halogen free, low smoke, fire resistant cables 6

advertisement
6
HALOGEN FREE, LOW SMOKE,
FIRE RESISTANT CABLES
COMMON GENERALCHARACTERISTICS
FIRE PERFORMANCES
FIRE RESISTANT
FIRE RETARDANT
IEC 331
BS 6387 Cat. CWZ
UNE 20-431
DIN VDE 0472
Teil 814(180 mm)
IEC 332 Part 3
NF C 32-070 Cat. C1* (test no 2)
+ NF C 2-072
BS 4066 Part 3
NBN C 30-004 Cat. F2
UNE 20-427 + UNE 20-432 (3)
DIN VDE 0472 Teil 804 (C)
CEI 20-22-3
IEEE 383
LOW SMOKE
27 M3 Chambertest
FLAME RETARDANT
IEC 332 Part 1
CENELEC HD 405.1
NF C 32-070 Cat. C2 (test no 1)
BS 4066 Part 1
NBN C 30-004 Cat. F1
UNE 20-432 (1)
DIN VDE 0472 Teil 804 (B)
CEI 20-35
UL44
NON CORROSIVITY- NON TOXICITY
IEC 754 Part 1 + Part 2
CENELEC HD 602 S1
NF C 32-074
NF C 20-902/1 NF C 20-453 + NF C 20-454
IEC 1034
BS 6425 Part 1 + LUL
BS 6401-83
UITP APTATest E4
UNE 21-147 Part 1 + Part 2
CENELEC HD 606 1/2 S1 CEI 20-37
DIN VDE 0472 Teil 813
NF C 32-073
CEI 20-37
BS 7622-93
NBS
chamber Test
UNE 21172 (Draft)
DIN VDE 0472 Teil 816
* NF C 32-070 tests are designed for cables diameters: ≤ 70 mm for no2 test - C1
CORE IDENTIFICATION : According to customer requirements
14
HALOGEN FREE, LOW SMOKE,
FIRE RESISTANT CABLES
Current carrying capacities (A)
(single circuit ratings)
Conductor
Cables in free air
Buried cable
sizes
(mm2)
single core cables(2)
≤ 5 cores cables
≤ 5 cores cables
2(1)
3(1)
2(1)
3(1)
2(1)
3(1)
Voltage drop
cos ϕ = 0.8
(V/Ax km)
2(1)
3(1)
24.8
14.8
9.2
6.2
3.7
2.4
1.6
1.2
-
21.5
12.8
8.0
5.4
3.2
2.1
1.35
1.0
0.75
0.55
0.42
0.35
0.30
0.25
0.21
0.20
0.17
0.15
0.14
Copper
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
(1)
161
200
242
310
377
437
504
575
679
783
940
1083
1254
Number of loaded conductors -
24
33
45
58
80
107
135
169
207
268
328
382
443
509
604
699
839
958
1077
(2)
free air
buried
23
32
42
54
75
100
127
157
192
246
298
346
399
456
538
620
-
37
48
63
80
104
136
173
208
247
304
360
410
463
518
598
677
-
31
41
53
66
87
113
144
174
206
254
301
343
387
434
501
565
-
Trefoil for 3 single core cables
Multicore cables
Instalation
26
36
49
63
86
115
149
185
225
289
352
410
473
542
641
741
-
Current carrying capacities (A)
Numberof cores
C. sizes
(mm2)
7
12
19
24
27
37
1.5
2.5
4
1.5
2.5
4
16
21
28
21
26
34
11
17
22
16
21
28
9
15
8
14
8
14
7
12
14
19
12
17
11
16
10
14
CURRENT RATING GENERAL CONDITIONS
These current data are indicated for continuous duty
operation and apply to :
• Maximum conductor temperature
90oC
• Industrial frequency
50Hz
- Cable in free air (Laying on perforated trays)
• Ambient temperature
30oC
- Directly buried cable :
• Ambient ground temperature
• Soil thermal resistivity
• Laying depth
Voltage drop
cos ϕ = 0.8
(V/Ax km)
21.5
12.8
8.0
21.5
12.8
8.0
Current rating ...data according to :
- IEC 364-5-523 (1983)
- or NF C 15-100 (1991)
- or LIBAN CABLES data
For other laying conditions, see here above
recommandations or standard.
20oC
1 K.m/W
0.7m
15
6
HALOGEN FREE, LOW SMOKE,
FIRE RESISTANT CABLES
6.1 - 0.6 / 1 kv Unarmoured
- Halogen free - Low smoke
- Fire resistant, Fire retardant
ACCORDING TO :
NF C 32-323
IEC 502 (for dimensions)
Maximum conductor
temperature : 90o C
CONSTRUCTION
1 - Conductors
Bare copper :
• solid-class 1 (≤ 4 mm2)
• stranded-class 2 (≥ 6 mm2)
NF C 32-013 / IEC 228
2 - Mica tape
3 - Insulation
Special XLPE
4 - Filler(optional)
5 - Outer sheath
Halogen free compound,
Colour : black
N.B.:
Colours and other constructional details
can be according to customer special
requirements.
Sheath marking
- Name of manufacturer
- Metric marking
- Number of cores / cross sectional area
(mm2)
- Other : as per customer requirements
Fire performances :
See page 18
Electrical data :
See page 19
1
2
3
4
5
INSTALLATION
These cables will be installed according to the wiring regulations and installation
standards in operation.
The use of these cables will be limited to short lenghts when buried in soil non-saturated
with water.
