TX6™ 10GIG™ Shielded Cable - U/FTP

TX6 ™ 10GIG ™ Shielded Cable – U/FTP
®
SPECIFICATION SHEET
specifications
Augmented Category 6 Shielded Copper Cable
shall be constructed of 4-pair twisted insulated
23 AWG conductors. Each individual pair shall
have a metallic foil shield and all four pairs shall
be covered with a flame retardant PVC jacket.
The shielded cable shall provide superior alien
cross-talk performance. The TX6 ™ 10GIG™ Shielded
Cable must be installed as part of the TX6 ™ 10GIG™
Shielded Copper Cabling System to achieve
certified 10GBASE-T performance.
TX6 ™ 10GIG™
Shielded Copper Cabling System
TX6 ™ 10GIG™
Shielded Cable – U/FTP*
Plenum:
Riser:
technical information
Augmented
Category 6/ISO 11801
Class EA Edition 2.1:
Certified channel performance in a 4-connector configuration up to
100 meters and exceeds the draft requirements of
TIA/EIA 568-B.2-AD10, ISO 11801 Class EA Edition 2.1 and IEEE
802.3an-2006 ratified standard for supporting 10GBASE-T
transmission over copper twisted pair cabling when used as part of
the PANDUIT ® TX6 ™ 10GIG™ Shielded Copper Cabling System
PSP6004BU-UG
PSR6004BU-UGY
TX6 ™ 10GIG™
Shielded Jack Module
Module:
™
CJS6X88TGY
™
TX6 10GIG
Shielded Patch Cords**
1 meters:
2 meters:
3 meters:
5 meters:
7 meters:
10 meters:
STP6X1MIG
STP6X2MIG
STP6X3MIG
STP6X5MIG
STP6X7MIG
STP6X10MIG
Category 6/Class E
performance:
Exceeds all Category 6/Class E component and channel
standard requirements
Cable jacket:
Riser and Plenum: 100% low-smoke, flame retardant PVC
Flame rating:
Plenum: meets NEC type CMP (UL) – FT6 rated
Riser:
meets NEC type CMR (UL) – FT4 rated
Installation tension:
25 lbs. (110 N) maximum
Temperature rating:
32° to 140°F (0° to 60°C) during installation
14° to 140°F (-10° to 60°C) during operation
24-port, 1 RU:
48-port, 2 RU:
72-port, 2 RU:
Cable outer diameter:
Plenum: 0.29'' (7.36mm)
Riser:
0.31'' (7.87mm)
MINI-COM ® Angled All Metal
Shielded Modular Patch Panels
Packaging:
1,000' (305M) per reel
CMR – 50 lbs. (22.6kg), CMP – 45 lbs. (20.4kg)
24-port, 1 RU:
48-port, 2 RU:
72-port, 2 RU:
key features and benefits
Individual screened pairs
Exceptional suppression of internal and external (Alien)
cross-talk which exceed IEEE 802.3an-2006 specifications
and EMI protection
Internal drain wire
Facilitates means of grounding the cable and provides for
efficient performance and protection of network investment
“Descending length”
cable markings
Easy identification of remaining cable reduces installation
time and scrap
applications
TX6 ™ 10GIG™ Shielded Cable is a component
of the TX6 ™ 10GIG™ Shielded Copper Cabling
System. This end-to-end system provides
a cost-effective medium for ensuring that
network bandwidth needs are easily met today
and tomorrow. This shielded cabling system
provides high performance, excellent EMI
suppression, and aids in secure data
transmission. The PANDUIT solution helps
ensure organizations efficiently and reliably
meet their data transmission needs.
w w w. p a n d u i t . c o m
MINI-COM ® Flat All Metal
Shielded Modular Patch Panels
CP24BL
CP48BL
CP72BL
CPA24BL
CPA48BL
CPA72BL
Termination Tools
Jack module
termination
tool:***
Wire
snipping tool:
Wire
stripping tool:
Panel
punchdown
tool:
EGJT
CWST
CJAST
PDT110
*For colors other than BU (Blue), substitute
with WH (White).
Usage of the TX6 ™ 10GIG™ Shielded Copper
Cabling System includes high bandwidth
applications within data centers and
connections to high-end workstations such as:
• Stacking switches and switch-to-switch links
• Storage area networks
• Aggregation of Gigabit Ethernet channels
• Real-time intensive financial transactions
• Streaming video
• Animation
• Scientific modeling
• Medical imaging
**For lengths 1 – 10 meters (increments of 1
meter) and 10 – 40 meters (increments of 5
meters) change the length designation in the
part number to the desired length. For standard
cable colors other than IG (International Gray),
substitute suffix with BL (Black), BU (Blue),
GR (Green), RD (Red), YL (yellow),
OR (Orange) or VL (Violet). For example, the
part number for a blue 15 meter cord is
STP6X15MBU.
***Terminates enhanced GIGA-TX ™ Style
Jack Modules.
Contact customer service for additional colors
and lengths requiring minimum order quantities.
TX6 ™ 10G IG ™ Shielded Cable – U/FTP
Additional TIA/EIA 568-B.2 Cable Specifications
Mechanical Test
Ultimate Breaking Strength
Minimum Bend Radius
> 400 N (90 lb. – ft.)
31.48mm (1.24 in.)
Electrical Test
DC Resistance
< 8.9 Ohm per 100m (328 ft.) @ 20°C
DC Resistance Unbalanced
< 3% @ 20°C per ASTM 4568
100 Ohms + 15% from 1 to 600 MHz per ASTM D 4566
Characteristic Impedance
Nominal Propagation of Velocity (NVP)
CMP: 78%, CMR: 75%
Cable Construction
Copper Conductor
Individual Foil Shield
Outer Jacket
Drain Wire
TX6 ™ 10GIG™ Shielded Copper Cabling System
PSANEXT 100 Meter Channel
Power Sum Alien NEXT (db)
-30
-40
-50
-60
-70
-80
-90
0
100
200
300
400
500
600
Frequency (MHz)
Pair 45
Pair 12
Pair 36
Pair 78
TIA Limit
WORLDWIDE SUBSIDIARIES AND SALES OFFICES
PANDUIT CANADA
Markham, Ontario
cs-cdn@panduit.com
Phone: 800.777.3300
PANDUIT EUROPE LTD.
London, UK
cs-emea@panduit.com
Phone: 44.20.8601.7200
PANDUIT SINGAPORE PTE. LTD.
Republic of Singapore
cs-ap@panduit.com
Phone: 65.6379.6700
PANDUIT JAPAN
Tokyo, Japan
cs-japan@panduit.com
Phone: 81.3.3767.7011
PANDUIT LATIN AMERICA
Jalisco, Mexico
cs-la@panduit.com
Phone: 52.333.777.6000
PANDUIT AUSTRALIA PTY. LTD.
Victoria, Australia
cs-aus@panduit.com
Phone: 61.3.9794.9020
For a copy of PANDUIT product warranties, log on to www.panduit.com/warranty
For more information
Visit us at www.panduit.com
Contact Customer Service by email: cs@panduit.com
or by phone: 800-777-3300 and reference COSP55
©2006 PANDUIT Corp.
ALL RIGHTS RESERVED.
Printed in the U.S.A.
WW-COSP55
8/2006