Transmission System Modeling Data Requirements and Reporting Procedures In Accordance with NERC’s MOD-032-1 Reliability Standard “Data for Power System Modeling and Analysis” Prepared by: Vito De Luca, Eng. Effective date: July 1, 2015 Revision: 1 Hydro-Québec TransÉnergie Table of Contents 1. Objective............................................................................................................................. 5 2. Power System Modeling .................................................................................................... 6 2.1 Power flow and Dynamics Case Building ........................................................................................6 2.2 Functional Entities within the Québec Interconnection....................................................................6 2.3 Power System Modeling Workflow and Processes ..........................................................................8 2.3.1 Power System Modeling Workflow ......................................................................................8 2.3.2 Description of Power System Modeling Activities .............................................................10 2.3.3 Case Building Timeline.......................................................................................................11 3. Modeling of Generating Facilities ....................................................................................12 3.1 Modeling Data Requirements .........................................................................................................12 3.1.1 Steady-State Data Requirements for Generator Modeling ..................................................13 3.1.2 Short-Circuit and Dynamics Data Requirements for Generator Modeling .........................14 3.2 Reporting Procedures .....................................................................................................................17 3.2.1 Data Format.........................................................................................................................17 3.2.2 Data Submission Procedure and Schedule ..........................................................................18 4. Transmission System Equipment ....................................................................................19 4.1 Modeling Data Requirements .........................................................................................................19 4.1.1 Transmission System Equipment Steady-State Data Requirements ...................................20 4.1.2 Transmission System Equipment Short-Circuit and Dynamics Data Requirements ..........23 4.2 Reporting Requirements .................................................................................................................25 4.2.1 Data Format.........................................................................................................................25 4.2.2 Data Submission Procedure and Schedule ..........................................................................26 5. Modeling of Aggregate Demand ......................................................................................27 5.1 Modeling Data Requirements .........................................................................................................27 5.1.1 Steady-State Data Requirements for Demand Modeling ....................................................27 5.1.2 Short-Circuit and Dynamics Data Requirements for Demand Modeling ...........................29 5.2 Reporting Procedures .....................................................................................................................29 5.2.1 Data Format.........................................................................................................................29 5.2.2 Data Submission Procedure and Schedule ..........................................................................29 6. Complementary Power System Information ...................................................................30 6.1 Resource Planning Data..................................................................................................................30 6.1.1 Resource Planning Data Requirements ...............................................................................30 6.1.2 Data Format.........................................................................................................................30 6.1.3 Data Submission Procedure and Schedule ..........................................................................30 6.2 Interchange Schedule......................................................................................................................30 6.2.1 Interchange Data Requirements ..........................................................................................31 6.2.2 6.2.3 7. Data Format ........................................................................................................................ 31 Data Submission Procedure and Schedule ......................................................................... 31 Data Submission Procedure and Schedule ....................................................................32 7.1 Data Submission Procedure ........................................................................................................... 32 7.2 Data Submission Schedule............................................................................................................. 33 7.3 Compliance Violations................................................................................................................... 34 REFERENCES .............................................................................................................................35 APPENDIX 1 – Load Data Reporting Templates .......................................................................36 APPENDIX 2 – List of Approved Dynamics Models..................................................................37 A2.1 Standard Library Models .................................................................................................................. 37 A2.2 Approved User-Defined Models....................................................................................................... 41 APPENDIX 3 – Examples of Siemens-PTI PSS/E Model Library Data sheets ......................... 43 APPENDIX 4 – Generator Modeling Data Reporting Template ................................................44 APPENDIX 5 – HQT Bus Numbering and Classification...........................................................45 A5.1 Bus Number Ranges ......................................................................................................................... 45 A5.2 NPCC Area Codes ............................................................................................................................ 46 A5.3 Québec Interconnection Zoning Codes ............................................................................................ 46 APPENDIX 6 – Interchange Data Template ...............................................................................49 Hydro-Québec TransÉnergie 1. Objective Hydro-Québec TransÉnergie (HQT), in its role as Planning Coordinator and Transmission Planner, is charged with the task of maintaining transmission system models (steady-state, dynamics, and short-circuit) and developing power flow and dynamics cases necessary to support planning studies and reliability analysis of Québec’s interconnected transmission system. The accuracy of system models is heavily dependent on the reliability of modeling data collected from the various functional entities that interface with the transmission system. The purpose of this document is to establish steady-state, dynamics, and short-circuit modeling data requirements and reporting procedures, in accordance with NERC’s MOD-032 reliability standard, “Data for Power System Modeling and Analysis”. The document shall serve as a reference guide to all functional entities that provide data necessary for system modeling, providing the basic requirements regarding the type of data required as well as applicable data submission procedures. It will also describe how entities shall reference and use existing HQT technical documents and procedures to meet modeling data requirements. The most updated version of the present document shall be made available to all concerned functional entities by means of an online posting on HQT’s website, via the following link: http://www.hydroquebec.com/transenergie/en/modeling.html. Transmission System Modeling Data Requirements and Reporting Procedures 5 Hydro-Québec TransÉnergie 2. Power System Modeling Power flow and dynamics cases are developed by the Planning Coordinator (PC) in order to realistically simulate the steady-state and dynamic performance of the Québec interconnected transmission system. All electrical elements that comprise the transmission system, such as generating units, power lines, transformers, reactive power compensation equipment, and system loads, are modeled based on measured electrical parameters (modeling data) provided by various functional entities within or connected to the transmission system. 2.1 Power flow and Dynamics Case Building Power flow and dynamics cases are developed using the Siemens Power Technologies Inc. (PTI) Power System Simulator for Engineers (PSS/E) simulation software. A power flow case is a collection of steady-state models of generation, transmission system equipment and topology, short-circuit data, load, dispatch, and interchanges that constitute a snapshot of the selected set of operating conditions. A dynamics case is a collection of dynamic models used in conjunction with a power flow case to perform stability analysis of system performance. The PC develops a series of power flow and dynamics cases (also referred to as base cases) on an annual basis, reflecting various system conditions and planning scenarios. These cases are used by the PC and Transmission Planners (TPs) for system studies and reliability analysis. They are also used by the NPCC through its SS-37 Working Group on Base Case Development. Consequently, the accuracy of studies and reliability of base cases are heavily dependent on the quality of modeling data collected from functional entities. The PC’s annual case building exercise is a structured and detailed process, which is explicitly outlined in HQT’s base case building manual document entitled “Mise à jour des réseaux planifiés” as well as in NPCC’s C-29 Document entitled “Procedures for System Modeling: Data Requirements & Facility Ratings”, available at https://www.npcc.org/Standards/Procedures/c29.pdf. 2.2 Functional Entities within the Québec Interconnection The functional entities, as per MOD-032-1 (part A, section 4.1 “Applicability”), that play key roles in obtaining, submitting, validating, and maintaining modeling data within the Québec Interconnection are defined in the following table. 6 Transmission System Modeling Data Requirements and Reporting Procedures Hydro-Québec TransÉnergie Table 1 – Functional Entities within the Québec Interconnection Functional Entities Generator Owners (GO) Names of Organization(s) • Canadian Hydro Developers Inc. • Cartier Wind Energy Inc. Role in Power System Modeling Provides modeling data for generating units and generation outage information. • Domtar Inc. • Énergie éolienne Le Plateau s.e.c. (Invenergy Wind LLC) • Énergie La Lièvre s.e.c. (Brookfield Renewable Power) • Hydro-Québec Production (HQP) • Hydro-Saguenay • Manicouagan Power Limited Partnership (SCHM) • NextEra Energy Resources (FPL Group) • Northland Power Inc. • Rio Tinto Alcan (RTA) • Rolls-Royce Canada Limited • TransCanada Québec Inc. • All other privately owned hydroelectric, biomass and fossil fuel generating stations, and windfarms Load Serving Entity (LSE) • Hydro-Québec Distribution (HQD) Provides aggregate demand modeling data. Planning Authority/Coordinator (PC) • HQT – Direction - Planification Responsible for Interconnectionwide base case building and modeling data maintenance (data storage). Resource Planner (RP) • Hydro-Québec Distribution (HQD) Provides generator dispatching information based on load-side contractual obligations. Transmission Owners (TO) • Arcelor Mittal Montréal • Canexus Chemicals Canada Limited Partnership Provides modeling data and outage information of transmission system equipment. • Cedars Rapids Transmission Co. (CRT) • Énergie éolienne Le Plateau s.e.c. (Invenergy Wind LLC) • Énergie La Lièvre s.e.c. (Brookfield Renewable Power) • HQT – Direction Principale – Exploitation des installations • Kruger Inc. (Trois-Rivières) • Manicouagan Power Limited Partnership (SCHM) • PPG Canada Inc. • Rio Tinto Alcan (RTA) Transmission System Modeling Data Requirements and Reporting Procedures 7 Hydro-Québec TransÉnergie Transmission Planners (TP) • HQT – Direction - Planification Users of base cases for system studies. Transmission Service Providers (TSP) • HQT - Direction – Commercialisation et affaires règlementaires • Cedars Rapids Transmission Co. (CRT) Provides transmission service customer contract data (point-topoint transmission service details) as published on OASIS. 