TEDAŞ-MYD/95-012.C TURKISH ELECTRICITY DISTRIBUTION CO. MATERIAL MANAGEMENT DEPARTMENT TECHNICAL SPECIFICATION FOR MV / LV DISTRIBUTION POWER TRANSFORMERS (WITH OIL CONSERVATOR, EXPOSED TO AIR) CONSULTANT ELTEM-TEK ELECTRICAL INSTALLATIONS ENGINEERING SERVICES AND TRADE CO. DECEMBER – 1995 MARCH – 1999 (REVISED) FEBRUARY – 2003 (REVISED) JANUARY – 2005 (REVISED) TEDAŞ-MYD/95-012.C TECHNICAL SPECIFICATION FOR MV / LV DISTRIBUTION POWER TRANSFORMERS (WITH OIL CONSERVATOR, EXPOSED TO AIR) CONSENTS 1. 2. GENERAL 1.1. Scope 1.2. Standards 1.3. Service Conditions CHARACTERISTICS 2.1. Type 2.2. Electrical Characteristics 2.2.1. Rated Frequency : 50 Hz 2.2.2. Rated Powers : 50-100-160-250-400-630-1000-1250-1600 kVA 2.2.3. Highest System Voltages (primary) : 7,2-12-17,5-36 kV 2.2.4. Rated Voltages 2.2.5. Off-Load Voltage Adjustment 2.2.6. Tapping Powers 2.2.7. Temperature Rise 2.2.8. Connection Symbol 2.2.9. Impedance Voltages 2.2.10. Short Circuit Thermal Withstand 2.2.11. Rated Insulation Levels 2.2.12. Sound Power Levels (LWA) 2.2.13. Losses 2.2.14. Operation (Loading) Mode 2.2.15. Operation Under Overvoltage Conditions 2.2.16. Temporary Overloading 2.2.17. Tolerances 2.3. Constructional Characteristics 2.3.1. Magnetic Circuit 2.3.2. Windings 2.3.3. Insulation 2.3.4. Oil Filling 2.3.5. Tap-Changer 2.3.6. Tank and Cover 2.3.7. Cooling Equipment 2.3.8. Oil-Conservator i TEDAŞ-MYD/95-012.C 3. 4. 2.3.9. Bushings and Terminals 2.3.10. Cable Box 2.3.11. Protection and Signalling Equipment 2.3.12. Insulating Oil 2.3.13. Arrangement of the Top Cover and Dimensions 2.3.14. Dimensions 2.3.15. Nameplate 2.3.16. Anticorrosion Precautions TESTS 3.1. Type Tests 3.2. Routine Tests ACCEPTANCE TESTS AND PROVISIONS 4.1. Sampling 4.2. Acceptance Tests 4.3. Acceptance Criteria 4.4. General Provisions for Acceptance Tests 5. DOCUMENTS TO BE SUBMITTED WITH THE BID 6. MISCELLANEOUS CONDITIONS 6.1. Bid Prices 6.2. Special Tools 6.3. Packing 6.4. Documents to be Submitted for Approval 6.5. Documents to be Submitted with the Transformers 6.6. Inspections and Tests Outside the Acceptance Tests 6.7. Warranty APPENDICES APP – I List Of Materials APP – II Schedule Of Guaranteed Characteristics APP – III Drawings (2 pieces) APP – IV Technical Specifications for Insulating Oils (2 pieces) ii TEDAŞ-MYD/95-012.C TECHNICAL SPECIFICATION FOR MV / LV DISTRIBUTION POWER TRANSFORMERS (WITH OIL CONSERVATOR, EXPOSED TO AIR) 1. GENERAL 1.1. Scope This specification covers the technical characteristics of MV/LV power transformers to be purchased for use in medium voltage distribution networks with rated voltages up to 36 kV and rated power from 50 kVA up to 1600 kVA. Unless otherwise specified in this specification and its enclosures, the transformers shall be supplied with all accessories mentioned in the specification as a complete unit filled with insulating oil. The types and the technical characteristics of the transformers to be purchased have been given in the Bill of Materials and/or Schedule of Guaranteed Characteristics. 1.2. Standards Unless otherwise specified in this specification and its enclosures, transformers shall be manufactured and tested in accordance with the latest editions of the following Turkish Standards (TS), European Standards (GENELEC) and International Electrotechnical Commission (IEC) standards. Standard No (TSE) TS 267 EN 60076-1 Standard No (GENELEC, IEC and Others) Name of Standard Power Transformers IEC 60076-1 TS 10901 EN 60076-2 IEC 60076-2 TS 10902 EN 60076-3 IEC 60076-3 Power Transformers-Part3: Insulation Levels and dielectric tests TS 10903 IEC 60076-4 Power Tranfsormers-Part4: Tappings and Connections IEC 60076-5 Power Transformers-Part5: Ability to Withstand Short circuit TS HD 428.1 S1 GENELEC HD 428.1 S1 Three-phase oil-immersed distribution transformers for rated voltages up to 24 kV TS HD 428.3 S1 GENELEC HD 428.3 S1 Three-phase oil-immersed distribution transformers for rated voltages up to 36 kV TS 8711 IEC 60551 Determination of transformer and reactor sound levels TS 3215 IEC 60354 Loading guide for oil-immersed power transformers TS 10904 EN 60076-5 Power Transformers-Part2: Temperature rise TEDAŞ-MYD/95-012.C Standard No (TSE) Standard No (GENELEC, IEC and Others) TS EN 50180 TS EN 50386 BS EN 50386 TS HD 428.2.1. S1 TS HD 428.2.2.S1 TS HD 428.2.3.S1 TS EN 60641-1+A1 IEC 60641-1-AM1 TS EN 60641-2 IEC 60641-2 Name of Standard Bushings-for equipment other than oil-immersed transformers. Voltage: 1 kV – 36 kV (including) and Current: 250 A-31.5 kA (including) Bushings for oil-immersed transformers. Up to 1 kV and from 250 A up to 5 kA 50 Hz, three-phase oil-immersed distribution transformers from 50 kVA up to 2500 kVA, for equipment whose highest voltage do not exceed 36 kV. Part2: Distribution transformers with cable boxes on their High Voltage and/or Low Voltage side. Section: 1 General Characteristics 50 Hz, three-phase oil-immersed distribution transformers from 50 kVA up to 2500 kVA, for equipment whose highest voltage do not exceed 36 kV. Part 2: Distribution transformers with cable boxes on their High Voltage and/or Low Voltage side. Section 2: Type: 1 distribution boxes used in distribution transformers meeting the characteristics in HD.428.2.1.S1 50 Hz, three-phase oil-immersed distribution transformers from 50 kVA up to 2500 kVA, for equipment whose highest voltage do not exceed 36 kV. Part 2: Distribution transformers with cable boxes on their High Voltage and/or Low Voltage side. Section 2: Type: 2 distribution boxes used in distribution transformers meeting the characteristics in HD.428.2.1.S1 Characteristics for Pressboard and Pressed Paper used for electrical purposes-Part 1: Definitions and General Provisions. Characteristics Required for Pressboard and Pressed Cardboard used for electrical purposes Part 2: Test Methods. 1.3. Service Conditions Transformer shall be suitable for operation under following conditions: Location use Indoor Outdoor Altitude Up to 1000 m Ambient Temperature - Minimum ......................................... - Maximum ........................................ - Average over 24 hours.................... - 25 0C + 40 0C below + 350C Exposure to earthquakes - Horizontal acceleration.................... - Vertical acceleration........................ 0.5 g 0.4 g The following Special Service Conditions shall be valid if specified in the Bill of Materials: 2 TEDAŞ-MYD/95-012.C Altitude * - up to 2000 m - up to 3000 m Ambient Temperature ** - 400C + 50 0C - Minimum ......................................... - Maximum ........................................ * : It shall be specified by the PURCHASER in the BILL of MATERIALS ** : For +500C ambient temperature, Winding Temperature Rise shall be 55 0K and Top Oil Temperature Rise 50 0K. 2. CHARACTERISTICS Power transformers, in the scope of this specification, shall be used in the distribution networks as voltage step-down transformers or auxiliary service transformers and shall have the following characteristics, unless otherwise specified in the Bill of Materials. 2.1. Type - Three phase, two windings - Oil-immersed (mineral oil), with oil conservator, exposed to air - Natural oil circulation and natural air cooling (ONAN) - Off-Load tap adjustment for voltage settings - Suitable for Outdoor or Indoor uses 2.2. Electrical Characteristics 2.2.1. Rated Frequency : 50 Hz 2.2.2. Rated Powers : 50-100-160-250-400-630-800-1000-1250-1600 kVA 2.2.3. Highest System Voltages (primary) : 7,2-12-17,5-36 kV (Secondary) : 1,1 kV 2.2.4. Rated Voltages • HV Winding (Main tapping) : 6.3-10.5-15.8-33 kV • LV Winding : 400/231 V 3 TEDAŞ-MYD/95-012.C 2.2.5. Off-Load Voltage Adjustment • Tapping Winding : On the HV side • Voltage adjustment range : Constant flux (TS-SAA; IEC-CFVV) • Tapping (adjustment) class 6.3-10.5-15.8 kV 33 kV • Tapping (adjustment) class : ± 2 x 2.5 % 28.5-30-31.5-33-34.5 kV • Number of taps : • Off-Load tap ratio : HV±2x2,5%/0.4 kV 28.5-30-31.5-33-34.5/0.4 kV 5 5 NOTE: Values written in bold letters are the main taps. 2.2.6. Tapping Powers • 6.3-10.5-15.8 kV transformers : Equal to the rated power for all taps • 33 kV transformers : Equal to the rated power between 30 kV and 34.5 kV 2.2.7. Temperature Rise • For windings : 65 K • For highest oil level : 60 K 2.2.8. Connection Symbol Up to 160 kVA (including 160 kVA) Yzn 11 250 kVA and up Dyn 11 2.2.9. Impedance Voltages (at 75 0C, and main tap) Impedance Voltage Uk (%) Transformer power (kVA) 6.3-10.5-15.8 kV 33 kV Up to 630 kVA (including 630 kVA) 4 4.5 Above 630 kVA 6 6 2.2.10. Short Circuit Thermal Withstand Transformer Power (kVA) Short Circuit Duration Up to 630 kVA (including 630 kVA) 2 seconds Above 630 kVA 3 second 4 TEDAŞ-MYD/95-012.C 2.2.11. Rated Insulation Levels HV winding: Rated voltage Impulse withstand voltage (kV-peak) (1.2 - 50µs) One-minute power-frequency withstand voltage (kV-rms) 6.3 kV 60 10.5 kV 75 15.8 kV 95 33 kV 170 20 28 38 70 LV winding: One-minute power-frequency withstand voltage (kV-rms) ………………: 3 kV 2.2.12. Sound Power Levels (LWA) Transformer power (kVA) 50 100 160 250 400 630 800 100 125 160 0 0 0 6.3-10.5-15.8 kV 55 59 62 65 68 70 72 73 74 76 33 kV 52 56 59 62 65 67 68 68 69 71 NOTE: The values in the Table are the highest values. Tolerance shall not be applied. 2.2.13. Losses Rate voltage (kV) Up to 15.8 kV 33 kV Rated Power (kVA) 50 100 160 250 400 630 800 1000 1250 1600 50 100 160 250 400 630 800 1000 1250 1600 No-Load Losses Pb (W) 190 320 460 650 930 1300 1500 1700 2100 2600 230 380 520 780 1120 1450 1750 2000 2250 2800 Load Losses Py (W) 1100 1750 2350 3250 4600 6500 8500 10500 13000 17000 1250 1950 2550 3500 4900 6650 8700 10500 13000 17000 NOTE: The values in the Table are the highest values. Tolerance shall not be applied. 5 TEDAŞ-MYD/95-012.C 2.2.14. Operation (Loading) Mode Transformers shall be suitable for continuous operation under 100 % unbalanced loading. 2.2.15. Operation Under Overvoltage Conditions Transformers shall be suitable for continuous operation under the following overvoltage conditions; • At 105% of rated voltage and at rated current • At 110% of rated voltage at no-load Note: The slight temperature rise increase which would correspond to the 5% overvoltage, due to higher no-load loss, is disregarded. 2.2.16. Temporary Overloading Shall be in accordance with TS 3215/IEC 60354 standards. 2.2.17. Tolerances Each transformer in the scope of the order, shall be considered as complying with this specification when the guaranteed characteristics are found within the following tolerances. Voltage ratios at no-load (at the main tap) : ± 0.5% Impedance voltage (At rated current) : ± 10% No-load current : + 30% Losses : + 0% 2.3. Constructional Characteristics 2.3.1. Magnetic Circuit The core shall be manufactured of high-grade silicone-steel laminations with low losses. 2.3.2. Windings Windings and winding connections shall be designed and manufactured in a way that they shall withstand thermal and dynamic stresses due to short circuits at transformer terminals, and insulation withstand tests, specified in the specification without any damage. Windings shall be dried out under vacuum. 2.3.3. Insulation 6 TEDAŞ-MYD/95-012.C 1 For insulation of the windings, high grade insulation materials of at least Class-A material shall be used. Neutral ends and line ends of the same LV windings shall have the same insulation level. 2.3.4. Oil Filling The oil-filling of transformers shall be made under vacuum. 