molded case circuit breaker catalog
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
www.barr-thorp.com
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
www.barr-thorp.com
cPRO line
molded case circuit breakers
molded case switches
F-series (15 – 225 Amps)
General Description...........................................................................
6
Single Pole Breakers...........................................................................
9
Two Pole Breakers...............................................................................
10
Three Pole Breakers............................................................................
13
Molded Case Switches.......................................................................
16
Field-Installable Accessories............................................................
22
Trip Curves............................................................................................
28
Technical Data....................................................................................
41
Dimensions..........................................................................................
45
K-series (70 – 400 Amps)
General Description...........................................................................
48
Two Pole Thermal-Magnetic Breakers...........................................
50
Three Pole Thermal-Magnetic Breakers........................................
54
Electronic Trip Breakers.....................................................................
58
100% Rated Electronic Trip Breakers..............................................
67
Molded Case Switches.......................................................................
70
Accessories...........................................................................................
71
Trip Curves............................................................................................
79
Technical Data....................................................................................
96
Dimensions..........................................................................................
100
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
www.barr-thorp.com
Control with CopperLogic
molded case circuit breakers
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
www.barr-thorp.com
cPRO molded case
circuit breakers & switches
circuit and personnel protection
Circuit breakers continue to offer a safe and reusable alternative to fuses for superior short circuit protection. In addition to being a “greener” solution by producing
less waste, most circuit breakers provide additional types of protection and features simply not found with fuses.
R
Circuit breakers also reduce downtime and increase safety. A simple flip of a switch
can restore continuity, where fuses require additional time and can be dangerous
to replace. Unlike fuses, which are “sacrificial overcurrent devices,” CopperLogic’s
cPRO circuit breakers are designed with high current withstand capabilities and
sophisticated arc quenching techniques for many years of reliable use.
CopperLogic’s Molded Case Circuit Breakers provide circuit protection for low voltage
distribution systems. The cPRO series ranges from 15 – 400 amperes, and includes
thermal-magnetic breakers, electronic trip breakers and molded case switches.
>15 to 400 amperes
> Meets NEMA design standards
>Multiple switching capacity options
>Thermal-magnetic and electronic trip
breakers available
>Molded case switches available
cPRO breakers offer protection of cable and exceed the requirements of the NEC for
branch circuit protection and UL 1087 for use as a disconnecting means. Reverse
loop contact design provides for current limiting performance and higher interrupting ratings within compact breaker sizes.
Quenches Arc Flashes
Arc flashes take only milliseconds to compromise expensive equipment and create
an extremely dangerous environment to personnel. CopperLogic’s cPRO molded
case breakers significantly outperform the calculations listed in IEEE Standard
1584-2002, Guide for Performing Arc Flash Hazard Calculations.
Applications
• Machine Tool Control Panels and Motor Control Centers
• Panelboards - as both main and branch circuit protection devices
• Feeder Pillars - in distribution systems to provide main and branch circuit
protection
(app
photo)
• Switchgear - in distribution systems to provide circuit protection up to 400
amperes
• Enclosed Circuit Breaker Disconnects - completely assembled in enclosures
to meet specific customer requirements
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
www.barr-thorp.com
3
CopperLogic’s catalog numbering system for molded case circuit
breakers and other devices follows a logical system. Device attributes
can be determined by the following nomenclature.
Dashes (–) are used to separate device attributes and should always
be included when ordering.
TM 3 – K4 M S
Continuous Rating
Device Type
S 80% Continuous Rating
C 100% Continuous Rating
TM Thermal-Magnetic Circuit Breaker
ET Electronic Trip Circuit Breaker
MF
Circuit Breaker Frame Only
(no trip module)
CS Molded Case Switch
Breaking Capacity
L Low Breaking Capacity
M Medium Breaking Capacity
H High Breaking Capacity
Number of Poles
1 Single Pole
2 Two Poles
3 Three Poles
Frame Size
F
K
K2
K4
F-series (to 225A)
K-series (without trip module)
K-series (to 250A)
K-series (to 400A)
This page for reference only.
Please turn to the appropriate pages to determine
the exact device and/or accessories required for your application.
4 copperLogic.com
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
CPRO-CAT-1109
www.barr-thorp.com
cPRO Nomenclature
Molded Case Circuit Breakers and Molded Case Switches
– 200 B – L S
Frame Window Option
Trip/Frame Rating
15
↓
400
S
Maximum Continuous Amp Rating
(blank) Without window
Terminals
Trip Module Type
A
B
E
F
G
H
VISA-window option for viewing main
power contacts
Line and Load side Terminals ship as
standard with assembled breakers.
L
Other options available; contact your
CopperLogic representative.
Fixed Thermal, Fixed Magnetic
Fixed Thermal, Adjustable Magnetic
Electronic Trip, I 2t response
Electronic Trip, flat response
(blank)
Electronic Trip, I 2t with ground fault
Without terminals (for Frame Only and
K-series Molded Case Switches)
Electronic Trip, flat with ground fault
No trip module (for Frame Only and
Molded Case Switches)
(blank)
CPRO-CAT-1109
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
copperLogic.com
www.barr-thorp.com
5
cPRO F-series
Factory complete breakers to 225 amps
cPRO F-series breakers offer compact control with many built-in accessory options.
Factory assembly means your breaker is ready-to-go from the box… saving time
and reducing installation costs. F-series molded case switches are 100% rated devices, eliminating the need for “sizing up” to match your application requirements.
R
Versatile protection in a small footprint
The F-series provides economical solutions from 15 to 225 amps at 600 V AC and
250 V DC. Three levels of breaking capacities are provided to a maximum of 200kA
(@240V AC). Industrial applications of 600V and 480V are protected to a maximum of 35kA and 100kA respectively.
F-series circuit breakers and molded case switches meet an array of requirements for
use in many kinds of applications. In addition to standard three pole circuit protection,
one and two pole breakers are available for single phase motors and other applications
including lighting, heating, transformer and branch circuit protection for single phase
receptacles.
Breakers are also suitable for use with refrigerant motor-compressors (HACR rated) and
back-fed mains (factory sealed and approved for reverse feed). All circuit breakers 15
through 30 amperes are also suitable for use with HID (high intensity discharge) lighting
circuits (480V max). F-series three pole breakers occupy a small footprint of just 6” x 41∕8”.
>15 – 225 amperes
>Suitable for reverse feed use
Interrupting Capacity [kA]
200
240V AC
(for two and three pole breakers)
>Factory-installed options allow breakers to
480V AC
600V AC
be ready-to-go from the box
> Listed in accordance with CSA C22.2 No. 5
and UL 489
250V DC
100
100
65
35
35
25 22
22
High
Breaking Capacity
65
Medium
Breaking Capacity
Low
Breaking Capacity
6
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
18 10
www.barr-thorp.com
You’ve got connections
Turn it On
All breakers are manufactured to accept compression lugs, however line
and load side box terminals are preinstalled and come standard with every F-series breaker. If desired, you can
also choose line side only or load side
only box terminals (or none) by special
order. Multi-wire connectors are also
available that allow you to distribute
the load from the breaker to multiple
devices without the use of separate distribution terminal
blocks.
In addition, a control wire terminal kit can be used to tap off
the main power terminal, which can eliminate the need for
additional panel wiring.
Safety you can see
CopperLogic breakers offer optional
viewing windows in the breaker frame
that allow you to see the position of the
main power contacts in toggle operated applications. This is a requirement
in the mining industry and certain
utilities. If a pole is welded closed, one
glance at the window can prevent serious injury. In addition,
accessories such as terminal shields and end covers provide
touch-safe protection.
The cPRO F-series
also includes two and
three-pole
Molded
Case Switches that offer up to 225A switching capabilities in applications to 600V AC
and 250V DC. Molded
case switches are
constructed of circuit
breaker components and include a fixed
magnetic trip to increase the short circuit withstand rating (65kA @480V) and
to protect the switch itself. They are also
listed for reverse feed use and are 100%
rated devices. A Shunt Trip is also available for these Switches,
a feature not offered by
many other manufacturers.
Factory Installed Options
Include:
• Line and Load Terminals
• Built-in Frame Window
• Alarm Lockout Switch
• Auxiliary Switch
• Alarm and Auxiliary
Combination Switch
• Shunt Trip
• Undervoltage Trip
Remote electrical operator
Two types of devices are available for remote operation and reset. The first has a
solenoid mechanism that trips the breaker
in as little as 80ms. The other type has built-in electric motor
that physically moves the breaker toggle in three seconds.
Through-the-door & Flange
Mounted Operators
All operators include a lock-out mechanism for up to three padlocks that prevent the handle from being turned to
the ON position. Door interlocks also
prevent the enclosure door from being
opened while the handle is in the ON
position (defeat mechanisms are included). Flange handle can be mounted up to 10 ft. away from the breaker.
Standard handles are rated
NEMA 1 and 12 - available in
black and red
Ergonomic handles are rated
NEMA 1, 12, 3R, 4 and 4X
Flange handles are rated NEMA
1, 12, 3R, 4 and 4X
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
www.barr-thorp.com
7
cPRO Molded Case Circuit Breakers
Notes
8 copperLogic.com
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
CPRO-CAT-1109
www.barr-thorp.com
cPRO Molded Case Circuit Breakers
Thermal-Magnetic Single Pole, F-series
> For single pole applications to 150A @347V
> Protection for single-phase motors, transformers and branch circuits
> UL and CSA approved for switching duty to 20A
> Factory installed options allows for quicker installation time
> HACR rated allows for use with refrigerant motor compressors
> Factory sealed and approved for reverse feed use with back-fed mains
Thermal-Magnetic Single Pole Circuit Breakers with
Non-Interchangeable Fixed Thermal, Fixed Magnetic Trip Module ➊➋➌
Continuous
Amp Rating
@ 40° C (104° F)
Maximum
Operating
Voltage
Low Breaking Capacity
18 kAIC @ 347 V AC
35 kAIC @ 277 V AC
10 kAIC @ 125 V DC ➍
AC
DC
Catalog Number
Price
15
347
125
TM1-FLS-15A-L ➎
581
20
347
125
TM1-FLS-20A-L ➎
581
25
347
125
TM1-FLS-25A-L
581
30
347
125
TM1-FLS-30A-L
581
35
347
125
TM1-FLS-35A-L
581
40
347
125
TM1-FLS-40A-L
581
45
347
125
TM1-FLS-45A-L
581
50
347
125
TM1-FLS-50A-L
581
60
347
125
TM1-FLS-60A-L
581
70
347
125
TM1-FLS-70A-L
653
80
347
125
TM1-FLS-80A-L
653
90
347
125
TM1-FLS-90A-L
653
100
347
125
TM1-FLS-100A-L
653
110
347
125
TM1-FLS-110A-L
1447
125
347
125
TM1-FLS-125A-L
1447
150
347
125
TM1-FLS-150A-L
1930
➊ Line and Load side terminals ship with breaker as standard. Other options are
available; contact your CopperLogic representative.
Ordering Instructions
1
2
➋ A VISA-window to view main power contacts is available. If desired, add “S” to end of
main breaker catalog number, and add $950 to price. For toggle style operators only.
Locate the desired main circuit breaker.
Order field-installable accessories separately on pages 22 – 27.
➌ Mounting hardware not included. Order base mounting hardware separately on page 27.
➍ DC ratings apply to substantially non-inductive circuits. Time constant is 3ms
minimum at 10kA and 8ms minimum at 22kA.
➎ UL and CSA listed for SWD (switching duty) lighting applications.
CPRO-CAT-1109
Discount
Code B30
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
copperLogic.com
www.barr-thorp.com
9
> For two pole applications to 225A @600V
> Protection for single-phase motors, transformers and branch circuits
> Factory installed options allows for quicker installation time
> HACR rated allows for use with refrigerant motor compressors
> Factory sealed and approved for reverse feed use with back-fed mains
Thermal-Magnetic Two Pole Circuit Breakers with
Non-Interchangeable Fixed Thermal, Fixed Magnetic Trip Module ➊➋➌
Step 1: Select Main Breaker
Continuous
Amp Rating
@ 40° C (104° F)
Maximum
Operating
Voltage
Low Breaking Capacity
18 kAIC @ 600 V AC
35 kAIC @ 480 V AC
65 kAIC @ 240 V AC
10 kAIC @ 250 V DC ➍
Price
Medium Breaking Capacity
25 kAIC @ 600 V AC
65 kAIC @ 480 V AC
100 kAIC @ 240 V AC
22 kAIC @ 250 V DC ➍
AC
DC
Catalog Number
Catalog Number
Price
Catalog Number
Price
15
600
250
TM2-FLS-15A-L
774
TM2-FMS-15A-L
1379
TM2-FHS-15A-L
1525
20
600
250
TM2-FLS-20A-L
774
TM2-FMS-20A-L
1379
TM2-FHS-20A-L
1525
25
600
250
TM2-FLS-25A-L
774
TM2-FMS-25A-L
1379
TM2-FHS-25A-L
1525
30
600
250
TM2-FLS-30A-L
774
TM2-FMS-30A-L
1379
TM2-FHS-30A-L
1525
35
600
250
TM2-FLS-35A-L
774
TM2-FMS-35A-L
1379
TM2-FHS-35A-L
1525
40
600
250
TM2-FLS-40A-L
774
TM2-FMS-40A-L
1379
TM2-FHS-40A-L
1525
45
600
250
TM2-FLS-45A-L
774
TM2-FMS-45A-L
1379
TM2-FHS-45A-L
1525
50
600
250
TM2-FLS-50A-L
774
TM2-FMS-50A-L
1379
TM2-FHS-50A-L
1525
60
600
250
TM2-FLS-60A-L
774
TM2-FMS-60A-L
1379
TM2-FHS-60A-L
1525
70
600
250
TM2-FLS-70A-L
798
TM2-FMS-70A-L
1742
TM2-FHS-70A-L
1851
80
600
250
TM2-FLS-80A-L
798
TM2-FMS-80A-L
1742
TM2-FHS-80A-L
1851
1851
90
600
250
TM2-FLS-90A-L
798
TM2-FMS-90A-L
1742
TM2-FHS-90A-L
100
600
250
TM2-FLS-100A-L
798
TM2-FMS-100A-L
1742
TM2-FHS-100A-L
1851
110
600
250
TM2-FLS-110A-L
1696
TM2-FMS-110A-L
3509
TM2-FHS-110A-L
4035
125
600
250
TM2-FLS-125A-L
1696
TM2-FMS-125A-L
3509
TM2-FHS-125A-L
4035
150
600
250
TM2-FLS-150A-L
1696
TM2-FMS-150A-L
4254
TM2-FHS-150A-L
4956
175
600
250
TM2-FLS-175A-L
1696
TM2-FMS-175A-L
4430
TM2-FHS-175A-L
5219
200
600
250
TM2-FLS-200A-L
1696
TM2-FMS-200A-L
4430
TM2-FHS-200A-L
5219
225
600
250
TM2-FLS-225A-L
1696
TM2-FMS-225A-L
4430
TM2-FHS-225A-L
5219
➊ Line and Load side terminals ship with breaker as standard. Other options are
available; contact your CopperLogic representative.
Ordering Instructions
1
2
3
High Breaking Capacity
35 kAIC @ 600 V AC
100 kAIC @ 480 V AC
200 kAIC @ 240 V AC
22 kAIC @ 250 V DC ➍
➋ A VISA-window to view main power contacts is available. If desired, add “S” to end of
main breaker catalog number, and add $950 to price. For toggle style operators only.
Locate the desired main circuit breaker.
Choose an optional right pole accessory on next page.
Order field-installable accessories separately on pages 22 – 27.
10 copperLogic.com
➌ Mounting hardware not included. Order base mounting hardware separately on page 27.
➍ DC ratings apply to substantially non-inductive circuits. Time constant is 3ms
minimum at 10kA and 8ms minimum at 22kA.
➎ Internal accessories must be factory installed to maintain UL/CSA approval with
F-series cPRO circuit breakers and molded case switches.
Discount Code B30
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
CPRO-CAT-1109
www.barr-thorp.com
cPRO Molded Case Circuit Breakers
Thermal-Magnetic Two Pole, F-series
Internal Accessories for Factory Installation ➎ - Right Pole mounted options
Step 2: Select Optional Right Pole Accessory (Choose One)
Factory
Installation Code
Installed Accessories
Description
For use with…
Schematic
(add to catalog
Operating Voltage number as suffix)
Price
Adder
Alarm Lockout Switch
For remote indication of trip operation. Switch
resets when circuit breaker resets.
18 inch pigtail leads, 18 AWG / 0.8 mm2
Installed on right pole, leads exit on rear of
breaker
Make
1 NO & 1 NC
+B06F
337
2 NO & 2 NC
+B13F
337
1 NO & 1 NC
+A06F
337
2 NO & 2 NC
+A13F
337
1 NO & 1 NC for
Auxilary
and
1 NO & 1 NC for Alarm
+C05F
337
12 – 24 V AC
12 – 24 V DC
+S18F
589
48 – 127 V AC
48 – 60 V DC
+S22F
589
208 – 380 V AC
110 – 127 V DC
+S26F
589
415 – 600 V AC
220 – 250 V DC
+S30F
589
12 V AC
12 V DC
24 V AC
24 V DC
+U50F
+U78F
+U54F
+U82F
592
592
592
592
48 V AC
48 V DC
+U86F
592
60 V AC
60 V DC
+U102F
592
110 – 127 V AC
110 – 127 V DC
208 – 240 V AC
220 – 250 V DC
380 – 480 V AC
525 – 600 V AC
+U62F
+U90F
+U66F
+U94F
+U70F
+U74F
592
592
592
592
592
592
Two pole F-series
Break
Auxiliary Switch
For remote indication of circuit breaker status.
18 inch pigtail leads, 18 AWG / 0.8 mm2
Installed on right pole, leads exit on rear of
breaker
a
Two pole F-series
b
Alarm and Auxiliary Switch Combination
18 inch pigtail leads, 18 AWG / 0.8 mm2
Installed on right pole, leads exit on rear of
breaker
a
Two pole F-series
b
Shunt Trip
Provides remote trip
Intermittent duty
18 inch pigtail leads, 18 AWG / 0.8 mm2
Installed on right pole, leads exit on rear of
breaker
Two pole F-series
Three pole F-series
ST
a
Undervoltage Trip
Monitors power feed to circuit breaker or
switch. Trips circuit breaker or switch when
voltage drops below threshold.
18 inch pigtail leads, 18 AWG / 0.8 mm2
Installed on right pole, leads exit on rear of
breaker
CPRO-CAT-1109
Two pole F-series
Three pole F-series
UV
Discount
Code B30
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
copperLogic.com
www.barr-thorp.com
11
cPRO Molded Case Circuit Breakers
Notes
12 copperLogic.com
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
CPRO-CAT-1109
www.barr-thorp.com
cPRO Molded Case Circuit Breakers
Thermal-Magnetic Three Pole, F-series
> For three pole applications to 225A @600V
> Protection for three-phase motors, transformers and branch circuits
> Factory installed options allows for quicker installation time
> HACR rated allows for use with refrigerant motor compressors
> Factory sealed and approved for reverse feed use with back-fed mains
Thermal-Magnetic Three Pole Circuit Breakers with
Non-Interchangeable Fixed Thermal, Fixed Magnetic Trip Module ➊➋➌
Step 1: Select Main Breaker
Continuous
Amp Rating
@ 40° C (104° F)
Maximum
Operating
Voltage
Low Breaking Capacity
18 kAIC @ 600 V AC
35 kAIC @ 480 V AC
65 kAIC @ 240 V AC
10 kAIC @ 250 V DC ➍
Price
Medium Breaking Capacity
25 kAIC @ 600 V AC
65 kAIC @ 480 V AC
100 kAIC @ 240 V AC
22 kAIC @ 250 V DC ➍
AC
DC
Catalog Number
Catalog Number
Price
Catalog Number
Price
15
600
250
TM3-FLS-15A-L
816
TM3-FMS-15A-L
1557
TM3-FHS-15A-L
2102
20
600
250
TM3-FLS-20A-L
816
TM3-FMS-20A-L
1557
TM3-FHS-20A-L
2102
25
600
250
TM3-FLS-25A-L
816
TM3-FMS-25A-L
1557
TM3-FHS-25A-L
2102
30
600
250
TM3-FLS-30A-L
816
TM3-FMS-30A-L
1557
TM3-FHS-30A-L
2102
35
600
250
TM3-FLS-35A-L
816
TM3-FMS-35A-L
1557
TM3-FHS-35A-L
2102
40
600
250
TM3-FLS-40A-L
816
TM3-FMS-40A-L
1557
TM3-FHS-40A-L
2102
45
600
250
TM3-FLS-45A-L
816
TM3-FMS-45A-L
1557
TM3-FHS-45A-L
2102
50
600
250
TM3-FLS-50A-L
816
TM3-FMS-50A-L
1557
TM3-FHS-50A-L
2102
60
600
250
TM3-FLS-60A-L
816
TM3-FMS-60A-L
1557
TM3-FHS-60A-L
2102
70
600
250
TM3-FLS-70A-L
816
TM3-FMS-70A-L
1692
TM3-FHS-70A-L
2272
80
600
250
TM3-FLS-80A-L
816
TM3-FMS-80A-L
1692
TM3-FHS-80A-L
2272
2863
90
600
250
TM3-FLS-90A-L
816
TM3-FMS-90A-L
1899
TM3-FHS-90A-L
100
600
250
TM3-FLS-100A-L
816
TM3-FMS-100A-L
2142
TM3-FHS-100A-L
2863
110
600
250
TM3-FLS-110A-L
1785
TM3-FMS-110A-L
3132
TM3-FHS-110A-L
4475
125
600
250
TM3-FLS-125A-L
1785
TM3-FMS-125A-L
3132
TM3-FHS-125A-L
4475
150
600
250
TM3-FLS-150A-L
1785
TM3-FMS-150A-L
3262
TM3-FHS-150A-L
5173
175
600
250
TM3-FLS-175A-L
1785
TM3-FMS-175A-L
4092
TM3-FHS-175A-L
5173
200
600
250
TM3-FLS-200A-L
1785
TM3-FMS-200A-L
5000
TM3-FHS-200A-L
6091
225
600
250
TM3-FLS-225A-L
1785
TM3-FMS-225A-L
5444
TM3-FHS-225A-L
6712
Ordering Instructions
1
2
3
4
High Breaking Capacity
35 kAIC @ 600 V AC
100 kAIC @ 480 V AC
200 kAIC @ 240 V AC
22 kAIC @ 250 V DC ➍
CPRO-CAT-1109
See next page for
Step 2.
➊ Line and Load side terminals ship with breaker as standard. Other options are
available; contact your CopperLogic representative.
Locate the desired main circuit breaker.
Choose an optional left pole accessory on next page.
Choose an optional right pole accessory on page 15.
Order field-installable accessories separately on pages 22 – 27.
➋ A VISA-window to view main power contacts is available. If desired, add “S” to end of
main breaker catalog number, and add $950 to price. For toggle style operators only.
➌ Mounting hardware not included. Order base mounting hardware separately on page 27.
➍ DC ratings apply to substantially non-inductive circuits. Time constant is 3ms
minimum at 10kA and 8ms minimum at 22kA.
Discount
Code B30
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
copperLogic.com
www.barr-thorp.com
13
Accessories
F-series Factory Installation Options
Internal Accessories for Factory Installation ➊ - Left Pole mounted options ➋
Step 2: Select Optional Left Pole Accessory (Choose One)
Factory
Installation Code
Installed Accessories
Description
For use with…
Schematic
Price
Adder
Contacts
(add to catalog
number as suffix)
1 NO & 1 NC
+B02F
337
2 NO & 2 NC
+B10F
337
1 NO & 1 NC
+A02F
337
2 NO & 2 NC
+A10F
337
1 NO & 1 NC for
Auxilary
and
1 NO & 1 NC for
Alarm
+C02F
337
Alarm Lockout Switch
For remote indication of trip operation. Switch resets
when circuit breaker resets.
18 inch pigtail leads, 18 AWG / 0.8 mm2
Installed on left pole, leads exit on rear of breaker
Make
Three pole F-series
Break
Auxiliary Switch
For remote indication of circuit breaker status.
18 inch pigtail leads, 18 AWG / 0.8 mm2
Installed on left pole, leads exit on rear of breaker
a
Three pole F-series
b
Alarm and Auxiliary Switch Combination
18 inch pigtail leads, 18 AWG / 0.8 mm2
Installed on left pole, leads exit on rear of breaker
a
Three pole F-series
b
Ordering Instructions
1
2
3
4
Locate the desired main circuit breaker from previous page.
Choose an optional left pole accessory on this page.
Choose an optional right pole accessory on next page.
Order field-installable accessories separately on pages 22 – 27.
14 copperLogic.com
➊ Internal accessories must be factory installed to maintain UL/CSA approval with
F-series cPRO circuit breakers and molded case switches.
➋ Popular configurations shown. Additional configurations including lead exit and
pole mounting locations are available, contact your CopperLogic representative.
Discount Code B30
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
CPRO-CAT-1109
www.barr-thorp.com
Accessories
F-series Factory Installation Options
Internal Accessories for Factory Installation ➊ - Right Pole mounted options ➋
Step 3: Select Optional Right Pole Accessory (Choose One)
Factory
Installation Code
Installed Accessories
Description
For use with…
Schematic
(add to catalog
Operating Voltage number as suffix)
Price
Adder
Shunt Trip
Provides remote trip
Intermittent duty
18 inch pigtail leads, 18 AWG / 0.8 mm2
Installed on right pole, leads exit on rear of
breaker
Two pole F-series
Three pole F-series
ST
a
12 – 24 V AC
12 – 24 V DC
+S18F
589
48 – 127 V AC
48 – 60 V DC
+S22F
589
208 – 380 V AC
110 – 127 V DC
+S26F
589
415 – 600 V AC
220 – 250 V DC
+S30F
589
12 V AC
12 V DC
24 V AC
24 V DC
+U50F
+U78F
+U54F
+U82F
592
592
592
592
48 V AC
48 V DC
+U86F
592
60 V AC
60 V DC
+U102F
592
110 – 127 V AC
110 – 127 V DC
208 – 240 V AC
220 – 250 V DC
380 – 480 V AC
525 – 600 V AC
+U62F
+U90F
+U66F
+U94F
+U70F
+U74F
592
592
592
592
592
592
Undervoltage Trip
Monitors power feed to circuit breaker or
switch. Trips circuit breaker or switch when
voltage drops below threshold.
18 inch pigtail leads, 18 AWG / 0.8 mm2
Installed on right pole, leads exit on rear of
breaker
Two pole F-series
Three pole F-series
UV
Ordering Instructions
1
2
3
4
CPRO-CAT-1109
Locate the desired main circuit breaker from page 13.
Choose an optional left pole accessory on previous page.
Choose an optional right pole accessory on this page.
Order field-installable accessories separately on pages 22 – 27.
➊ Internal accessories must be factory installed to maintain UL/CSA approval with
F-series cPRO circuit breakers and molded case switches.
➋ Popular configurations shown. Additional configurations including lead exit and
pole mounting locations are available, contact your CopperLogic representative.
Discount
Code B30
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
copperLogic.com
www.barr-thorp.com
15
> For two pole, single-phase motor disconnecting and switching to 225A
> 100% Rated device prevents need to select a larger switch size
> Built-in fixed instantaneous trip opens above 1800 Amps
> Factory installed options allows for quicker installation time
> HACR rated allows for use with refrigerant motor compressors
Two Pole Molded Case Switches ➊➋➌➍
Step 1: Select Main Switch
Maximum
Operating
Voltage
Medium Short-circuit
Withstand Rating
25 kAIC @ 600 V AC
65 kAIC @ 480 V AC
100 kAIC @ 240 V AC
22 kAIC @ 250 V DC
Low Short-circuit
Withstand Rating
18 kAIC @ 600 V AC
25 kAIC @ 480 V AC
65 kAIC @ 240 V AC
10 kAIC @ 250 V DC
Continuous
Amp Rating
@ 40° C (104° F)
AC
DC
Catalog Number
Price
Catalog Number
Price
100
600
250
CS2-FLC-100-L
1360
CS2-FMC-100-L
1842
150
600
250
CS2-FLC-150-L
2193
CS2-FMC-150-L
2500
225
600
250
CS2-FLC-225-L
2917
CS2-FMC-225-L
3246
➊ Line and Load side terminals ship with molded case switch as standard. Other
options are available; contact your CopperLogic representative.
Ordering Instructions
1
2
3
➋ A VISA-window to view main power contacts is available. If desired, add “S” to end of
main switch catalog number, and add $950 to price. For toggle style operators only.
Locate the desired main molded case switch.
Choose an optional right pole accessory on next page.
Order field-installable accessories separately on pages 22 – 27.
16 copperLogic.com
➌ Molded case switches are supplied with a fixed instantaneous trip that opens
above 1800A.
➍ Mounting hardware not included. Order base mounting hardware separately on page 27.
➎ Internal accessories must be factory installed to maintain UL/CSA approval with
F-series cPRO circuit breakers and molded case switches.
Discount Code B30
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
CPRO-CAT-1109
www.barr-thorp.com
cPRO Molded Case Switches
Molded Case Switches, Two pole, F-series
Internal Accessories for Factory Installation ➎ - Right Pole mounted options
Step 2: Select Optional Right Pole Accessory (Choose One)
Factory
Installation Code
Installed Accessories
Description
For use with…
Schematic
(add to catalog
Operating Voltage number as suffix)
Price
Adder
Alarm Lockout Switch
For remote indication of trip operation. Switch
resets when circuit breaker resets.
18 inch pigtail leads, 18 AWG / 0.8 mm2
Installed on right pole, leads exit on rear of
breaker
Make
1 NO & 1 NC
+B06F
337
2 NO & 2 NC
+B13F
337
1 NO & 1 NC
+A06F
337
2 NO & 2 NC
+A13F
337
1 NO & 1 NC for
Auxilary
and
1 NO & 1 NC for Alarm
+C05F
337
12 – 24 V AC
12 – 24 V DC
+S18F
589
48 – 127 V AC
48 – 60 V DC
+S22F
589
208 – 380 V AC
110 – 127 V DC
+S26F
589
415 – 600 V AC
220 – 250 V DC
+S30F
589
12 V AC
12 V DC
24 V AC
24 V DC
+U50F
+U78F
+U54F
+U82F
592
592
592
592
48 V AC
48 V DC
+U86F
592
60 V AC
60 V DC
+U102F
592
110 – 127 V AC
110 – 127 V DC
208 – 240 V AC
220 – 250 V DC
380 – 480 V AC
525 – 600 V AC
+U62F
+U90F
+U66F
+U94F
+U70F
+U74F
592
592
592
592
592
592
Two pole F-series
Break
Auxiliary Switch
For remote indication of circuit breaker status.