2.3 Power System Modeling Workflow and Processes 2.3.1 Power System Modeling Workflow The PC’s annual exercise of developing reliable base cases is an intricate process requiring active inter-organizational collaboration from all function entities. The following figure illustrates a general overview of how the functional entities listed above shall interact in regards to the submittal and processing of modeling data within the Québec Interconnection. 8 Transmission System Modeling Data Requirements and Reporting Procedures Hydro-Québec TransÉnergie Figure 1 – Planning Coordinator Modeling Data Workflow Transmission System Modeling Data Requirements and Reporting Procedures 9 Hydro-Québec TransÉnergie 2.3.2 Description of Power System Modeling Activities As illustrated above, power system modeling is comprised of a sequence of modeling data submission, validation and processing activities required to produce interconnection-wide base cases suitable for system studies. Modeling data is collected from various functional entities, validated to ensure functionality and compatibility with simulation tools, and then entered into specific data bases for referencing and base case building. Essentially, case building is achieved based on the following inputs: 1. Steady-state and Short-circuit Modeling Data from PSS® Model on Demand (MOD) Database The MOD database consolidates all generation and transmission system steady-state and short-circuit modelling data (including planned future projects) collected from various functional entities in a central data repository. MOD is synched with DSR, the PC’s main equipment data base containing updated modeling data of all existing generating and transmission system facilities, producing a MOD base case scenario in PSS/E format (.sav). Future projects, consisting of generation or transmission system additions, upgrades or modifications, are submitted to the PC by TPs and stored in MOD. They are then applied to the MOD base case scenario, allowing the PC and TPs to customize planning cases for any desired future point in time. Corrections or modifications to modeling data for existing facilities are validated before data is updated in the DSR database. In the case of future projects, preliminary modeling data submitted by GOs, TOs and TPs are entered directly into MOD, after model validation by the PC. New generating units or transmission system equipment are only added to DSR after project commissioning and after the PC has received all updated modeling data. This updated data is obtained from GOs and TOs at the later stages of the project commissioning phase. 2. Dynamics Models and Modeling Parameters Validated dynamics models and modeling parameters of existing facilities and future projects collected from GOs, TOs and TPs are stored in the PC’s dynamics library. The PC’s dynamics library consists of all dynamics model files required to run dynamics simulations in PSS/E (*.lib, *.obj, *.dll, etc.), source code files for certain user-defined models, dynamics parameters in the form of DYR files, and any IDEV or PYTHON programs necessary to set up dynamics simulation parameters. 3. Aggregate Demand Data Once aggregate demand data for each load-serving bus is received from the LSE, the PC validates and processes the data, mapping load data to the appropriate load serving buses in the MOD base case. The validated data is then stored in the PC’s Load Forecast Database which is used to produce load profiles for a given forecast year in the form of PYTHON 10 Transmission System Modeling Data Requirements and Reporting Procedures Hydro-Québec TransÉnergie automation files. These files are applied to the MOD base case scenario to produce customized planning cases for any desired future point in time. 4. Resource Data The RP, in collaboration with GOs, provide the PC with data regarding all available resources needed to fulfill LSE demand requirements. This allows the PC to produce realistic generation dispatch scenarios, adequately balancing load and generation. 5. Interchange Data from TSPs When preparing a base case scenario, the PC must consider scheduled MW transfer levels at each inter-area interconnection facility. Interchange data used in base case building is based on transmission service customer contract data (point-to-point transmission service details) as published on OASIS, as well as the NPCC Interchange Schedule prepared annually by NPCC’s SS37 work group. 6. Equipment Outage Information Planned maintenance or commissioning of generating units and transmission system equipment resulting in outages must be considered in base case development. Short-term generator outages are reported to the PC by GOs and transmission system equipment outages are reported by the TOs. 2.3.3 Case Building Timeline The modeling data produced by the power system modeling activities described above are assembled during case building according to the timeline illustrated in the following figure. June 1st Phase 1 of Load Data Collection March 1st Reporting deadline for new future projects and modifications to existing modeling data (DSR & MOD) January 15th Start of Annual Case Building Exercise (Winter Peak) October 1st Phase 2 of Load Data Collection (All data) February 1st Generation Modeling Data Collection May 1st Delivery of finalized Power flow and dynamics base cases April 1st Integration of complementary power system information (Outage, resource allocation and Interchange data) Figure 2 - Case Building Timeline Transmission System Modeling Data Requirements and Reporting Procedures 11 Hydro-Québec TransÉnergie 3. Modeling of Generating Facilities 3.1 Modeling Data Requirements All Generator Owners (GOs) connected to the Québec interconnected transmission system must provide valid modeling data of existing and future generating units to the PC on an annual basis. The PC also requires GOs of existing facilities to recertify generator modeling data on an annual basis, either by resubmitting all required modeling data or by certifying that data has not changed from the previous year’s data submission. In the case of changes to modeling data, GOs must clearly identify all changes and submit all modified modeling data in accordance with the requirements herein. For new or future planned generating units, generator modeling data shall be submitted 1) during the project’s planning phase, normally 3-5 years prior to commissioning, and 2) immediately after project commissioning. 1- Project Planning Phase Data The PC and TPs initially collect approximated generator modeling data from new and prospective GOs in order to conduct interconnection or system impact studies prior to commissioning of generating facilities. This preliminary data is submitted to the PC and TPs in conjunction with GOs’ request for system impact studies, as described in section 3 of HQT’s technical requirements document and in HQT’s Procedure document for the connection of new generating units, available (in French) on HQT’s website at: http://www.hydroquebec.com/transenergie/fr/commerce/pdf/demarche-a-suivre-2012.pdf. 2- Post-commissioning Data GOs shall update the preliminary data provided to the PC and TPs during the project planning phase by providing actual or measured modeling parameters. GOs must conduct data validation testing in order to validate modeling data as well as demonstrate that their facilities meet the requirements set out in the document “Transmission Provider Technical Requirements for the Connection of Power Plants to the Hydro-Québec Transmission System”, available on HQT’s website at: http://www.hydroquebec.com/transenergie/fr/commerce/pdf/exigence_raccordement_fev_09_e n.pdf. The validation procedures and testing for wind farms are outlined in HQT’s “General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System” document, available on HQT’s website at: http://www.hydroquebec.com/transenergie/fr/commerce/pdf/essais-eoliennes2011-en.pdf 12 Transmission System Modeling Data Requirements and Reporting Procedures Hydro-Québec TransÉnergie The validation of modeling data is a prerequisite for final TO acceptance of the generating facility project and must be completed within 6 months of initial commercial commissioning. GOs of generating units with capacities less than 10 MW that are connected at the distribution network level are not required to provide detailed modeling data unless specifically requested by TPs or the PC for system studies purposes. The following sections present the steady-state, dynamics and short-circuit data required to effectively model all generating units within the Québec interconnected transmission system, defining the type of data required and the units this data is to be reported in. 3.1.1 Steady-State Data Requirements for Generator Modeling i. In general, generator owners shall provide steady-state modeling data of existing and prospective generating units according to the requirements set forth in Appendix A of HQT’s technical requirements document entitled “Transmission Provider Technical Requirements for the Connection of Power Plants to the Hydro-Québec Transmission System”. The most updated version of the document is readily available on HQT’s website at: http://www.hydroquebec.com/transenergie/fr/commerce/pdf/exigence_raccordement_fev_0 9_en.pdf. ii. The table below summarizes the main steady-state data requirements, as outlined in MOD032-01, A1-3. Table 2 – Steady-State Data Reporting Requirements for Generator Modeling Generator Unit Component Synchronous/Asynchronous Generators Generator Step-Up Transformers * * Steady-State Modeling Data Requirements • Generator type (hydroelectric, thermal, wind, etc.) • Real power capabilities (maximum and minimum values in MW) • Reactive power capabilities (maximum and minimum values in MVAR) • Machine MVA base • Generator unit regulated bus and set point voltage • Machine grounding impedances • In-service status • Number of transformers • Nominal voltages of windings (kV) • Rated power (MVA) • Power ratings (MVA) with corresponding cooling method • Positive sequence impedances and winding resistance (Ohms or p.u.) This data shall be provided by the owner of generator step-up transformers, which can be the GO or the TO. Transmission System Modeling Data Requirements and Reporting Procedures 13 Hydro-Québec TransÉnergie Wind Farm Collector Network Equipment • Coupling (winding connection) • Number of tap positions (kV or p.u.) • Tap ratios (voltage or phase angle) • Minimum and maximum tap position limits • Regulated bus (for voltage regulating transformers) • In-service status • Transmission line impedance parameters (ohms or p.u.) • Transmission line admittance (siemens or p.u.) • Transmission line ratings (MVA or A) • Capacitor/Inductor number, in-service status, reactive power ratings and voltage. iii. For future planned generating units, GOs shall provide the expected commissioning date. iv. GOs shall also provide generating station service auxiliary load information for existing units, detailing real (MW) and reactive power (MVAR) load values associated with a given generating unit. v. In regards to “in-service status”, a 10-year forecast of scheduled outages of duration greater than 6 months shall be provided by GOs on a yearly basis. Outage information shall consist of: • Start and end dates of planned outage • Generating unit(s) and/or specific equipment within generation facility scheduled to be out of service. • Impact of outage on generation (i.e. reduction in power plant generation in MW) 3.1.2 Short-Circuit and Dynamics Data Requirements for Generator Modeling i. In general, GOs shall provide short-circuit and dynamics modeling data of existing and future planned generating units according to the requirements set forth in Appendices A and B of HQT’s technical requirements document entitled “Transmission Provider Technical Requirements for the Connection of Power Plants to the Hydro-Québec Transmission System”. The most updated version of the document is readily available on HQT’s website at: http://www.hydroquebec.com/transenergie/fr/commerce/pdf/exigence_raccordement_fev_0 9_en.pdf. ii. In order to accurately simulate dynamic performance of generating units, GOs must provide the PC with validated dynamics models and associated parameters of all power generating equipment and components of the power plant, including: • 14 Generators, including Wind Turbines, Photovoltaic Systems, Fuel Cells and any other resource that delivers MW to the electric power system. Transmission System Modeling Data Requirements and Reporting Procedures Hydro-Québec TransÉnergie iii. • Excitation systems • Turbine and speed governors • Voltage regulators (if equipped) • Power system stabilizers (if equipped) All dynamics models submitted to the PC must be based on standard IEEE models and must be compatible with the current version of Siemens-PTI’s PSS/E (Power System Simulator for Engineers) software, which