2.3.5. Tap-Changer Each transformer shall be supplied with off-load tap-changers mounted at the HV winding. The construction of regulation windings and tap-changers shall be strong enough to withstand against high voltage impulses, overload and short-circuit currents without any damage. Tap-changing operation shall be performed by means of a control mechanism mounted on the top cover of the tank. Control mechanism shall be marked such that the tap position 1 shall indicate the minimum number of turns of the windings. For each of the tap positions tap indicator shall have a stop slot. 2.3.6. Tank and Cover Tank and cover shall be fabricated of high grade steel plates with high durability and best workmanship. Tank base shall have a chassis which will carry all the weight of the transformer on four wheels. All the bolts and nuts on the tank shall be made of stainless or galvanized steel. Welding shall be carried out in accordance with strict standards, with double weld provided where tightness is required. All oil-tight welds shall be tested to ensure that no oil leakage will occur. All the gaskets for leakage prevention shall be manufactured by using materials resistant to insulating oil and suitable for use within operation temperature range of the transformer, and shall not deteriorate the characteristics of the insulating oil2 Metal continuity shall be ensured between the parts forming the tank and the various pipes etc. so that they will all be at the same potential. The tank shall be equipped with the following arrangements and equipment: - Two lifting rings, to lift the transformer safely and to pull out the core and windings together with the cover from the tank, 1 The highest permissable temperature for the insulating material Class A is 105 C (FOR INFORMATION) o 2 Sample gasket material: Neopren, Nitrile. (All responsibility in the choice of gasket, shall belong to Manufacturing firm) 7 TEDAŞ-MYD/95-012.C - Four wheels, which are lockable and orientable in two perpendicular directions (the transformers having the rated power 250 kVA or less, shall be designed for wheel mounting, but the wheels shall not be delivered for these transformers). - An oil sampling and oil drain valve located at 2-3 cm above the tank base (in conformity with DIN 42551, at the same level as the winding base, sealed), - Thermometer pocket (for transformers having rated power 400 kVA or less and in conformity with DIN 42554), - Two earthing terminals (in conformity with DIN 48088-B) Two M12 size bolted type, earthing terminals from stainless steel shall be provided, one of which shall be on the cover and the other on the side surface, at the base. The bolts, shall be equipped with nut, washer and spring-washers, made also from stainless steel. Earthing terminals shall be marked with earth symbols. 2.3.7. Cooling Equipment Sheet thickness of the fixed flat or corrugated-wall type radiators to be used in the natural cooling of the transformers, shall not be less than 1.2 mm. 2.3.8. Oil-Conservator Each transformer shall be equipped with an oil-conservator of suitable capacity and the oilconservator shall include following arrangements: - Oil precipitation arrangement Oil drain tap Oil filling tap (according to DIN 42533) Magnetic oil level indicator (according to DIN 42569) Connection flange for air dryer (for 250 kVA and larger units) For 630 kVA and larger units, an arrangement for mounting of Buchholz relay on the pipe connecting the conservator to the tank. 2.3.9. Bushings and Terminals The HV line & LV windings and LV neutral ends shall be taken out through ceramic bushings, having the same insulation level with the relevant windings. 2.3.9.1 HV Bushings and Terminals • HV bushings and terminals shall comply with TS EN 50180 standard, be Open Type or 8 TEDAŞ-MYD/95-012.C Outside Cone-Plug-in Type as indicated in the Bill of Materials. In case any specific type is not specified in the Bill of Materials, Open Type Bushings shall be used. • Bushings’ rated current shall be 250 A. • Insulating material of Open Type HV Bushings shall be ceramic and insulating material of Plug-in Type HV Bushings shall be epoxy resin. • Minimum Rated Specific Creepage Distance for Open Type HV Bushings shall be chosen by the PURCHASER according to the following Table and specified in the Bill of Materials. Pollution Level of the Medium (According to IEC 60815) Surface I (Slightly polluted) Rated Distance Specific Creepage 16 mm / kV Surface II (Moderately polluted) 20 mm / kV Surface III (Heavily polluted) 25 mm / kV In case any alternative is not indicated in the Bill of Materials, Rated Specific Creepage Distance shall be selected as 20 mm/kV. NOTE: Outside Cone-Plug-in Bushings shall be used with detachable full-insulated cable terminals (sealing ends). Unless otherwise specified in the Bill of Materials, Detachable Cable Sealing Ends shall be supplied by the PURCHASER. 2.3.9.2 LV Bushings and Terminals LV Bushings and Terminals shall comply with TS EN 50386 standards, shall be open type and shall have ceramic insulating material. The number, rated current and rated voltage of the bushings to be used according to the powers of the distribution transformers, are given below: Transformer Rated Power kVA Bushings Rated Current (Amper) 250 Number Rated Voltage (kV) 1 50 – 100 – 160 4 250 – 400 4 630 1 630 – 800 4 1250 1 1000 – 1250 4 2000 1 1600 4 3150 1 NOTE: Connectors to be used for connection of cables or flat busbar conductors to the LV terminals shall be supplied with 630 kVA or larger transformers. 9 TEDAŞ-MYD/95-012.C 2.3.10. Cable Box In case it is specified in the Bill of Materials, in order to prevent an accidental touch to the parts under voltage, a metallic and/or non-metallic protective enclosure (Cable Box) shall be provided in the HV or LV connection end arrangements of the transformer. Construction of Protective Enclosure (Cable Box) shall comply with TS HD 428.2.3.S1. NOTE: In case Plug-in Type, Outside Cone Type bushings are used on the HV side of indoor type distribution transformers, no Cable Box shall be required on their HV side. 2.3.11. Protection and Signalling Equipment Following protection and signaling equipment for transformers shall be supplied unless otherwise specified in the Bill of Materials: - Air dryer, (For units with 250 kVA and higher capacity, in compliance with DIN 42567), - Buchholz relay, (two-stage), (For units with 630 kVA and higher capacity, in compliance with DIN 42566), - Double-scaled, double-contact bimetal thermometer (For units having 630 kVA and higher capacity, in compliance with DIN 16160), - Clemens box (for units with 630 kVA and higher capacity. Enclosure of the clemens box may be of a metallic or insulating material and have a Protection Level of at least IP 44. Should it be of insulating material, the material to be used shall be flame-resistant). 