18 inch pigtail leads, 18 AWG / 0.8 mm2
Installed on right pole, leads exit on rear of
breaker
a
Two pole F-series
b
Alarm and Auxiliary Switch Combination
18 inch pigtail leads, 18 AWG / 0.8 mm2
Installed on right pole, leads exit on rear of
breaker
a
Two pole F-series
b
Shunt Trip
Provides remote trip
Intermittent duty
18 inch pigtail leads, 18 AWG / 0.8 mm2
Installed on right pole, leads exit on rear of
breaker
Two pole F-series
Three pole F-series
ST
a
Undervoltage Trip
Monitors power feed to circuit breaker or
switch. Trips circuit breaker or switch when
voltage drops below threshold.
18 inch pigtail leads, 18 AWG / 0.8 mm2
Installed on right pole, leads exit on rear of
breaker
CPRO-CAT-1109
Two pole F-series
Three pole F-series
UV
Discount
Code B30
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
copperLogic.com
www.barr-thorp.com
17
cPRO Molded Case Circuit Breakers
Notes
18 copperLogic.com
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
CPRO-CAT-1109
www.barr-thorp.com
cPRO Molded Case Switches
Molded Case Switches, Three pole, F-series
> For three pole, three-phase motor disconnecting and switching to 225A
> 100% Rated device prevents need to select a larger switch size
> Built-in fixed instantaneous trip opens above 1800 Amps
> Factory installed options allows for quicker installation time
> HACR rated allows for use with refrigerant motor compressors
Three Pole Molded Case Switches ➊➋➌➍
Step 1: Select Main Switch
Maximum
Operating
Voltage
Medium Short-circuit
Withstand Rating
25 kAIC @ 600 V AC
65 kAIC @ 480 V AC
100 kAIC @ 240 V AC
22 kAIC @ 250 V DC
Low Short-circuit
Withstand Rating
18 kAIC @ 600 V AC
25 kAIC @ 480 V AC
65 kAIC @ 240 V AC
10 kAIC @ 250 V DC
Continuous
Amp Rating
@ 40° C (104° F)
AC
DC
Catalog Number
Price
Catalog Number
Price
100
600
250
CS3-FLC-100-L
1480
CS3-FMC-100-L
1899
150
600
250
CS3-FLC-150-L
2191
CS3-FMC-150-L
3333
225
600
250
CS3-FLC-225-L
3690
CS3-FMC-225-L
4386
Ordering Instructions
1
2
3
4
See next page for Step 2.
➊ Line and Load side terminals ship with molded case switch as standard. Other
options are available; contact your CopperLogic representative.
Locate the desired main molded case switch.
Choose an optional left pole accessory on next page.
Choose an optional right pole accessory on page 21.
Order field-installable accessories separately on pages 22 – 27.
➋ A VISA-window to view main power contacts is available. If desired, add “S” to end of
main switch catalog number, and add $950 to price. For toggle style operators only.
➌ Molded case switches are supplied with a fixed instantaneous trip that opens
above 1800A.
➍ Mounting hardware not included. Order base mounting hardware separately on page 27.
CPRO-CAT-1109
Discount
Code B30
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
copperLogic.com
www.barr-thorp.com
19
Accessories
F-series Factory Installation Options
Internal Accessories for Factory Installation ➊ - Left Pole mounted options ➋
Step 2: Select Optional Left Pole Accessory (Choose One)
Factory
Installation Code
Installed Accessories
Description
For use with…
Schematic
Price
Adder
Contacts
(add to catalog
number as suffix)
1 NO & 1 NC
+B02F
337
2 NO & 2 NC
+B10F
337
1 NO & 1 NC
+A02F
337
2 NO & 2 NC
+A10F
337
1 NO & 1 NC for
Auxilary
and
1 NO & 1 NC for
Alarm
+C02F
337
Alarm Lockout Switch
For remote indication of trip operation. Switch resets
when circuit breaker resets.
18 inch pigtail leads, 18 AWG / 0.8 mm2
Installed on left pole, leads exit on rear of breaker
Make
Three pole F-series
Break
Auxiliary Switch
For remote indication of circuit breaker status.
18 inch pigtail leads, 18 AWG / 0.8 mm2
Installed on left pole, leads exit on rear of breaker
a
Three pole F-series
b
Alarm and Auxiliary Switch Combination
18 inch pigtail leads, 18 AWG / 0.8 mm2
Installed on left pole, leads exit on rear of breaker
a
Three pole F-series
b
Ordering Instructions
1
2
3
4
Locate the desired molded case switch from previous page.
Choose an optional left pole accessory on this page.
Choose an optional right pole accessory on next page.
Order field-installable accessories separately on pages 22 – 27.
20 copperLogic.com
➊ Internal accessories must be factory installed to maintain UL/CSA approval with
F-series cPRO circuit breakers and molded case switches.
➋ Popular configurations shown. Additional configurations including lead exit and
pole mounting locations are available, contact your CopperLogic representative.
Discount Code B30
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
CPRO-CAT-1109
www.barr-thorp.com
Accessories
F-series Factory Installation Options
Internal Accessories for Factory Installation ➊ - Right Pole mounted options ➋
Step 3: Select Optional Right Pole Accessory (Choose One)
Factory
Installation Code
Installed Accessories
Description
For use with…
Schematic
(add to catalog
Operating Voltage number as suffix)
Price
Adder
Shunt Trip
Provides remote trip
Intermittent duty
18 inch pigtail leads, 18 AWG / 0.8 mm2
Installed on right pole, leads exit on rear of
breaker
Two pole F-series
Three pole F-series
ST
a
12 – 24 V AC
12 – 24 V DC
+S18F
589
48 – 127 V AC
48 – 60 V DC
+S22F
589
208 – 380 V AC
110 – 127 V DC
+S26F
589
415 – 600 V AC
220 – 250 V DC
+S30F
589
12 V AC
12 V DC
24 V AC
24 V DC
+U50F
+U78F
+U54F
+U82F
592
592
592
592
48 V AC
48 V DC
+U86F
592
60 V AC
60 V DC
+U102F
592
110 – 127 V AC
110 – 127 V DC
208 – 240 V AC
220 – 250 V DC
380 – 480 V AC
525 – 600 V AC
+U62F
+U90F
+U66F
+U94F
+U70F
+U74F
592
592
592
592
592
592
Undervoltage Trip
Monitors power feed to circuit breaker or
switch. Trips circuit breaker or switch when
voltage drops below threshold.
18 inch pigtail leads, 18 AWG / 0.8 mm2
Installed on right pole, leads exit on rear of
breaker
Two pole F-series
Three pole F-series
UV
Ordering Instructions
1
2
3
4
CPRO-CAT-1109
Locate the desired molded case switch from page 19.
Choose an optional left pole accessory on previous page.
Choose an optional right pole accessory on this page.
Order field-installable accessories separately on pages 22 – 27.
➊ Internal accessories must be factory installed to maintain UL/CSA approval with
F-series cPRO circuit breakers and molded case switches.
➋ Popular configurations shown. Additional configurations including lead exit and
pole mounting locations are available, contact your CopperLogic representative.
Discount
Code B30
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
copperLogic.com
www.barr-thorp.com
21
Accessories
F-series Field Installation Options
Through-the-door Handles - Complete Units (includes handle, mechanism and shaft) ➊
Accessory
Shaft Length
mm (in.)
Description
Handle
Color
Catalog Number
Price
Black
Red
Black
Red
Black
Red
FHMVD06B
FHMVD06R
FHMVD12B
FHMVD12R
FHMVD24B
FHMVD24R
295
295
305
305
420
420
152.4 (6)
Black
HM1R06
593
304.8 (12)
Black
HM1R12
624
406.4 (16)
Black
HM1R16
690
609.6 (24)
Black
HM1R24
765
152.4 (6)
Black
HM1R06X
658
304.8 (12)
Black
HM1R12X
675
406.4 (16)
Black
HM1R16X
739
609.6 (24)
Black
HM1R24X
802
Standard Handle Kit - NEMA 1, 12
152.4 (6)
NEMA 1, 12
Molded plastic handle
For F-series
90 degree rotation
304.8 (12)
609.6 (24)
Ergonomic Handle Kit- NEMA 1, 12, 3R
NEMA 1, 12, 3R
Steel handle
For F-series
Ergonomic design for
‘gloved hand’ operation
45 degree rotation
Ergonomic Handle Kit - NEMA 4/4X
NEMA 4/4X
Steel handle
For F-series
Ergonomic design for
‘gloved hand’ operation
45 degree rotation
Through-the-door Handles - Components (order separately) ➊
Mechanism
Handle
Description
Handle
Color Catalog Number
Price
Catalog Number
Shaft
Price
Length [mm (in.)] Catalog Number
Price
Handle Components for NEMA 1, 12, 3R
NEMA 1, 12, 3R
Ergonomic Steel handle
For F-series
Ergonomic design for
‘gloved hand’ operation
45 degree rotation
Black
6648C22G25
541
6648C23G11
602
152.4 (6)
4217B37G08
150
304.8 (12)
4217B37G05
180
406.4 (16)
4217B37G06
211
609.6 (24)
4217B37G07
241
152.4 (6)
4217B37G08
150
304.8 (12)
4217B37G05
180
406.4 (16)
4217B37G06
211
609.6 (24)
4217B37G07
241
Handle Components for NEMA 4/4X
NEMA 4/4X
Ergonomic Steel handle
For F-series
Ergonomic design for
‘gloved hand’ operation
45 degree rotation
Black
6648C22G27
677
6648C23G11
602
➊ Not for use with VISA-window option.
22 copperLogic.com
Discount Code B30
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
CPRO-CAT-1109
www.barr-thorp.com
Accessories
F-series Field Installation Options
Flange Mounted Handles ➊
Accessory
NEMA 1, 12, 3R
Flexible
Shaft Length
m (ft.)
Catalog Number
Price
Description
NEMA 4/4X
Catalog Number
Price
Flange Handles
For F-series
Extra heavy-duty flexible shaft
Accepts up to 3 padlocks
0.9 (3)
F1S03C
1475
F1S03CX
1801
1.2 (4)
F1S04C
1507
F1S04CX
1840
1.5 (5)
F1S05C
1539
F1S05CX
1880
1.8 (6)
F1S06C
1573
F1S06CX
1920
2.1 (7)
F1S07C
1603
F1S07CX
1959
2.4 (8)
F1S08C
1634
F1S08CX
1999
2.7 (9)
F1S09C
1666
F1S09CX
2031
3.0 (10)
F1S10C
1689
F1S10CX
2062
Safety Door Hardware for NEMA 12 Flex Shafts
Accessory
Description
Handle Length
mm (in.)
Catalog Number
Price
Hardware Kit
Provides enclosure sealing and
protection against unauthorized entry
101.6 (4.0)
C361KJ4
500
152.4 (6.0)
C361KJ6
500
–
C361KR
66
Roller Latch
Required for 3-point latching
➊ Not for use with VISA-window option.
CPRO-CAT-1109
Discount
Code B30
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
copperLogic.com
www.barr-thorp.com
23
Accessories
F-series Field Installation Options
Remote Electrical Operators
Accessory
Description
Inrush
Current
[A]
Max.
Operating
Time
Fuse
[A]
10
5 cycles (80 ms)
5
Operating
Voltage
AC
DC
For use
with… Catalog Number
3
120
–
F-series
EOP1P07
3485
5 cycles (80 ms)
2
240
–
F-series
EOP1P11
3485
10
5 cycles (80 ms)
3
–
120
F-series
EOP1P07DC
3485
5
5 cycles (80 ms)
2
–
240
F-series
EOP1P11DC
3485
–
120
–
F-series
MOP1P07
3485
–
–
24
F-series
MOP1P03DC
3485
–
–
48
F-series
MOP1P05DC
3485
–
–
125
F-series
MOP1P07DC
3485
Price
Electrical Solenoid Operator
Enables local and remote switching (ON, OFF
and reset).
Unique bistable latch allows device to operate
with only one solenoid
Padlockable in OFF position
Endurance tested for 10,000 electrical
operations
Electrical Motor Operator
Allows for circuit breaker to be opened, closed
or reset remotely
Lock-off capable
Operator uses a reversible motor to operate
the circuit breaker handle.
Endurance tested for 4,000 electrical operations
2
5
3
3 seconds
(intermittent
duty - safe duty
cycle should not
exceed one per
minute)
2
Current Limiter
Current Limiter
Description
For Use With…
Catalog Number
Price
F-series circuit breakers
Amp rating:
15 – 70
LFD3070R
1096
F-series circuit breakers
Amp rating:
80 – 150
LFD3150R
1535
LFD Current Limiter
For thermal-magnetic circuit breakers
to 150A
Provides 200 kA Interrupting Capacity
to 600V AC
24 copperLogic.com
Discount Code B30
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
CPRO-CAT-1109
www.barr-thorp.com
Accessories
F-series Field Installation Options
Miscellaneous Accessories
Accessory
Description
For use with…
Catalog Number
Price
Terminal Shield
Protection against accidental contact with line side
terminals
Order in sets of 10; priced individually
Single pole F-series
625B229G06
84
Two pole F-series
625B229G07
84
Three pole F-series
625B229G08
84
Three pole F-series with
Electrical Operator
4210B95G01
842
TEC1
158
F-series
Conductor Opening: 10.41 mm TEC2
(0.41 in)
158
F-series
IPB1
105
F-series
LKD1
105
F-series
PHL1
105
Two Pole F-series
Three Pole F-series
PLK1
105
Left side mounting
PLK1LOFF
105
Right side mounting
PLK1ROFF
105
Terminal End Cover
Close fitting conductor openings are molded into
the end cover. The end cover and circuit breaker or
switch case fit together to form terminal compartments that isolate discharged ionizing gases during
circuit breaker tripping.
F-series
Conductor Opening: 6.35 mm
(0.25 in)
Interphase Barriers
High dielectric insulating plates provide additional
electrical clearance between circuit breaker or
switch poles
Priced and packaged in sets of two.
Non-padlockable Handle Block
Used to secure the circuit breaker or switch handle in
either the ON or OFF position. Breaker is allowed to
trip when blocked in the ON position. Secured by a
setscrew, handle block deters accidental operation of
circuit breaker handle.
Snap-on Padlockable Handle Lock Hasp
Used to lock the circuit breaker or switch handle in
either the ON or OFF position. Breaker is allowed to
trip when blocked in the ON position. Accepts one
padlock up to 1/4 inch (6 mm) shackle.
Padlockable Handle Lock Hasp
Used to lock the circuit breaker or switch handle in
either the ON or OFF position. Breaker is allowed to
trip when blocked in the ON position. Accepts up to
three padlocks with 1/4 inch (6 mm) shackles.
Used to lock the circuit breaker handle or switch in
OFF position. Accepts up to three padlocks with 1/4
inch (6 mm) shackles.
CPRO-CAT-1109
Discount
Code B30
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
copperLogic.com
www.barr-thorp.com
25
Accessories
F-series Field Installation Options
Ring Terminal Adapters
Accessory
Description
Thread Size
For use with…
Catalog Number
Price
Two pole F-series
KPEK12
53
Three pole F-series
KPEK1
53
Imperial
10-32
F-series
KPR1A
158
Max. Amps
For use with…
150
F-series
from 25 to 100 Amps
225
F-series
FCWTK225 ➋
from 110 to 225 Amps
End Cap Kit
A threaded adapter to accept a ring terminal or other
bolt-on connector to the circuit breaker or switch
Imperial
10-32
Keeper Nut
A threaded adapter to accept a ring terminal or other
bolt-on connector to the circuit breaker or switch
Order in sets of 12; priced individually
Control Wire Terminal Kits
Accessory
Description
Catalog Number
Price
Control Wire Terminal Kit
Used to tap off control power from circuit breaker
or switch
Order in sets of 12; priced individually
FCWTK ➊
26
26
Multi-wire Connectors
Accessory
Description
Max. Amps
Wires per
Terminal
225
3
Wire Size
For use with…
Catalog Number
Price
Multi-wire Connectors
Used to distribute the load from the
circuit breaker or switch to multiple
devices without the use of separate
distribution terminal blocks.
Priced and packaged in sets of three.
14 – 2 AWG
Cu
3TA150F3K
228
3TA150F6K
290
F-series
225
6
14 – 6 AWG
Cu
➊ For use with steel or stainless steel terminals only.
➊ Use only with aluminum terminal 3TA225FD.
26 copperLogic.com
Discount Code B30
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
CPRO-CAT-1109
www.barr-thorp.com
Accessories
F-series Field Installation Options
Base Mounting Hardware
Accessory
Description
Thread
Type
Screw Size
Mounting
Imperial
.164-32 x 3.188 in.
Individual
For use with…
Catalog Number
Price
Base Mounting Hardware
MHDF11
10
MHDF21
10
Single Pole F-series
For surface mounting of circuit breakers or switches. Includes pan-head
screws and lockwashers
Mounting hardware is not included
with breaker.
Imperial
.164-32 x 3.188 in. Two Breakers
Imperial
.164-32 x 1.5 in.
Individual
Two Pole F-series
MHDF2
10
Imperial
.164-32 x 1.5 in.
Individual
Three Pole F-series
MHDF3
10
Replacement Terminal Kits
Maximum
Set of Three Terminals Amp Rating
Material
Wire Type
Wire Range
For use with…
Catalog Number
Price
Replacement for Standard Terminals (line and load side terminals supplied with breaker)
CPRO-CAT-1109
100
Steel
Cu / Al
14 – 1/0 AWG
2.5 – 50 mm2
F-series
from 15 to 100 Amps
225
Aluminum
Cu / Al
4 – 4/0 AWG
25 – 95 mm2
F-series
3TA225FD
from 110 to 225 Amps
Discount
Code B30
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
3T100FB
copperLogic.com
www.barr-thorp.com
39
79
27
Application Data
Time / Current Curves
Time/Current Curve
TM1-FLS-15A…
TM1-FLS-20A…
15A
1h 2h
Maximum single pole
trip times at 25 °C
Minimum
1
.7
.5
.3
.2
1
.7
.5
.3
.2
Maximum
interrupting
time
TM1-FLS-30A…
25A
1h 2h
Maximum
Minimum
1
.7
.5
.3
.2
1
.7
.5
.3
.2
Maximum
interrupting
time
.01
.007
.005
.003
.002
2000
3000
5000
7000
10000
.001
Interrupting
rating
determines
end of curve
200
300
2000
3000
5000
7000
10000
500
700
1000
200
300
20
30
50
70
100
5
7
10
Interrupting
rating
determines
end of curve
CURRENT IN AMPERES
Maximum
Minimum
.1
.07
.05
.03
.02
Maximum
interrupting
time
.01
.007
.005
.003
.002
10
7
5
3
2
20
30
50
70
100
.1
.07
.05
.03
.02
Maximum single pole
trip times at 25 °C
100
70
50
30
20
CURRENT IN AMPERES
20000
30000
50000
70000
100000
TIME IN SECONDS
1 min
Maximum single pole
trip times at 25 °C
100
70
50
30
20
.001
30A
1000
700
500
300
200
20000
30000
50000
70000
100000
TIME IN SECONDS
1 min
1000
700
500
300
200
10000
7000
5000
3000
2000
5
7
10
1h 2h
Time/Current Curve
TM1-FLS-25A…
10
7
5
3
2
2000
3000
5000
7000
10000
CURRENT IN AMPERES
Time/Current Curve
10000
7000
5000
3000
2000
500
700
1000
Interrupting
rating
determines
end of curve
200
300
.001
20000
30000
50000
70000
100000
2000
3000
5000
7000
10000
500
700
1000
200
300
CURRENT IN AMPERES
Maximum
Minimum
.01
.007
.005
.003
.002
Interrupting
rating
determines
end of curve
20
30
50
70
100
5
7
10
.001
10
7
5
3
2
.1
.07
.05
.03
.02
Maximum
interrupting
time
.01
.007
.005
.003
.002
Maximum single pole
trip times at 25 °C
100
70
50
30
20
20000
30000
50000
70000
100000
Maximum
.1
.07
.05
.03
.02
20A
500
700
1000
10
7
5
3
2
1 min
100
70
50
30
20
For application and coordination purposes only.
Based on 40°C ambient, cold
start. Connected with four feet
of rated wire (60°C up to 125A,
75°C above 125A) per terminal.
Tested in open air with current
in all poles.
Single pole test data at 25°C
based on NEMA procedures (AB
4-2003) for verifying performance of molded case circuit
breakers.
1000
700
500
300
200
5
7
10
TIME IN SECONDS
1 min
1000
700
500
300
200
10000
7000
5000
3000
2000
20
30
50
70
100
10000
7000
5000
3000
2000
TIME IN SECONDS
1h 2h
Time/Current Curve
28 copperLogic.com
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
CPRO-CAT-1109
www.barr-thorp.com
Application Data
Time / Current Curves
Time/Current Curve
TM1-FLS-35A…
TM1-FLS-40A…
35A
1000
700
500
300
200
1
.7
.5
.3
.2
.1
.07
.05
.03
.02
TM1-FLS-50A…
45A
1h 2h
1 min
Maximum
Minimum
1
.7
.5
.3
.2
CPRO-CAT-1109
Maximum
interrupting
time
.01
.007
.005
.003
.002
Interrupting
rating
determines
end of curve
2000
3000
5000
7000
10000
.001
5
7
10
2000
3000
5000
7000
10000
500
700
1000
200
300
20
30
50
70
100
5
7
10
.1
.07
.05
.03
.02
Interrupting
rating
determines
end of curve
CURRENT IN AMPERES
Maximum
Minimum
1
.7
.5
.3
.2
Maximum
interrupting
time
.01
.007
.005
.003
.002
.001
10
7
5
3
2
200
300
.1
.07
.05
.03
.02
Maximum single pole
trip times at 25 °C
20
30
50
70
100
10
7
5
3
2
50A
100
70
50
30
20
TIME IN SECONDS
1 min
TIME IN SECONDS
Maximum single pole
trip times at 25 °C
100
70
50
30
20
10000
7000
5000
3000
2000
1000
700
500
300
200
20000
30000
50000
70000
100000
1h 2h
Time/Current Curve
TM1-FLS-45A…
1000
700
500
300
200
2000
3000
5000
7000
10000
CURRENT IN AMPERES
Time/Current Curve
10000
7000
5000
3000
2000
500
700
1000
200
300
Interrupting
rating
determines
end of curve
20
30
50
70
100
.001
20000
30000
50000
70000
100000
2000
3000
5000
7000
10000
500
700
1000
200
300
CURRENT IN AMPERES
Maximum
interrupting
time
.01
.007
.005
.003
.002
Interrupting
rating
determines
end of curve
20
30
50
70
100
5
7
10
.001
1
.7
.5
.3
.2
Maximum
interrupting
time
.01
.007
.005
.003
.002
Maximum
Minimum
20000
30000
50000
70000
100000
Minimum
.1
.07
.05
.03
.02
10
7
5
3
2
CURRENT IN AMPERES
20000
30000
50000
70000
100000
Maximum
Maximum single pole
trip times at 25 °C
100
70
50
30
20
5
7
10
10
7
5
3
2
1 min
Maximum single pole
trip times at 25 °C
100
70
50
30
20
TIME IN SECONDS
TIME IN SECONDS
1 min
1000
700
500
300
200
For application and coordination purposes only.
Based on 40°C ambient, cold
start. Connected with four feet
of rated wire (60°C up to 125A,
75°C above 125A) per terminal.
Tested in open air with current
in all poles.
Single pole test data at 25°C
based on NEMA procedures (AB
4-2003) for verifying performance of molded case circuit
breakers.
40A
10000
7000
5000
3000
2000
500
700
1000
10000
7000
5000
3000
2000
1h 2h
1h 2h
Time/Current Curve
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
copperLogic.com
www.barr-thorp.com
29
Application Data
Time / Current Curves
Time/Current Curve
TM1-FLS-60A…
TM1-FLS-70A…
60A
1h 2h
1000
700
500
300
200
Maximum single pole
trip times at 25 °C
1 min
Minimum
1
.7
.5
.3
.2
CURRENT IN AMPERES
Time/Current Curve
TM1-FLS-80A…
TM1-FLS-90A…
1h 2h
80A
Maximum single pole
trip times at 25 °C
1 min
100
70
50
30
20
Maximum
Minimum
1
.7
.5
.3
.2
CURRENT IN AMPERES
Maximum
Minimum
1
.7
.5
.3
.2
Maximum
interrupting
time
.01
.007
.005
.003
.002
2000
3000
5000
7000
10000
.001
Interrupting
rating
determines
end of curve
200
300
2000
3000
5000
7000
10000
500
700
1000
200
300
Interrupting
rating
determines
end of curve
20
30
50
70
100
5
7
10
.001
10
7
5
3
2
.1
.07
.05
.03
.02
Maximum
interrupting
time
.01
.007
.005
.003
.002
Maximum single pole
trip times at 25 °C
20
30
50
70
100
.1
.07
.05
.03
.02
90A
100
70
50
30
20
5
7
10
10
7
5
3
2
10000
7000
5000
3000
2000
1000
700
500
300
200
TIME IN SECONDS
TIME IN SECONDS
1 min
1000
700
500
300
200
20000
30000
50000
70000
100000
1h 2h
Time/Current Curve
10000
7000
5000
3000
2000
2000
3000
5000
7000
10000
Interrupting
rating
determines
end of curve
500
700
1000
.001
20000
30000
50000
70000
100000
2000
3000
5000
7000
10000
500
700
1000
200
300
CURRENT IN AMPERES
Maximum
interrupting
time
.01
.007
.005
.003
.002
Interrupting
rating
determines
end of curve
20
30
50
70
100
5
7
10
.001
1
.7
.5
.3
.2
.1
.07
.05
.03
.02
Maximum
interrupting
time
.01
.007
.005
.003
.002
Maximum
Minimum
200
300
.1
.07
.05
.03
.02
10
7
5
3
2
20000
30000
50000
70000
100000
Maximum
500
700
1000
10
7
5
3
2
Maximum single pole
trip times at 25 °C
100
70
50
30
20
CURRENT IN AMPERES
20000
30000
50000
70000
100000
100
70
50
30
20
5
7
10
TIME IN SECONDS
1 min
1000
700
500
300
200
For application and coordination purposes only.
Based on 40°C ambient, cold
start. Connected with four feet
of rated wire (60°C up to 125A,
75°C above 125A) per terminal.
Tested in open air with current
in all poles.
Single pole test data at 25°C
based on NEMA procedures (AB
4-2003) for verifying performance of molded case circuit
breakers.
70A
10000
7000
5000
3000
2000
20
30
50
70
100
10000
7000
5000
3000
2000
TIME IN SECONDS
1h 2h
Time/Current Curve
30 copperLogic.com
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
CPRO-CAT-1109
www.barr-thorp.com
Application Data
Time / Current Curves
Time/Current Curve
TM1-FLS-100A…
TM1-FLS-110A…
100A
1h 2h
1000
700
500
300
200
Maximum single pole
trip times at 25 °C
1 min
.1
.07
.05
.03
.02
CURRENT IN AMPERES
Time/Current Curve
TM1-FLS-125A…
TM1-FLS-150A…
1h 2h
Maximum
Minimum
1
.7
.5
.3
.2
.1
.07
.05
.03
.02
CURRENT IN AMPERES
CPRO-CAT-1109
Maximum
Minimum
1
.7
.5
.3
.2
.1
.07
.05
.03
.02
Maximum
interrupting
time
.01
.007
.005
.003
.002
.001
5
7
10
2000
3000
5000
7000
10000
500
700
1000
200
300
Interrupting
rating
determines
end of curve
20
30
50
70
100
5
7
10
10
7
5
3
2
Maximum
interrupting
time
.01
.007
.005
.003
.002
.001
100
70
50
30
20
Interrupting
rating
determines
end of curve
200
300
1 min
100
70
50
30
20
Maximum single pole
trip times at 25 °C
20
30
50
70
100
Maximum single pole
trip times at 25 °C
10
7
5
3
2
150A
1000
700
500
300
200
TIME IN SECONDS
TIME IN SECONDS
1 min
1000
700
500
300
200
10000
7000
5000
3000
2000
2000
3000
5000
7000
10000
125A
20000
30000
50000
70000
100000
1h 2h
Time/Current Curve
10000
7000
5000
3000
2000
2000
3000
5000
7000
10000
Interrupting
rating
determines
end of curve
500
700
1000
.001
20000
30000
50000
70000
100000
2000
3000
5000
7000
10000
500
700
1000
200
300
CURRENT IN AMPERES
Maximum
interrupting
time
.01
.007
.005
.003
.002
Interrupting
rating
determines
end of curve
20
30
50
70
100
5
7
10
1
.7
.5
.3
.2
Maximum
interrupting
time
.01
.007
.005
.003
.002
Maximum
Minimum
20000
30000
50000
70000
100000
Minimum
1
.7
.5
.3
.2
.001
10
7
5
3
2
CURRENT IN AMPERES
20000
30000
50000
70000
100000
Maximum
.1
.07
.05
.03
.02
100
70
50
30
20
200
300
10
7
5
3
2
Maximum single pole
trip times at 25 °C
500
700
1000
100
70
50
30
20
5
7
10
TIME IN SECONDS
1 min
1000
700
500
300
200
For application and coordination purposes only.
Based on 40°C ambient, cold
start. Connected with four feet
of rated wire (60°C up to 125A,
75°C above 125A) per terminal.
Tested in open air with current
in all poles.
Single pole test data at 25°C
based on NEMA procedures (AB
4-2003) for verifying performance of molded case circuit
breakers.
110A
10000
7000
5000
3000
2000
20
30
50
70
100
10000
7000
5000
3000
2000
TIME IN SECONDS
1h 2h
Time/Current Curve
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
copperLogic.com
www.barr-thorp.com
31
Application Data
Time / Current Curves
Time/Current Curve
TM(2)(3)-FLS-15A…, TM(2)(3)-FMS-15A…
TM(2)(3)-FHS-15A…
15A
10000
7000
5000
3000
2000
1h 2h
15A
CURRENT IN AMPERES
TM(2)(3)-FHS-20A…
20A
1h 2h
20A
1000
700
500
300
200
2000
3000
5000
7000
10000
500
700
1000
200
300
20
30
50
70
100
5
7
10
Interrupting
rating
determines
end of curve
CURRENT IN AMPERES
Maximum
.1
.07
.05
.03
.02
Maximum
interrupting
time
.01
.007
.005
.003
.002
.001
200000
20000
30000
50000
70000
100000
10000
Minimum
.01
.007
.005
.003
.002
See Inset for
end of curve
CURRENT IN AMPERES
20000
30000
50000
70000
100000
.01
.007
.005
.003
.002
240V
2000
3000
5000
7000
10000
Maximum
interrupting
time
480V
500
700
1000
.1
.07
.05
.03
.02
1
.7
.5
.3
.2
.02
600V
10
7
5
3
2
200
300
1
.7
.5
.3
.2
Maximum single pole
trip times at 25 °C
100
70
50
30
20
20
30
50
70
100
Maximum
TIME IN SECONDS
Minimum
1 min
Maximum single pole
trip times at 25 °C
100
70
50
30
20
20000
30000
50000
70000
100000
TIME IN SECONDS
1 min
1000
700
500
300
200
10000
7000
5000
3000
2000
5
7
10
1h 2h
Time/Current Curve
20000
30000
50000
70000
100000
See Inset for
end of curve
TM(2)(3)-FLS-20A…, TM(2)(3)-FMS-20A…
.001
200000
Maximum
interrupting
time
Time/Current Curve
10000
7000
5000
3000
2000
.01
.007
.005
.003
.002
Maximum
2000
3000
5000
7000
10000
.001
5
7
10
2000
3000
5000
7000
10000
500
700
1000
200
300
20
30
50
70
100
5
7
10
CURRENT IN AMPERES
Minimum
.01
.007
.005
.003
.002
Interrupting
rating
determines
end of curve
.001
240V
.1
.07
.05
.03
.02
Maximum
interrupting
time
.01
.007
.005
.003
.002
1
.7
.5
.3
.2
500
700
1000
.1
.07
.05
.03
.02
480V
200
300
1
.7
.5
.3
.2
.02
600V
10
7
5
3
2
20000
30000
50000
70000
100000
TIME IN SECONDS
Minimum
Maximum single pole
trip times at 25 °C
100
70
50
30
20
10000
1 min
Maximum
20000
30000
50000
70000
100000
1 min
TIME IN SECONDS
Maximum single pole
trip times at 25 °C
100
70
50
30
20
10
7
5
3
2
For application and coordination purposes only.