is used by the PC and TPs for dynamics system studies. The use of Siemens-PTI PSS/E standard dynamics models is preferred when they can accurately represent the dynamic performance of the device being modeled. A list of Siemens-PTI PSS/E standard dynamics models as well as all user-defined models approved by the PC for use in dynamic simulations is listed in Appendix 2 of the present document. iv. User-defined models a) In the event that a compatible standard IEEE or PSS/E dynamics model is unavailable, user-defined or “black-box” models may be used. A user-defined model is any model that is not a standard Siemens-PTI PSS/E library model but has been accepted by the PC after being successfully tested for compatibility. b) User-defined models submitted to the PC shall fulfill the following requirements: • User-defined models must be able to work with a time-step exceeding 4 ms. • User-defined models must be accompanied by a user manual providing all relevant technical documentation and characteristics of the model, including block diagrams, values and names for all model parameters and a list of all state variables. • GOs must also provide compliance test results demonstrating that the model accurately represents the dynamic performance of the device being modeled. GOs must ensure that model compliance testing is performed every 10 years. c) GOs are responsible for validating and maintaining all dynamics models, ensuring that models submitted to the PC are compatible and fully functional in the current version of PSS/E, allowing for error-free initialization. In the event of PSS/E version updates (PC migrates to a newer version of the PSS/E software), GOs shall provide all necessary model updates, ensuring all models are compatible with the new version of PSS/E. Transmission System Modeling Data Requirements and Reporting Procedures 15 Hydro-Québec TransÉnergie d) In the case of user-defined models representing wind farms, the following requirements shall be observed: • Validation of wind turbine models shall be conducted using HQT’s “Procedure for PSS/E model validation” document, available on HQT’s website at: http://www.hydroquebec.com/transenergie/fr/commerce/pdf/procedurevalidation-modeles-psse-en.pdf Test base cases are also available on HQT’s website at: http://www.hydroquebec.com/transenergie/fr/commerce/zip/procedurevalidation-eolien-v32.zip. • The user-defined model must allow wind turbines to be represented as a single generator and must be functional across its entire range of real and reactive power. • In the case where voltage regulation of a wind power plant is achieved by means of additional compensation equipment in the switchyard, the GO shall also provide the complete PSS/E model for the corresponding reactive power compensation equipment, including all associated technical documentation, modeling data and parameters. e) In addition to providing all required data for user-defined models as stipulated in 3.1.2.iv above, GOs must also identify the Siemens-PTI PSS/E standard library model(s) that most closely represents the dynamic performance of the user-defined model, as well as provide the corresponding modeling parameters. GOs may refer to the list of accepted models presented in Appendix 2. v. When submitting model parameters, GOs shall indicate the source of the data reported (manufacturer technical specifications, measured values, typical or estimated theoretical values, etc.). vi. In the case of incomplete data or unknown parameters, GOs shall provide the PC with estimated values based on the GO’s assumptions and hypotheses. All estimated values shall be clearly indicated as such. vii. In regards to under/over-frequency protection of generating units, all GOs shall provide under/over-frequency relay data, specifically generator unit protection relay trip settings and time delay, as described in NERC’s PRC-006-1 standard “Automatic Underfrequency Load Shedding”. 16 Transmission System Modeling Data Requirements and Reporting Procedures Hydro-Québec TransÉnergie 3.2 Reporting Procedures 3.2.1 Data Format i. ii. iii. Steady-state, dynamics and short-circuit data shall be submitted to the PC in one of the following formats: • Table format: Siemens-PTI PSS/E dynamic library models are identified and all corresponding model parameters are provided in a table format. GOs with numerous generating units may use the sample modeling data reporting table provided in Appendix 4 of the present document. • PSS/E Library Data Sheets: GOs using Siemens-PTI PSS/E dynamic library models may also elect to submit modeling parameters using the corresponding Siemens-PTI PSS/E library model data sheets. These data sheets may be provided to the GO upon request. An example of a PSS/E library model data sheet is included in Appendix 3. • PSS/E RAW, DYR format: PSS/E dynamic library models are identified and all corresponding steady-state and dynamics parameters are provided in RAW and DYR files, respectively. In the case of user-defined models, GOs shall submit: • All associated model files required to run simulations in PSS/E (*.lib, *.obj, *.dll, etc.). The PC may request the source code for certain user-defined models, which must be submitted in the FLECS language of the current PSS/E revision, in C, or in FORTRAN. • All corresponding user-defined model steady-state and dynamics parameters, provided in RAW and DYR files, respectively. • All relevant technical documentation and characteristics of the user-defined model, including compliance test results, block diagrams, values and names for all model parameters and a list of all state variables. • Any IDEV or PYTHON programs necessary to set up dynamics simulation parameters. • The Siemens-PTI PSS/E standard library model that most closely represents the generating unit’s dynamics performance, along with all corresponding model parameters. GOs shall provide generator outage information in an Excel table format. Transmission System Modeling Data Requirements and Reporting Procedures 17 Hydro-Québec TransÉnergie 3.2.2 Data Submission Procedure and Schedule i. 18 Data submission is to be performed annually according to the procedures and schedule described in section 7. Transmission System Modeling Data Requirements and Reporting Procedures Hydro-Québec TransÉnergie 4. Transmission System Equipment 4.1 Modeling Data Requirements All Transmission Owners within the Québec Interconnection shall provide the PC with valid modeling data of all existing and future transmission system equipment, including: • AC transmission lines • DC transmission systems • Voltage and phase shifting transformers • Breakers • Shunt reactive compensation equipment (capacitors and reactors) • Series reactive compensation equipment • Static Var systems and synchronous condensers • Special protection systems (SPS) The PC, in accordance with NERC’s MOD-032 standard, requires all TOs of existing facilities to recertify system modeling data on an annual basis, either by resubmitting all required modeling data or by certifying that data has not changed from the previous year’s data submission. In the case of changes to modeling data, TOs must clearly identify all changes and submit all modified modeling data in accordance with the requirements herein. For future planned modifications, additions or upgrades of transmission system equipment, TOs must submit preliminary modeling data to the PC and TPs during the planning phase of the project, during which system impact studies are conducted. This data is generally submitted to the PC and TPs approximately 3-5 years prior to project commissioning. At this stage, estimated or typical modeling parameters are acceptable. TOs shall update the preliminary data provided to the PC during the project planning phase by providing actual or measured modeling parameters based on equipment compliance testing results conducted during the commissioning phase. The validation of modeling data is a prerequisite for final TO acceptance of the transmission system facility project and must be completed within 6 months of initial commercial commissioning. The following sections present the steady-state, dynamics and short-circuit data required to effectively model transmission system equipment within the Québec Interconnection, defining the type of data required and the units this data is to be reported in. Transmission System Modeling Data Requirements and Reporting Procedures 19 Hydro-Québec TransÉnergie 4.1.1 Transmission System Equipment Steady-State Data Requirements i. Each TO shall provide steady-state modeling data of existing and future transmission equipment according to the requirements set forth in the present document. ii. The table below summarizes the main steady-state data requirements, as outlined in MOD032-01, A1- 1, 4-8. Table 3 – Transmission System Equipment Steady-State Data Reporting Requirements Transmission System Component Buses AC Transmission Lines DC Transmission Systems (DC lines and converter stations) Transformers (Voltage and Phase Shifting) 20 Steady-State Modeling Data Requirements • Bus numbers and alphanumeric names • Nominal voltage • Type of bus (substation bus bar, load or generator) • Area, zone and owner • Associated substation or line • To and from buses or substations • Line length (km) • Impedance parameters, R and X (ohms or p.u.) • Susceptance, B (siemens or p.u.) • Thermal ratings at -20⁰C, 0⁰C and 30⁰C (MVA or A) • In-service status • To and from buses or substations • DC Line length (km) • DC Line impedances and data (Voltage, Rcmp-Ohms, Vcmode, CCC Itmax, Rdc-Ohms, Delti, Dcvmin, CCC Accel) • Rectifier and Inverter data (Primary base voltage, Bridges in Series, Trans Ratio, CCC X, AC Tx From Bus, AC Tx To Bus, Max Firing Angle, Commutating R and X, Max & Min Tap Settings, Tap Step) • In-service status • Location of transformer (substation name) • Transformer name (ID number) and assigned position number • Nominal voltages of primary, secondary and tertiary windings (kV) • Impedance parameters, R and X (p.u.) • Magnetizing admittance G and susceptance B (p.u.) • Nominal MVA base • Tap ratios (voltage or phase angle) • Minimum and maximum tap position limits • Number of tap positions • Regulated bus (for voltage regulated transformers) • Capacity ratings at -20⁰C, 0⁰C and 30⁰C (MVA) Transmission System Modeling Data Requirements and Reporting Procedures Hydro-Québec TransÉnergie Breakers Shunt Reactive Compensation Devices (Capacitors and Reactors) Series Reactive Compensation Devices Static Var Systems and Synchronous Condensers iii. • In-service status • Location of breaker (substation name) • Breaker name (ID number) and assigned position number • Nominal voltage (kV) • Manufacturing data (manufacturer, year, design standard) • Breaker interrupting symmetrical and asymmetrical current capacities (kA) • Breaker X/R ratio • Location of shunt unit (substation name) • Shunt unit name (ID number) and assigned position number • Number of capacitors and reactors in unit • Reactive power capacity of each capacitor and reactor (MVAR) • Rated voltage (kV) • Regulated voltage band limits (kV) • Mode of operation (fixed, discrete, continuous, etc.) • Regulated bus • In-service status • Location of series capacitor (substation name and transmission line compensated) • Series capacitor unit name • Unit type • Rated voltage (kV) • Unit impedance (p.u. or ohms) • Unit admittance (p.u. or siemens) • Reactive compensation % • Reactive power capacity (MVA) • Overload factor • In-service status • Location of Static VAR or Synchronous Condenser (substation name) • Rated voltage (kV) • Machine MVA base • Reactive power limits (MVAR) • Regulated bus • Voltage set point (p.u. or kV) • In-service status Attribution of bus numbers and associated bus data must be consistent with the PC’s bus numbering and naming practices presented in the table below: Table 4 – HQT Bus Numbering and Naming Practices Bus Data Bus Number Bus Numbering and Naming Practices • Bus numbers must be unique for all buses in the Québec Transmission System Modeling Data Requirements and Reporting Procedures 21 Hydro-Québec TransÉnergie Interconnection. Bus Name • Bus numbers must be attributed in accordance to the assigned bus number ranges presented in Appendix 5. • Bus names are descriptive names given to buses in PSS/E • Bus names must be unique for all buses in the Québec Interconnection and must not exceed 8 alphanumeric characters. • By convention, bus names must be in the following format: ABC123-1 or ABC123-A In general, the first 3 characters are letters relating to the name of the substation where the bus is located, and the next 3 characters are numbers denoting the nominal voltage level of the bus. A dash and a number or letter may be added at the end of the name in order to help differentiate between multiple buses with the same first 6 characters. For example, according to the naming practice, the PSS/E names of two 315 kV bus bars at the Duvernay substation would be DUV315-1 and DUV315-2. Bus Location • For each bus in the transmission system, an Area number, Zone number