2.3.12. Insulating Oil Transformers shall be delivered with their oil filled-in. Oil used for filling transformers shall be new and free of humidity and with a characteristics which will not cause precipitation. Unless otherwise specified in the Bill of Materials or Bidding Documents, the insulating oil shall comply with the enclosed Transformer Oil Specifications. Should the PURCHASER deems necessary, may cause the oil sample he will take from a manufactured transformer outside the Acceptance Tests, according to the relevant oil specifications. The results of the test shall be binding for the CONTRACTOR. The type and brand of insulating oil used shall be indicated in the routine test reports and as well as on the nameplates of all the transformers within the scope of the order. 2.3.13. Arrangement of the Top Cover and Dimensions Arrangement of HV and LV bushings on the top cover, marking of the connection terminals, location of the oil conservator as well as distances between wheels’ axis shall be according to the drawings given in APP.III. 10 TEDAŞ-MYD/95-012.C Marking of low voltage, high voltage and external neutral terminals of the transformer shall be carried out on the tank cover. Marking shall be durable (for instance: marking by punch, etc.), easily visible and legible. Painting, label-sticking or similar marking procedures shall not be accepted. Marking shall be carried out as follows: MARKING ON THE COVER High Voltage Low Voltage For connection conductor L1 1U 2U For connection conductor L2 1V 2V For connection conductor L3 1W 2W - 2N For neutral connection conductor 2.3.14. Dimensions The maximum external dimensions of transformers including the oil conservator and the wheels shall not be greater than those given in the table below. Dimensions (Maximum) of MV/LV Power Transformers Up to 630 800-1000 1250 1600 400 kVA kVA kVA kVA kVA Width (mm) 1100 1200 1300 1500 1850 Length (mm) 1700 1700 2100 2100 2100 Height (mm) 1950 1950 2250 2300 2450 NOTE: Cable Box is not included in the dimensions 2.3.15. Nameplate Each transformer shall have an easily visible nameplate made of stainless steel or other noncorroding metal. The nameplate shall be fixed on the transformer with stainless steel screws or rivets and the lettering shall be legible and durable. In addition to the information given in TS 267/EN 60076-1, following information shall be included on the nameplate. - Purchaser’s name and order number Year and month of manufacture Type and brand of insulating oil No-load losses and load losses Numbers of tapping positions and the corresponding voltages (V and/or kV) 11 TEDAŞ-MYD/95-012.C - Insulation measurement results Purchaser’s material code number Each transformer shall bear the Purchase’s symbol and/or name with letters of 25 mm height on two opposite sides of the transformer or on the oil conservator. 2.3.16. Anticorrosion Precautions 2.3.16.1 General Metal parts of the transformers shall be manufactured with corrosion resistant materials and be finished in such a way that corrosion is minimized. The following precautions shall be taken against corrosion: Current-carrying parts shall be made from non-ferrous metals All surfaces shall be self-draining Materials and combination of materials used in the construction of the equipment shall be selected and arranged in a way to prevent galvanic corrosion; Aluminium alloys used for current carrying or structural purposes, shall be resistant to corrosion, Ferrous parts shall be either hot-dip galvanized or painted, Surfaces to be galvanized or painted shall be sound, clean and free from any foreign materials which will in any way reduce the life and functioning of the coating. 2.3.16.2 Painting All the externally exposed surfaces such as tank, radiator, oil-conservator etc. and all parts of the transformers manufactured by using corroding metals, unless otherwise specified in the Bill of Materials, shall be painted. In case the internal surfaces of the tank are painted or coated with varnish, the paint or varnish to be used shall have rust-inhibiting characteristics and shall not be affected from the maximum temperature (at least 105 0C) reachable by the insulating oil. For the painting of exterior surfaces following procedure shall be adopted: Prior to painting, all surfaces shall be subjected to complete cleaning process according to methods given in painting standards (such as sandblasting or chemical cleaning, etc.) Coating with zinc by hot dipping.(If requested at the Bill of Materials) Catalyzed epoxy paints with anti-corrosion pigments shall be used for primary-coating.(In case of a request by coating with zinc, the primer paint shall be chosen by the firm.) 12 TEDAŞ-MYD/95-012.C Any paint, for intermediate coats, may be selected by the Manufacturer. One of the following types of paints having color code RAL 7033; - Polyurethane paints; - Alkyd and silicone-based paints; - Modified vinyl paints; shall be used as finishing coat. The minimum thickness of each coat shall be 35 microns. Painting of the transformers shall be completed before the routine tests. The thickness of the film at five points, chosen at random on the painted surface, shall be measured by employing a paint inspection gauge. The mean of the values measured shall not be less than 105 microns. The quality of painting shall be determined by checking the thickness and adhesion of coating. The film adhesion shall be verified by the adhesive tape test according to TS 4313/ASTM D 3359. The degree of adhesion shall not be worse than Class-1 mentioned in these standards. 2.3.16.3 Galvanizing Galvanizing and tests on galvanized surfaces shall be carried out in accordance with TS 914 “Galvanizing (with the hot-dip method)”. 