QUICKTRONIC® Emergency Ballasts 1000 Lumens

advertisement
www.sylvania.com
QUICKTRONIC® Emergency Ballasts
1000 Lumens
1 or 2 Lamp Emergency Operation
Downlighting Series
Lamp/Emergency Ballast Guide
T4 Compact (4-pin)
CF5S/E, CF7S/E, CF9S/E, CF13S/E,
CF13DD/E, CF13DT/E, FT18DL, CF18DF,
FT24DL, CF24DL, CF26DD/E, CF26DT/E,
CF32DT/E, FT36DL, CF36DF, FT40DL,
CF42DT/E, FT50DL, FT55DL, CF57DT/E,
CF70DT/E
One or two lamp(s) in a fixture can
be illuminated.
SYLVANIA QUICKTRONIC® EMERGENCY
BALLASTS enable an existing compact
fluorescent downlighting fixture to
operate as both an emergency egress
lighting fixture as well as a normal
lighting fixture. During a power loss,
the emergency ballast automatically
switches the fixture to emergency mode
and continues to operate one or two
lamp(s) at reduced lumen output for at
least 90 minutes.
These Emergency Ballasts can be installed
as part of a fixture by an OEM or added to
an existing fixture during a retrofit.
Key System Features
•
•
•
•
•
•
•
•
•
•
90 minute emergency operation
Integrated test switch and pilot light
Automatic battery recharge
Dual Input Voltage (120V/277V)
Designed specifically for
downlighting applications
Sealed, maintenance-free, hightemperature nickel cadmium battery
UL Listed as “Emergency Lighting
and Power Equipment”
Meets or exceeds all National
Electric Code (NEC) requirements
Meets or exceeds NFPA 101/Life
Safety Code (LSC) requirements for
Emergency Lighting
5 year warranty
Application Information
SYLVANIA QUICKTRONIC
EMERGENCY BALLASTS
are ideally suited for:
• Commercial
• Retail
• Offices
• Wherever emergency illumination
is required
ECS107 – 8/2009
This series has dual input voltage (120 or
277V) and it supports many lamp types
and wattages.
A single pole test switch and charge
indicator accessory kit is supplied
with each unit.
Each SYLVANIA QUICKTRONIC Emergency
Ballast comes with the SYLVANIA Total
System Solution that includes AC lamp
ballast and emergency ballast compatibility.
AVERAGE INITIAL LUMENS
System Information
• Unit can be remote mounted up to half
the distance recommended by the
ballast manufacturer or 50 feet,
whichever is less.
• Unit can be wired into building circuit in
one of two ways: on night light circuit
(permanently energized) or on
switchable circuit (unswitched circuit to
the battery charger and switched circuit
to the fixture ballast).
Lamp Type
T4 Compact (4-pin)
Initial Lumens
1 Lamp
2 Lamps
Lamp Base
OSI Example
2G7
DULUX® S/E CF9DS/E 9W
Contact SYLVANIA
2GX7
DULUX S/E CF13DS/E 13W
Contact SYLVANIA
GX24q-2
DULUX D/E CF18DD/E/8 18W
675
750
GX24q-3
DULUX D/E CF26DD/E/8 26W
790
900
GX24q-3
DULUX T/E CF26DT/E/IN/8 26W
412
749
GX24q-3
DULUX T/E CF32DT/E/IN/8 32W
657
1038
GX24q-3
DULUX T/E CF42DT/E/IN/8 42W
948
N/A
QUICKTRONIC® EMERGENCY BALLASTS
Application Examples
TYPICAL STEPS REQUIRED TO DETERMINE EMERGENCY BALLASTED FIXTURE SPACING
(1) Codes: What national, state, and local codes are required? Determines minimum illuminance and average luminance
(2) Path: What is the space layout and proposed egress path? Specs include ceiling height, egress path width, space reflectances
(3) Fixtures: What fixtures and lamps are used?
Photometric data determines how much light will illuminate egress path
(4) Pick: Propose an emergency ballast.
Discount average initial lumens for life and temperature
(5) Calc: Calculate the emergency ballasted fixture spacing.
Run calculations with above data
1 FC average
Example 1: 100 Foot Corridor
0.1 FC minimum
Codes: LSC minimum 0.1FC and average 1.0FC
Path: 9' ceiling, 100'x8' corridor, reflectances of
80/50/20, egress path 3' wide
CORRIDOR
33'
Fixtures: Common CF downlight fixture with
2xCF26DD/E Lamps
33'
Pick: QTEB2L1000-DL-120/277 with 900 lumens
running two lamps
Calc: 33' between emergency fixtures
1 FC average
0.1 FC minimum
OPEN OFFICE
Example 2: 100 x 100 Foot Open Office
Codes: LSC minimum 0.1FC and average 1.0FC
Path: 9' ceiling, 100x100' space, reflectances of
80/50/20, egress path 3' wide
28'
28'
28'
Fixtures: Common CF downlight fixture with
2xCF26DD/E Lamps
Pick: QTEB2L1000-DL-120/277 with 900 lumens
running two lamps
Calc: 28' between emergency fixtures
Accessories
Test switch/charge indicator harness:
Black/White = 36"
End-of-Life Adapter (optional):
Black/White = 5.5"
Blue, Yellow, Gray, Violet = 5.25"
QUICKTRONIC® EMERGENCY BALLASTS
Example Wiring Diagrams
ONE FOUR-PIN COMPACT LAMP PROGRAM START / DIMMING BALLAST
CONNECT 120 OR 277 TO
SWITCHED OR UNSWITCHED
BLACK
WHITE
WHT/RED
WHT/RED
WHITE
BLACK
1 LAMP
PROGRAM START/
DIMMING BALLAST
BLUE
BLUE
BLUE
BLU/WHT
NEUTRAL
OPTIONAL
END-OF-LIFE
ADAPTER
WHITE
RED
RED
YELL/BLK
RED
YELLOW
EMERGENCY BALLAST
BLACK
ORANGE
TEST SWITCH/
PILOT LIGHT
NEUTRAL
120 VAC
BATTERY PACK INPUT
UNSWITCHED ONLY
277 VAC
USE PROPER VOLTAGE TAP
AND CAP UNUSED LEAD
ORANGE
ORANGE
NORMAL / EMERGENCY LAMP
LAMP SELECTOR
TWO FOUR-PIN COMPACT LAMP PROGRAM START / DIMMING BALLAST
BLACK
WHITE
WHT/RED
WHT/RED
BLUE
BLACK
2 LAMP
PROGRAM START/
DIMMING BALLAST
YELLOW
YELLOW
OPTIONAL
END-OF-LIFE
ADAPTER
BLUE
BLUE
WHITE
NEUTRAL
BLU/WHT
YELL/BLK
RED
YELLOW
RED
RED
EMERGENCY BALLAST
WHITE
BLACK
NEUTRAL
120 VAC
ORANGE
277 VAC
ORANGE
B
NORMAL / EMERGENCY LAMP
ORANGE
LAMP SELECTOR
BLUE
A
NORMAL / EMERGENCY LAMP
Specifications subject to change without notice.