and Owner name/number must be specified. • Area refers to the NPCC Area where a given bus is located. For example, buses of the HQT transmission system are located in the HQTÉ Area denoted by number 104. • Zone refers to the specific geographic region within the Québec Interconnection. • Owner refers to the specific transmission owner responsible for a given bus. • A complete listing of all available Area and Zone number codes are presented in Appendix 5. iv. Transmission owners shall also provide substation service auxiliary load information for existing substations, detailing real (MW) and reactive power (MVAR) load values associated with a given substation. v. For all future additions or upgrades where HQT is TO, steady-state modeling data shall reflect technical data specified in the Design Specifications Document (cahier des charges). vi. In regards to “in-service status”, transmission system equipment outages for the upcoming year of duration greater than 6 months shall be provided by the TO on a yearly basis. Outage information shall consist of: 22 • Start and end dates of planned outage • Transmission equipment scheduled to be out of service • Voltage level • Location (substation name, zone, etc.) Transmission System Modeling Data Requirements and Reporting Procedures Hydro-Québec TransÉnergie • Description of project or maintenance causing outage 4.1.2 Transmission System Equipment Short-Circuit and Dynamics Data Requirements i. Each TO shall provide short-circuit and dynamics modeling data of existing and future transmission equipment according to the requirements set forth in the present document. ii. The table below summarizes the main short-circuit and dynamics modeling data requirements, as outlined in MOD-032-01, A1. Table 5 – Transmission System Equipment Short-circuit and Dynamic Data Reporting Requirements Transmission System Component Dynamics and Short-Circuit Modeling Data Requirements • Zero sequence impedance parameters, R and X (ohms or p.u.) • Zero sequence susceptance, B (siemens or p.u.) DC Transmission Systems (DC lines and converter stations) • DC line dynamics model and associated parameters • DC converter dynamics model and associated parameters Transformers (Voltage and Phase Shifting) • Winding connection • Zero sequence impedance parameters, R and X (ohms or p.u.) • Zero sequence grounding impedances, RG and XG (ohms or p.u.) Shunt Reactive Compensation Devices (Capacitors and Reactors) • Zero sequence shunt admittances, G and B (p.u.) Series Reactive Compensation Devices • Zero sequence impedances, R and X (p.u. or ohms) • Zero sequence admittance, B (p.u. or siemens) • Unit admittance (p.u. or siemens) • Positive sequence machine impedances, R1 and X1 (p.u.) • Negative sequence machine impedances, R2 and X2 (p.u.) • Zero sequence machine impedances, R0 and X0 (p.u.) • Static Var System equipment dynamics model and associated parameters • Synchronous Condenser dynamics model and associated parameters • SPS dynamics model and associated parameters AC Transmission Lines Static Var Systems and Synchronous Condensers Special protection systems (SPS) Transmission System Modeling Data Requirements and Reporting Procedures 23 Hydro-Québec TransÉnergie iii. All dynamics models submitted to the PC must be based on standard IEEE models and must be compatible with the current version of Siemens-PTI’s PSS/E (Power System Simulator for Engineers) software, which is used by the PC and TPs for dynamics system studies. The use of Siemens-PTI PSS/E standard dynamics models is preferred when they can accurately represent the dynamic performance of the device being modeled. A list of Siemens-PTI PSS/E standard dynamics models as well as all user-defined models approved by the PC for use in dynamic simulations is listed in Appendix 2 of the present document. iv. In the event that a compatible standard IEEE or PSS/E dynamics model is unavailable, userdefined or “black-box” models may be used. A user-defined model is any model that is not a standard Siemens-PTI PSS/E library model but has been accepted by the PC after being successfully tested for compatibility. v. User-defined models submitted to the PC shall fulfill the following requirements: • User-defined models must be able to work with a time-step exceeding 4 ms. • User-defined models must be accompanied by a user manual providing all relevant technical documentation and characteristics of the model, including block diagrams, values and names for all model parameters and a list of all state variables. • TOs must also provide compliance test results demonstrating that the model accurately represents the dynamic performance of the device being modeled. TOs must ensure that model compliance testing is performed every 10 years. vi. TOs are responsible for validating and maintaining all dynamics models, ensuring that models submitted to the PC are compatible and fully functional in the current version of PSS/E, allowing for error-free initialization. In the event of PSS/E version updates (PC migrates to a newer version of the PSS/E software), TOs shall provide all necessary model updates, ensuring all models are compatible with the new version of PSS/E. vii. In addition to providing all required data for user-defined models as stipulated in 4.1.2.iv-vi, TOs must also identify the Siemens-PTI PSS/E standard library model(s) that most closely represents the dynamic performance of the user-defined model, as well as provide the corresponding modeling parameters. TOs may refer to the list of accepted models presented in Appendix 2. viii. When submitting model parameters, TOs shall indicate the source of the data reported (manufacturer technical specifications, measured values, typical or estimated theoretical values, etc.). 24 Transmission System Modeling Data Requirements and Reporting Procedures Hydro-Québec TransÉnergie ix. In the case of incomplete data or unknown parameters, TOs shall provide the PC with estimated values based on the TO’s assumptions and hypotheses. All estimated values shall be clearly indicated as such. x. For all future additions or upgrades where HQT is TO, short-circuit modeling data shall reflect technical data specified in the Design Specifications Document (cahier des charges). 4.2 Reporting Requirements 4.2.1 Data Format iv. Steady-state, dynamics and short-circuit data shall be submitted to the PC in one of the following formats: • Table format: Siemens-PTI PSS/E dynamic library models are identified and all corresponding model parameters are provided in a table format. • Manufacturer Testing Reports: Modeling parameters may be submitted in the form of a report, presenting results from the manufacturer’s technical compliance testing. • PSS/E Library Data Sheets: TOs using Siemens-PTI PSS/E dynamic library models may also elect to submit modeling parameters using the corresponding Siemens-PTI PSS/E library model data sheets. These data sheets may be provided to the TO upon request. An example of a PSS/E library model data sheet is included in Appendix 3. • PSS/E RAW, DYR format: PSS/E dynamic library models are identified and all corresponding steady-state and dynamics parameters are provided in RAW and DYR files, respectively. • Siemens PSS®MOD format: This form of data reporting is only applicable to HQT. Future projects or modifications shall be submitted to the PC in the form of MOD *.prj files or entered directly into HQT’s MOD database, available online at: http://131.195.100.81/MODWeb/login.aspx?ReturnUrl=%2fmodweb%2fDefault.asp x. v. TOs shall also submit a one-line diagram, illustrating the planned or commissioned transmission system additions and/or modifications. vi. In the case of user-defined models, TOs shall submit: • All associated model files required to run simulations in PSS/E (*.lib, *.obj, *.dll, etc.). The PC may request the source code for certain user-defined models, which must be submitted in the FLECS language of the current PSS/E revision, in C, or in FORTRAN. Transmission System Modeling Data Requirements and Reporting Procedures 25 Hydro-Québec TransÉnergie vii. • All corresponding user-defined model steady-state and dynamics parameters, provided in RAW and DYR files, respectively. • All relevant technical documentation and characteristics of the user-defined model, including compliance test results, block diagrams, values and names for all model parameters and a list of all state variables. • Any IDEV or PYTHON programs necessary to set up dynamics simulation parameters. • The Siemens-PTI PSS/E standard library model that most closely represents the generating unit’s dynamics performance, along with all corresponding model parameters. The TO shall provide transmission system equipment outage information in the form of a report or a simplified Excel table. 4.2.2 Data Submission Procedure and Schedule i. 26 Data submission is to be performed annually according to the procedures and schedule described in section 7. Transmission System Modeling Data Requirements and Reporting Procedures Hydro-Québec TransÉnergie 5. Modeling of Aggregate Demand 5.1 Modeling Data Requirements The main Load Serving Entity (LSE), in this case Hydro-Québec Distribution (HQD), is responsible for preparing and submitting demand data to the Planning Coordinator (PC) for the entire Québec Interconnection. This data is based on demand forecasts prepared and/or assembled on an annual basis by all LSEs. The following sections present the steady-state, dynamics and short-circuit data required to effectively model demand within the interconnected transmission system, defining the type of data required and the units this data is to be reported in. 5.1.1 Steady-State Data Requirements for Demand Modeling i. Steady-state load data shall be submitted to the PC, listing forecasted aggregated load data at each load-serving bus bar for each year of a given demand forecast. ii. The LSE shall also provide Interconnection-wide total demand forecasts, summing substation, customer facility and substation auxiliary load data. iii. Demand forecasts shall be prepared and submitted to the PC in accordance with HQD-HQT agreements (“Ententes sectorielles”) 1, 3 and 6, available at http://transenergie.hydro.qc.ca/ planification_expertise_aff_reglementaires/528.htm, and in compliance with NERC standards MOD-016, MOD-017, MOD-018, MOD-019, MOD-020, MOD-021. The table below summarizes the steady-state data requirements outlined in the HQD-HQT agreements for loads modeled at satellite substation feeder buses (< 44 kV) and loads representing customer facilities (large industrial plants, pulp and paper mills, aluminum smelters, refineries, mining facilities, etc.), directly connected to the high voltage transmission system (44 kV to 324 kV). Table 6 – Steady-State Data Reporting Requirements for Demand Modeling Loads at satellite substation feeder buses < 44 KV (15 year forecast) Customer facility loads at buses > 44 kV (10 year forecast) Bus number Bus number Substation name Customer facility name Real power (MW) Expected real power (MW) Reactive power (MVAR) Total load apparent power (MVA) Load apparent power (MVA) Load in-service status Rated power (MVA) and voltage (kV) of low-voltage side reactive compensation Number of shunt capacitors and reactors Rated power (MVA) and voltage (kV) of each Transmission System Modeling Data Requirements and Reporting Procedures 27 Hydro-Québec TransÉnergie equipment iv. v. reactive compensation equipment Reactive compensation equipment in-service status Quantity of interruptible load In general, load data submitted to the PC shall reflect the following annually prepared demand forecasts: • A 15-year aggregate demand forecast for all load-serving satellite substations within the Hydro-Québec Distribution system with secondary bus voltages less than 44 kV. • A 15-year aggregate demand forecast for all load-serving substations belonging to independent municipal distribution systems with secondary bus voltages less than 44 kV. • A 10-year estimated demand forecast for industrial customer facilities (large industrial plants, pulp and paper mills, aluminum smelters, refineries, mining facilities, etc.), directly connected to the high voltage transmission system (44 kV to 324 kV). • A 10-year Interconnection-wide aggregated demand forecast for all three categories listed above. Each demand forecast shall provide load data for the following types of load levels: • Winter Peak Load • Summer Peak Load • Summer Light Load vi. According to HQD-HQT Agreement #1, Part 2, Article 1, HQD must also provide historical load data based on meter readings at each load-serving satellite substation. vii. In the case of new customer facilities connected directly to the high voltage transmission system, the submission of more detailed modeling information is required prior to the commissioning of new customer facilities, as stipulated in the PC’s “Technical Requirements for Customer Facilities Connected to the Hydro-Québec Transmission System” document. The most updated version of the document is readily available on HQT’s website at: http://www.hydroquebec.com/transenergie/fr/commerce/pdf/ ex_inst_client_en.pdf. viii. 28 Existing customer facilities must also provide load modeling data according to these same technical requirements upon request from the PC or in the event of any modifications to customer facilities. Transmission System Modeling Data Requirements and Reporting Procedures Hydro-Québec TransÉnergie 5.1.2 Short-Circuit and Dynamics Data Requirements for Demand Modeling i. Short-circuit and dynamics data is normally required for customer facilities equipped with large motors that can impact the transmission system’s transient and dynamic performance. This information is normally provided by customer facilities prior to commissioning and connection to the transmission system or in the event of modifications to existing customer facilities. ii. Customer facilities, with the collaboration of HQD, shall provide short-circuit and dynamics data according to the requirements set forth in Appendix 1 of HQT’s “Technical Requirements for Customer Facilities Connected to the Hydro-Québec Transmission System” document. The most updated version of the document is readily available on HQT’s website at: http://www.hydroquebec.com/transenergie/fr/commerce/pdf/ ex_inst_client_en.pdf. iii. Customer facilities must also indicate the source of the data submitted (manufacturer technical specifications, measured values, typical or estimated theoretical values, etc.). iv. In the case of incomplete data or unknown parameters, HQD/Customer facilities are responsible for providing theoretical or estimated values. 