3. TESTS Unless otherwise specified, the tests shall be carried out according to relevant standards, on completely assembled and oil filled transformers. 3.1. Type Tests Full wave impulse test, Temperature rise (heating) test, The test shall be performed for 33/0.4 kV transformers at the 30 kV tapping; and for 6.310.5-15.8/0.4 kV transformers at the lowest tapping, with the corresponding load losses taken into account. Measurement of sound power level, Dynamic ability to withstand short-circuit test (DAWSCT), Unless any design difference 13 TEDAŞ-MYD/95-012.C exists, distribution transformers are grouped with respect to DAWSCT as follows: Rated Voltage (kV) 6.3-10.5-15.8 33 50 – 160 50 – 160 250 – 630 250 – 630 800 – 2500 800 - 2500 Transformer Rated Power (kVA) Checking of quality of painting (According to Clause 2.3.16.2 of this specification) 3.2. Routine Tests Following routine tests shall be carried out by the Manufacturer on all of the fully manufactured transformers in the scope of this specification: Measurement of winding resistance, Measurement of voltage (turn) ratio and check of voltage group symbol, Measurement of impedance voltage (short circuit impedance) and load losses, Measurement of no-load loss and current, Applied voltage test, Induced voltage test, Measurement of insulation resistance, The measurement shall be carried out between windings and between each winding and tank at 0,15,30,45 and 60 seconds, by 2500 V or 5000 V insulation tester on oil filled transformers and the results shall be corrected to 20 0C. The measurement results at 60 seconds shall be indicated on the nameplate of the transformer. Measurement of loss angle tangent For transformers with rated power of 630 kVA or higher, the loss angle tangent or power factor (tan δ or Cos∅) between windings and between each winding and the tank shall be measured by a Schering bridge or Doble instrument and the results shall be corrected to 20 0C. Oil Leakage Tightness Test, (to test oil leakage and oil tightness) Measurement of paint thickness (According to Clause 2.3.16.2 of this specification) 14 TEDAŞ-MYD/95-012.C 4. ACCEPTANCE TESTS AND PROVISIONS 4.1. Sampling The transformers which are submitted for inspection and testing at one time and having the same design and type, shall be considered a party. The samples shall be selected at random by the PURCHASER’s representative / representatives. The number of samples shall, unless otherwise specified, be determined according to the following table. Party Size 1 – 10 11 – 30 31 – 50 51 – 100 101 – 200 Sample Size 2 3 4 6 8 4.2. Acceptance Tests The type test specified in the Contract: Shall be performed on an appropriate number of samples, depending upon special requirements of the test. The routine tests specified in Clause 3.2: (Oil tightness test shall be performed as specified below.) Oil-tightness Test: Shall be performed on every selected sample. The test shall be performed by applying inside the tank a pressure which is equal to two times the static oil pressure to be measured at the base of the tank. Duration of the test shall be 12 hours. No oil leakage shall occur in the transformer at the end of the test. Insulating Oil Tests: Unless otherwise specified in the Bidding Documents, shall be performed on a sample to be taken from supplied ones. Breakdown voltage, Water Content, Interior Surface Tension, Neutralization Number and Power Factor (at 250C and 100 0 C) shall be measured (According to the relevant oil specification). Oil sample, shall be taken two times in the presence of the Supplier/Manufacturer’s representative(s) in Oil Sampling Jars, one of them as witness sample, and the lids of the jars shall be properly sealed by the PURCHASER. Oil Sampling Jars shall be provided by the Manufacturer/Supplier. Of the two samples, one shall be sent to the test, while the other will remain at the manufacturing firm as a witness sample. All responsibility for the process of proper sampling shall lie with the manufacturing firm. 4.3. Acceptance Criteria 15 TEDAŞ-MYD/95-012.C i. All type tests shall have positive result. In case of a negative result that causes the PURCHASER to reach the conclusion that service reliability of the transformers will be lost, it may reject all the transformers in the party. The Purchaser, at its unobjectionable judgement, may accept the repetition of the test, if the Supplier proposes to modify within a reasonable period of time the design of the transformers and to repeat at its own expense, all the type tests specified in the Specification. ii. All Routine Tests and Oil Tightness Test shall produce positive results. Should the results of any routine tests on any sample prove negative, then these test(s) shall be repeated on all the transformers in the party. In this case, the defective units shall be replaced or repaired at the full expense of the Supplier. iii. In case a negative result is obtained from the Insulating Oil Sample sent for test, witness sample shall be tested. In case a positive result is obtained from the witness sample, the result of the test shall be accepted as POSITIVE. Otherwise, it will be concluded that the insulating oil of the transformers comprising the delivery lot in question is inappropriate and request will be made for the insulating oil of the transformers in the scope of the delivery to be improved to acceptable conditions. The Supplier shall not be given any extention of time for these operations. 