BY A CR CR O DIGITAL, ASTRONOMICAL TIME CLOCK (TORK OR APPROVED EQUAL) TO BAS SYSTEM THREE-POSITION SELECTOR SWITCH H C OPEN C LOCATE PHOTOCELL ON INSIDE FACE OF ROOF PARAPET FACING NORTH MECHANICALLY-HELD LIGHTING CONTACTOR C L CLOSE 5L1-8 5L1-9 ZONE Z3 PARKING GARAGE GA FIXTURES 5L1-10 5L1-12 ZONE Z7 PARKING GARAGE SLD FIXTURES DIGITAL, ASTRONOMICAL TIME CLOCK (TORK OR APPROVED EQUAL) TO BAS SYSTEM 5L1-3 5L1-4 ZONE Z9 EXTERIOR SLA FIXTURES THREE-POSITION SELECTOR SWITCH SPARE SPARE N S/N 120V CONTROL POWER CKT 6R1-4 CONTROL RELAY A CR CR O H C OPEN C MECHANICALLY-HELD LIGHTING CONTACTOR HKS Architects, Inc. 225 East Robinson St., Suite 405 Orlando, Florida 32801 407-648-9956 #AA F000119 CANOPY CONTROL RELAY 02/19/2016 DATE STAINLESS STEEL 1/4-20 THREADED ROD 120V CONTROL POWER CKT 5R1A-26 Addendum 2 LOCATE PHOTOCELL ON INSIDE FACE OF ROOF PARAPET FACING NORTH REVISIONS NP1 SEALANT (TOP OR BOTTOM OF CANOPY) # STAINLESS STEEL WASHER WITH RUBBER BACKING 2 STAINLESS STEEL WASHER C L CLOSE 6L1-5 6L1-3 EXTERIOR SLA FIXTURES 6L1-7 EXTERIOR SLB FIXTURES SPARE SPARE SPARE SPARE SPARE N SEE SITE PLAN, SHEET E1.101 FOR EXACT INSIDE DIMENSIONS OF ALL PULLBOXES S/N ON AT DUSK/OFF AT DAWN VIA PHOTOCELL FLUORESCENT FIXTURE (TYP) ZONES Z3 AND Z7 - ON AT DUSK THROUGH PHOTOCELL / OFF VIA TIMECLOCK CONTROLLED BY BAS SYSTEM 4 7 NOT USED 8 NOT USED 12 No Scale No Scale No Scale No Scale No Scale 2 NEW SHEET IN ITS ENTIRETY Plot Date: 2/19/2016 3:31:33 PM File Name: C:\Users\holly.nichols\Documents\120084_PS8_DOC_MEP_holly_nichols_tlc-eng_com.rvt No Scale ORANGE COUNTY PUBLIC SCHOOLS NOT USED ELECTRICAL DETAILS NOT USED BUILDING 600 NORMAL EXTERIOR LIGHTING TYPICAL PULLBOX DETAIL ORLANDO, FLORIDA 32809 6 No Scale 3 BLDG. 200, 6501 MAGIC WAY NOT USED BUILDING 500 NORMAL LIGHTING LIGHTING CONTACTOR 6LC1 FACILITIES SERVICES 5 No Scale 2 CORNER OF PARRAMORE AVE AND AMELIA ORLANDO FL, 32805 OCPS PROJ. No: C0076 LIGHTING CONTACTOR 5LC5 DOWNTOWN URBAN PS8 No Scale 1 DESIGN & CONSTRUCTION DIT DECK CANOPY VAPORPROOF FIXTURE MOUNTING C. PROJ. No: C0076 DESIGN IS APPLICABLE FOR SITUATIONS WHERE FIXTURE EITHER FITS BETWEEN CORRIGATION OR BELOW. NOT USED No Scale 9 NOT USED No Scale 10 NOT USED No Scale DRAWN: Author Wayne Edward Allred, P.E. Florida License #45800 CHECKED: Checker 11 ENGINEERING FOR ARCHITECTURE © Copyright 2015 COA 15 Seal 00/00/00 255 S. Orange Avenue Suite 1600 Orlando, FL 32801 DATE: 02/15/16 Phone: 407-841-9050 Fax: 407-425-7367 SHEET NUMBER: www.tlc-engineers.com TLC Engineering for Architecture, Inc. TLC NO: 115023 SCALE: 12" = 1'-0" OCPS DRAWING FILE NAME: E1.537 OF (Total): 0000