5.2 Reporting Procedures 5.2.1 Data Format i. Steady-state load data submitted to the PC shall be presented in an Excel table format similar to the sample tables provided in Appendix 1, as stipulated in HQD-HQT Agreement #1, Part 2, Articles 2 and 4. ii. Short-circuit and dynamic load data shall be submitted to the PC using the modeling data template provided in Appendix A of the “Technical Requirements for Customer Facilities Connected to the Hydro-Québec Transmission System” document. All fields of the said document must be completed in order to be considered as a valid data submission. Other accepted data submission formats for short-circuit and dynamic load data are the following: • Excel Table listing model parameters • PSS/E RAW and DYR files, with all corresponding PSS/E dynamic model files. 5.2.2 Data Submission Procedure and Schedule i. Data submission is to be performed annually according to the procedures and schedule described in section 7. Transmission System Modeling Data Requirements and Reporting Procedures 29 Hydro-Québec TransÉnergie 6. Complementary Power System Information In addition to steady-state and dynamics models, power flow and dynamics cases require quantitative power system information in order to set generation dispatch and inter-area transfer levels. This additional information consists of resource planning data and interchange transfer quantities to neighbouring Areas. The following sections present the data required to effectively integrate resource planning and interchange data into power flow and dynamics cases, defining the type of data required and the units this data is to be reported in. 6.1 Resource Planning Data 6.1.1 Resource Planning Data Requirements i. The Resource Planner (RP), in this case Hydro-Québec Distribution (HQD), shall provide the PC with data regarding all long term generation purchasing agreements between GOs and LSEs, determining the generating resources available to fulfill demand requirements. ii. This data shall be prepared and submitted to the PC in accordance with HQD-HQT agreements (“Ententes sectorielles”) 1, 3 and 6, available at http://transenergie.hydro.qc.ca/ planification_expertise_aff_reglementaires/528.htm 6.1.2 Data Format i. Resource data shall be reported in an Excel table format, as specified in the above mentioned HQD-HQT agreements. 6.1.3 Data Submission Procedure and Schedule i. Data submission is to be performed annually according to the procedures and schedule described in section 7. 6.2 Interchange Schedule An Interchange schedule is a list of scheduled power transfer quantities exchanged between the Québec Interconnection and its neighbouring Area systems (i.e. New England, New York, Ontario, and New Brunswick). These transactions and transmission reservations reflect firm export/import or point-to-point transmission agreements, as per HQT’s Open Access Transmission Tariff (OATT). This information is published on the OATI webOASIS application and provided to the PC by the Transmission Service Provider (TSP). 30 Transmission System Modeling Data Requirements and Reporting Procedures Hydro-Québec TransÉnergie 6.2.1 Interchange Data Requirements i. The TSP shall collect and provide the required interchange data regarding all point-to-point transmission agreements, transmission reservations and spot trades between TOs within the Québec Interconnection as well as TOs of neighbouring NPCC Areas. This information must be reflective of the most updated transaction information available on OASIS. ii. Interchange data shall include: • Transmission service customer name • OASIS reference number • Source and destination substations • Name of interconnection path • Transaction quantity (MW) • Transaction frequency (yearly, monthly, etc.) • Transmission service type • Start and end date of transmission service contract 6.2.2 Data Format i. Interchange data shall be reported in an Excel table format, similar to the sample table in Appendix 6. 6.2.3 Data Submission Procedure and Schedule i. Data submission is to be performed annually according to the procedures and schedule described in section 7. Transmission System Modeling Data Requirements and Reporting Procedures 31 Hydro-Québec TransÉnergie 7. Data Submission Procedure and Schedule 7.1 Data Submission Procedure i. All communication regarding modeling data submission shall be sent to the following email address: te_donneesdemodelisation@hydro.qc.ca. ii. Data submission is to be performed electronically by email, preferably using a secure file transfer server such as Hydro-Québec’s secure FTP server, available to HQ entities at https://ftps.hydro.qc.ca/ and external clients at https://ftps.hydroquebec.com/. iii. TOs owned by HQT may also submit modeling data using Hydro-Québec’s file storage software, Hydro-Doc (Enterprise Connect) or enter future project data directly into MOD using the MOD online application, available at: http://131.195.100.81/MODWeb/login.aspx?ReturnUrl=%2fmodweb%2fDefault.aspx iv. Recertification Process As stipulated in sections 3.1 and 4.1 of the present document, in addition to reporting additions or modifications to modeling data, GOs and TOs of existing facilities must recertify that existing unchanged modeling data is valid. This recertification of modeling data shall be performed on an annual basis, either by resubmitting all required modeling data or by submitting a written confirmation that data has not changed from the previous year’s data submission. The recertification process is presented as follows: v. 32 • Request for recertification: Every year, the PC shall send an email to GOs and TOs requesting the recertification of modeling data for existing generators and transmission system equipment 90 calendar days prior to scheduled data submission deadlines. The PC’s request for recertification will include the modeling information currently maintained by the PC in DSR and MOD. • Recertification response: Recertification of modeling data or information indicating changes to modeling data shall be provided to the PC prior to the data reporting deadline. GOs and TOs must identify all changes or updates to modeling data (including model compatibility updates for PSS/E version upgrades) and submit the changes in accordance to the requirements specified in sections 3 and 4 of the present document. In the case there are no changes to modeling data, GOs and TOs must submit a written confirmation indicating that there are no changes to report and that current modeling data is valid. Technical Concerns and Questions Regarding Submitted Modeling Data Transmission System Modeling Data Requirements and Reporting Procedures Hydro-Québec TransÉnergie a) In the case there are technical concerns with regards to the data submitted, the concerned entity (GO, TO, LSE, RP, etc.) will receive a written notification from the PC or a TP describing the technical basis or reason for the technical concerns. b) Each notified entity shall respond to the notifying PC or TP as follows: • Provide either updated data or an explanation with a technical basis for maintaining the current data; • Provide the response within 90 calendar days of receipt of the notification, unless a longer time period is agreed upon with the PC or TP. 7.2 Data Submission Schedule All concerned entities responsible for providing modeling data shall submit data annually according to the following schedule: Table 7 – Modeling Data Submission Schedule Modeling Data Aggregate Demand Data Generation Data Transmission System Equipment Data Complementary Power System Information Description of Deliverables Steady-state winter peak load forecast Functional Entity Responsible Load Serving Entity Submission Date st June 1 Steady-state summer peak and light load Load Serving Entity forecasts October 1 st Steady-state demand forecast for industrial customer facilities Load Serving Entity October 1 st Total system load forecast Resource Planner October 1 st Recertification of steady-state, dynamics Generator Owners and short-circuit modeling data for existing generating units February 1 st Steady-state, dynamics and short-circuit modeling data for new future planned projects Generator Owners February 1 st Generator facilities outage schedule Generator Owners April 1 st Recertification of steady-state, dynamics Transmission Owners and short-circuit modeling data for existing equipment March 1 st Steady-state, dynamics and short-circuit modeling data for new future planned projects Transmission Owners March 1 st Transmission system equipment outage schedule Reliability Coordinator April 1 st Resource Planning Data Resource Planner April 1 st Interchange Data Transmission Service Provider April 1 st Transmission Planners Transmission System Modeling Data Requirements and Reporting Procedures 33 Hydro-Québec TransÉnergie 7.3 Compliance Violations For entities registered with NERC, failure to submit required modeling data by the prescribed submission schedule and in the requested format may be in violation of the requirements established in NERC’s MOD-032 standard. For more information regarding compliance violations, functional entities may refer to pages 5-11 of the MOD-032-1 standard document, available on NERC’s website at: http://www.nerc.com/pa/Stand/Reliability%20Standards/MOD-032-1.pdf 34 Transmission System Modeling Data Requirements and Reporting Procedures Hydro-Québec TransÉnergie REFERENCES [1] Data for Power System Modeling and Analysis, NERC Reliability Standard MOD-032-1, 2015. [2] Automatic Underfrequency Load Shedding, NERC Standard PRC-006-1, 2015. [3] Demand and Energy Data, NERC Reliability Standard MOD-031-1, 2015. [4] Procedures for System Modeling: Data Requirements & Facility Ratings, NPCC Document C-29, March 2007. [5] F. Bélanger, ing, “Mise à jour des réseaux planifiés,” Hydro-Québec TransÉnergie, Montréal, Québec, September 2015. [6] Hydro-Québec TransÉnergie (July 2012), Démarche à suivre pour un raccordement de centrale au réseau d’Hydro-Québec [Online]. Available : http://www.hydroquebec.com/ transenergie/fr/commerce/pdf/demarche-a-suivre-2012.pdf [7] Hydro-Québec TransÉnergie (February 2009), Transmission Provider Technical Requirements for the Connection of Power Plants to the Hydro-Québec Transmission System [Online]. Available : http://www.hydroquebec.com/transenergie/fr/commerce/pdf/exigence_raccordement_fev_0 9_en.pdf [8] Hydro-Québec TransÉnergie (February 2011), General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System [Online]. Available : http://www.hydroquebec.com/transenergie/fr/commerce/pdf/essais-eoliennes2011-en.pdf. [9] Hydro-Québec TransÉnergie (April 2014), Procedure for PSS/E Model Validation [Online]. Available : http://www.hydroquebec.com/transenergie/fr/commerce/pdf/procedurevalidation-modeles-psse-en.pdf. [10] Hydro-Québec TransÉnergie (December 2008), Technical Requirements for Customer Facilities Connected to the Hydro-Québec Transmission System [Online]. Available : http://www.hydroquebec.com/transenergie/fr/commerce/pdf/ex_inst_client_en.pdf. [11] Ententes sectorielles HQ Distribution / HQ TransÉnergie [Online]. Available FTP : transport.hydro.qc.ca Directory : commerce/commerce/ File : FBack_ententes_sect.htm [12] Siemens Energy Inc. (October 2010), PSSE 32.05 Model Library [Online]. Available FTP : transport.hydro.qc.ca Directory : PTI/PSSE32/DOCS/ModelLibrary File : MODELS.pdf [13] Siemens Energy Inc. (October 2010), PSSE 32.05 Program Operation Manual [Online]. Available FTP : transport.hydro.qc.ca Directory : PTI/PSSE32/DOCS/POM File : POM.pdf Transmission System Modeling Data Requirements and Reporting Procedures 35 Hydro-Québec TransÉnergie APPENDIX 1 – Load Data Reporting Templates 36 Transmission System Modeling Data Requirements and Reporting Procedures Total Demand Forecast Template (Winter) PRÉVISION DE LA CHARGE LOCALE DU TRANSPORTEUR - POINTE D'HIVER (MW) Version du JJ/MM/AAAA 2014-15 Besoins réguliers du Distributeur1 - Consommation des centrales HQP dans BRD = Charge locale du Transporteur Croissance annuelle en % dont Alcan 1 2015-16 2016-17 2017-18 2018-19 2019-20 2020-21 2021-22 2022-23 2023-24 37 892 74 37 818 375 1.0% 92 La définition des besoins réguliers du Distributeur (BRD) se limite aux besoins des clients desservis par le réseau de TransÉnergie (exclusion des besoins des réseaux autonomes). Les BRD incluent la consommation des centrales d'HQP associée à l'électricité patrimoniale. Ils sont après effacement de la bi-énergie résidentielle (tarif DT) et avant interruptions chez les clients de la Grande entreprise. 