DCB-650-C4 Fluorescent Emergency Ballast Installation Instructions ! IMPORTANT ! WHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETY PRECAUTIONS SHOULD ALWAYS BE FOLLOWED, INCLUDING THE FOLLOWING: READ AND FOLLOW ALL SAFETY INSTRUCTIONS 1. To prevent high voltage from being present on red & yellow leads, prior to installation, battery connector must be open. Do not join battery connector until installation is complete and AC power is supplied to the emergency ballast. 2. This product is for use with most 2’ through 8’ (17W - 215W) single or bi-pin fluorescent lamps. 3. Please ensure that all connections are in accordance with the National Electric Code (NEC) and other local regulations (if applicable). 4. To avoid the chance of electric shock, disconnect both normal and emergency power supplies and the battery connector of the emergency ballast before servicing. 5. This emergency ballast is designed for factory or field installation in either the ballast channel, or on top of the fixture. 6. Do not install this device near gas or electric heaters. 7. An AC power source is required (120 or 277VAC, 60Hz) 8. The battery used in this product is a sealed, no-maintenance unit, and is not field replaceable. Contact the manufacturer for information on service. 9. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition. 10. Do not use this emergency ballast for other than intended use. 11. Product servicing should only be performed by qualified service personnel. SAVE THESE INSTRUCTIONS Deco Lighting 14208 S. Western Gardena, CA 90249 (800) 613-DECO Fax: (310) 366-6855 Support: (310) 366-6866 www.getdeco.com NI-Cd CONTAINS NICKEL-CADMIUM RECHARGEABLE BATTERY MUST BE RECYCLED OR DISPOSED OF PROPERLY. 04/18/07 DCB650C4INST-001 INSTALLATION INSTRUCTIONS WARNING: TO PREVENT HIGH VOLTAGE FROM BEING PRESENT ON RED, YELLOW & YELLOW/BLACK OUTPUT LEADS PRIOR TO INSTALLATION, BATTERY CONNECTOR MUST BE OPEN. DO NOT JOIN BATTERY CONNECTOR UNTIL INSTALLATION IS COMPLETE AND AC POWER IS SUPPLIED TO THE EMERGENCY BALLAST. NOTE: Please verify that the necessary branch wiring is available before continuing. An unswitched source of power is required. The emergency ballast must be fed from the same branch circuit as the AC ballast. STEP 1 ► Installing the Emergency Ballast • Disconnect AC power from the fixture. • Select the appropriate wiring diagram to connect the emergency ballast to the AC ballast and lamp. • Refer to Diagram 1 to install the emergency ballast and test/monitor plate. Make electrical connections in accordance with the National Electrical Code and any local regulations. The test/monitor plate may be installed close to the fixture in the ceiling or at a remote location (up to 50 feet). The emergency ballast may be remotely installed up to half the distance the AC ballast manufacturer recommends remoting the AC ballast from the lamp, or up to 50 feet, whichever is less. If no AC ballast is used, the emergency ballast can be remotely mounted up to 50 feet away. Note: A switch box is not supplied. STEP 2 ► Wiring The Emergency Ballast • See page fore more detailed wiring schematics. The emergency ballast can be used with one or two lamp fixtures, and operates one or two lamps in the emergency mode. • Cut fixture wire between the lamp holder and AC ballasts and connect the blue and blue/white emergency ballast wires to the AC ballast and the yellow and yellow/black wires to