600 250 CS3-FLC-100-L 1480 CS3-FMC-100-L 1899 150 600 250 CS3-FLC-150-L 2191 CS3-FMC-150-L 3333 225 600 250 CS3-FLC-225-L 3690 CS3-FMC-225-L 4386 Ordering Instructions 1 2 3 4 See next page for Step 2. ➊ Line and Load side terminals ship with molded case switch as standard. Other options are available; contact your CopperLogic representative. Locate the desired main molded case switch. Choose an optional left pole accessory on next page. Choose an optional right pole accessory on page 21. Order field-installable accessories separately on pages 22 – 27. ➋ A VISA-window to view main power contacts is available. If desired, add “S” to end of main switch catalog number, and add $950 to price. For toggle style operators only. ➌ Molded case switches are supplied with a fixed instantaneous trip that opens above 1800A. ➍ Mounting hardware not included. Order base mounting hardware separately on page 27. CPRO-CAT-1109 Discount Code B30 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 copperLogic.com www.barr-thorp.com 19 Accessories F-series Factory Installation Options Internal Accessories for Factory Installation ➊ - Left Pole mounted options ➋ Step 2: Select Optional Left Pole Accessory (Choose One) Factory Installation Code Installed Accessories Description For use with… Schematic Price Adder Contacts (add to catalog number as suffix) 1 NO & 1 NC +B02F 337 2 NO & 2 NC +B10F 337 1 NO & 1 NC +A02F 337 2 NO & 2 NC +A10F 337 1 NO & 1 NC for Auxilary and 1 NO & 1 NC for Alarm +C02F 337 Alarm Lockout Switch For remote indication of trip operation. Switch resets when circuit breaker resets. 18 inch pigtail leads, 18 AWG / 0.8 mm2 Installed on left pole, leads exit on rear of breaker Make Three pole F-series Break Auxiliary Switch For remote indication of circuit breaker status. 18 inch pigtail leads, 18 AWG / 0.8 mm2 Installed on left pole, leads exit on rear of breaker a Three pole F-series b Alarm and Auxiliary Switch Combination 18 inch pigtail leads, 18 AWG / 0.8 mm2 Installed on left pole, leads exit on rear of breaker a Three pole F-series b Ordering Instructions 1 2 3 4 Locate the desired molded case switch from previous page. Choose an optional left pole accessory on this page. Choose an optional right pole accessory on next page. Order field-installable accessories separately on pages 22 – 27. 20 copperLogic.com ➊ Internal accessories must be factory installed to maintain UL/CSA approval with F-series cPRO circuit breakers and molded case switches. ➋ Popular configurations shown. Additional configurations including lead exit and pole mounting locations are available, contact your CopperLogic representative. Discount Code B30 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 CPRO-CAT-1109 www.barr-thorp.com Accessories F-series Factory Installation Options Internal Accessories for Factory Installation ➊ - Right Pole mounted options ➋ Step 3: Select Optional Right Pole Accessory (Choose One) Factory Installation Code Installed Accessories Description For use with… Schematic (add to catalog Operating Voltage number as suffix) Price Adder Shunt Trip Provides remote trip Intermittent duty 18 inch pigtail leads, 18 AWG / 0.8 mm2 Installed on right pole, leads exit on rear of breaker Two pole F-series Three pole F-series ST a 12 – 24 V AC 12 – 24 V DC +S18F 589 48 – 127 V AC 48 – 60 V DC +S22F 589 208 – 380 V AC 110 – 127 V DC +S26F 589 415 – 600 V AC 220 – 250 V DC +S30F 589 12 V AC 12 V DC 24 V AC 24 V DC +U50F +U78F +U54F +U82F 592 592 592 592 48 V AC 48 V DC +U86F 592 60 V AC 60 V DC +U102F 592 110 – 127 V AC 110 – 127 V DC 208 – 240 V AC 220 – 250 V DC 380 – 480 V AC 525 – 600 V AC +U62F +U90F +U66F +U94F +U70F +U74F 592 592 592 592 592 592 Undervoltage Trip Monitors power feed to circuit breaker or switch. Trips circuit breaker or switch when voltage drops below threshold. 18 inch pigtail leads, 18 AWG / 0.8 mm2 Installed on right pole, leads exit on rear of breaker Two pole F-series Three pole F-series UV Ordering Instructions 1 2 3 4 CPRO-CAT-1109 Locate the desired molded case switch from page 19. Choose an optional left pole accessory on previous page. Choose an optional right pole accessory on this page. Order field-installable accessories separately on pages 22 – 27. ➊ Internal accessories must be factory installed to maintain UL/CSA approval with F-series cPRO circuit breakers and molded case switches. ➋ Popular configurations shown. Additional configurations including lead exit and pole mounting locations are available, contact your CopperLogic representative. Discount Code B30 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 copperLogic.com www.barr-thorp.com 21 Accessories F-series Field Installation Options Through-the-door Handles - Complete Units (includes handle, mechanism and shaft) ➊ Accessory Shaft Length mm (in.) Description Handle Color Catalog Number Price Black Red Black Red Black Red FHMVD06B FHMVD06R FHMVD12B FHMVD12R FHMVD24B FHMVD24R 295 295 305 305 420 420 152.4 (6) Black HM1R06 593 304.8 (12) Black HM1R12 624 406.4 (16) Black HM1R16 690 609.6 (24) Black HM1R24 765 152.4 (6) Black HM1R06X 658 304.8 (12) Black HM1R12X 675 406.4 (16) Black HM1R16X 739 609.6 (24) Black HM1R24X 802 Standard Handle Kit - NEMA 1, 12 152.4 (6) NEMA 1, 12 Molded plastic handle For F-series 90 degree rotation 304.8 (12) 609.6 (24) Ergonomic Handle Kit- NEMA 1, 12, 3R NEMA 1, 12, 3R Steel handle For F-series Ergonomic design for ‘gloved hand’ operation 45 degree rotation Ergonomic Handle Kit - NEMA 4/4X NEMA 4/4X Steel handle For F-series Ergonomic design for ‘gloved hand’ operation 45 degree rotation Through-the-door Handles - Components (order separately) ➊ Mechanism Handle Description Handle Color Catalog Number Price Catalog Number Shaft Price Length [mm (in.)] Catalog Number Price Handle Components for NEMA 1, 12, 3R NEMA 1, 12, 3R Ergonomic Steel handle For F-series Ergonomic design for ‘gloved hand’ operation 45 degree rotation Black 6648C22G25 541 6648C23G11 602 152.4 (6) 4217B37G08 150 304.8 (12) 4217B37G05 180 406.4 (16) 4217B37G06 211 609.6 (24) 4217B37G07 241 152.4 (6) 4217B37G08 150 304.8 (12) 4217B37G05 180 406.4 (16) 4217B37G06 211 609.6 (24) 4217B37G07 241 Handle Components for NEMA 4/4X NEMA 4/4X Ergonomic Steel handle For F-series Ergonomic design for ‘gloved hand’ operation 45 degree rotation Black 6648C22G27 677 6648C23G11 602 ➊ Not for use with VISA-window option. 22 copperLogic.com Discount Code B30 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 CPRO-CAT-1109 www.barr-thorp.com Accessories F-series Field Installation Options Flange Mounted Handles ➊ Accessory NEMA 1, 12, 3R Flexible Shaft Length m (ft.) Catalog Number Price Description NEMA 4/4X Catalog Number Price Flange Handles For F-series Extra heavy-duty flexible shaft Accepts up to 3 padlocks 0.9 (3) F1S03C 1475 F1S03CX 1801 1.2 (4) F1S04C 1507 F1S04CX 1840 1.5 (5) F1S05C 1539 F1S05CX 1880 1.8 (6) F1S06C 1573 F1S06CX 1920 2.1 (7) F1S07C 1603 F1S07CX 1959 2.4 (8) F1S08C 1634 F1S08CX 1999 2.7 (9) F1S09C 1666 F1S09CX 2031 3.0 (10) F1S10C 1689 F1S10CX 2062 Safety Door Hardware for NEMA 12 Flex Shafts Accessory Description Handle Length mm (in.) Catalog Number Price Hardware Kit Provides enclosure sealing and protection against unauthorized entry 101.6 (4.0) C361KJ4 500 152.4 (6.0) C361KJ6 500 – C361KR 66 Roller Latch Required for 3-point latching ➊ Not for use with VISA-window option. CPRO-CAT-1109 Discount Code B30 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 copperLogic.com www.barr-thorp.com 23 Accessories F-series Field Installation Options Remote Electrical Operators Accessory Description Inrush Current [A] Max. Operating Time Fuse [A] 10 5 cycles (80 ms) 5 Operating Voltage AC DC For use with… Catalog Number 3 120 – F-series EOP1P07 3485 5 cycles (80 ms) 2 240 – F-series EOP1P11 3485 10 5 cycles (80 ms) 3 – 120 F-series EOP1P07DC 3485 5 5 cycles (80 ms) 2 – 240 F-series EOP1P11DC 3485 – 120 – F-series MOP1P07 3485 – – 24 F-series MOP1P03DC 3485 – – 48 F-series MOP1P05DC 3485 – – 125 F-series MOP1P07DC 3485 Price Electrical Solenoid Operator Enables local and remote switching (ON, OFF and reset). Unique bistable latch allows device to operate with only one solenoid Padlockable in OFF position Endurance tested for 10,000 electrical operations Electrical Motor Operator Allows for circuit breaker to be opened, closed or reset remotely Lock-off capable Operator uses a reversible motor to operate the circuit breaker handle. Endurance tested for 4,000 electrical operations 2 5 3 3 seconds (intermittent duty - safe duty cycle should not exceed one per minute) 2 Current Limiter Current Limiter Description For Use With… Catalog Number Price F-series circuit breakers Amp rating: 15 – 70 LFD3070R 1096 F-series circuit breakers Amp rating: 80 – 150 LFD3150R 1535 LFD Current Limiter For thermal-magnetic circuit breakers to 150A Provides 200 kA Interrupting Capacity to 600V AC 24 copperLogic.com Discount Code B30 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 CPRO-CAT-1109 www.barr-thorp.com Accessories F-series Field Installation Options Miscellaneous Accessories Accessory Description For use with… Catalog Number Price Terminal Shield Protection against accidental contact with line side terminals Order in sets of 10; priced individually Single pole F-series 625B229G06 84 Two pole F-series 625B229G07 84 Three pole F-series 625B229G08 84 Three pole F-series with Electrical Operator 4210B95G01 842 TEC1 158 F-series Conductor Opening: 10.41 mm TEC2 (0.41 in) 158 F-series IPB1 105 F-series LKD1 105 F-series PHL1 105 Two Pole F-series Three Pole F-series PLK1 105 Left side mounting PLK1LOFF 105 Right side mounting PLK1ROFF 105 Terminal End Cover Close fitting conductor openings are molded into the end cover. The end cover and circuit breaker or switch case fit together to form terminal compartments that isolate discharged ionizing gases during circuit breaker tripping. F-series Conductor Opening: 6.35 mm (0.25 in) Interphase Barriers High dielectric insulating plates provide additional electrical clearance between circuit breaker or switch poles Priced and packaged in sets of two. Non-padlockable Handle Block Used to secure the circuit breaker or switch handle in either the ON or OFF position. Breaker is allowed to trip when blocked in the ON position. Secured by a setscrew, handle block deters accidental operation of circuit breaker handle. Snap-on Padlockable Handle Lock Hasp Used to lock the circuit breaker or switch handle in either the ON or OFF position. Breaker is allowed to trip when blocked in the ON position. Accepts one padlock up to 1/4 inch (6 mm) shackle. Padlockable Handle Lock Hasp Used to lock the circuit breaker or switch handle in either the ON or OFF position. Breaker is allowed to trip when blocked in the ON position. Accepts up to three padlocks with 1/4 inch (6 mm) shackles. Used to lock the circuit breaker handle or switch in OFF position. Accepts up to three padlocks with 1/4 inch (6 mm) shackles. CPRO-CAT-1109 Discount Code B30 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 copperLogic.com www.barr-thorp.com 25 Accessories F-series Field Installation Options Ring Terminal Adapters Accessory Description Thread Size For use with… Catalog Number Price Two pole F-series KPEK12 53 Three pole F-series KPEK1 53 Imperial 10-32 F-series KPR1A 158 Max. Amps For use with… 150 F-series from 25 to 100 Amps 225 F-series FCWTK225 ➋ from 110 to 225 Amps End Cap Kit A threaded adapter to accept a ring terminal or other bolt-on connector to the circuit breaker or switch Imperial 10-32 Keeper Nut A threaded adapter to accept a ring terminal or other bolt-on connector to the circuit breaker or switch Order in sets of 12; priced individually Control Wire Terminal Kits Accessory Description Catalog Number Price Control Wire Terminal Kit Used to tap off control power from circuit breaker or switch Order in sets of 12; priced individually FCWTK ➊ 26 26 Multi-wire Connectors Accessory Description Max. Amps Wires per Terminal 225 3 Wire Size For use with… Catalog Number Price Multi-wire Connectors Used to distribute the load from the circuit breaker or switch to multiple devices without the use of separate distribution terminal blocks. Priced and packaged in sets of three. 14 – 2 AWG Cu 3TA150F3K 228 3TA150F6K 290 F-series 225 6 14 – 6 AWG Cu ➊ For use with steel or stainless steel terminals only. ➊ Use only with aluminum terminal 3TA225FD. 26 copperLogic.com Discount Code B30 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 CPRO-CAT-1109 www.barr-thorp.com Accessories F-series Field Installation Options Base Mounting Hardware Accessory Description Thread Type Screw Size Mounting Imperial .164-32 x 3.188 in. Individual For use with… Catalog Number Price Base Mounting Hardware MHDF11 10 MHDF21 10 Single Pole F-series For surface mounting of circuit breakers or switches. Includes pan-head screws and lockwashers Mounting hardware is not included with breaker. Imperial .164-32 x 3.188 in. Two Breakers Imperial .164-32 x 1.5 in. Individual Two Pole F-series MHDF2 10 Imperial .164-32 x 1.5 in. Individual Three Pole F-series MHDF3 10 Replacement Terminal Kits Maximum Set of Three Terminals Amp Rating Material Wire Type Wire Range For use with… Catalog Number Price Replacement for Standard Terminals (line and load side terminals supplied with breaker) CPRO-CAT-1109 100 Steel Cu / Al 14 – 1/0 AWG 2.5 – 50 mm2 F-series from 15 to 100 Amps 225 Aluminum Cu / Al 4 – 4/0 AWG 25 – 95 mm2 F-series 3TA225FD from 110 to 225 Amps Discount Code B30 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 3T100FB copperLogic.com www.barr-thorp.com 39 79 27 Application Data Time / Current Curves Time/Current Curve TM1-FLS-15A… TM1-FLS-20A… 15A 1h 2h Maximum single pole trip times at 25 °C Minimum 1 .7 .5 .3 .2 1 .7 .5 .3 .2 Maximum interrupting time TM1-FLS-30A… 25A 1h 2h Maximum Minimum 1 .7 .5 .3 .2 1 .7 .5 .3 .2 Maximum interrupting time .01 .007 .005 .003 .002 2000 3000 5000 7000 10000 .001 Interrupting rating determines end of curve 200 300 2000 3000 5000 7000 10000 500 700 1000 200 300 20 30 50 70 100 5 7 10 Interrupting rating determines end of curve CURRENT IN AMPERES Maximum Minimum .1 .07 .05 .03 .02 Maximum interrupting time .01 .007 .005 .003 .002 10 7 5 3 2 20 30 50 70 100 .1 .07 .05 .03 .02 Maximum single pole trip times at 25 °C 100 70 50 30 20 CURRENT IN AMPERES 20000 30000 50000 70000 100000 TIME IN SECONDS 1 min Maximum single pole trip times at 25 °C 100 70 50 30 20 .001 30A 1000 700 500 300 200 20000 30000 50000 70000 100000 TIME IN SECONDS 1 min 1000 700 500 300 200 10000 7000 5000 3000 2000 5 7 10 1h 2h Time/Current Curve TM1-FLS-25A… 10 7 5 3 2 2000 3000 5000 7000 10000 CURRENT IN AMPERES Time/Current Curve 10000 7000 5000 3000 2000 500 700 1000 Interrupting rating determines end of curve 200 300 .001 20000 30000 50000 70000 100000 2000 3000 5000 7000 10000 500 700 1000 200 300 CURRENT IN AMPERES Maximum Minimum .01 .007 .005 .003 .002 Interrupting rating determines end of curve 20 30 50 70 100 5 7 10 .001 10 7 5 3 2 .1 .07 .05 .03 .02 Maximum interrupting time .01 .007 .005 .003 .002 Maximum single pole trip times at 25 °C 100 70 50 30 20 20000 30000 50000 70000 100000 Maximum .1 .07 .05 .03 .02 20A 500 700 1000 10 7 5 3 2 1 min 100 70 50 30 20 For application and coordination purposes only. Based on 40°C ambient, cold start. Connected with four feet of rated wire (60°C up to 125A, 75°C above 125A) per terminal. Tested in open air with current in all poles. Single pole test data at 25°C based on NEMA procedures (AB 4-2003) for verifying performance of molded case circuit breakers. 1000 700 500 300 200 5 7 10 TIME IN SECONDS 1 min 1000 700 500 300 200 10000 7000 5000 3000 2000 20 30 50 70 100 10000 7000 5000 3000 2000 TIME IN SECONDS 1h 2h Time/Current Curve 28 copperLogic.com This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 CPRO-CAT-1109 www.barr-thorp.com Application Data Time / Current Curves Time/Current Curve TM1-FLS-35A… TM1-FLS-40A… 35A 1000 700 500 300 200 1 .7 .5 .3 .2 .1 .07 .05 .03 .02 TM1-FLS-50A… 45A 1h 2h 1 min Maximum Minimum 1 .7 .5 .3 .2 CPRO-CAT-1109 Maximum interrupting time .01 .007 .005 .003 .002 Interrupting rating determines end of curve 2000 3000 5000 7000 10000 .001 5 7 10 2000 3000 5000 7000 10000 500 700 1000 200 300 20 30 50 70 100 5 7 10 .1 .07 .05 .03 .02 Interrupting rating determines end of curve CURRENT IN AMPERES Maximum Minimum 1 .7 .5 .3 .2 Maximum interrupting time .01 .007 .005 .003 .002 .001 10 7 5 3 2 200 300 .1 .07 .05 .03 .02 Maximum single pole trip times at 25 °C 20 30 50 70 100 10 7 5 3 2 50A 100 70 50 30 20 TIME IN SECONDS 1 min TIME IN SECONDS Maximum single pole trip times at 25 °C 100 70 50 30 20 10000 7000 5000 3000 2000 1000 700 500 300 200 20000 30000 50000 70000 100000 1h 2h Time/Current Curve TM1-FLS-45A… 1000 700 500 300 200 2000 3000 5000 7000 10000 CURRENT IN AMPERES Time/Current Curve 10000 7000 5000 3000 2000 500 700 1000 200 300 Interrupting rating determines end of curve 20 30 50 70 100 .001 20000 30000 50000 70000 100000 2000 3000 5000 7000 10000 500 700 1000 200 300 CURRENT IN AMPERES Maximum interrupting time .01 .007 .005 .003 .002 Interrupting rating determines end of curve 20 30 50 70 100 5 7 10 .001 1 .7 .5 .3 .2 Maximum interrupting time .01 .007 .005 .003 .002 Maximum Minimum 20000 30000 50000 70000 100000 Minimum .1 .07 .05 .03 .02 10 7 5 3 2 CURRENT IN AMPERES 20000 30000 50000 70000 100000 Maximum Maximum single pole trip times at 25 °C 100 70 50 30 20 5 7 10 10 7 5 3 2 1 min Maximum single pole trip times at 25 °C 100 70 50 30 20 TIME IN SECONDS TIME IN SECONDS 1 min 1000 700 500 300 200 For application and coordination purposes only. Based on 40°C ambient, cold start. Connected with four feet of rated wire (60°C up to 125A, 75°C above 125A) per terminal. Tested in open air with current in all poles. Single pole test data at 25°C based on NEMA procedures (AB 4-2003) for verifying performance of molded case circuit breakers. 40A 10000 7000 5000 3000 2000 500 700 1000 10000 7000 5000 3000 2000 1h 2h 1h 2h Time/Current Curve This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 copperLogic.com www.barr-thorp.com 29 Application Data Time / Current Curves Time/Current Curve TM1-FLS-60A… TM1-FLS-70A… 60A 1h 2h 1000 700 500 300 200 Maximum single pole trip times at 25 °C 1 min Minimum 1 .7 .5 .3 .2 CURRENT IN AMPERES Time/Current Curve TM1-FLS-80A… TM1-FLS-90A… 1h 2h 80A Maximum single pole trip times at 25 °C 1 min 100 70 50 30 20 Maximum Minimum 1 .7 .5 .3 .2 CURRENT IN AMPERES Maximum Minimum 1 .7 .5 .3 .2 Maximum interrupting time .01 .007 .005 .003 .002 2000 3000 5000 7000 10000 .001 Interrupting rating determines end of curve 200 300 2000 3000 5000 7000 10000 500 700 1000 200 300 Interrupting rating determines end of curve 20 30 50 70 100 5 7 10 .001 10 7 5 3 2 .1 .07 .05 .03 .02 Maximum interrupting time .01 .007 .005 .003 .002 Maximum single pole trip times at 25 °C 20 30 50 70 100 .1 .07 .05 .03 .02 90A 100 70 50 30 20 5 7 10 10 7 5 3 2 10000 7000 5000 3000 2000 1000 700 500 300 200 TIME IN SECONDS TIME IN SECONDS 1 min 1000 700 500 300 200 20000 30000 50000 70000 100000 1h 2h Time/Current Curve 10000 7000 5000 3000 2000 2000 3000 5000 7000 10000 Interrupting rating determines end of curve 500 700 1000 .001 20000 30000 50000 70000 100000 2000 3000 5000 7000 10000 500 700 1000 200 300 CURRENT IN AMPERES Maximum interrupting time .01 .007 .005 .003 .002 Interrupting rating determines end of curve 20 30 50 70 100 5 7 10 .001 1 .7 .5 .3 .2 .1 .07 .05 .03 .02 Maximum interrupting time .01 .007 .005 .003 .002 Maximum Minimum 200 300 .1 .07 .05 .03 .02 10 7 5 3 2 20000 30000 50000 70000 100000 Maximum 500 700 1000 10 7 5 3 2 Maximum single pole trip times at 25 °C 100 70 50 30 20 CURRENT IN AMPERES 20000 30000 50000 70000 100000 100 70 50 30 20 5 7 10 TIME IN SECONDS 1 min 1000 700 500 300 200 For application and coordination purposes only. Based on 40°C ambient, cold start. Connected with four feet of rated wire (60°C up to 125A, 75°C above 125A) per terminal. Tested in open air with current in all poles. Single pole test data at 25°C based on NEMA procedures (AB 4-2003) for verifying performance of molded case circuit breakers. 70A 10000 7000 5000 3000 2000 20 30 50 70 100 10000 7000 5000 3000 2000 TIME IN SECONDS 1h 2h Time/Current Curve 30 copperLogic.com This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 CPRO-CAT-1109 www.barr-thorp.com Application Data Time / Current Curves Time/Current Curve TM1-FLS-100A… TM1-FLS-110A… 100A 1h 2h 1000 700 500 300 200 Maximum single pole trip times at 25 °C 1 min .1 .07 .05 .03 .02 CURRENT IN AMPERES Time/Current Curve TM1-FLS-125A… TM1-FLS-150A… 1h 2h Maximum Minimum 1 .7 .5 .3 .2 .1 .07 .05 .03 .02 CURRENT IN AMPERES CPRO-CAT-1109 Maximum Minimum 1 .7 .5 .3 .2 .1 .07 .05 .03 .02 Maximum interrupting time .01 .007 .005 .003 .002 .001 5 7 10 2000 3000 5000 7000 10000 500 700 1000 200 300 Interrupting rating determines end of curve 20 30 50 70 100 5 7 10 10 7 5 3 2 Maximum interrupting time .01 .007 .005 .003 .002 .001 100 70 50 30 20 Interrupting rating determines end of curve 200 300 1 min 100 70 50 30 20 Maximum single pole trip times at 25 °C 20 30 50 70 100 Maximum single pole trip times at 25 °C 10 7 5 3 2 150A 1000 700 500 300 200 TIME IN SECONDS TIME IN SECONDS 1 min 1000 700 500 300 200 10000 7000 5000 3000 2000 2000 3000 5000 7000 10000 125A 20000 30000 50000 70000 100000 1h 2h Time/Current Curve 10000 7000 5000 3000 2000 2000 3000 5000 7000 10000 Interrupting rating determines end of curve 500 700 1000 .001 20000 30000 50000 70000 100000 2000 3000 5000 7000 10000 500 700 1000 200 300 CURRENT IN AMPERES Maximum interrupting time .01 .007 .005 .003 .002 Interrupting rating determines end of curve 20 30 50 70 100 5 7 10 1 .7 .5 .3 .2 Maximum interrupting time .01 .007 .005 .003 .002 Maximum Minimum 20000 30000 50000 70000 100000 Minimum 1 .7 .5 .3 .2 .001 10 7 5 3 2 CURRENT IN AMPERES 20000 30000 50000 70000 100000 Maximum .1 .07 .05 .03 .02 100 70 50 30 20 200 300 10 7 5 3 2 Maximum single pole trip times at 25 °C 500 700 1000 100 70 50 30 20 5 7 10 TIME IN SECONDS 1 min 1000 700 500 300 200 For application and coordination purposes only. Based on 40°C ambient, cold start. Connected with four feet of rated wire (60°C up to 125A, 75°C above 125A) per terminal. Tested in open air with current in all poles. Single pole test data at 25°C based on NEMA procedures (AB 4-2003) for verifying performance of molded case circuit breakers. 