Based on 40°C ambient, cold
start. Connected with four feet
of rated wire (60°C up to 125A,
75°C above 125A) per terminal.
Tested in open air with current
in all poles.
Single pole test data at 25°C
based on NEMA procedures (AB
4-2003) for verifying performance of molded case circuit
breakers.
1000
700
500
300
200
1000
700
500
300
200
10
7
5
3
2
10000
7000
5000
3000
2000
20
30
50
70
100
1h 2h
Time/Current Curve
32 copperLogic.com
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
CPRO-CAT-1109
www.barr-thorp.com
Application Data
Time / Current Curves
Time/Current Curve
TM(2)(3)-FLS-25A…, TM(2)(3)-FMS-25A…
TM(2)(3)-FHS-25A…
Maximum
interrupting
time
TM(2)(3)-FHS-30A…
CURRENT IN AMPERES
CPRO-CAT-1109
20000
30000
50000
70000
100000
Maximum
interrupting
time
See Inset for
end of curve
2000
3000
5000
7000
10000
.001
200000
20000
30000
50000
70000
100000
10000
Maximum
.01
.007
.005
.003
.002
5
7
10
2000
3000
5000
7000
10000
500
700
1000
200
300
20
30
50
70
100
5
7
10
.001
Interrupting
rating
determines
end of curve
.01
.007
.005
.003
.002
240V
Minimum
.1
.07
.05
.03
.02
Maximum
interrupting
time
.01
.007
.005
.003
.002
480V
20
30
50
70
100
.1
.07
.05
.03
.02
1
.7
.5
.3
.2
.02
600V
10
7
5
3
2
Maximum
1
.7
.5
.3
.2
Maximum single pole
trip times at 25 °C
100
70
50
30
20
500
700
1000
1h 2h
1 min
Maximum single pole
trip times at 25 °C
Minimum
30A
1000
700
500
300
200
TIME IN SECONDS
1 min
TIME IN SECONDS
10
7
5
3
2
10000
7000
5000
3000
2000
200
300
30A
20000
30000
50000
70000
100000
1h 2h
Time/Current Curve
100
70
50
30
20
2000
3000
5000
7000
10000
CURRENT IN AMPERES
TM(2)(3)-FLS-30A…, TM(2)(3)-FMS-30A…
1000
700
500
300
200
500
700
1000
See Inset for
end of curve
Time/Current Curve
10000
7000
5000
3000
2000
200000
Maximum
200
300
.001
5
7
10
2000
3000
5000
7000
10000
500
700
1000
200
300
20
30
50
70
100
5
7
10
CURRENT IN AMPERES
Minimum
.01
.007
.005
.003
.002
Interrupting
rating
determines
end of curve
.01
.007
.005
.003
.002
240V
.1
.07
.05
.03
.02
Maximum
interrupting
time
.01
.007
.005
.003
.002
.001
1
.7
.5
.3
.2
20
30
50
70
100
.1
.07
.05
.03
.02
480V
For application and coordination purposes only.
Based on 40°C ambient, cold
start. Connected with four feet
of rated wire (60°C up to 125A,
75°C above 125A) per terminal.
Tested in open air with current
in all poles.
Single pole test data at 25°C
based on NEMA procedures (AB
4-2003) for verifying performance of molded case circuit
breakers.
CURRENT IN AMPERES
20000
30000
50000
70000
100000
TIME IN SECONDS
1
.7
.5
.3
.2
.02
600V
10
7
5
3
2
Maximum
Minimum
Maximum single pole
trip times at 25 °C
100
70
50
30
20
20000
30000
50000
70000
100000
1 min
Maximum single pole
trip times at 25 °C
100
70
50
30
20
10
7
5
3
2
25A
1000
700
500
300
200
20000
30000
50000
70000
100000
TIME IN SECONDS
1 min
1000
700
500
300
200
10000
7000
5000
3000
2000
10000
25A
10000
7000
5000
3000
2000
1h 2h
1h 2h
Time/Current Curve
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
copperLogic.com
www.barr-thorp.com
33
Application Data
Time / Current Curves
Time/Current Curve
TM(2)(3)-FLS-35A…, TM(2)(3)-FMS-35A…
TM(2)(3)-FHS-35A…
TM(2)(3)-FHS-40A…
.1
.07
.05
.03
.02
Maximum
interrupting
time
.01
.007
.005
.003
.002
2000
3000
5000
7000
10000
500
700
1000
200
300
20
30
50
70
100
5
7
10
.001
Interrupting
rating
determines
end of curve
CURRENT IN AMPERES
Minimum
20000
30000
50000
70000
100000
240V
20000
30000
50000
70000
100000
Maximum
.1
.07
.05
.03
.02
Maximum
interrupting
time
.01
.007
.005
.003
.002
.001
.01
.007
.005
.003
.002
200000
480V
10000
1
.7
.5
.3
.2
.02
600V
10
7
5
3
2
See Inset for
end of curve
20
30
50
70
100
TIME IN SECONDS
1
.7
.5
.3
.2
Maximum single pole
trip times at 25 °C
100
70
50
30
20
5
7
10
1 min
Maximum
Minimum
20000
30000
50000
70000
100000
1 min
TIME IN SECONDS
10
7
5
3
2
40A
1000
700
500
300
200
Maximum single pole
trip times at 25 °C
100
70
50
30
20
10000
7000
5000
3000
2000
200
300
1h 2h
40A
1000
700
500
300
200
200000
10000
Time/Current Curve
TM(2)(3)-FLS-40A…, TM(2)(3)-FMS-40A…
1h 2h
Time/Current Curve
10000
7000
5000
3000
2000
2000
3000
5000
7000
10000
CURRENT IN AMPERES
2000
3000
5000
7000
10000
CURRENT IN AMPERES
.001
See Inset for
end of curve
500
700
1000
2000
3000
5000
7000
10000
500
700
1000
200
300
20
30
50
70
100
5
7
10
.001
Maximum
interrupting
time
.01
.007
.005
.003
.002
Interrupting
rating
determines
end of curve
.01
.007
.005
.003
.002
Maximum
.1
.07
.05
.03
.02
Maximum
interrupting
time
.01
.007
.005
.003
.002
240V
Minimum
500
700
1000
.1
.07
.05
.03
.02
1
.7
.5
.3
.2
200
300
1
.7
.5
.3
.2
480V
20
30
50
70
100
Minimum
.02
600V
10
7
5
3
2
CURRENT IN AMPERES
20000
30000
50000
70000
100000
1h 2h
Maximum
Maximum single pole
trip times at 25 °C
100
70
50
30
20
5
7
10
10
7
5
3
2
1 min
Maximum single pole
trip times at 25 °C
100
70
50
30
20
For application and coordination purposes only.
Based on 40°C ambient, cold
start. Connected with four feet
of rated wire (60°C up to 125A,
75°C above 125A) per terminal.
Tested in open air with current
in all poles.
Single pole test data at 25°C
based on NEMA procedures (AB
4-2003) for verifying performance of molded case circuit
breakers.
35A
1000
700
500
300
200
TIME IN SECONDS
TIME IN SECONDS
1 min
1000
700
500
300
200
10000
7000
5000
3000
2000
20000
30000
50000
70000
100000
35A
10000
7000
5000
3000
2000
20000
30000
50000
70000
100000
1h 2h
Time/Current Curve
34 copperLogic.com
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
CPRO-CAT-1109
www.barr-thorp.com
Application Data
Time / Current Curves
Time/Current Curve
TM(2)(3)-FLS-45A…, TM(2)(3)-FMS-45A…
TM(2)(3)-FHS-45A…
.01
.007
.005
.003
.002
Time/Current Curve
TM(2)(3)-FLS-50A…, TM(2)(3)-FMS-50A…
TM(2)(3)-FHS-50A…
1h 2h
.1
.07
.05
.03
.02
CURRENT IN AMPERES
CPRO-CAT-1109
200000
20000
30000
50000
70000
100000
480V
Maximum
Maximum
interrupting
time
.01
.007
.005
.003
.002
.001
.01
.007
.005
.003
.002
240V
Minimum
.1
.07
.05
.03
.02
5
7
10
2000
3000
5000
7000
10000
500
700
1000
200
300
20
30
50
70
100
Interrupting
rating
determines
end of curve
.02
600V
20000
30000
50000
70000
100000
1
.7
.5
.3
.2
Maximum
interrupting
time
.01
.007
.005
.003
.002
5
7
10
10
7
5
3
2
See Inset for
end of curve
200
300
1 min
1
.7
.5
.3
.2
.001
100
70
50
30
20
Maximum
Minimum
Maximum single pole
trip times at 25 °C
20
30
50
70
100
Maximum single pole
trip times at 25 °C
100
70
50
30
20
10
7
5
3
2
50A
1000
700
500
300
200
TIME IN SECONDS
TIME IN SECONDS
1 min
1000
700
500
300
200
10000
7000
5000
3000
2000
200000
50A
20000
30000
50000
70000
100000
1h 2h
Time/Current Curve
10000
7000
5000
3000
2000
2000
3000
5000
7000
10000
CURRENT IN AMPERES
2000
3000
5000
7000
10000
CURRENT IN AMPERES
.001
See Inset for
end of curve
500
700
1000
2000
3000
5000
7000
10000
500
700
1000
200
300
Interrupting
rating
determines
end of curve
20
30
50
70
100
5
7
10
.001
Maximum
interrupting
time
200
300
.01
.007
.005
.003
.002
Maximum
.1
.07
.05
.03
.02
Maximum
interrupting
time
.01
.007
.005
.003
.002
240V
Minimum
500
700
1000
.1
.07
.05
.03
.02
1
.7
.5
.3
.2
20
30
50
70
100
1
.7
.5
.3
.2
480V
10000
1 min
Minimum
.02
600V
10
7
5
3
2
Maximum
5
7
10
10
7
5
3
2
Maximum single pole
trip times at 25 °C
100
70
50
30
20
For application and coordination purposes only.
Based on 40°C ambient, cold
start. Connected with four feet
of rated wire (60°C up to 125A,
75°C above 125A) per terminal.
Tested in open air with current
in all poles.
Single pole test data at 25°C
based on NEMA procedures (AB
4-2003) for verifying performance of molded case circuit
breakers.
CURRENT IN AMPERES
20000
30000
50000
70000
100000
1h 2h
Maximum single pole
trip times at 25 °C
100
70
50
30
20
45A
1000
700
500
300
200
TIME IN SECONDS
TIME IN SECONDS
1 min
1000
700
500
300
200
10000
7000
5000
3000
2000
20000
30000
50000
70000
100000
45A
10000
7000
5000
3000
2000
20000
30000
50000
70000
100000
1h 2h
Time/Current Curve
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
copperLogic.com
www.barr-thorp.com
35
Application Data
Time / Current Curves
Time/Current Curve
TM(2)(3)-FLS-60A…, TM(2)(3)-FMS-60A…
TM(2)(3)-FHS-60A…
CURRENT IN AMPERES
Time/Current Curve
TM(2)(3)-FLS-70A…, TM(2)(3)-FMS-70A…
TM(2)(3)-FHS-70A…
.1
.07
.05
.03
.02
Maximum
interrupting
time
.01
.007
.005
.003
.002
2000
3000
5000
7000
10000
500
700
1000
200
300
20
30
50
70
100
5
7
10
.001
Interrupting
rating
determines
end of curve
CURRENT IN AMPERES
10
7
5
3
2
1
.7
.5
.3
.2
Minimum
200000
Maximum
.1
.07
.05
.03
.02
Maximum
interrupting
time
600V
.01
.007
.005
.003
.002
.001
480V
240V
20000
30000
50000
70000
100000
1
.7
.5
.3
.2
100
70
50
30
20
200
300
500
700
1000
1 min
Maximum
Minimum
Maximum single pole
trip times at 25 °C
50
70
100
Maximum single pole
trip times at 25 °C
100
70
50
30
20
10
7
5
3
2
70A
1000
700
500
300
200
TIME IN SECONDS
TIME IN SECONDS
1 min
1000
700
500
300
200
10000
7000
5000
3000
2000
2000
3000
1h 2h
70A
20000
30000
50000
70000
100000
1h 2h
Time/Current Curve
10000
7000
5000
3000
2000
2000
3000
5000
7000
10000
See Inset for
end of curve
.001
20000
30000
50000
70000
100000
2000
3000
5000
7000
10000
500
700
1000
200
300
20
30
50
70
100
5
7
10
.01
.007
.005
.003
.002
Interrupting
rating
determines
end of curve
CURRENT IN AMPERES
Maximum
interrupting
time
500
700
1000
.01
.007
.005
.003
.002
.001
.1
.07
.05
.03
.02
Maximum
interrupting
time
.01
.007
.005
.003
.002
Maximum
200
300
.1
.07
.05
.03
.02
240V
Minimum
1
.7
.5
.3
.2
5000
7000
10000
1
.7
.5
.3
.2
480V
20
30
50
70
100
Minimum
.02
600V
10
7
5
3
2
20000
30000
50000
70000
100000
1 min
Maximum
Maximum single pole
trip times at 25 °C
100
70
50
30
20
20000
30000
50000
70000
100000
Maximum single pole
trip times at 25 °C
100
70
50
30
20
10
7
5
3
2
60A
10000
7000
5000
3000
2000
1000
700
500
300
200
TIME IN SECONDS
TIME IN SECONDS
1 min
1000
700
500
300
200
For application and coordination purposes only.
Based on 40°C ambient, cold
start. Connected with four feet
of rated wire (60°C up to 125A,
75°C above 125A) per terminal.
Tested in open air with current
in all poles.
Single pole test data at 25°C
based on NEMA procedures (AB
4-2003) for verifying performance of molded case circuit
breakers.
CURRENT IN AMPERES
200000
300000
500000
700000
1000000
60A
5
7
10
10000
7000
5000
3000
2000
1h 2h
1h 2h
Time/Current Curve
36 copperLogic.com
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
CPRO-CAT-1109
www.barr-thorp.com
Application Data
Time / Current Curves
Time/Current Curve
TM(2)(3)-FLS-80A…, TM(2)(3)-FMS-80A…
TM(2)(3)-FHS-80A…
1 min
600V
480V
TM(2)(3)-FHS-90A…
CPRO-CAT-1109
50
70
100
2000
3000
5000
7000
10000
500
700
1000
200
300
CURRENT IN AMPERES
Maximum
interrupting
time
600V
.01
.007
.005
.003
.002
.001
20
30
50
70
100
5
7
10
Interrupting
rating
determines
end of curve
Maximum
.1
.07
.05
.03
.02
Maximum
interrupting
time
.01
.007
.005
.003
.002
Minimum
480V
240V
200
300
500
700
1000
.1
.07
.05
.03
.02
1
.7
.5
.3
.2
20000
30000
50000
70000
100000
1h 2h
1 min
1
.7
.5
.3
.2
.001
10
7
5
3
2
Maximum
Minimum
Maximum single pole
trip times at 25 °C
100
70
50
30
20
TIME IN SECONDS
1 min
TIME IN SECONDS
10
7
5
3
2
90A
1000
700
500
300
200
Maximum single pole
trip times at 25 °C
100
70
50
30
20
10000
7000
5000
3000
2000
2000
3000
90A
20000
30000
50000
70000
100000
1h 2h
Time/Current Curve
TM(2)(3)-FLS-90A…, TM(2)(3)-FMS-90A…
1000
700
500
300
200
20000
30000
50000
70000
100000
CURRENT IN AMPERES
Time/Current Curve
10000
7000
5000
3000
2000
5000
7000
10000
50
70
100
2000
3000
240V
.001
20000
30000
50000
70000
100000
2000
3000
5000
7000
10000
500
700
1000
200
300
20
30
50
70
100
5
7
10
Maximum
interrupting
time
.01
.007
.005
.003
.002
Interrupting
rating
determines
end of curve
CURRENT IN AMPERES
Maximum
.1
.07
.05
.03
.02
Maximum
interrupting
time
.01
.007
.005
.003
.002
Minimum
5000
7000
10000
.1
.07
.05
.03
.02
1
.7
.5
.3
.2
200
300
500
700
1000
1
.7
.5
.3
.2
.001
10
7
5
3
2
Maximum
Minimum
Maximum single pole
trip times at 25 °C
100
70
50
30
20
200000
300000
500000
700000
1000000
Maximum single pole
trip times at 25 °C
100
70
50
30
20
10
7
5
3
2
80A
1000
700
500
300
200
TIME IN SECONDS
TIME IN SECONDS
1 min
1000
700
500
300
200
10000
7000
5000
3000
2000
For application and coordination purposes only.
Based on 40°C ambient, cold
start. Connected with four feet
of rated wire (60°C up to 125A,
75°C above 125A) per terminal.
Tested in open air with current
in all poles.
Single pole test data at 25°C
based on NEMA procedures (AB
4-2003) for verifying performance of molded case circuit
breakers.
CURRENT IN AMPERES
200000
300000
500000
700000
1000000
80A
10000
7000
5000
3000
2000
1h 2h
1h 2h
Time/Current Curve
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
copperLogic.com
www.barr-thorp.com
37
Application Data
Time / Current Curves
Time/Current Curve
TM(2)(3)-FLS-100A…, TM(2)(3)-FMS-100A…
TM(2)(3)-FHS-100A…
1 min
Maximum
600V
480V
TM(2)(3)-FHS-110A…
Maximum
interrupting
time
.01
.007
.005
.003
.002
2000
3000
5000
7000
10000
500
700
1000
200
300
20
30
50
70
100
5
7
10
.001
Interrupting
rating
determines
end of curve
CURRENT IN AMPERES
10
7
5
3
2
1
.7
.5
.3
.2
Minimum
Maximum
.1
.07
.05
.03
.02
Maximum
interrupting
time
600V
.01
.007
.005
.003
.002
.001
480V
240V
20000
30000
50000
70000
100000
.1
.07
.05
.03
.02
100
70
50
30
20
200
300
500
700
1000
1
.7
.5
.3
.2
Maximum single pole
trip times at 25 °C
50
70
100
1 min
Maximum
TIME IN SECONDS
1 min
TIME IN SECONDS
Maximum single pole
trip times at 25 °C
Minimum
110A
1000
700
500
300
200
100
70
50
30
20
10
7
5
3
2
10000
7000
5000
3000
2000
2000
3000
1h 2h
110A
20000
30000
50000
70000
100000
1h 2h
Time/Current Curve
TM(2)(3)-FLS-110A…, TM(2)(3)-FMS-110A…
1000
700
500
300
200
20000
30000
50000
70000
100000
CURRENT IN AMPERES
Time/Current Curve
10000
7000
5000
3000
2000
5000
7000
10000
240V
.001
20000
30000
50000
70000
100000
2000
3000
5000
7000
10000
500
700
1000
200
300
CURRENT IN AMPERES
Maximum
interrupting
time
.01
.007
.005
.003
.002
Interrupting
rating
determines
end of curve
20
30
50
70
100
5
7
10
.001
Maximum
.1
.07
.05
.03
.02
Maximum
interrupting
time
.01
.007
.005
.003
.002
Minimum
5000
7000
10000
.1
.07
.05
.03
.02
1
.7
.5
.3
.2
2000
3000
1
.7
.5
.3
.2
10
7
5
3
2
200
300
500
700
1000
Minimum
Maximum single pole
trip times at 25 °C
100
70
50
30
20
200000
300000
500000
700000
1000000
Maximum single pole
trip times at 25 °C
100
70
50
30
20
10
7
5
3
2
100A
1000
700
500
300
200
TIME IN SECONDS
TIME IN SECONDS
1 min
1000
700
500
300
200
10000
7000
5000
3000
2000
For application and coordination purposes only.
Based on 40°C ambient, cold
start. Connected with four feet
of rated wire (60°C up to 125A,
75°C above 125A) per terminal.
Tested in open air with current
in all poles.
Single pole test data at 25°C
based on NEMA procedures (AB
4-2003) for verifying performance of molded case circuit
breakers.
CURRENT IN AMPERES
200000
300000
500000
700000
1000000
100A
50
70
100
10000
7000
5000
3000
2000
1h 2h
1h 2h
Time/Current Curve
38 copperLogic.com
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
CPRO-CAT-1109
www.barr-thorp.com
Application Data
Time / Current Curves
Time/Current Curve
TM(2)(3)-FLS-125A…, TM(2)(3)-FMS-125A…
TM(2)(3)-FHS-125A…
1
.7
.5
.3
.2
600V
480V
TM(2)(3)-FHS-150A…
CURRENT IN AMPERES
CPRO-CAT-1109
Maximum
Maximum
interrupting
time
600V
.01
.007
.005
.003
.002
480V
240V
200
300
500
700
1000
.001
50
70
100
2000
3000
5000
7000
10000
500
700
1000
200
300
20
30
50
70
100
Interrupting
rating
determines
end of curve
Minimum
.1
.07
.05
.03
.02
Maximum
interrupting
time
.01
.007
.005
.003
.002
5
7
10
1
.7
.5
.3
.2
20000
30000
50000
70000
100000
1h 2h
1 min
.1
.07
.05
.03
.02
.001
10
7
5
3
2
Maximum
1
.7
.5
.3
.2
Maximum single pole
trip times at 25 °C
100
70
50
30
20
TIME IN SECONDS
1 min
TIME IN SECONDS
100
70
50
30
20
Minimum
150A
1000
700
500
300
200
Maximum single pole
trip times at 25 °C
10
7
5
3
2
10000
7000
5000
3000
2000
2000
3000
150A
20000
30000
50000
70000
100000
1h 2h
Time/Current Curve
TM(2)(3)-FLS-150A…, TM(2)(3)-FMS-150A…
1000
700
500
300
200
20000
30000
50000
70000
100000
CURRENT IN AMPERES
Time/Current Curve
10000
7000
5000
3000
2000
5000
7000
10000
50
70
100
2000
3000
240V
.001
20000
30000
50000
70000
100000
2000
3000
5000
7000
10000
500
700
1000
200
300
20
30
50
70
100
Maximum
interrupting
time
.01
.007
.005
.003
.002
Interrupting
rating
determines
end of curve
CURRENT IN AMPERES
Maximum
.1
.07
.05
.03
.02
Maximum
interrupting
time
.01
.007
.005
.003
.002
Minimum
5000
7000
10000
.1
.07
.05
.03
.02
5
7
10
10
7
5
3
2
200
300
500
700
1000
1
.7
.5
.3
.2
.001
100
70
50
30
20
Maximum
Minimum
Maximum single pole
trip times at 25 °C
200000
300000
500000
700000
1000000
1 min
100
70
50
30
20
10
7
5
3
2
125A
1000
700
500
300
200
Maximum single pole
trip times at 25 °C
TIME IN SECONDS
TIME IN SECONDS
1 min
1000
700
500
300
200
10000
7000
5000
3000
2000
For application and coordination purposes only.
Based on 40°C ambient, cold
start. Connected with four feet
of rated wire (60°C up to 125A,
75°C above 125A) per terminal.
Tested in open air with current
in all poles.
Single pole test data at 25°C
based on NEMA procedures (AB
4-2003) for verifying performance of molded case circuit
breakers.
CURRENT IN AMPERES
200000
300000
500000
700000
1000000
125A
10000
7000
5000
3000
2000
1h 2h
1h 2h
Time/Current Curve
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
copperLogic.com
www.barr-thorp.com
39
Application Data
Time / Current Curves
Time/Current Curve
TM(2)(3)-F(L)(M)S-(175)(200)(225)A…
TM(2)(3)-FHS-(175)(200)(225)A…
Minimum
175 A
200 A
225 A
Drawn for In=200A;
for In π 200A, the end
points in this region
are displaced along
the current axis by
a factor (200A/In)
200
300
500
700
1000
50
70
100
20
30
2
3
5
7
10
0.5
0.7
1
.001
CURRENT IN MULTIPLES OF In
Minimum
1
.7
.5
.3
.2
175 A
200 A
225 A
.1
.07
.05
.03
.02
Maximum
interrupting
time
.01
.007
.005
.003
.002
Maximum
Maximum
interrupting
time
Drawn for In=200A;
for In π 200A, the end
points in this region
are displaced along
the current axis by
a factor (200A/In)
.01
.007
.005
.003
.002
.001
20
30
.1
.07
.05
.03
.02
10
7
5
3
2
2
3
5
7
10
1
.7
.5
.3
.2
100
70
50
30
20
2000
3000
5000
7000
10000
Maximum
Maximum single pole
trip times at 25 °C
200
300
500
700
1000
1 min
100
70
50
30
20
10
7
5
3
2
1000
700
500
300
200
Maximum single pole
trip times at 25 °C
For application and coordination purposes only.
Based on 40°C ambient, cold
start. Connected with four feet
of rated wire (60°C up to 125A,
75°C above 125A) per terminal.
Tested in open air with current
in all poles.
Single pole test data at 25°C
based on NEMA procedures (AB
4-2003) for verifying performance of molded case circuit
breakers.
175 – 225A
0.5
0.7
1
TIME IN SECONDS
1 min
1000
700
500
300
200
10000
7000
5000
3000
2000
50
70
100
1h 2h
175 – 225A
TIME IN SECONDS
10000
7000
5000
3000
2000
2000
3000
5000
7000
10000
1h 2h
Time/Current Curve
CURRENT IN MULTIPLES OF In
40 copperLogic.com
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
CPRO-CAT-1109
www.barr-thorp.com
Technical Data
cPRO F-series
cPRO F-series Circuit Breakers
cPRO F-series Molded Case Switches
General
Standards
Dimensions (W x H x D)
Single pole
Two pole
Three pole
Weight
Single pole
Two pole
Three pole
Mounting
…-FL(S)(C)-…
CS(2)(3)-FLC-…
[mm]
[mm]
[mm]
35 x 152 x 86
70 x 152 x 86
105 x 152 x 86
35 x 152 x 86
70 x 152 x 86
105 x 152 x 86
35 x 152 x 86
70 x 152 x 86
105 x 152 x 86
[kg]
[kg]
[kg]
0.91
1.36
2.04
0.91
1.36
2.04
0.91
1.36
2.04
90
90
[A]
[A]
90
90
110 – 225 Amps
…-FHS-…
UL 489, CSA C22.2 No. 5
Maximum rated current
Single pole
Two and Three pole
Rated operational voltage
NEMA
Permissible ambient temperature
DC Interrupting Rating
NEMA Time constant T = 8 rms
1 conducting path
2 conducting paths in series
AC Interrupting Rating
NEMA, Single pole breakers
277 V AC
347 V AC
125 V DC
NEMA, Two- and Three- pole breakers
240 V AC
480 V AC
600 V AC
250 V DC
Endurance (operating cycles)
Maximum switching frequency
Main Conductor Terminal Capacities
Terminal type
Solid or stranded
15 – 20 Amps
25 – 100 Amps
110 – 225 Amps
Tightening torque for box terminals
15 – 20 Amps
25 – 100 Amps
…-FM(S)(C)-…
CS(2)(3)-FMC-…
150
225
30
225
30
225
600
0 … 40 °C / 32 … 104 °F
600
0 … 40 °C / 32 … 104 °F
600
0 … 40 °C / 32 … 104 °F
[kA]
[kA]
10
22
10
22
10
22
[kA]
[kA]
[kA]
35
18
10
65
25 ➊
10
–
30 ➊
10 ➊
[kA]
[kA]
[kA]
[kA]
65
35
18
10
10000
300
100
65
25
22
10000
300
200
100
35
22
10000
300
box terminals
box terminals
box terminals
[AWG]
[AWG]
[AWG]
#14 – #10
#14 – #1/0
#4 – #4/0
#14 – #10
#14 – #1/0
#4 – #4/0
#14 – #10
#14 – #1/0
#4 – #4/0
[lbs-in]
[lbs-in]
35
#14 – #10 AWG: 35;
#8 AWG: 40;
#6 – #4 AWG: 45;
#3 – #1/0 AWG: 50
120
35
#14 – #10 AWG: 35;
#8 AWG: 40;
#6 – #4 AWG: 45;
#3 – #1/0 AWG: 50
120
35
#14 – #10 AWG: 35;
#8 AWG: 40;
#6 – #4 AWG: 45;
#3 – #1/0 AWG: 50
120
[V AC]
[°C / °F]
250 V DC
250 V DC
[per hour]
[lbs-in]
➊ CSA only; not UL listed.