4.4. General Provisions for Acceptance Tests i. Upon the signing of the Contract, the Supplier shall notify the Purchaser of a Test Program, at least 20 (twenty) days in advance for the tests to be performed abroad and at least 7 (seven) days in advance for the tests to be performed in Turkey, which shall cover the information such as name, place and starting date of tests. ii. Acceptance tests shall be carried out under the supervision of the PURCHASER’s representative(s). Unless otherwise specified in the Contract, performance of acceptance tests on the Manufacturer’s premises is essential. Tests which are included in the scope of acceptance tests but can not be performed on the manufacturer’s premises, may be carried out in another place to be deemed appropriate by the PURCHASER, Implementation regarding type tests shall be made according to Clause 4.4.iii herein. iii. Type tests to be performed within acceptance tests, may be carried out at an accredited laboratory or alternatively, at an unaccredited laboratory but under the supervision of the PURCHASER’s representative(s). Other acceptance tests shall not start before the submission to the PURCHASER of the type test reports with positive results. In case the type tests are performed at an accredited laboratory, the presence of the PURCHASER’s representative(s) is not necessary. iv. The Purchaser, by notifying the Supplier in due course, may inform that it will not attend the tests. In such a case the Supplier shall carry out the tests together with the Manufacturer and notify the PURCHASER of their results. The test reports 16 TEDAŞ-MYD/95-012.C prepared and signed together by the Supplier and Manufacturer, shall be sent to the PURCHASER in 2 (two) copies for review and approval. If test reports are approved, the PURCHASER shall issue a Release Note for shipment and return 1 (one) approved set of the Test Reports to the Supplier. v. Outside the reasons arising from the PURCHASER’s actions (failure to be present at the test site on the date notified, failure to reach a clear decision on the test results etc.), no extention of time shall be given to the Supplier for delays that may occur in the delivery due to incompletion of acceptance tests. vi. No payment shall be made to the Supplier before the conclusion of acceptance tests. vii. Test reports shall include the serial number(s) and characteristics of the sample(s) tested. Test reports shall also clearly state the compliance or incompliance of the test results with this specification and than shall be countersigned. In case the test results and other related issues (if any) stipulated in the specification are appropriate, the PURCHASER’s representative(s) shall give permission for the shipment of relevant party of goods. The Purchaser’s representatives may leave the decision to the General Management, if a clear decision concerning the test results can not be reached by them. 5. DOCUMENTS TO BE SUBMITTED WITH THE BID Schedule of Guaranteed Characteristics Schedule of Guaranteed Characteristics shall be signed by the Bidder and the Manufacturer firm after being filled in separately for the transformer in each item. Information given in these schedules shall be binding for both the Bidder and the Manufacturer firm. Type test reports and certificates Bidders are required to submit with their bids, reports or certificates of type tests carried out in an accredited laboratory. Reports of type tests which were carried out with the presence of PURCHASER’s or TSE’s representatives, may also be accepted. The test reports must belong to the type of equipment offered. Therefore, the PURCHASER, if deems necessary, may ask the Bidder the proof that the test reports belong to the type of equipment offered. The test reports shall contain the name of the laboratory, names, titles, and signatures of observers and persons performing the tests, and the date of tests. If the equipment offered are manufactured under a license, type test reports shall belong to the transformer produced in the place where the manufacturing process in question is being carried out. The Purchaser reserves the right to determine to its satisfaction to evaluate the bids of the Bidders who did not submit appropriate or any type test reports, provided that the type tests to be carried out in Turkey shall be carried 17 out on a sample unit to be selected out of the TEDAŞ-MYD/95-012.C first delivery lot, and the type tests to be carried out abroad shall be carried out before the first lot is delivered, at the Supplier’s cost. Following documents and drawings; In addition to the Schedule of Guaranteed Characteristics, the Bidders shall submit their bids with following documents for each type of equipment offered. - T.S.E. Certificate, - ISO 9000 : 2000 Quality System Certificate and ISO 14 000 Environment Management Systems Certificate, held by the Manufacturing firm, - Detailed catalogues, manuals for mounting, operation and maintenance instructions, - Descriptive information and drawings concerning tank, type of core and windings and winding arrangement, - Drawings with overall dimensions and location of auxiliary equipment, - Drawings with transport dimensions and transport weights. The Bidder’s failure to submit any of the documents required herein or any missing data may entitle the PURCHASER to reject the bid. 6. MISCELLANEOUS CONDITIONS 6.1. Bid Prices The bid units prices shall be given in accordance with the relevant terms of the bidding documents: The bid unit prices shall include the prices of: - The complete transformer with all the equipment required in the specification, Acceptance tests, Special tools (if any) Packing 6.2. Special Tools If special tools are required for mounting and dismantling of transformers, these special tools shall be delivered together with transformers and list of the tools shall be specified in the bid, 18 TEDAŞ-MYD/95-012.C 6.3. Packing Transformers shall be delivered together with their bushings, radiators oil-conservators and all other specified accessories and equipment (except wheels) mounted on them and their oil filled in. Transformers shall be delivered without packing, but necessary measures shall be taken to protect the bushings from breakage during transportation and storage by enclosing them into wooden boxes fixed to the tank properly. Parts which shall be delivered as unmounted on the transformer, such as spare parts, special tools, wheels (if any) shall be placed into a separate wooden box and delivered together with the transformers. Packing box shall be marked with transformer brand, characteristics and order number. 