110A 10000 7000 5000 3000 2000 20 30 50 70 100 10000 7000 5000 3000 2000 TIME IN SECONDS 1h 2h Time/Current Curve This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 copperLogic.com www.barr-thorp.com 31 Application Data Time / Current Curves Time/Current Curve TM(2)(3)-FLS-15A…, TM(2)(3)-FMS-15A… TM(2)(3)-FHS-15A… 15A 10000 7000 5000 3000 2000 1h 2h 15A CURRENT IN AMPERES TM(2)(3)-FHS-20A… 20A 1h 2h 20A 1000 700 500 300 200 2000 3000 5000 7000 10000 500 700 1000 200 300 20 30 50 70 100 5 7 10 Interrupting rating determines end of curve CURRENT IN AMPERES Maximum .1 .07 .05 .03 .02 Maximum interrupting time .01 .007 .005 .003 .002 .001 200000 20000 30000 50000 70000 100000 10000 Minimum .01 .007 .005 .003 .002 See Inset for end of curve CURRENT IN AMPERES 20000 30000 50000 70000 100000 .01 .007 .005 .003 .002 240V 2000 3000 5000 7000 10000 Maximum interrupting time 480V 500 700 1000 .1 .07 .05 .03 .02 1 .7 .5 .3 .2 .02 600V 10 7 5 3 2 200 300 1 .7 .5 .3 .2 Maximum single pole trip times at 25 °C 100 70 50 30 20 20 30 50 70 100 Maximum TIME IN SECONDS Minimum 1 min Maximum single pole trip times at 25 °C 100 70 50 30 20 20000 30000 50000 70000 100000 TIME IN SECONDS 1 min 1000 700 500 300 200 10000 7000 5000 3000 2000 5 7 10 1h 2h Time/Current Curve 20000 30000 50000 70000 100000 See Inset for end of curve TM(2)(3)-FLS-20A…, TM(2)(3)-FMS-20A… .001 200000 Maximum interrupting time Time/Current Curve 10000 7000 5000 3000 2000 .01 .007 .005 .003 .002 Maximum 2000 3000 5000 7000 10000 .001 5 7 10 2000 3000 5000 7000 10000 500 700 1000 200 300 20 30 50 70 100 5 7 10 CURRENT IN AMPERES Minimum .01 .007 .005 .003 .002 Interrupting rating determines end of curve .001 240V .1 .07 .05 .03 .02 Maximum interrupting time .01 .007 .005 .003 .002 1 .7 .5 .3 .2 500 700 1000 .1 .07 .05 .03 .02 480V 200 300 1 .7 .5 .3 .2 .02 600V 10 7 5 3 2 20000 30000 50000 70000 100000 TIME IN SECONDS Minimum Maximum single pole trip times at 25 °C 100 70 50 30 20 10000 1 min Maximum 20000 30000 50000 70000 100000 1 min TIME IN SECONDS Maximum single pole trip times at 25 °C 100 70 50 30 20 10 7 5 3 2 For application and coordination purposes only. Based on 40°C ambient, cold start. Connected with four feet of rated wire (60°C up to 125A, 75°C above 125A) per terminal. Tested in open air with current in all poles. Single pole test data at 25°C based on NEMA procedures (AB 4-2003) for verifying performance of molded case circuit breakers. 1000 700 500 300 200 1000 700 500 300 200 10 7 5 3 2 10000 7000 5000 3000 2000 20 30 50 70 100 1h 2h Time/Current Curve 32 copperLogic.com This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 CPRO-CAT-1109 www.barr-thorp.com Application Data Time / Current Curves Time/Current Curve TM(2)(3)-FLS-25A…, TM(2)(3)-FMS-25A… TM(2)(3)-FHS-25A… Maximum interrupting time TM(2)(3)-FHS-30A… CURRENT IN AMPERES CPRO-CAT-1109 20000 30000 50000 70000 100000 Maximum interrupting time See Inset for end of curve 2000 3000 5000 7000 10000 .001 200000 20000 30000 50000 70000 100000 10000 Maximum .01 .007 .005 .003 .002 5 7 10 2000 3000 5000 7000 10000 500 700 1000 200 300 20 30 50 70 100 5 7 10 .001 Interrupting rating determines end of curve .01 .007 .005 .003 .002 240V Minimum .1 .07 .05 .03 .02 Maximum interrupting time .01 .007 .005 .003 .002 480V 20 30 50 70 100 .1 .07 .05 .03 .02 1 .7 .5 .3 .2 .02 600V 10 7 5 3 2 Maximum 1 .7 .5 .3 .2 Maximum single pole trip times at 25 °C 100 70 50 30 20 500 700 1000 1h 2h 1 min Maximum single pole trip times at 25 °C Minimum 30A 1000 700 500 300 200 TIME IN SECONDS 1 min TIME IN SECONDS 10 7 5 3 2 10000 7000 5000 3000 2000 200 300 30A 20000 30000 50000 70000 100000 1h 2h Time/Current Curve 100 70 50 30 20 2000 3000 5000 7000 10000 CURRENT IN AMPERES TM(2)(3)-FLS-30A…, TM(2)(3)-FMS-30A… 1000 700 500 300 200 500 700 1000 See Inset for end of curve Time/Current Curve 10000 7000 5000 3000 2000 200000 Maximum 200 300 .001 5 7 10 2000 3000 5000 7000 10000 500 700 1000 200 300 20 30 50 70 100 5 7 10 CURRENT IN AMPERES Minimum .01 .007 .005 .003 .002 Interrupting rating determines end of curve .01 .007 .005 .003 .002 240V .1 .07 .05 .03 .02 Maximum interrupting time .01 .007 .005 .003 .002 .001 1 .7 .5 .3 .2 20 30 50 70 100 .1 .07 .05 .03 .02 480V For application and coordination purposes only. Based on 40°C ambient, cold start. Connected with four feet of rated wire (60°C up to 125A, 75°C above 125A) per terminal. Tested in open air with current in all poles. Single pole test data at 25°C based on NEMA procedures (AB 4-2003) for verifying performance of molded case circuit breakers. CURRENT IN AMPERES 20000 30000 50000 70000 100000 TIME IN SECONDS 1 .7 .5 .3 .2 .02 600V 10 7 5 3 2 Maximum Minimum Maximum single pole trip times at 25 °C 100 70 50 30 20 20000 30000 50000 70000 100000 1 min Maximum single pole trip times at 25 °C 100 70 50 30 20 10 7 5 3 2 25A 1000 700 500 300 200 20000 30000 50000 70000 100000 TIME IN SECONDS 1 min 1000 700 500 300 200 10000 7000 5000 3000 2000 10000 25A 10000 7000 5000 3000 2000 1h 2h 1h 2h Time/Current Curve This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 copperLogic.com www.barr-thorp.com 33 Application Data Time / Current Curves Time/Current Curve TM(2)(3)-FLS-35A…, TM(2)(3)-FMS-35A… TM(2)(3)-FHS-35A… TM(2)(3)-FHS-40A… .1 .07 .05 .03 .02 Maximum interrupting time .01 .007 .005 .003 .002 2000 3000 5000 7000 10000 500 700 1000 200 300 20 30 50 70 100 5 7 10 .001 Interrupting rating determines end of curve CURRENT IN AMPERES Minimum 20000 30000 50000 70000 100000 240V 20000 30000 50000 70000 100000 Maximum .1 .07 .05 .03 .02 Maximum interrupting time .01 .007 .005 .003 .002 .001 .01 .007 .005 .003 .002 200000 480V 10000 1 .7 .5 .3 .2 .02 600V 10 7 5 3 2 See Inset for end of curve 20 30 50 70 100 TIME IN SECONDS 1 .7 .5 .3 .2 Maximum single pole trip times at 25 °C 100 70 50 30 20 5 7 10 1 min Maximum Minimum 20000 30000 50000 70000 100000 1 min TIME IN SECONDS 10 7 5 3 2 40A 1000 700 500 300 200 Maximum single pole trip times at 25 °C 100 70 50 30 20 10000 7000 5000 3000 2000 200 300 1h 2h 40A 1000 700 500 300 200 200000 10000 Time/Current Curve TM(2)(3)-FLS-40A…, TM(2)(3)-FMS-40A… 1h 2h Time/Current Curve 10000 7000 5000 3000 2000 2000 3000 5000 7000 10000 CURRENT IN AMPERES 2000 3000 5000 7000 10000 CURRENT IN AMPERES .001 See Inset for end of curve 500 700 1000 2000 3000 5000 7000 10000 500 700 1000 200 300 20 30 50 70 100 5 7 10 .001 Maximum interrupting time .01 .007 .005 .003 .002 Interrupting rating determines end of curve .01 .007 .005 .003 .002 Maximum .1 .07 .05 .03 .02 Maximum interrupting time .01 .007 .005 .003 .002 240V Minimum 500 700 1000 .1 .07 .05 .03 .02 1 .7 .5 .3 .2 200 300 1 .7 .5 .3 .2 480V 20 30 50 70 100 Minimum .02 600V 10 7 5 3 2 CURRENT IN AMPERES 20000 30000 50000 70000 100000 1h 2h Maximum Maximum single pole trip times at 25 °C 100 70 50 30 20 5 7 10 10 7 5 3 2 1 min Maximum single pole trip times at 25 °C 100 70 50 30 20 For application and coordination purposes only. Based on 40°C ambient, cold start. Connected with four feet of rated wire (60°C up to 125A, 75°C above 125A) per terminal. Tested in open air with current in all poles. Single pole test data at 25°C based on NEMA procedures (AB 4-2003) for verifying performance of molded case circuit breakers. 35A 1000 700 500 300 200 TIME IN SECONDS TIME IN SECONDS 1 min 1000 700 500 300 200 10000 7000 5000 3000 2000 20000 30000 50000 70000 100000 35A 10000 7000 5000 3000 2000 20000 30000 50000 70000 100000 1h 2h Time/Current Curve 34 copperLogic.com This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 CPRO-CAT-1109 www.barr-thorp.com Application Data Time / Current Curves Time/Current Curve TM(2)(3)-FLS-45A…, TM(2)(3)-FMS-45A… TM(2)(3)-FHS-45A… .01 .007 .005 .003 .002 Time/Current Curve TM(2)(3)-FLS-50A…, TM(2)(3)-FMS-50A… TM(2)(3)-FHS-50A… 1h 2h .1 .07 .05 .03 .02 CURRENT IN AMPERES CPRO-CAT-1109 200000 20000 30000 50000 70000 100000 480V Maximum Maximum interrupting time .01 .007 .005 .003 .002 .001 .01 .007 .005 .003 .002 240V Minimum .1 .07 .05 .03 .02 5 7 10 2000 3000 5000 7000 10000 500 700 1000 200 300 20 30 50 70 100 Interrupting rating determines end of curve .02 600V 20000 30000 50000 70000 100000 1 .7 .5 .3 .2 Maximum interrupting time .01 .007 .005 .003 .002 5 7 10 10 7 5 3 2 See Inset for end of curve 200 300 1 min 1 .7 .5 .3 .2 .001 100 70 50 30 20 Maximum Minimum Maximum single pole trip times at 25 °C 20 30 50 70 100 Maximum single pole trip times at 25 °C 100 70 50 30 20 10 7 5 3 2 50A 1000 700 500 300 200 TIME IN SECONDS TIME IN SECONDS 1 min 1000 700 500 300 200 10000 7000 5000 3000 2000 200000 50A 20000 30000 50000 70000 100000 1h 2h Time/Current Curve 10000 7000 5000 3000 2000 2000 3000 5000 7000 10000 CURRENT IN AMPERES 2000 3000 5000 7000 10000 CURRENT IN AMPERES .001 See Inset for end of curve 500 700 1000 2000 3000 5000 7000 10000 500 700 1000 200 300 Interrupting rating determines end of curve 20 30 50 70 100 5 7 10 .001 Maximum interrupting time 200 300 .01 .007 .005 .003 .002 Maximum .1 .07 .05 .03 .02 Maximum interrupting time .01 .007 .005 .003 .002 240V Minimum 500 700 1000 .1 .07 .05 .03 .02 1 .7 .5 .3 .2 20 30 50 70 100 1 .7 .5 .3 .2 480V 10000 1 min Minimum .02 600V 10 7 5 3 2 Maximum 5 7 10 10 7 5 3 2 Maximum single pole trip times at 25 °C 100 70 50 30 20 For application and coordination purposes only. Based on 40°C ambient, cold start. Connected with four feet of rated wire (60°C up to 125A, 75°C above 125A) per terminal. Tested in open air with current in all poles. Single pole test data at 25°C based on NEMA procedures (AB 4-2003) for verifying performance of molded case circuit breakers. CURRENT IN AMPERES 20000 30000 50000 70000 100000 1h 2h Maximum single pole trip times at 25 °C 100 70 50 30 20 45A 1000 700 500 300 200 TIME IN SECONDS TIME IN SECONDS 1 min 1000 700 500 300 200 10000 7000 5000 3000 2000 20000 30000 50000 70000 100000 45A 10000 7000 5000 3000 2000 20000 30000 50000 70000 100000 1h 2h Time/Current Curve This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 copperLogic.com www.barr-thorp.com 35 Application Data Time / Current Curves Time/Current Curve TM(2)(3)-FLS-60A…, TM(2)(3)-FMS-60A… TM(2)(3)-FHS-60A… CURRENT IN AMPERES Time/Current Curve TM(2)(3)-FLS-70A…, TM(2)(3)-FMS-70A… TM(2)(3)-FHS-70A… .1 .07 .05 .03 .02 Maximum interrupting time .01 .007 .005 .003 .002 2000 3000 5000 7000 10000 500 700 1000 200 300 20 30 50 70 100 5 7 10 .001 Interrupting rating determines end of curve CURRENT IN AMPERES 10 7 5 3 2 1 .7 .5 .3 .2 Minimum 200000 Maximum .1 .07 .05 .03 .02 Maximum interrupting time 600V .01 .007 .005 .003 .002 .001 480V 240V 20000 30000 50000 70000 100000 1 .7 .5 .3 .2 100 70 50 30 20 200 300 500 700 1000 1 min Maximum Minimum Maximum single pole trip times at 25 °C 50 70 100 Maximum single pole trip times at 25 °C 100 70 50 30 20 10 7 5 3 2 70A 1000 700 500 300 200 TIME IN SECONDS TIME IN SECONDS 1 min 1000 700 500 300 200 10000 7000 5000 3000 2000 2000 3000 1h 2h 70A 20000 30000 50000 70000 100000 1h 2h Time/Current Curve 10000 7000 5000 3000 2000 2000 3000 5000 7000 10000 See Inset for end of curve .001 20000 30000 50000 70000 100000 2000 3000 5000 7000 10000 500 700 1000 200 300 20 30 50 70 100 5 7 10 .01 .007 .005 .003 .002 Interrupting rating determines end of curve CURRENT IN AMPERES Maximum interrupting time 500 700 1000 .01 .007 .005 .003 .002 .001 .1 .07 .05 .03 .02 Maximum interrupting time .01 .007 .005 .003 .002 Maximum 200 300 .1 .07 .05 .03 .02 240V Minimum 1 .7 .5 .3 .2 5000 7000 10000 1 .7 .5 .3 .2 480V 20 30 50 70 100 Minimum .02 600V 10 7 5 3 2 20000 30000 50000 70000 100000 1 min Maximum Maximum single pole trip times at 25 °C 100 70 50 30 20 20000 30000 50000 70000 100000 Maximum single pole trip times at 25 °C 100 70 50 30 20 10 7 5 3 2 60A 10000 7000 5000 3000 2000 1000 700 500 300 200 TIME IN SECONDS TIME IN SECONDS 1 min 1000 700 500 300 200 For application and coordination purposes only. Based on 40°C ambient, cold start. Connected with four feet of rated wire (60°C up to 125A, 75°C above 125A) per terminal. Tested in open air with current in all poles. Single pole test data at 25°C based on NEMA procedures (AB 4-2003) for verifying performance of molded case circuit breakers. CURRENT IN AMPERES 200000 300000 500000 700000 1000000 60A 5 7 10 10000 7000 5000 3000 2000 1h 2h 1h 2h Time/Current Curve 36 copperLogic.com This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 CPRO-CAT-1109 www.barr-thorp.com Application Data Time / Current Curves Time/Current Curve TM(2)(3)-FLS-80A…, TM(2)(3)-FMS-80A… TM(2)(3)-FHS-80A… 1 min 600V 480V TM(2)(3)-FHS-90A… CPRO-CAT-1109 50 70 100 2000 3000 5000 7000 10000 500 700 1000 200 300 CURRENT IN AMPERES Maximum interrupting time 600V .01 .007 .005 .003 .002 .001 20 30 50 70 100 5 7 10 Interrupting rating determines end of curve Maximum .1 .07 .05 .03 .02 Maximum interrupting time .01 .007 .005 .003 .002 Minimum 480V 240V 200 300 500 700 1000 .1 .07 .05 .03 .02 1 .7 .5 .3 .2 20000 30000 50000 70000 100000 1h 2h 1 min 1 .7 .5 .3 .2 .001 10 7 5 3 2 Maximum Minimum Maximum single pole trip times at 25 °C 100 70 50 30 20 TIME IN SECONDS 1 min TIME IN SECONDS 10 7 5 3 2 90A 1000 700 500 300 200 Maximum single pole trip times at 25 °C 100 70 50 30 20 10000 7000 5000 3000 2000 2000 3000 90A 20000 30000 50000 70000 100000 1h 2h Time/Current Curve TM(2)(3)-FLS-90A…, TM(2)(3)-FMS-90A… 1000 700 500 300 200 20000 30000 50000 70000 100000 CURRENT IN AMPERES Time/Current Curve 10000 7000 5000 3000 2000 5000 7000 10000 50 70 100 2000 3000 240V .001 20000 30000 50000 70000 100000 2000 3000 5000 7000 10000 500 700 1000 200 300 20 30 50 70 100 5 7 10 Maximum interrupting time .01 .007 .005 .003 .002 Interrupting rating determines end of curve CURRENT IN AMPERES Maximum .1 .07 .05 .03 .02 Maximum interrupting time .01 .007 .005 .003 .002 Minimum 5000 7000 10000 .1 .07 .05 .03 .02 1 .7 .5 .3 .2 200 300 500 700 1000 1 .7 .5 .3 .2 .001 10 7 5 3 2 Maximum Minimum Maximum single pole trip times at 25 °C 100 70 50 30 20 200000 300000 500000 700000 1000000 Maximum single pole trip times at 25 °C 100 70 50 30 20 10 7 5 3 2 80A 1000 700 500 300 200 TIME IN SECONDS TIME IN SECONDS 1 min 1000 700 500 300 200 10000 7000 5000 3000 2000 For application and coordination purposes only. Based on 40°C ambient, cold start. Connected with four feet of rated wire (60°C up to 125A, 75°C above 125A) per terminal. Tested in open air with current in all poles. Single pole test data at 25°C based on NEMA procedures (AB 4-2003) for verifying performance of molded case circuit breakers. CURRENT IN AMPERES 200000 300000 500000 700000 1000000 80A 10000 7000 5000 3000 2000 1h 2h 1h 2h Time/Current Curve This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 copperLogic.com www.barr-thorp.com 37 Application Data Time / Current Curves Time/Current Curve TM(2)(3)-FLS-100A…, TM(2)(3)-FMS-100A… TM(2)(3)-FHS-100A… 1 min Maximum 600V 480V TM(2)(3)-FHS-110A… Maximum interrupting time .01 .007 .005 .003 .002 2000 3000 5000 7000 10000 500 700 1000 200 300 20 30 50 70 100 5 7 10 .001 Interrupting rating determines end of curve CURRENT IN AMPERES 10 7 5 3 2 1 .7 .5 .3 .2 Minimum Maximum .1 .07 .05 .03 .02 Maximum interrupting time 600V .01 .007 .005 .003 .002 .001 480V 240V 20000 30000 50000 70000 100000 .1 .07 .05 .03 .02 100 70 50 30 20 200 300 500 700 1000 1 .7 .5 .3 .2 Maximum single pole trip times at 25 °C 50 70 100 1 min Maximum TIME IN SECONDS 1 min TIME IN SECONDS Maximum single pole trip times at 25 °C Minimum 110A 1000 700 500 300 200 100 70 50 30 20 10 7 5 3 2 10000 7000 5000 3000 2000 2000 3000 1h 2h 110A 20000 30000 50000 70000 100000 1h 2h Time/Current Curve TM(2)(3)-FLS-110A…, TM(2)(3)-FMS-110A… 1000 700 500 300 200 20000 30000 50000 70000 100000 CURRENT IN AMPERES Time/Current Curve 10000 7000 5000 3000 2000 5000 7000 10000 240V .001 20000 30000 50000 70000 100000 2000 3000 5000 7000 10000 500 700 1000 200 300 CURRENT IN AMPERES Maximum interrupting time .01 .007 .005 .003 .002 Interrupting rating determines end of curve 20 30 50 70 100 5 7 10 .001 Maximum .1 .07 .05 .03 .02 Maximum interrupting time .01 .007 .005 .003 .002 Minimum 5000 7000 10000 .1 .07 .05 .03 .02 1 .7 .5 .3 .2 2000 3000 1 .7 .5 .3 .2 10 7 5 3 2 200 300 500 700 1000 Minimum Maximum single pole trip times at 25 °C 100 70 50 30 20 200000 300000 500000 700000 1000000 Maximum single pole trip times at 25 °C 100 70 50 30 20 10 7 5 3 2 100A 1000 700 500 300 200 TIME IN SECONDS TIME IN SECONDS 1 min 1000 700 500 300 200 10000 7000 5000 3000 2000 For application and coordination purposes only. Based on 40°C ambient, cold start. Connected with four feet of rated wire (60°C up to 125A, 75°C above 125A) per terminal. Tested in open air with current in all poles. Single pole test data at 25°C based on NEMA procedures (AB 4-2003) for verifying performance of molded case circuit breakers. CURRENT IN AMPERES 200000 300000 500000 700000 1000000 100A 50 70 100 10000 7000 5000 3000 2000 1h 2h 1h 2h Time/Current Curve 38 copperLogic.com This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 CPRO-CAT-1109 www.barr-thorp.com Application Data Time / Current Curves Time/Current Curve TM(2)(3)-FLS-125A…, TM(2)(3)-FMS-125A… TM(2)(3)-FHS-125A… 1 .7 .5 .3 .2 600V 480V TM(2)(3)-FHS-150A… CURRENT IN AMPERES CPRO-CAT-1109 Maximum Maximum interrupting time 600V .01 .007 .005 .003 .002 480V 240V 200 300 500 700 1000 .001 50 70 100 2000 3000 5000 7000 10000 500 700 1000 200 300 20 30 50 70 100 Interrupting rating determines end of curve Minimum .1 .07 .05 .03 .02 Maximum interrupting time .01 .007 .005 .003 .002 5 7 10 1 .7 .5 .3 .2 20000 30000 50000 70000 100000 1h 2h 1 min .1 .07 .05 .03 .02 .001 10 7 5 3 2 Maximum 1 .7 .5 .3 .2 Maximum single pole trip times at 25 °C 100 70 50 30 20 TIME IN SECONDS 1 min TIME IN SECONDS 100 70 50 30 20 Minimum 150A 1000 700 500 300 200 Maximum single pole trip times at 25 °C 10 7 5 3 2 10000 7000 5000 3000 2000 2000 3000 150A 20000 30000 50000 70000 100000 1h 2h Time/Current Curve TM(2)(3)-FLS-150A…, TM(2)(3)-FMS-150A… 1000 700 500 300 200 20000 30000 50000 70000 100000 CURRENT IN AMPERES Time/Current Curve 10000 7000 5000 3000 2000 5000 7000 10000 50 70 100 2000 3000 240V .001 20000 30000 50000 70000 100000 2000 3000 5000 7000 10000 500 700 1000 200 300 20 30 50 70 100 Maximum interrupting time .01 .007 .005 .003 .002 Interrupting rating determines end of curve CURRENT IN AMPERES Maximum .1 .07 .05 .03 .02 Maximum interrupting time .01 .007 .005 .003 .002 Minimum 5000 7000 10000 .1 .07 .05 .03 .02 5 7 10 10 7 5 3 2 200 300 500 700 1000 1 .7 .5 .3 .2 .001 100 70 50 30 20 Maximum Minimum Maximum single pole trip times at 25 °C 200000 300000 500000 700000 1000000 1 min 100 70 50 30 20 10 7 5 3 2 125A 1000 700 500 300 200 Maximum single pole trip times at 25 °C TIME IN SECONDS TIME IN SECONDS 1 min 1000 700 500 300 200 10000 7000 5000 3000 2000 For application and coordination purposes only. Based on 40°C ambient, cold start. Connected with four feet of rated wire (60°C up to 125A, 75°C above 125A) per terminal. Tested in open air with current in all poles. Single pole test data at 25°C based on NEMA procedures (AB 4-2003) for verifying performance of molded case circuit breakers. CURRENT IN AMPERES 200000 300000 500000 700000 1000000 125A 10000 7000 5000 3000 2000 1h 2h 1h 2h Time/Current Curve This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 copperLogic.com www.barr-thorp.com 39 Application Data Time / Current Curves Time/Current Curve TM(2)(3)-F(L)(M)S-(175)(200)(225)A… TM(2)(3)-FHS-(175)(200)(225)A… Minimum 175 A 200 A 225 A Drawn for In=200A; for In π 200A, the end points in this region are displaced along the current axis by a factor (200A/In) 200 300 500 700 1000 50 70 100 20 30 2 3 5 7 10 0.5 0.7 1 .001 CURRENT IN MULTIPLES OF In Minimum 1 .7 .5 .3 .2 175 A 200 A 225 A .1 .07 .05 .03 .02 Maximum interrupting time .01 .007 .005 .003 .002 Maximum Maximum interrupting time Drawn for In=200A; for In π 200A, the end points in this region are displaced along the current axis by a factor (200A/In) .01 .007 .005 .003 .002 .001 20 30 .1 .07 .05 .03 .02 10 7 5 3 2 2 3 5 7 10 1 .7 .5 .3 .2 100 70 50 30 20 2000 3000 5000 7000 10000 Maximum Maximum single pole trip times at 25 °C 200 300 500 700 1000 1 min 100 70 50 30 20 10 7 5 3 2 1000 700 500 300 200 Maximum single pole trip times at 25 °C For application and coordination purposes only. Based on 40°C ambient, cold start. Connected with four feet of rated wire (60°C up to 125A, 75°C above 125A) per terminal. Tested in open air with current in all poles. Single pole test data at 25°C based on NEMA procedures (AB 4-2003) for verifying performance of molded case circuit breakers. 