DCB-650-C4 - Deco Lighting

advertisement
DCB-650-C4
Fluorescent Emergency Ballast
Installation
Instructions
! IMPORTANT !
WHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETY
PRECAUTIONS SHOULD ALWAYS BE FOLLOWED,
INCLUDING THE FOLLOWING:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
1. To prevent high voltage from being present on red & yellow leads, prior to installation,
battery connector must be open. Do not join battery connector until installation is complete
and AC power is supplied to the emergency ballast.
2. This product is for use with most 2’ through 8’ (17W - 215W) single or bi-pin fluorescent
lamps.
3. Please ensure that all connections are in accordance with the National Electric Code (NEC)
and other local regulations (if applicable).
4. To avoid the chance of electric shock, disconnect both normal and emergency power
supplies and the battery connector of the emergency ballast before servicing.
5. This emergency ballast is designed for factory or field installation in either the ballast
channel, or on top of the fixture.
6. Do not install this device near gas or electric heaters.
7. An AC power source is required (120 or 277VAC, 60Hz)
8. The battery used in this product is a sealed, no-maintenance unit, and is not field
replaceable. Contact the manufacturer for information on service.
9. The use of accessory equipment not recommended by the manufacturer may cause an
unsafe condition.
10. Do not use this emergency ballast for other than intended use.
11. Product servicing should only be performed by qualified service personnel.
SAVE THESE INSTRUCTIONS
Deco Lighting
14208 S. Western
Gardena, CA 90249
(800) 613-DECO
Fax: (310) 366-6855
Support: (310) 366-6866
www.getdeco.com
NI-Cd
CONTAINS NICKEL-CADMIUM
RECHARGEABLE BATTERY
MUST BE RECYCLED OR
DISPOSED OF PROPERLY.
04/18/07
DCB650C4INST-001
INSTALLATION INSTRUCTIONS
WARNING: TO PREVENT HIGH VOLTAGE FROM BEING PRESENT ON RED, YELLOW &
YELLOW/BLACK OUTPUT LEADS PRIOR TO INSTALLATION, BATTERY CONNECTOR MUST
BE OPEN. DO NOT JOIN BATTERY CONNECTOR UNTIL INSTALLATION IS COMPLETE AND AC
POWER IS SUPPLIED TO THE EMERGENCY BALLAST.
NOTE: Please verify that the necessary branch wiring is available before continuing. An unswitched source of power is
required. The emergency ballast must be fed from the same branch circuit as the AC ballast.
STEP 1 ► Installing the Emergency Ballast
• Disconnect AC power from the fixture.
• Select the appropriate wiring diagram to connect the emergency ballast to the AC ballast and lamp.
• Refer to Diagram 1 to install the emergency ballast and test/monitor plate. Make electrical connections
in accordance with the National Electrical Code and any local regulations. The test/monitor plate may be
installed close to the fixture in the ceiling or at a remote location (up to 50 feet). The emergency ballast
may be remotely installed up to half the distance the AC ballast manufacturer recommends remoting the
AC ballast from the lamp, or up to 50 feet, whichever is less. If no AC ballast is used, the emergency ballast
can be remotely mounted up to 50 feet away.
Note: A switch box is not supplied.
STEP 2 ► Wiring The Emergency Ballast
• See page fore more detailed wiring schematics. The emergency ballast can be used with one or two lamp
fixtures, and operates one or two lamps in the emergency mode.
• Cut fixture wire between the lamp holder and AC ballasts and connect the blue and blue/white emergency
ballast wires to the AC ballast and the yellow and yellow/black wires to the lamp holder.
• On switched fixtures, an additional unswitched hot (120 or 277VAC) wire must be run to the junction box
and connected to the emergency ballast.
• The emergency ballast must be connected to an unswitched 120 or 277VAC power source. Do not connect
to other voltages. After fixture installation is complete, supply AC power to the emergency ballast, then join
the ballast connector.
STEP 3 ► Emergency Ballast Quick Check and Labeling
• For short-term testing of the emergency function, the battery must be charged for at least one hour. The
emergency ballast must be charged for at least 24 hours before conducting a long-term test.
• In a readily visible location, attach the label “CAUTION: This unit has more than one power supply
connection point. To reduce the risk of electrical shock, disconnect both the branch circuit breakers or
fuses and emergency power supplies before servicing.”
Standard Installation
Diagram 1
2
LAMP
HOLDER
3
AC
LINE IN
JUNCTION
BOX
Remote Installation
SWITCH
BOX
TEST/MONITOR
PLATE
WALL OR
CEILING
CEILING
3
AC
LINE IN
REFLECTOR
EMERGENCY BALLAST
WALL OR
CEILING
4
CEILING
REFLECTOR
4
2
LAMP
HOLDER
1
SWITCH
BOX
TEST/MONITOR
PLATE
1 - Flexible conduit (supplied) to connect ballast wires
3 - AC line in
2 - Existing conduit to run existing wires to lamp holder (AC ballast on junction box).