TEST SWITCH/
PILOT LIGHT
CONNECT TO POINT Aì ” FOR ONE LAMP OR
“B” FOR TWO LAMP EMERGENCY OPERATION.
SEE CONNECTOR TABLE FOR TWO LAMP
EMERGENCY OPERATION.
BATTERY PACK INPUT
UNSWITCHED ONLY
USE PROPER VOLTAGE TAP
AND CAP UNUSED LEAD
Emergency Ballast
SPECIFICATION DATA
Catalog #
Date
Type
Project
Prepared by
Comments
Downlighting Series
QUICKTRONIC® Emergency Ballasts
Max.
Input
Current
(Amps)
Average
Initial Lumens
During
Emergency
Operation (lm)
No. of
Lamps
Warranty
Input
Power
(Watts)
0.27/0.25
415-1000
1 or 2
5 year
3.3W/3.2W
Description
Input
Voltage
(VAC)
45106
QTEB2L1000-DL-120/277
120/277
45116
QTEB-EOLA-TSI
End Of Life Adapter - Test switch interface - Suitable for T5 and T4 Systems with EOL circuits
Item
Number
COMPETITIVE CROSS REFERENCE
SYLVANIA
QTEB2L1000
ALP
EFP42EMA
BIG BEAM
EPLB42
BODINE
B94C
CARPENTER
CP-5
CHLORIDE
CFPPL-42
DAYBRITE
DEB9
DUALITE
UFO-12
EMERGILITE
FPDL 10-42
ENCORE
EP94
EXITRONIX
XEB42CF
HIGHLITES
211
HUBBELL
N/A
IOTA
I-42-A
LIGHTALARMS
AM20
LIGHTGUARD
LF750-4P
MULE
MF40-94
PATHWAY
FPLT
PRESCOLITE
EFCFP13C/32C-4P
SIDELITE
S28C
SILTRON
UP42-FC
SURELITES
FBP-2-40C
**Cross Reference is for reference only. Please check datasheets before installation.**
Specifications
Circuit Type: 1 or 2 Lamp Emergency
Operation, see chart
AC Input:
Input Voltage: 120V or 277V
Max. Input Current: see chart
Fed from the same branch circuit
as primary ballast
Battery:
Optimum Temp:1 32-100°F
Shelf Life:2 3 years
Expected Battery Life:2 7-9 years
Standards:
UL Listed
For sealed and gasketed fixtures
UL924, NFPA 101, NEC and OSHA
illumination standards
Housing:
Black, 20-gauge steel, permanently
sealed housing
Dimensions
Can Size
CL x CW x CH
Can Mounting
Qty
Weight
Length (CML) (per case) each (lbs)
1
QTEB2L1000/DL/UNV
13.625" x 3.19" x 1.69"
13.125"
8
5
2
Can Mounting Width (CMW): 2.0"
Can Length (CL): 13.625"
* with hood: 17.625"
Can Mounting Length (CML): 13.125"
* with hood: 17.25"
* incl. minimum can/hood overlap of 0.5"
Optimum ambient temperature range
where unit will provide capacity for 90
minutes. Higher and lower temperatures
affect life and capacity.
At 77°F. Emergency Ballast must be fully
charged within 3 years of manufacture
date in order to ensure battery functionality.
CH
CL
CL w/hood
CML
CML w/hood
System Life / Warranty
This OSRAM SYLVANIA Emergency
Ballast is covered by a full five year
customer satisfaction warranty.
CW
CMW
Item Number
45106 QTEB 2L 1000 - DL - 120/277
Voltage
QUICKTRONIC Emergency Ballast
Application
Number of Lamps Supported
(2L = 1 or 2 lamps)
Average Initial Lumens
(Emergency Operation)
OSRAM SYLVANIA
National Customer
Service and Sales Center
1-800-LIGHTBULB
(1-800-544-4828)
www.sylvania.com
SYLVANIA,
The System Solution and See the World in a New Light are registered trademarks of OSRAM SYLVANIA, Inc. QUICKTRONIC and DULUX are registered trademarks of OSRAM GmbH.
Information subject to change without notice.