175 – 225A 0.5 0.7 1 TIME IN SECONDS 1 min 1000 700 500 300 200 10000 7000 5000 3000 2000 50 70 100 1h 2h 175 – 225A TIME IN SECONDS 10000 7000 5000 3000 2000 2000 3000 5000 7000 10000 1h 2h Time/Current Curve CURRENT IN MULTIPLES OF In 40 copperLogic.com This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 CPRO-CAT-1109 www.barr-thorp.com Technical Data cPRO F-series cPRO F-series Circuit Breakers cPRO F-series Molded Case Switches General Standards Dimensions (W x H x D) Single pole Two pole Three pole Weight Single pole Two pole Three pole Mounting …-FL(S)(C)-… CS(2)(3)-FLC-… [mm] [mm] [mm] 35 x 152 x 86 70 x 152 x 86 105 x 152 x 86 35 x 152 x 86 70 x 152 x 86 105 x 152 x 86 35 x 152 x 86 70 x 152 x 86 105 x 152 x 86 [kg] [kg] [kg] 0.91 1.36 2.04 0.91 1.36 2.04 0.91 1.36 2.04 90 90 [A] [A] 90 90 110 – 225 Amps …-FHS-… UL 489, CSA C22.2 No. 5 Maximum rated current Single pole Two and Three pole Rated operational voltage NEMA Permissible ambient temperature DC Interrupting Rating NEMA Time constant T = 8 rms 1 conducting path 2 conducting paths in series AC Interrupting Rating NEMA, Single pole breakers 277 V AC 347 V AC 125 V DC NEMA, Two- and Three- pole breakers 240 V AC 480 V AC 600 V AC 250 V DC Endurance (operating cycles) Maximum switching frequency Main Conductor Terminal Capacities Terminal type Solid or stranded 15 – 20 Amps 25 – 100 Amps 110 – 225 Amps Tightening torque for box terminals 15 – 20 Amps 25 – 100 Amps …-FM(S)(C)-… CS(2)(3)-FMC-… 150 225 30 225 30 225 600 0 … 40 °C / 32 … 104 °F 600 0 … 40 °C / 32 … 104 °F 600 0 … 40 °C / 32 … 104 °F [kA] [kA] 10 22 10 22 10 22 [kA] [kA] [kA] 35 18 10 65 25 ➊ 10 – 30 ➊ 10 ➊ [kA] [kA] [kA] [kA] 65 35 18 10 10000 300 100 65 25 22 10000 300 200 100 35 22 10000 300 box terminals box terminals box terminals [AWG] [AWG] [AWG] #14 – #10 #14 – #1/0 #4 – #4/0 #14 – #10 #14 – #1/0 #4 – #4/0 #14 – #10 #14 – #1/0 #4 – #4/0 [lbs-in] [lbs-in] 35 #14 – #10 AWG: 35; #8 AWG: 40; #6 – #4 AWG: 45; #3 – #1/0 AWG: 50 120 35 #14 – #10 AWG: 35; #8 AWG: 40; #6 – #4 AWG: 45; #3 – #1/0 AWG: 50 120 35 #14 – #10 AWG: 35; #8 AWG: 40; #6 – #4 AWG: 45; #3 – #1/0 AWG: 50 120 [V AC] [°C / °F] 250 V DC 250 V DC [per hour] [lbs-in] ➊ CSA only; not UL listed. CPRO-CAT-1109 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 copperLogic.com www.barr-thorp.com 41 Technical Data cPRO F-series cPRO F-series Circuit Breakers cPRO F-series Molded Case Switches Auxiliary Switches Maximum rated voltage AC DC Rated operational current - AC 600V Rated operational current - DC 125V 250V Undervoltage Releases Response voltage - AC, 50/60 Hz 12V Dropout Min Dropout Max Pickup Max 24V Dropout Min Dropout Max Pickup Max 48 – 60V Dropout Min Dropout Max Pickup Max 110 – 127V Dropout Min Dropout Max Pickup Max 208 – 240V Dropout Min Dropout Max Pickup Max 380 – 480V Dropout Min Dropout Max Pickup Max 525 – 600V Dropout Min Dropout Max Pickup Max Power consumption - AC, 50/60 Hz 12V 24V 48V 60V 110V 120V 127V 208V 220V 240V 380V 415V 440V 480V 525V 550V 600V …-FL(S)(C)-… CS(2)(3)-FLC-… …-FM(S)(C)-… CS(2)(3)-FMC-… …-FHS-… [V] [V] 600 250 600 250 600 250 [A] 6 6 6 [A] [A] 0.5 0.25 0.5 0.25 0.5 0.25 [V] [V] [V] 4.2 6.3 7.6 4.2 6.3 7.6 4.2 6.3 7.6 [V] [V] [V] 8.4 16.8 20.4 8.4 16.8 20.4 8.4 16.8 20.4 [V] [V] [V] 21.0 33.6 40.8 21.0 33.6 40.8 21.0 33.6 40.8 [V] [V] [V] 44.5 77.0 93.5 44.5 77.0 93.5 44.5 77.0 93.5 [V] [V] [V] 84.0 145.6 176.8 84.0 145.6 176.8 84.0 145.6 176.8 [V] [V] [V] 168.0 266.0 323.0 168.0 266.0 323.0 168.0 266.0 323.0 [V] [V] [V] 210.0 367.0 446.0 210.0 367.0 446.0 210.0 367.0 446.0 [VA] [VA] [VA] [VA] [VA] [VA] [VA] [VA] [VA] [VA] [VA] [VA] [VA] [VA] [VA] [VA] [VA] 1.3 / 2.5 1.4 1.2 1.9 1.3 1.5 1.7 2.2 2.4 2.9 2.9 3.5 3.9 4.6 4.3 4.8 5.8 1.3 / 2.5 1.4 1.2 1.9 1.3 1.5 1.7 2.2 2.4 2.9 2.9 3.5 3.9 4.6 4.3 4.8 5.8 1.3 / 2.5 1.4 1.2 1.9 1.3 1.5 1.7 2.2 2.4 2.9 2.9 3.5 3.9 4.6 4.3 4.8 5.8 42 copperLogic.com This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 CPRO-CAT-1109 www.barr-thorp.com Technical Data cPRO F-series cPRO F-series Circuit Breakers cPRO F-series Molded Case Switches Undervoltage Releases (continued) Response voltage - DC 12V Dropout Min Dropout Max Pickup Max 24V Dropout Min Dropout Max Pickup Max 48 – 60V Dropout Min Dropout Max Pickup Max 110 – 125V Dropout Min Dropout Max Pickup Max 220 – 250V Dropout Min Dropout Max Pickup Max Power consumption - DC 12V 24V 48V 60V 110V 120V 125V 220V 250V Shunt Trips Minimum operating voltage - AC, 50/60 Hz 12 – 24V 48 – 127V 208 – 380V 415 – 600V Power consumption - AC, 50/60 Hz 12V 24V 48V 60V 110V 120V 127V 208V 220V 240V 380V 415V 440V 480V 525V 550V 600V CPRO-CAT-1109 …-FL(S)(C)-… CS(2)(3)-FLC-… …-FM(S)(C)-… CS(2)(3)-FMC-… …-FHS-… [V] [V] [V] 4.2 8.4 10.2 4.2 8.4 10.2 4.2 8.4 10.2 [V] [V] [V] 8.4 16.8 20.4 8.4 16.8 20.4 8.4 16.8 20.4 [V] [V] [V] 21.0 33.6 40.8 21.0 33.6 40.8 21.0 33.6 40.8 [V] [V] [V] 44.5 77.0 93.5 44.5 77.0 93.5 44.5 77.0 93.5 [V] [V] [V] 87.5 154.0 187.0 87.5 154.0 187.0 87.5 154.0 187.0 [VA] [VA] [VA] [VA] [VA] [VA] [VA] [VA] [VA] 2.8 1.6 1.3 2.0 1.5 1.7 1.9 2.6 3.4 2.8 1.6 1.3 2.0 1.5 1.7 1.9 2.6 3.4 2.8 1.6 1.3 2.0 1.5 1.7 1.9 2.6 3.4 [V] [V] [V] [V] 6.75 36 156 300 6.75 36 156 300 6.75 36 156 300 [VA] [VA] [VA] [VA] [VA] [VA] [VA] [VA] [VA] [VA] [VA] [VA] [VA] [VA] [VA] [VA] [VA] 75 300 92 140 480 570 640 180 200 240 610 130 330 380 450 530 590 75 300 92 140 480 570 640 180 200 240 610 130 330 380 450 530 590 75 300 92 140 480 570 640 180 200 240 610 130 330 380 450 530 590 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 copperLogic.com www.barr-thorp.com 43 Technical Data cPRO F-series cPRO F-series Circuit Breakers cPRO F-series Molded Case Switches Shunt Trips (continued) Minimum operating voltage - DC 12 – 24V 48 – 60V 110 – 127V 220 – 250V Power consumption - DC 12V 24V 48V 60V 110V 120V 125V 127V 220V 250V …-FL(S)(C)-… CS(2)(3)-FLC-… …-FM(S)(C)-… CS(2)(3)-FMC-… …-FHS-… [V] [V] [V] [V] 9 36 77 – 9 36 77 – 9 36 77 – [VA] [VA] [VA] [VA] [VA] [VA] [VA] [VA] [VA] [VA] 100 400 100 160 55 66 71 72 110 140 100 400 100 160 55 66 71 72 110 140 100 400 100 160 55 66 71 72 110 140 44 copperLogic.com This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 CPRO-CAT-1109 www.barr-thorp.com Dimensions cPRO F-series Circuit Breakers Dimensions are in inches (millimeters). Not intended for manufacturing purposes. TM1-F… .750 (19.05) .469 (11.91) Handle: .344(8.74) wide x .375(9.53) thick 0˚ taper, load end 7˚ taper, line end On Off 2.350(59.69) R 6.000 (152.40) 4.500 (114.30) Push to Trip .750 (19.05) .469 (11.91) .344 (8.74) .062(1.57) 1.375 (34.93) 3.188(80.98) 3.375(85.73) 3.500(88.90) 4.12 (104.65) 1.562 (39.67) .740 (18.80) Drilling Plans TM1-F… Front Connected Front Cover Cutout Rear Connected .250(6.35) R .469 (11.91) .750 (19.05) 2.313 (58.75) 2.906 (73.81) 3.156 (73.03) 2.875 (73.03) Breaker Handle 4.500 (114.30) 1.906 (48.41) 1.189(30.20) .188(4.78) Diameter .594 (15.10) Breaker Handle 5.063 (114.30) Breaker Handle .581 (14.76) Location of .500(12.70) diameter megger holes, if required .688 (17.46) 1.375 (34.93) .164-32(M4 x 0.7) tap, 2 holes CPRO-CAT-1109 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 .438(11.13) diameter holes for 15 to 100 amp .563(14.30) diameter holes for 125 to 150 amp copperLogic.com www.barr-thorp.com 45 Dimensions cPRO F-series Circuit Breakers / Molded Case Switches Dimensions are in inches (millimeters). Not intended for manufacturing purposes. TM2-F…; CS2-F… 1.375 (34.93) .750 (19.05) .469 (11.91) Handle: .344(8.74) wide x .375(9.53) thick 0˚ taper, load end 7˚ taper, line end On Off 2.350(59.69) R 4.500 (114.30) 6.000 (152.40) .344 (8.74) Push To Trip .750 (19.05) .469 (11.91) .062(1.57) 2.750 (69.85) 3.188(80.98) 3.375(85.73) 3.500(88.90) 4.12 (104.65) 1.562 (39.67) .740 (18.80) Drilling Plans TM2-F…; CS2-F… Front Connected Front Cover Cutout Rear Connected .25 0(6.35) R .469 (11.91) .750 (19.05) 2.313 (58.75) 2.906 (73.81) 1.906 (48.41) 1.189 (30.20) 4.500 (114.30) .594 (15.10) .581 (14.76) .18 8 (4.78) diameter 3.156 (80.16) 2.875 (73.03) Breaker Handle 5.063 (128.60) Breaker Handle Breaker Handle 1.375 (34.93) Location of .50 0 (12.70) diameter megger holes, if required .688 (17.46) 1.375 (34.93) .164-3 2 (M4 x 0.7) tap, 2 holes .43 8 (11.13) diameter holes for 15 to 100 amp .56 3 (14.30) diameter holes for 125 to 150 amp 46 copperLogic.com This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 CPRO-CAT-1109 www.barr-thorp.com Dimensions cPRO F-series Circuit Breakers / Molded Case Switches Dimensions are in inches (millimeters). Not intended for manufacturing purposes. TM3-F…; CS3-F… 1.375 (34.93) 1.375 (34.93) .750 (19.05) .469 (11.91) Handle: .344(8.74) wide x .375(9.53) thick 0˚ taper, load end 7˚ taper, line end On Off 2.350(59.69) R 4.500 (114.30) 6.000 (152.40) .344 (8.74) Push to Trip .750 (19.05) .469 (11.91) .062(1.57) 4.125 (104.78) 3.188(80.98) 3.375(85.73) 3.500(88.90) 4.12 (104.65) 1.562 (39.67) .740 (18.80) Drilling Plans TM3-F…; CS3-F… Front Connected Front Cover Cutout Rear Connected .250(6.35) R .469 (11.91) .750 (19.05) 2.313 (58.75) 2.906 (73.81) 2.875 (73.03) Breaker Handle 1.906 (48.41) 4.500 (114.30) .594 (15.10) 1.189 (30.20) .581 (14.76) 1.375 (34.93) 1.375 (34.93) 3.156 (80.16) Breaker Handle 5.063 (128.60) Breaker Handle .188(4.78) Diameter Location of .500(12.70) diameter megger holes, if required .688 (17.48) 1.375 (34.93) .164-32(M4 x 0.7) tap, 4 holes 2.750 (69.85) 1.375 (34.93) .438(11.13) diameter holes for 15 to 100 amp .563(14.30) diameter holes for 125 to 150 amp CPRO-CAT-1109 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 copperLogic.com www.barr-thorp.com 47 cPRO K-series Interchangeable Trip Units to 400 amps R K-series cPRO molded case circuit breakers are designed to use interchangeable trip modules that control an array of operating characteristics from amp range to the type of protection desired. The breakers are available in both thermal-magnetic and electronic types. In addition, several devices are 100% rated breakers. This can prevent the need to upsize to a larger breaker size. Accessories and other options are UL listed to be field installed, so adding or changing functionality is a simple, on-site procedure. The Choice is Yours The thermal-magnetic breakers are rated to 600V AC / 250V DC, with continuous amp ratings from 100 - 400A. Three levels of breaking capacity; high, medium and low, are available up to 200kA. >70 – 400 amperes >100% rated breakers available Electronic trip breakers can be used to tailor protection to your specific application by offering multiple interchangeable trip options. Their modular design allows for a range of trip ratings from 70 to 400A within the same compact frame size. Three levels of breaking capacity are also available for every breaker. >Thermal-magnetic and electronic breakers have interchangeable trip units >Also suitable for use with refrigerant motor Interrupting Capacity [kA] 200 240V AC (electronic breakers available as AC only) 480V AC compressors (HACR rated) > Listed in accordance with CSA C22.2 No. 5 and UL 489 600V AC 250V DC 100 100 65 65 35 22 High Breaking Capacity 65 35 22 Medium Breaking Capacity Low Breaking Capacity 48 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 25 18 10 www.barr-thorp.com Electronic breakers Turn it On Choosing a K-series breaker with an electronic trip module allows you to coordinate the breaker with your application and circuit scheme. Four trip characteristics are available: (see page The cPRO K-series also includes two and three-pole Molded Case Switches, that offer up to 400A switching capabilities in applications to 600V AC and 250V DC. Molded case switches are constructed of circuit breaker components and include a fixed magnetic trip to increase the short circuit withstand rating (65kA @480V) and to protect the switch itself. They are also listed for reverse feed use and are 100% rated devices. A Shunt Trip is also available for these Switches, a feature not offered by many other manufacturers. 58 for a complete description) • Long and short delay protection • Long and short delay, instantaneous protection • Long and short delay, ground fault protection • Long and short delay, ground fault and instantaneous protection In more complex panels, these options can guard against nuisance tripping and assure that the breaker closest to the fault trips first. Safety you can see 1 The Rating Plug is installed into the Trip Module in seconds. This determines the amp range of the device. 2 Trip characteristics are determined by the type of Trip Module chosen. Modules install in minutes. CopperLogic breakers offer optional viewing windows in the breaker frame that allow you to see the position of the main power contacts in toggle operated applications. This is a requirement in the mining industry and certain utilities. If a pole is welded, one glance at the window can prevent serious injury. Breakers can be purchased as an assembled unit or by components for reduced inventories. Rather than stocking many sizes of complete breakers, a few frames can be inventoried with various Ratings Plugs and Trip Modules. Through-the-door & Flange Mounted Operators All operators include a lock-out mechanism for up to three padlocks that prevent the handle from being turned to the ON position. Door interlocks also prevent the enclosure door from being opened while the handle is in the ON position (defeat mechanisms are included). Flange handle can be mounted up to 10 ft. away from the breaker. Standard handles are rated NEMA 1 and 12 - available in black and red Ergonomic handles are rated NEMA 1, 12, 3R, 4 and 4X Flange handles are rated NEMA 1, 12, 3R, 4 and 4X This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com 49 > The economical solution for two pole applications to 250A @600V > Protection for single-phase motors, transformers and branch circuits > Interchangeable trip module allows for flexibility in the field > HACR rated allows for use with refrigerant motor compressors > Assembled units are factory sealed and approved for reverse feed use Order by Assembly with back-fed mains Thermal-Magnetic Two Pole Circuit Breakers with Interchangeable Trip Module (to 250A) ➊➋➌➍➎ Continuous Amp Rating @ 40° C (104° F) Maximum Operating Voltage AC DC Low Breaking Capacity 25 kAIC @ 600 V AC 35 kAIC @ 480 V AC 65 kAIC @ 240 V AC 10 kAIC @ 250 V DC ➏ Catalog Number Price Catalog Number Price High Breaking Capacity 65 kAIC @ 600 V AC 100 kAIC @ 480 V AC 200 kAIC @ 240 V AC 22 kAIC @ 250 V DC ➏ Catalog Number Price 100 600 250 TM2-K2LS-100B-L 3752 TM2-K2MS-100B-L 4114 TM2-K2HS-100B-L 4802 125 600 250 TM2-K2LS-125B-L 3752 TM2-K2MS-125B-L 4114 TM2-K2HS-125B-L 4802 150 600 250 TM2-K2LS-150B-L 3752 TM2-K2MS-150B-L 4114 TM2-K2HS-150B-L 4802 175 600 250 TM2-K2LS-175B-L 3752 TM2-K2MS-175B-L 4114 TM2-K2HS-175B-L 4802 200 600 250 TM2-K2LS-200B-L 3752 TM2-K2MS-200B-L 4114 TM2-K2HS-200B-L 4802 225 600 250 TM2-K2LS-225B-L 3752 TM2-K2MS-225B-L 4114 TM2-K2HS-225B-L 4802 250 600 250 TM2-K2LS-250B-L 3752 TM2-K2MS-250B-L 4114 TM2-K2HS-250B-L 4802 Ordering Instructions 1 2 Medium Breaking Capacity 35 kAIC @ 600 V AC 65 kAIC @ 480 V AC 100 kAIC @ 240 V AC 22 kAIC @ 250 V DC ➏ Locate the desired complete circuit breaker See pages 71 – 78 for accessories. 50 copperLogic.com ➊ Line and Load side terminals ship with breaker as standard. Other options are available; contact your CopperLogic representative. ➋ A VISA-window to view main power contacts is available. If desired, add “S” to end of catalog number, and add $1790 to price. For toggle style operators only. ➌ Two-pole circuit breakers are supplied in three-pole frame. ➍ Included trip modules have fixed thermal and adjustable magnetic settings. ➎ Mounting hardware not included. Order base mounting hardware separately on page 78. ➏Time constant is 3ms minimum at 10kA and 8ms minimum at 22kA. Discount Code B30 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 CPRO-CAT-1109 www.barr-thorp.com cPRO Molded Case Circuit Breakers 250A Thermal-Magnetic Two Pole, K-series Order by Components Frames for Two Pole Thermal-Magnetic Circuit Breakers (to 250A) ➊➋➌ Maximum Continuous Amp Rating @ 40° C (104° F) 250 Maximum Operating Voltage Low Breaking Capacity 25 kAIC @ 600 V AC 35 kAIC @ 480 V AC 65 kAIC @ 240 V AC 10 kAIC @ 250 V DC ➍ Medium Breaking Capacity 35 kAIC @ 600 V AC 65 kAIC @ 480 V AC 100 kAIC @ 240 V AC 22 kAIC @ 250 V DC ➍ High Breaking Capacity 65 kAIC @ 600 V AC 100 kAIC @ 480 V AC 200 kAIC @ 240 V AC 22 kAIC @ 250 V DC ➍ AC DC Catalog Number Price Catalog Number Price Catalog Number Price 600 250 MF2-KLS-250 2171 MF2-KMS-250 2500 MF2-KHS-250 3125 Trip Modules and Terminals Trip Modules Fixed Thermal, Adjustable Magnetic Continuous Amp Rating @ 40° C (104° F) 100 Terminals (individually priced and packaged) Maximum Operating Voltage Suitable for Low, Medium or High Breaking Capacities AC DC Catalog Number Price 600 250 KT2100T 1069 125 600 250 KT2125T 1069 150 600 250 KT2150T 1069 175 600 250 KT2175T 1069 200 600 250 KT2200T 1069 225 600 250 KT2225T 1069 250 600 250 KT2250T 1069 Wire Range Material AWG Aluminum #3 – 350 MCM TA300K 46 Aluminum 250 – 500 MCM TA350K 46 Catalog Number Price Ordering Instructions 1 2 3 CPRO-CAT-1109 Choose desired circuit breaker frame. Select trip module and terminals. See pages 71 – 78 for accessories. ➊ A VISA-window to view main power contacts is available. If desired, add “S” to end of breaker frame catalog number, and add $1790 to price. For toggle style operators only. ➋ Two-pole circuit breakers are supplied in three-pole frame. ➌ Mounting hardware not included. Order base mounting hardware separately on page 78. ➍ Time constant is 3ms minimum at 10kA and 8ms minimum at 22kA. Discount Code B30 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 copperLogic.com www.barr-thorp.com 51 > Future-proof your systems with superior scalability from 100A to Order by Assembly 400A with just a quick change of the trip module! Lower cost and installation time when your business grows. > For two pole applications to 400A @600V > Protection for single-phase motors, transformers and branch circuits > Interchangeable trip module allows for flexibility in the field > HACR rated allows for use with refrigerant motor compressors > Assembled units are factory sealed and approved for reverse feed use with back-fed mains Thermal-Magnetic Two Pole Circuit Breakers with Interchangeable Trip Module (to 400A) ➊➋➌➍➎ Continuous Amp Rating @ 40° C (104° F) Maximum Operating Voltage AC DC Low Breaking Capacity 25 kAIC @ 600 V AC 35 kAIC @ 480 V AC 65 kAIC @ 240 V AC 10 kAIC @ 250 V DC ➏ Catalog Number Price Catalog Number Price High Breaking Capacity 65 kAIC @ 600 V AC 100 kAIC @ 480 V AC 200 kAIC @ 240 V AC 22 kAIC @ 250 V DC ➏ Catalog Number Price 100 600 250 TM2-K4LS-100B-L 5996 TM2-K4MS-100B-L 6719 TM2-K4HS-100B-L 7877 125 600 250 TM2-K4LS-125B-L 5996 TM2-K4MS-125B-L 6719 TM2-K4HS-125B-L 7877 150 600 250 TM2-K4LS-150B-L 5996 TM2-K4MS-150B-L 6719 TM2-K4HS-150B-L 7877 175 600 250 TM2-K4LS-175B-L 5996 TM2-K4MS-175B-L 6719 TM2-K4HS-175B-L 7877 200 600 250 TM2-K4LS-200B-L 5996 TM2-K4MS-200B-L 6719 TM2-K4HS-200B-L 7877 225 600 250 TM2-K4LS-225B-L 5996 TM2-K4MS-225B-L 6719 TM2-K4HS-225B-L 7877 250 600 250 TM2-K4LS-250B-L 5996 TM2-K4MS-250B-L 6719 TM2-K4HS-250B-L 7877 300 600 250 TM2-K4LS-300B-L 5996 TM2-K4MS-300B-L 6719 TM2-K4HS-300B-L 7877 350 600 250 TM2-K4LS-350B-L 5996 TM2-K4MS-350B-L 6719 TM2-K4HS-350B-L 7877 400 600 250 TM2-K4LS-400B-L 5988 TM2-K4MS-400B-L 6712 TM2-K4HS-400B-L 7870 Ordering Instructions 1 2 Medium Breaking Capacity 35 kAIC @ 600 V AC 65 kAIC @ 480 V AC 100 kAIC @ 240 V AC 22 kAIC @ 250 V DC ➏ Locate the desired complete circuit breaker See pages 71 – 78 for accessories. 52 copperLogic.com ➊ Line and Load side terminals ship with breaker as standard. Other options are available; contact your CopperLogic representative. ➋ A VISA-window to view main power contacts is available. If desired, add “S” to end of catalog number, and add $1790 to price. For toggle style operators only. ➌ Two-pole circuit breakers are supplied in three-pole frame. ➍ Included trip modules have fixed thermal and adjustable magnetic settings. ➎ Mounting hardware not included. Order base mounting hardware separately on page 78. ➏Time constant is 3ms minimum at 10kA and 8ms minimum at 22kA. Discount Code B30 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 CPRO-CAT-1109 www.barr-thorp.com cPRO Molded Case Circuit Breakers 400A Thermal-Magnetic Two Pole, K-series Order by Components Frames for Two Pole Thermal-Magnetic Circuit Breakers (to 400A) ➊➋➌ Maximum Continuous Amp Rating @ 40° C (104° F) 400 Maximum Operating Voltage Low Breaking Capacity 25 kAIC @ 600 V AC 35 kAIC @ 480 V AC 65 kAIC @ 240 V AC 10 kAIC @ 250 V DC ➍ Medium Breaking Capacity 35 kAIC @ 600 V AC 65 kAIC @ 480 V AC 100 kAIC @ 240 V AC 22 kAIC @ 250 V DC ➍ High Breaking Capacity 65 kAIC @ 600 V AC 100 kAIC @ 480 V AC 200 kAIC @ 240 V AC 22 kAIC @ 250 V DC ➍ AC DC Catalog Number Price Catalog Number Price Catalog Number Price 600 250 MF2-KLS-400 4211 MF2-KMS-400 4868 MF2-KHS-400 5921 Trip Modules and Terminals Trip Modules Fixed Thermal, Adjustable Magnetic Continuous Amp Rating @ 40° C (104° F) 100 Terminals (individually priced and packaged, except where noted) ➎ Maximum Operating Voltage Suitable for Low, Medium or High Breaking Capacities AC DC Catalog Number Price 600 250 KT2100T 1069 125 600 250 KT2125T 1069 150 600 250 KT2150T 1069 175 600 250 KT2175T 1069 200 600 250 KT2200T 1069 225 600 250 KT2225T 1069 250 600 250 KT2250T 1069 300 600 250 KT2300T 1069 350 600 250 KT2350T 1069 400 600 250 KT2400T 1069 Wire Range Material AWG Aluminum #3 – 350 MCM TA300K 46 Aluminum 250 – 500 MCM TA350K 46 Aluminum 2x (#3/0 – 250 MCM) Catalog Number 2TA400K ➎ Price 175 (set of two) Ordering Instructions 1 2 3 CPRO-CAT-1109 Choose desired circuit breaker frame. Select trip module and terminals. See pages 71 – 78 for accessories. ➊ A VISA-window to view main power contacts is available. If desired, add “S” to end of breaker frame catalog number, and add $1790 to price. For toggle style operators only. ➋ Two-pole circuit breakers are supplied in three-pole frame. ➌ Mounting hardware not included. Order base mounting hardware separately on page 78. ➍ Time constant is 3ms minimum at 10kA and 8ms minimum at 22kA. ➎ Priced and packaged in sets of two. If line and load terminals are desired, order two sets. Discount Code B30 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 copperLogic.com www.barr-thorp.com 53 > The economical solution for three pole applications to 250A @600V > Protection for three-phase motors, transformers and branch circuits > Interchangeable trip module allows for flexibility in the field > HACR rated allows for use with refrigerant motor compressors > Assembled units are factory sealed and approved for reverse feed use Order by Assembly with back-fed mains Thermal-Magnetic Three Pole Circuit Breakers with Interchangeable Trip Module (to 250A) ➊➋➌➍ Continuous Amp Rating @ 40° C (104° F) Maximum Operating Voltage AC DC Low Breaking Capacity 25 kAIC @ 600 V AC 35 kAIC @ 480 V AC 65 kAIC @ 240 V AC 10 kAIC @ 250 V DC ➎ Catalog Number Price Catalog Number Price High Breaking Capacity 65 kAIC @ 600 V AC 100 kAIC @ 480 V AC 200 kAIC @ 240 V AC 22 kAIC @ 250 V DC ➎ Catalog Number Price 100 600 250 TM3-K2LS-100B-L 4534 TM3-K2MS-100B-L 4986 TM3-K2HS-100B-L 5800 125 600 250 TM3-K2LS-125B-L 4534 TM3-K2MS-125B-L 4986 TM3-K2HS-125B-L 5800 150 600 250 TM3-K2LS-150B-L 4534 TM3-K2MS-150B-L 4986 TM3-K2HS-150B-L 5800 175 600 250 TM3-K2LS-175B-L 4534 TM3-K2MS-175B-L 4986 TM3-K2HS-175B-L 5800 200 600 250 TM3-K2LS-200B-L 4534 TM3-K2MS-200B-L 4986 TM3-K2HS-200B-L 5800 225 600 250 TM3-K2LS-225B-L 4534 TM3-K2MS-225B-L 4986 TM3-K2HS-225B-L 5800 250 600 250 TM3-K2LS-250B-L 4534 TM3-K2MS-250B-L 4986 TM3-K2HS-250B-L 5800 Ordering Instructions 1 2 Medium Breaking Capacity 35 kAIC @ 600 V AC 65 kAIC @ 480 V AC 100 kAIC @ 240 V AC 22 kAIC @ 250 V DC ➎ Locate the desired complete circuit breaker See pages 71 – 78 for accessories. 