CPRO-CAT-1109
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
copperLogic.com
www.barr-thorp.com
41
Technical Data
cPRO F-series
cPRO F-series Circuit Breakers
cPRO F-series Molded Case Switches
Auxiliary Switches
Maximum rated voltage
AC
DC
Rated operational current - AC
600V
Rated operational current - DC
125V
250V
Undervoltage Releases
Response voltage - AC, 50/60 Hz
12V
Dropout Min
Dropout Max
Pickup Max
24V
Dropout Min
Dropout Max
Pickup Max
48 – 60V
Dropout Min
Dropout Max
Pickup Max
110 – 127V
Dropout Min
Dropout Max
Pickup Max
208 – 240V
Dropout Min
Dropout Max
Pickup Max
380 – 480V
Dropout Min
Dropout Max
Pickup Max
525 – 600V
Dropout Min
Dropout Max
Pickup Max
Power consumption - AC, 50/60 Hz
12V
24V
48V
60V
110V
120V
127V
208V
220V
240V
380V
415V
440V
480V
525V
550V
600V
…-FL(S)(C)-…
CS(2)(3)-FLC-…
…-FM(S)(C)-…
CS(2)(3)-FMC-…
…-FHS-…
[V]
[V]
600
250
600
250
600
250
[A]
6
6
6
[A]
[A]
0.5
0.25
0.5
0.25
0.5
0.25
[V]
[V]
[V]
4.2
6.3
7.6
4.2
6.3
7.6
4.2
6.3
7.6
[V]
[V]
[V]
8.4
16.8
20.4
8.4
16.8
20.4
8.4
16.8
20.4
[V]
[V]
[V]
21.0
33.6
40.8
21.0
33.6
40.8
21.0
33.6
40.8
[V]
[V]
[V]
44.5
77.0
93.5
44.5
77.0
93.5
44.5
77.0
93.5
[V]
[V]
[V]
84.0
145.6
176.8
84.0
145.6
176.8
84.0
145.6
176.8
[V]
[V]
[V]
168.0
266.0
323.0
168.0
266.0
323.0
168.0
266.0
323.0
[V]
[V]
[V]
210.0
367.0
446.0
210.0
367.0
446.0
210.0
367.0
446.0
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
1.3 / 2.5
1.4
1.2
1.9
1.3
1.5
1.7
2.2
2.4
2.9
2.9
3.5
3.9
4.6
4.3
4.8
5.8
1.3 / 2.5
1.4
1.2
1.9
1.3
1.5
1.7
2.2
2.4
2.9
2.9
3.5
3.9
4.6
4.3
4.8
5.8
1.3 / 2.5
1.4
1.2
1.9
1.3
1.5
1.7
2.2
2.4
2.9
2.9
3.5
3.9
4.6
4.3
4.8
5.8
42 copperLogic.com
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
CPRO-CAT-1109
www.barr-thorp.com
Technical Data
cPRO F-series
cPRO F-series Circuit Breakers
cPRO F-series Molded Case Switches
Undervoltage Releases (continued)
Response voltage - DC
12V
Dropout Min
Dropout Max
Pickup Max
24V
Dropout Min
Dropout Max
Pickup Max
48 – 60V
Dropout Min
Dropout Max
Pickup Max
110 – 125V
Dropout Min
Dropout Max
Pickup Max
220 – 250V
Dropout Min
Dropout Max
Pickup Max
Power consumption - DC
12V
24V
48V
60V
110V
120V
125V
220V
250V
Shunt Trips
Minimum operating voltage - AC, 50/60 Hz
12 – 24V
48 – 127V
208 – 380V
415 – 600V
Power consumption - AC, 50/60 Hz
12V
24V
48V
60V
110V
120V
127V
208V
220V
240V
380V
415V
440V
480V
525V
550V
600V
CPRO-CAT-1109
…-FL(S)(C)-…
CS(2)(3)-FLC-…
…-FM(S)(C)-…
CS(2)(3)-FMC-…
…-FHS-…
[V]
[V]
[V]
4.2
8.4
10.2
4.2
8.4
10.2
4.2
8.4
10.2
[V]
[V]
[V]
8.4
16.8
20.4
8.4
16.8
20.4
8.4
16.8
20.4
[V]
[V]
[V]
21.0
33.6
40.8
21.0
33.6
40.8
21.0
33.6
40.8
[V]
[V]
[V]
44.5
77.0
93.5
44.5
77.0
93.5
44.5
77.0
93.5
[V]
[V]
[V]
87.5
154.0
187.0
87.5
154.0
187.0
87.5
154.0
187.0
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
2.8
1.6
1.3
2.0
1.5
1.7
1.9
2.6
3.4
2.8
1.6
1.3
2.0
1.5
1.7
1.9
2.6
3.4
2.8
1.6
1.3
2.0
1.5
1.7
1.9
2.6
3.4
[V]
[V]
[V]
[V]
6.75
36
156
300
6.75
36
156
300
6.75
36
156
300
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
75
300
92
140
480
570
640
180
200
240
610
130
330
380
450
530
590
75
300
92
140
480
570
640
180
200
240
610
130
330
380
450
530
590
75
300
92
140
480
570
640
180
200
240
610
130
330
380
450
530
590
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
copperLogic.com
www.barr-thorp.com
43
Technical Data
cPRO F-series
cPRO F-series Circuit Breakers
cPRO F-series Molded Case Switches
Shunt Trips (continued)
Minimum operating voltage - DC
12 – 24V
48 – 60V
110 – 127V
220 – 250V
Power consumption - DC
12V
24V
48V
60V
110V
120V
125V
127V
220V
250V
…-FL(S)(C)-…
CS(2)(3)-FLC-…
…-FM(S)(C)-…
CS(2)(3)-FMC-…
…-FHS-…
[V]
[V]
[V]
[V]
9
36
77
–
9
36
77
–
9
36
77
–
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
100
400
100
160
55
66
71
72
110
140
100
400
100
160
55
66
71
72
110
140
100
400
100
160
55
66
71
72
110
140
44 copperLogic.com
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
CPRO-CAT-1109
www.barr-thorp.com
Dimensions
cPRO F-series
Circuit Breakers
Dimensions are in inches (millimeters).
Not intended for manufacturing purposes.
TM1-F…
.750
(19.05)
.469
(11.91)
Handle: .344(8.74) wide
x .375(9.53) thick
0˚ taper, load end
7˚ taper, line end
On
Off
2.350(59.69) R
6.000
(152.40)
4.500
(114.30)
Push to Trip
.750
(19.05)
.469
(11.91)
.344
(8.74)
.062(1.57)
1.375
(34.93)
3.188(80.98)
3.375(85.73)
3.500(88.90)
4.12 (104.65)
1.562
(39.67)
.740
(18.80)
Drilling Plans
TM1-F…
Front Connected
Front Cover Cutout
Rear Connected
.250(6.35) R
.469
(11.91)
.750
(19.05)
2.313
(58.75)
2.906
(73.81)
3.156
(73.03)
2.875
(73.03)
Breaker
Handle
4.500
(114.30)
1.906
(48.41)
1.189(30.20)
.188(4.78)
Diameter
.594
(15.10)
Breaker
Handle
5.063
(114.30)
Breaker
Handle
.581
(14.76)
Location of .500(12.70) diameter
megger holes, if required
.688
(17.46)
1.375
(34.93)
.164-32(M4 x 0.7) tap, 2 holes
CPRO-CAT-1109
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
.438(11.13) diameter holes for 15 to 100 amp
.563(14.30) diameter holes for 125 to 150 amp
copperLogic.com
www.barr-thorp.com
45
Dimensions
cPRO F-series
Circuit Breakers / Molded Case Switches
Dimensions are in inches (millimeters).
Not intended for manufacturing purposes.
TM2-F…; CS2-F…
1.375
(34.93)
.750
(19.05)
.469
(11.91)
Handle: .344(8.74) wide
x .375(9.53) thick
0˚ taper, load end
7˚ taper, line end
On
Off
2.350(59.69) R
4.500
(114.30)
6.000
(152.40)
.344
(8.74)
Push To Trip
.750
(19.05)
.469
(11.91)
.062(1.57)
2.750
(69.85)
3.188(80.98)
3.375(85.73)
3.500(88.90)
4.12 (104.65)
1.562
(39.67)
.740
(18.80)
Drilling Plans
TM2-F…; CS2-F…
Front Connected
Front Cover Cutout
Rear Connected
.25 0(6.35) R
.469
(11.91)
.750
(19.05)
2.313
(58.75)
2.906
(73.81)
1.906
(48.41)
1.189
(30.20)
4.500
(114.30)
.594
(15.10)
.581
(14.76)
.18 8 (4.78)
diameter
3.156
(80.16)
2.875
(73.03)
Breaker
Handle
5.063
(128.60)
Breaker
Handle
Breaker
Handle
1.375
(34.93)
Location of .50 0 (12.70)
diameter megger holes,
if required
.688
(17.46)
1.375
(34.93)
.164-3 2 (M4 x 0.7) tap,
2 holes
.43 8 (11.13) diameter holes for 15 to 100 amp
.56 3 (14.30) diameter holes for 125 to 150 amp
46 copperLogic.com
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
CPRO-CAT-1109
www.barr-thorp.com
Dimensions
cPRO F-series
Circuit Breakers / Molded Case Switches
Dimensions are in inches (millimeters).
Not intended for manufacturing purposes.
TM3-F…; CS3-F…
1.375
(34.93)
1.375
(34.93)
.750
(19.05)
.469
(11.91)
Handle: .344(8.74) wide
x .375(9.53) thick
0˚ taper, load end
7˚ taper, line end
On
Off
2.350(59.69) R
4.500
(114.30)
6.000
(152.40)
.344
(8.74)
Push to Trip
.750
(19.05)
.469
(11.91)
.062(1.57)
4.125
(104.78)
3.188(80.98)
3.375(85.73)
3.500(88.90)
4.12 (104.65)
1.562
(39.67)
.740
(18.80)
Drilling Plans
TM3-F…; CS3-F…
Front Connected
Front Cover Cutout
Rear Connected
.250(6.35) R
.469
(11.91)
.750 (19.05)
2.313
(58.75)
2.906
(73.81)
2.875
(73.03)
Breaker
Handle
1.906
(48.41)
4.500
(114.30)
.594
(15.10)
1.189
(30.20)
.581
(14.76)
1.375
(34.93)
1.375
(34.93)
3.156
(80.16)
Breaker
Handle
5.063
(128.60)
Breaker
Handle
.188(4.78)
Diameter
Location of .500(12.70) diameter
megger holes, if required
.688
(17.48)
1.375
(34.93)
.164-32(M4 x 0.7) tap,
4 holes
2.750
(69.85)
1.375
(34.93)
.438(11.13) diameter holes for 15 to 100 amp
.563(14.30) diameter holes for 125 to 150 amp
CPRO-CAT-1109
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
copperLogic.com
www.barr-thorp.com
47
cPRO K-series
Interchangeable Trip Units to 400 amps
R
K-series cPRO molded case circuit breakers are designed to use interchangeable
trip modules that control an array of operating characteristics from amp range to
the type of protection desired. The breakers are available in both thermal-magnetic and electronic types. In addition, several devices are 100% rated breakers.
This can prevent the need to upsize to a larger breaker size. Accessories and other
options are UL listed to be field installed, so adding or changing functionality is a
simple, on-site procedure.
The Choice is Yours
The thermal-magnetic breakers are rated to 600V AC / 250V DC, with continuous
amp ratings from 100 - 400A. Three levels of breaking capacity; high, medium and
low, are available up to 200kA.
>70 – 400 amperes
>100% rated breakers available
Electronic trip breakers can be used to tailor protection to your specific application
by offering multiple interchangeable trip options. Their modular design allows for
a range of trip ratings from 70 to 400A within the same compact frame size. Three
levels of breaking capacity are also available for every breaker.
>Thermal-magnetic and electronic breakers
have interchangeable trip units
>Also suitable for use with refrigerant motor
Interrupting Capacity [kA]
200
240V AC
(electronic breakers available as AC only)
480V AC
compressors (HACR rated)
> Listed in accordance with CSA C22.2 No. 5
and UL 489
600V AC
250V DC
100
100
65
65
35
22
High
Breaking Capacity
65
35
22
Medium
Breaking Capacity
Low
Breaking Capacity
48
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
25
18 10
www.barr-thorp.com
Electronic breakers
Turn it On
Choosing a K-series breaker with an
electronic trip module allows you to
coordinate the breaker with your application and circuit scheme. Four trip
characteristics are available: (see page
The cPRO K-series also includes
two and three-pole Molded Case
Switches, that offer up to 400A
switching capabilities in applications
to 600V AC and 250V DC. Molded
case switches are constructed of
circuit breaker components and
include a fixed magnetic trip to
increase the short circuit withstand
rating (65kA @480V) and to protect
the switch itself. They are also
listed for reverse feed use and are
100% rated devices. A Shunt Trip is
also available for these Switches, a
feature not offered by many other
manufacturers.
58 for a complete description)
• Long and short delay protection
• Long and short delay, instantaneous protection
• Long and short delay, ground
fault protection
• Long and short delay, ground fault
and instantaneous protection
In more complex panels, these options can guard against nuisance
tripping and assure that the breaker
closest to the fault trips first.
Safety you can see
1
The Rating Plug is installed into
the Trip Module in seconds. This determines the amp
range of the device.
2
Trip characteristics are determined by the type of Trip
Module chosen. Modules install in minutes.
CopperLogic breakers offer optional
viewing windows in the breaker frame that allow you to see
the position of the main power
contacts in toggle operated applications. This is a requirement
in the mining industry and certain utilities. If a pole is welded,
one glance at the window can
prevent serious injury.
Breakers can be purchased as an assembled unit or by
components for reduced inventories. Rather than stocking many sizes of complete breakers, a few frames can be
inventoried with various Ratings Plugs and Trip Modules.
Through-the-door & Flange
Mounted Operators
All operators include a lock-out mechanism for up to three padlocks that prevent the handle from being turned to
the ON position. Door interlocks also
prevent the enclosure door from being
opened while the handle is in the ON
position (defeat mechanisms are included). Flange handle can be mounted up to 10 ft. away from the breaker.
Standard handles are rated
NEMA 1 and 12 - available in
black and red
Ergonomic handles are rated
NEMA 1, 12, 3R, 4 and 4X
Flange handles are rated NEMA
1, 12, 3R, 4 and 4X
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
www.barr-thorp.com
49
> The economical solution for two pole applications to 250A @600V
> Protection for single-phase motors, transformers and branch circuits
> Interchangeable trip module allows for flexibility in the field
> HACR rated allows for use with refrigerant motor compressors
> Assembled units are factory sealed and approved for reverse feed use
Order by
Assembly
with back-fed mains
Thermal-Magnetic Two Pole Circuit Breakers with Interchangeable Trip Module (to 250A) ➊➋➌➍➎
Continuous
Amp Rating
@ 40° C (104° F)
Maximum
Operating
Voltage
AC
DC
Low Breaking Capacity
25 kAIC @ 600 V AC
35 kAIC @ 480 V AC
65 kAIC @ 240 V AC
10 kAIC @ 250 V DC ➏
Catalog Number
Price
Catalog Number
Price
High Breaking Capacity
65 kAIC @ 600 V AC
100 kAIC @ 480 V AC
200 kAIC @ 240 V AC
22 kAIC @ 250 V DC ➏
Catalog Number
Price
100
600
250
TM2-K2LS-100B-L
3752
TM2-K2MS-100B-L
4114
TM2-K2HS-100B-L
4802
125
600
250
TM2-K2LS-125B-L
3752
TM2-K2MS-125B-L
4114
TM2-K2HS-125B-L
4802
150
600
250
TM2-K2LS-150B-L
3752
TM2-K2MS-150B-L
4114
TM2-K2HS-150B-L
4802
175
600
250
TM2-K2LS-175B-L
3752
TM2-K2MS-175B-L
4114
TM2-K2HS-175B-L
4802
200
600
250
TM2-K2LS-200B-L
3752
TM2-K2MS-200B-L
4114
TM2-K2HS-200B-L
4802
225
600
250
TM2-K2LS-225B-L
3752
TM2-K2MS-225B-L
4114
TM2-K2HS-225B-L
4802
250
600
250
TM2-K2LS-250B-L
3752
TM2-K2MS-250B-L
4114
TM2-K2HS-250B-L
4802
Ordering Instructions
1
2
Medium Breaking Capacity
35 kAIC @ 600 V AC
65 kAIC @ 480 V AC
100 kAIC @ 240 V AC
22 kAIC @ 250 V DC ➏
Locate the desired complete circuit breaker
See pages 71 – 78 for accessories.
50 copperLogic.com
➊ Line and Load side terminals ship with breaker as standard. Other options are
available; contact your CopperLogic representative.
➋ A VISA-window to view main power contacts is available. If desired, add “S” to end of
catalog number, and add $1790 to price. For toggle style operators only.
➌ Two-pole circuit breakers are supplied in three-pole frame.
➍ Included trip modules have fixed thermal and adjustable magnetic settings.
➎ Mounting hardware not included. Order base mounting hardware separately on page 78.
➏Time constant is 3ms minimum at 10kA and 8ms minimum at 22kA.
Discount Code B30
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
CPRO-CAT-1109
www.barr-thorp.com
cPRO Molded Case Circuit Breakers
250A Thermal-Magnetic Two Pole, K-series
Order by
Components
Frames for Two Pole Thermal-Magnetic Circuit Breakers (to 250A) ➊➋➌
Maximum
Continuous
Amp Rating
@ 40° C (104° F)
250
Maximum
Operating
Voltage
Low Breaking Capacity
25 kAIC @ 600 V AC
35 kAIC @ 480 V AC
65 kAIC @ 240 V AC
10 kAIC @ 250 V DC ➍
Medium Breaking Capacity
35 kAIC @ 600 V AC
65 kAIC @ 480 V AC
100 kAIC @ 240 V AC
22 kAIC @ 250 V DC ➍
High Breaking Capacity
65 kAIC @ 600 V AC
100 kAIC @ 480 V AC
200 kAIC @ 240 V AC
22 kAIC @ 250 V DC ➍
AC
DC
Catalog Number
Price
Catalog Number
Price
Catalog Number
Price
600
250
MF2-KLS-250
2171
MF2-KMS-250
2500
MF2-KHS-250
3125
Trip Modules and Terminals
Trip Modules
Fixed Thermal, Adjustable Magnetic
Continuous
Amp Rating
@ 40° C (104° F)
100
Terminals
(individually priced and packaged)
Maximum
Operating
Voltage
Suitable for Low, Medium or
High Breaking Capacities
AC
DC
Catalog Number
Price
600
250
KT2100T
1069
125
600
250
KT2125T
1069
150
600
250
KT2150T
1069
175
600
250
KT2175T
1069
200
600
250
KT2200T
1069
225
600
250
KT2225T
1069
250
600
250
KT2250T
1069
Wire Range
Material
AWG
Aluminum
#3 – 350 MCM
TA300K
46
Aluminum
250 – 500 MCM
TA350K
46
Catalog Number
Price
Ordering Instructions
1
2
3
CPRO-CAT-1109
Choose desired circuit breaker frame.
Select trip module and terminals.
See pages 71 – 78 for accessories.
➊ A VISA-window to view main power contacts is available. If desired, add “S” to end of
breaker frame catalog number, and add $1790 to price. For toggle style operators only.
➋ Two-pole circuit breakers are supplied in three-pole frame.
➌ Mounting hardware not included. Order base mounting hardware separately on page 78.
➍ Time constant is 3ms minimum at 10kA and 8ms minimum at 22kA.
Discount
Code B30
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
copperLogic.com
www.barr-thorp.com
51
> Future-proof your systems with superior scalability from 100A to
Order by
Assembly
400A with just a quick change of the trip module! Lower cost and
installation time when your business grows.
> For two pole applications to 400A @600V
> Protection for single-phase motors, transformers and branch circuits
> Interchangeable trip module allows for flexibility in the field
> HACR rated allows for use with refrigerant motor compressors
> Assembled units are factory sealed and approved for reverse feed use
with back-fed mains
Thermal-Magnetic Two Pole Circuit Breakers with Interchangeable Trip Module (to 400A) ➊➋➌➍➎
Continuous
Amp Rating
@ 40° C (104° F)
Maximum
Operating
Voltage
AC
DC
Low Breaking Capacity
25 kAIC @ 600 V AC
35 kAIC @ 480 V AC
65 kAIC @ 240 V AC
10 kAIC @ 250 V DC ➏
Catalog Number
Price
Catalog Number
Price
High Breaking Capacity
65 kAIC @ 600 V AC
100 kAIC @ 480 V AC
200 kAIC @ 240 V AC
22 kAIC @ 250 V DC ➏
Catalog Number
Price
100
600
250
TM2-K4LS-100B-L
5996
TM2-K4MS-100B-L
6719
TM2-K4HS-100B-L
7877
125
600
250
TM2-K4LS-125B-L
5996
TM2-K4MS-125B-L
6719
TM2-K4HS-125B-L
7877
150
600
250
TM2-K4LS-150B-L
5996
TM2-K4MS-150B-L
6719
TM2-K4HS-150B-L
7877
175
600
250
TM2-K4LS-175B-L
5996
TM2-K4MS-175B-L
6719
TM2-K4HS-175B-L
7877
200
600
250
TM2-K4LS-200B-L
5996
TM2-K4MS-200B-L
6719
TM2-K4HS-200B-L
7877
225
600
250
TM2-K4LS-225B-L
5996
TM2-K4MS-225B-L
6719
TM2-K4HS-225B-L
7877
250
600
250
TM2-K4LS-250B-L
5996
TM2-K4MS-250B-L
6719
TM2-K4HS-250B-L
7877
300
600
250
TM2-K4LS-300B-L
5996
TM2-K4MS-300B-L
6719
TM2-K4HS-300B-L
7877
350
600
250
TM2-K4LS-350B-L
5996
TM2-K4MS-350B-L
6719
TM2-K4HS-350B-L
7877
400
600
250
TM2-K4LS-400B-L
5988
TM2-K4MS-400B-L
6712
TM2-K4HS-400B-L
7870
Ordering Instructions
1
2
Medium Breaking Capacity
35 kAIC @ 600 V AC
65 kAIC @ 480 V AC
100 kAIC @ 240 V AC
22 kAIC @ 250 V DC ➏
Locate the desired complete circuit breaker
See pages 71 – 78 for accessories.
52 copperLogic.com
➊ Line and Load side terminals ship with breaker as standard. Other options are
available; contact your CopperLogic representative.
➋ A VISA-window to view main power contacts is available. If desired, add “S” to end of
catalog number, and add $1790 to price. For toggle style operators only.
➌ Two-pole circuit breakers are supplied in three-pole frame.
➍ Included trip modules have fixed thermal and adjustable magnetic settings.
➎ Mounting hardware not included. Order base mounting hardware separately on page 78.
➏Time constant is 3ms minimum at 10kA and 8ms minimum at 22kA.
Discount Code B30
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
CPRO-CAT-1109
www.barr-thorp.com
cPRO Molded Case Circuit Breakers
400A Thermal-Magnetic Two Pole, K-series
Order by
Components
Frames for Two Pole Thermal-Magnetic Circuit Breakers (to 400A) ➊➋➌
Maximum
Continuous
Amp Rating
@ 40° C (104° F)
400
Maximum
Operating
Voltage
Low Breaking Capacity
25 kAIC @ 600 V AC
35 kAIC @ 480 V AC
65 kAIC @ 240 V AC
10 kAIC @ 250 V DC ➍
Medium Breaking Capacity
35 kAIC @ 600 V AC
65 kAIC @ 480 V AC
100 kAIC @ 240 V AC
22 kAIC @ 250 V DC ➍
High Breaking Capacity
65 kAIC @ 600 V AC
100 kAIC @ 480 V AC
200 kAIC @ 240 V AC
22 kAIC @ 250 V DC ➍
AC
DC
Catalog Number
Price
Catalog Number
Price
Catalog Number
Price
600
250
MF2-KLS-400
4211
MF2-KMS-400
4868
MF2-KHS-400
5921
Trip Modules and Terminals
Trip Modules
Fixed Thermal, Adjustable Magnetic
Continuous
Amp Rating
@ 40° C (104° F)
100
Terminals
(individually priced and packaged, except where noted) ➎
Maximum
Operating
Voltage
Suitable for Low, Medium or
High Breaking Capacities
AC
DC
Catalog Number
Price
600
250
KT2100T
1069
125
600
250
KT2125T
1069
150
600
250
KT2150T
1069
175
600
250
KT2175T
1069
200
600
250
KT2200T
1069
225
600
250
KT2225T
1069
250
600
250
KT2250T
1069
300
600
250
KT2300T
1069
350
600
250
KT2350T
1069
400
600
250
KT2400T
1069
Wire Range
Material
AWG
Aluminum
#3 – 350 MCM
TA300K
46
Aluminum
250 – 500 MCM
TA350K
46
Aluminum
2x (#3/0 – 250 MCM)
Catalog Number
2TA400K ➎
Price
175
(set of two)
Ordering Instructions
1
2
3
CPRO-CAT-1109
Choose desired circuit breaker frame.
Select trip module and terminals.
See pages 71 – 78 for accessories.
➊ A VISA-window to view main power contacts is available. If desired, add “S” to end of
breaker frame catalog number, and add $1790 to price. For toggle style operators only.
➋ Two-pole circuit breakers are supplied in three-pole frame.
➌ Mounting hardware not included. Order base mounting hardware separately on page 78.
➍ Time constant is 3ms minimum at 10kA and 8ms minimum at 22kA.
➎ Priced and packaged in sets of two. If line and load terminals are desired, order two sets.
Discount
Code B30
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
copperLogic.com
www.barr-thorp.com
53
> The economical solution for three pole applications to 250A @600V
> Protection for three-phase motors, transformers and branch circuits
> Interchangeable trip module allows for flexibility in the field
> HACR rated allows for use with refrigerant motor compressors
> Assembled units are factory sealed and approved for reverse feed use
Order by
Assembly
with back-fed mains
Thermal-Magnetic Three Pole Circuit Breakers with Interchangeable Trip Module (to 250A) ➊➋➌➍
Continuous
Amp Rating
@ 40° C (104° F)
Maximum
Operating
Voltage
AC
DC
Low Breaking Capacity
25 kAIC @ 600 V AC
35 kAIC @ 480 V AC
65 kAIC @ 240 V AC
10 kAIC @ 250 V DC ➎
Catalog Number
Price
Catalog Number
Price
High Breaking Capacity
65 kAIC @ 600 V AC
100 kAIC @ 480 V AC
200 kAIC @ 240 V AC
22 kAIC @ 250 V DC ➎
Catalog Number
Price
100
600
250
TM3-K2LS-100B-L
4534
TM3-K2MS-100B-L
4986
TM3-K2HS-100B-L
5800
125
600
250
TM3-K2LS-125B-L
4534
TM3-K2MS-125B-L
4986
TM3-K2HS-125B-L
5800
150
600
250
TM3-K2LS-150B-L
4534
TM3-K2MS-150B-L
4986
TM3-K2HS-150B-L
5800
175
600
250
TM3-K2LS-175B-L
4534
TM3-K2MS-175B-L
4986
TM3-K2HS-175B-L
5800
200
600
250
TM3-K2LS-200B-L
4534
TM3-K2MS-200B-L
4986
TM3-K2HS-200B-L
5800
225
600
250
TM3-K2LS-225B-L
4534
TM3-K2MS-225B-L
4986
TM3-K2HS-225B-L
5800
250
600
250
TM3-K2LS-250B-L
4534
TM3-K2MS-250B-L
4986
TM3-K2HS-250B-L
5800
Ordering Instructions
1
2
Medium Breaking Capacity
35 kAIC @ 600 V AC
65 kAIC @ 480 V AC
100 kAIC @ 240 V AC
22 kAIC @ 250 V DC ➎
Locate the desired complete circuit breaker
See pages 71 – 78 for accessories.
54 copperLogic.com
➊ Line and Load side terminals ship with breaker as standard. Other options are
available; contact your CopperLogic representative.
➋ A VISA-window to view main power contacts is available. If desired, add “S” to end of
catalog number, and add $1790 to price. For toggle style operators only.
➌ Included trip modules have fixed thermal and adjustable magnetic settings.
➍ Mounting hardware not included. Order base mounting hardware separately on page 78.
➎Time constant is 3ms minimum at 10kA and 8ms minimum at 22kA.
Discount Code B30
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
CPRO-CAT-1109
www.barr-thorp.com
cPRO Molded Case Circuit Breakers
250A Thermal-Magnetic Three Pole, K-series
Order by
Components
Frames for Three Pole Thermal-Magnetic Circuit Breakers (to 250A) ➊➋
Maximum
Continuous
Amp Rating
@ 40° C (104° F)
250
Maximum
Operating
Voltage
Low Breaking Capacity
25 kAIC @ 600 V AC
35 kAIC @ 480 V AC
65 kAIC @ 240 V AC
10 kAIC @ 250 V DC ➌
Medium Breaking Capacity
35 kAIC @ 600 V AC
65 kAIC @ 480 V AC
100 kAIC @ 240 V AC
22 kAIC @ 250 V DC ➌
High Breaking Capacity
65 kAIC @ 600 V AC
100 kAIC @ 480 V AC
200 kAIC @ 240 V AC
22 kAIC @ 250 V DC ➌
AC
DC
Catalog Number
Price
Catalog Number
Price
Catalog Number
Price
600
250
MF3-KLS-250
2714
MF3-KMS-250
3125
MF3-KHS-250
3865
Trip Modules and Terminals
Trip Modules
Fixed Thermal, Adjustable Magnetic
Continuous
Amp Rating
@ 40° C (104° F)
100
Terminals
(individually priced and packaged)
Maximum
Operating
Voltage
Suitable for Low, Medium or
High Breaking Capacities
AC
DC
Catalog Number
Price
600
250
KT3100T
1151
125
600
250
KT3125T
1151
150
600
250
KT3150T
1151
175
600
250
KT3175T
1151
200
600
250
KT3200T
1151
225
600
250
KT3225T
1151
250
600
250
KT3250T
1151
Wire Range
Material
AWG
Aluminum
#3 – 350 MCM
TA300K
46
Aluminum
250 – 500 MCM
TA350K
46
Catalog Number
Price
Ordering Instructions
1
2
3
CPRO-CAT-1109
Choose desired circuit breaker frame.
Select trip module and terminals.
See pages 71 – 78 for accessories.
➊ A VISA-window to view main power contacts is available. If desired, add “S” to end of
breaker frame catalog number, and add $1790 to price. For toggle style operators only.
➋ Mounting hardware not included. Order base mounting hardware separately on page 78.
➌ Time constant is 3ms minimum at 10kA and 8ms minimum at 22kA.
Discount
Code B30
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
copperLogic.com
www.barr-thorp.com
55
> Future-proof your systems with superior scalability from 100A to
Order by
Assembly
400A with just a quick change of the trip module! Lower cost and
installation time when your business grows.
