Catalog Number Notes FEATURES & SPECIFICATIONS INTENDED USE — An off-line AC power system for the emergency operation of LED HID, incandescent and fluorescent emergency lighting loads that provides full light output for 1-1/2 hours of operation. CONSTRUCTION — Inverter: Solid-state, pulse width modulated inverter, utilizing IGBT technology. Offline uninterruptible system has 2-millisecond transfer time. 4800 to 50000 VA output ratings available. Sinusoidal output waveform has <3% maximum Total Harmonic Distortion for linear load. Operating efficiency is 97% at full load. Input: 120/208V or 277/480V, 3-phase, 4-wire input. Protection: Input circuit breaker standard. Synchronizing slew rate is 1 Hz per second nominal. Harmonic distortion <10%. 65KAIC (amp input current) rating. Output: 120/208V or 277/480V, 3-phase, 4-wire output. Output frequency is 60Hz and is ±0.05Hz during emergency mode. Load power factor is 0.5 lag to 0.5 lead. Cabinet: Free-standing NEMA Type 1. Custom manufactured. 14 gauge steel cabinet with hinged lockable doors. Modular design enables versatile installation. Stackable cabinets on 4800-16700VA. Cooling: Forced air during emergency mode. Conduit entry through 2” knockouts on top or left side. Automatic low battery disconnect; automatic restart upon utility return. Extended run times available. Fuse and fuse/circuit breaker above 2400VA. Charger: Microprocessor controlled for various battery types and temperature compensating (recharge per UL924 spec). Overload capacity to 100% continuous rating, is 115% for five minutes to 125% for 12-line cycle. Lowvoltage battery disconnect, short-circuit proof, current-limiting, fused battery circuit, reverse polarity, brownout protection standard. Self-Diagnostics: Programmable self-diagnostic testing for five minutes monthly and 90 minutes annually. Microprocessor controlled 2 x 20 character display with touch pad (4 x 4) controls, functions and data logging. LCD displays input voltage, output voltage, battery voltage, battery current, output current, output VA, temperature and inverter wattage. Five LED indicators display utility present, battery power, battery charging, system ready and fault. Standard RS232 diagnostic interface. Manual maintenance bypass switch is standard. ORDERING INFORMATION EAC 3FT 3-PHASE FAST-TRANSFER AC POWER SYSTEM Alarm functions: One audible alarm will indicate high/low battery charger fault, near low battery, low battery, load reduction fault, output overload, high/low AC input volts, high ambient temperature, inverter fault, output fault and optional circuit breaker trip. Battery: Available with maintenance-free, sealed lead-calcium or lead-calcium batteries with 20-year life. Discharge cycle of 90 minutes at full load with fully charged batteries. Standard 24-hour battery recharge. LISTINGS — UL listed. Meets UL 924, NFPA 101, NFPA 70, NEC and OSHA. WARRANTY — One-year full warranty within the 48 contiguous states on system electronics. Battery warranty details listed on back. System must be installed within 180 days of battery shipment or warranty will be void. Two-year warranty on systems electronics available with purchase of FSP (factory start-up program). Complete warranty terms located at www.acuitybrands.com/CustomerResources/Terms_and_conditions.aspx Actual performance may differ as a result of end-user environment and application. Note: Specifications subject to change without notice. Example: EAC 3FT 6000 208 OB2 DFC Lead times will vary depending on options selected. Consult with your sales representative. EAC 3FT Family EAC Type Battery type Emergency AC power system (blank) LC20 10-year lead calcium 20-year lead calcium System type 3FT 3-phase fast transfer VA rating 4800 6000 8000 10000 12500 16700 24000 33000 40000 50000 Voltage1 Input/Output 208 120-208/ 120-208 480 277-480/ 277-480 Output circuit breaker2 (blank) OB1 OB2 OB3 OB4 OB5 OB6 OB7 OB8 OB9 0B10 OB11 0B12 None Options (blank) None Battery 12HR 12-hour battery recharge Supervisory RMP Remote meter panel XMBYP External maintenance bypass switch Miscellaneous FSP Factory start-up program DFC Form “C” contacts OTA Output trip alarm NOFF Normally OFF output circuit3 MODEM External modem for RS232 SEISMIC Zone 4 4 Notes 1 Consult factory for other voltage requirements. Special voltages may affect the weight, size and number of cabinets. 2 Standard 20-amp, normally ON unless otherwise specified. 3 Normally off load cannot exceed 20% of total VA rating with any combination of HID loads. 4 2006 Seismic IBC ASCE 7-05 occupancy category 3 sight class D qualification. EMERGENCYEAC-3FT EAC 3FT 3-Phase Fast Transfer AC Power System SPECIFICATIONS CONSTRUCTION Information provided is for lead-calcium batteries only.1 Output Max. input Max. input Battery rating AC 120/208V AC 277/480V voltage Battery Heat loss (VA) (Amps) (Amps) (VDC)1 (Amps) (BTU/HR) Inverter cab. dim. width, height, depth (in/cm)(in/cm)(in/cm)2 Battery cab. dim. width, height, depth (in/cm)(in/cm)(in/cm)2,3 Number of battery cabinets2,3 Inverter weight (lbs/kgs) Battery weight with cabinets (lbs/kgs) Non reflect. aud. noise dBa @ 6 ft. 45 4800 17 7 144 39 245 30/77 47/120 25/64 30/77 47/120 25/64 1 535/243 1098/499 6000 21 9 180 39 300 30/77 47/120 25/64 30/77 47/120 25/64 1 535/243 1320/600 45 8000 28 12 240 39 400 30/77 47/120 25/64 30/77 47/120 25/64 1 535/243 1712/778 45 10000 35 15 144 81 500 30/77 47/120 25/64 30/77 47/120 25/64 2 639/290 2196/997 45 12500 43 19 180 81 660 30/77 47/120 25/64 30/77 47/120 25/64 2 639/290 2640/1198 45 16700 58 25 240 81 840 30/77 47/120 25/64 30/77 47/120 25/64 2 639/290 3424/1554 45 24000 84 36 240 117 1200 44/112 72/183 31/79 48/122 72/183 31/79 1 1250/567 5140/2332 45 33000 115 50 240 160 1500 44/112 72/183 31/79 48/122 72/183 31/79 2 1250/567 7380/3348 45 40000 139 60 240 194 1980 44/112 72/183 31/79 48/122 72/183 31/79 2 1450/658 8700/3947 45 50000 174 75 240 243 2520 44/112 72/183 31/79 48/122 72/183 31/79 2 1450/658 10520/4772 45 Relative system cost Expected life + Maintenance Optimum ambient temperature range (F) Full Sealed lead calcium 1.0 10 years None 32° – 90° 1 year 9 years Sealed lead calcium, 20-year long life (LC20) 1.3 20 years None 32° – 90° 1 year 19 years Notes 1 Consult factory for lead-calcium and 20-year (LC20) battery information. 2 Special voltages may effect the weight, size and number of cabinet. 3 Battery cabinets should be located to the right side of main cabinet. BATTERY COMPARISON Type Warranty Pro rata + Under normal operating conditions SYSTEM DIAGRAM Maintenance Bypass Line Utility Power Line Transformer (4) Battery Charger (1) Battery (2) Inverter (3) Bypass Switch (5) AC No-Break Power Output LEGEND Normal Flow Battery Back-up EAC-3FT EMERGENCY: One Lithonia Way, Conyers, GA 30012 Phone: 800-334-8694 Fax: 770-981-814 www.AcuityBrands.com © 2003-2016 Acuity Brands Lighting, Inc. All rights reserved. Rev. 05/31/16