54 copperLogic.com ➊ Line and Load side terminals ship with breaker as standard. Other options are available; contact your CopperLogic representative. ➋ A VISA-window to view main power contacts is available. If desired, add “S” to end of catalog number, and add $1790 to price. For toggle style operators only. ➌ Included trip modules have fixed thermal and adjustable magnetic settings. ➍ Mounting hardware not included. Order base mounting hardware separately on page 78. ➎Time constant is 3ms minimum at 10kA and 8ms minimum at 22kA. Discount Code B30 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 CPRO-CAT-1109 www.barr-thorp.com cPRO Molded Case Circuit Breakers 250A Thermal-Magnetic Three Pole, K-series Order by Components Frames for Three Pole Thermal-Magnetic Circuit Breakers (to 250A) ➊➋ Maximum Continuous Amp Rating @ 40° C (104° F) 250 Maximum Operating Voltage Low Breaking Capacity 25 kAIC @ 600 V AC 35 kAIC @ 480 V AC 65 kAIC @ 240 V AC 10 kAIC @ 250 V DC ➌ Medium Breaking Capacity 35 kAIC @ 600 V AC 65 kAIC @ 480 V AC 100 kAIC @ 240 V AC 22 kAIC @ 250 V DC ➌ High Breaking Capacity 65 kAIC @ 600 V AC 100 kAIC @ 480 V AC 200 kAIC @ 240 V AC 22 kAIC @ 250 V DC ➌ AC DC Catalog Number Price Catalog Number Price Catalog Number Price 600 250 MF3-KLS-250 2714 MF3-KMS-250 3125 MF3-KHS-250 3865 Trip Modules and Terminals Trip Modules Fixed Thermal, Adjustable Magnetic Continuous Amp Rating @ 40° C (104° F) 100 Terminals (individually priced and packaged) Maximum Operating Voltage Suitable for Low, Medium or High Breaking Capacities AC DC Catalog Number Price 600 250 KT3100T 1151 125 600 250 KT3125T 1151 150 600 250 KT3150T 1151 175 600 250 KT3175T 1151 200 600 250 KT3200T 1151 225 600 250 KT3225T 1151 250 600 250 KT3250T 1151 Wire Range Material AWG Aluminum #3 – 350 MCM TA300K 46 Aluminum 250 – 500 MCM TA350K 46 Catalog Number Price Ordering Instructions 1 2 3 CPRO-CAT-1109 Choose desired circuit breaker frame. Select trip module and terminals. See pages 71 – 78 for accessories. ➊ A VISA-window to view main power contacts is available. If desired, add “S” to end of breaker frame catalog number, and add $1790 to price. For toggle style operators only. ➋ Mounting hardware not included. Order base mounting hardware separately on page 78. ➌ Time constant is 3ms minimum at 10kA and 8ms minimum at 22kA. Discount Code B30 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 copperLogic.com www.barr-thorp.com 55 > Future-proof your systems with superior scalability from 100A to Order by Assembly 400A with just a quick change of the trip module! Lower cost and installation time when your business grows. > For three pole applications to 400A @600V > Protection for three-phase motors, transformers and branch circuits > Interchangeable trip module allows for flexibility in the field > HACR rated allows for use with refrigerant motor compressors > Assembled units are factory sealed and approved for reverse feed use with back-fed mains Thermal-Magnetic Three Pole Circuit Breakers with Interchangeable Trip Module (to 400A) ➊➋➌➍ Continuous Amp Rating @ 40° C (104° F) Maximum Operating Voltage AC DC Low Breaking Capacity 25 kAIC @ 600 V AC 35 kAIC @ 480 V AC 65 kAIC @ 240 V AC 10 kAIC @ 250 V DC ➎ Catalog Number Price Catalog Number Price High Breaking Capacity 65 kAIC @ 600 V AC 100 kAIC @ 480 V AC 200 kAIC @ 240 V AC 22 kAIC @ 250 V DC ➎ Catalog Number Price 100 600 250 TM3-K4LS-100B-L 7338 TM3-K4MS-100B-L 8243 TM3-K4HS-100B-L 9632 125 600 250 TM3-K4LS-125B-L 7338 TM3-K4MS-125B-L 8243 TM3-K4HS-125B-L 9632 150 600 250 TM3-K4LS-150B-L 7338 TM3-K4MS-150B-L 8243 TM3-K4HS-150B-L 9632 175 600 250 TM3-K4LS-175B-L 7338 TM3-K4MS-175B-L 8243 TM3-K4HS-175B-L 9632 200 600 250 TM3-K4LS-200B-L 7338 TM3-K4MS-200B-L 8243 TM3-K4HS-200B-L 9632 225 600 250 TM3-K4LS-225B-L 7338 TM3-K4MS-225B-L 8243 TM3-K4HS-225B-L 9632 250 600 250 TM3-K4LS-250B-L 7338 TM3-K4MS-250B-L 8243 TM3-K4HS-250B-L 9632 300 600 250 TM3-K4LS-300B-L 7338 TM3-K4MS-300B-L 8243 TM3-K4HS-300B-L 9632 350 600 250 TM3-K4LS-350B-L 7338 TM3-K4MS-350B-L 8243 TM3-K4HS-350B-L 9632 400 600 250 TM3-K4LS-400B-L 7327 TM3-K4MS-400B-L 8232 TM3-K4HS-400B-L 9622 Ordering Instructions 1 2 Medium Breaking Capacity 35 kAIC @ 600 V AC 65 kAIC @ 480 V AC 100 kAIC @ 240 V AC 22 kAIC @ 250 V DC ➎ Locate the desired complete circuit breaker See pages 71 – 78 for accessories. 56 copperLogic.com ➊ Line and Load side terminals ship with breaker as standard. Other options are available; contact your CopperLogic representative. ➋ A VISA-window to view main power contacts is available. If desired, add “S” to end of catalog number, and add $1790 to price. For toggle style operators only. ➌ Included trip modules have fixed thermal and adjustable magnetic settings. ➍ Mounting hardware not included. Order base mounting hardware separately on page 78. ➎Time constant is 3ms minimum at 10kA and 8ms minimum at 22kA. Discount Code B30 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 CPRO-CAT-1109 www.barr-thorp.com cPRO Molded Case Circuit Breakers 400A Thermal-Magnetic Three Pole, K-series Order by Components Frames for Three Pole Thermal-Magnetic Circuit Breakers (to 400A) ➊➋ Maximum Continuous Amp Rating @ 40° C (104° F) 400 Maximum Operating Voltage Low Breaking Capacity 25 kAIC @ 600 V AC 35 kAIC @ 480 V AC 65 kAIC @ 240 V AC 10 kAIC @ 250 V DC ➌ Medium Breaking Capacity 35 kAIC @ 600 V AC 65 kAIC @ 480 V AC 100 kAIC @ 240 V AC 22 kAIC @ 250 V DC ➌ High Breaking Capacity 65 kAIC @ 600 V AC 100 kAIC @ 480 V AC 200 kAIC @ 240 V AC 22 kAIC @ 250 V DC ➌ AC DC Catalog Number Price Catalog Number Price Catalog Number Price 600 250 MF3-KLS-400 5263 MF3-KMS-400 6086 MF3-KHS-400 7401 Trip Modules and Terminals Trip Modules Fixed Thermal, Adjustable Magnetic Continuous Amp Rating @ 40° C (104° F) 100 Terminals (individually priced and packaged, except where noted) ➍ Maximum Operating Voltage Suitable for Low, Medium or High Breaking Capacities AC DC Catalog Number Price 600 250 KT3100T 1151 125 600 250 KT3125T 1151 150 600 250 KT3150T 1151 175 600 250 KT3175T 1151 200 600 250 KT3200T 1151 225 600 250 KT3225T 1151 250 600 250 KT3250T 1151 300 600 250 KT3300T 1151 350 600 250 KT3350T 1151 400 600 250 KT3400T 1151 Wire Range Material AWG Aluminum #3 – 350 MCM TA300K 46 Aluminum 250 – 500 MCM TA350K 46 Aluminum 2x (#3/0 – 250 MCM) Catalog Number 3TA400K ➍ Price 263 (set of three) Ordering Instructions 1 2 3 CPRO-CAT-1109 Choose desired circuit breaker frame. Select trip module and terminals. See pages 71 – 78 for accessories. ➊ A VISA-window to view main power contacts is available. If desired, add “S” to end of breaker frame catalog number, and add $1790 to price. For toggle style operators only. ➋ Mounting hardware not included. Order base mounting hardware separately on page 78. ➌ Time constant is 3ms minimum at 10kA and 8ms minimum at 22kA. ➍ Priced and packaged in sets of three. If line and load terminals are desired, order two sets. Discount Code B30 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 copperLogic.com www.barr-thorp.com 57 cPRO Electronic Circuit Breakers cPRO K-series Electronic Trip Modules LS Type KES3125LS KES3250LS KES3400LS LSI Type KES3125LSI KES3250LSI KES3400LSI LSG Type KES3125LSG KES3250LSG KES3400LSG LSIG Type KES3125LSIG KES3250LSIG KES3400LSIG • Long Delay Pickup • Adjustable Short Delay Pickup with Fixed Short Delay Time (I 2t Response) • Adjustable Long Delay Pickup • Independently Adjustable Short Delay Pickup and Short Delay Time (Flat Response) • Long Delay Pickup • Adjustable Short Delay Pickup with Fixed Short Delay Time (I 2t Response) • Ground Fault Protection • Adjustable Long Delay Pickup • Independently Adjustable Short Delay Pickup and Short Delay Time (Flat Response) • Ground Fault Protection This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com cPRO Molded Case Circuit Breakers Assembled Electronic 250A Three Pole, K-series > Electronic breakers provide superior coordination with systems; best Order by Assembly suited for control of main incoming loads or main branch systems > Interchangeable trip module AND rating plug allows for maximum coordinating flexibility with minimal cost > The economical solution for three pole applications to 250A @600V > Select models offer built-in ground fault protection, reducing additional Order by Components on next two pages equipment costs > HACR rated allows for use with refrigerant motor compressors > Assembled units are factory sealed and approved for reverse feed use with back-fed mains Electronic Three Pole Circuit Breakers with Interchangeable Trip Module (to 250A) ➊➋➌ Continuous Amp Rating @ 40° C (104° F) ➍ ➎ Maximum Operating Voltage Low Breaking Capacity 25 kAIC @ 600 V AC 35 kAIC @ 480 V AC 65 kAIC @ 240 V AC Medium Breaking Capacity 35 kAIC @ 600 V AC 65 kAIC @ 480 V AC 100 kAIC @ 240 V AC High Breaking Capacity 65 kAIC @ 600 V AC 100 kAIC @ 480 V AC 200 kAIC @ 240 V AC AC DC Catalog Number Price Catalog Number Price Catalog Number Price 70 600 – ET3-K2LS-70◆-L 7725 ET3-K2MS-70◆-L 8136 ET3-K2HS-70◆-L 8876 90 600 – ET3-K2LS-90◆-L 7725 ET3-K2MS-90◆-L 8136 ET3-K2HS-90◆-L 8876 100 600 – ET3-K2LS-100◆-L 7725 ET3-K2MS-100◆-L 8136 ET3-K2HS-100◆-L 8876 110 600 – ET3-K2LS-110◆-L 7725 ET3-K2MS-110◆-L 8136 ET3-K2HS-110◆-L 8876 125 600 – ET3-K2LS-125◆-L 7725 ET3-K2MS-125◆-L 8136 ET3-K2HS-125◆-L 8876 150 600 – ET3-K2LS-150◆-L 8184 ET3-K2MS-150◆-L 8595 ET3-K2HS-150◆-L 9336 160 600 – ET3-K2LS-160◆-L 8184 ET3-K2MS-160◆-L 8595 ET3-K2HS-160◆-L 9336 175 600 – ET3-K2LS-175◆-L 8184 ET3-K2MS-175◆-L 8595 ET3-K2HS-175◆-L 9336 200 600 – ET3-K2LS-200◆-L 8184 ET3-K2MS-200◆-L 8595 ET3-K2HS-200◆-L 9336 225 600 – ET3-K2LS-225◆-L 8184 ET3-K2MS-225◆-L 8595 ET3-K2HS-225◆-L 9336 250 600 – ET3-K2LS-250◆-L 8184 ET3-K2MS-250◆-L 8595 ET3-K2HS-250◆-L 9336 Trip Unit Codes Complete catalog number (◆) with… E F G H Trip Unit Type (see page 58 for full description) LS Type: Long and Short Delay Protection LSI Type: Long and Short Delay, and Instantaneous Protection LSG Type: Long and Short Delay, and Ground Fault Protection LSIG Type: Long and Short Delay; Instantaneous and Ground Fault Protection Ordering Instructions 1 2 3 CPRO-CAT-1109 Locate the desired electronic circuit breaker. Complete catalog number with Trip Unit Code. See pages 71 – 78 for accessories. Price Adder (70 – 125A) ➍ – 427 1364 1709 Price Adder (150 – 250A) ➎ – 461 1513 1892 ➊ Line and Load side terminals ship with breaker as standard. Other options are available; contact your CopperLogic representative. ➋ A VISA-window to view main power contacts is available. If desired, add “S” to end of catalog number, and add $1790 to price. For toggle style operators only. ➌ Mounting hardware not included. Order base mounting hardware separately on page 78. ➍ Supplied with trip module of max continuous rating 125A and fixed rating plug that determines max continuous rating of assembled breaker. ➎ Supplied with trip module of max continuous rating 250A and fixed rating plug that determines max continuous rating of assembled breaker. Discount Code B30 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 copperLogic.com www.barr-thorp.com 59 Order by > Electronic breakers provide superior coordination with systems; best suited for control of main incoming loads or main branch systems > Interchangeable trip module AND rating plug allows for maximum coordinating flexibility with minimal cost Order by Assembly on previous page > The economical solution for three pole applications to 250A @600V > Select models offer built-in ground fault protection, reducing additional equipment costs > HACR rated allows for use with refrigerant motor compressors > Assembled units are factory sealed and approved for reverse feed use with back-fed mains Frames for Three Pole Electronic Circuit Breakers (to 250A) ➊➋ Step 1 - choose frame Maximum Continuous Amp Rating @ 40° C (104° F) 250 Low Breaking Capacity 25 kAIC @ 600 V AC 35 kAIC @ 480 V AC 65 kAIC @ 240 V AC Maximum Operating Voltage Medium Breaking Capacity 35 kAIC @ 600 V AC 65 kAIC @ 480 V AC 100 kAIC @ 240 V AC High Breaking Capacity 65 kAIC @ 600 V AC 100 kAIC @ 480 V AC 200 kAIC @ 240 V AC AC DC Catalog Number Price Catalog Number Price Catalog Number Price 600 – MF3-KLS-250 2714 MF3-KMS-250 3125 MF3-KHS-250 3865 Interchangeable Trip Modules Step 2 - choose trip module type Suitable for Low, Medium or High Breaking Capacities Maximum Operating Voltage LS Type LSI Type LSG Type LSIG Type Long and Short Delay Protection (see page 58 for full description) Long and Short Delay, and Instantaneous Protection (see page 58 for full description) Long and Short Delay, and Ground Fault Protection (see page 58 for full description) Long and Short Delay; Instantaneous and Ground Fault Protection (see page 58 for full description) AC DC Catalog Number Price Catalog Number Price Catalog Number Price Catalog Number Choose Rating Plug and Terminals from Price Table… 125 600 – KES3125LS 3618 KES3125LSI 4030 KES3125LSG 4967 KES3125LSIG 5313 A 250 600 – KES3250LS 4063 KES3250LSI 4523 KES3250LSG 5576 KES3250LSIG 5954 B Maximum Continuous Amp Rating @ 40° C (104° F) Ordering Instructions 1 2 3 4 Locate the desired circuit breaker frame. Select trip module. Choose rating plug and terminals on next page. See pages 71 – 78 for accessories. 60 copperLogic.com ➊ A VISA-window to view main power contacts is available. If desired, add “S” to end of breaker frame catalog number, and add $1790 to price. For toggle style operators only. ➋ Mounting hardware not included. Order base mounting hardware separately on page 78. Discount Code B30 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 CPRO-CAT-1109 www.barr-thorp.com cPRO Molded Case Circuit Breakers Components for Electronic 250A Three Pole, K-series Components Table A (for 125A Trip Modules): Rating Plugs and Terminals Step 3 - choose rating plug and terminals Table A Fixed Rating Plug Continuous Amp Rating Catalog @ 40° C (104° F) Number 1KES070T 1KES090T 1KES100T 1KES110T 1KES125T 70 90 100 110 125 or Price Continuous Amp Rating Settings Catalog @ 40° C (104° F) Number 329 329 329 329 329 Terminals (individually priced and packaged) Adjustable Rating Plug 70, 90, 100, 125 A1KES125T1 Wire Range Price Material AWG 526 Aluminum #3 – 350 MCM Catalog Number TA300K Price 46 Table B (for 250A Trip Modules): Rating Plugs and Terminals Step 3 - choose rating plug and terminals Table B Fixed Rating Plug Continuous Amp Rating Catalog @ 40° C (104° F) Number 2KES070T 2KES100T 2KES125T 2KES150T 2KES160T 2KES175T 2KES200T 2KES225T 2KES250T 70 100 125 150 160 175 200 225 250 CPRO-CAT-1109 or Price 329 329 329 329 329 329 329 329 329 Terminals (individually priced and packaged) Adjustable Rating Plug Continuous Amp Rating Settings Catalog @ 40° C (104° F) Number – – 125, 150, 200, 250 A2KES250T1 Wire Range Catalog Number Price Material AWG – Aluminum #3 – 350 MCM TA300K 46 526 Aluminum 250 – 500 MCM TA350K 46 copperLogic.com 61 Discount Code B30 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com Price cPRO Molded Case Circuit Breakers Notes 62 copperLogic.com This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 CPRO-CAT-1109 www.barr-thorp.com cPRO Molded Case Circuit Breakers Assembled Electronic 400A Three Pole, K-series > Future-proof your systems with superior scalability from 100A to 400A Order by Assembly with just a quick change of the trip module! Lower cost and installation time when your business grows. > Electronic breakers provide superior coordination with systems; best suited for control of main incoming loads or main branch systems > Interchangeable trip module AND rating plug allows for maximum coordinating flexibility with minimal cost > Select models offer built-in ground fault protection, reducing additional equipment costs Order by Components on next two pages Electronic Three Pole Circuit Breakers with Interchangeable Trip Module (to 400A) ➊➋➌ Continuous Amp Rating @ 40° C (104° F) ➍ ➎ ➏ Maximum Operating Voltage Low Breaking Capacity 25 kAIC @ 600 V AC 35 kAIC @ 480 V AC 65 kAIC @ 240 V AC Medium Breaking Capacity 35 kAIC @ 600 V AC 65 kAIC @ 480 V AC 100 kAIC @ 240 V AC High Breaking Capacity 65 kAIC @ 600 V AC 100 kAIC @ 480 V AC 200 kAIC @ 240 V AC AC DC Catalog Number Price Catalog Number Price Catalog Number Price 70 600 – ET3-K4LS-70◆-L 10289 ET3-K4MS-70◆-L 11112 ET3-K4HS-70◆-L 12428 90 600 – ET3-K4LS-90◆-L 10289 ET3-K4MS-90◆-L 11112 ET3-K4HS-90◆-L 12428 100 600 – ET3-K4LS-100◆-L 10289 ET3-K4MS-100◆-L 11112 ET3-K4HS-100◆-L 12428 110 600 – ET3-K4LS-110◆-L 10289 ET3-K4MS-110◆-L 11112 ET3-K4HS-110◆-L 12428 125 600 – ET3-K4LS-125◆-L 10289 ET3-K4MS-125◆-L 11112 ET3-K4HS-125◆-L 12428 150 600 – ET3-K4LS-150◆-L 10734 ET3-K4MS-150◆-L 11556 ET3-K4HS-150◆-L 12872 160 600 – ET3-K4LS-160◆-L 10734 ET3-K4MS-160◆-L 11556 ET3-K4HS-160◆-L 12872 175 600 – ET3-K4LS-175◆-L 10734 ET3-K4MS-175◆-L 11556 ET3-K4HS-175◆-L 12872 200 600 – ET3-K4LS-200◆-L 10734 ET3-K4MS-200◆-L 11556 ET3-K4HS-200◆-L 12872 225 600 – ET3-K4LS-225◆-L 10734 ET3-K4MS-225◆-L 11556 ET3-K4HS-225◆-L 12872 250 600 – ET3-K4LS-250◆-L 10734 ET3-K4MS-250◆-L 11556 ET3-K4HS-250◆-L 12872 300 600 – ET3-K4LS-300◆-L 11030 ET3-K4MS-300◆-L 11852 ET3-K4HS-300◆-L 13168 350 600 – ET3-K4LS-350◆-L 11030 ET3-K4MS-350◆-L 11852 ET3-K4HS-350◆-L 13168 400 600 – ET3-K4LS-400◆-L 11030 ET3-K4MS-400◆-L 11852 ET3-K4HS-400◆-L 13168 Trip Unit Codes Complete catalog number (◆) with… E F G H Trip Unit Type (see page 58 for full description) LS Type: Long and Short Delay Protection LSI Type: Long and Short Delay, and Instantaneous Protection LSG Type: Long and Short Delay, and Ground Fault Protection LSIG Type: Long and Short Delay; Instantaneous and Ground Fault Protection Ordering Instructions 1 2 3 CPRO-CAT-1109 Locate the desired electronic circuit breaker. Complete catalog number with Trip Unit Code. See pages 71 – 78 for accessories. Price Adder (70 – 125A) ➍ – 412 1349 1695 Price Adder (150 – 250A) ➎ – 460 1513 1891 Price Adder (300 – 400A) ➏ – 493 1628 2039 ➊ Line and Load side terminals ship with breaker as standard. Other options are available; contact your CopperLogic representative. ➋ A VISA-window to view main power contacts is available. If desired, add “S” to end of catalog number, and add $1790 to price. For toggle style operators only. ➌ Mounting hardware not included. Order base mounting hardware separately on page 78. ➍ Supplied with trip module of max continuous rating 125A and fixed rating plug that determines max continuous rating of assembled breaker. ➎ Supplied with trip module of max continuous rating 250A and fixed rating plug that determines max continuous rating of assembled breaker. ➏ Supplied with trip module of max continuous rating 400A and fixed rating plug that determines max continuous rating of assembled breaker. Discount Code B30 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 copperLogic.com www.barr-thorp.com 63 Order by > Future-proof your systems with superior scalability from 100A to 400A with just a quick change of the trip module! Lower cost and installation time when your business grows. > Electronic breakers provide superior coordination with systems; best suited for control of main incoming loads or main branch systems > Interchangeable trip module AND rating plug allows for maximum coordinating flexibility with minimal cost > Select models offer built-in ground fault protection, reducing additional equipment costs Order by Assembly on previous page Frames for Three Pole Electronic Circuit Breakers (to 400A) ➊➋ Step 1 - choose frame Maximum Continuous Amp Rating @ 40° C (104° F) 400 Low Breaking Capacity 25 kAIC @ 600 V AC 35 kAIC @ 480 V AC 65 kAIC @ 240 V AC Maximum Operating Voltage Medium Breaking Capacity 35 kAIC @ 600 V AC 65 kAIC @ 480 V AC 100 kAIC @ 240 V AC High Breaking Capacity 65 kAIC @ 600 V AC 100 kAIC @ 480 V AC 200 kAIC @ 240 V AC AC DC Catalog Number Price Catalog Number Price Catalog Number Price 600 – MF3-KLS-400 5263 MF3-KMS-400 6086 MF3-KHS-400 7401 Interchangeable Trip Modules Step 2 - choose trip module type Suitable for Low, Medium or High Breaking Capacities Maximum Operating Voltage LS Type LSI Type LSG Type LSIG Type Long and Short Delay Protection (see page 58 for full description) Long and Short Delay, and Instantaneous Protection (see page 58 for full description) Long and Short Delay, and Ground Fault Protection (see page 58 for full description) Long and Short Delay; Instantaneous and Ground Fault Protection (see page 58 for full description) AC DC Catalog Number Price Catalog Number Price Catalog Number Price Catalog Number Choose Rating Plug and Terminals from Price Table… 125 600 – KES3125LS 3618 KES3125LSI 4030 KES3125LSG 4967 KES3125LSIG 5313 A 250 600 – KES3250LS 4063 KES3250LSI 4523 KES3250LSG 5576 KES3250LSIG 5954 B 400 600 – KES3400LS 4359 KES3400LSI 4852 KES3400LSG 5987 KES3400LSIG 6398 C Maximum Continuous Amp Rating @ 40° C (104° F) Ordering Instructions 1 2 3 4 Locate the desired circuit breaker frame. Select trip module. Choose rating plug and terminals on next page. See pages 71 – 78 for accessories. 