> For three pole applications to 400A @600V
> Protection for three-phase motors, transformers and branch circuits
> Interchangeable trip module allows for flexibility in the field
> HACR rated allows for use with refrigerant motor compressors
> Assembled units are factory sealed and approved for reverse feed use
with back-fed mains
Thermal-Magnetic Three Pole Circuit Breakers with Interchangeable Trip Module (to 400A) ➊➋➌➍
Continuous
Amp Rating
@ 40° C (104° F)
Maximum
Operating
Voltage
AC
DC
Low Breaking Capacity
25 kAIC @ 600 V AC
35 kAIC @ 480 V AC
65 kAIC @ 240 V AC
10 kAIC @ 250 V DC ➎
Catalog Number
Price
Catalog Number
Price
High Breaking Capacity
65 kAIC @ 600 V AC
100 kAIC @ 480 V AC
200 kAIC @ 240 V AC
22 kAIC @ 250 V DC ➎
Catalog Number
Price
100
600
250
TM3-K4LS-100B-L
7338
TM3-K4MS-100B-L
8243
TM3-K4HS-100B-L
9632
125
600
250
TM3-K4LS-125B-L
7338
TM3-K4MS-125B-L
8243
TM3-K4HS-125B-L
9632
150
600
250
TM3-K4LS-150B-L
7338
TM3-K4MS-150B-L
8243
TM3-K4HS-150B-L
9632
175
600
250
TM3-K4LS-175B-L
7338
TM3-K4MS-175B-L
8243
TM3-K4HS-175B-L
9632
200
600
250
TM3-K4LS-200B-L
7338
TM3-K4MS-200B-L
8243
TM3-K4HS-200B-L
9632
225
600
250
TM3-K4LS-225B-L
7338
TM3-K4MS-225B-L
8243
TM3-K4HS-225B-L
9632
250
600
250
TM3-K4LS-250B-L
7338
TM3-K4MS-250B-L
8243
TM3-K4HS-250B-L
9632
300
600
250
TM3-K4LS-300B-L
7338
TM3-K4MS-300B-L
8243
TM3-K4HS-300B-L
9632
350
600
250
TM3-K4LS-350B-L
7338
TM3-K4MS-350B-L
8243
TM3-K4HS-350B-L
9632
400
600
250
TM3-K4LS-400B-L
7327
TM3-K4MS-400B-L
8232
TM3-K4HS-400B-L
9622
Ordering Instructions
1
2
Medium Breaking Capacity
35 kAIC @ 600 V AC
65 kAIC @ 480 V AC
100 kAIC @ 240 V AC
22 kAIC @ 250 V DC ➎
Locate the desired complete circuit breaker
See pages 71 – 78 for accessories.
56 copperLogic.com
➊ Line and Load side terminals ship with breaker as standard. Other options are
available; contact your CopperLogic representative.
➋ A VISA-window to view main power contacts is available. If desired, add “S” to end of
catalog number, and add $1790 to price. For toggle style operators only.
➌ Included trip modules have fixed thermal and adjustable magnetic settings.
➍ Mounting hardware not included. Order base mounting hardware separately on page 78.
➎Time constant is 3ms minimum at 10kA and 8ms minimum at 22kA.
Discount Code B30
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
CPRO-CAT-1109
www.barr-thorp.com
cPRO Molded Case Circuit Breakers
400A Thermal-Magnetic Three Pole, K-series
Order by
Components
Frames for Three Pole Thermal-Magnetic Circuit Breakers (to 400A) ➊➋
Maximum
Continuous
Amp Rating
@ 40° C (104° F)
400
Maximum
Operating
Voltage
Low Breaking Capacity
25 kAIC @ 600 V AC
35 kAIC @ 480 V AC
65 kAIC @ 240 V AC
10 kAIC @ 250 V DC ➌
Medium Breaking Capacity
35 kAIC @ 600 V AC
65 kAIC @ 480 V AC
100 kAIC @ 240 V AC
22 kAIC @ 250 V DC ➌
High Breaking Capacity
65 kAIC @ 600 V AC
100 kAIC @ 480 V AC
200 kAIC @ 240 V AC
22 kAIC @ 250 V DC ➌
AC
DC
Catalog Number
Price
Catalog Number
Price
Catalog Number
Price
600
250
MF3-KLS-400
5263
MF3-KMS-400
6086
MF3-KHS-400
7401
Trip Modules and Terminals
Trip Modules
Fixed Thermal, Adjustable Magnetic
Continuous
Amp Rating
@ 40° C (104° F)
100
Terminals
(individually priced and packaged, except where noted) ➍
Maximum
Operating
Voltage
Suitable for Low, Medium or
High Breaking Capacities
AC
DC
Catalog Number
Price
600
250
KT3100T
1151
125
600
250
KT3125T
1151
150
600
250
KT3150T
1151
175
600
250
KT3175T
1151
200
600
250
KT3200T
1151
225
600
250
KT3225T
1151
250
600
250
KT3250T
1151
300
600
250
KT3300T
1151
350
600
250
KT3350T
1151
400
600
250
KT3400T
1151
Wire Range
Material
AWG
Aluminum
#3 – 350 MCM
TA300K
46
Aluminum
250 – 500 MCM
TA350K
46
Aluminum
2x (#3/0 – 250 MCM)
Catalog Number
3TA400K ➍
Price
263
(set of three)
Ordering Instructions
1
2
3
CPRO-CAT-1109
Choose desired circuit breaker frame.
Select trip module and terminals.
See pages 71 – 78 for accessories.
➊ A VISA-window to view main power contacts is available. If desired, add “S” to end of
breaker frame catalog number, and add $1790 to price. For toggle style operators only.
➋ Mounting hardware not included. Order base mounting hardware separately on page 78.
➌ Time constant is 3ms minimum at 10kA and 8ms minimum at 22kA.
➍ Priced and packaged in sets of three. If line and load terminals are desired, order two sets.
Discount
Code B30
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
copperLogic.com
www.barr-thorp.com
57
cPRO Electronic Circuit Breakers
cPRO K-series Electronic Trip Modules
LS Type
KES3125LS
KES3250LS
KES3400LS
LSI Type
KES3125LSI
KES3250LSI
KES3400LSI
LSG Type
KES3125LSG
KES3250LSG
KES3400LSG
LSIG Type
KES3125LSIG
KES3250LSIG
KES3400LSIG
• Long Delay Pickup
• Adjustable Short Delay Pickup with Fixed Short Delay
Time (I 2t Response)
• Adjustable Long Delay Pickup
• Independently Adjustable Short Delay Pickup and
Short Delay Time (Flat Response)
• Long Delay Pickup
• Adjustable Short Delay Pickup with Fixed Short Delay
Time (I 2t Response)
• Ground Fault Protection
• Adjustable Long Delay Pickup
• Independently Adjustable Short Delay Pickup and
Short Delay Time (Flat Response)
• Ground Fault Protection
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
www.barr-thorp.com
cPRO Molded Case Circuit Breakers
Assembled Electronic 250A Three Pole, K-series
> Electronic breakers provide superior coordination with systems; best
Order by
Assembly
suited for control of main incoming loads or main branch systems
> Interchangeable trip module AND rating plug allows for maximum coordinating flexibility with minimal cost
> The economical solution for three pole applications to 250A @600V
> Select models offer built-in ground fault protection, reducing additional
Order by Components
on next two pages
equipment costs
> HACR rated allows for use with refrigerant motor compressors
> Assembled units are factory sealed and approved for reverse feed use
with back-fed mains
Electronic Three Pole Circuit Breakers with Interchangeable Trip Module (to 250A) ➊➋➌
Continuous
Amp Rating
@ 40° C (104° F)
➍
➎
Maximum
Operating
Voltage
Low Breaking Capacity
25 kAIC @ 600 V AC
35 kAIC @ 480 V AC
65 kAIC @ 240 V AC
Medium Breaking Capacity
35 kAIC @ 600 V AC
65 kAIC @ 480 V AC
100 kAIC @ 240 V AC
High Breaking Capacity
65 kAIC @ 600 V AC
100 kAIC @ 480 V AC
200 kAIC @ 240 V AC
AC
DC
Catalog Number
Price
Catalog Number
Price
Catalog Number
Price
70
600
–
ET3-K2LS-70◆-L
7725
ET3-K2MS-70◆-L
8136
ET3-K2HS-70◆-L
8876
90
600
–
ET3-K2LS-90◆-L
7725
ET3-K2MS-90◆-L
8136
ET3-K2HS-90◆-L
8876
100
600
–
ET3-K2LS-100◆-L
7725
ET3-K2MS-100◆-L
8136
ET3-K2HS-100◆-L
8876
110
600
–
ET3-K2LS-110◆-L
7725
ET3-K2MS-110◆-L
8136
ET3-K2HS-110◆-L
8876
125
600
–
ET3-K2LS-125◆-L
7725
ET3-K2MS-125◆-L
8136
ET3-K2HS-125◆-L
8876
150
600
–
ET3-K2LS-150◆-L
8184
ET3-K2MS-150◆-L
8595
ET3-K2HS-150◆-L
9336
160
600
–
ET3-K2LS-160◆-L
8184
ET3-K2MS-160◆-L
8595
ET3-K2HS-160◆-L
9336
175
600
–
ET3-K2LS-175◆-L
8184
ET3-K2MS-175◆-L
8595
ET3-K2HS-175◆-L
9336
200
600
–
ET3-K2LS-200◆-L
8184
ET3-K2MS-200◆-L
8595
ET3-K2HS-200◆-L
9336
225
600
–
ET3-K2LS-225◆-L
8184
ET3-K2MS-225◆-L
8595
ET3-K2HS-225◆-L
9336
250
600
–
ET3-K2LS-250◆-L
8184
ET3-K2MS-250◆-L
8595
ET3-K2HS-250◆-L
9336
Trip Unit Codes
Complete catalog
number (◆) with…
E
F
G
H
Trip Unit Type (see page 58 for full description)
LS Type: Long and Short Delay Protection
LSI Type: Long and Short Delay, and Instantaneous Protection
LSG Type: Long and Short Delay, and Ground Fault Protection
LSIG Type: Long and Short Delay; Instantaneous and Ground Fault Protection
Ordering Instructions
1
2
3
CPRO-CAT-1109
Locate the desired electronic circuit breaker.
Complete catalog number with Trip Unit Code.
See pages 71 – 78 for accessories.
Price Adder
(70 – 125A)
➍
–
427
1364
1709
Price Adder
(150 – 250A)
➎
–
461
1513
1892
➊ Line and Load side terminals ship with breaker as standard. Other options are
available; contact your CopperLogic representative.
➋ A VISA-window to view main power contacts is available. If desired, add “S” to end of
catalog number, and add $1790 to price. For toggle style operators only.
➌ Mounting hardware not included. Order base mounting hardware separately on page 78.
➍ Supplied with trip module of max continuous rating 125A and fixed rating plug
that determines max continuous rating of assembled breaker.
➎ Supplied with trip module of max continuous rating 250A and fixed rating plug
that determines max continuous rating of assembled breaker.
Discount
Code B30
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
copperLogic.com
www.barr-thorp.com
59
Order by > Electronic breakers provide superior coordination with systems; best
suited for control of main incoming loads or main branch systems
> Interchangeable trip module AND rating plug allows for maximum coordinating flexibility with minimal cost
Order by Assembly
on previous page
> The economical solution for three pole applications to 250A @600V
> Select models offer built-in ground fault protection, reducing additional
equipment costs
> HACR rated allows for use with refrigerant motor compressors
> Assembled units are factory sealed and approved for reverse feed use
with back-fed mains
Frames for Three Pole Electronic Circuit Breakers (to 250A) ➊➋
Step 1 - choose frame
Maximum
Continuous
Amp Rating
@ 40° C (104° F)
250
Low Breaking Capacity
25 kAIC @ 600 V AC
35 kAIC @ 480 V AC
65 kAIC @ 240 V AC
Maximum
Operating
Voltage
Medium Breaking Capacity
35 kAIC @ 600 V AC
65 kAIC @ 480 V AC
100 kAIC @ 240 V AC
High Breaking Capacity
65 kAIC @ 600 V AC
100 kAIC @ 480 V AC
200 kAIC @ 240 V AC
AC
DC
Catalog Number
Price
Catalog Number
Price
Catalog Number
Price
600
–
MF3-KLS-250
2714
MF3-KMS-250
3125
MF3-KHS-250
3865
Interchangeable Trip Modules
Step 2 - choose trip module type
Suitable for Low, Medium or High Breaking Capacities
Maximum
Operating
Voltage
LS Type
LSI Type
LSG Type
LSIG Type
Long and Short Delay
Protection
(see page 58 for full description)
Long and Short Delay, and
Instantaneous Protection
(see page 58 for full description)
Long and Short Delay, and
Ground Fault Protection
(see page 58 for full description)
Long and Short Delay;
Instantaneous and Ground
Fault Protection
(see page 58 for full description)
AC
DC
Catalog Number
Price
Catalog Number
Price
Catalog Number
Price
Catalog Number
Choose
Rating
Plug and
Terminals
from
Price Table…
125
600
–
KES3125LS
3618
KES3125LSI
4030
KES3125LSG
4967
KES3125LSIG
5313
A
250
600
–
KES3250LS
4063
KES3250LSI
4523
KES3250LSG
5576
KES3250LSIG
5954
B
Maximum
Continuous
Amp Rating
@ 40° C
(104° F)
Ordering Instructions
1
2
3
4
Locate the desired circuit breaker frame.
Select trip module.
Choose rating plug and terminals on next page.
See pages 71 – 78 for accessories.
60 copperLogic.com
➊ A VISA-window to view main power contacts is available. If desired, add “S” to end of
breaker frame catalog number, and add $1790 to price. For toggle style operators only.
➋ Mounting hardware not included. Order base mounting hardware separately on page 78.
Discount Code B30
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
CPRO-CAT-1109
www.barr-thorp.com
cPRO Molded Case Circuit Breakers
Components for Electronic 250A Three Pole, K-series
Components
Table A (for 125A Trip Modules): Rating Plugs and Terminals
Step 3 - choose rating plug and terminals
Table A
Fixed Rating Plug
Continuous Amp
Rating
Catalog
@ 40° C (104° F) Number
1KES070T
1KES090T
1KES100T
1KES110T
1KES125T
70
90
100
110
125
or
Price
Continuous Amp
Rating Settings Catalog
@ 40° C (104° F) Number
329
329
329
329
329
Terminals
(individually priced and packaged)
Adjustable Rating Plug
70, 90, 100, 125
A1KES125T1
Wire Range
Price
Material
AWG
526
Aluminum
#3 – 350 MCM
Catalog
Number
TA300K
Price
46
Table B (for 250A Trip Modules): Rating Plugs and Terminals
Step 3 - choose rating plug and terminals
Table B
Fixed Rating Plug
Continuous Amp
Rating
Catalog
@ 40° C (104° F) Number
2KES070T
2KES100T
2KES125T
2KES150T
2KES160T
2KES175T
2KES200T
2KES225T
2KES250T
70
100
125
150
160
175
200
225
250
CPRO-CAT-1109
or
Price
329
329
329
329
329
329
329
329
329
Terminals
(individually priced and packaged)
Adjustable Rating Plug
Continuous Amp
Rating Settings Catalog
@ 40° C (104° F) Number
–
–
125, 150, 200, 250
A2KES250T1
Wire Range
Catalog
Number
Price
Material
AWG
–
Aluminum
#3 – 350 MCM
TA300K
46
526
Aluminum
250 – 500 MCM
TA350K
46
copperLogic.com
61
Discount
Code B30
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
www.barr-thorp.com
Price
cPRO Molded Case Circuit Breakers
Notes
62 copperLogic.com
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
CPRO-CAT-1109
www.barr-thorp.com
cPRO Molded Case Circuit Breakers
Assembled Electronic 400A Three Pole, K-series
> Future-proof your systems with superior scalability from 100A to 400A
Order by
Assembly
with just a quick change of the trip module! Lower cost and installation
time when your business grows.
> Electronic breakers provide superior coordination with systems; best
suited for control of main incoming loads or main branch systems
> Interchangeable trip module AND rating plug allows for maximum coordinating flexibility with minimal cost
> Select models offer built-in ground fault protection, reducing additional
equipment costs
Order by Components
on next two pages
Electronic Three Pole Circuit Breakers with Interchangeable Trip Module (to 400A) ➊➋➌
Continuous
Amp Rating
@ 40° C (104° F)
➍
➎
➏
Maximum
Operating
Voltage
Low Breaking Capacity
25 kAIC @ 600 V AC
35 kAIC @ 480 V AC
65 kAIC @ 240 V AC
Medium Breaking Capacity
35 kAIC @ 600 V AC
65 kAIC @ 480 V AC
100 kAIC @ 240 V AC
High Breaking Capacity
65 kAIC @ 600 V AC
100 kAIC @ 480 V AC
200 kAIC @ 240 V AC
AC
DC
Catalog Number
Price
Catalog Number
Price
Catalog Number
Price
70
600
–
ET3-K4LS-70◆-L
10289
ET3-K4MS-70◆-L
11112
ET3-K4HS-70◆-L
12428
90
600
–
ET3-K4LS-90◆-L
10289
ET3-K4MS-90◆-L
11112
ET3-K4HS-90◆-L
12428
100
600
–
ET3-K4LS-100◆-L
10289
ET3-K4MS-100◆-L
11112
ET3-K4HS-100◆-L
12428
110
600
–
ET3-K4LS-110◆-L
10289
ET3-K4MS-110◆-L
11112
ET3-K4HS-110◆-L
12428
125
600
–
ET3-K4LS-125◆-L
10289
ET3-K4MS-125◆-L
11112
ET3-K4HS-125◆-L
12428
150
600
–
ET3-K4LS-150◆-L
10734
ET3-K4MS-150◆-L
11556
ET3-K4HS-150◆-L
12872
160
600
–
ET3-K4LS-160◆-L
10734
ET3-K4MS-160◆-L
11556
ET3-K4HS-160◆-L
12872
175
600
–
ET3-K4LS-175◆-L
10734
ET3-K4MS-175◆-L
11556
ET3-K4HS-175◆-L
12872
200
600
–
ET3-K4LS-200◆-L
10734
ET3-K4MS-200◆-L
11556
ET3-K4HS-200◆-L
12872
225
600
–
ET3-K4LS-225◆-L
10734
ET3-K4MS-225◆-L
11556
ET3-K4HS-225◆-L
12872
250
600
–
ET3-K4LS-250◆-L
10734
ET3-K4MS-250◆-L
11556
ET3-K4HS-250◆-L
12872
300
600
–
ET3-K4LS-300◆-L
11030
ET3-K4MS-300◆-L
11852
ET3-K4HS-300◆-L
13168
350
600
–
ET3-K4LS-350◆-L
11030
ET3-K4MS-350◆-L
11852
ET3-K4HS-350◆-L
13168
400
600
–
ET3-K4LS-400◆-L
11030
ET3-K4MS-400◆-L
11852
ET3-K4HS-400◆-L
13168
Trip Unit Codes
Complete catalog
number (◆) with…
E
F
G
H
Trip Unit Type (see page 58 for full description)
LS Type: Long and Short Delay Protection
LSI Type: Long and Short Delay, and Instantaneous Protection
LSG Type: Long and Short Delay, and Ground Fault Protection
LSIG Type: Long and Short Delay; Instantaneous and Ground Fault Protection
Ordering Instructions
1
2
3
CPRO-CAT-1109
Locate the desired electronic circuit breaker.
Complete catalog number with Trip Unit Code.
See pages 71 – 78 for accessories.
Price Adder
(70 – 125A)
➍
–
412
1349
1695
Price Adder
(150 – 250A)
➎
–
460
1513
1891
Price Adder
(300 – 400A)
➏
–
493
1628
2039
➊ Line and Load side terminals ship with breaker as standard. Other options are
available; contact your CopperLogic representative.
➋ A VISA-window to view main power contacts is available. If desired, add “S” to end of
catalog number, and add $1790 to price. For toggle style operators only.
➌ Mounting hardware not included. Order base mounting hardware separately on page 78.
➍ Supplied with trip module of max continuous rating 125A and fixed rating plug
that determines max continuous rating of assembled breaker.
➎ Supplied with trip module of max continuous rating 250A and fixed rating plug
that determines max continuous rating of assembled breaker.
➏ Supplied with trip module of max continuous rating 400A and fixed rating plug
that determines max continuous rating of assembled breaker.
Discount
Code B30
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
copperLogic.com
www.barr-thorp.com
63
Order by > Future-proof your systems with superior scalability from 100A to 400A
with just a quick change of the trip module! Lower cost and installation
time when your business grows.
> Electronic breakers provide superior coordination with systems; best
suited for control of main incoming loads or main branch systems
> Interchangeable trip module AND rating plug allows for maximum coordinating flexibility with minimal cost
> Select models offer built-in ground fault protection, reducing additional
equipment costs
Order by Assembly
on previous page
Frames for Three Pole Electronic Circuit Breakers (to 400A) ➊➋
Step 1 - choose frame
Maximum
Continuous
Amp Rating
@ 40° C (104° F)
400
Low Breaking Capacity
25 kAIC @ 600 V AC
35 kAIC @ 480 V AC
65 kAIC @ 240 V AC
Maximum
Operating
Voltage
Medium Breaking Capacity
35 kAIC @ 600 V AC
65 kAIC @ 480 V AC
100 kAIC @ 240 V AC
High Breaking Capacity
65 kAIC @ 600 V AC
100 kAIC @ 480 V AC
200 kAIC @ 240 V AC
AC
DC
Catalog Number
Price
Catalog Number
Price
Catalog Number
Price
600
–
MF3-KLS-400
5263
MF3-KMS-400
6086
MF3-KHS-400
7401
Interchangeable Trip Modules
Step 2 - choose trip module type
Suitable for Low, Medium or High Breaking Capacities
Maximum
Operating
Voltage
LS Type
LSI Type
LSG Type
LSIG Type
Long and Short Delay
Protection
(see page 58 for full description)
Long and Short Delay, and
Instantaneous Protection
(see page 58 for full description)
Long and Short Delay, and
Ground Fault Protection
(see page 58 for full description)
Long and Short Delay;
Instantaneous and Ground
Fault Protection
(see page 58 for full description)
AC
DC
Catalog Number
Price
Catalog Number
Price
Catalog Number
Price
Catalog Number
Choose
Rating
Plug and
Terminals
from
Price Table…
125
600
–
KES3125LS
3618
KES3125LSI
4030
KES3125LSG
4967
KES3125LSIG
5313
A
250
600
–
KES3250LS
4063
KES3250LSI
4523
KES3250LSG
5576
KES3250LSIG
5954
B
400
600
–
KES3400LS
4359
KES3400LSI
4852
KES3400LSG
5987
KES3400LSIG
6398
C
Maximum
Continuous
Amp Rating
@ 40° C
(104° F)
Ordering Instructions
1
2
3
4
Locate the desired circuit breaker frame.
Select trip module.
Choose rating plug and terminals on next page.
See pages 71 – 78 for accessories.
64 copperLogic.com
➊ A VISA-window to view main power contacts is available. If desired, add “S” to end of
breaker frame catalog number, and add $1790 to price. For toggle style operators only.
➋ Mounting hardware not included. Order base mounting hardware separately on page 78.
➌ Priced and packaged in sets of three. If line and load terminals are desired, order two sets.
Discount Code B30
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
CPRO-CAT-1109
www.barr-thorp.com
cPRO Molded Case Circuit Breakers
Components for Electronic 400A Three Pole, K-series
Components
Table A (for 125A Trip Modules): Rating Plugs and Terminals
Step 3 - choose rating plug and terminals
Table A
Fixed Rating Plug
Continuous Amp
Rating
Catalog
@ 40° C (104° F) Number
1KES070T
1KES090T
1KES100T
1KES110T
1KES125T
70
90
100
110
125
or
Price
Continuous Amp
Rating Settings Catalog
@ 40° C (104° F) Number
329
329
329
329
329
Terminals
(individually priced and packaged)
Adjustable Rating Plug
70, 90, 100, 125
A1KES125T1
Wire Range
Price
Material
AWG
526
Aluminum
#3 – 350 MCM
Catalog
Number
TA300K
Price
46
Table B (for 250A Trip Modules): Rating Plugs and Terminals
Step 3 - choose rating plug and terminals
Table B
Fixed Rating Plug
Continuous Amp
Rating
Catalog
@ 40° C (104° F) Number
2KES070T
2KES100T
2KES125T
2KES150T
2KES160T
2KES175T
2KES200T
2KES225T
2KES250T
70
100
125
150
160
175
200
225
250
or
Price
Continuous Amp
Rating Settings Catalog
@ 40° C (104° F) Number
329
329
329
329
329
329
329
329
329
Terminals
(individually priced and packaged)
Adjustable Rating Plug
–
–
125, 150, 200, 250
A2KES250T1
Wire Range
Catalog
Number
Price
Material
AWG
–
Aluminum
#3 – 350 MCM
TA300K
46
526
Aluminum
250 – 500 MCM
TA350K
46
Price
Table C (for 400A Trip Modules): Rating Plugs and Terminals
Step 3 - choose rating plug and terminals
Table C
Fixed Rating Plug
Continuous Amp
Rating
Catalog
@ 40° C (104° F) Number
or
Price
200
225
250
300
350
4KES200T
4KES225T
4KES250T
4KES300T
4KES350T
329
329
329
329
329
400
4KES400T
329
CPRO-CAT-1109
Terminals
(individually priced and packaged, except where noted) ➌
Adjustable Rating Plug
Continuous Amp
Rating Settings Catalog
@ 40° C (104° F) Number
–
–
220, 240, 260, 280
A4KES200T5
Wire Range
Catalog
Number
Price
Material
AWG
–
Aluminum
#3 – 350 MCM
TA300K
46
526
Aluminum
250 – 500 MCM
TA350K
46
Aluminum
2x (#3/0 – 250 MCM)
200, 250, 300, 400
A4KES400T1
526
320, 340, 360, 380
A4KES300T5
526
Discount
Code B30
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
3TA400K ➌
(set of three)
copperLogic.com
www.barr-thorp.com
Price
263
65
cPRO Molded Case Circuit Breakers
Notes
66 copperLogic.com
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
CPRO-CAT-1109
www.barr-thorp.com
cPRO Molded Case Circuit Breakers
Assembled 100% Rated, Electronic 400A Three Pole, K-series
> Future-proof your systems with superior scalability from 100A to 400A
Order by
Assembly
with just a quick change of the trip module! Lower cost and installation
time when your business grows.
> 100% Rated device prevents need to select a larger breaker size
> Electronic breakers provide superior coordination with systems; best
suited for control of main incoming loads or main branch systems
Order by Components
on next two pages
> Interchangeable trip module AND rating plug allows for maximum coordinating flexibility with minimal cost
> Select models offer built-in ground fault protection, reducing additional
equipment costs
100% Rated Electronic Three Pole Circuit Breakers with Interchangeable Trip Module (to 400A) ➊➋➌
Continuous
Amp Rating
@ 40° C (104° F)
➍
➎
➏
Maximum
Operating
Voltage
Low Breaking Capacity
25 kAIC @ 600 V AC
35 kAIC @ 480 V AC
65 kAIC @ 240 V AC
Medium Breaking Capacity
35 kAIC @ 600 V AC
65 kAIC @ 480 V AC
100 kAIC @ 240 V AC
AC
DC
Catalog Number
Price
Catalog Number
Price
70
600
–
ET3-K4LC-70◆-L
12098
ET3-K4MC-70◆-L
13151
90
600
–
ET3-K4LC-90◆-L
12098
ET3-K4MC-90◆-L
13151
100
600
–
ET3-K4LC-100◆-L
12098
ET3-K4MC-100◆-L
13151
110
600
–
ET3-K4LC-110◆-L
12098
ET3-K4MC-110◆-L
13151
125
600
–
ET3-K4LC-125◆-L
12098
ET3-K4MC-125◆-L
13151
150
600
–
ET3-K4LC-150◆-L
12572
ET3-K4MC-150◆-L
13625
160
600
–
ET3-K4LC-160◆-L
12572
ET3-K4MC-160◆-L
13625
175
600
–
ET3-K4LC-175◆-L
12572
ET3-K4MC-175◆-L
13625
200
600
–
ET3-K4LC-200◆-L
12572
ET3-K4MC-200◆-L
13625
225
600
–
ET3-K4LC-225◆-L
12572
ET3-K4MC-225◆-L
13625
250
600
–
ET3-K4LC-250◆-L
12572
ET3-K4MC-250◆-L
13625
300
600
–
ET3-K4LC-300◆-L
12888
ET3-K4MC-300◆-L
13940
350
600
–
ET3-K4LC-350◆-L
12888
ET3-K4MC-350◆-L
13940
400
600
–
ET3-K4LC-400◆-L
12888
ET3-K4MC-400◆-L
13940
Trip Unit Codes
Complete catalog
number (◆) with…
E
F
G
H
Trip Unit Type (see page 58 for full description)
LS Type: Long and Short Delay Protection
LSI Type: Long and Short Delay, and Instantaneous Protection
LSG Type: Long and Short Delay, and Ground Fault Protection
LSIG Type: Long and Short Delay; Instantaneous and Ground Fault Protection
Ordering Instructions
1
2
3
CPRO-CAT-1109
Locate the desired electronic circuit breaker.
Complete catalog number with Trip Unit Code.
See pages 71 – 78 for accessories.
Price Adder
(70 – 125A)
➍
–
439
1439
1807
Price Adder
(150 – 250A)
➎
–
491
1614
2017
Price Adder
(300 – 400A)
➏
–
526
1737
2175
➊ Line and Load side terminals ship with breaker as standard. Other options are
available; contact your CopperLogic representative.
➋ A VISA-window to view main power contacts is available. If desired, add “S” to end of
catalog number, and add $1790 to price. For toggle style operators only.
➌ Mounting hardware not included. Order base mounting hardware separately on page 78.
➍ Supplied with trip module of max continuous rating 125A and fixed rating plug
that determines max continuous rating of assembled breaker.
➎ Supplied with trip module of max continuous rating 250A and fixed rating plug
that determines max continuous rating of assembled breaker.
➏ Supplied with trip module of max continuous rating 400A and fixed rating plug
that determines max continuous rating of assembled breaker.
Discount
Code B30
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
copperLogic.com
www.barr-thorp.com
67
Order by > Future-proof your systems with superior scalability from 100A to 400A
with just a quick change of the trip module! Lower cost and installation
time when your business grows.
> 100% Rated device prevents need to select a larger breaker size
> Electronic breakers provide superior coordination with systems; best
Order by Assembly
on previous page
suited for control of main incoming loads or main branch systems
> Interchangeable trip module AND rating plug allows for maximum coordinating flexibility with minimal cost
> Select models offer built-in ground fault protection, reducing additional
equipment costs
Frames for 100% Rated Three Pole Electronic Circuit Breakers (to 400A) ➊➋
Step 1 - choose frame
Maximum
Continuous
Amp Rating
@ 40° C (104° F)
400
Low Breaking Capacity
25 kAIC @ 600 V AC
35 kAIC @ 480 V AC
65 kAIC @ 240 V AC
Maximum
Operating
Voltage
Medium Breaking Capacity
35 kAIC @ 600 V AC
65 kAIC @ 480 V AC
100 kAIC @ 240 V AC
AC
DC
Catalog Number
Price
Catalog Number
Price
600
–
MF3-KLC-400
6737
MF3-KMC-400
7789
Interchangeable Trip Modules
Step 2 - choose trip module type
Suitable for Low, Medium or High Breaking Capacities
Maximum
Operating
Voltage
LS Type
LSI Type
LSG Type
LSIG Type
Long and Short Delay
Protection
(see page 58 for full description)
Long and Short Delay, and
Instantaneous Protection
(see page 58 for full description)
Long and Short Delay, and
Ground Fault Protection
(see page 58 for full description)
Long and Short Delay;
Instantaneous and Ground
Fault Protection
(see page 58 for full description)
AC
DC
Catalog Number
Price
Catalog Number
Price
Catalog Number
Price
Catalog Number
Choose
Rating
Plug and
Terminals
from
Price Table…
125
600
–
KES3125LS
3618
KES3125LSI
4030
KES3125LSG
4967
KES3125LSIG
5313
A
250
600
–
KES3250LS
4063
KES3250LSI
4523
KES3250LSG
5576
KES3250LSIG
5954
B
400
600
–
KES3400LS
4359
KES3400LSI
4852
KES3400LSG
5987
KES3400LSIG
6398
C
Maximum
Continuous
Amp Rating
@ 40° C
(104° F)
Ordering Instructions
1
2
3
4
Locate the desired circuit breaker frame.