2015-12-16 H:\deluca\2015\Autres\MOD-032\APPENDIX 1 - Load Data Reporting Templates.xlsx Total Demand Tarification, prévision et caractérisation Vice-présidence - Clientèle Aggregate (per bus/substation) Demand Forecast Template (Winter) Nom_Poste Abitibi Abitibi Abitibi Achigan Achigan Achigan Acton Acton Acton Adamsville Adamsville Adamsville Alain-Grandbois Alain-Grandbois Alain-Grandbois Albanel Albanel Albanel Alma Alma Alma Almaville Almaville Almaville Amos Amos Amos Amqui Amqui Amqui Anne-Hébert Anne-Hébert Anne-Hébert Anse Pleureuse 25 kV Anse Pleureuse 25 kV Anse Pleureuse 25 kV Antoine Lemieux Antoine Lemieux Antoine Lemieux Aqueduc 25 Aqueduc 25 Aqueduc 25 Armagh Armagh Armagh Arthabaska Arthabaska Arthabaska Arthur-Buies Arthur-Buies Arthur-Buies Asbestos Asbestos Asbestos Atwater 12 Atwater 12 Atwater 12 Atwater 25 Atwater 25 Atwater 25 Aubertois Aubertois Aubertois Austin Austin Austin Baie D'urfée 12 Baie D'urfée 12 Baie D'urfée 12 Baie D'urfée 25 Baie D'urfée 25 Baie D'urfée 25 Baie Saint-Paul Baie Saint-Paul Baie Saint-Paul Baie Saint-Paul 315 Baie Saint-Paul 315 Baie Saint-Paul 315 Baie-Trinité Baie-Trinité Baie-Trinité Beauceville Est Beauceville Est Beauceville Est Beaulieu Beaulieu Beaulieu Beaumont 12 Beaumont 12 Bus No. Unité MW MVAR MVA MW MVAR MVA MW MVAR MVA MW MVAR MVA MW MVAR MVA MW MVAR MVA MW MVAR MVA MW MVAR MVA MW MVAR MVA MW MVAR MVA MW MVAR MVA MW MVAR MVA MW MVAR MVA MW MVAR MVA MW MVAR MVA MW MVAR MVA MW MVAR MVA MW MVAR MVA MW MVAR MVA MW MVAR MVA MW MVAR MVA MW MVAR MVA MW MVAR MVA MW MVAR MVA MW MVAR MVA MW MVAR MVA MW MVAR MVA MW MVAR MVA MW MVAR MVA MW MVAR Saison Année V01 Charge V01 Charge V02 Charge V03 Charge V04 Charge V05 Charge P01 Charge P02 Charge P03 Charge P04 Charge P05 Charge P06 Charge P07 Charge P08 Charge P09 Charge P10 Charge P11 Charge P12 Charge P13 Charge P14 Charge P15 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hiver 2009 Hydro-Québec TransÉnergie APPENDIX 2 – List of Approved Dynamics Models A2.1 Standard Library Models Model Name Model Description Developer CBEST EPRI battery energy storage FACTS model PTI-Siemens CDSMS1 American Superconductor DSMES device model PTI-Siemens CGEN1 Third order generator model PTI-Siemens CIMTR1 Induction generator model with rotor flux transients PTI-Siemens CIMTR2 Induction motor model with rotor flux transients PTI-Siemens CIMTR3 Induction generator model with rotor flux transients PTI-Siemens CIMTR4 Induction motor model with rotor flux transients PTI-Siemens CSMEST EPRI superconducting electromagnetic energy storage FACTS model PTI-Siemens CSTATT Static condenser FACTS model PTI-Siemens CSVGN1 SCR controlled static var source model PTI-Siemens CSVGN3 SCR controlled static var source model PTI-Siemens CSVGN4 SCR controlled static var source model PTI-Siemens CSVGN5 WECC controlled static var source model PTI-Siemens CSVGN6 WECC controlled static var source model PTI-Siemens FRECHG Salient pole frequency changer model PTI-Siemens Generator Models GENCLS Classical generator model PTI-Siemens GENDCO Round rotor generator model with dc offset torque component PTI-Siemens GENROE Round rotor generator model PTI-Siemens GENROU Round rotor generator model PTI-Siemens GENSAE Salient pole generator model PTI-Siemens GENSAL Salient pole generator model PTI-Siemens GENTRA Transient level generator model PTI-Siemens Compensator Models COMP Voltage regulator compensating model PTI-Siemens COMPCC Cross compound compensating model PTI-Siemens IEEEVC 1981 IEEE voltage compensating model PTI-Siemens REMCMP Remote bus voltage signal model PTI-Siemens Stabilizer Models BEPSST Transient excitation boosting stabilizer model PTI-Siemens IEE2ST Dual-input signal power system stabilizer model PTI-Siemens IEEEST 1981 IEEE power system stabilizer model PTI-Siemens IVOST IVO stabilizer model PTI-Siemens OSTB2T Ontario Hydro delta-omega power system stabilizer PTI-Siemens OSTB5T Ontario Hydro delta-omega power system stabilizer PTI-Siemens PSS1A IEEE Std. 421.5-2005 PSS1A Single-Input Stabilizer model PTI-Siemens PSS2A 1992 IEEE type PSS2A dual-input signal stabilizer model PTI-Siemens Transmission System Modeling Data Requirements and Reporting Procedures 37 Hydro-Québec TransÉnergie PSS2B IEEE 421.5 2005 PSS2B IEEE dual-input stabilizer model PTI-Siemens PSS3B IEEE Std. 421.5 2005 PSS3B IEEE dual-input stabilizer model PTI-Siemens PSS4B IEEE 421.5(2005) dual-input stabilizer model PTI-Siemens PTIST1 PTI microprocessor-based stabilizer model PTI-Siemens PTIST3 PTI microprocessor-based stabilizer model PTI-Siemens ST2CUT Dual-input signal power system stabilizer model PTI-Siemens STAB1 Speed sensitive stabilizer model PTI-Siemens STAB2A ASEA power sensitive stabilizer model PTI-Siemens STAB3 Power sensitive stabilizer model PTI-Siemens STAB4 Power sensitive stabilizer model PTI-Siemens STABNI Power sensitive stabilizer model type NI (NVE) PTI-Siemens STBSVC WECC supplementary signal for static var system PTI-Siemens Excitation System Models AC7B 38 IEEE 421.5 2005 AC7B excitation system PTI-Siemens AC8B IEEE 421.5 2005 AC8B excitation system PTI-Siemens BBSEX1 Brown-Boveri static excitation system model PTI-Siemens BUDCZT Czech proportional/integral excitation system model PTI-Siemens CELIN ELIN brushless excitation system model PTI-Siemens DC3A IEEE 421.5 2005 DC3A excitation system PTI-Siemens DC4B IEEE 421.5 2005 DC4B excitation system PTI-Siemens EMAC1T AEP Rockport excitation system model PTI-Siemens ESAC1A 1992 IEEE type AC1A excitation system model PTI-Siemens ESAC2A 1992 IEEE type AC2A excitation system model PTI-Siemens ESAC3A 1992 IEEE type AC3A excitation system model PTI-Siemens ESAC4A 1992 IEEE type AC4A excitation system model PTI-Siemens ESAC5A 1992 IEEE type AC5A excitation system model PTI-Siemens ESAC6A 1992 IEEE type AC6A excitation system model PTI-Siemens ESAC8B Basler DECS model PTI-Siemens ESDC1A 1992 IEEE type DC1A excitation system model PTI-Siemens ESDC2A 1992 IEEE type DC2A excitation system model PTI-Siemens ESST1A 1992 IEEE type ST1A excitation system model PTI-Siemens ESST2A 1992 IEEE type ST2A excitation system model PTI-Siemens ESST3A 1992 IEEE type ST3A excitation system model PTI-Siemens ESST4B IEEE type ST4B potential or compounded source-controlled rectifierexciter PTI-Siemens ESURRY Modified IEEE Type AC1A excitation model PTI-Siemens EX2000 EX2000 Excitation System PTI-Siemens EXAC1 1981 IEEE type AC1 excitation system model PTI-Siemens EXAC1A Modified type AC1 excitation system model PTI-Siemens EXAC2 1981 IEEE type AC2 excitation system model PTI-Siemens EXAC3 1981 IEEE type AC3 excitation system model PTI-Siemens EXAC4 1981 IEEE type AC4 excitation system model PTI-Siemens EXBAS Basler static voltage regulator feeding dc or ac rotating exciter model PTI-Siemens EXDC2 1981 IEEE type DC2 excitation system model PTI-Siemens EXELI Static PI transformer fed excitation system model PTI-Siemens Transmission System Modeling Data Requirements and Reporting Procedures Hydro-Québec TransÉnergie EXNEBB Bus or solid fed SCR bridge excitation system model type NEBB (NVE) PTI-Siemens EXNI Bus or solid fed SCR bridge excitation system model type NI (NVE) PTI-Siemens EXPIC1 Proportional/integral excitation system model PTI-Siemens EXST1 1981 IEEE type ST1 excitation system model PTI-Siemens EXST2 1981 IEEE type ST2 excitation system model PTI-Siemens EXST2A Modified 1981 IEEE type ST2 excitation system model PTI-Siemens EXST3 1981 IEEE type ST3 excitation system model PTI-Siemens IEEET1 1968 IEEE type 1 excitation system model PTI-Siemens IEEET2 1968 IEEE type 2 excitation system model PTI-Siemens IEEET3 1968 IEEE type 3 excitation system model PTI-Siemens IEEET4 1968 IEEE type 4 excitation system model PTI-Siemens IEEET5 Modified 1968 IEEE type 4 excitation system model PTI-Siemens IEEEX1 1979 IEEE type 1 excitation system model and 1981 IEEE type DC1 model PTI-Siemens IEEEX2 1979 IEEE type 2 excitation system model PTI-Siemens IEEEX3 1979 IEEE type 3 excitation system model PTI-Siemens IEEEX4 1979 IEEE type 4 excitation system, 1981 IEEE type DC3 and 1992 IEEE type DC3A models PTI-Siemens IEET1A Modified 1968 IEEE type 1 excitation system model PTI-Siemens IEET1B Modified 1968 IEEE type 1 excitation system model PTI-Siemens IEET5A Modified 1968 IEEE type 4 excitation system model PTI-Siemens IEEX2A 1979 IEEE type 2A excitation system model PTI-Siemens IVOEX IVO excitation system model PTI-Siemens OEX12T Ontario Hydro IEEE Type ST1 excitation system with continuous and bang bang terminal voltage limiter PTI-Siemens OEX3T Ontario Hydro IEEE Type ST1 excitation system with semicontinuousand acting terminal voltage limiter PTI-Siemens REXSYS General purpose rotating excitation system model PTI-Siemens MAXEX1 Maximum excitation limiter model PTI-Siemens MAXEX2 Maximum excitation limiter model PTI-Siemens MNLEX1 Minimum excitation limiter model PTI-Siemens MNLEX2 Minimum excitation limiter model PTI-Siemens Excitation Limiter Models MNLEX3 Minimum excitation limiter model PTI-Siemens UEL1 IEEE 421.5 2005 UEL1 under-excitation limiter PTI-Siemens UEL2 IEEE 421.5 2005 UEL2 minimum excitation limiter PTI-Siemens BBGOV1 Brown-Boveri turbine-governor model PTI-Siemens CRCMGV Cross compound turbine-governor model PTI-Siemens Turbine-Governor Model DEGOV Woodward diesel governor model PTI-Siemens DEGOV1 Woodward diesel governor model PTI-Siemens GAST Gas turbine-governor model PTI-Siemens GAST2A Gas turbine-governor model PTI-Siemens GASTWD Gas turbine-governor model PTI-Siemens GGOV1 GE general purpose turbine-governor model PTI-Siemens HYGOV Hydro turbine-governor model PTI-Siemens Transmission System Modeling Data Requirements and Reporting Procedures 39 Hydro-Québec TransÉnergie HYGOV2 Hydro turbine-governor model PTI-Siemens HYGOVM Hydro turbine-governor lumped parameter model PTI-Siemens HYGOVT Hydro turbine-governor traveling wave model PTI-Siemens IEEEG1 1981 IEEE type 1 turbine-governor model PTI-Siemens IEEEG2 1981 IEEE type 2 turbine-governor model PTI-Siemens IEEEG3 1981 IEEE type 3 turbine-governor model PTI-Siemens IEESGO 1973 IEEE standard turbine-governor model PTI-Siemens IVOGO IVO turbine-governor model PTI-Siemens PIDGOV Hydro turbine and governor model PTI-Siemens SHAF25 Torsional-elastic shaft model for 25 masses PTI-Siemens TGOV1 Steam turbine-governor model PTI-Siemens TGOV2 Steam turbine-governor model with fast valving PTI-Siemens TGOV3 Modified IEEE type 1 turbine-governor model with fast valving PTI-Siemens TGOV4 Modified IEEE type 1 speed governing model with PLU and EVA PTI-Siemens TGOV5 Modified IEEE type 1 turbine-governor model with boiler controls PTI-Siemens Two-Terminal DC Line Models CDC1T Two-terminal dc line model PTI-Siemens CDC4T Two-terminal dc line model PTI-Siemens CDC6T Two-terminal dc line model PTI-Siemens CDC6TA Two-terminal dc line model PTI-Siemens CDC7T dc line model PTI-Siemens CDCABT ABB dc line model for Kontek line PTI-Siemens CEELT New Eel River dc line and auxiliaries model. This model internally uses the following models: CHAAUT (auxiliary-signal model), CEEL2T (two-terminal dc line model), and RUNBK (dc line runback model). PTI-Siemens New Eel River dc line model PTI-Siemens CEEL2T Multi-Terminal DC Line Models MTDC1T Multiterminal (five converter) dc line model PTI-Siemens MTDC2T Multiterminal (five converter) dc line model PTI-Siemens MTDC3T Multiterminal (eight converter) dc line model PTI-Siemens VSCDCT Two-terminal VSC dc line model VSC dc Line Model PTI-Siemens Generic Wind Generator Models WT1G1 Direct connected (Type 1) generator PTI-Siemens WT2G1 Induction generator with controlled external rotor resistor (Type 2) PTI-Siemens WT3G1 Doubly-fed induction generator (Type 3) PTI-Siemens WT3G2U Doubly-fed induction generator (Type 3), version 2 PTI-Siemens WT4G1 Wind generator model with power converter (Type 4) PTI-Siemens W4G2U Wind generator model with power converter (Type 4), version 2 PTI-Siemens Generic Wind Electrical Model WT2E1 Rotor resistance control model for Type 2 wind generator PTI-Siemens WT3E1 Electrical control for Type 3 wind generator PTI-Siemens WT4E1 