64 copperLogic.com ➊ A VISA-window to view main power contacts is available. If desired, add “S” to end of breaker frame catalog number, and add $1790 to price. For toggle style operators only. ➋ Mounting hardware not included. Order base mounting hardware separately on page 78. ➌ Priced and packaged in sets of three. If line and load terminals are desired, order two sets. Discount Code B30 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 CPRO-CAT-1109 www.barr-thorp.com cPRO Molded Case Circuit Breakers Components for Electronic 400A Three Pole, K-series Components Table A (for 125A Trip Modules): Rating Plugs and Terminals Step 3 - choose rating plug and terminals Table A Fixed Rating Plug Continuous Amp Rating Catalog @ 40° C (104° F) Number 1KES070T 1KES090T 1KES100T 1KES110T 1KES125T 70 90 100 110 125 or Price Continuous Amp Rating Settings Catalog @ 40° C (104° F) Number 329 329 329 329 329 Terminals (individually priced and packaged) Adjustable Rating Plug 70, 90, 100, 125 A1KES125T1 Wire Range Price Material AWG 526 Aluminum #3 – 350 MCM Catalog Number TA300K Price 46 Table B (for 250A Trip Modules): Rating Plugs and Terminals Step 3 - choose rating plug and terminals Table B Fixed Rating Plug Continuous Amp Rating Catalog @ 40° C (104° F) Number 2KES070T 2KES100T 2KES125T 2KES150T 2KES160T 2KES175T 2KES200T 2KES225T 2KES250T 70 100 125 150 160 175 200 225 250 or Price Continuous Amp Rating Settings Catalog @ 40° C (104° F) Number 329 329 329 329 329 329 329 329 329 Terminals (individually priced and packaged) Adjustable Rating Plug – – 125, 150, 200, 250 A2KES250T1 Wire Range Catalog Number Price Material AWG – Aluminum #3 – 350 MCM TA300K 46 526 Aluminum 250 – 500 MCM TA350K 46 Price Table C (for 400A Trip Modules): Rating Plugs and Terminals Step 3 - choose rating plug and terminals Table C Fixed Rating Plug Continuous Amp Rating Catalog @ 40° C (104° F) Number or Price 200 225 250 300 350 4KES200T 4KES225T 4KES250T 4KES300T 4KES350T 329 329 329 329 329 400 4KES400T 329 CPRO-CAT-1109 Terminals (individually priced and packaged, except where noted) ➌ Adjustable Rating Plug Continuous Amp Rating Settings Catalog @ 40° C (104° F) Number – – 220, 240, 260, 280 A4KES200T5 Wire Range Catalog Number Price Material AWG – Aluminum #3 – 350 MCM TA300K 46 526 Aluminum 250 – 500 MCM TA350K 46 Aluminum 2x (#3/0 – 250 MCM) 200, 250, 300, 400 A4KES400T1 526 320, 340, 360, 380 A4KES300T5 526 Discount Code B30 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 3TA400K ➌ (set of three) copperLogic.com www.barr-thorp.com Price 263 65 cPRO Molded Case Circuit Breakers Notes 66 copperLogic.com This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 CPRO-CAT-1109 www.barr-thorp.com cPRO Molded Case Circuit Breakers Assembled 100% Rated, Electronic 400A Three Pole, K-series > Future-proof your systems with superior scalability from 100A to 400A Order by Assembly with just a quick change of the trip module! Lower cost and installation time when your business grows. > 100% Rated device prevents need to select a larger breaker size > Electronic breakers provide superior coordination with systems; best suited for control of main incoming loads or main branch systems Order by Components on next two pages > Interchangeable trip module AND rating plug allows for maximum coordinating flexibility with minimal cost > Select models offer built-in ground fault protection, reducing additional equipment costs 100% Rated Electronic Three Pole Circuit Breakers with Interchangeable Trip Module (to 400A) ➊➋➌ Continuous Amp Rating @ 40° C (104° F) ➍ ➎ ➏ Maximum Operating Voltage Low Breaking Capacity 25 kAIC @ 600 V AC 35 kAIC @ 480 V AC 65 kAIC @ 240 V AC Medium Breaking Capacity 35 kAIC @ 600 V AC 65 kAIC @ 480 V AC 100 kAIC @ 240 V AC AC DC Catalog Number Price Catalog Number Price 70 600 – ET3-K4LC-70◆-L 12098 ET3-K4MC-70◆-L 13151 90 600 – ET3-K4LC-90◆-L 12098 ET3-K4MC-90◆-L 13151 100 600 – ET3-K4LC-100◆-L 12098 ET3-K4MC-100◆-L 13151 110 600 – ET3-K4LC-110◆-L 12098 ET3-K4MC-110◆-L 13151 125 600 – ET3-K4LC-125◆-L 12098 ET3-K4MC-125◆-L 13151 150 600 – ET3-K4LC-150◆-L 12572 ET3-K4MC-150◆-L 13625 160 600 – ET3-K4LC-160◆-L 12572 ET3-K4MC-160◆-L 13625 175 600 – ET3-K4LC-175◆-L 12572 ET3-K4MC-175◆-L 13625 200 600 – ET3-K4LC-200◆-L 12572 ET3-K4MC-200◆-L 13625 225 600 – ET3-K4LC-225◆-L 12572 ET3-K4MC-225◆-L 13625 250 600 – ET3-K4LC-250◆-L 12572 ET3-K4MC-250◆-L 13625 300 600 – ET3-K4LC-300◆-L 12888 ET3-K4MC-300◆-L 13940 350 600 – ET3-K4LC-350◆-L 12888 ET3-K4MC-350◆-L 13940 400 600 – ET3-K4LC-400◆-L 12888 ET3-K4MC-400◆-L 13940 Trip Unit Codes Complete catalog number (◆) with… E F G H Trip Unit Type (see page 58 for full description) LS Type: Long and Short Delay Protection LSI Type: Long and Short Delay, and Instantaneous Protection LSG Type: Long and Short Delay, and Ground Fault Protection LSIG Type: Long and Short Delay; Instantaneous and Ground Fault Protection Ordering Instructions 1 2 3 CPRO-CAT-1109 Locate the desired electronic circuit breaker. Complete catalog number with Trip Unit Code. See pages 71 – 78 for accessories. Price Adder (70 – 125A) ➍ – 439 1439 1807 Price Adder (150 – 250A) ➎ – 491 1614 2017 Price Adder (300 – 400A) ➏ – 526 1737 2175 ➊ Line and Load side terminals ship with breaker as standard. Other options are available; contact your CopperLogic representative. ➋ A VISA-window to view main power contacts is available. If desired, add “S” to end of catalog number, and add $1790 to price. For toggle style operators only. ➌ Mounting hardware not included. Order base mounting hardware separately on page 78. ➍ Supplied with trip module of max continuous rating 125A and fixed rating plug that determines max continuous rating of assembled breaker. ➎ Supplied with trip module of max continuous rating 250A and fixed rating plug that determines max continuous rating of assembled breaker. ➏ Supplied with trip module of max continuous rating 400A and fixed rating plug that determines max continuous rating of assembled breaker. Discount Code B30 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 copperLogic.com www.barr-thorp.com 67 Order by > Future-proof your systems with superior scalability from 100A to 400A with just a quick change of the trip module! Lower cost and installation time when your business grows. > 100% Rated device prevents need to select a larger breaker size > Electronic breakers provide superior coordination with systems; best Order by Assembly on previous page suited for control of main incoming loads or main branch systems > Interchangeable trip module AND rating plug allows for maximum coordinating flexibility with minimal cost > Select models offer built-in ground fault protection, reducing additional equipment costs Frames for 100% Rated Three Pole Electronic Circuit Breakers (to 400A) ➊➋ Step 1 - choose frame Maximum Continuous Amp Rating @ 40° C (104° F) 400 Low Breaking Capacity 25 kAIC @ 600 V AC 35 kAIC @ 480 V AC 65 kAIC @ 240 V AC Maximum Operating Voltage Medium Breaking Capacity 35 kAIC @ 600 V AC 65 kAIC @ 480 V AC 100 kAIC @ 240 V AC AC DC Catalog Number Price Catalog Number Price 600 – MF3-KLC-400 6737 MF3-KMC-400 7789 Interchangeable Trip Modules Step 2 - choose trip module type Suitable for Low, Medium or High Breaking Capacities Maximum Operating Voltage LS Type LSI Type LSG Type LSIG Type Long and Short Delay Protection (see page 58 for full description) Long and Short Delay, and Instantaneous Protection (see page 58 for full description) Long and Short Delay, and Ground Fault Protection (see page 58 for full description) Long and Short Delay; Instantaneous and Ground Fault Protection (see page 58 for full description) AC DC Catalog Number Price Catalog Number Price Catalog Number Price Catalog Number Choose Rating Plug and Terminals from Price Table… 125 600 – KES3125LS 3618 KES3125LSI 4030 KES3125LSG 4967 KES3125LSIG 5313 A 250 600 – KES3250LS 4063 KES3250LSI 4523 KES3250LSG 5576 KES3250LSIG 5954 B 400 600 – KES3400LS 4359 KES3400LSI 4852 KES3400LSG 5987 KES3400LSIG 6398 C Maximum Continuous Amp Rating @ 40° C (104° F) Ordering Instructions 1 2 3 4 Locate the desired circuit breaker frame. Select trip module. Choose rating plug and terminals on next page. See pages 71 – 78 for accessories. 68 copperLogic.com ➊ A VISA-window to view main power contacts is available. If desired, add “S” to end of breaker frame catalog number, and add $1790 to price. For toggle style operators only. ➋ Mounting hardware not included. Order base mounting hardware separately on page 78. ➌ Priced and packaged in sets of three. If line and load terminals are desired, order two sets. Discount Code B30 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 CPRO-CAT-1109 www.barr-thorp.com cPRO Molded Case Circuit Breakers Components for 100% Rated Electronic 400A Three Pole, K-series Components Table A (for 125A Trip Modules): Rating Plugs and Terminals Step 3 - choose rating plug and terminals Table A Fixed Rating Plug Continuous Amp Rating Catalog @ 40° C (104° F) Number 1KES070T 1KES090T 1KES100T 1KES110T 1KES125T 70 90 100 110 125 or Price Continuous Amp Rating Settings Catalog @ 40° C (104° F) Number 329 329 329 329 329 Terminals (individually priced and packaged) Adjustable Rating Plug 70, 90, 100, 125 A1KES125T1 Wire Range Price Material AWG 526 Aluminum #3 – 350 MCM Catalog Number TA300K Price 46 Table B (for 250A Trip Modules): Rating Plugs and Terminals Step 3 - choose rating plug and terminals Table B Fixed Rating Plug Continuous Amp Rating Catalog @ 40° C (104° F) Number 2KES070T 2KES100T 2KES125T 2KES150T 2KES160T 2KES175T 2KES200T 2KES225T 2KES250T 70 100 125 150 160 175 200 225 250 or Price Continuous Amp Rating Settings Catalog @ 40° C (104° F) Number 329 329 329 329 329 329 329 329 329 Terminals (individually priced and packaged) Adjustable Rating Plug – – 125, 150, 200, 250 A2KES250T1 Wire Range Catalog Number Price Material AWG – Aluminum #3 – 350 MCM TA300K 46 526 Aluminum 250 – 500 MCM TA350K 46 Price Table C (for 400A Trip Modules): Rating Plugs and Terminals Step 3 - choose rating plug and terminals Table C Fixed Rating Plug Continuous Amp Rating Catalog @ 40° C (104° F) Number or Price 200 225 250 300 350 4KES200T 4KES225T 4KES250T 4KES300T 4KES350T 329 329 329 329 329 400 4KES400T 329 CPRO-CAT-1109 Terminals (individually priced and packaged, except where noted) ➌ Adjustable Rating Plug Continuous Amp Rating Settings Catalog @ 40° C (104° F) Number – – 220, 240, 260, 280 A4KES200T5 Wire Range Catalog Number Price Material AWG – Aluminum #3 – 350 MCM TA300K 46 526 Aluminum 250 – 500 MCM TA350K 46 Aluminum 2x (#3/0 – 250 MCM) 200, 250, 300, 400 A4KES400T1 526 320, 340, 360, 380 A4KES300T5 526 Discount Code B30 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 3TA400K ➌ (set of three) copperLogic.com www.barr-thorp.com Price 263 69 cPRO Molded Case Switches 400A Molded Case Switches, K-series > Two pole switches are suitable for single-phase motor discon- > 100% Rated device prevents need to select a larger switch size > Built-in fixed instantaneous trip opens above 4000 Amps > HACR rated allows for use with refrigerant motor compressors necting and switching to 400 Amps > Three pole switches are suitable for three-phase motor disconnecting and switching to 400 Amps Two Pole Molded Case Switches (to 400A) ➊➋➌➍ Step 1 - choose frame Medium Short-circuit Withstand Rating 35 kAIC @ 600 V AC 65 kAIC @ 480 V AC 100 kAIC @ 240 V AC 22 kAIC @ 250 V DC Low Short-circuit Withstand Rating 25 kAIC @ 600 V AC 35 kAIC @ 480 V AC 65 kAIC @ 240 V AC 10 kAIC @ 250 V DC Maximum Operating Voltage Continuous Amp Rating @ 40° C (104° F) AC DC Catalog Number Price Catalog Number Price 400 600 250 CS2-KLC-400 4772 CS2-KMC-400 5368 Three Pole Molded Case Switches (to 400A) ➊➋➌ Step 1 - choose frame Maximum Operating Voltage Medium Short-circuit Withstand Rating 35 kAIC @ 600 V AC 65 kAIC @ 480 V AC 100 kAIC @ 240 V AC 22 kAIC @ 250 V DC Low Short-circuit Withstand Rating 25 kAIC @ 600 V AC 35 kAIC @ 480 V AC 65 kAIC @ 240 V AC 10 kAIC @ 250 V DC Continuous Amp Rating @ 40° C (104° F) AC DC Catalog Number Price Catalog Number Price 400 600 250 CS3-KLC-400 5614 CS3-KMC-400 6316 Terminals Step 2 - select terminals Max. Amp Rating Material Terminals Wire Type No. of Conductors Wire Range Terminals Terminals with Control Wire For use with… Catalog Number K-series TA300K ➎ 46 – – K-series TA350K ➎ 46 – – Two Pole K-series (set of two) Three Pole K-series (set of three) Price Catalog Number Price Standard Terminals 225 Aluminum Cu / Al 1 350 Aluminum Cu / Al 1 400 Aluminum Cu / Al Ordering Instructions 1 2 3 Locate the desired molded case switch. Select terminals. See pages 71 – 78 for accessories. 70 copperLogic.com 2 #3 – 350 kcmil 35 – 185 mm2 250 – 500 kcmil 120 – 240 mm2 #3/0 – 250 kcmil 95 – 120 mm2 2TA400K ➏ 3TA400K ➐ 175 263 2TA400KCW ➏ (set of two) 3TA400KCW ➐ (set of three) 263 386 ➊ A VISA-window to view main power contacts is available. If desired, add “S” to end of switch catalog number, and add $1790 to price. For toggle style operators only. ➋ Molded case switches are supplied with a fixed instantaneous trip that opens above 4000A. ➌ Mounting hardware not included. Order base mounting hardware separately on page 78. ➍ Two-pole molded case switches are supplied in a three-pole frame. ➎ Individually priced and packaged. ➏ Priced and packaged in sets of two. If line and load terminals are desired, order two sets. ➐ Priced and packaged in sets of three. If line and load terminals are desired, order two sets. Discount Code B30 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 CPRO-CAT-1109 www.barr-thorp.com Accessories K-series Rotary Handles Through-the-door Handles - Complete Units (includes handle, mechanism and shaft) ➊ Accessory Shaft Length mm (in.) Description Handle Color Catalog Number Price Black Red Black Red Black Red KHMVD06B KHMVD06R KHMVD12B KHMVD12R KHMVD24B KHMVD24R 795 795 842 842 1029 1029 152.4 (6) Black HM3R06 968 304.8 (12) Black HM3R12 1011 406.4 (16) Black HM3R16 1116 609.6 (24) Black HM3R24 1221 152.4 (6) Black HM3R06X 1053 304.8 (12) Black HM3R12X 1095 406.4 (16) Black HM3R16X 1200 609.6 (24) Black HM3R24X 1305 Standard Handle Kit - NEMA 1, 12 152.4 (6) NEMA 1, 12 Molded plastic handle For K-series 90 degree rotation 304.8 (12) 609.6 (24) Ergonomic Handle Kit- NEMA 1, 12, 3R NEMA 1, 12, 3R Steel handle For K-series Ergonomic design for ‘gloved hand’ operation 45 degree rotation Ergonomic Handle Kit - NEMA 4/4X NEMA 4/4X Steel handle For K-series Ergonomic design for ‘gloved hand’ operation 45 degree rotation Through-the-door Handles - Components (order separately) ➊ Mechanism Handle Handle Color Catalog Number Description Price Catalog Number Shaft Price Length [mm (in.)] Catalog Number Price Handle Components for NEMA 1, 12, 3R NEMA 1, 12, 3R Ergonomic Steel handle For K-series Ergonomic design for ‘gloved hand’ operation 45 degree rotation Black 6648C22G01 344 6648C23G25 574 152.4 (6) 4217B37G08 150 304.8 (12) 4217B37G05 180 406.4 (16) 4217B37G06 211 609.6 (24) 4217B37G07 241 152.4 (6) 4217B37G08 150 304.8 (12) 4217B37G05 180 406.4 (16) 4217B37G06 211 609.6 (24) 4217B37G07 241 Handle Components for NEMA 4/4X NEMA 4/4X Ergonomic Steel handle For K-series Ergonomic design for ‘gloved hand’ operation 45 degree rotation Black 6648C22G03 431 6648C23G25 574 ➊ Not for use with VISA-window option. CPRO-CAT-1109 Discount Code B30 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 copperLogic.com www.barr-thorp.com 71 Accessories K-series Flange and Toggle Operators Flange Mounted Handles ➊ Accessory NEMA 1, 12, 3R Flexible Shaft Length m (ft.) Catalog Number Price Description NEMA 4/4X Catalog Number Price Flange Handles For K-series Extra heavy-duty flexible shaft Accepts up to 3 padlocks 0.9 (3) F3S03C 2784 F3S03CX 3275 1.2 (4) F3S04C 2830 F3S04CX 3333 1.5 (5) F3S05C 2877 F3S05CX 3392 1.8 (6) F3S06C 2924 F3S06CX 3450 2.1 (7) F3S07C 2971 F3S07CX 3509 2.4 (8) F3S08C 3018 F3S08CX 3556 2.7 (9) F3S09C 3064 F3S09CX 3602 3.0 (10) F3S10C 3111 F3S10CX 3661 Safety Door Hardware for NEMA 12 Flex Shafts Accessory Handle Length mm (in.) Description Catalog Number Price Hardware Kit 101.6 (4.0) C361KJ4 500 152.4 (6.0) C361KJ6 500 – C361KR 66 Provides enclosure sealing and protection against unauthorized entry Roller Latch Required for 3-point latching Handle Extension Accessory Description Catalog Number Price For K-series Used to extend operating handle of circuit breaker HEX3 211 Handle Extension ➊ Not for use with VISA-window option. 72 copperLogic.com Discount Code B30 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 CPRO-CAT-1109 www.barr-thorp.com Accessories K-series Internal Accessories Alarm and Auxiliary Switches Accessory Description Schematic Contacts For use Mounting with… Options 1 NO & 1 NC K-series 2 NO & 2 NC K-series 1 NO & 1 NC K-series 2 NO & 2 NC K-series 3 NO & 3 NC K-series Pigtail Leads (18 in., 18 AWG) Catalog Number Price Terminal Block Catalog No. Price Alarm Lockout Switch For remote indication of trip operation. Switch resets when circuit breaker resets. Make Break For Left pole A1L3LPK 491 A1L3LTK 491 For Right pole A1L3RPK 491 A1L3RTK 491 For Left pole A2L3LPK 982 A2L3LTK 982 For Right pole A2L3RPK 982 A2L3RTK 982 A1X3PK 491 A1X3LTK 491 A1X3RTK 491 A2X3PK 982 A2X3LTK 982 A2X3RTK 982 For Left pole A3X3LPK 1474 A3X3LTK 1474 For Right pole A3X3RPK 1474 A3X3RTK 1474 For Left pole AAL3LPK 982 AAL3LTK 982 For Right pole AAL3RPK 982 AAL3RTK 982 Auxiliary Switch a For remote indication of circuit breaker status. b For Left pole For Right pole For Left pole For Right pole Alarm and Auxiliary Switch Combination For remote indication of trip operation and circuit breaker status. Switch resets when circuit breaker resets. a b 2 NO & 2 NC K-series Shunt Trips Accessory Description Schematic Pigtail Leads (18 in., 18 AWG) Terminal Block For use Mounting with… Options Operating Voltage Catalog Number Price Catalog No. Price Intermittent Duty Shunt Trip Provides remote trip. CPRO-CAT-1109 ST a K-series Shunt trip suitable for left or right pole 12 – 24 V AC 12 – 24 V DC SNT3P04K 602 SNT3T04K 602 48 – 60 V AC 48 – 60 V DC SNT3P06K 602 SNT3T06K 602 110 – 240 V AC 110 – 125 V DC SNT3P11K 602 SNT3T11K 602 380 – 440 V AC 220 – 250 V DC SNT3P14K 602 SNT3T14K 602 480 – 600 V AC SNT3P18K 602 SNT3T18K 602 Discount Code B30 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 copperLogic.com www.barr-thorp.com 73 Accessories K-series Internal Accessories Undervoltage Trips Accessory Description Schematic For Use With… Operating Voltage AC DC 12 – 24 – 48 – 60 – 110 – 127 – 208 – 240 – 380 – 480 – – 12 – 24 – 48 – 60 – 110 – 127 – 220 – 250 Pigtail Leads (18 in., 18 AWG) Terminal Block Mounting Options Catalog Number Price Catalog No. Price Undervoltage Trip Trips breaker when voltage drops below threshold. (see tech. data for individual thresholds - pages 97 – 98) 74 copperLogic.com UV K-series Left pole UVH3LP02K 722 UVH3LT02K 722 Right pole UVH3RP02K 722 UVH3RT02K 722 Left pole UVH3LP03K 722 UVH3LT03K 722 Right pole UVH3RP03K 722 UVH3RT03K 722 Left pole UVH3LP05K 722 UVH3LT05K 722 Right pole UVH3RP05K 722 UVH3RT05K 722 Left pole UVH3LP08K 722 UVH3LT08K 722 Right pole UVH3RP08K 722 UVH3RT08K 722 Left pole UVH3LP11K 722 UVH3LT11K 722 Right pole UVH3RP11K 722 UVH3RT11K 722 Left pole UVH3LP15K 722 UVH3LT15K 722 Right pole UVH3RP15K 722 UVH3RT15K 722 Left pole UVH3LP20K 722 UVH3LT20K 722 Right pole UVH3RP20K 722 UVH3RT20K 722 Left pole UVH3LP21K 722 UVH3LT21K 722 Right pole UVH3RP21K 722 UVH3RT21K 722 Left pole UVH3LP23K 722 UVH3LT23K 722 Right pole UVH3RP23K 722 UVH3RT23K 722 Left pole UVH3LP26K 722 UVH3LT26K 722 Right pole UVH3RP26K 722 UVH3RT26K 722 Left pole UVH3LP28K 722 UVH3LT28K 722 Right pole UVH3RP28K 722 UVH3RT28K 722 Discount Code B30 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 CPRO-CAT-1109 www.barr-thorp.com Accessories K-series Remote Electrical Operators Accessory Description Inrush Current [A] Max. Operating Time Fuse [A] 30 5 cycles (80 ms) 16 Operating Voltage AC DC For use with… Catalog Number 6 120 – K-series EOP3MT07 7602 5 cycles (80 ms) 4 240 – K-series EOP3MT11 7602 30 5 cycles (80 ms) 6 – 120 K-series EOP3MT07DC 7602 16 5 cycles (80 ms) 4 – 240 K-series EOP3MT11DC 7602 Price Electrical Solenoid Operator Enables local and remote switching (ON, OFF and reset). Unique bistable latch allows device to operate with only one solenoid Padlockable in OFF position Accessories for Electronic Breakers Accessory Description For Use With… Catalog Number Price Electronic Trip Units STK2 23158 Solid-State Portable Test Kit for Electronic Trip Units Provides performance verification of electronic trip units Operating voltage 120V, 50/60Hz CPRO-CAT-1109 Discount Code B30 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 copperLogic.com www.barr-thorp.com 75 Accessories K-series Miscellaneous Accessories Accessory Description Terminal Side For use with… Catalog Number Price Protection against accidental contact with line side terminals Priced and packaged in sets of ten. Line K-series TS33LN 140 Protection against accidental contact with load side terminals Priced and packaged in sets of ten. Load K-series TS33LD 140 – K-series IPB3 140 – K-series LKD3 211 – K-series PHB3 211 Used to lock the circuit breaker or switch handle in either the ON or OFF position. Breaker is allowed to trip when blocked in the ON position. Accepts up to three padlocks with 1/4 inch (6 mm) shackles. – K-series PLK3 211 Used to lock the circuit breaker or switch handle in OFF position. Accepts up to three padlocks with 1/4 inch (6 mm) shackles. Left side mounting PLK3LOFF 211 – Right side mounting PLK3ROFF 211 Terminal Shield Interphase Barriers High dielectric insulating plates provide additional electrical clearance between circuit breaker or switch poles Priced and packaged in sets of two. Non-padlockable Handle Block Used to secure the circuit breaker or switch handle in either the ON or OFF position. Breaker is allowed to trip when blocked in the ON position. Secured by a setscrew, handle block deters accidental operation of circuit breaker or switch handle. Padlockable Handle Block Positioned in the cover opening to prevent handle movement Allows one 5/16 inch padlock Padlockable Handle Lock Hasp 76 copperLogic.com Discount Code B30 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 CPRO-CAT-1109 www.barr-thorp.com Accessories K-series Terminal Adapters Accessory Description Thread Size Terminal Side For use with… Catalog Number Line or Load Three pole K-series KPEK3 132 KPR3A 351 KPR3B 351 Price End Cap Kit A threaded adapter to accept a ring terminal or other bolt-on connector to the circuit breaker or switch Imperial 0.312-32 A threaded adapter to accept a ring terminal or other bolt-on connector to the circuit breaker or switch Priced and packaged in sets of three. Imperial .375-16 Keeper Nut Line K-series Load Control Wire Terminal Kits Accessory Description For use with… Catalog Number Price Control Wire Terminal Kit Used to tap off control power from a circuit breaker or switch K-series KCWTK 44 Multi-wire Connectors Accessory Description Max. Amps Wires per Terminal 400 3 Wire Size For use with… Catalog Number Price Multi-wire Connectors Used to distribute the load from the circuit breaker to multiple devices without the use of separate distribution terminal blocks. Priced and packaged in sets of three. CPRO-CAT-1109 14 – 2/0 AWG Cu 3TA400K3K 833 3TA400K6K 1053 K-series 400 6 14 – 3 AWG Cu Discount Code B30 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 copperLogic.com www.barr-thorp.com 77 Accessories K-series Base Mounting Hardware Accessory Description Thread Type Screw Size Mounting For use with… Imperial .250-20 x 1.5 in. Individual K-series Catalog Number Price Base Mounting Hardware For surface mounting of circuit breakers or switches. Includes pan-head screws and lockwashers Mounting hardware is not included with breaker. MHDK3 22 Replacement Terminal Kits Terminals Max. Amp Rating Material Wire Type No. of Conductors Wire Range For use with… Terminals Catalog Number Terminals with Control Wire Price Catalog Number Price Replacement for Standard Terminals (line and load side terminals supplied with breaker) 225 Aluminum Cu / Al 1 #3 – 350 kcmil 35 – 185 mm2 K-series TA300K ➊ 46 – – 350 Aluminum Cu / Al 1 250 – 500 kcmil 120 – 240 mm2 K-series TA350K ➊ 46 – – Two Pole K-series (set of two) Three Pole K-series (set of three) 400 Aluminum Cu / Al 2 2TA400K ➋ 175 2TA400KCW ➋ (set of two) 263 #3/0 – 250 kcmil 95 – 120 mm2 3TA400K ➌ 263 3TA400KCW ➌ (set of three) 386 ➊ Individually priced and packaged. ➋ Priced and packaged in sets of two. If line and load terminals are desired, order two sets. ➌ Priced and packaged in sets of three. If line and load terminals are desired, order two sets. 78 copperLogic.com Discount Code B30 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 CPRO-CAT-1109 www.barr-thorp.com Application Data Time / Current Curves Time/Current Curve For application and coordination purposes only. Based on 40°C ambient, cold start. Connected with four feet of rated wire (75°C) per terminal. Tested in open air with current in all poles. Instantaneous calibration based on single-pole tests. Single pole test data at 25°C based on NEMA procedures (AB 4-2003) for verifying performance of molded case circuit breakers. 