Select trip module.
Choose rating plug and terminals on next page.
See pages 71 – 78 for accessories.
68 copperLogic.com
➊ A VISA-window to view main power contacts is available. If desired, add “S” to end of
breaker frame catalog number, and add $1790 to price. For toggle style operators only.
➋ Mounting hardware not included. Order base mounting hardware separately on page 78.
➌ Priced and packaged in sets of three. If line and load terminals are desired, order two sets.
Discount Code B30
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
CPRO-CAT-1109
www.barr-thorp.com
cPRO Molded Case Circuit Breakers
Components for 100% Rated Electronic 400A Three Pole, K-series
Components
Table A (for 125A Trip Modules): Rating Plugs and Terminals
Step 3 - choose rating plug and terminals
Table A
Fixed Rating Plug
Continuous Amp
Rating
Catalog
@ 40° C (104° F) Number
1KES070T
1KES090T
1KES100T
1KES110T
1KES125T
70
90
100
110
125
or
Price
Continuous Amp
Rating Settings Catalog
@ 40° C (104° F) Number
329
329
329
329
329
Terminals
(individually priced and packaged)
Adjustable Rating Plug
70, 90, 100, 125
A1KES125T1
Wire Range
Price
Material
AWG
526
Aluminum
#3 – 350 MCM
Catalog
Number
TA300K
Price
46
Table B (for 250A Trip Modules): Rating Plugs and Terminals
Step 3 - choose rating plug and terminals
Table B
Fixed Rating Plug
Continuous Amp
Rating
Catalog
@ 40° C (104° F) Number
2KES070T
2KES100T
2KES125T
2KES150T
2KES160T
2KES175T
2KES200T
2KES225T
2KES250T
70
100
125
150
160
175
200
225
250
or
Price
Continuous Amp
Rating Settings Catalog
@ 40° C (104° F) Number
329
329
329
329
329
329
329
329
329
Terminals
(individually priced and packaged)
Adjustable Rating Plug
–
–
125, 150, 200, 250
A2KES250T1
Wire Range
Catalog
Number
Price
Material
AWG
–
Aluminum
#3 – 350 MCM
TA300K
46
526
Aluminum
250 – 500 MCM
TA350K
46
Price
Table C (for 400A Trip Modules): Rating Plugs and Terminals
Step 3 - choose rating plug and terminals
Table C
Fixed Rating Plug
Continuous Amp
Rating
Catalog
@ 40° C (104° F) Number
or
Price
200
225
250
300
350
4KES200T
4KES225T
4KES250T
4KES300T
4KES350T
329
329
329
329
329
400
4KES400T
329
CPRO-CAT-1109
Terminals
(individually priced and packaged, except where noted) ➌
Adjustable Rating Plug
Continuous Amp
Rating Settings Catalog
@ 40° C (104° F) Number
–
–
220, 240, 260, 280
A4KES200T5
Wire Range
Catalog
Number
Price
Material
AWG
–
Aluminum
#3 – 350 MCM
TA300K
46
526
Aluminum
250 – 500 MCM
TA350K
46
Aluminum
2x (#3/0 – 250 MCM)
200, 250, 300, 400
A4KES400T1
526
320, 340, 360, 380
A4KES300T5
526
Discount
Code B30
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
3TA400K ➌
(set of three)
copperLogic.com
www.barr-thorp.com
Price
263
69
cPRO Molded Case Switches
400A Molded Case Switches, K-series
> Two pole switches are suitable for single-phase motor discon-
> 100% Rated device prevents need to select a larger switch size
> Built-in fixed instantaneous trip opens above 4000 Amps
> HACR rated allows for use with refrigerant motor compressors
necting and switching to 400 Amps
> Three pole switches are suitable for three-phase motor disconnecting and switching to 400 Amps
Two Pole Molded Case Switches (to 400A) ➊➋➌➍
Step 1 - choose frame
Medium Short-circuit
Withstand Rating
35 kAIC @ 600 V AC
65 kAIC @ 480 V AC
100 kAIC @ 240 V AC
22 kAIC @ 250 V DC
Low Short-circuit
Withstand Rating
25 kAIC @ 600 V AC
35 kAIC @ 480 V AC
65 kAIC @ 240 V AC
10 kAIC @ 250 V DC
Maximum
Operating
Voltage
Continuous
Amp Rating
@ 40° C (104° F)
AC
DC
Catalog Number
Price
Catalog Number
Price
400
600
250
CS2-KLC-400
4772
CS2-KMC-400
5368
Three Pole Molded Case Switches (to 400A) ➊➋➌
Step 1 - choose frame
Maximum
Operating
Voltage
Medium Short-circuit
Withstand Rating
35 kAIC @ 600 V AC
65 kAIC @ 480 V AC
100 kAIC @ 240 V AC
22 kAIC @ 250 V DC
Low Short-circuit
Withstand Rating
25 kAIC @ 600 V AC
35 kAIC @ 480 V AC
65 kAIC @ 240 V AC
10 kAIC @ 250 V DC
Continuous
Amp Rating
@ 40° C (104° F)
AC
DC
Catalog Number
Price
Catalog Number
Price
400
600
250
CS3-KLC-400
5614
CS3-KMC-400
6316
Terminals
Step 2 - select terminals
Max.
Amp
Rating Material
Terminals
Wire
Type
No. of
Conductors
Wire Range
Terminals
Terminals with Control Wire
For use
with…
Catalog Number
K-series
TA300K ➎
46
–
–
K-series
TA350K ➎
46
–
–
Two Pole
K-series
(set of two)
Three Pole
K-series
(set of three)
Price
Catalog Number
Price
Standard Terminals
225
Aluminum
Cu / Al
1
350
Aluminum
Cu / Al
1
400
Aluminum
Cu / Al
Ordering Instructions
1
2
3
Locate the desired molded case switch.
Select terminals.
See pages 71 – 78 for accessories.
70 copperLogic.com
2
#3 – 350 kcmil
35 – 185 mm2
250 – 500 kcmil
120 – 240 mm2
#3/0 – 250 kcmil
95 – 120 mm2
2TA400K ➏
3TA400K ➐
175
263
2TA400KCW ➏
(set of two)
3TA400KCW ➐
(set of three)
263
386
➊ A VISA-window to view main power contacts is available. If desired, add “S” to end of
switch catalog number, and add $1790 to price. For toggle style operators only.
➋ Molded case switches are supplied with a fixed instantaneous trip that opens
above 4000A.
➌ Mounting hardware not included. Order base mounting hardware separately on page 78.
➍ Two-pole molded case switches are supplied in a three-pole frame.
➎ Individually priced and packaged.
➏ Priced and packaged in sets of two. If line and load terminals are desired, order two sets.
➐ Priced and packaged in sets of three. If line and load terminals are desired, order two sets.
Discount Code B30
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
CPRO-CAT-1109
www.barr-thorp.com
Accessories
K-series Rotary Handles
Through-the-door Handles - Complete Units (includes handle, mechanism and shaft) ➊
Accessory
Shaft Length
mm (in.)
Description
Handle
Color
Catalog Number
Price
Black
Red
Black
Red
Black
Red
KHMVD06B
KHMVD06R
KHMVD12B
KHMVD12R
KHMVD24B
KHMVD24R
795
795
842
842
1029
1029
152.4 (6)
Black
HM3R06
968
304.8 (12)
Black
HM3R12
1011
406.4 (16)
Black
HM3R16
1116
609.6 (24)
Black
HM3R24
1221
152.4 (6)
Black
HM3R06X
1053
304.8 (12)
Black
HM3R12X
1095
406.4 (16)
Black
HM3R16X
1200
609.6 (24)
Black
HM3R24X
1305
Standard Handle Kit - NEMA 1, 12
152.4 (6)
NEMA 1, 12
Molded plastic handle
For K-series
90 degree rotation
304.8 (12)
609.6 (24)
Ergonomic Handle Kit- NEMA 1, 12, 3R
NEMA 1, 12, 3R
Steel handle
For K-series
Ergonomic design for
‘gloved hand’ operation
45 degree rotation
Ergonomic Handle Kit - NEMA 4/4X
NEMA 4/4X
Steel handle
For K-series
Ergonomic design for
‘gloved hand’ operation
45 degree rotation
Through-the-door Handles - Components (order separately) ➊
Mechanism
Handle
Handle
Color Catalog Number
Description
Price
Catalog Number
Shaft
Price
Length [mm (in.)] Catalog Number
Price
Handle Components for NEMA 1, 12, 3R
NEMA 1, 12, 3R
Ergonomic Steel handle
For K-series
Ergonomic design for
‘gloved hand’ operation
45 degree rotation
Black
6648C22G01
344
6648C23G25
574
152.4 (6)
4217B37G08
150
304.8 (12)
4217B37G05
180
406.4 (16)
4217B37G06
211
609.6 (24)
4217B37G07
241
152.4 (6)
4217B37G08
150
304.8 (12)
4217B37G05
180
406.4 (16)
4217B37G06
211
609.6 (24)
4217B37G07
241
Handle Components for NEMA 4/4X
NEMA 4/4X
Ergonomic Steel handle
For K-series
Ergonomic design for
‘gloved hand’ operation
45 degree rotation
Black
6648C22G03
431
6648C23G25
574
➊ Not for use with VISA-window option.
CPRO-CAT-1109
Discount
Code B30
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
copperLogic.com
www.barr-thorp.com
71
Accessories
K-series Flange and Toggle Operators
Flange Mounted Handles ➊
Accessory
NEMA 1, 12, 3R
Flexible
Shaft Length
m (ft.)
Catalog Number
Price
Description
NEMA 4/4X
Catalog Number
Price
Flange Handles
For K-series
Extra heavy-duty flexible shaft
Accepts up to 3 padlocks
0.9 (3)
F3S03C
2784
F3S03CX
3275
1.2 (4)
F3S04C
2830
F3S04CX
3333
1.5 (5)
F3S05C
2877
F3S05CX
3392
1.8 (6)
F3S06C
2924
F3S06CX
3450
2.1 (7)
F3S07C
2971
F3S07CX
3509
2.4 (8)
F3S08C
3018
F3S08CX
3556
2.7 (9)
F3S09C
3064
F3S09CX
3602
3.0 (10)
F3S10C
3111
F3S10CX
3661
Safety Door Hardware for NEMA 12 Flex Shafts
Accessory
Handle Length
mm (in.)
Description
Catalog Number
Price
Hardware Kit
101.6 (4.0)
C361KJ4
500
152.4 (6.0)
C361KJ6
500
–
C361KR
66
Provides enclosure sealing and
protection against unauthorized entry
Roller Latch
Required for 3-point latching
Handle Extension
Accessory
Description
Catalog Number
Price
For K-series
Used to extend operating
handle of circuit breaker
HEX3
211
Handle Extension
➊ Not for use with VISA-window option.
72 copperLogic.com
Discount Code B30
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
CPRO-CAT-1109
www.barr-thorp.com
Accessories
K-series Internal Accessories
Alarm and Auxiliary Switches
Accessory
Description
Schematic
Contacts
For use Mounting
with… Options
1 NO & 1 NC
K-series
2 NO & 2 NC
K-series
1 NO & 1 NC
K-series
2 NO & 2 NC
K-series
3 NO & 3 NC
K-series
Pigtail Leads (18 in., 18 AWG)
Catalog Number
Price
Terminal Block
Catalog No.
Price
Alarm Lockout Switch
For remote
indication of trip
operation. Switch
resets when circuit
breaker resets.
Make
Break
For Left pole
A1L3LPK
491
A1L3LTK
491
For Right pole
A1L3RPK
491
A1L3RTK
491
For Left pole
A2L3LPK
982
A2L3LTK
982
For Right pole
A2L3RPK
982
A2L3RTK
982
A1X3PK
491
A1X3LTK
491
A1X3RTK
491
A2X3PK
982
A2X3LTK
982
A2X3RTK
982
For Left pole
A3X3LPK
1474
A3X3LTK
1474
For Right pole
A3X3RPK
1474
A3X3RTK
1474
For Left pole
AAL3LPK
982
AAL3LTK
982
For Right pole
AAL3RPK
982
AAL3RTK
982
Auxiliary Switch
a
For remote
indication of circuit
breaker status.
b
For Left pole
For Right pole
For Left pole
For Right pole
Alarm and Auxiliary Switch Combination
For remote
indication of trip
operation and
circuit breaker
status. Switch
resets when circuit
breaker resets.
a
b
2 NO & 2 NC
K-series
Shunt Trips
Accessory
Description
Schematic
Pigtail Leads (18 in., 18 AWG)
Terminal Block
For use Mounting
with… Options Operating Voltage Catalog Number
Price Catalog No.
Price
Intermittent Duty Shunt Trip
Provides remote
trip.
CPRO-CAT-1109
ST
a
K-series
Shunt trip
suitable for
left or right
pole
12 – 24 V AC
12 – 24 V DC
SNT3P04K
602
SNT3T04K
602
48 – 60 V AC
48 – 60 V DC
SNT3P06K
602
SNT3T06K
602
110 – 240 V AC
110 – 125 V DC
SNT3P11K
602
SNT3T11K
602
380 – 440 V AC
220 – 250 V DC
SNT3P14K
602
SNT3T14K
602
480 – 600 V AC
SNT3P18K
602
SNT3T18K
602
Discount
Code B30
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
copperLogic.com
www.barr-thorp.com
73
Accessories
K-series Internal Accessories
Undervoltage Trips
Accessory
Description
Schematic
For Use
With…
Operating Voltage
AC
DC
12
–
24
–
48 – 60
–
110 – 127
–
208 – 240
–
380 – 480
–
–
12
–
24
–
48 – 60
–
110 – 127
–
220 – 250
Pigtail Leads (18 in., 18 AWG)
Terminal Block
Mounting
Options
Catalog Number
Price Catalog No.
Price
Undervoltage Trip
Trips breaker
when voltage
drops below
threshold.
(see tech. data
for individual
thresholds - pages
97 – 98)
74 copperLogic.com
UV
K-series
Left pole
UVH3LP02K
722
UVH3LT02K
722
Right pole
UVH3RP02K
722
UVH3RT02K
722
Left pole
UVH3LP03K
722
UVH3LT03K
722
Right pole
UVH3RP03K
722
UVH3RT03K
722
Left pole
UVH3LP05K
722
UVH3LT05K
722
Right pole
UVH3RP05K
722
UVH3RT05K
722
Left pole
UVH3LP08K
722
UVH3LT08K
722
Right pole
UVH3RP08K
722
UVH3RT08K
722
Left pole
UVH3LP11K
722
UVH3LT11K
722
Right pole
UVH3RP11K
722
UVH3RT11K
722
Left pole
UVH3LP15K
722
UVH3LT15K
722
Right pole
UVH3RP15K
722
UVH3RT15K
722
Left pole
UVH3LP20K
722
UVH3LT20K
722
Right pole
UVH3RP20K
722
UVH3RT20K
722
Left pole
UVH3LP21K
722
UVH3LT21K
722
Right pole
UVH3RP21K
722
UVH3RT21K
722
Left pole
UVH3LP23K
722
UVH3LT23K
722
Right pole
UVH3RP23K
722
UVH3RT23K
722
Left pole
UVH3LP26K
722
UVH3LT26K
722
Right pole
UVH3RP26K
722
UVH3RT26K
722
Left pole
UVH3LP28K
722
UVH3LT28K
722
Right pole
UVH3RP28K
722
UVH3RT28K
722
Discount Code B30
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
CPRO-CAT-1109
www.barr-thorp.com
Accessories
K-series
Remote Electrical Operators
Accessory
Description
Inrush
Current
[A]
Max.
Operating
Time
Fuse
[A]
30
5 cycles (80 ms)
16
Operating
Voltage
AC
DC
For use
with… Catalog Number
6
120
–
K-series
EOP3MT07
7602
5 cycles (80 ms)
4
240
–
K-series
EOP3MT11
7602
30
5 cycles (80 ms)
6
–
120
K-series
EOP3MT07DC
7602
16
5 cycles (80 ms)
4
–
240
K-series
EOP3MT11DC
7602
Price
Electrical Solenoid Operator
Enables local and remote switching (ON, OFF
and reset).
Unique bistable latch allows device to operate
with only one solenoid
Padlockable in OFF position
Accessories for Electronic Breakers
Accessory
Description
For Use With…
Catalog Number
Price
Electronic Trip Units
STK2
23158
Solid-State Portable Test Kit for Electronic Trip Units
Provides performance verification of electronic
trip units
Operating voltage 120V, 50/60Hz
CPRO-CAT-1109
Discount
Code B30
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
copperLogic.com
www.barr-thorp.com
75
Accessories
K-series
Miscellaneous Accessories
Accessory
Description
Terminal Side
For use with…
Catalog Number
Price
Protection against accidental contact with
line side terminals
Priced and packaged in sets of ten.
Line
K-series
TS33LN
140
Protection against accidental contact with
load side terminals
Priced and packaged in sets of ten.
Load
K-series
TS33LD
140
–
K-series
IPB3
140
–
K-series
LKD3
211
–
K-series
PHB3
211
Used to lock the circuit breaker or switch
handle in either the ON or OFF position.
Breaker is allowed to trip when blocked
in the ON position. Accepts up to three
padlocks with 1/4 inch (6 mm) shackles.
–
K-series
PLK3
211
Used to lock the circuit breaker or switch
handle in OFF position. Accepts up to three
padlocks with 1/4 inch (6 mm) shackles.
Left side mounting
PLK3LOFF
211
–
Right side mounting
PLK3ROFF
211
Terminal Shield
Interphase Barriers
High dielectric insulating plates provide
additional electrical clearance between
circuit breaker or switch poles
Priced and packaged in sets of two.
Non-padlockable Handle Block
Used to secure the circuit breaker or switch
handle in either the ON or OFF position.
Breaker is allowed to trip when blocked
in the ON position. Secured by a setscrew,
handle block deters accidental operation
of circuit breaker or switch handle.
Padlockable Handle Block
Positioned in the cover opening to prevent
handle movement
Allows one 5/16 inch padlock
Padlockable Handle Lock Hasp
76 copperLogic.com
Discount Code B30
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
CPRO-CAT-1109
www.barr-thorp.com
Accessories
K-series
Terminal Adapters
Accessory
Description
Thread Size
Terminal
Side
For use with…
Catalog Number
Line or Load
Three pole K-series
KPEK3
132
KPR3A
351
KPR3B
351
Price
End Cap Kit
A threaded adapter to accept a ring terminal or other
bolt-on connector to the circuit breaker or switch
Imperial
0.312-32
A threaded adapter to accept a ring terminal or other
bolt-on connector to the circuit breaker or switch
Priced and packaged in sets of three.
Imperial
.375-16
Keeper Nut
Line
K-series
Load
Control Wire Terminal Kits
Accessory
Description
For use with…
Catalog Number
Price
Control Wire Terminal Kit
Used to tap off control power from a circuit breaker
or switch
K-series
KCWTK
44
Multi-wire Connectors
Accessory
Description
Max. Amps
Wires per
Terminal
400
3
Wire Size
For use with…
Catalog Number
Price
Multi-wire Connectors
Used to distribute the load from the
circuit breaker to multiple devices
without the use of separate distribution terminal blocks.
Priced and packaged in sets of three.
CPRO-CAT-1109
14 – 2/0 AWG
Cu
3TA400K3K
833
3TA400K6K
1053
K-series
400
6
14 – 3 AWG
Cu
Discount
Code B30
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
copperLogic.com
www.barr-thorp.com
77
Accessories
K-series
Base Mounting Hardware
Accessory
Description
Thread
Type
Screw Size
Mounting
For use with…
Imperial
.250-20 x 1.5 in.
Individual
K-series
Catalog Number
Price
Base Mounting Hardware
For surface mounting of circuit breakers or switches. Includes pan-head
screws and lockwashers
Mounting hardware is not included
with breaker.
MHDK3
22
Replacement Terminal Kits
Terminals
Max.
Amp
Rating Material
Wire
Type
No. of
Conductors
Wire Range
For use
with…
Terminals
Catalog Number
Terminals with Control Wire
Price
Catalog Number
Price
Replacement for Standard Terminals (line and load side terminals supplied with breaker)
225
Aluminum
Cu / Al
1
#3 – 350 kcmil
35 – 185 mm2
K-series
TA300K ➊
46
–
–
350
Aluminum
Cu / Al
1
250 – 500 kcmil
120 – 240 mm2
K-series
TA350K ➊
46
–
–
Two Pole
K-series
(set of two)
Three Pole
K-series
(set of three)
400
Aluminum
Cu / Al
2
2TA400K ➋
175
2TA400KCW ➋
(set of two)
263
#3/0 – 250 kcmil
95 – 120 mm2
3TA400K ➌
263
3TA400KCW ➌
(set of three)
386
➊ Individually priced and packaged.
➋ Priced and packaged in sets of two. If line and load terminals are desired, order two sets.
➌ Priced and packaged in sets of three. If line and load terminals are desired, order two sets.
78 copperLogic.com
Discount Code B30
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
CPRO-CAT-1109
www.barr-thorp.com
Application Data
Time / Current Curves
Time/Current Curve
For application and coordination purposes only.
Based on 40°C ambient, cold
start. Connected with four
feet of rated wire (75°C) per
terminal. Tested in open air
with current in all poles. Instantaneous calibration based
on single-pole tests.
Single pole test data at 25°C
based on NEMA procedures (AB
4-2003) for verifying performance of molded case circuit
breakers.
1h
2h
TM(2)(3)-KLS…, TM(2)(3)-KMS…
10000
7000
5000
3000
2000
1000
700
500
(250 – 400A)
1 min
300
200
(100A)
100
70
50
30
20
Maximum single pole
trip times at 25°C
(125 – 225A)
Maximum
Minimum
1
.7
.5
Adjustable
Magnetic
Trip
±20%
Adjustable
Magnetic
Trip
±10%
10x
3
2
5x
.3
.2
.1
.07
.05
Maximum
interrupting
time
.03
.02
.01
.007
.005
500000
700000
1000000
20000
30000
5000
7000
10000
3000
2000
500
700
1000
200
300
.001
50
70
100
.003
.002
200000
300000
Interrupting
rating determines
end of curve
50000
70000
100000
TIME IN SECONDS
10
7
5
CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING (In)
CPRO-CAT-1109
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
copperLogic.com
www.barr-thorp.com
79
Application Data
Time / Current Curves
Time/Current Curve
For application and coordination purposes only.
Based on 40°C ambient, cold
start. Connected with four
feet of rated wire (75°C) per
terminal. Tested in open air
with current in all poles. Instantaneous calibration based
on single-pole tests.
Single pole test data at 25°C
based on NEMA procedures (AB
4-2003) for verifying performance of molded case circuit
breakers.
1h
2h
TM(2)(3)-KHS…
10000
7000
5000
3000
2000
1000
700
500
(250 – 400A)
1 min
300
200
(100A)
100
70
50
30
20
Maximum single pole
trip times at 25°C
(125 – 225A)
Maximum
Minimum
1
.7
.5
Adjustable
Magnetic
Trip
±20%
Adjustable
Magnetic
Trip
±10%
10x
3
2
5x
.3
.2
.1
.07
.05
Maximum
interrupting
time
.03
.02
.01
.007
.005
600V
480V
500000
700000
1000000
20000
30000
5000
7000
10000
3000
2000
500
700
1000
200
300
50
70
100
.001
Interrupting
rating determines
end of curve
200000
300000
240V
.003
.002
50000
70000
100000
TIME IN SECONDS
10
7
5
CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING (In)
80 copperLogic.com
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
CPRO-CAT-1109
www.barr-thorp.com
Application Data
Time / Current Curves
Time/Current Curve
For application and coordination purposes only.
Based on 40°C ambient, cold
start. Connected with four
feet of rated wire (75°C) per
terminal. Tested in open air
with current in all poles. Instantaneous calibration based
on single-pole tests.
Single pole test data at 25°C
based on NEMA procedures (AB
4-2003) for verifying performance of molded case circuit
breakers.
2h
MF3-K(L)(M)(S)(C)-(250)(400) + KES3125(LS)(LSG)…
10000
9000
8000
7000
6000
Standard Fixed
Rating Plug
1h
5000
4000
3000
2000
1000
900
800
700
600
Long Delay
Maximum total
clearing time
500
400
300
1 min
200
100
90
80
70
Long Delay
Minimum total
clearing time
60
50
40
30
10
9
8
7
6
2x
5
Short Delay
Pick-up Settings
Tolerance ±10%
4x
TIME IN SECONDS
3x
20
4
5x
8x
3
2
1
.9
.8
.7
6x
1
.9
.8
.7
.6
.4
.3
.3
7x
.5
.4
.2
.2
.1
.09
.08
.07
.1
.09
.08
.07
.06
.06
.05
.05
Fixed Instantaneous
Override at 4000A
.04
.04
.03
.03
.02
.02
Interrupting rating
determines
end of curve
.006
.01
.009
.008
.007
.006
.005
.005
.004
.004
.003
.003
.002
.002
.01
.009
.008
.007
70
.001
100
CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)
CPRO-CAT-1109
200000
50
70000
40
100000
30
50000
20
40000
10
30000
7
20000
5
7000
4
10000
3
5000
2
4000
1
3000
.7
2000
.5
1000
.001
TIME IN SECONDS
.6
.5
CURRENT IN AMPERES
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
copperLogic.com
www.barr-thorp.com
81
Application Data
Time / Current Curves
Time/Current Curve
For application and coordination purposes only.
Based on 40°C ambient, cold
start. Connected with four
feet of rated wire (75°C) per
terminal. Tested in open air
with current in all poles. Instantaneous calibration based
on single-pole tests.
Single pole test data at 25°C
based on NEMA procedures (AB
4-2003) for verifying performance of molded case circuit
breakers.
2h
MF3-K(L)(M)(S)(C)-(250)(400) + KES3125(LSI)(LSIG)…
10000
9000
8000
7000
6000
Standard Fixed
Rating Plug
1h
5000
4000
3000
2000
1000
900
800
700
600
Long Delay
Maximum total
clearing time
500
400
300
1 min
200
100
90
80
70
Long Delay
Minimum total
clearing time
60
50
40
30
10
9
8
7
6
2x
5
Short Delay
Pick-up Settings
Tolerance ±10%
4x
TIME IN SECONDS
20
6x
4
8x
3
7x
2
1
.9
.8
.7
.6
1
.9
.8
.7
.6
.5
5x
3x
.5
.4
.4
300 ms
.3
.3
200 ms
.2
.2
100 ms
.1
.09
.08
.07
.06
I
.06
.05
.05
Fixed Instantaneous
Override at 4000A
.04
.04
.03
.03
.02
.02
Interrupting rating
determines
end of curve
.006
.01
.009
.008
.007
.006
.005
.005
.004
.004
.003
.003
.002
.002
.01
.009
.008
.007
CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)
70
100
.001
200000
50
70000
40
100000
30
50000
20
40000
10
30000
7
20000
5
7000
4
10000
3
5000
2
4000
1
3000
.7
2000
.5
1000
.001
TIME IN SECONDS
.1
.09
.08
.07
CURRENT IN AMPERES
82 copperLogic.com
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
CPRO-CAT-1109
www.barr-thorp.com
Application Data
Time / Current Curves
Time/Current Curve
For application and coordination purposes only.
Based on 40°C ambient, cold
start. Connected with four
feet of rated wire (75°C) per
terminal. Tested in open air
with current in all poles. Instantaneous calibration based
on single-pole tests.
Single pole test data at 25°C
based on NEMA procedures (AB
4-2003) for verifying performance of molded case circuit
breakers.
2h
MF3-K(L)(M)(S)(C)-(250)(400) + KES3250(LS)(LSG)…
10000
9000
8000
7000
6000
Standard Fixed
Rating Plug
1h
5000
4000
3000
2000
1000
900
800
700
600
Long Delay
Maximum total
clearing time
500
400
300
1 min
200
100
90
80
70
Long Delay
Minimum total
clearing time
60
50
40
30
10
9
8
7
6
2x
5
Short Delay
Pick-up Settings
Tolerance ±10%
4x
TIME IN SECONDS
3x
20
4
5x
8x
3
2
1
.9
.8
.7
6x
1
.9
.8
.7
.6
.4
.3
.3
7x
.5
.4
.2
.2
.1
.09
.08
.07
.1
.09
.08
.07
.06
.06
.05
.05
Fixed Instantaneous
Override at 4000A
.04
.04
.03
.03
.02
.02
Interrupting rating
determines
end of curve
.006
.01
.009
.008
.007
.006
.005
.005
.004
.004
.003
.003
.002
.002
.01
.009
.008
.007
70
.001
100
CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)
CPRO-CAT-1109
200000
50
70000
40
100000
30
50000
20
40000
10
30000
7
20000
5
7000
4
10000
3
5000
2
4000
1
3000
.7
2000
.5
1000
.001
TIME IN SECONDS
.6
.5
CURRENT IN AMPERES
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
copperLogic.com
www.barr-thorp.com
83
Application Data
Time / Current Curves
Time/Current Curve
For application and coordination purposes only.
Based on 40°C ambient, cold
start. Connected with four
feet of rated wire (75°C) per
terminal. Tested in open air
with current in all poles. Instantaneous calibration based
on single-pole tests.
Single pole test data at 25°C
based on NEMA procedures (AB
4-2003) for verifying performance of molded case circuit
breakers.
2h
MF3-K(L)(M)(S)(C)-(250)(400) + KES3250(LSI)(LSIG)…
10000
9000
8000
7000
6000
Standard Fixed
Rating Plug
1h
5000
4000
3000
2000
1000
900
800
700
600
Long Delay
Maximum total
clearing time
500
400
300
1 min
200
100
90
80
70
Long Delay
Minimum total
clearing time
60
50
40
30
10
9
8
7
6
2x
5
Short Delay
Pick-up Settings
Tolerance ±10%
4x
TIME IN SECONDS
20
6x
4
8x
3
7x
2
1
.9
.8
.7
.6
1
.9
.8
.7
.6
.5
5x
3x
.5
.4
.4
300 ms
.3
.3
200 ms
.2
.2
100 ms
.1
.09
.08
.07
.06
I
.06
.05
.05
Fixed Instantaneous
Override at 4000A
.04
.04
.03
.03
.02
.02
Interrupting rating
determines
end of curve
.006
.01
.009
.008
.007
.006
.005
.005
.004
.004
.003
.003
.002
.002
.01
.009
.008
.007
CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)
70
100
.001
200000
50
70000
40
100000
30
50000
20
40000
10
30000
7
20000
5
7000
4
10000
3
5000
2
4000
1
3000
.7
2000
.5
1000
.001
TIME IN SECONDS
.1
.09
.08
.07
CURRENT IN AMPERES
84 copperLogic.com
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
CPRO-CAT-1109
www.barr-thorp.com
Application Data
Time / Current Curves
Time/Current Curve
For application and coordination purposes only.