Laying temperature : in case of laying between 0 and -10oC, it is advised to warm up
again the cables in a hot room 48 hours minimum before installation.
16
UNARMOURED, HALOGEN FREE, LOW SMOKE,
FIRE RESISTANT CABLES
Specifications can change according to customer requirements.
Min.
(mm)
Max.
(mm)
Min.
bending
radius
(mm)➀
1 x 1.5
1 x 2.5
1x4
1x6
1 x 10
1 x 16
1 x 25
1 x 35
1 x 50
1 x 70
1 x 95
1 x 120
1 x 150
1 x 185
1 x 240
1 x 300
1 x 400
1 x 500
1 x 630
5.8
6.0
6.6
7.0
8.0
8.7
10.8
11.8
12.9
14.7
16.5
18.0
20.0
22.0
24.5
27.0
30.5
34.0
38.5
6.6
7.0
7.6
8.2
9.2
10.5
12.5
13.5
15.0
17.0
19.0
21.0
23.0
25.5
28.5
31.0
34.5
38.5
43.0
60
65
70
75
80
90
110
120
130
150
170
180
200
220
250
280
310
350
390
70
80
110
120
170
230
340
440
600
820
1 100
1 370
1 670
2 040
2 680
3 500
4 440
6 710
7 190
2 x 1.5
2 x 2.5
2x4
2x6
2 x 10
2 x 16
2 x 25
2 x 35
8.8
10.6
11.5
12.9
14.4
16.5
19.5
21.5
10.5
11.7
12.7
14.1
16.0
18.5
22.0
24.0
65
70
80
85
100
110
130
150
170
210
270
350
480
670
1 000
1 280
3 G 1.5
3 G 2.5
3G4
3G6
3 G 10
3 G 16
3 G 25
9.2
10.0
12.2
13.2
15.0
17.5
21.0
11.0
12.5
13.4
14.6
17.0
19.5
23.5
70
75
80
90
100
120
140
190
240
320
410
590
840
1 250
3 x 1.5
3 x 2.5
3x4
3x6
3 x 10
3 x 16
3 x 25
3 x 35
3 x 50
3 x 70
3 x 95
3 x 120
3 x 150
3 x 185
3 x 240
3 x 300
9.2
10.0
12.2
13.2
15.0
17.5
21.0
23.0
25.5
29.5
33.5
37.0
41.0
45.5
51.5
56.5
11.0
12.5
13.4
14.6
17.0
19.5
23.5
26.0
29.0
34.0
38.5
42.5
47.5
53.0
59.5
66.0
70
75
80
90
100
120
140
160
175
205
230
255
285
320
360
400
190
240
320
410
590
840
1 250
1 640
2 130
2 980
3 960
4 960
6 080
7 480
9 830
12 100
Cables
(mm2)
Outerdiam.
Weight
approx.
(kg/km)
Min.
(mm)
Max.
(mm)
Min.
bending
radius
(mm)➀
3 x 50 + 35
3 x 70 + 50
3 x 95 + 50
3x120+70
3x150+70
3x185+70
3x240+95
27.5
32.0
35.0
39.5
43.0
47.1
53.2
31.1
36.2
40.6
45.4
49.5
54.4
61.5
190
220
245
275
300
330
370
2 530
3 500
4 440
5 690
6 770
8 080
10 700
4G 1.5
4G2
4G4
4G6
4 G 10
4 G 16
4 G 25
9.8
12.1
13.1
14.7
16.5
17.0
23.0
12.0
13.3
14.5
16.0
18.0
21.0
25.5
75
80
90
100
110
130
160
220
290
380
500
720
1 000
1 580
4 x 1.5
4x2
4x4
4x6
4 x 10
4 x 16
4 x 25
4 x 35
4 x 50
4 x 70
4 x 95
4 x 120
4 x 150
4 x 185
4 x 240
4 x 300
9.8
12.1
13.1
14.7
16.5
17.0
23.0
25.5
28.0
33.0
37.0
41.0
45.5
51.0
57.5
63.0
12.0
13.3
14.5
16.0
18.0
21.0
25.5
28.5
32.5
37.5
42.5
47.5
52.5
59.0
66.5
73.5
75
80
90
100
110
130
160
170
195
225
255
285
315
355
400
440
220
290
380
500
720
1 000
1 580
2 050
2 690
3 780
5 060
6 310
7 770
9 550
12 600
15 500
5 G 1.5
5 G 2.5
5G4
5G6
5 G 10
5 G 16
5 G 25
10.5
11.5
14.0
14.0
18.0
18.5
25.5
13.0
14.5
16.0
17.5
20.0
23.0
28.0
80
90
100
110
120
140
170
270
340
450
590
860
1 230
1 900
7 G 1.5
7 G 2.5
7G4
13.0
14.1
15.5
14.2
15.5
17.0
85
95
100
330
430
570
12 G 1.5
12 G 2.5
12 G 4
16.5
18.0
20.0
18.5
20.0
22.0
110
120
130
540
720
970
19 G 1.5
19 G 2.5
19 G 4
19.0
21.0
23.5
21.5
23.5
26.0
130
140
160
750
1 010
1 410
37 G 1.5
37 G 2.5
25.5
28.0
28.5
31.0
170
190
1 370
1 870
Cables
(mm2)
Outerdiam.
Weight
approx.
(kg/km)
G = with green / yellow core
➀ Values to be doubled during laying operations
• Other sizes are also available
17
Download