the lamp holder. • On switched fixtures, an additional unswitched hot (120 or 277VAC) wire must be run to the junction box and connected to the emergency ballast. • The emergency ballast must be connected to an unswitched 120 or 277VAC power source. Do not connect to other voltages. After fixture installation is complete, supply AC power to the emergency ballast, then join the ballast connector. STEP 3 ► Emergency Ballast Quick Check and Labeling • For short-term testing of the emergency function, the battery must be charged for at least one hour. The emergency ballast must be charged for at least 24 hours before conducting a long-term test. • In a readily visible location, attach the label “CAUTION: This unit has more than one power supply connection point. To reduce the risk of electrical shock, disconnect both the branch circuit breakers or fuses and emergency power supplies before servicing.” Standard Installation Diagram 1 2 LAMP HOLDER 3 AC LINE IN JUNCTION BOX Remote Installation SWITCH BOX TEST/MONITOR PLATE WALL OR CEILING CEILING 3 AC LINE IN REFLECTOR EMERGENCY BALLAST WALL OR CEILING 4 CEILING REFLECTOR 4 2 LAMP HOLDER 1 SWITCH BOX TEST/MONITOR PLATE 1 - Flexible conduit (supplied) to connect ballast wires 3 - AC line in 2 - Existing conduit to run existing wires to lamp holder (AC ballast on junction box). If AC ballast is on reflector, run yellow, yellow/black, blue/white and blue wires from emergency ballast through this conduit. 4 - Conduit and junction box (not supplied), necessary for remote installation 1 JUNCTION BOX EMERGENCY BALLAST OPERATION When AC power is supplied to the emergency ballast, the charging light is illuminated; the battery is being charged at this point. When power fails, the emergency ballast will switch over to the battery, and will operate one or two lamps at reduced illumination. This emergency ballast will operate 6W through 42W lamps for a minimum of 90 minutes. MAINTENANCE NOTE: Emergency ballast servicing should only be performed by qualified personnel. No routine maintenance is required to keep the emergency ballast functional, but it should still be checked periodically to confirm that it is working correctly. The following should be performed as specified: 1. Inspect the charging indicator and confirm that it is lit. 2. At 30-day intervals, a short-term discharge test should be performed. The test switch should be held for 30 seconds, and either one or two lamps should be functioning (at reduced illumination). 3. Annually, a long-term (90 minutes) discharge test should be performed. One or two lamps should function for a minimum of 90 minutes WIRING DIAGRAMS The following diagrams are typical schematics only. Consult the factory for other wiring diagrams. NOTE: Emergency ballast and AC ballast must be fed from the SAME BRANCH CIRCUIT. Diagrams for Two-Lamp Emergency Operation TWO (2) 4-PIN COMPACT LAMP RAPID START BALLAST COMMON UNSWITCHED HOT WHITE (CAP UNUSED LEAD) WALL SWITCH WHITE BLACK YELLOW WHITE BLACK 120V OR ORANGE 277V WHT/BLK BLUE BLUE RED RED BALLAST YELLOW BLUE BLU/WHT YEL/BLK YELLOW F L E X A RED LAMP 1 E M E R G E N C Y B A L L A S T F WHT/BLK L VIOLET(+) E X BROWN(-) TWO (2) LAMP RAPID START BALLAST BLK BLK COMMON TEST SWITCH INDICATOR LIGHT UNSWITCHED HOT (CAP UNUSED LEAD) WALL SWITCH WHITE BLACK YELLOW BATTERY CONNECTOR WHT/BLK BLUE BLUE RED RED BLUE BLU/WHT RED YEL/BLK F L E X A YELLOW LAMP 1 LAMP 2 