Based on 40°C ambient, cold
start. Connected with four
feet of rated wire (75°C) per
terminal. Tested in open air
with current in all poles. Instantaneous calibration based
on single-pole tests.
Single pole test data at 25°C
based on NEMA procedures (AB
4-2003) for verifying performance of molded case circuit
breakers.
2h
MF3-K(L)(M)(S)(C)-400 + KES3400(LS)(LSG)…
10000
9000
8000
7000
6000
Standard Fixed
Rating Plug
1h
5000
4000
3000
2000
1000
900
800
700
600
Long Delay
Maximum total
clearing time
500
400
300
1 min
200
100
90
80
70
Long Delay
Minimum total
clearing time
60
50
40
30
10
9
8
7
6
2x
5
Short Delay
Pick-up Settings
Tolerance ±10%
4x
TIME IN SECONDS
3x
20
4
5x
8x
3
2
1
.9
.8
.7
6x
1
.9
.8
.7
.6
.4
.3
.3
7x
.5
.4
.2
.2
.1
.09
.08
.07
.1
.09
.08
.07
.06
.06
.05
.05
Fixed Instantaneous
Override at 4000A
.04
.04
.03
.03
.02
.02
Interrupting rating
determines
end of curve
.006
.01
.009
.008
.007
.006
.005
.005
.004
.004
.003
.003
.002
.002
.01
.009
.008
.007
70
.001
100
CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)
CPRO-CAT-1109
200000
50
70000
40
100000
30
50000
20
40000
10
30000
7
20000
5
7000
4
10000
3
5000
2
4000
1
3000
.7
2000
.5
1000
.001
TIME IN SECONDS
.6
.5
CURRENT IN AMPERES
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
copperLogic.com
www.barr-thorp.com
85
Application Data
Time / Current Curves
Time/Current Curve
For application and coordination purposes only.
Based on 40°C ambient, cold
start. Connected with four
feet of rated wire (75°C) per
terminal. Tested in open air
with current in all poles. Instantaneous calibration based
on single-pole tests.
Single pole test data at 25°C
based on NEMA procedures (AB
4-2003) for verifying performance of molded case circuit
breakers.
2h
MF3-K(L)(M)(S)(C)-400 + KES3400(LSI)(LSIG)…
10000
9000
8000
7000
6000
Standard Fixed
Rating Plug
1h
5000
4000
3000
2000
1000
900
800
700
600
Long Delay
Maximum total
clearing time
500
400
300
1 min
200
100
90
80
70
Long Delay
Minimum total
clearing time
60
50
40
30
10
9
8
7
6
2x
5
Short Delay
Pick-up Settings
Tolerance ±10%
4x
TIME IN SECONDS
20
6x
4
8x
3
7x
2
1
.9
.8
.7
.6
1
.9
.8
.7
.6
.5
5x
3x
.5
.4
.4
300 ms
.3
.3
200 ms
.2
.2
100 ms
.1
.09
.08
.07
I
.06
.05
.05
Fixed Instantaneous
Override at 4000A
.04
.04
.03
.03
.02
.02
Interrupting rating
determines
end of curve
.006
.01
.009
.008
.007
.006
.005
.005
.004
.004
.003
.003
.002
.002
.01
.009
.008
.007
CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)
70
100
.001
200000
50
70000
40
100000
30
50000
20
40000
10
30000
7
20000
5
7000
4
10000
3
5000
2
4000
1
3000
.7
2000
.5
1000
.001
TIME IN SECONDS
.1
.09
.08
.07
.06
CURRENT IN AMPERES
86 copperLogic.com
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
CPRO-CAT-1109
www.barr-thorp.com
Application Data
Time / Current Curves
Time/Current Curve
For application and coordination purposes only.
Based on 40°C ambient, cold
start. Connected with four
feet of rated wire (75°C) per
terminal. Tested in open air
with current in all poles. Instantaneous calibration based
on single-pole tests.
Single pole test data at 25°C
based on NEMA procedures (AB
4-2003) for verifying performance of molded case circuit
breakers.
2h
MF3-KHS-(250)(400) + KES3125(LS)(LSG)…
10000
9000
8000
7000
6000
Standard Fixed
Rating Plug
1h
5000
4000
3000
2000
1000
900
800
700
600
Long Delay
Maximum total
clearing time
500
400
300
1 min
200
100
90
80
70
Long Delay
Minimum total
clearing time
60
50
40
30
10
9
8
7
6
2x
5
Short Delay
Pick-up Settings
Tolerance ±10%
4x
TIME IN SECONDS
3x
20
4
5x
8x
3
2
1
.9
.8
.7
6x
1
.9
.8
.7
.6
.4
.3
.3
7x
.5
.4
.2
.2
.1
.09
.08
.07
.1
.09
.08
.07
.06
.06
.05
.05
Fixed Instantaneous
Override at 4000A
.04
.04
.03
.03
.02
.02
600V AC
.01
.009
.008
.007
.01
.009
.008
.007
.006
480V AC
.006
.005
.005
.004
240V AC
.004
.003
.003
Interrupting rating
determines
end of curve
.002
70
.001
100
CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)
CPRO-CAT-1109
.002
200000
50
70000
40
100000
30
50000
20
40000
10
30000
7
20000
5
7000
4
10000
3
5000
2
4000
1
3000
.7
2000
.5
1000
.001
TIME IN SECONDS
.6
.5
CURRENT IN AMPERES
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
copperLogic.com
www.barr-thorp.com
87
Application Data
Time / Current Curves
Time/Current Curve
For application and coordination purposes only.
Based on 40°C ambient, cold
start. Connected with four
feet of rated wire (75°C) per
terminal. Tested in open air
with current in all poles. Instantaneous calibration based
on single-pole tests.
Single pole test data at 25°C
based on NEMA procedures (AB
4-2003) for verifying performance of molded case circuit
breakers.
2h
MF3-KHS-(250)(400) + KES3125(LSI)(LSIG)…
10000
9000
8000
7000
6000
Standard Fixed
Rating Plug
1h
5000
4000
3000
2000
1000
900
800
700
600
Long Delay
Maximum total
clearing time
500
400
300
1 min
200
100
90
80
70
Long Delay
Minimum total
clearing time
60
50
40
30
10
9
8
7
6
2x
5
Short Delay
Pick-up Settings
Tolerance ±10%
4x
TIME IN SECONDS
20
6x
4
8x
3
7x
2
1
.9
.8
.7
.6
1
.9
.8
.7
.6
.5
5x
3x
.5
.4
.4
300 ms
.3
.3
200 ms
.2
.2
100 ms
.1
.09
.08
.07
.06
I
.06
.05
.05
Fixed Instantaneous
Override at 4000A
.04
.04
.03
.03
.02
.02
600V AC
.01
.009
.008
.007
.01
.009
.008
.007
.006
480V AC
.006
.005
.005
.004
240V AC
Interrupting rating
determines
end of curve
.002
100
.002
.001
200000
70
70000
50
100000
40
50000
30
40000
20
30000
10
20000
7
7000
5
10000
4
5000
3
4000
2
3000
1
2000
.7
1000
.5
CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)
.004
.003
.003
.001
TIME IN SECONDS
.1
.09
.08
.07
CURRENT IN AMPERES
88 copperLogic.com
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
CPRO-CAT-1109
www.barr-thorp.com
Application Data
Time / Current Curves
Time/Current Curve
For application and coordination purposes only.
Based on 40°C ambient, cold
start. Connected with four
feet of rated wire (75°C) per
terminal. Tested in open air
with current in all poles. Instantaneous calibration based
on single-pole tests.
Single pole test data at 25°C
based on NEMA procedures (AB
4-2003) for verifying performance of molded case circuit
breakers.
2h
MF3-KHS-(250)(400) + KES3250(LS)(LSG)…
10000
9000
8000
7000
6000
Standard Fixed
Rating Plug
1h
5000
4000
3000
2000
1000
900
800
700
600
Long Delay
Maximum total
clearing time
500
400
300
1 min
200
100
90
80
70
Long Delay
Minimum total
clearing time
60
50
40
30
10
9
8
7
6
2x
5
Short Delay
Pick-up Settings
Tolerance ±10%
4x
TIME IN SECONDS
3x
20
4
5x
8x
3
2
1
.9
.8
.7
6x
1
.9
.8
.7
.6
.4
.3
.3
7x
.5
.4
.2
.2
.1
.09
.08
.07
.1
.09
.08
.07
.06
.06
.05
.05
Fixed Instantaneous
Override at 4000A
.04
.04
.03
.03
.02
.02
600V AC
.01
.009
.008
.007
.01
.009
.008
.007
.006
480V AC
.006
.005
.005
.004
240V AC
.004
.003
.003
Interrupting rating
determines
end of curve
.002
70
.001
100
CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)
CPRO-CAT-1109
.002
200000
50
70000
40
100000
30
50000
20
40000
10
30000
7
20000
5
7000
4
10000
3
5000
2
4000
1
3000
.7
2000
.5
1000
.001
TIME IN SECONDS
.6
.5
CURRENT IN AMPERES
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
copperLogic.com
www.barr-thorp.com
89
Application Data
Time / Current Curves
Time/Current Curve
For application and coordination purposes only.
Based on 40°C ambient, cold
start. Connected with four
feet of rated wire (75°C) per
terminal. Tested in open air
with current in all poles. Instantaneous calibration based
on single-pole tests.
Single pole test data at 25°C
based on NEMA procedures (AB
4-2003) for verifying performance of molded case circuit
breakers.
2h
MF3-KHS-(250)(400) + KES3250(LSI)(LSIG)…
10000
9000
8000
7000
6000
Standard Fixed
Rating Plug
1h
5000
4000
3000
2000
1000
900
800
700
600
Long Delay
Maximum total
clearing time
500
400
300
1 min
200
100
90
80
70
Long Delay
Minimum total
clearing time
60
50
40
30
10
9
8
7
6
2x
5
Short Delay
Pick-up Settings
Tolerance ±10%
4x
TIME IN SECONDS
20
6x
4
8x
3
7x
2
1
.9
.8
.7
.6
1
.9
.8
.7
.6
.5
5x
3x
.5
.4
.4
300 ms
.3
.3
200 ms
.2
.2
100 ms
.1
.09
.08
.07
.06
I
.06
.05
.05
Fixed Instantaneous
Override at 4000A
.04
.04
.03
.03
.02
.02
600V AC
.01
.009
.008
.007
.01
.009
.008
.007
.006
480V AC
.006
.005
.005
.004
240V AC
Interrupting rating
determines
end of curve
.002
100
.002
.001
200000
70
70000
50
100000
40
50000
30
40000
20
30000
10
20000
7
7000
5
10000
4
5000
3
4000
2
3000
1
2000
.7
1000
.5
CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)
.004
.003
.003
.001
TIME IN SECONDS
.1
.09
.08
.07
CURRENT IN AMPERES
90 copperLogic.com
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
CPRO-CAT-1109
www.barr-thorp.com
Application Data
Time / Current Curves
Time/Current Curve
For application and coordination purposes only.
Based on 40°C ambient, cold
start. Connected with four
feet of rated wire (75°C) per
terminal. Tested in open air
with current in all poles. Instantaneous calibration based
on single-pole tests.
Single pole test data at 25°C
based on NEMA procedures (AB
4-2003) for verifying performance of molded case circuit
breakers.
2h
MF3-KHS-400 + KES3400(LS)(LSG)…
10000
9000
8000
7000
6000
Standard Fixed
Rating Plug
1h
5000
4000
3000
2000
1000
900
800
700
600
Long Delay
Maximum total
clearing time
500
400
300
1 min
200
100
90
80
70
Long Delay
Minimum total
clearing time
60
50
40
30
10
9
8
7
6
2x
5
Short Delay
Pick-up Settings
Tolerance ±10%
4x
TIME IN SECONDS
3x
20
4
5x
8x
3
2
1
.9
.8
.7
6x
1
.9
.8
.7
.6
.4
.3
.3
7x
.5
.4
.2
.2
.1
.09
.08
.07
.1
.09
.08
.07
.06
.06
.05
.05
Fixed Instantaneous
Override at 4000A
.04
.04
.03
.03
.02
.02
600V AC
.01
.009
.008
.007
.01
.009
.008
.007
.006
480V AC
.006
.005
.005
.004
240V AC
.004
.003
.003
Interrupting rating
determines
end of curve
.002
70
.001
100
CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)
CPRO-CAT-1109
.002
200000
50
70000
40
100000
30
50000
20
40000
10
30000
7
20000
5
7000
4
10000
3
5000
2
4000
1
3000
.7
2000
.5
1000
.001
TIME IN SECONDS
.6
.5
CURRENT IN AMPERES
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
copperLogic.com
www.barr-thorp.com
91
Application Data
Time / Current Curves
Time/Current Curve
For application and coordination purposes only.
Based on 40°C ambient, cold
start. Connected with four
feet of rated wire (75°C) per
terminal. Tested in open air
with current in all poles. Instantaneous calibration based
on single-pole tests.
Single pole test data at 25°C
based on NEMA procedures (AB
4-2003) for verifying performance of molded case circuit
breakers.
2h
MF3-KHS-400 + KES3400(LSI)(LSIG)…
10000
9000
8000
7000
6000
Standard Fixed
Rating Plug
1h
5000
4000
3000
2000
1000
900
800
700
600
Long Delay
Maximum total
clearing time
500
400
300
1 min
200
100
90
80
70
Long Delay
Minimum total
clearing time
60
50
40
30
10
9
8
7
6
2x
5
Short Delay
Pick-up Settings
Tolerance ±10%
4x
TIME IN SECONDS
20
6x
4
8x
3
7x
2
1
.9
.8
.7
.6
1
.9
.8
.7
.6
.5
5x
3x
.5
.4
.4
300 ms
.3
.3
200 ms
.2
.2
100 ms
.1
.09
.08
.07
.06
I
.06
.05
.05
Fixed Instantaneous
Override at 4000A
.04
.04
.03
.03
.02
.02
TIME IN SECONDS
.1
.09
.08
.07
600V AC
.01
.009
.008
.007
.01
.009
.008
.007
.006
480V AC
.006
.005
.005
.004
240V AC
Interrupting rating
determines
end of curve
.002
CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)
70
100
.002
.001
200000
50
70000
40
100000
30
50000
20
40000
10
30000
7
20000
5
7000
4
10000
3
5000
2
4000
1
3000
.7
2000
.5
1000
.001
.004
.003
.003
CURRENT IN AMPERES
92 copperLogic.com
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
CPRO-CAT-1109
www.barr-thorp.com
Application Data
Time / Current Curves
Time/Current Curve
For application and coordination purposes only.
Based on 40°C ambient, cold
start. Connected with four
feet of rated wire (75°C) per
terminal. Tested in open air
with current in all poles. Instantaneous calibration based
on single-pole tests.
Single pole test data at 25°C
based on NEMA procedures (AB
4-2003) for verifying performance of molded case circuit
breakers.
2h
KES3125(LSG)(LSIG)…
10000
9000
8000
7000
6000
1h
5000
4000
3000
2000
1000
900
800
700
600
500
400
300
1 min
200
100
90
80
70
60
50
40
30
3x IG
10
9
8
7
6
5
4x IG
TIME IN SECONDS
20
4
Short Delay
Pick-up Settings
Tolerance ±10%
2
5x IG
2x IG
3
1
.9
.8
.7
.6
500 ms
.5
.4
300 ms
.3
150 ms
.2
.1
.09
.08
.07
I
.06
.05
.04
.03
.02
.01
.009
.008
.007
.006
.005
.004
.003
.002
.001
.5
.7
1
2
3
4
5
7
10
20
30
40
50
70
100
GROUND CURRENT IN MULTIPLES OF (IG) = 25A
CPRO-CAT-1109
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
copperLogic.com
www.barr-thorp.com
93
Application Data
Time / Current Curves
Time/Current Curve
For application and coordination purposes only.
Based on 40°C ambient, cold
start. Connected with four
feet of rated wire (75°C) per
terminal. Tested in open air
with current in all poles. Instantaneous calibration based
on single-pole tests.
Single pole test data at 25°C
based on NEMA procedures (AB
4-2003) for verifying performance of molded case circuit
breakers.
2h
KES3250(LSG)(LSIG)…
10000
9000
8000
7000
6000
1h
5000
4000
3000
2000
1000
900
800
700
600
500
400
300
1 min
200
100
90
80
70
60
50
40
30
3x IG
10
9
8
7
6
5
4x IG
1x IG
TIME IN SECONDS
20
4
Short Delay
Pick-up Settings
Tolerance ±10%
2
5x IG
2x IG
3
1
.9
.8
.7
.6
500 ms
.5
.4
300 ms
.3
.2
150 ms
.1
.09
.08
.07
I
.06
.05
.04
.03
.02
.01
.009
.008
.007
.006
.005
.004
.003
.002
.001
.5
.7
1
2
3
4
5
7
10
20
30
40
50
70
100
GROUND CURRENT IN MULTIPLES OF (IG) = 50A
94 copperLogic.com
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
CPRO-CAT-1109
www.barr-thorp.com
Application Data
Time / Current Curves
Time/Current Curve
For application and coordination purposes only.
Based on 40°C ambient, cold
start. Connected with four
feet of rated wire (75°C) per
terminal. Tested in open air
with current in all poles. Instantaneous calibration based
on single-pole tests.
Single pole test data at 25°C
based on NEMA procedures (AB
4-2003) for verifying performance of molded case circuit
breakers.
2h
KES3400(LSG)(LSIG)…
10000
9000
8000
7000
6000
1h
5000
4000
3000
2000
1000
900
800
700
600
500
400
300
1 min
200
100
90
80
70
60
50
40
30
3x IG
10
9
8
7
6
5
4x IG
1x IG
TIME IN SECONDS
20
4
Short Delay
Pick-up Settings
Tolerance ±10%
2
5x IG
2x IG
3
1
.9
.8
.7
.6
500 ms
.5
.4
300 ms
.3
.2
150 ms
.1
.09
.08
.07
I
.06
.05
.04
.03
.02
.01
.009
.008
.007
.006
.005
.004
.003
.002
.001
.5
.7
1
2
3
4
5
7
10
20
30
40
50
70
100
GROUND CURRENT IN MULTIPLES OF (IG) = 80A
CPRO-CAT-1109
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
copperLogic.com
www.barr-thorp.com
95
Technical Data
cPRO K-series
cPRO K-series Circuit Breakers
cPRO K-series Molded Case Switches
General
Standards
Dimensions (W x H x D)
Two pole
Three pole
Weight
Three pole
Mounting
…-K(2)(4)L(S)(C)-…
CS(2)(3)-KLC-…
…-K(2)(4)HS-…
UL 489, CSA C22.2 No. 5
[mm]
[mm]
140 x 258 x 104
140 x 258 x 104
140 x 258 x 104
140 x 258 x 104
140 x 258 x 104
140 x 258 x 104
[kg]
6.1
6.1
6.1
Rated operational voltage
NEMA
Permissible ambient temperature
DC Interrupting Rating
NEMA Time constant T = 8 rms
1 conducting path
2 conducting paths in series
AC Interrupting Rating
NEMA, Two and Three pole breakers
240 V AC
480 V AC
600 V AC
250 V DC
Endurance (operating cycles)
Maximum switching frequency
Main Conductor Terminal Capacities
Terminal type
Solid or stranded
70 – 225 Amps
250 – 350 Amps
400 Amps
Tightening torque for box terminals
70 – 225 Amps
250 – 350 Amps
400 Amps
K2: 250
K4: 400
K2: 250
K4: 400
K2: 250
K4: 400
600
0 … 40 °C / 32 … 104 °F
600
0 … 40 °C / 32 … 104 °F
600
0 … 40 °C / 32 … 104 °F
[kA]
[kA]
10
22
10
22
10
22
[kA]
[kA]
[kA]
[kA]
65
35
25
10
8000
240
100
65
35
22
8000
240
200
100
50
22
8000
240
box terminals
box terminals
box terminals
[AWG]
[AWG]
[AWG]
#3 – 350 MCM
250 – 500 MCM
2x (#3/0 – 250 MCM)
#3 – 350 MCM
250 – 500 MCM
2x (#3/0 – 250 MCM)
#3 – 350 MCM
250 – 500 MCM
2x (#3/0 – 250 MCM)
[lbs-in]
[lbs-in]
[lbs-in]
275
375
275
275
375
275
275
375
275
[V AC]
[°C / °F]
250 V DC
250 V DC
90
90
[A]
90
90
Maximum rated current In
Two and Three pole
…-K(2)(4)M(S)(C)-…
CS(2)(3)-KMC-…
[per hour]
96 copperLogic.com
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
CPRO-CAT-1109
www.barr-thorp.com
Technical Data
cPRO K-series
cPRO K-series Circuit Breakers
cPRO K-series Molded Case Switches
Auxiliary Switches
Maximum rated voltage
AC
DC
Rated operational current - AC
600 V
Rated operational current - DC
125 V
240 V
Undervoltage Releases
Response voltage - AC, 50/60 Hz
12V
Dropout Min
Dropout Max
Pickup Max
24V
Dropout Min
Dropout Max
Pickup Max
48 – 60V
Dropout Min
Dropout Max
Pickup Max
110 – 127V
Dropout Min
Dropout Max
Pickup Max
208 – 240V
Dropout Min
Dropout Max
Pickup Max
380 – 480V
Dropout Min
Dropout Max
Pickup Max
Power consumption - AC, 50/60 Hz
12V
24V
48V
60V
110V
120V
127V
208V
220V
240V
380V
415V
440V
480V
CPRO-CAT-1109
…-K(2)(4)L(S)(C)-…
CS(2)(3)-KLC-…
…-K(2)(4)M(S)(C)-…
CS(2)(3)-KMC-…
…-K(2)(4)HS-…
[V]
[V]
600
250
600
250
600
250
[A]
6
6
6
[A]
[A]
0.5
0.25
0.5
0.25
0.5
0.25
[V]
[V]
[V]
4.2
8.4
10.2
4.2
8.4
10.2
4.2
8.4
10.2
[V]
[V]
[V]
8.4
16.8
20.4
8.4
16.8
20.4
8.4
16.8
20.4
[V]
[V]
[V]
21.0
33.6
40.8
21.0
33.6
40.8
21.0
33.6
40.8
[V]
[V]
[V]
44.5
77.0
93.5
44.5
77.0
93.5
44.5
77.0
93.5
[V]
[V]
[V]
85.0
145.6
176.8
85.0
145.6
176.8
85.0
145.6
176.8
[V]
[V]
[V]
168.0
266.0
323.0
168.0
266.0
323.0
168.0
266.0
323.0
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
1.9
3.9
2.5
3.8
1.8
2.1
2.4
2.7
3.1
3.8
3.4
4.0
4.6
5.4
1.9
3.9
2.5
3.8
1.8
2.1
2.4
2.7
3.1
3.8
3.4
4.0
4.6
5.4
1.9
3.9
2.5
3.8
1.8
2.1
2.4
2.7
3.1
3.8
3.4
4.0
4.6
5.4
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
copperLogic.com
www.barr-thorp.com
97
Technical Data
cPRO K-series
cPRO K-series Circuit Breakers
cPRO K-series Molded Case Switches
Undervoltage Releases (continued)
Response voltage - DC
12V
Dropout Min
Dropout Max
Pickup Max
24V
Dropout Min
Dropout Max
Pickup Max
48 – 60V
Dropout Min
Dropout Max
Pickup Max
110 – 125V
Dropout Min
Dropout Max
Pickup Max
220 – 250V
Dropout Min
Dropout Max
Pickup Max
Power consumption - DC
12V
24V
48V
60V
110V
120V
125V
220V
250V
Shunt Trips
Minimum operating voltage - AC, 50/60 Hz
12 – 60V
110 – 240V
380 – 440V
480 – 600V
Power consumption - AC, 50/60 Hz
12V
24V
48V
60V
110V
120V
127V
208V
220V
240V
380V
400V
415V
440V
480V
525V
550V
600V
…-K(2)(4)L(S)(C)-…
CS(2)(3)-KLC-…
…-K(2)(4)M(S)(C)-…
CS(2)(3)-KMC-…
…-K(2)(4)HS-…
[V]
[V]
[V]
4.2
8.4
10.2
4.2
8.4
10.2
4.2
8.4
10.2
[V]
[V]
[V]
8.4
16.8
20.4
8.4
16.8
20.4
8.4
16.8
20.4
[V]
[V]
[V]
21.0
33.6
40.8
21.0
33.6
40.8
21.0
33.6
40.8
[V]
[V]
[V]
44.5
77.0
93.5
44.5
77.0
93.5
44.5
77.0
93.5
[V]
[V]
[V]
87.5
154.0
187.0
87.5
154.0
187.0
87.5
154.0
187.0
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
1.6
3.1
2.0
3.1
1.6
1.9
2.2
3.1
4.0
1.6
3.1
2.0
3.1
1.6
1.9
2.2
3.1
4.0
1.6
3.1
2.0
3.1
1.6
1.9
2.2
3.1
4.0
[V]
[V]
[V]
[V]
9
60
285
360
9
60
285
360
9
60
285
360
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
45
200
830
1280
100
120
140
420
470
550
95
108
120
136
40
50
50
70
45
200
830
1280
100
120
140
420
470
550
95
108
120
136
40
50
50
70
45
200
830
1280
100
120
140
420
470
550
95
108
120
136
40
50
50
70
98 copperLogic.com
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
CPRO-CAT-1109
www.barr-thorp.com
Technical Data
cPRO K-series
cPRO K-series Circuit Breakers
cPRO K-series Molded Case Switches
Shunt Trips (continued)
Minimum operating voltage - DC
12 – 60V
110 – 125V
220 – 250V
Power consumption - DC
12V
24V
48V
60V
110V
120V
125V
220V
250V
CPRO-CAT-1109
…-K(2)(4)L(S)(C)-…
CS(2)(3)-KLC-…
…-K(2)(4)M(S)(C)-…
CS(2)(3)-KMC-…
…-K(2)(4)HS-…
[V]
[V]
[V]
8.4
77
154
8.4
77
154
8.4
77
154
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
[VA]
35
170
710
1105
110
130
140
41
54
35
170
710
1105
110
130
140
41
54
35
170
710
1105
110
130
140
41
54
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
copperLogic.com
www.barr-thorp.com
99
Dimensions
cPRO K-series
Circuit Breakers
Dimensions are in inches (millimeters).
Not intended for manufacturing purposes.
TM2-K…; MF2-K…; CS2-K…; TM3-K…; MF3-K…; ET3-K…; CS3-K…
4.313
(109.55)
5.490(139.43)
1.719
(43.66)
.625
(15.88)
3.813
(96.85)
ON
8.875
(225.43)
10.125
(257.18)
OFF
CL
Handle
3.875 R
(98.42) R
1.250
(31.75)
4.782(121.46)
1.160
(29.49)
4.062
(103.17)
Dimensions for Extended
Terminals and Barrier Style
Nos. 4212B60G02,
4212B61G02 and 1492D24H01
.062
(1.57)
4.95
(125.7)
.875
(22.25)
1.063
(27.00)
3.812
(96.82)
2.375
(60.33)
100 copperLogic.com
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
CPRO-CAT-1109
www.barr-thorp.com
Dimensions
cPRO K-series
Drilling Plans
Dimensions are in inches (millimeters).
Not intended for manufacturing purposes.
TM2-K…; MF2-K…; CS2-K…; TM3-K…; MF3-K…; ET3-K…; CS3-K…
Front Connected
Front Cover Cutout
Rear Connected
.344 R
(8.74) R
.844
(21.44)
.875(22.23) Dia.
(6 Places)
(Omit 2 Center
Holes for 2-Pole)
3.750
(95.25)
CL Breaker Handle
.188 R
(4.77) R
.828
(21.03)
4.922
(125.02)
1.640
(41.66)
1.250
(31.75)
5.141
(130.58)
8.438
(214.33)
CL Breaker Handle
1.313
(33.34)
2.625
(66.68)
3.734
(94.84)
3.516
(89.31)
2.391
(60.73)
8.875
(225.42)
CL Breaker Handle
4.782
(121.46)
.250-20 (M6)
4 Holes
CPRO-CAT-1109
1.719
(43.66)
.859
(21.83)
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
1.719
(43.66)
1.719
(43.66)
copperLogic.com
www.barr-thorp.com
101
cPRO Molded Case Circuit Breakers
Notes
102 copperLogic.com
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
CPRO-CAT-1109
www.barr-thorp.com
Conditions of Sale and Shipment
Valid in United States of America
Note: The following terms are for general information
only. All conditions of sales are subject to change and
are valid as determined in the latest terms and conditions publication of CopperLogic, Inc. (referred to
herein after as “The Company”).
shipment other than that selected by the Company, the purchaser will be billed accordingly.
No credits will be allowed in lieu of transportation in the case of pickups at the Company’s
warehouses, branches, or factory. No transportation charges can be deducted from a selling
price. Air freight, water freight, heavy lift charges, pier delivery charges, wharfage, marine
insurance and the cost of stevedoring are chargeable to the purchaser. These terms include
shipments to Alaska, Hawaii, Puerto Rico, and the Virgin Islands.
1. Acceptance of orders
All orders are subject to final acceptance by an authorized representative of the Company
and are subject to the Company’s terms and conditions in effect at the time of acceptance.
The Company takes exception to any other terms and conditions except for such terms and
conditions as the Company may expressly accept in writing.
9. Packing other than standard
If other than standard commercial packing is required the cost of such special packing (determinable only after packing is completed) will be charged to the purchaser. Export packing
shall be considered as packing other than standard.
2. Prices
Prices and discounts as shown in the company’s publications are subject to change without
notice. In the event of a net price change, the price of equipment on order but unshipped
will be the price in effect on the date of shipment. In no case will the amount of a price
increase exceed 10% of the price at which the order was accepted, except that, if the delivery
is delayed upon instructions from the purchaser, prices shall be those in effect when the
instructions are received to proceed with the order. Price reductions shall only apply to unshipped portions of outstanding orders. Any addition or alteration to an outstanding order
will be accepted at prices in effect when the addition or alteration is accepted. Applicable
taxes are additional.
3. Quotations
All quotations are in accordance with the Company’s interpretation of plans and specifications and only material shown on the Company’s quotations are included. Written quotations automatically expire thirty (30) days from the date of issue unless sooner terminated
by notice. Quotations are subject to all existing or future limitations and regulations issued
by any government agency. In the event that a quotation is not accepted in its entirety, the
Company reserves the right to decline any parts of the order based on such quotation.