If AC ballast is on reflector, run yellow, yellow/black, blue/white and blue wires from
emergency ballast through this conduit.
4 - Conduit and junction box (not supplied), necessary for
remote installation
1
JUNCTION
BOX
EMERGENCY BALLAST
OPERATION
When AC power is supplied to the emergency ballast, the charging light is illuminated; the battery is being charged at
this point. When power fails, the emergency ballast will switch over to the battery, and will operate one or two lamps
at reduced illumination. This emergency ballast will operate 6W through 42W lamps for a minimum of 90 minutes.
MAINTENANCE
NOTE: Emergency ballast servicing should only be performed by qualified personnel.
No routine maintenance is required to keep the emergency ballast functional, but it should still be checked periodically to
confirm that it is working correctly. The following should be performed as specified:
1. Inspect the charging indicator and confirm that it is lit.
2. At 30-day intervals, a short-term discharge test should be performed. The test switch should be held
for 30 seconds, and either one or two lamps should be functioning (at reduced illumination).
3. Annually, a long-term (90 minutes) discharge test should be performed. One or two lamps should
function for a minimum of 90 minutes
WIRING DIAGRAMS
The following diagrams are typical schematics only. Consult the factory for other wiring diagrams.
NOTE: Emergency ballast and AC ballast must be fed from the SAME BRANCH CIRCUIT.
Diagrams for Two-Lamp Emergency Operation
TWO (2) 4-PIN COMPACT LAMP RAPID START BALLAST
COMMON
UNSWITCHED HOT
WHITE
(CAP UNUSED LEAD)
WALL
SWITCH
WHITE
BLACK
YELLOW
WHITE
BLACK 120V
OR
ORANGE 277V
WHT/BLK
BLUE
BLUE
RED
RED
BALLAST
YELLOW
BLUE
BLU/WHT
YEL/BLK
YELLOW
F
L
E
X
A
RED
LAMP 1
E
M
E
R
G
E
N
C
Y
B
A
L
L
A
S
T
F WHT/BLK
L VIOLET(+)
E
X
BROWN(-)
TWO (2) LAMP RAPID START BALLAST
BLK
BLK
COMMON
TEST
SWITCH
INDICATOR
LIGHT
UNSWITCHED HOT
(CAP UNUSED LEAD)
WALL
SWITCH
WHITE
BLACK
YELLOW
BATTERY
CONNECTOR
WHT/BLK
BLUE
BLUE
RED
RED
BLUE
BLU/WHT
RED
YEL/BLK
F
L
E
X
A
YELLOW
LAMP 1
LAMP 2
BALLAST
YELLOW
B RED
WHITE
WHITE
BLACK 120V
OR
ORANGE 277V
E
M
E
R
G
E
N
C
Y
B
A
L
L
A
S
T
WHITE
BLK
F WHT/BLK
L VIOLET(+)
E
X
BLK
BROWN(-)
TEST
SWITCH
INDICATOR
LIGHT
B RED
WHITE
BATTERY
CONNECTOR
LAMP 2
Diagrams for Emergency Only Fixtures
ONE (1) LAMP WITHOUT AC BALLAST
COMMON
UNSWITCHED HOT
WHITE
(CAP UNUSED LEAD)
CAP
CAP
CAP
WHT/BLK
BLUE
BLU/WHT
YELLOW
YEL/BLK
LAMP 1
WHITE
BLACK 120V
OR
ORANGE 277V
RED
F
L
E
X
A
E
M
E
R
G
E
N
C
Y
B
A
L
L
A
S
T
F WHT/BLK
L VIOLET(+)
E
X
BROWN(-)
ONE (1) 4-PIN COMPACT LAMP WITHOUT AC BALLAST
BLK
BLK
COMMON
TEST
SWITCH
WHITE
BLACK 120V
OR
ORANGE 277V
(CAP UNUSED LEAD)
CAP
CAP
INDICATOR
LIGHT
B RED
WHITE
UNSWITCHED HOT
CAP
LAMP 1
BATTERY
CONNECTOR
WHT/BLK
BLUE
BLU/WHT
YELLOW
YEL/BLK
RED
F
L
E
X
A
E
M
E
R
G
E
N
C
Y
B
A
L
L
A
S
T
WHITE
BLK
F WHT/BLK
L VIOLET(+)
E
X
BLK
BROWN(-)
TEST
SWITCH
INDICATOR
LIGHT
B RED
WHITE
BATTERY
CONNECTOR
WIRING DIAGRAMS (cont.)
The following diagrams are typical schematics only. Consult the factory for other wiring diagrams.
NOTE: Emergency ballast and AC ballast must be fed from the SAME BRANCH CIRCUIT.