1h 2h TM(2)(3)-KLS…, TM(2)(3)-KMS… 10000 7000 5000 3000 2000 1000 700 500 (250 – 400A) 1 min 300 200 (100A) 100 70 50 30 20 Maximum single pole trip times at 25°C (125 – 225A) Maximum Minimum 1 .7 .5 Adjustable Magnetic Trip ±20% Adjustable Magnetic Trip ±10% 10x 3 2 5x .3 .2 .1 .07 .05 Maximum interrupting time .03 .02 .01 .007 .005 500000 700000 1000000 20000 30000 5000 7000 10000 3000 2000 500 700 1000 200 300 .001 50 70 100 .003 .002 200000 300000 Interrupting rating determines end of curve 50000 70000 100000 TIME IN SECONDS 10 7 5 CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING (In) CPRO-CAT-1109 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 copperLogic.com www.barr-thorp.com 79 Application Data Time / Current Curves Time/Current Curve For application and coordination purposes only. Based on 40°C ambient, cold start. Connected with four feet of rated wire (75°C) per terminal. Tested in open air with current in all poles. Instantaneous calibration based on single-pole tests. Single pole test data at 25°C based on NEMA procedures (AB 4-2003) for verifying performance of molded case circuit breakers. 1h 2h TM(2)(3)-KHS… 10000 7000 5000 3000 2000 1000 700 500 (250 – 400A) 1 min 300 200 (100A) 100 70 50 30 20 Maximum single pole trip times at 25°C (125 – 225A) Maximum Minimum 1 .7 .5 Adjustable Magnetic Trip ±20% Adjustable Magnetic Trip ±10% 10x 3 2 5x .3 .2 .1 .07 .05 Maximum interrupting time .03 .02 .01 .007 .005 600V 480V 500000 700000 1000000 20000 30000 5000 7000 10000 3000 2000 500 700 1000 200 300 50 70 100 .001 Interrupting rating determines end of curve 200000 300000 240V .003 .002 50000 70000 100000 TIME IN SECONDS 10 7 5 CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING (In) 80 copperLogic.com This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 CPRO-CAT-1109 www.barr-thorp.com Application Data Time / Current Curves Time/Current Curve For application and coordination purposes only. Based on 40°C ambient, cold start. Connected with four feet of rated wire (75°C) per terminal. Tested in open air with current in all poles. Instantaneous calibration based on single-pole tests. Single pole test data at 25°C based on NEMA procedures (AB 4-2003) for verifying performance of molded case circuit breakers. 2h MF3-K(L)(M)(S)(C)-(250)(400) + KES3125(LS)(LSG)… 10000 9000 8000 7000 6000 Standard Fixed Rating Plug 1h 5000 4000 3000 2000 1000 900 800 700 600 Long Delay Maximum total clearing time 500 400 300 1 min 200 100 90 80 70 Long Delay Minimum total clearing time 60 50 40 30 10 9 8 7 6 2x 5 Short Delay Pick-up Settings Tolerance ±10% 4x TIME IN SECONDS 3x 20 4 5x 8x 3 2 1 .9 .8 .7 6x 1 .9 .8 .7 .6 .4 .3 .3 7x .5 .4 .2 .2 .1 .09 .08 .07 .1 .09 .08 .07 .06 .06 .05 .05 Fixed Instantaneous Override at 4000A .04 .04 .03 .03 .02 .02 Interrupting rating determines end of curve .006 .01 .009 .008 .007 .006 .005 .005 .004 .004 .003 .003 .002 .002 .01 .009 .008 .007 70 .001 100 CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In) CPRO-CAT-1109 200000 50 70000 40 100000 30 50000 20 40000 10 30000 7 20000 5 7000 4 10000 3 5000 2 4000 1 3000 .7 2000 .5 1000 .001 TIME IN SECONDS .6 .5 CURRENT IN AMPERES This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 copperLogic.com www.barr-thorp.com 81 Application Data Time / Current Curves Time/Current Curve For application and coordination purposes only. Based on 40°C ambient, cold start. Connected with four feet of rated wire (75°C) per terminal. Tested in open air with current in all poles. Instantaneous calibration based on single-pole tests. Single pole test data at 25°C based on NEMA procedures (AB 4-2003) for verifying performance of molded case circuit breakers. 2h MF3-K(L)(M)(S)(C)-(250)(400) + KES3125(LSI)(LSIG)… 10000 9000 8000 7000 6000 Standard Fixed Rating Plug 1h 5000 4000 3000 2000 1000 900 800 700 600 Long Delay Maximum total clearing time 500 400 300 1 min 200 100 90 80 70 Long Delay Minimum total clearing time 60 50 40 30 10 9 8 7 6 2x 5 Short Delay Pick-up Settings Tolerance ±10% 4x TIME IN SECONDS 20 6x 4 8x 3 7x 2 1 .9 .8 .7 .6 1 .9 .8 .7 .6 .5 5x 3x .5 .4 .4 300 ms .3 .3 200 ms .2 .2 100 ms .1 .09 .08 .07 .06 I .06 .05 .05 Fixed Instantaneous Override at 4000A .04 .04 .03 .03 .02 .02 Interrupting rating determines end of curve .006 .01 .009 .008 .007 .006 .005 .005 .004 .004 .003 .003 .002 .002 .01 .009 .008 .007 CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In) 70 100 .001 200000 50 70000 40 100000 30 50000 20 40000 10 30000 7 20000 5 7000 4 10000 3 5000 2 4000 1 3000 .7 2000 .5 1000 .001 TIME IN SECONDS .1 .09 .08 .07 CURRENT IN AMPERES 82 copperLogic.com This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 CPRO-CAT-1109 www.barr-thorp.com Application Data Time / Current Curves Time/Current Curve For application and coordination purposes only. Based on 40°C ambient, cold start. Connected with four feet of rated wire (75°C) per terminal. Tested in open air with current in all poles. Instantaneous calibration based on single-pole tests. Single pole test data at 25°C based on NEMA procedures (AB 4-2003) for verifying performance of molded case circuit breakers. 2h MF3-K(L)(M)(S)(C)-(250)(400) + KES3250(LS)(LSG)… 10000 9000 8000 7000 6000 Standard Fixed Rating Plug 1h 5000 4000 3000 2000 1000 900 800 700 600 Long Delay Maximum total clearing time 500 400 300 1 min 200 100 90 80 70 Long Delay Minimum total clearing time 60 50 40 30 10 9 8 7 6 2x 5 Short Delay Pick-up Settings Tolerance ±10% 4x TIME IN SECONDS 3x 20 4 5x 8x 3 2 1 .9 .8 .7 6x 1 .9 .8 .7 .6 .4 .3 .3 7x .5 .4 .2 .2 .1 .09 .08 .07 .1 .09 .08 .07 .06 .06 .05 .05 Fixed Instantaneous Override at 4000A .04 .04 .03 .03 .02 .02 Interrupting rating determines end of curve .006 .01 .009 .008 .007 .006 .005 .005 .004 .004 .003 .003 .002 .002 .01 .009 .008 .007 70 .001 100 CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In) CPRO-CAT-1109 200000 50 70000 40 100000 30 50000 20 40000 10 30000 7 20000 5 7000 4 10000 3 5000 2 4000 1 3000 .7 2000 .5 1000 .001 TIME IN SECONDS .6 .5 CURRENT IN AMPERES This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 copperLogic.com www.barr-thorp.com 83 Application Data Time / Current Curves Time/Current Curve For application and coordination purposes only. Based on 40°C ambient, cold start. Connected with four feet of rated wire (75°C) per terminal. Tested in open air with current in all poles. Instantaneous calibration based on single-pole tests. Single pole test data at 25°C based on NEMA procedures (AB 4-2003) for verifying performance of molded case circuit breakers. 2h MF3-K(L)(M)(S)(C)-(250)(400) + KES3250(LSI)(LSIG)… 10000 9000 8000 7000 6000 Standard Fixed Rating Plug 1h 5000 4000 3000 2000 1000 900 800 700 600 Long Delay Maximum total clearing time 500 400 300 1 min 200 100 90 80 70 Long Delay Minimum total clearing time 60 50 40 30 10 9 8 7 6 2x 5 Short Delay Pick-up Settings Tolerance ±10% 4x TIME IN SECONDS 20 6x 4 8x 3 7x 2 1 .9 .8 .7 .6 1 .9 .8 .7 .6 .5 5x 3x .5 .4 .4 300 ms .3 .3 200 ms .2 .2 100 ms .1 .09 .08 .07 .06 I .06 .05 .05 Fixed Instantaneous Override at 4000A .04 .04 .03 .03 .02 .02 Interrupting rating determines end of curve .006 .01 .009 .008 .007 .006 .005 .005 .004 .004 .003 .003 .002 .002 .01 .009 .008 .007 CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In) 70 100 .001 200000 50 70000 40 100000 30 50000 20 40000 10 30000 7 20000 5 7000 4 10000 3 5000 2 4000 1 3000 .7 2000 .5 1000 .001 TIME IN SECONDS .1 .09 .08 .07 CURRENT IN AMPERES 84 copperLogic.com This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 CPRO-CAT-1109 www.barr-thorp.com Application Data Time / Current Curves Time/Current Curve For application and coordination purposes only. Based on 40°C ambient, cold start. Connected with four feet of rated wire (75°C) per terminal. Tested in open air with current in all poles. Instantaneous calibration based on single-pole tests. Single pole test data at 25°C based on NEMA procedures (AB 4-2003) for verifying performance of molded case circuit breakers. 2h MF3-K(L)(M)(S)(C)-400 + KES3400(LS)(LSG)… 10000 9000 8000 7000 6000 Standard Fixed Rating Plug 1h 5000 4000 3000 2000 1000 900 800 700 600 Long Delay Maximum total clearing time 500 400 300 1 min 200 100 90 80 70 Long Delay Minimum total clearing time 60 50 40 30 10 9 8 7 6 2x 5 Short Delay Pick-up Settings Tolerance ±10% 4x TIME IN SECONDS 3x 20 4 5x 8x 3 2 1 .9 .8 .7 6x 1 .9 .8 .7 .6 .4 .3 .3 7x .5 .4 .2 .2 .1 .09 .08 .07 .1 .09 .08 .07 .06 .06 .05 .05 Fixed Instantaneous Override at 4000A .04 .04 .03 .03 .02 .02 Interrupting rating determines end of curve .006 .01 .009 .008 .007 .006 .005 .005 .004 .004 .003 .003 .002 .002 .01 .009 .008 .007 70 .001 100 CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In) CPRO-CAT-1109 200000 50 70000 40 100000 30 50000 20 40000 10 30000 7 20000 5 7000 4 10000 3 5000 2 4000 1 3000 .7 2000 .5 1000 .001 TIME IN SECONDS .6 .5 CURRENT IN AMPERES This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 copperLogic.com www.barr-thorp.com 85 Application Data Time / Current Curves Time/Current Curve For application and coordination purposes only. Based on 40°C ambient, cold start. Connected with four feet of rated wire (75°C) per terminal. Tested in open air with current in all poles. Instantaneous calibration based on single-pole tests. Single pole test data at 25°C based on NEMA procedures (AB 4-2003) for verifying performance of molded case circuit breakers. 2h MF3-K(L)(M)(S)(C)-400 + KES3400(LSI)(LSIG)… 10000 9000 8000 7000 6000 Standard Fixed Rating Plug 1h 5000 4000 3000 2000 1000 900 800 700 600 Long Delay Maximum total clearing time 500 400 300 1 min 200 100 90 80 70 Long Delay Minimum total clearing time 60 50 40 30 10 9 8 7 6 2x 5 Short Delay Pick-up Settings Tolerance ±10% 4x TIME IN SECONDS 20 6x 4 8x 3 7x 2 1 .9 .8 .7 .6 1 .9 .8 .7 .6 .5 5x 3x .5 .4 .4 300 ms .3 .3 200 ms .2 .2 100 ms .1 .09 .08 .07 I .06 .05 .05 Fixed Instantaneous Override at 4000A .04 .04 .03 .03 .02 .02 Interrupting rating determines end of curve .006 .01 .009 .008 .007 .006 .005 .005 .004 .004 .003 .003 .002 .002 .01 .009 .008 .007 CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In) 70 100 .001 200000 50 70000 40 100000 30 50000 20 40000 10 30000 7 20000 5 7000 4 10000 3 5000 2 4000 1 3000 .7 2000 .5 1000 .001 TIME IN SECONDS .1 .09 .08 .07 .06 CURRENT IN AMPERES 86 copperLogic.com This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 CPRO-CAT-1109 www.barr-thorp.com Application Data Time / Current Curves Time/Current Curve For application and coordination purposes only. Based on 40°C ambient, cold start. Connected with four feet of rated wire (75°C) per terminal. Tested in open air with current in all poles. Instantaneous calibration based on single-pole tests. Single pole test data at 25°C based on NEMA procedures (AB 4-2003) for verifying performance of molded case circuit breakers. 2h MF3-KHS-(250)(400) + KES3125(LS)(LSG)… 10000 9000 8000 7000 6000 Standard Fixed Rating Plug 1h 5000 4000 3000 2000 1000 900 800 700 600 Long Delay Maximum total clearing time 500 400 300 1 min 200 100 90 80 70 Long Delay Minimum total clearing time 60 50 40 30 10 9 8 7 6 2x 5 Short Delay Pick-up Settings Tolerance ±10% 4x TIME IN SECONDS 3x 20 4 5x 8x 3 2 1 .9 .8 .7 6x 1 .9 .8 .7 .6 .4 .3 .3 7x .5 .4 .2 .2 .1 .09 .08 .07 .1 .09 .08 .07 .06 .06 .05 .05 Fixed Instantaneous Override at 4000A .04 .04 .03 .03 .02 .02 600V AC .01 .009 .008 .007 .01 .009 .008 .007 .006 480V AC .006 .005 .005 .004 240V AC .004 .003 .003 Interrupting rating determines end of curve .002 70 .001 100 CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In) CPRO-CAT-1109 .002 200000 50 70000 40 100000 30 50000 20 40000 10 30000 7 20000 5 7000 4 10000 3 5000 2 4000 1 3000 .7 2000 .5 1000 .001 TIME IN SECONDS .6 .5 CURRENT IN AMPERES This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 copperLogic.com www.barr-thorp.com 87 Application Data Time / Current Curves Time/Current Curve For application and coordination purposes only. Based on 40°C ambient, cold start. Connected with four feet of rated wire (75°C) per terminal. Tested in open air with current in all poles. Instantaneous calibration based on single-pole tests. Single pole test data at 25°C based on NEMA procedures (AB 4-2003) for verifying performance of molded case circuit breakers. 2h MF3-KHS-(250)(400) + KES3125(LSI)(LSIG)… 10000 9000 8000 7000 6000 Standard Fixed Rating Plug 1h 5000 4000 3000 2000 1000 900 800 700 600 Long Delay Maximum total clearing time 500 400 300 1 min 200 100 90 80 70 Long Delay Minimum total clearing time 60 50 40 30 10 9 8 7 6 2x 5 Short Delay Pick-up Settings Tolerance ±10% 4x TIME IN SECONDS 20 6x 4 8x 3 7x 2 1 .9 .8 .7 .6 1 .9 .8 .7 .6 .5 5x 3x .5 .4 .4 300 ms .3 .3 200 ms .2 .2 100 ms .1 .09 .08 .07 .06 I .06 .05 .05 Fixed Instantaneous Override at 4000A .04 .04 .03 .03 .02 .02 600V AC .01 .009 .008 .007 .01 .009 .008 .007 .006 480V AC .006 .005 .005 .004 240V AC Interrupting rating determines end of curve .002 100 .002 .001 200000 70 70000 50 100000 40 50000 30 40000 20 30000 10 20000 7 7000 5 10000 4 5000 3 4000 2 3000 1 2000 .7 1000 .5 CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In) .004 .003 .003 .001 TIME IN SECONDS .1 .09 .08 .07 CURRENT IN AMPERES 88 copperLogic.com This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 CPRO-CAT-1109 www.barr-thorp.com Application Data Time / Current Curves Time/Current Curve For application and coordination purposes only. Based on 40°C ambient, cold start. Connected with four feet of rated wire (75°C) per terminal. Tested in open air with current in all poles. Instantaneous calibration based on single-pole tests. Single pole test data at 25°C based on NEMA procedures (AB 4-2003) for verifying performance of molded case circuit breakers. 2h MF3-KHS-(250)(400) + KES3250(LS)(LSG)… 10000 9000 8000 7000 6000 Standard Fixed Rating Plug 1h 5000 4000 3000 2000 1000 900 800 700 600 Long Delay Maximum total clearing time 500 400 300 1 min 200 100 90 80 70 Long Delay Minimum total clearing time 60 50 40 30 10 9 8 7 6 2x 5 Short Delay Pick-up Settings Tolerance ±10% 4x TIME IN SECONDS 3x 20 4 5x 8x 3 2 1 .9 .8 .7 6x 1 .9 .8 .7 .6 .4 .3 .3 7x .5 .4 .2 .2 .1 .09 .08 .07 .1 .09 .08 .07 .06 .06 .05 .05 Fixed Instantaneous Override at 4000A .04 .04 .03 .03 .02 .02 600V AC .01 .009 .008 .007 .01 .009 .008 .007 .006 480V AC .006 .005 .005 .004 240V AC .004 .003 .003 Interrupting rating determines end of curve .002 70 .001 100 CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In) CPRO-CAT-1109 .002 200000 50 70000 40 100000 30 50000 20 40000 10 30000 7 20000 5 7000 4 10000 3 5000 2 4000 1 3000 .7 2000 .5 1000 .001 TIME IN SECONDS .6 .5 CURRENT IN AMPERES This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 copperLogic.com www.barr-thorp.com 89 Application Data Time / Current Curves Time/Current Curve For application and coordination purposes only. Based on 40°C ambient, cold start. Connected with four feet of rated wire (75°C) per terminal. Tested in open air with current in all poles. Instantaneous calibration based on single-pole tests. Single pole test data at 25°C based on NEMA procedures (AB 4-2003) for verifying performance of molded case circuit breakers. 2h MF3-KHS-(250)(400) + KES3250(LSI)(LSIG)… 10000 9000 8000 7000 6000 Standard Fixed Rating Plug 1h 5000 4000 3000 2000 1000 900 800 700 600 Long Delay Maximum total clearing time 500 400 300 1 min 200 100 90 80 70 Long Delay Minimum total clearing time 60 50 40 30 10 9 8 7 6 2x 5 Short Delay Pick-up Settings Tolerance ±10% 4x TIME IN SECONDS 20 6x 4 8x 3 7x 2 1 .9 .8 .7 .6 1 .9 .8 .7 .6 .5 5x 3x .5 .4 .4 300 ms .3 .3 200 ms .2 .2 100 ms .1 .09 .08 .07 .06 I .06 .05 .05 Fixed Instantaneous Override at 4000A .04 .04 .03 .03 .02 .02 600V AC .01 .009 .008 .007 .01 .009 .008 .007 .006 480V AC .006 .005 .005 .004 240V AC Interrupting rating determines end of curve .002 100 .002 .001 200000 70 70000 50 100000 40 50000 30 40000 20 30000 10 20000 7 7000 5 10000 4 5000 3 4000 2 3000 1 2000 .7 1000 .5 CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In) .004 .003 .003 .001 TIME IN SECONDS .1 .09 .08 .07 CURRENT IN AMPERES 90 copperLogic.com This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 CPRO-CAT-1109 www.barr-thorp.com Application Data Time / Current Curves Time/Current Curve For application and coordination purposes only. Based on 40°C ambient, cold start. Connected with four feet of rated wire (75°C) per terminal. Tested in open air with current in all poles. Instantaneous calibration based on single-pole tests. Single pole test data at 25°C based on NEMA procedures (AB 4-2003) for verifying performance of molded case circuit breakers. 2h MF3-KHS-400 + KES3400(LS)(LSG)… 10000 9000 8000 7000 6000 Standard Fixed Rating Plug 1h 5000 4000 3000 2000 1000 900 800 700 600 Long Delay Maximum total clearing time 500 400 300 1 min 200 100 90 80 70 Long Delay Minimum total clearing time 60 50 40 30 10 9 8 7 6 2x 5 Short Delay Pick-up Settings Tolerance ±10% 4x TIME IN SECONDS 3x 20 4 5x 8x 3 2 1 .9 .8 .7 6x 1 .9 .8 .7 .6 .4 .3 .3 7x .5 .4 .2 .2 .1 .09 .08 .07 .1 .09 .08 .07 .06 .06 .05 .05 Fixed Instantaneous Override at 4000A .04 .04 .03 .03 .02 .02 600V AC .01 .009 .008 .007 .01 .009 .008 .007 .006 480V AC .006 .005 .005 .004 240V AC .004 .003 .003 Interrupting rating determines end of curve .002 70 .001 100 CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In) CPRO-CAT-1109 .002 200000 50 70000 40 100000 30 50000 20 40000 10 30000 7 20000 5 7000 4 10000 3 5000 2 4000 1 3000 .7 2000 .5 1000 .001 TIME IN SECONDS .6 .5 CURRENT IN AMPERES This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 copperLogic.com www.barr-thorp.com 91 Application Data Time / Current Curves Time/Current Curve For application and coordination purposes only. Based on 40°C ambient, cold start. Connected with four feet of rated wire (75°C) per terminal. Tested in open air with current in all poles. Instantaneous calibration based on single-pole tests. Single pole test data at 25°C based on NEMA procedures (AB 4-2003) for verifying performance of molded case circuit breakers. 2h MF3-KHS-400 + KES3400(LSI)(LSIG)… 10000 9000 8000 7000 6000 Standard Fixed Rating Plug 1h 5000 4000 3000 2000 1000 900 800 700 600 Long Delay Maximum total clearing time 500 400 300 1 min 200 100 90 80 70 Long Delay Minimum total clearing time 60 50 40 30 10 9 8 7 6 2x 5 Short Delay Pick-up Settings Tolerance ±10% 4x TIME IN SECONDS 20 6x 4 8x 3 7x 2 1 .9 .8 .7 .6 1 .9 .8 .7 .6 .5 5x 3x .5 .4 .4 300 ms .3 .3 200 ms .2 .2 100 ms .1 .09 .08 .07 .06 I .06 .05 .05 Fixed Instantaneous Override at 4000A .04 .04 .03 .03 .02 .02 TIME IN SECONDS .1 .09 .08 .07 600V AC .01 .009 .008 .007 .01 .009 .008 .007 .006 480V AC .006 .005 .005 .004 240V AC Interrupting rating determines end of curve .002 CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In) 70 100 .002 .001 200000 50 70000 40 100000 30 50000 20 40000 10 30000 7 20000 5 7000 4 10000 3 5000 2 4000 1 3000 .7 2000 .5 1000 .001 .004 .003 .003 CURRENT IN AMPERES 92 copperLogic.com This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 CPRO-CAT-1109 www.barr-thorp.com Application Data Time / Current Curves Time/Current Curve For application and coordination purposes only. Based on 40°C ambient, cold start. Connected with four feet of rated wire (75°C) per terminal. Tested in open air with current in all poles. Instantaneous calibration based on single-pole tests. Single pole test data at 25°C based on NEMA procedures (AB 4-2003) for verifying performance of molded case circuit breakers. 2h KES3125(LSG)(LSIG)… 10000 9000 8000 7000 6000 1h 5000 4000 3000 2000 1000 900 800 700 600 500 400 300 1 min 200 100 90 80 70 60 50 40 30 3x IG 10 9 8 7 6 5 4x IG TIME IN SECONDS 20 4 Short Delay Pick-up Settings Tolerance ±10% 2 5x IG 2x IG 3 1 .9 .8 .7 .6 500 ms .5 .4 300 ms .3 150 ms .2 .1 .09 .08 .07 I .06 .05 .04 .03 .02 .01 .009 .008 .007 .006 .005 .004 .003 .002 .001 .5 .7 1 2 3 4 5 7 10 20 30 40 50 70 100 GROUND CURRENT IN MULTIPLES OF (IG) = 25A CPRO-CAT-1109 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 copperLogic.com www.barr-thorp.com 93 Application Data Time / Current Curves Time/Current Curve For application and coordination purposes only. Based on 40°C ambient, cold start. Connected with four feet of rated wire (75°C) per terminal. Tested in open air with current in all poles. Instantaneous calibration based on single-pole tests. Single pole test data at 25°C based on NEMA procedures (AB 4-2003) for verifying performance of molded case circuit breakers. 2h KES3250(LSG)(LSIG)… 10000 9000 8000 7000 6000 1h 5000 4000 3000 2000 1000 900 800 700 600 500 400 300 1 min 200 100 90 80 70 60 50 40 30 3x IG 10 9 8 7 6 5 4x IG 1x IG TIME IN SECONDS 20 4 Short Delay Pick-up Settings Tolerance ±10% 2 5x IG 2x IG 3 1 .9 .8 .7 .6 500 ms .5 .4 300 ms .3 .2 150 ms .1 .09 .08 .07 I .06 .05 .04 .03 .02 .01 .009 .008 .007 .006 .005 .004 .003 .002 .001 .5 .7 1 2 3 4 5 7 10 20 30 40 50 70 100 GROUND CURRENT IN MULTIPLES OF (IG) = 50A 94 copperLogic.com This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 CPRO-CAT-1109 www.barr-thorp.com Application Data Time / Current Curves Time/Current Curve For application and coordination purposes only. Based on 40°C ambient, cold start. Connected with four feet of rated wire (75°C) per terminal. Tested in open air with current in all poles. Instantaneous calibration based on single-pole tests. Single pole test data at 25°C based on NEMA procedures (AB 4-2003) for verifying performance of molded case circuit breakers. 