6.4. Documents to be Submitted for Approval After the signing of the Contract, the Supplier shall submit the following drawings in 2 (two) copies for approval within an appropriate time, taking into account the delivery program, Drawings indicating the overall dimensions of transformers complete with all auxiliary equipment, Nameplate drawings Warning labels The approval of drawings and documents shall not relieve the Supplier of his obligations for carrying out the terms of the Contract, and of his responsibility for correctness of drawings and manufacturing according to technical aspects. The drawings submitted for approval shall be approved and sent back to the Supplier not later than 10 (ten) days, however any delay due to late submission of drawings shall not entitle the Supplier to claim for a time extension. 6.5. Documents to be Submitted with the Transformers Following documents shall be submitted with each transformer, enclosed in a plastic protection envelope Operation and maintenance instruction Approved drawings Routine test reports Type, brand and weight of insulating oil. Warranty Certificate obtained from the Manufacturer 6.6. Inspections and Tests Outside the Acceptance Tests 19 TEDAŞ-MYD/95-012.C i. The fact that goods have been inspected, tested and accepted by the PURCHASER’s representative(s) before loading, shall not restrict or remove the right of the PURCHASER to re-inspect, re-test and, if necessary, reject them at their last point of delivery. ii. The PURCHASER may, at its unobjectionable judgement, decide upon the repetition of all or a part of type tests or routine tests on the manufacturer’s premises or at an accredited laboratory either inside or outside the country, within the contract period. Sample(s) shall be selected by the PURCHASER’s representative(s) and countersealed. Should the result of the tests to be performed prove positive, all the costs thereof shall be paid by the PURCHASER. However, If the result of the tests come out negative all the test expenses shall be borne by the Supplier. The PURCHASER may, at its unobjectionable decision, decide on the change of such transformer with the appropriate ones, after the performance of the relevant type tests and routine test of the latter, provided that this change shall be done within a reasonable period of time and that all the expenses shall met by the Supplier, or it may decide on the unilateral cancellation of the contract. 6.7. Warranty The Supplier shall warrant that each transformer of the supply shall have no defects arising from design, materials or workmanship, for a period of 24 months after the date of delivery. Should the transformers become defected/damaged within the warranty period, defected transformers shall be transported to the manufacturer by the PURCHASER for expertise. At the end of this expertise: i. In case it is determined that the transformer has become defected/damaged due to reasons arising from the Manufacturer such as design, workmanship, material and/or packing (including the reason that some other construction is used than the one used during the type tests), it shall be repaired or replaced by a new unit at full expense of the Manufacturer/Supplier and transported to the destination to be indicated by the PURCHASER. The expenses incurred by the PURCASER during the transportation of the transformers to the Manufacturer, shall be repaid by the Manufacturer to the PURCHASER. ii. In case it is determined that the same quality of material as stipulated in the specification is not used, notwithstanding the determination that the transformer has become defected due to reasons arising from operation, the reason of this defect shall be attributed to the Manufacturer and the case shall be treated within the scope of clause “i”. iii. In case it is determined that the transformer has become defected due to reasons arising from operation and if its repair is decided by the PURCHASER, the necessary repair work shall be carried out on the Manufacturer’s premises at the contract unit price3 which were 3 In determining repair cost ,the unit prices to be used are determined according to following clarifications: 20 TEDAŞ-MYD/95-012.C realized at the latest transformer repair contract awarded by the General Management within the last two years (excluding transformers with wound type cores), and the calculated sum shall be paid by the PURCHASER. If no repair work has been carried out within the last two years, repair price shall be determined by mutual negotiations. iv. In case no determination can be made as to which party is responsible for the transformer’s defect: - The transformers which are decided to be repaired, shall be repaired on their manufacturer’s premises, and repair price, to be determined according to the clause “iii”, shall be shared on a fifty-fifty basis between the PURCHASER and the Manufacturer. - In case the transformer is replaced with a new unit, the price included in the relevant purchasing contract shall be met on a fifty-fifty basis by the PURCHASER and the Manufacturer. - The transformer repaired or replaced with a new unit, shall be transported by the Manufacturer to the destination indicated by the PURCHASER at expense of the Manufacturer. The Manufacturer, shall get the defective/newly replaced transformer ready for acceptance within at the latest 1 (one) month as of the date of expertise. Upon the completetion of acceptance tests, the transformers repaired within the scope of “I”, “ii” and “iv”, shall be transported to the destination to be indicated by the PURCHASER within 15 (fifteen) days at the latest. If the Manufacturer fails to meet the repair and transportation expenses arising from his own default, these expenses and costs shall be collected from the earnings or performance security of the Supplier. The repaired or replaced equipment shall be covered by the same warranty stipulations. - Should the repair contract has been awarded on a fixed price basis and the main order still continues, exactly same prices of the relevant contract are used. - Should the repair contract has been awarded on a fixed price basis and main order already completed; contract prices are escalated, taking into account the date of completion of the main order according to the delivery program and using DEI’s Wholesale Price Index. - Should the repair contract has been awarded on a escalated price basis, contract prices are escalated to the date of expertise according to the escalation formula and the prices thus found are used. 21 TEDAŞ-MYD/95-012.C APPENDICES APP. – I BILL OF MATERIALS APP. – II SCHEDULE OF GUARANTEED CHARACTERISTICS APP.