10. Acceptance of orders
The purchaser will be responsible for any applicable export license and all associated costs
involved with said license on any export project.
11. Export Control
Equipment and associated materials supplied or licensed under this transaction may be subject to various export laws and regulations. It is the responsibility of the exporter to comply
with all such laws and regulations.
12. Responsibility and Title
Title in the equipment shall remain with the Company as security only and until full payment is received. Risk of loss for the equipment shall pass to purchaser upon shipment from
F.O.B. point of shipment or date of invoicing, which ever is sooner.
All Accounting, clerical or other errors are subject to correction.
13. Loss or Damage in Transit
The Company does not hold itself responsible for any loss, damage, (obvious or concealed)
or pilferage sustained in transit. Claims of such character should be made, by the purchaser,
promptly against the transportation company. If the Company is notified of such claims, the
Company will offer to lend assistance to secure adjustment. The Company employs experienced packers and cannot be held responsible for breakage that occurs after the Company’s
securing the “Received in Good Order” receipt from the transportation company.
4. Minimum Billing
Orders amounting to less than $100.00 net will be billed at $100.00 plus the transportation
charge, at a minimum of $25.00.
14. Return of Merchandise
No equipment may be returned unless authorization has been obtained from an authorized
representative of the Company. Unauthorized returns of equipment cannot be accepted.
5. Terms - Regular
Terms to purchasers of satisfactory credit are: 30 days net from the date of invoice. Cash discounts, when applicable, are indicated on the face of the Company’s invoice. To avoid delay
in filling orders purchasers without previous experience with the Company should include
credit references with the first order, or send a certified check or money order. Any amount
owed to the Company becomes due and payable immediately in case of change of ownership of the purchaser, attachment or execution against the purchaser or it’s representatives,
unless the Company otherwise agrees.
A. To be returned for credit
Only unused equipment of current design may be returned for credit. Where a purchaser returns equipment for reasons of his own, a minimum restocking charge of 20%
of billing, plus transportation charges, will be made. Any cost incurred in putting the
equipment into saleable condition shall also be deducted from allowed credit. If return
of equipment is made necessary by fault of the Company, full credit will be allowed
including transportation charges.
6. Payments
Payments should be made to the address indicated on the invoice, or to CopperLogic, Inc., PO
Box 62073, Houston, TX 77205.
7. Delivery
The Company reserves the right to make delivery in installments, unless otherwise expressly
stipulated in the contract for sale; and all such installments when separately invoiced shall
be paid for when due per invoice, without regard to subsequent deliveries. Delay in delivery
of any installment shall not relieve the purchaser of its obligations to accept remaining deliveries. Shipments delayed to accommodate the purchaser will be invoiced upon completion
of fabrication and additional charges for warehousing, trucking and other incidental expenses created by the delay will be at the expense of the purchaser. Delivery is dependent upon
prompt receipt of all specifications, final approved prints and any other details essential to
the proper execution of the purchaser’s order. Claims for shortages or other errors must be
reported in writing to the Company within 10 days after receipt of shipment. Failure to do so
will constitute a waiver of all claims by the purchaser.
8. Shipping Terms
The method and route of shipment is determined by the Company. All merchandise orders
of $500.00 net or more will be shipped F.O.B. CopperLogic’s warehouse, freight prepaid, best
way ground transportation. All engineered equipment orders will be shipped F.O.B. CopperLogic’s loading dock, freight not allowed. When purchaser specifies a method or routing of
CPRO-CAT-1109
B. To be returned for replacement
If the equipment is under guarantee and the return is made necessary because of defect
in material and/or workmanship, providing permission is obtained from the Company
for its return, the Company will replace the defective goods “no charge”, and will assume
the transportation charges.
C. Custom-built equipment
Equipment built based upon purchaser specification cannot be returned for credit.
15. Cancellations:
Any order placed with the Company can be canceled by the purchaser provided that: a) the
cancellation is agreed to in writing by the Company; and b) the purchaser agrees to compensate the Company for engineering, fabrication, outside sourcing of devices and any other
demonstrated expenses incurred or commitments made by the Company up to the date of
notice of cancellation and all charges incurred by the Company in respect of the cancellation.
16. Force Majeure
The Company shall not be liable for any delay in the performance of orders or contracts or in
the delivery or shipment of equipment or for any loss and/or damages suffered by purchaser
by reason of such delay when such delay is directly or indirectly caused by fire, floods, accidents, riots, acts of God, war, invasion, sabotage, terrorism and governmental interference
or embargoes, strikes, labor difficulties, shortage of labor, fuel, power, materials or supplies
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
copperLogic.com
www.barr-thorp.com
103
Conditions of Sale and Shipment
Valid in United States of America
or any other cause beyond the Company’s reasonable control. In any event, the Company
shall not be liable for special or consequential damages for loss of use. Should such a delay
occur, the delivery date shall be extended as may be necessary to compensate for the delay.
The Company shall not be liable for any change of dimensions, weights and materials as long
as the change is nonessential for the proper performance of the product.
17. Guarantee
The Company guarantees for a period of one (1) year from the date of the Company invoice
that equipment furnished under the order will be of merchantable quality, free from defects
in material, workmanship and design each as determined, at the date of shipment by the
Company by generally recognized, applicable and accepted practices and procedures in the
industry including any specifications furnished by the purchaser and agreed to in writing by
the Company for incorporation into the equipment. Satisfaction of this guarantee, consistent
with other provisions herein, will be limited to the replacement or repair or modification
of, or issuance of a credit for, the equipment involved at the Company’s option, with the
Company to determine the availability of service personnel and purchaser to pay associated
service expenses: such guarantee satisfaction available only if: (a) the Company is promptly
notified in writing upon discovery of an alleged defect and (b) the company’s examination
of the subject equipment discloses, to the Company’s satisfaction, that any defect has not
been caused by misuse, neglect, improper installation, improper operation, improper maintenance, repair or alteration, accident, or unusual deterioration or degradation of the equipment parts, thereof due to physical environment or due to electrical or electromagnetic
noise environment. THIS GUARANTEE IS IN LIEU OF ALL OTHER GUARANTEES WHETHER EXPRESSED, IMPLIED OR STATUTORY, INCLUDING IMPLIED GUARANTEES OF MERCHANTABILITY
OR FITNESS and thereby excludes certifications or the like for equipment performance, use
or design with respect to any standard, regulation or the like (unless and to the extent independently approved in writing by the Company) AND EXTENDS ONLY TO THE CUSTOMER OR
PURCHASER PURCHASING FROM THE COMPANY OR AN AUTHORIZED COMPANY DISTRIBUTOR.
18. Limitation of Liability
IN NO EVENT WILL THE COMPANY BE LIABLE FOR INCIDENTAL, INDIRECT OR AS IS CONSEQUENTIAL DAMAGES OF ANY KIND. THE COMPANY’S MAXIMUM CUMULATIVE LIABILITY RELATIVE
TO ALL OTHER CLAIMS AND LIABILITIES, INCLUDING THAT WITH RESPECT TO DIRECT DAMAGES
AND OBLIGATIONS UNDER ANY INDEMNITY, WHETHER OR NOT INSURED, WILL NOT EXCEED
THE COST OF THE PRODUCTS GIVING RISE TO THE CLAIM OR LIABILITY. THE COMPANY DISCLAIMS ALL LIABILITY RELATIVE TO GRATUITOUS INFORMATION OR ASSISTANCE PROVIDED
BY, BUT NOT REQUIRED OF THE COMPANY HEREUNDER. ANY ACTION AGAINST THE COMPANY
MUST BE BROUGHT WITHIN EIGHTEEN (18) MONTHS AFTER THE CAUSE OF ACTIONS ACCRUES.
THESE DISCLAIMERS AND LIMITATIONS OF LIABILITY WILL APPLY REGARDLESS OF ANY OTHER
CONTRARY PROVISION OF THE AGREEMENT AND REGARDLESS OF THE FORM OF ACTION,
WHETHER IN CONTRACT, TORT OR OTHERWISE AND FURTHER WILL EXTEND TO THE BENEFIT
OF THE COMPANY’S VENDORS, APPOINTED DISTRIBUTORS AND OTHER AUTHORIZED RESELLERS AS THIRD-PARTY BENEFICIARIES. EACH PROVISION IN THE AGREEMENT WHICH PROVIDES
FOR A LIMITATION OF LIABILITY, DISCLAIMER OF WARRANTY OR CONDITION OR EXCLUSION
OF DAMAGES IS SEVERABLE AND INDEPENDENT OF ANY OTHER PROVISION AND IS TO BE ENFORCED AS SUCH.
19. Penalty Clauses
The Company will not accept any liability for penalty clauses of any kind, written or implied,
unless specifically approved in writing by the Company.
20. Nuclear Applications
Unless otherwise agreed to in writing by a duly authorized representative of the Company,
equipment sold hereunder are not intended for use in connection with, any nuclear facility
or activity. The Company disclaims all liability for any nuclear damage, injury or contamination and purchaser shall indemnify the Company against such liability, whether as a result
of breach of contract, warranty, tort (including negligence) or otherwise. The Company shall
identify special controls which are manufactured and tested for use in connection with any
nuclear installation or activity by the appropriate catalog number. The Company will charge
a price addition for control devices sold for nuclear applications. Any questions by purchaser
regarding products or pricing should be referred to the Company for clarification.
21. Government Clauses and Contracts
No government contract regulations or clauses will apply to the equipment agreement or act to
bind the Company unless specifically agreed to by the Company in writing at the Company’s headquarters. Equipment sold or licensed hereunder are not intended to be used, nor should they be
used, in any nuclear-related application either as a ”Basic Component” under 10 CFR 21 (United
States NRC) or otherwise under similar nuclear laws and regulations of this or any other country.
22. Intellectual Property (not applicable to third-party branded products as is)
The Company will defend any suit or proceeding brought against the customer based on a
claim that the design or construction of the Products sold or licensed hereunder by the Company infringe any United States or Canadian Patent, Copyright or Mask Work Registration,
provided that the customer promptly notifies the Company of any such claim and resulting
suit or proceeding, in writing and further provided that, at the Company’s expense, (a) the
customer gives the Company the sole right to defend or control the defense of the suit or
proceeding including settlement, and (b) the customer provides all necessary information
and assistance for that defense. Except for any consequential damages, the Company will
pay all costs and damages finally awarded or agreed upon by Sell that are directly related to
any such claim. In the event of a charge of infringement the Company’s obligation under the
Agreement will be fulfilled if the Company, at its option and expense, either (i) procures for
the customer the right to continue using such Products; (ii) replaces the same with non-infringing Products; (iii) modifies the same so as to make them non-infringing: or (iv) accepts
the return of any infringing Products and refunds their purchase price, Notwithstanding the
foregoing. The Company will have no liability with respect to any claim of infringement to
the extent based on a configuration or modification incorporated in the Products at the request of the customer, on any process application into which the Products are integrated
by the customer, or on use of the Products in combination with other equipment or products not supplied by the Company. THIS PARAGRAPH SETS FORTH THE COMPANY’S ENTIRE
LIABILITY WITH RESPECT TO INTELLECTUAL PROPERTY AN INFRINGEMENT OF PATENTS BY
ANY PRODUCTS (INCLUDING SOFTWARE PROGRAMS, EQUIPMENT OR PRODUCTS THEREOF)
OR BY THEIR OPERATION, AND IS IN LIEU OF ALL WARRANTIES OR CONDITIONS RELATION TO
INFRINGEMENT OR INTELLECTUAL PROPERTY, EITHER EXPRESS OR IMPLIED.
23. Third Party Branded Products
THE COMPANY MAKES NO REPRESENTATIONS AND DISCLAIMS ALL WARRANTIES OF ANY KIND,
EXPRESS OR IMPLIED, RELATIVE TO ANY THIRD-PARTY BRANDED EQUIPMENT WHICH MAY BE
SOLD BY THE COMPANY HEREUNDER. The only warranty associated with such equipment
will be that provided directly by the original manufacturer, if any. The Company assumes no
post-sale technical support or warranty repair obligation with respect to such equipment,
however, at its discretion, the Company may assist the customer in processing warranties or
representations made or provided relative to such equipment, which in all cases will be the
responsibility of the original equipment solely for the convenience of the purchaser, and the
purchaser must make its own determination as to the accuracy and completeness of such
information.
24. Disputes
The parties will attempt in good faith promptly to resolve any dispute arising out of this
transaction by negotiations between representatives who have authority to settle the controversy. If unsuccessful, the parties further will attempt in good faith to settle the dispute
by non-binding third-party mediation, with fees and expenses of such mediation apportioned equally to each side. Any dispute not so resolved by negotiation or mediation may
then be submitted to a court of competent jurisdiction in accordance with the terms of this
transaction. These procedures are the exclusive procedures for the resolution of all such disputes between the parties.
25. Governing Law
This transaction and all disputes arising thereunder will be governed by and interpreted in
accordance with the internal laws of the state, province or other governmental jurisdiction
in which the Company’s principal place of business resides, but specifically excluding its conflict of laws provisions and the provisions of the 1980 UN Convention on Contracts for the
International Sales of Goods.
26. Assignment
This transaction may not be assigned by either party without the written consent of the
other (which consent will not be unreasonably withheld), however, consent will not be required for internal transfers and assignments as between the company and its parent corporations, subsidiaries or affiliates as part of consolidation, merger or other form of corporate
reorganization.
27. Language
The parties acknowledge that they have required that this transaction be drawn up in English, Les parties reconnaissent avoir exigE la rEdaction en anglais du Contrat. In the event of
a conflict between the English and other language versions of this agreement, the English
version will prevail.
104 copperLogic.com
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
CPRO-CAT-1109
www.barr-thorp.com
Conditions of Sale and Shipment
Valid in Canada
Note: The following terms are for general information only. All conditions of sales are subject to change
and are valid as determined in the latest terms and
conditions publication of CopperLogic Ltd. (referred to
herein after as “The Company”).
1. Acceptance of orders:
All orders are subject to final acceptance by an authorized representative of the Company
and are subject to the Company’s terms and conditions in effect at the time of acceptance.
The Company takes exception to any other terms and conditions except for such terms and
conditions as the Company may expressly accept in writing.
2. Prices:
Prices and discounts as shown in the company’s publications are subject to change without
notice. In the event of a net price change, the price of equipment on order but unshipped will
be the price in effect on the date of shipment. In no case will the amount of a price increase
exceed 10% of the price at which the order was accepted, except that, if the delivery is delayed
upon instructions from the purchaser, prices shall be those in effect when the instructions are
received to proceed with the order. Price reductions shall only apply to unshipped portions
of outstanding orders. Any addition or alteration to an outstanding order will be accepted at
prices in effect when the addition or alteration is accepted. Applicable taxes are additional.
3. Quotations:
All quotations are in accordance with the Company’s interpretation of plans and specifications and only material shown on the Company’s quotations are included. Written quotations automatically expire thirty (30) days from the date of issue unless sooner terminated
by notice. Quotations are subject to all existing or future limitations and regulations issued
by any government agency. In the event that a quotation is not accepted in its entirety, the
Company reserves the right to decline any parts of the order based on such quotation.
All Accounting, clerical or other errors are subject to correction.
4. Minimum Billing:
Orders amounting to less than $ 100.00 net will be billed at $ 100.00 plus the transportation
charge, at a minimum of $25.00.
5. Terms - Regular:
Terms to purchasers of satisfactory credit are: 30 days net from the date of invoice. Cash discounts, when applicable, are indicated on the face of the Company’s invoice. To avoid delay
in filling orders purchasers without previous experience with the Company should include
credit references with the first order, or send a certified check or money order. Any amount
owed to the Company becomes due and payable immediately in case of change of ownership of the purchaser, attachment or execution against the purchaser or it’s representatives,
unless the Company otherwise agrees.
6. Payments:
Payments should be made to the address indicated on the invoice, or to CopperLogic Ltd,
6175 Kenway Drive, Mississauga, Ontario, L5T 2L3.
7. Delivery:
The Company reserves the right to make delivery in installments, unless otherwise expressly
stipulated in the contract for sale; and all such installments when separately invoiced shall
be paid for when due per invoice, without regard to subsequent deliveries. Delay in delivery
of any installment shall not relieve the purchaser of its obligations to accept remaining deliveries. Shipments delayed to accommodate the purchaser will be invoiced upon completion
of fabrication and additional charges for warehousing, trucking and other incidental expenses created by the delay will be at the expense of the purchaser. Delivery is dependent upon
prompt receipt of all specifications, final approved prints and any other details essential to
the proper execution of the purchaser’s order. Claims for shortages or other errors must be
reported in writing to the Company within 10 days after receipt of shipment. Failure to do so
will constitute a waiver of all claims by the purchaser.
8. Shipping Terms:
The method and route of shipment is determined by the Company. All merchandise orders
of $500.00 net or more will be shipped F.O.B. CopperLogic’s warehouse, freight prepaid, best
way ground transportation. All engineered equipment orders will be shipped F.O.B. CopperLogic’s loading dock, freight not allowed. When purchaser specifies a method or routing of
shipment other than that selected by the Company, the purchaser will be billed accordingly.
No credits will be allowed in lieu of transportation in the case of pickups at the Company’s
CPRO-CAT-1109
warehouses, branches, or factory. No transportation charges can be deducted from a selling
price. Air freight, water freight, heavy lift charges, pier delivery charges, wharfage, marine
insurance and the cost of stevedoring are chargeable to the purchaser.
9. Packing other than standard:
If other than standard commercial packing is required the cost of such special packing (determinable only after packing is completed) will be charged to the purchaser. Export packing
shall be considered as packing other than standard.
10. Acceptance of orders:
The purchaser will be responsible for any applicable export license and all associated costs
involved with said license on any export project.
11. Export Control
Equipment and associated materials supplied or licensed under this transaction may be subject to various export laws and regulations. It is the responsibility of the purchaser to comply
with all such laws and regulations.
12. Responsibility and Title:
Title in the equipment shall remain with the Company as security only and until full payment is received. Risk of loss for the equipment shall pass to purchaser upon shipment from
F.O.B. point of shipment or date of invoicing, which ever is sooner.
13. Loss or Damage in Transit:
The Company does not hold itself responsible for any loss, damage, (obvious or concealed)
or pilferage sustained in transit. Claims of such character should be made, by the purchaser,
promptly against the transportation company. If the Company is notified of such claims, the
Company will offer to lend assistance to secure adjustment. The Company employs experienced packers and cannot be held responsible for breakage that occurs after the Company’s
securing the “Received in Good Order” receipt from the transportation company.
14. Return of Merchandise:
No equipment may be returned unless authorization has been obtained from an authorized
representative of the Company and if so authorized is subject to the conditions below. Unauthorized returns of equipment cannot be accepted.
A. To be returned for credit:
Only unused equipment of current design may be returned for credit. Where a purchaser returns equipment for reasons of his own, a minimum restocking charge of 20%
of billing, plus transportation charges, will be made. Any cost incurred in putting the
equipment into saleable condition shall also be deducted from allowed credit. If return
of equipment is made necessary by fault of the Company, full credit will be allowed
including transportation charges.
B. To be returned for replacement:
If the equipment is under guarantee and the return is made necessary because of defect in material and/or workmanship, the Company will replace the defective goods “no
charge”, and will assume the transportation charges.
C. Custom-built equipment:
Equipment built based upon purchaser specification cannot be returned for credit.
15. Cancellations:
Any order placed with the Company can be canceled by the purchaser provided that: a) the
cancellation is agreed to in writing by the Company; and b) the purchaser agrees to compensate the Company for engineering, fabrication, outside sourcing of devices and any other
demonstrated expenses incurred or commitments made by the Company up to the date of
notice of cancellation and all charges incurred by the Company in respect of the cancellation.
16. Force Majeure:
The Company shall not be liable for any delay in the performance of orders or contracts or in
the delivery or shipment of equipment or for any loss and/or damages suffered by purchaser
by reason of such delay when such delay is directly or indirectly caused by fire, floods, accidents, riots, acts of God, war, invasion, sabotage, terrorism and governmental interference
or embargoes, strikes, labor difficulties, shortage of labor, fuel, power, materials or supplies
or any other cause beyond the Company’s reasonable control. In any event, the Company
shall not be liable for special or consequential damages for loss of use. Should such a delay
occur, the delivery date shall be extended as may be necessary to compensate for the delay.
The Company shall not be liable for any change of dimensions, weights and materials as long
as the change is nonessential for the proper performance of the product.
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
copperLogic.com
www.barr-thorp.com
105
Conditions of Sale and Shipment
Valid in Canada
17. Guarantee:
The Company guarantees for a period of one (1) year from the date of the Company invoice
that equipment furnished under the order will be of merchantable quality, free from defects
in material, workmanship and design each as determined, at the date of shipment by the
Company by generally recognized, applicable and accepted practices and procedures in the
industry including any specifications furnished by the purchaser and agreed to in writing by
the Company for incorporation into the equipment. Satisfaction of this guarantee, consistent
with other provisions herein, will be limited to the replacement or repair or modification
of, or issuance of a credit for, the equipment involved at the Company’s option, with the
Company to determine the availability of service personnel and purchaser to pay associated
service expenses: such guarantee satisfaction available only if: (a) the Company is promptly
notified in writing upon discovery of an alleged defect and (b) the company’s examination
of the subject equipment discloses, to the Company’s satisfaction, that any defect has not
been caused by misuse, neglect, improper installation, improper operation, improper maintenance, repair or alteration, accident, or unusual deterioration or degradation of the equipment parts, thereof due to physical environment or due to electrical or electromagnetic
noise environment. THIS GUARANTEE IS IN LIEU OF ALL OTHER GUARANTEES WHETHER EXPRESSED, IMPLIED OR STATUTORY, INCLUDING IMPLIED GUARANTEES OF MERCHANTABILITY
OR FITNESS and thereby excludes certifications or the like for equipment performance, use
or design with respect to any standard, regulation or the like (unless and to the extent independently approved in writing by the Company) AND EXTENDS ONLY TO THE CUSTOMER OR
PURCHASER PURCHASING FROM THE COMPANY OR AN AUTHORIZED COMPANY DISTRIBUTOR.
18. Limitation of Liability:
IN NO EVENT WILL THE COMPANY BE LIABLE FOR INCIDENTAL, INDIRECT OR AS IS CONSEQUENTIAL DAMAGES OF ANY KIND. THE COMPANY’S MAXIMUM CUMULATIVE LIABILITY RELATIVE
TO ALL OTHER CLAIMS AND LIABILITIES, INCLUDING THAT WITH RESPECT TO DIRECT DAMAGES
AND OBLIGATIONS UNDER ANY INDEMNITY, WHETHER OR NOT INSURED, WILL NOT EXCEED
THE COST OF THE PRODUCTS GIVING RISE TO THE CLAIM OR LIABILITY. THE COMPANY DISCLAIMS ALL LIABILITY RELATIVE TO GRATUITOUS INFORMATION OR ASSISTANCE PROVIDED
BY, BUT NOT REQUIRED OF THE COMPANY HEREUNDER. ANY ACTION AGAINST THE COMPANY
MUST BE BROUGHT WITHIN EIGHTEEN (18) MONTHS AFTER THE CAUSE OF ACTIONS ACCRUES.
THESE DISCLAIMERS AND LIMITATIONS OF LIABILITY WILL APPLY REGARDLESS OF ANY OTHER
CONTRARY PROVISION OF THE AGREEMENT AND REGARDLESS OF THE FORM OF ACTION,
WHETHER IN CONTRACT, TORT OR OTHERWISE AND FURTHER WILL EXTEND TO THE BENEFIT
OF THE COMPANY’S VENDORS, APPOINTED DISTRIBUTORS AND OTHER AUTHORIZED RESELLERS AS THIRD-PARTY BENEFICIARIES. EACH PROVISION IN THE AGREEMENT WHICH PROVIDES
FOR A LIMITATION OF LIABILITY, DISCLAIMER OF WARRANTY OR CONDITION OR EXCLUSION
OF DAMAGES IS SEVERABLE AND INDEPENDENT OF ANY OTHER PROVISION AND IS TO BE ENFORCED AS SUCH.
19. Penalty Clauses:
The Company will not accept any liability for penalty clauses of any kind, written or implied,
unless specifically approved in writing by the Company.
20. Nuclear Applications:
Unless otherwise agreed to in writing by a duly authorized representative of the Company,
equipment sold hereunder are not intended for use in connection with, any nuclear facility
or activity. The Company disclaims all liability for any nuclear damage, injury or contamination and purchaser shall indemnify the Company against such liability, whether as a result of
breach of contract, warranty, tort (including negligence) or otherwise. Upon authorization
by a representative of the Company for sale or use of equipment in a nuclear facility or activity, the Company shall identify special controls which are manufactured and tested for use in
connection with any nuclear installation or activity by the appropriate catalog number. The
Company will charge a price addition for control devices sold for nuclear applications. Any
questions by purchaser regarding products or pricing should be referred to the Company for
clarification.
21. Government Clauses and Contracts:
No government contract regulations or clauses will apply to the equipment agreement or
act to bind the Company unless specifically agreed to by the Company in writing at the Company’s headquarters. Equipment sold or licensed hereunder are not intended to be used, nor
should they be used, in any nuclear-related application either as a ”Basic Component” under
10 CFR 21 (United States NRC) or otherwise under similar nuclear laws and regulations of
this or any other country.
22. Intellectual Property: (not applicable to third-party branded products as is)
The Company will defend any suit or proceeding brought against the customer based on a
claim that the design or construction of the Products sold or licensed hereunder by the Com-
pany infringe any United States or Canadian Patent, Copyright or Mask Work Registration,
provided that the customer promptly notifies the Company of any such claim and resulting
suit or proceeding, in writing and further provided that, at the Company’s expense, (a) the
customer gives the Company the sole right to defend or control the defense of the suit or
proceeding including settlement, and (b) the customer provides all necessary information
and assistance for that defense. Except for any consequential damages, the Company will
pay all costs and damages finally awarded or agreed upon by the Company that are directly
related to any such claim. In the event of a claim of infringement the Company’s obligation
under the Agreement will be fulfilled if the Company, at its option and expense, either (i)
procures for the customer the right to continue using such Products; (ii) replaces the same
with non-infringing Products; (iii) modifies the same so as to make them non-infringing: or
(iv) accepts the return of any infringing Products and refunds their purchase price, Notwithstanding the foregoing. The Company will have no liability with respect to any claim of infringement to the extent based on a configuration or modification incorporated in the Products at the request of the customer, on any process application into which the Products are
integrated by the customer, or on use of the Products in combination with other equipment
or products not supplied by the Company. THIS PARAGRAPH SETS FORTH THE COMPANY’S ENTIRE LIABILITY WITH RESPECT TO INTELLECTUAL PROPERTY AND INFRINGEMENT OF PATENTS
BY ANY PRODUCTS (INCLUDING SOFTWARE PROGRAMS, EQUIPMENT OR PRODUCTS THEREOF)
OR BY THEIR OPERATION, AND IS IN LIEU OF ALL WARRANTIES OR CONDITIONS RELATION TO
INFRINGEMENT OR INTELLECTUAL PROPERTY, EITHER EXPRESS OR IMPLIED.
23. Third Party Branded Products:
THE COMPANY MAKES NO REPRESENTATIONS AND DISCLAIMS ALL WARRANTIES OF ANY KIND,
EXPRESS OR IMPLIED, RELATIVE TO ANY THIRD-PARTY BRANDED EQUIPMENT WHICH MAY BE
SOLD BY THE COMPANY HEREUNDER. The only warranty associated with such equipment
will be that provided directly by the original manufacturer, if any. The Company assumes no
post-sale technical support or warranty repair obligation with respect to such equipment,
however, at its discretion, the Company may assist the customer in processing warranties or
representations made or provided relative to such equipment, which in all cases will be the
responsibility of the original equipment solely for the convenience of the purchaser, and the
purchaser must make its own determination as to the accuracy and completeness of such
information.
24. Disputes:
The parties will attempt in good faith promptly to resolve any dispute arising out of this
transaction by negotiations between representatives who have authority to settle the controversy. If unsuccessful, the parties further will attempt in good faith to settle the dispute
by non-binding third-party mediation, with fees and expenses of such mediation apportioned equally to each side. Any dispute not so resolved by negotiation or mediation may
then be submitted to a court of competent jurisdiction in accordance with the terms of this
transaction. These procedures are the exclusive procedures for the resolution of all such disputes between the parties.
25. Governing Law:
This transaction and all disputes arising thereunder will be governed by and interpreted
in accordance with the domestic-laws of the Province of Ontario. The provisions of the International Sale of Goods Act, R.S.O. (1990), C.I.10 as amended shall not be applicable to
this transaction and are specifically excluded. At the sole discretion of the Company, for the
purpose of legal proceedings, this transaction shall be deemed to have been performed in
the Province of Ontario and the Courts of the Province of Ontario shall have jurisdiction to
entertain any action arising under this transaction. The purchaser hereby attorns to the jurisdiction of the Courts of the Province of Ontario. However, nothing contained herein shall
derogate from the right of the Company to proceed in such other jurisdiction as, in its sole
discretion, it deems necessary.
26. Assignment:
This transaction may not be assigned by either party without the written consent of the
other (which consent will not be unreasonably withheld), however, consent will not be required for internal transfers and assignments as between the company and its parent corporations, subsidiaries or affiliates as part of consolidation, merger or other form of corporate
reorganization.
27. Language:
The parties acknowledge that they have required that this transaction be drawn up in
English, Les parties reconnaissent avoir exigE la rEdaction en
anglais du Contrat. In the event of a conflict between the English and other language versions of this agreement, the English
version will prevail.
106 copperLogic.com
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
CPRO-CAT-1109
www.barr-thorp.com
cPRO Molded Case Circuit Breakers
Notes
CPRO-CAT-1109
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
copperLogic.com
www.barr-thorp.com
107
cPRO Molded Case Circuit Breakers
Notes
108 copperLogic.com
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
CPRO-CAT-1109
www.barr-thorp.com
cPRO Molded Case Circuit Breakers
Notes
CPRO-CAT-1109
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
copperLogic.com
www.barr-thorp.com
109
cPRO Molded Case Circuit Breakers
Notes
110 copperLogic.com
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
CPRO-CAT-1109
www.barr-thorp.com
cPRO Molded Case Circuit Breakers
Notes
CPRO-CAT-1109
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
copperLogic.com
www.barr-thorp.com
111
cPRO Molded Case Circuit Breakers
Notes
112 copperLogic.com
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
CPRO-CAT-1109
www.barr-thorp.com
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
www.barr-thorp.com
© by CopperLogic
Technical and other changes reserved.
Publication CPRO-CAT-1109
Printed in the USA 11/09
Article No.: 1-030722
US Corporate Headquarters
4140 World Houston Parkway, No 100, Houston, Texas USA 77032
Tel 713.933.0999 | Fax 832.613.6255
Canadian Corporate Headquarters
6175 Kenway Drive, Mississauga, Ontario CANADA L5T 2L3
Tel 905.542.2323 | Fax 905.542.2321