2h KES3400(LSG)(LSIG)… 10000 9000 8000 7000 6000 1h 5000 4000 3000 2000 1000 900 800 700 600 500 400 300 1 min 200 100 90 80 70 60 50 40 30 3x IG 10 9 8 7 6 5 4x IG 1x IG TIME IN SECONDS 20 4 Short Delay Pick-up Settings Tolerance ±10% 2 5x IG 2x IG 3 1 .9 .8 .7 .6 500 ms .5 .4 300 ms .3 .2 150 ms .1 .09 .08 .07 I .06 .05 .04 .03 .02 .01 .009 .008 .007 .006 .005 .004 .003 .002 .001 .5 .7 1 2 3 4 5 7 10 20 30 40 50 70 100 GROUND CURRENT IN MULTIPLES OF (IG) = 80A CPRO-CAT-1109 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 copperLogic.com www.barr-thorp.com 95 Technical Data cPRO K-series cPRO K-series Circuit Breakers cPRO K-series Molded Case Switches General Standards Dimensions (W x H x D) Two pole Three pole Weight Three pole Mounting …-K(2)(4)L(S)(C)-… CS(2)(3)-KLC-… …-K(2)(4)HS-… UL 489, CSA C22.2 No. 5 [mm] [mm] 140 x 258 x 104 140 x 258 x 104 140 x 258 x 104 140 x 258 x 104 140 x 258 x 104 140 x 258 x 104 [kg] 6.1 6.1 6.1 Rated operational voltage NEMA Permissible ambient temperature DC Interrupting Rating NEMA Time constant T = 8 rms 1 conducting path 2 conducting paths in series AC Interrupting Rating NEMA, Two and Three pole breakers 240 V AC 480 V AC 600 V AC 250 V DC Endurance (operating cycles) Maximum switching frequency Main Conductor Terminal Capacities Terminal type Solid or stranded 70 – 225 Amps 250 – 350 Amps 400 Amps Tightening torque for box terminals 70 – 225 Amps 250 – 350 Amps 400 Amps K2: 250 K4: 400 K2: 250 K4: 400 K2: 250 K4: 400 600 0 … 40 °C / 32 … 104 °F 600 0 … 40 °C / 32 … 104 °F 600 0 … 40 °C / 32 … 104 °F [kA] [kA] 10 22 10 22 10 22 [kA] [kA] [kA] [kA] 65 35 25 10 8000 240 100 65 35 22 8000 240 200 100 50 22 8000 240 box terminals box terminals box terminals [AWG] [AWG] [AWG] #3 – 350 MCM 250 – 500 MCM 2x (#3/0 – 250 MCM) #3 – 350 MCM 250 – 500 MCM 2x (#3/0 – 250 MCM) #3 – 350 MCM 250 – 500 MCM 2x (#3/0 – 250 MCM) [lbs-in] [lbs-in] [lbs-in] 275 375 275 275 375 275 275 375 275 [V AC] [°C / °F] 250 V DC 250 V DC 90 90 [A] 90 90 Maximum rated current In Two and Three pole …-K(2)(4)M(S)(C)-… CS(2)(3)-KMC-… [per hour] 96 copperLogic.com This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 CPRO-CAT-1109 www.barr-thorp.com Technical Data cPRO K-series cPRO K-series Circuit Breakers cPRO K-series Molded Case Switches Auxiliary Switches Maximum rated voltage AC DC Rated operational current - AC 600 V Rated operational current - DC 125 V 240 V Undervoltage Releases Response voltage - AC, 50/60 Hz 12V Dropout Min Dropout Max Pickup Max 24V Dropout Min Dropout Max Pickup Max 48 – 60V Dropout Min Dropout Max Pickup Max 110 – 127V Dropout Min Dropout Max Pickup Max 208 – 240V Dropout Min Dropout Max Pickup Max 380 – 480V Dropout Min Dropout Max Pickup Max Power consumption - AC, 50/60 Hz 12V 24V 48V 60V 110V 120V 127V 208V 220V 240V 380V 415V 440V 480V CPRO-CAT-1109 …-K(2)(4)L(S)(C)-… CS(2)(3)-KLC-… …-K(2)(4)M(S)(C)-… CS(2)(3)-KMC-… …-K(2)(4)HS-… [V] [V] 600 250 600 250 600 250 [A] 6 6 6 [A] [A] 0.5 0.25 0.5 0.25 0.5 0.25 [V] [V] [V] 4.2 8.4 10.2 4.2 8.4 10.2 4.2 8.4 10.2 [V] [V] [V] 8.4 16.8 20.4 8.4 16.8 20.4 8.4 16.8 20.4 [V] [V] [V] 21.0 33.6 40.8 21.0 33.6 40.8 21.0 33.6 40.8 [V] [V] [V] 44.5 77.0 93.5 44.5 77.0 93.5 44.5 77.0 93.5 [V] [V] [V] 85.0 145.6 176.8 85.0 145.6 176.8 85.0 145.6 176.8 [V] [V] [V] 168.0 266.0 323.0 168.0 266.0 323.0 168.0 266.0 323.0 [VA] [VA] [VA] [VA] [VA] [VA] [VA] [VA] [VA] [VA] [VA] [VA] [VA] [VA] 1.9 3.9 2.5 3.8 1.8 2.1 2.4 2.7 3.1 3.8 3.4 4.0 4.6 5.4 1.9 3.9 2.5 3.8 1.8 2.1 2.4 2.7 3.1 3.8 3.4 4.0 4.6 5.4 1.9 3.9 2.5 3.8 1.8 2.1 2.4 2.7 3.1 3.8 3.4 4.0 4.6 5.4 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 copperLogic.com www.barr-thorp.com 97 Technical Data cPRO K-series cPRO K-series Circuit Breakers cPRO K-series Molded Case Switches Undervoltage Releases (continued) Response voltage - DC 12V Dropout Min Dropout Max Pickup Max 24V Dropout Min Dropout Max Pickup Max 48 – 60V Dropout Min Dropout Max Pickup Max 110 – 125V Dropout Min Dropout Max Pickup Max 220 – 250V Dropout Min Dropout Max Pickup Max Power consumption - DC 12V 24V 48V 60V 110V 120V 125V 220V 250V Shunt Trips Minimum operating voltage - AC, 50/60 Hz 12 – 60V 110 – 240V 380 – 440V 480 – 600V Power consumption - AC, 50/60 Hz 12V 24V 48V 60V 110V 120V 127V 208V 220V 240V 380V 400V 415V 440V 480V 525V 550V 600V …-K(2)(4)L(S)(C)-… CS(2)(3)-KLC-… …-K(2)(4)M(S)(C)-… CS(2)(3)-KMC-… …-K(2)(4)HS-… [V] [V] [V] 4.2 8.4 10.2 4.2 8.4 10.2 4.2 8.4 10.2 [V] [V] [V] 8.4 16.8 20.4 8.4 16.8 20.4 8.4 16.8 20.4 [V] [V] [V] 21.0 33.6 40.8 21.0 33.6 40.8 21.0 33.6 40.8 [V] [V] [V] 44.5 77.0 93.5 44.5 77.0 93.5 44.5 77.0 93.5 [V] [V] [V] 87.5 154.0 187.0 87.5 154.0 187.0 87.5 154.0 187.0 [VA] [VA] [VA] [VA] [VA] [VA] [VA] [VA] [VA] 1.6 3.1 2.0 3.1 1.6 1.9 2.2 3.1 4.0 1.6 3.1 2.0 3.1 1.6 1.9 2.2 3.1 4.0 1.6 3.1 2.0 3.1 1.6 1.9 2.2 3.1 4.0 [V] [V] [V] [V] 9 60 285 360 9 60 285 360 9 60 285 360 [VA] [VA] [VA] [VA] [VA] [VA] [VA] [VA] [VA] [VA] [VA] [VA] [VA] [VA] [VA] [VA] [VA] [VA] 45 200 830 1280 100 120 140 420 470 550 95 108 120 136 40 50 50 70 45 200 830 1280 100 120 140 420 470 550 95 108 120 136 40 50 50 70 45 200 830 1280 100 120 140 420 470 550 95 108 120 136 40 50 50 70 98 copperLogic.com This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 CPRO-CAT-1109 www.barr-thorp.com Technical Data cPRO K-series cPRO K-series Circuit Breakers cPRO K-series Molded Case Switches Shunt Trips (continued) Minimum operating voltage - DC 12 – 60V 110 – 125V 220 – 250V Power consumption - DC 12V 24V 48V 60V 110V 120V 125V 220V 250V CPRO-CAT-1109 …-K(2)(4)L(S)(C)-… CS(2)(3)-KLC-… …-K(2)(4)M(S)(C)-… CS(2)(3)-KMC-… …-K(2)(4)HS-… [V] [V] [V] 8.4 77 154 8.4 77 154 8.4 77 154 [VA] [VA] [VA] [VA] [VA] [VA] [VA] [VA] [VA] 35 170 710 1105 110 130 140 41 54 35 170 710 1105 110 130 140 41 54 35 170 710 1105 110 130 140 41 54 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 copperLogic.com www.barr-thorp.com 99 Dimensions cPRO K-series Circuit Breakers Dimensions are in inches (millimeters). Not intended for manufacturing purposes. TM2-K…; MF2-K…; CS2-K…; TM3-K…; MF3-K…; ET3-K…; CS3-K… 4.313 (109.55) 5.490(139.43) 1.719 (43.66) .625 (15.88) 3.813 (96.85) ON 8.875 (225.43) 10.125 (257.18) OFF CL Handle 3.875 R (98.42) R 1.250 (31.75) 4.782(121.46) 1.160 (29.49) 4.062 (103.17) Dimensions for Extended Terminals and Barrier Style Nos. 4212B60G02, 4212B61G02 and 1492D24H01 .062 (1.57) 4.95 (125.7) .875 (22.25) 1.063 (27.00) 3.812 (96.82) 2.375 (60.33) 100 copperLogic.com This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 CPRO-CAT-1109 www.barr-thorp.com Dimensions cPRO K-series Drilling Plans Dimensions are in inches (millimeters). Not intended for manufacturing purposes. TM2-K…; MF2-K…; CS2-K…; TM3-K…; MF3-K…; ET3-K…; CS3-K… Front Connected Front Cover Cutout Rear Connected .344 R (8.74) R .844 (21.44) .875(22.23) Dia. (6 Places) (Omit 2 Center Holes for 2-Pole) 3.750 (95.25) CL Breaker Handle .188 R (4.77) R .828 (21.03) 4.922 (125.02) 1.640 (41.66) 1.250 (31.75) 5.141 (130.58) 8.438 (214.33) CL Breaker Handle 1.313 (33.34) 2.625 (66.68) 3.734 (94.84) 3.516 (89.31) 2.391 (60.73) 8.875 (225.42) CL Breaker Handle 4.782 (121.46) .250-20 (M6) 4 Holes CPRO-CAT-1109 1.719 (43.66) .859 (21.83) This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 1.719 (43.66) 1.719 (43.66) copperLogic.com www.barr-thorp.com 101 cPRO Molded Case Circuit Breakers Notes 102 copperLogic.com This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 CPRO-CAT-1109 www.barr-thorp.com Conditions of Sale and Shipment Valid in United States of America Note: The following terms are for general information only. All conditions of sales are subject to change and are valid as determined in the latest terms and conditions publication of CopperLogic, Inc. (referred to herein after as “The Company”). shipment other than that selected by the Company, the purchaser will be billed accordingly. No credits will be allowed in lieu of transportation in the case of pickups at the Company’s warehouses, branches, or factory. No transportation charges can be deducted from a selling price. Air freight, water freight, heavy lift charges, pier delivery charges, wharfage, marine insurance and the cost of stevedoring are chargeable to the purchaser. These terms include shipments to Alaska, Hawaii, Puerto Rico, and the Virgin Islands. 1. Acceptance of orders All orders are subject to final acceptance by an authorized representative of the Company and are subject to the Company’s terms and conditions in effect at the time of acceptance. The Company takes exception to any other terms and conditions except for such terms and conditions as the Company may expressly accept in writing. 9. Packing other than standard If other than standard commercial packing is required the cost of such special packing (determinable only after packing is completed) will be charged to the purchaser. Export packing shall be considered as packing other than standard. 2. Prices Prices and discounts as shown in the company’s publications are subject to change without notice. In the event of a net price change, the price of equipment on order but unshipped will be the price in effect on the date of shipment. In no case will the amount of a price increase exceed 10% of the price at which the order was accepted, except that, if the delivery is delayed upon instructions from the purchaser, prices shall be those in effect when the instructions are received to proceed with the order. Price reductions shall only apply to unshipped portions of outstanding orders. Any addition or alteration to an outstanding order will be accepted at prices in effect when the addition or alteration is accepted. Applicable taxes are additional. 3. Quotations All quotations are in accordance with the Company’s interpretation of plans and specifications and only material shown on the Company’s quotations are included. Written quotations automatically expire thirty (30) days from the date of issue unless sooner terminated by notice. Quotations are subject to all existing or future limitations and regulations issued by any government agency. In the event that a quotation is not accepted in its entirety, the Company reserves the right to decline any parts of the order based on such quotation. 10. Acceptance of orders The purchaser will be responsible for any applicable export license and all associated costs involved with said license on any export project. 11. Export Control Equipment and associated materials supplied or licensed under this transaction may be subject to various export laws and regulations. It is the responsibility of the exporter to comply with all such laws and regulations. 12. Responsibility and Title Title in the equipment shall remain with the Company as security only and until full payment is received. Risk of loss for the equipment shall pass to purchaser upon shipment from F.O.B. point of shipment or date of invoicing, which ever is sooner. All Accounting, clerical or other errors are subject to correction. 13. Loss or Damage in Transit The Company does not hold itself responsible for any loss, damage, (obvious or concealed) or pilferage sustained in transit. Claims of such character should be made, by the purchaser, promptly against the transportation company. If the Company is notified of such claims, the Company will offer to lend assistance to secure adjustment. The Company employs experienced packers and cannot be held responsible for breakage that occurs after the Company’s securing the “Received in Good Order” receipt from the transportation company. 4. Minimum Billing Orders amounting to less than $100.00 net will be billed at $100.00 plus the transportation charge, at a minimum of $25.00. 14. Return of Merchandise No equipment may be returned unless authorization has been obtained from an authorized representative of the Company. Unauthorized returns of equipment cannot be accepted. 5. Terms - Regular Terms to purchasers of satisfactory credit are: 30 days net from the date of invoice. Cash discounts, when applicable, are indicated on the face of the Company’s invoice. To avoid delay in filling orders purchasers without previous experience with the Company should include credit references with the first order, or send a certified check or money order. Any amount owed to the Company becomes due and payable immediately in case of change of ownership of the purchaser, attachment or execution against the purchaser or it’s representatives, unless the Company otherwise agrees. A. To be returned for credit Only unused equipment of current design may be returned for credit. Where a purchaser returns equipment for reasons of his own, a minimum restocking charge of 20% of billing, plus transportation charges, will be made. Any cost incurred in putting the equipment into saleable condition shall also be deducted from allowed credit. If return of equipment is made necessary by fault of the Company, full credit will be allowed including transportation charges. 6. Payments Payments should be made to the address indicated on the invoice, or to CopperLogic, Inc., PO Box 62073, Houston, TX 77205. 7. Delivery The Company reserves the right to make delivery in installments, unless otherwise expressly stipulated in the contract for sale; and all such installments when separately invoiced shall be paid for when due per invoice, without regard to subsequent deliveries. Delay in delivery of any installment shall not relieve the purchaser of its obligations to accept remaining deliveries. Shipments delayed to accommodate the purchaser will be invoiced upon completion of fabrication and additional charges for warehousing, trucking and other incidental expenses created by the delay will be at the expense of the purchaser. Delivery is dependent upon prompt receipt of all specifications, final approved prints and any other details essential to the proper execution of the purchaser’s order. Claims for shortages or other errors must be reported in writing to the Company within 10 days after receipt of shipment. Failure to do so will constitute a waiver of all claims by the purchaser. 8. Shipping Terms The method and route of shipment is determined by the Company. All merchandise orders of $500.00 net or more will be shipped F.O.B. CopperLogic’s warehouse, freight prepaid, best way ground transportation. All engineered equipment orders will be shipped F.O.B. CopperLogic’s loading dock, freight not allowed. When purchaser specifies a method or routing of CPRO-CAT-1109 B. To be returned for replacement If the equipment is under guarantee and the return is made necessary because of defect in material and/or workmanship, providing permission is obtained from the Company for its return, the Company will replace the defective goods “no charge”, and will assume the transportation charges. C. Custom-built equipment Equipment built based upon purchaser specification cannot be returned for credit. 15. Cancellations: Any order placed with the Company can be canceled by the purchaser provided that: a) the cancellation is agreed to in writing by the Company; and b) the purchaser agrees to compensate the Company for engineering, fabrication, outside sourcing of devices and any other demonstrated expenses incurred or commitments made by the Company up to the date of notice of cancellation and all charges incurred by the Company in respect of the cancellation. 16. Force Majeure The Company shall not be liable for any delay in the performance of orders or contracts or in the delivery or shipment of equipment or for any loss and/or damages suffered by purchaser by reason of such delay when such delay is directly or indirectly caused by fire, floods, accidents, riots, acts of God, war, invasion, sabotage, terrorism and governmental interference or embargoes, strikes, labor difficulties, shortage of labor, fuel, power, materials or supplies This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 copperLogic.com www.barr-thorp.com 103 Conditions of Sale and Shipment Valid in United States of America or any other cause beyond the Company’s reasonable control. In any event, the Company shall not be liable for special or consequential damages for loss of use. Should such a delay occur, the delivery date shall be extended as may be necessary to compensate for the delay. The Company shall not be liable for any change of dimensions, weights and materials as long as the change is nonessential for the proper performance of the product. 17. Guarantee The Company guarantees for a period of one (1) year from the date of the Company invoice that equipment furnished under the order will be of merchantable quality, free from defects in material, workmanship and design each as determined, at the date of shipment by the Company by generally recognized, applicable and accepted practices and procedures in the industry including any specifications furnished by the purchaser and agreed to in writing by the Company for incorporation into the equipment. Satisfaction of this guarantee, consistent with other provisions herein, will be limited to the replacement or repair or modification of, or issuance of a credit for, the equipment involved at the Company’s option, with the Company to determine the availability of service personnel and purchaser to pay associated service expenses: such guarantee satisfaction available only if: (a) the Company is promptly notified in writing upon discovery of an alleged defect and (b) the company’s examination of the subject equipment discloses, to the Company’s satisfaction, that any defect has not been caused by misuse, neglect, improper installation, improper operation, improper maintenance, repair or alteration, accident, or unusual deterioration or degradation of the equipment parts, thereof due to physical environment or due to electrical or electromagnetic noise environment. THIS GUARANTEE IS IN LIEU OF ALL OTHER GUARANTEES WHETHER EXPRESSED, IMPLIED OR STATUTORY, INCLUDING IMPLIED GUARANTEES OF MERCHANTABILITY OR FITNESS and thereby excludes certifications or the like for equipment performance, use or design with respect to any standard, regulation or the like (unless and to the extent independently approved in writing by the Company) AND EXTENDS ONLY TO THE CUSTOMER OR PURCHASER PURCHASING FROM THE COMPANY OR AN AUTHORIZED COMPANY DISTRIBUTOR. 18. Limitation of Liability IN NO EVENT WILL THE COMPANY BE LIABLE FOR INCIDENTAL, INDIRECT OR AS IS CONSEQUENTIAL DAMAGES OF ANY KIND. THE COMPANY’S MAXIMUM CUMULATIVE LIABILITY RELATIVE TO ALL OTHER CLAIMS AND LIABILITIES, INCLUDING THAT WITH RESPECT TO DIRECT DAMAGES AND OBLIGATIONS UNDER ANY INDEMNITY, WHETHER OR NOT INSURED, WILL NOT EXCEED THE COST OF THE PRODUCTS GIVING RISE TO THE CLAIM OR LIABILITY. THE COMPANY DISCLAIMS ALL LIABILITY RELATIVE TO GRATUITOUS INFORMATION OR ASSISTANCE PROVIDED BY, BUT NOT REQUIRED OF THE COMPANY HEREUNDER. ANY ACTION AGAINST THE COMPANY MUST BE BROUGHT WITHIN EIGHTEEN (18) MONTHS AFTER THE CAUSE OF ACTIONS ACCRUES. THESE DISCLAIMERS AND LIMITATIONS OF LIABILITY WILL APPLY REGARDLESS OF ANY OTHER CONTRARY PROVISION OF THE AGREEMENT AND REGARDLESS OF THE FORM OF ACTION, WHETHER IN CONTRACT, TORT OR OTHERWISE AND FURTHER WILL EXTEND TO THE BENEFIT OF THE COMPANY’S VENDORS, APPOINTED DISTRIBUTORS AND OTHER AUTHORIZED RESELLERS AS THIRD-PARTY BENEFICIARIES. EACH PROVISION IN THE AGREEMENT WHICH PROVIDES FOR A LIMITATION OF LIABILITY, DISCLAIMER OF WARRANTY OR CONDITION OR EXCLUSION OF DAMAGES IS SEVERABLE AND INDEPENDENT OF ANY OTHER PROVISION AND IS TO BE ENFORCED AS SUCH. 19. Penalty Clauses The Company will not accept any liability for penalty clauses of any kind, written or implied, unless specifically approved in writing by the Company. 20. Nuclear Applications Unless otherwise agreed to in writing by a duly authorized representative of the Company, equipment sold hereunder are not intended for use in connection with, any nuclear facility or activity. The Company disclaims all liability for any nuclear damage, injury or contamination and purchaser shall indemnify the Company against such liability, whether as a result of breach of contract, warranty, tort (including negligence) or otherwise. The Company shall identify special controls which are manufactured and tested for use in connection with any nuclear installation or activity by the appropriate catalog number. The Company will charge a price addition for control devices sold for nuclear applications. Any questions by purchaser regarding products or pricing should be referred to the Company for clarification. 21. Government Clauses and Contracts No government contract regulations or clauses will apply to the equipment agreement or act to bind the Company unless specifically agreed to by the Company in writing at the Company’s headquarters. Equipment sold or licensed hereunder are not intended to be used, nor should they be used, in any nuclear-related application either as a ”Basic Component” under 10 CFR 21 (United States NRC) or otherwise under similar nuclear laws and regulations of this or any other country. 22. Intellectual Property (not applicable to third-party branded products as is) The Company will defend any suit or proceeding brought against the customer based on a claim that the design or construction of the Products sold or licensed hereunder by the Company infringe any United States or Canadian Patent, Copyright or Mask Work Registration, provided that the customer promptly notifies the Company of any such claim and resulting suit or proceeding, in writing and further provided that, at the Company’s expense, (a) the customer gives the Company the sole right to defend or control the defense of the suit or proceeding including settlement, and (b) the customer provides all necessary information and assistance for that defense. Except for any consequential damages, the Company will pay all costs and damages finally awarded or agreed upon by Sell that are directly related to any such claim. In the event of a charge of infringement the Company’s obligation under the Agreement will be fulfilled if the Company, at its option and expense, either (i) procures for the customer the right to continue using such Products; (ii) replaces the same with non-infringing Products; (iii) modifies the same so as to make them non-infringing: or (iv) accepts the return of any infringing Products and refunds their purchase price, Notwithstanding the foregoing. The Company will have no liability with respect to any claim of infringement to the extent based on a configuration or modification incorporated in the Products at the request of the customer, on any process application into which the Products are integrated by the customer, or on use of the Products in combination with other equipment or products not supplied by the Company. THIS PARAGRAPH SETS FORTH THE COMPANY’S ENTIRE LIABILITY WITH RESPECT TO INTELLECTUAL PROPERTY AN INFRINGEMENT OF PATENTS BY ANY PRODUCTS (INCLUDING SOFTWARE PROGRAMS, EQUIPMENT OR PRODUCTS THEREOF) OR BY THEIR OPERATION, AND IS IN LIEU OF ALL WARRANTIES OR CONDITIONS RELATION TO INFRINGEMENT OR INTELLECTUAL PROPERTY, EITHER EXPRESS OR IMPLIED. 