BALLAST YELLOW B RED WHITE WHITE BLACK 120V OR ORANGE 277V E M E R G E N C Y B A L L A S T WHITE BLK F WHT/BLK L VIOLET(+) E X BLK BROWN(-) TEST SWITCH INDICATOR LIGHT B RED WHITE BATTERY CONNECTOR LAMP 2 Diagrams for Emergency Only Fixtures ONE (1) LAMP WITHOUT AC BALLAST COMMON UNSWITCHED HOT WHITE (CAP UNUSED LEAD) CAP CAP CAP WHT/BLK BLUE BLU/WHT YELLOW YEL/BLK LAMP 1 WHITE BLACK 120V OR ORANGE 277V RED F L E X A E M E R G E N C Y B A L L A S T F WHT/BLK L VIOLET(+) E X BROWN(-) ONE (1) 4-PIN COMPACT LAMP WITHOUT AC BALLAST BLK BLK COMMON TEST SWITCH WHITE BLACK 120V OR ORANGE 277V (CAP UNUSED LEAD) CAP CAP INDICATOR LIGHT B RED WHITE UNSWITCHED HOT CAP LAMP 1 BATTERY CONNECTOR WHT/BLK BLUE BLU/WHT YELLOW YEL/BLK RED F L E X A E M E R G E N C Y B A L L A S T WHITE BLK F WHT/BLK L VIOLET(+) E X BLK BROWN(-) TEST SWITCH INDICATOR LIGHT B RED WHITE BATTERY CONNECTOR WIRING DIAGRAMS (cont.) The following diagrams are typical schematics only. Consult the factory for other wiring diagrams. NOTE: Emergency ballast and AC ballast must be fed from the SAME BRANCH CIRCUIT. Diagrams for One-Lamp Emergency Operation TWO (2) 4-PIN COMPACT LAMP RAPID START BALLAST COMMON UNSWITCHED HOT WHITE (CAP UNUSED LEAD) WALL SWITCH WHITE BLACK YELLOW WHITE BLACK 120V OR ORANGE 277V BALLAST YELLOW BLUE BLUE RED RED WHT/BLK BLUE BLU/WHT RED YEL/BLK F L E X A YELLOW LAMP 1 E M E R G E N C Y B A L L A S T F WHT/BLK L VIOLET(+) E X ONE (1) LAMP RAPID START BALLAST BLK BLK COMMON TEST SWITCH INDICATOR LIGHT BROWN(-) UNSWITCHED HOT WHITE BLACK 120V OR ORANGE 277V (CAP UNUSED LEAD) WALL SWITCH WHITE BLACK BALLAST B RED BATTERY CONNECTOR WHITE BLUE BLUE RED RED WHT/BLK BLUE BLU/WHT YELLOW YEL/BLK F L E X A RED E M E R G E N C Y B A L L A S T WHITE BLK F WHT/BLK L VIOLET(+) E X BLK INDICATOR LIGHT BROWN(-) B RED BATTERY CONNECTOR WHITE LAMP 1 TEST SWITCH LAMP 2 ONE (1) LAMP CIRCLINE RAPID START BALLAST COMMON UNSWITCHED HOT WHITE (CAP UNUSED LEAD) WALL SWITCH WHITE BLACK 120V OR ORANGE 277V WHITE BLACK BALLAST RED RED BLUE WHT/BLK BLUE BLU/WHT YEL/BLK F L E X A YELLOW RED LAMP 1 E M E R G E N C Y B A L L A S T F WHT/BLK L VIOLET(+) E X TWO (2) LAMP CIRCLINE RAPID START BALLAST BLK BLK COMMON TEST SWITCH INDICATOR LIGHT BROWN(-) UNSWITCHED HOT (CAP UNUSED LEAD) WALL SWITCH B RED WHITE BLACK BLUE WHITE RED RED BALLAST TWO (2) 4-PIN COMPACT LAMP RAPID START BALLAST (Lamp 2 operates in emergency mode) UNSWITCHED HOT WHITE BLACK 120V OR ORANGE 277V (CAP UNUSED LEAD) WALL SWITCH WHITE BLACK YELLOW BALLAST YELLOW LAMP 1 LAMP 2 WHITE BLUE BLUE RED RED WHT/BLK BLUE BLU/WHT RED YEL/BLK YELLOW F L E X A E M E R G E N C Y B A L L A S T F WHT/BLK L VIOLET(+) E X BROWN(-) BLK INDICATOR LIGHT YEL/BLK A B A L L A S T WHITE BLK F WHT/BLK L VIOLET(+) E X BLK TEST SWITCH INDICATOR LIGHT BROWN(-) B RED BATTERY CONNECTOR WHITE TWO (2) LAMP RAPID START BALLAST (Lamp 2 operates in emergency mode) UNSWITCHED HOT WHITE BLACK 120V OR ORANGE 277V (CAP UNUSED LEAD) WALL SWITCH WHITE BLACK YELLOW YELLOW BATTERY CONNECTOR BLUE BLU/WHT RED F L E X E M E R G E N C Y LAMP 2 COMMON TEST SWITCH WHT/BLK YELLOW BLK B RED WHITE RED RED BLUE WHITE BATTERY CONNECTOR WHITE LAMP 1 COMMON WHITE BLACK 120V OR ORANGE 277V LAMP 1 LAMP 2 BALLAST BLUE BLUE RED RED WHT/BLK BLUE BLU/WHT YEL/BLK YELLOW RED F L E X A E M E R G E N C Y B A L L A S T WHITE BLK F WHT/BLK L VIOLET(+) E X BLK BROWN(-) TEST SWITCH INDICATOR LIGHT B RED WHITE BATTERY CONNECTOR