Diagrams for One-Lamp Emergency Operation
TWO (2) 4-PIN COMPACT LAMP RAPID START BALLAST
COMMON
UNSWITCHED HOT
WHITE
(CAP UNUSED LEAD)
WALL
SWITCH
WHITE
BLACK
YELLOW
WHITE
BLACK 120V
OR
ORANGE 277V
BALLAST
YELLOW
BLUE
BLUE
RED
RED
WHT/BLK
BLUE
BLU/WHT
RED
YEL/BLK
F
L
E
X
A
YELLOW
LAMP 1
E
M
E
R
G
E
N
C
Y
B
A
L
L
A
S
T
F WHT/BLK
L VIOLET(+)
E
X
ONE (1) LAMP RAPID START BALLAST
BLK
BLK
COMMON
TEST
SWITCH
INDICATOR
LIGHT
BROWN(-)
UNSWITCHED HOT
WHITE
BLACK 120V
OR
ORANGE 277V
(CAP UNUSED LEAD)
WALL
SWITCH
WHITE
BLACK
BALLAST
B RED
BATTERY
CONNECTOR
WHITE
BLUE
BLUE
RED
RED
WHT/BLK
BLUE
BLU/WHT
YELLOW
YEL/BLK
F
L
E
X
A
RED
E
M
E
R
G
E
N
C
Y
B
A
L
L
A
S
T
WHITE
BLK
F WHT/BLK
L VIOLET(+)
E
X
BLK
INDICATOR
LIGHT
BROWN(-)
B RED
BATTERY
CONNECTOR
WHITE
LAMP 1
TEST
SWITCH
LAMP 2
ONE (1) LAMP CIRCLINE RAPID START BALLAST
COMMON
UNSWITCHED HOT
WHITE
(CAP UNUSED LEAD)
WALL
SWITCH
WHITE
BLACK 120V
OR
ORANGE 277V
WHITE
BLACK
BALLAST
RED
RED
BLUE
WHT/BLK
BLUE
BLU/WHT
YEL/BLK
F
L
E
X
A
YELLOW
RED
LAMP 1
E
M
E
R
G
E
N
C
Y
B
A
L
L
A
S
T
F WHT/BLK
L VIOLET(+)
E
X
TWO (2) LAMP CIRCLINE RAPID START BALLAST
BLK
BLK
COMMON
TEST
SWITCH
INDICATOR
LIGHT
BROWN(-)
UNSWITCHED HOT
(CAP UNUSED LEAD)
WALL
SWITCH
B RED
WHITE
BLACK
BLUE
WHITE
RED
RED
BALLAST
TWO (2) 4-PIN COMPACT LAMP RAPID START BALLAST
(Lamp 2 operates in emergency mode)
UNSWITCHED HOT
WHITE
BLACK 120V
OR
ORANGE 277V
(CAP UNUSED LEAD)
WALL
SWITCH
WHITE
BLACK
YELLOW
BALLAST
YELLOW
LAMP 1
LAMP 2
WHITE
BLUE
BLUE
RED
RED
WHT/BLK
BLUE
BLU/WHT
RED
YEL/BLK
YELLOW
F
L
E
X
A
E
M
E
R
G
E
N
C
Y
B
A
L
L
A
S
T
F WHT/BLK
L VIOLET(+)
E
X
BROWN(-)
BLK
INDICATOR
LIGHT
YEL/BLK
A
B
A
L
L
A
S
T
WHITE
BLK
F WHT/BLK
L VIOLET(+)
E
X
BLK
TEST
SWITCH
INDICATOR
LIGHT
BROWN(-)
B RED
BATTERY
CONNECTOR
WHITE
TWO (2) LAMP RAPID START BALLAST
(Lamp 2 operates in emergency mode)
UNSWITCHED HOT
WHITE
BLACK 120V
OR
ORANGE 277V
(CAP UNUSED LEAD)
WALL
SWITCH
WHITE
BLACK
YELLOW
YELLOW
BATTERY
CONNECTOR
BLUE
BLU/WHT
RED
F
L
E
X
E
M
E
R
G
E
N
C
Y
LAMP 2
COMMON
TEST
SWITCH
WHT/BLK
YELLOW
BLK
B RED
WHITE
RED
RED
BLUE
WHITE
BATTERY
CONNECTOR
WHITE
LAMP 1
COMMON
WHITE
BLACK 120V
OR
ORANGE 277V
LAMP 1
LAMP 2
BALLAST
BLUE
BLUE
RED
RED
WHT/BLK
BLUE
BLU/WHT
YEL/BLK
YELLOW
RED
F
L
E
X
A
E
M
E
R
G
E
N
C
Y
B
A
L
L
A
S
T
WHITE
BLK
F WHT/BLK
L VIOLET(+)
E
X
BLK
BROWN(-)
TEST
SWITCH
INDICATOR
LIGHT
B RED
WHITE
BATTERY
CONNECTOR
Download