23. Third Party Branded Products THE COMPANY MAKES NO REPRESENTATIONS AND DISCLAIMS ALL WARRANTIES OF ANY KIND, EXPRESS OR IMPLIED, RELATIVE TO ANY THIRD-PARTY BRANDED EQUIPMENT WHICH MAY BE SOLD BY THE COMPANY HEREUNDER. The only warranty associated with such equipment will be that provided directly by the original manufacturer, if any. The Company assumes no post-sale technical support or warranty repair obligation with respect to such equipment, however, at its discretion, the Company may assist the customer in processing warranties or representations made or provided relative to such equipment, which in all cases will be the responsibility of the original equipment solely for the convenience of the purchaser, and the purchaser must make its own determination as to the accuracy and completeness of such information. 24. Disputes The parties will attempt in good faith promptly to resolve any dispute arising out of this transaction by negotiations between representatives who have authority to settle the controversy. If unsuccessful, the parties further will attempt in good faith to settle the dispute by non-binding third-party mediation, with fees and expenses of such mediation apportioned equally to each side. Any dispute not so resolved by negotiation or mediation may then be submitted to a court of competent jurisdiction in accordance with the terms of this transaction. These procedures are the exclusive procedures for the resolution of all such disputes between the parties. 25. Governing Law This transaction and all disputes arising thereunder will be governed by and interpreted in accordance with the internal laws of the state, province or other governmental jurisdiction in which the Company’s principal place of business resides, but specifically excluding its conflict of laws provisions and the provisions of the 1980 UN Convention on Contracts for the International Sales of Goods. 26. Assignment This transaction may not be assigned by either party without the written consent of the other (which consent will not be unreasonably withheld), however, consent will not be required for internal transfers and assignments as between the company and its parent corporations, subsidiaries or affiliates as part of consolidation, merger or other form of corporate reorganization. 27. Language The parties acknowledge that they have required that this transaction be drawn up in English, Les parties reconnaissent avoir exigE la rEdaction en anglais du Contrat. In the event of a conflict between the English and other language versions of this agreement, the English version will prevail. 104 copperLogic.com This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 CPRO-CAT-1109 www.barr-thorp.com Conditions of Sale and Shipment Valid in Canada Note: The following terms are for general information only. All conditions of sales are subject to change and are valid as determined in the latest terms and conditions publication of CopperLogic Ltd. (referred to herein after as “The Company”). 1. Acceptance of orders: All orders are subject to final acceptance by an authorized representative of the Company and are subject to the Company’s terms and conditions in effect at the time of acceptance. The Company takes exception to any other terms and conditions except for such terms and conditions as the Company may expressly accept in writing. 2. Prices: Prices and discounts as shown in the company’s publications are subject to change without notice. In the event of a net price change, the price of equipment on order but unshipped will be the price in effect on the date of shipment. In no case will the amount of a price increase exceed 10% of the price at which the order was accepted, except that, if the delivery is delayed upon instructions from the purchaser, prices shall be those in effect when the instructions are received to proceed with the order. Price reductions shall only apply to unshipped portions of outstanding orders. Any addition or alteration to an outstanding order will be accepted at prices in effect when the addition or alteration is accepted. Applicable taxes are additional. 3. Quotations: All quotations are in accordance with the Company’s interpretation of plans and specifications and only material shown on the Company’s quotations are included. Written quotations automatically expire thirty (30) days from the date of issue unless sooner terminated by notice. Quotations are subject to all existing or future limitations and regulations issued by any government agency. In the event that a quotation is not accepted in its entirety, the Company reserves the right to decline any parts of the order based on such quotation. All Accounting, clerical or other errors are subject to correction. 4. Minimum Billing: Orders amounting to less than $ 100.00 net will be billed at $ 100.00 plus the transportation charge, at a minimum of $25.00. 5. Terms - Regular: Terms to purchasers of satisfactory credit are: 30 days net from the date of invoice. Cash discounts, when applicable, are indicated on the face of the Company’s invoice. To avoid delay in filling orders purchasers without previous experience with the Company should include credit references with the first order, or send a certified check or money order. Any amount owed to the Company becomes due and payable immediately in case of change of ownership of the purchaser, attachment or execution against the purchaser or it’s representatives, unless the Company otherwise agrees. 6. Payments: Payments should be made to the address indicated on the invoice, or to CopperLogic Ltd, 6175 Kenway Drive, Mississauga, Ontario, L5T 2L3. 7. Delivery: The Company reserves the right to make delivery in installments, unless otherwise expressly stipulated in the contract for sale; and all such installments when separately invoiced shall be paid for when due per invoice, without regard to subsequent deliveries. Delay in delivery of any installment shall not relieve the purchaser of its obligations to accept remaining deliveries. Shipments delayed to accommodate the purchaser will be invoiced upon completion of fabrication and additional charges for warehousing, trucking and other incidental expenses created by the delay will be at the expense of the purchaser. Delivery is dependent upon prompt receipt of all specifications, final approved prints and any other details essential to the proper execution of the purchaser’s order. Claims for shortages or other errors must be reported in writing to the Company within 10 days after receipt of shipment. Failure to do so will constitute a waiver of all claims by the purchaser. 8. Shipping Terms: The method and route of shipment is determined by the Company. All merchandise orders of $500.00 net or more will be shipped F.O.B. CopperLogic’s warehouse, freight prepaid, best way ground transportation. All engineered equipment orders will be shipped F.O.B. CopperLogic’s loading dock, freight not allowed. When purchaser specifies a method or routing of shipment other than that selected by the Company, the purchaser will be billed accordingly. No credits will be allowed in lieu of transportation in the case of pickups at the Company’s CPRO-CAT-1109 warehouses, branches, or factory. No transportation charges can be deducted from a selling price. Air freight, water freight, heavy lift charges, pier delivery charges, wharfage, marine insurance and the cost of stevedoring are chargeable to the purchaser. 9. Packing other than standard: If other than standard commercial packing is required the cost of such special packing (determinable only after packing is completed) will be charged to the purchaser. Export packing shall be considered as packing other than standard. 10. Acceptance of orders: The purchaser will be responsible for any applicable export license and all associated costs involved with said license on any export project. 11. Export Control Equipment and associated materials supplied or licensed under this transaction may be subject to various export laws and regulations. It is the responsibility of the purchaser to comply with all such laws and regulations. 12. Responsibility and Title: Title in the equipment shall remain with the Company as security only and until full payment is received. Risk of loss for the equipment shall pass to purchaser upon shipment from F.O.B. point of shipment or date of invoicing, which ever is sooner. 13. Loss or Damage in Transit: The Company does not hold itself responsible for any loss, damage, (obvious or concealed) or pilferage sustained in transit. Claims of such character should be made, by the purchaser, promptly against the transportation company. If the Company is notified of such claims, the Company will offer to lend assistance to secure adjustment. The Company employs experienced packers and cannot be held responsible for breakage that occurs after the Company’s securing the “Received in Good Order” receipt from the transportation company. 14. Return of Merchandise: No equipment may be returned unless authorization has been obtained from an authorized representative of the Company and if so authorized is subject to the conditions below. Unauthorized returns of equipment cannot be accepted. A. To be returned for credit: Only unused equipment of current design may be returned for credit. Where a purchaser returns equipment for reasons of his own, a minimum restocking charge of 20% of billing, plus transportation charges, will be made. Any cost incurred in putting the equipment into saleable condition shall also be deducted from allowed credit. If return of equipment is made necessary by fault of the Company, full credit will be allowed including transportation charges. B. To be returned for replacement: If the equipment is under guarantee and the return is made necessary because of defect in material and/or workmanship, the Company will replace the defective goods “no charge”, and will assume the transportation charges. C. Custom-built equipment: Equipment built based upon purchaser specification cannot be returned for credit. 15. Cancellations: Any order placed with the Company can be canceled by the purchaser provided that: a) the cancellation is agreed to in writing by the Company; and b) the purchaser agrees to compensate the Company for engineering, fabrication, outside sourcing of devices and any other demonstrated expenses incurred or commitments made by the Company up to the date of notice of cancellation and all charges incurred by the Company in respect of the cancellation. 16. Force Majeure: The Company shall not be liable for any delay in the performance of orders or contracts or in the delivery or shipment of equipment or for any loss and/or damages suffered by purchaser by reason of such delay when such delay is directly or indirectly caused by fire, floods, accidents, riots, acts of God, war, invasion, sabotage, terrorism and governmental interference or embargoes, strikes, labor difficulties, shortage of labor, fuel, power, materials or supplies or any other cause beyond the Company’s reasonable control. In any event, the Company shall not be liable for special or consequential damages for loss of use. Should such a delay occur, the delivery date shall be extended as may be necessary to compensate for the delay. The Company shall not be liable for any change of dimensions, weights and materials as long as the change is nonessential for the proper performance of the product. This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 copperLogic.com www.barr-thorp.com 105 Conditions of Sale and Shipment Valid in Canada 17. Guarantee: The Company guarantees for a period of one (1) year from the date of the Company invoice that equipment furnished under the order will be of merchantable quality, free from defects in material, workmanship and design each as determined, at the date of shipment by the Company by generally recognized, applicable and accepted practices and procedures in the industry including any specifications furnished by the purchaser and agreed to in writing by the Company for incorporation into the equipment. Satisfaction of this guarantee, consistent with other provisions herein, will be limited to the replacement or repair or modification of, or issuance of a credit for, the equipment involved at the Company’s option, with the Company to determine the availability of service personnel and purchaser to pay associated service expenses: such guarantee satisfaction available only if: (a) the Company is promptly notified in writing upon discovery of an alleged defect and (b) the company’s examination of the subject equipment discloses, to the Company’s satisfaction, that any defect has not been caused by misuse, neglect, improper installation, improper operation, improper maintenance, repair or alteration, accident, or unusual deterioration or degradation of the equipment parts, thereof due to physical environment or due to electrical or electromagnetic noise environment. THIS GUARANTEE IS IN LIEU OF ALL OTHER GUARANTEES WHETHER EXPRESSED, IMPLIED OR STATUTORY, INCLUDING IMPLIED GUARANTEES OF MERCHANTABILITY OR FITNESS and thereby excludes certifications or the like for equipment performance, use or design with respect to any standard, regulation or the like (unless and to the extent independently approved in writing by the Company) AND EXTENDS ONLY TO THE CUSTOMER OR PURCHASER PURCHASING FROM THE COMPANY OR AN AUTHORIZED COMPANY DISTRIBUTOR. 18. Limitation of Liability: IN NO EVENT WILL THE COMPANY BE LIABLE FOR INCIDENTAL, INDIRECT OR AS IS CONSEQUENTIAL DAMAGES OF ANY KIND. THE COMPANY’S MAXIMUM CUMULATIVE LIABILITY RELATIVE TO ALL OTHER CLAIMS AND LIABILITIES, INCLUDING THAT WITH RESPECT TO DIRECT DAMAGES AND OBLIGATIONS UNDER ANY INDEMNITY, WHETHER OR NOT INSURED, WILL NOT EXCEED THE COST OF THE PRODUCTS GIVING RISE TO THE CLAIM OR LIABILITY. THE COMPANY DISCLAIMS ALL LIABILITY RELATIVE TO GRATUITOUS INFORMATION OR ASSISTANCE PROVIDED BY, BUT NOT REQUIRED OF THE COMPANY HEREUNDER. ANY ACTION AGAINST THE COMPANY MUST BE BROUGHT WITHIN EIGHTEEN (18) MONTHS AFTER THE CAUSE OF ACTIONS ACCRUES. THESE DISCLAIMERS AND LIMITATIONS OF LIABILITY WILL APPLY REGARDLESS OF ANY OTHER CONTRARY PROVISION OF THE AGREEMENT AND REGARDLESS OF THE FORM OF ACTION, WHETHER IN CONTRACT, TORT OR OTHERWISE AND FURTHER WILL EXTEND TO THE BENEFIT OF THE COMPANY’S VENDORS, APPOINTED DISTRIBUTORS AND OTHER AUTHORIZED RESELLERS AS THIRD-PARTY BENEFICIARIES. EACH PROVISION IN THE AGREEMENT WHICH PROVIDES FOR A LIMITATION OF LIABILITY, DISCLAIMER OF WARRANTY OR CONDITION OR EXCLUSION OF DAMAGES IS SEVERABLE AND INDEPENDENT OF ANY OTHER PROVISION AND IS TO BE ENFORCED AS SUCH. 19. Penalty Clauses: The Company will not accept any liability for penalty clauses of any kind, written or implied, unless specifically approved in writing by the Company. 20. Nuclear Applications: Unless otherwise agreed to in writing by a duly authorized representative of the Company, equipment sold hereunder are not intended for use in connection with, any nuclear facility or activity. The Company disclaims all liability for any nuclear damage, injury or contamination and purchaser shall indemnify the Company against such liability, whether as a result of breach of contract, warranty, tort (including negligence) or otherwise. Upon authorization by a representative of the Company for sale or use of equipment in a nuclear facility or activity, the Company shall identify special controls which are manufactured and tested for use in connection with any nuclear installation or activity by the appropriate catalog number. The Company will charge a price addition for control devices sold for nuclear applications. Any questions by purchaser regarding products or pricing should be referred to the Company for clarification. 21. Government Clauses and Contracts: No government contract regulations or clauses will apply to the equipment agreement or act to bind the Company unless specifically agreed to by the Company in writing at the Company’s headquarters. Equipment sold or licensed hereunder are not intended to be used, nor should they be used, in any nuclear-related application either as a ”Basic Component” under 10 CFR 21 (United States NRC) or otherwise under similar nuclear laws and regulations of this or any other country. 22. Intellectual Property: (not applicable to third-party branded products as is) The Company will defend any suit or proceeding brought against the customer based on a claim that the design or construction of the Products sold or licensed hereunder by the Com- pany infringe any United States or Canadian Patent, Copyright or Mask Work Registration, provided that the customer promptly notifies the Company of any such claim and resulting suit or proceeding, in writing and further provided that, at the Company’s expense, (a) the customer gives the Company the sole right to defend or control the defense of the suit or proceeding including settlement, and (b) the customer provides all necessary information and assistance for that defense. Except for any consequential damages, the Company will pay all costs and damages finally awarded or agreed upon by the Company that are directly related to any such claim. In the event of a claim of infringement the Company’s obligation under the Agreement will be fulfilled if the Company, at its option and expense, either (i) procures for the customer the right to continue using such Products; (ii) replaces the same with non-infringing Products; (iii) modifies the same so as to make them non-infringing: or (iv) accepts the return of any infringing Products and refunds their purchase price, Notwithstanding the foregoing. The Company will have no liability with respect to any claim of infringement to the extent based on a configuration or modification incorporated in the Products at the request of the customer, on any process application into which the Products are integrated by the customer, or on use of the Products in combination with other equipment or products not supplied by the Company. THIS PARAGRAPH SETS FORTH THE COMPANY’S ENTIRE LIABILITY WITH RESPECT TO INTELLECTUAL PROPERTY AND INFRINGEMENT OF PATENTS BY ANY PRODUCTS (INCLUDING SOFTWARE PROGRAMS, EQUIPMENT OR PRODUCTS THEREOF) OR BY THEIR OPERATION, AND IS IN LIEU OF ALL WARRANTIES OR CONDITIONS RELATION TO INFRINGEMENT OR INTELLECTUAL PROPERTY, EITHER EXPRESS OR IMPLIED. 23. Third Party Branded Products: THE COMPANY MAKES NO REPRESENTATIONS AND DISCLAIMS ALL WARRANTIES OF ANY KIND, EXPRESS OR IMPLIED, RELATIVE TO ANY THIRD-PARTY BRANDED EQUIPMENT WHICH MAY BE SOLD BY THE COMPANY HEREUNDER. The only warranty associated with such equipment will be that provided directly by the original manufacturer, if any. The Company assumes no post-sale technical support or warranty repair obligation with respect to such equipment, however, at its discretion, the Company may assist the customer in processing warranties or representations made or provided relative to such equipment, which in all cases will be the responsibility of the original equipment solely for the convenience of the purchaser, and the purchaser must make its own determination as to the accuracy and completeness of such information. 24. Disputes: The parties will attempt in good faith promptly to resolve any dispute arising out of this transaction by negotiations between representatives who have authority to settle the controversy. If unsuccessful, the parties further will attempt in good faith to settle the dispute by non-binding third-party mediation, with fees and expenses of such mediation apportioned equally to each side. Any dispute not so resolved by negotiation or mediation may then be submitted to a court of competent jurisdiction in accordance with the terms of this transaction. These procedures are the exclusive procedures for the resolution of all such disputes between the parties. 25. Governing Law: This transaction and all disputes arising thereunder will be governed by and interpreted in accordance with the domestic-laws of the Province of Ontario. The provisions of the International Sale of Goods Act, R.S.O. (1990), C.I.10 as amended shall not be applicable to this transaction and are specifically excluded. At the sole discretion of the Company, for the purpose of legal proceedings, this transaction shall be deemed to have been performed in the Province of Ontario and the Courts of the Province of Ontario shall have jurisdiction to entertain any action arising under this transaction. The purchaser hereby attorns to the jurisdiction of the Courts of the Province of Ontario. However, nothing contained herein shall derogate from the right of the Company to proceed in such other jurisdiction as, in its sole discretion, it deems necessary. 26. Assignment: This transaction may not be assigned by either party without the written consent of the other (which consent will not be unreasonably withheld), however, consent will not be required for internal transfers and assignments as between the company and its parent corporations, subsidiaries or affiliates as part of consolidation, merger or other form of corporate reorganization. 27. Language: The parties acknowledge that they have required that this transaction be drawn up in English, Les parties reconnaissent avoir exigE la rEdaction en anglais du Contrat. In the event of a conflict between the English and other language versions of this agreement, the English version will prevail. 106 copperLogic.com This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 CPRO-CAT-1109 www.barr-thorp.com cPRO Molded Case Circuit Breakers Notes CPRO-CAT-1109 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 copperLogic.com www.barr-thorp.com 107 cPRO Molded Case Circuit Breakers Notes 108 copperLogic.com This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 CPRO-CAT-1109 www.barr-thorp.com cPRO Molded Case Circuit Breakers Notes CPRO-CAT-1109 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 copperLogic.com www.barr-thorp.com 109 cPRO Molded Case Circuit Breakers Notes 110 copperLogic.com This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 CPRO-CAT-1109 www.barr-thorp.com cPRO Molded Case Circuit Breakers Notes CPRO-CAT-1109 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 copperLogic.com www.barr-thorp.com 111 cPRO Molded Case Circuit Breakers Notes 112 copperLogic.com This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 CPRO-CAT-1109 www.barr-thorp.com This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com © by CopperLogic Technical and other changes reserved. Publication CPRO-CAT-1109 Printed in the USA 11/09 Article No.: 1-030722 US Corporate Headquarters 4140 World Houston Parkway, No 100, Houston, Texas USA 77032 Tel 713.933.0999 | Fax 832.613.6255 Canadian Corporate Headquarters 6175 Kenway Drive, Mississauga, Ontario CANADA L5T 2L3 Tel 905.542.2323 | Fax 905.542.2321 Online copperlogic.com CopperLogic is the exclusive North American representative of Moeller products. This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com