Electrical control models for Type 4 wind generator PTI-Siemens W4E2U Electrical control for Type 4 wind generator, version 2 PTI-Siemens Generic Wind Mechanical Model 40 Transmission System Modeling Data Requirements and Reporting Procedures Hydro-Québec TransÉnergie WT12T1 Two mass turbine model for Type 1 and Type 2 wind generators PTI-Siemens WT3T1 Mechanical system model for Type 3 wind generator PTI-Siemens Generic Wind Pitch Control WT3P1 Pitch control model for Type 3 wind generator PTI-Siemens Generic Wind Aerodynamic Model WT12A1 Pseudo-governor model for Type 1 and Type 2 wind generators PTI-Siemens Switched Shunt Model CHSVCT SVC for switched shunt PTI-Siemens CSSCST SVG for switched shunt PTI-Siemens SWSHNT Switched shunt model PTI-Siemens A2.2 Approved User-Defined Models Model Name Model Description Developer Stabilizer Models MBPS4S User-defined PSS model EXHQSC User-defined Excitation System model for synchronous condensers Hydro-Québec TransÉnergie Excitation System Models Hydro-Québec TransÉnergie Excitation Limiter Models OELHQ User-defined Excitation Limiter Model (TCE) Hydro-Québec TransÉnergie Turbine-Governor Model HQRVW User-defined Hydro turbine-governor model Hydro-Québec TransÉnergie HQRVM User-defined Hydro turbine-governor model Hydro-Québec TransÉnergie HQRVN User-defined Hydro turbine-governor model Hydro-Québec TransÉnergie HQRVC User-defined Hydro turbine-governor model Hydro-Québec TransÉnergie Two-Terminal DC Line Models CHTFWX User-defined Hydro-Québec DC Model Hydro-Québec TransÉnergie CHTRVX User-defined Hydro-Québec DC Model Hydro-Québec TransÉnergie CHTFWD User-defined Hydro-Québec DC Model Hydro-Québec TransÉnergie CHARVS User-defined Hydro-Québec DC Model Hydro-Québec TransÉnergie RSPDC3 User-defined Hydro-Québec DC Model Hydro-Québec TransÉnergie HIGTDC User-defined Hydro-Québec DC Model (High Gate) Hydro-Québec TransÉnergie CMDS User-defined Hydro-Québec DC Model Hydro-Québec TransÉnergie Multi-Terminal DC Line Models NEDCV3 User-defined Multi-Terminal DC Line Model (HQ-NE) VSCDCT Two-terminal VSC dc line model VSC dc Line Model PTI-Siemens CABB02 HVDC Light® Open model version Ov1.1.10 ABB CEmpty HVDC Light® Open model version Ov1.1.10 (Dummy call) ABB Generic Wind Generator Models EXF2 User-defined Wind Generator Model for Enercon E82 Enercon EXS3 User-defined Wind Generator Model for Enercon E82 Enercon E822S3 User-defined Wind Generator Model for Enercon Enercon Transmission System Modeling Data Requirements and Reporting Procedures 41 Hydro-Québec TransÉnergie R21201 User-defined Wind Generator Model for Senvion MM92 Senvion R21301 User-defined Wind Generator Model for Senvion MM82 Senvion Generic Wind Electrical Model EFCU02 User-defined Wind Farm Control Unit Model (Enercon) Enercon RPMU01 Senvion User-defined Power Management Unit Model Senvion Switched Shunt Model CHASVC User-defined SVC Model for synchronous condensers Hydro-Québec TransÉnergie IM_AM1 User-defined SVC Model for shunt reactors Hydro-Québec TransÉnergie IM_CMP User-defined SVC Model (Master) Hydro-Québec TransÉnergie IM_EXC User-defined SVC Model (Slave) Hydro-Québec TransÉnergie SVSMO1U1 User written model for continuously controled SVC PTI-Siemens SVSMO2U1 User written model for discretely controled SVC PTI-Siemens Other Models 42 VFTU1 User-defined Phase Shifting Transformer Model Hydro-Québec TransÉnergie PVGU1 User written generator model to represent photo-voltaic (PV) systems PTI-Siemens PVEU1 User written electrical control model for photo-voltaic (PV) systems PTI-Siemens PANELU1 User written model to represent the linearized model of PV panel’soutput curve PTI-Siemens IRRADU1 User written model to represent the linearized model of PV panel’ssolar irradiance profile. PTI-Siemens Transmission System Modeling Data Requirements and Reporting Procedures Hydro-Québec TransÉnergie APPENDIX 3 – Examples of Siemens-PTI PSS/E Model Library Data sheets Transmission System Modeling Data Requirements and Reporting Procedures 43 PSS®E32.0.5 PSS®E Model Library Generator Model Data Sheets GENSAL 1.21 GENSAL Salient Pole Generator Model (Quadratic Saturation on d-Axis) This model is located at system bus #_____ IBUS, Machine identifier #_____ ID, This model uses CONs starting with #_____ and STATEs starting with #_____ Pm PMECH EFD J, Efd K. VOLT at VT Terminal Bus The machine MVA is _________ for each of units = _________ MBASE. # Speed ISORCE Source Current GENSAL ETERM ANGLE ZSORCE for this machine is _________ + j ________ on the above MBASE. CONs SPEED Value Terminal Voltage Angle Description J T´do (>0) (sec) J+1 Tdo (>0) (sec) J+2 Tqo (>0) (sec) J+3 H, Inertia J+4 D, Speed damping J+5 Xd J+6 Xq J+7 X´d J+8 Xd = Xq J+9 Xl J+10 S(1.0) J+11 S(1.2) Note: Xd, Xq, X´d, Xd, Xq, Xl, H, and D are in pu, machine MVA base. Xq must be equal to Xd. STATEs # Description K E´q K+1 kd K+2 q K+3 speed (pu) K+4 Angle (radians) IBUS, ’GENSAL’, ID, CON(J) to CON(J+11) / Siemens Energy, Inc., Power Technologies International 1-47 PSS®E 32.0.5 ® PSS E Model Library Excitation System Model Data Sheets IEEEX1 6.44 IEEEX1 IEEE Type 1 Excitation System This model is located at system bus #_______ IBUS, Machine identifier #_______ ID, ECOMP This model uses CONs starting with #_______ J, VOTHSG and STATEs starting with #_______ K, VUEL and VAR #_______ L. VOEL CONs # Value EFD Description TR (sec) J J+1 KA J+2 TA (sec) J+3 TB (sec) J+4 TC (sec) J+5 VRMAX or zero J+6 VRMIN J+7 KE or zero J+8 TE (>0) (sec) J+9 KF J+10 TF1 (>0) (sec) J+11 Switch J+12 E1 J+13 SE(E1) J+14 E2 J+15 SE(E2) STATEs K 6-98 IEEEX1 # Description Sensed VT K+1 Lead lag K+2 Regulator output, VR K+3 Exciter output, EFD K+4 Rate feedback integrator Siemens Energy, Inc., Power Technologies International PSS®E 32.0.5 PSS®E Model Library Excitation System Model Data Sheets IEEEX1 VAR # Description KE L IBUS, ’IEEEX1’, ID, CON(J) to CON(J+15) / VREF VS + EC (pu) 1 1 + sTR – + + VERR VRMAX Regulator 1 + sTC KA 1 + sTB 1 + sTA – VRMIN VFB + VR 1 sTE EFD (pu) – SE + KE sKF 1 + sTF1 VS = VOTHSG + VUEL + VOEL Damping Siemens Energy, Inc., Power Technologies International 6-99 PSS®E 32.0.5 PSS®E Model Library Turbine-Governor Model Data Sheets GAST2A 7.6 GAST2A Gas Turbine Model This model is located at system bus #_______ IBUS, Machine identifier #_______ ID, This model uses CONs starting with #_______ J, and STATEs starting with #_______ K, and VARs starting with #_______ L. CONs J # Value SPEED GAST2A PMECH Description W, governor gain (1/droop) (on turbine rating) J+1 X (sec) governor lead time constant J+2 Y (sec) (> 0) governor lag time constant Z, governor mode: J+3 1 Droop 0 ISO J+4 ETD (sec) J+5 TCD (sec) J+6 TRATE turbine rating (MW) J+7 T (sec) J+8 MAX (pu) limit (on turbine rating) J+9 MIN (pu) limit (on turbine rating) J+10 ECR (sec) J+11 K3 J+12 a (> 0) valve positioner J+13 b (sec) (> 0) valve positioner J+14 c valve positioner J+15 f (sec) (> 0) J+16 Kf J+17 K5 J+18 K4 J+19 T3 (sec) (> 0) J+20 T4 (sec) (> 0) J+21 t (> 0) J+22 T5 (sec) (> 0) J+23 af1 Siemens Energy, Inc., Power Technologies International 7-13 PSS®E 32.0.5 ® PSS E Model Library Turbine-Governor Model Data Sheets GAST2A CONs # Value Description J+24 bf1 J+25 af2 J+26 bf2 J+27 cf2 J+28 TR (degree), Rated temperature1 J+29 K6 (pu), Minimum fuel flow J+30 TC (degree), Temperature control1 1 Units can be F or C depending on constants a and b . f1 f1 STATEs # Description K Speed governor K+1 Valve positioner K+2 Fuel system K+3 Radiation shield K+4 Thermocouple K+5 Temperature control K+6 Gas turbine dynamics K+7 Combustor K+8 Combustor K+9 Turbine/exhaust K+10 Turbine/exhaust K+11 Fuel controller delay K+12 Fuel controller delay VARs L # Description Governor reference L+1 Temperature reference flag L+2 Low value select output L+3 Output of temperature control IBUS, ’GAST2A’, ID, CON(J) to CON(J+30) / 7-14 Siemens Energy, Inc., Power Technologies International PSS®E 32.0.5 PSS®E Model Library Turbine-Governor Model Data Sheets GAST2A MAX TC + Temperature Control* T5s + 1 t s Thermocouple 1 T4s + 1 – Radiation Shield K4 + Turbine K5 f1 T3s + 1 Wf1 Reference VAR(L) MAX + W(Xs+1) Ys + Z – MIN Speed Governor Low Value Select Speed Control K6 Fuel Control K3 X e-sT + + Turbine Exhaust Valve Positioner Fuel System a bs + c fs + 1 1 – Kf SPEED (pu deviation) PMECH TRATE MBASE + + 1.0 Wf Fuel Combustor Flow e-sECR Gas Turbine Dynamics 1 TCDS + 1 Turbine X e-sETD f2 Wf2 N f1 = TR - af1(1 - wf1) - bf1(SPEED) f2 = af2 +bf2(wf2) - cf2 (SPEED) *Temperature control output is set to output of speed governor when temperature control input changes from positive to negative. Siemens Energy, Inc., Power Technologies International 7-15 PSS®E 32.0.5 ® PSS E Model Library Generic Wind Generator Model Data Sheets WT3G2U 17.5 WT3G2U Doubly-Fed Induction Generator (Type 3) This model is located at system bus #_______ IBUS, Machine identifier #_______ ID, This model uses CONs starting with #_______ J, and STATEs starting with #_______ K, and VAR #_______ L, and ICON #_______ M. CONs # Value Description J Tiqcmd, Converter time constant for IQcmd J+1 Tipcmd, Converter time constant for IPcmd J+2 KPLL, PLL gain J+3 KIPLL, PLL integrator gain J+4 PLLMAX, PLL max. limit J+5 Prated J+6 VLVPL1, LVPL voltage 1 Low voltage power logic J+7 VLVPL2, LVPL voltage 2 J+8 GLVPL, LVPL gain J+9 VHVRCR, High Voltage Reactive Current (HVRC) logic, pu voltage J+10 CURHVRCR, HVRC logic, current (pu) J+11 RIp_LVPL, Rate of active current change J+12 T_LVPL, Voltage sensor for LVPL, second STATEs Description K Converter lag for Ipcmd K+1 Converter lag for Iqcmd K+2 PLL first integrator K+3 PLL second integrator K+4 Voltage sensor for LVPL VAR L 17-8 # # Description deltaQ, overvoltage correction factor Siemens Energy, Inc., Power Technologies International PSS®E 32.0.5 PSS®E Model Library Generic Wind Generator Model Data Sheets WT3G2U ICON M # Description Number of lumped wind turbines IBUS, ’USRMDL’, ID, ’WT3G2U’, 1, 1, 1, 13, 5,1, ICON(M), CON(J) TO COM(J+12) Siemens Energy, Inc., Power Technologies International 17-9 Hydro-Québec TransÉnergie APPENDIX 4 – Generator Modeling Data Reporting Template 44 Transmission System Modeling Data Requirements and Reporting Procedures Generator Modeling Data Reporting Template Generator Characteristics and Steady-state Data Base Values i Bus No. Installation No. 9000 9001 9002 9003 9004 9005 99990 99991 99992 99993 99994 99995 Power Plant Name Unit No. Plant 1 Plant 1 Plant 1 Plant 2 Plant 2 Plant 3 1 2 3 1 2 1 Machine Type MES Sb (MVA)* Round rotor or salient Initial Commissioning Rated apparent pole Date power Generator Capacties Eb (kV) Rated phase voltage Damper winding (connection method) Coolant Nominal Values Sété (MVA) Shiv (MVA) Coolant temp. Rated power @ Temp. rise at Rated power @ Design ambient rated power ⁰C design ambient temperature ⁰C ⁰C high temp. temp. S2h Pnom (MW) Nominal Real Power En (kV) Nominal Voltage Snom (MVAR) Nominal Apparent Power PF (%) Power Factor H Inertia Constant (for each generating unit) * Machine reactances (in p.u.) and inertia values must all be based on the base apparent power Sb (MVA) of the machine. Generator Dynamics Data - Syncrhonous Machines Unsaturated reactances i Bus No. Installation No. 9000 9001 9002 9003 9004 9005 99990 99991 99992 99993 99994 99995 Power Plant Name Unit No. Plant 1 Plant 1 Plant 1 Plant 2 Plant 2 Plant 3 1 2 3 1 2 1 Saturation coefficients Saturated reactances Model Type Ra @ 25 C R1 Xl X2 Xdu X'du X''du Xqu X'qu X''qu Dynamic Model Standard Library Model or User-written Model Armature resistance per phase Stator forward resistance Positivesequence leakage reactance Negativesequence reactance Unsaturated direct-axis synchronous reactance Unsaturated direct-axis transient reactance Unsaturated direct-axis subtransient reactance Unsaturated quadrature-axis synchronous reactance Unsaturated quadrature-axis transient reactance Unsaturated quadrature-axis subtransient reactance GENSAL Standard X'ds X''ds Saturated direct- Saturated directaxis subtransient axis transient reactance reactance X'qs X''qs Saturated quadrature-axis transient reactance Saturated quadrature-axis subtransient reactance Sgl Sgu Saturation factor Saturation factor at 1 p.u. of at 1.2 p.u. of nominal voltage nominal voltage Time constants T'do T''do T'qo T''qo Direct-axis transient opencircuit time constant Direct-axis subtransient open-circuit time constant Quadrature-axis transient opencircuit time constant Quadrature-axis subtransient open-circuit time constant KF T F1 T F2 Generator Dynamics Data - Asyncrhonous Machines i Bus No. Installation No. 9000 9001 9002 9003 9004 9005 99990 99991 99992 99993 99994 99995 Model Type Power Plant Name Unit No. Plant 1 Plant 1 Plant 1 Plant 2 Plant 2 Plant 3 1 2 3 1 2 1 Dynamic Model Rs Standard Library Model Stator resistance or User-written Model Xs Rr Xr Xm Xlr Xo T'do s Stator leakage reactance Rotor resistance Rotor leakage reactance Magnetizing reactance Locked rotor reactance Open-circuit reactance Direct-axis transient opencircuit time constant Generator slip factor CON2 CON3 CON4 CON5 CON7 CON8 CON9 Voltage Regulator Dynamics