– III DRAWINGS APP.– IV TECHNICAL SPECIFICATION FOR INSULATING OIL (TWO COPIES) 22 TEDAŞ-MYD/95-012.C APP. – I BILL OF MATERIALS FOR MV/LV DISTRIBUTION POWER TRANSFORMERS File No: 1 Rated Power 2 Rated Voltage 3 UNIT kVA - HV winding kV - LV winding kV 1 ITEM NO 2 3 Service Conditions - Altitude meter - Lowest ambient temperature 0 - Highest ambient temperature 0 C C - Environment Pollution 4 Off-load voltage regulation - Voltage regulation range - Number of taps 5 Connection symbol 6 HV Bushing -(Open type/Outside Cone Type) 7 Cable Box - at HV-(YES/NO) - at LV-(YES/NO) 8 Other Issues (Other issues requested by the PURCHASER as different from the technical specification shall be written in this part.) 9 PURCHASER’s material code number - 10 Quantity to be purchased PIECES 23 TEDAŞ-MYD/95-012.C APP. – II SCHEDULE OF GUARANTEED LIST File No : ……………… Item No : ……………… Purchaser’s Material Code No. : ……………… UNIT 1 Manufacturer’s name - 2 Manufacturer’s type designation - 3 Numbers of Standards applied 4 Type - 5 Rated power kVA 6 Rated voltage - HV winding GUARANTEED with conservator exposed to the air - - LV winding - 7 Voltage regulation range and number of taps - 8 Voltage regulation type - 9 Connection symbol 10 Service Conditions HV and Off-load - Service altitude meter - Lowest ambient temperature 0 C - Highest ambient temperature 0 C - Environment Pollution - 11 HV Bushing (Open type/Outside Cone Plug type) - 12 Rated creepage distance for Open type HV Bushings 13 Cable Box kV/mm - at LV (YES/NO) - at MV (YES/NO) 14 15 16 Temperature Rise Limits - LV Winding K * - HV Winding K * Top oil K * - One-minute power frequency withstand voltage for HV windings kV-rms * - One-minute power frequency withstand voltage for LV windings kV-rms * - Lightning Impulse withstand voltage for HV windings (1.2-50 microsecond) kV-rms * Insulation Levels Impedance Voltage (at 750C) - at main tapping % - at highest tapping % - at lowest tapping % 24 TEDAŞ-MYD/95-012.C UNIT GUARANTEED * 17 No-load losses (at main tapping voltage) Watt 18 No-load current (at main tapping voltage) % 19 Load Loss (corrected to 75 C) o - At main tapping Watt - At highest tapping Watt - At lowest tapping Watt 20 Sound power level LWA 21 Thermal ability to withstand short-circuit Sec. 22 LV Winding * - Conductor material (aluminum/copper) 23 - Conductor cross section mm 2 - Conductor type (metal foil-rectangular) - - Coil type - Circular concentric Non-circular concentric HV Winding - Conductor material (aluminum/copper) 24 - Conductor cross section mm 2 - Conductor type (metal foil-rectangular) - - Coil type - Circular concentric Non-circular concentric Conductor weight of windings - LV winding Kg/phase - HV winding Kg/phase 25 Core type (shell type/core type) - 26 Quality of silicone steel laminations used - 27 Magnetizing flux density Wb/m 2 28 Weight of magnetic circuit (core) Kg 29 Weight of tank Kg 30 Insulating oil brand and type - 31 Weight of oil Kg 32 Weight of complete transformer Kg 33 Gasket used between Tank and Cover; - Gasket material - Gasket type (cork, round etc.) 34 Dimension (without Cable Box) - Width - Height - Length - Height of Upper Cover 25 ** TEDAŞ-MYD/95-012.C UNIT 35 GUARANTEED Dimensions (with Cable Box) - Width - Height - Length - Upper cover height (*): This part shall be filled in, if the guaranteed values are different than those specified in the Technical Specification. (**) : As mineral-based oils, oils with brand such as NYNAS-NYTRO 10 GB XT, SHELL-DIALA AX, TECHNOL-296 XT, NYNAS-NYTRO 10 XT; TECHNOL-2000 shall be used in transformers. In case a mineral-based different oil is proposed, the sample of the oil proposed, shall be tested in TEİAŞ’s Chemical Laboratory according to the relevant oil specifications given in the appendix. All the test expenses (regardless of the test results) shall be borne by the Supplier. In case positive results are obtained from the tests, use of the oil in question shall be permitted. 26 TEDAŞ-MYD/95-012.C APP-III/1 PRINCIPLE DRAWINGS SHOWING INSULATORS, OIL CONVERSATOR LOCATION, MARKING OF CONNECTION TERMINALS AND DISTANCES BETWEEN WHEELS FOR DISTRIBUTION POWER TRANSFORMERS WITH CAPACITIES 160 kV AND BLOW “IMPORTANT: The Drawings at the Turkish Copy of this specification, shall be taken as the Basis for all Bidding.” FRONT VIEW VIEW-A 50-160 kVA 1 2 3 4 5 D G VIEW FROM TOP 27 D 520 mm G 50 mm Name plate Lifting ring Earthing Terminal Oil Drain Valve Tap Changer Distance Between Wheels Width of Wheel TEDAŞ-MYD/95-012.C APP-III/2 PRINCIPLE DRAWINGS SHOWING INSULATORS, OIL CONVERSATOR LOCATION, MARKING OF CONNECTION TERMINALS, DISTANCES BETWEEN WHEELS FOR DISTRIBUTION POWER TRANSFORMERS WITH CAPACITIES 250 kVA AND UP “IMPORTANT: The Drawings at the Turkish Copy of this specification, shall be taken as the Basis for all Bidding.” FRONT VIEW VIEW-A 250 kVA 400-630 kVA 800-1600 kVA 1 2 3 4 5 6 D G D 520 mm 670 mm 820 mm G 50 mm 50 mm 70 mm Terminal Box Name Plate Lifting Ring Earthing Terminal Tap Changer Oil Drain Valve Distances Between Wheels Wheel Width VIEW FROM TOP NOTES: Protective equipment specified in the technical specification depending on the transformer power, are shown on the drawings. Placement of the protective equipment included in the technical specification shall be carried out by the manufacturing firm. 28