Data Model CONS i Bus No. Installation No. 9000 9001 9002 9003 9004 9005 99990 99991 99992 99993 99994 99995 Power Plant Name Unit No. Plant 1 Plant 1 Plant 1 Plant 2 Plant 2 Plant 3 1 2 3 1 2 1 CON1 Dynamic Model Model Type Standard Library Model or User-written Model Dynamic Model VR Type Model Type RR T RH Regulator Standard Library Excitation Type Exciter Model or User-written response ratio Input filter time constant Model CON6 Model ICONS CON10 ICON1 ICON2 ICON3 ICON4 Excitation System Dynamics Data Typical Exciter Parameters, Constants and Coefficients (may vary depending on type of exciter model) i Bus No. Installation No. Power Plant Name Unit No. Plant 1 Plant 1 Plant 1 Plant 2 Plant 2 Plant 3 1 2 3 1 2 1 KA T A1 T A2 VRMAX VRMIN KE TE Regulator gain Regulator time constant 1 (s) Regulator time constant 2 (s) Maximum regulator output Minimum regulator output Exciter selfexcitation Exciter time constant (s) SE.75 max SE max Rotating exciter Rotating exciter saturation at 0.75 saturation at max field voltage max field voltage EFD max EFD min AEX BEX Maximum field voltage (p.u.) Minimum field voltage (p.u.) Derived saturation constant Derived saturation constant CON3 CON4 CON5 Regulator Regulator Regulator stabilizing circuit stabilizing circuit stabilizing circuit time constant (s) time constant (s) gain (s) 9000 9001 9002 9003 9004 9005 99990 99991 99992 99993 99994 99995 IEEET5 Standard Turbine & Speed Governor Dynamics Data Other Constants Typical Governor Parameters, Constants and Coefficients (may vary depending on type of governor model) i Bus No. Installation No. Power Plant Name Unit No. Plant 1 Plant 1 Plant 1 Plant 2 Plant 2 Plant 3 1 2 3 1 2 1 Dynamic Model GOV Model Type R PMAX T1 Control time Maximum Standard Library Governor Type Turbine steadyconstant state regulation turbine output Model or User-written (governor (MW) setting (droop) Model delay) 9000 9001 9002 9003 9004 9005 99990 99991 99992 99993 99994 99995 HQRVN T2 T3 T4 T5 F Hydro reset time constant or pilot valve time Servo time constant or dashpot time constant Steam valve bowl time constant Steam reheat time, hydro water starting time constant (s) or minimum gate velocity (MW/s) Shaft output (p.u.) or maximum gate velocity (MW/s) CON1 CON2 CON6 CON7 User-Written Power System Stabilizer Governor Dynamics Data Typical Stabilizer Parameters, Constants and Coefficients (may vary depending on type of stabilizer model) Other Constants CON8 CON9 CON10 i Bus No. Installation No. Power Plant Name Unit No. Plant 1 Plant 1 Plant 1 Plant 2 Plant 2 Plant 3 1 2 3 1 2 1 Dynamic Model Model Type PSS KQV PSS feedback PSS voltage gain Standard Library (p.u.) Model or User-written (frequency, speed, accelerating Model power) 9000 9001 9002 9003 9004 9005 99990 99991 99992 99993 99994 99995 IEEEST Standard KQS TQ T'Q1 T Q1 PSS speed gain (p.u.) PSS reset time constant (s) First lead time constant (s) First lag time constant (s) T'Q2 T Q2 Second lead time Second lag time constant (s) constant (s) T'Q3 T Q3 VS lim Third lead time constant (s) Third lag time constant (s) PSS output limit setting (p.u.) CON1 CON2 CON3 CON4 CON5 CON6 CON7 CON8 Wind Farm Modeling Data Reporting Template Wind Generator Characteristics and Steady-state Data Single Wind Turbine (WT) Data i Bus No. 9500 9501 Wind Farm Name Wind Farm 1 Wind Farm 2 MES Unit Initial Commissioning No. Date PMAX (MW) Installed Capacity EPOI (kV) PRated (MW) Rated power of one WT Number of WTs WEC Manufacturer Model Name CON1 CON2 CON3 CON4 CON5 Voltage level at point of interconnection QMAX (MVAR) Max Reactive Power Export Collector Network Data QMIN (MVAR) Min Reactive Power Import En (kV) Nominal Voltage Snom (MVAR) Nominal Apparent Power XSource (p.u.) Source Reactance ECollector (kV) RCollector (p.u.) XCollector (p.u.) Voltage level of collector network Equivalent Equivalent Resistance of Reactance of collector network collector network CON7 CON8 CON9 CON10 ICON1 ICON2 CON7 CON8 CON9 CON10 ICON1 ICON2 CON7 CON8 CON9 CON10 ICON1 ICON2 CON7 CON8 CON9 CON10 ICON1 ICON2 1 1 Wind Generator Dynamics Data Model CONS i Bus No. Model Type Wind Farm Name Unit No. 9500 9501 Wind Farm 1 Wind Farm 2 1 1 Dynamic Model Standard Library Model or User-written Model CON1 CON2 CON3 CON4 CON5 Dynamic Model Model Type Standard Library Model or User-written Model CON1 CON2 CON3 CON4 CON5 Dynamic Model Model Type Standard Library Model or User-written Model Model Type CON1 CON2 CON3 CON4 CON5 CON6 Model ICONS ICON3 ICON4 Wind Electrical Model Data Model CONS i Bus No. Wind Farm Name Unit No. 9500 9501 Wind Farm 1 Wind Farm 2 1 1 CON6 Model ICONS ICON3 ICON4 Wind Mechanical Model Data Model CONS i Bus No. Wind Farm Name Unit No. 9500 9501 Wind Farm 1 Wind Farm 2 1 1 CON6 Model ICONS ICON3 ICON4 Wind Pitch Control Model Data Model ICONS Model CONS i U it CON6 ICON3 ICON4 Bus No. Wind Farm Name Unit No. 9500 9501 Wind Farm 1 Wind Farm 2 1 1 Dynamic Model Standard Library Model or User-written Model Wind Aerodynamic Model Data Model CONS i Bus No. Wind Farm Name Unit No. 9500 9501 Wind Farm 1 Wind Farm 2 1 1 Dynamic Model Model Type Standard Library Model or User-written Model CON1 CON2 CON3 CON4 CON5 CON6 Model ICONS CON7 CON8 CON9 CON10 ICON1 ICON2 ICON3 ICON4 Hydro-Québec TransÉnergie APPENDIX 5 – HQT Bus Numbering and Classification A5.1 Bus Number Ranges Bus Number Ranges Bus Types Nominal Voltage Regional Area 1-299 Generator Buses All All 300-699 Substation and Line Buses 315 kV All 700-799 Substation and Line Buses 735 kV All 800-999 Reactive Compensator Buses 735 kV All 1000-1099 Miscellaneous Buses All All 1100-1599 Substation and Line Buses 120 kV All 1600-1699 Substation and Line Buses 161 kV All 1700-1999 Miscellaneous Buses All All 2000-2399 Substation and Line Buses 230 kV All 2400-2499 Substation and Line Buses 69 kV All 2500-2799 Load Buses < 120 kV La Grande 2800-3149 Load Buses < 120 kV Mauricie Nord 3150-3499 Load Buses < 120 kV Manicouagan 3500-3829 Load Buses < 120 kV Montmorency Nord 3860-4149 Load Buses < 120 kV Saguenay 4150-4499 Load Buses < 120 kV Laurentides (Outaouais) 4500-5509 Load Buses < 120 kV Richelieu 5510-5699 Load Buses < 120 kV Mauricie Sud 5700-6349 Load Buses < 120 kV Montmorency Sud 6350-6999 Load Buses < 120 kV Matapédia 7000-7599 Load Buses < 120 kV St-Laurent 7600-8899 Load Buses < 120 kV Laurentides (inc. Laval) 8900-8999 Reserved Buses All All 9000-9999 Miscellaneous Load Buses < 120 kV All 10000-12999 Miscellaneous All All 13000-13999 Generator Buses (Wind Farm) < 6 kV Montmorency 14000-14999 Generator Buses (Wind Farm) < 6 kV Richelieu 15000-15999 Generator Buses (Wind Farm) < 6 kV Mauricie 16000-16999 Generator Buses (Wind Farm) < 6 kV Matapédia 17000-19999 Miscellaneous Buses All All 20000-98999 Transformer tertiary winding bus < 69 kV All 99000-99999 Miscellaneous Buses All All Transmission System Modeling Data Requirements and Reporting Procedures 45 Hydro-Québec TransÉnergie A5.2 NPCC Area Codes Area Number Area ID Area Name 101 ISO-NE ISO New England 102 NYISO New York ISO 103 IESO Independant Electric System Operator (Ontario) 104 HQT Hydro-Québec TransÉnergie 105 NB New Brunswick Power 106 NS Nova Scotia Power 107 CRT Cedars Rapids Transmission A5.3 Québec Interconnection Zoning Codes 46 Zone Number Classification Voltage Level Regional Zone 1 HQT Transmission System 315 kV St-Laurent 2 HQT Transmission System 315 kV Laval 3 HQT Transmission System 161 to 49 kV St-Laurent 4 HQT Transmission System 161 to 49 kV Laval 5 HQT Transmission System 230 kV Richelieu 7 HQT Transmission System 315 kV Rive-Nord 8 HQT Transmission System 315 kV Mauricie Nord, Mauricie Sud 9 HQT Transmission System 315 kV Montmorency Nord, Montmorency Sud 10 HQT Transmission System 230 kV Mauricie Nord 11 HQT Transmission System 230 kV Montmorency Nord 12 HQT Transmission System 161 to 49 kV Rive-Nord 13 HQT Transmission System 161 to 49 kV Mauricie Nord 14 HQT Transmission System 161 to 49 kV Montmorency Nord 15 HQP Generating Facilities N/A Mauricie Nord 16 HQP Generating Facilities N/A Laval, Rive-Nord 17 HQT Transmission System 315 kV Richelieu 18 HQT Transmission System 230 kV Mauricie Sud 19 HQT Transmission System 230 kV Montmorency Sud 20 HQT Transmission System 230 kV Richelieu 21 HQT Transmission System 161 to 49 kV Richelieu 22 HQT Transmission System 161 to 49 kV Mauricie Sud 23 HQT Transmission System 161 to 49 kV Montmorency Sud 24 HQP Generating Facilities N/A Richelieu 25 HQP Generating Facilities N/A Mauricie Sud 26 HQT Transmission System 161 to 49 kV Mauricie Nord 27 HQT Transmission System 315 kV Matapédia 28 HQT Transmission System 230 kV Matapédia 29 HQT Transmission System 161 to 49 kV Matapédia 30 HQP Generating Facilities N/A Matapédia 32 HQT Transmission System 315 kV Manicouagan 33 HQT Transmission System 161 to 49 kV Manicouagan 34 HQP Generating Facilities N/A Manicouagan Transmission System Modeling Data Requirements and Reporting Procedures Hydro-Québec TransÉnergie 36 SCHM Transmission System N/A Manicouagan 37 RTA Transmission System N/A Saguenay 38 RTA Transmission System N/A Saguenay 39 RTA Generating Facilities N/A Saguenay 41 HQT Transmission System 230 kV Saguenay 42 RTA Transmission System 161 to 49 kV Saguenay 43 HQT Transmission System 230 kV Outaouais 44 HQT Transmission System 315 kV Outaouais 45 HQT Transmission System 161 to 49 kV Outaouais 46 HQP Generating Facilities N/A Outaouais 47 ÉLL Transmission System N/A Outaouais 48 HQT Transmission System 315 kV Abitibi 49 HQT Transmission System 161 to 49 kV Abitibi 50 HQP Generating Facilities N/A Abitibi 51 HQT Transmission System 161 to 49 kV Baie James 53 HQT Transmission System 735 kV Manicouagan 54 HQT Transmission System 735 kV Montmorency Nord, Rive-Nord, Saguenay 55 HQT Transmission System 735 kV Mauricie Sud, Montmorency Sud, Richelieu 56 HQT Transmission System 735 kV Laval 57 HQT Transmission System 735 kV Baie James, Rive-Nord, Sageunay 58 HQT Transmission System 315 kV Baie James 59 HQP Generating Facilities N/A Baie James 60 Privately Owned Generating Facilities N/A Abitibi, Baie James 61 Privately Owned Generating Facilities N/A Laval, Rive-Nord 62 Privately Owned Generating Facilities N/A Matapédia 63 Privately Owned Generating Facilities N/A Mauricie Nord, Mauricie Sud 64 Privately Owned Generating Facilities N/A Manicouagan 65 Privately Owned Generating Facilities N/A Montmorency Nord, Montmorency Sud 66 Privately Owned Generating Facilities N/A Richelieu 67 Privately Owned Generating Facilities N/A St-Laurent 68 Privately Owned Generating Facilities N/A Saguenau 69 High Voltage Client Facilites N/A Manicouagan 70 High Voltage Client Facilites N/A Matapédia 71 High Voltage Client Facilites N/A Saguenay 72 High Voltage Client Facilites N/A Outaouais 73 High Voltage Client Facilites N/A Abitibi 74 High Voltage Client Facilites N/A Mauricie Sud 75 High Voltage Client Facilites N/A Richelieu 76 High Voltage Client Facilites N/A Montmorency Nord 77 High Voltage Client Facilites N/A Montmorency Sud 78 High Voltage Client Facilites N/A St-Laurent 79 High Voltage Client Facilites N/A Rive-Nord 80 High Voltage Client Facilites N/A Mauricie Nord 81 Interconnections N/A Outaouais 82 Interconnections N/A Richelieu 83 RTA Transmission System N/A Mauricie Nord 84 RTA Transmission System N/A Richelieu 85 RTA Transmission System N/A Saguenay Transmission System Modeling Data Requirements and Reporting Procedures 47 Hydro-Québec TransÉnergie 48 86 Interconnections N/A Abitibi 87 Interconnections N/A Richelieu 88 Interconnections N/A Matapédia 90 Load Zone < 49 kV Saguenay 91 Load Zone < 49 kV Manicouagan 92 Load Zone < 49 kV St-Laurent 93 Load Zone < 49 kV Richelieu 94 Load Zone < 49 kV Montmorency Nord, Montmorency Sud 95 Load Zone < 49 kV Laval, Outaouais, Rive-Nord 96 Load Zone < 49 kV Mauricie Nord, Mauricie Sud 97 Load Zone < 49 kV Abitibi, Baie James 98 Load Zone < 49 kV Matapédia 99 Reserved for internal usage N/A N/A Transmission System Modeling Data Requirements and Reporting Procedures Hydro-Québec TransÉnergie APPENDIX 6 – Interchange Data Template Transmission System Modeling Data Requirements and Reporting Procedures 49 LISTE DES CLIENTS 20XX POUR LE SERVICE DE TRANSPORT POINT-À-POINT No. dossier Clients Code OASIS Résev. No ref OASIS Code PSE Tag Nom original Mode prépaiement Date signat. Convention AA/MM/JJ POR/POD MW (sortie) Convention LT Début Fin LT Lcrédit /garantie CT Révoquée Actifs Dernier achat achats en 2015 Année Délégué responsable AA/MM/JJ 1 2 3 4 5 6 7 8 9 10 Mise à jour: 23 février 2015 1 HQT-DYMO HQT-LAW HQT-ON HQT-P33C HQT-CORN HQT-NB HQT-DEN HQT-MASS HQT-DER HQT-HIGH HQT-NE EMI-MAHO LAW-HQT ON-HQT OTTO-HQT Q4C-HQT NB-HQT LAB-HQT DEN-HQT MASS-HQT HIGH-HQT NE-HQT MATI-HQT MAFA-HQT MAHO-MATI cacapcité maximale des chemins HQT-CHNO Fin Début À L'ÉTUDE RECALL REDIRECT MW sortie POR / POD client Référence OASIS RÉCEPTIONS LIVRAISONS 65 85 800 1250 345 160 1029 199 1800 50 225 2000 250 470 1250 85 140 785 5150 100 1000 170 2000 250 99 110 LÉGENDE : renouvellement à l'étude Planification et stratégies du réseau principal Direction Planification Hydro-Québec TransÉnergie Division d’Hydro-Québec