Edco Sheets

advertisement
Surge Protection
For Business-Critical ContinuityTM
Edco PC642 Series
Zone/Loop/Data
The Ed co PC642 Series surge suppressor is a two- pair pair (four wire) module
i mpl em ent i ng thre e- stage hybrid technology. This module add resses over- vo l tage
t ra n s ients with gas tub es and silicon ava la n che components. In addi t io n, sneak and
fault cu rrents are mitigated with reset table fuses (PTCs). The PTCs increase res i stance
several orders of magnitude when over-currents exceed safe levels. A normal state
resumes when over- cu rrents are removed. The ability to sel f- resto re in this manner
significantly increases suppressor performance and survivability.
The Edco PC642 card edge module is gold-plated, double sided and is designed to
mate with the the Edco PCB1B gold-plated female terminal connector (sold separately).
When snapped together, the data circuits “pass thru” the prote ctor in a serial fashion
f rom the four “Field Side” terminals to the four “Electro n ics Sid e” termi na ls .
Term i nals 1 or 10 of the PCB1B must be at tached to Buildi ng-Approved Grou nd per
Edco Technical Bulletin # 2015.
PCB!B-WKEY may be ord ered along with PC642 module by addi ng “-Kit” to the end
of the module part number (Example: PC642C-036LC-KIT).
Features
497B
Three-stage hybrid protection
Sneak/fault current protection
Resettable fuses – PTCs
Low capacitance option
General Technical Specifications
Plug-in module
Operating Voltage
5, 12, 18, 24, 30, 36, 43, 52, 180 VDC
Clamping Voltage
8, 15, 20, 30, 36, 43, 50, 60, 270 VDC
Operating Current
0.15 A
Peak Surge Current
Frequency Range
Insertion Loss
SPD Technology
Connection Type
Operating Temperature
Dimensions (Inches)
Weight
Certifications
10 kA (8 x 20 µs)
Requires Edco PCB1B base
Fast response time
UL listed 497B
0 to 20 MHz
< 0.1 dB at 20 MHz
PC642PTU (Pass Thru Unit)
available for troubleshooting
GDT, SAD, w/Series PTC
Terminal block
w/compression lugs
Terminals accept up to 10 AWG
5 year warranty
-40°C to +85°C
2H x 1W x 2.5L
(PC642 + PCB1B Base)
1 oz
UL 497B
Caut ion: The hybr id design of this
product includes series resistance. Do not
place this product in service on any signal
l i ne capable of supply i ng more than 150
milliamperes continuously.
Installation Instructions
Terminal Assignments
Grou nd Terminal 1 or 10 to Buildi ng Approved Grou nd.
DO NOT daisy chain grounds. NOT intended for shield termination.
Install ground in accordance with all applicable codes.
Read and Understa nd These Inst ru ct ion s:
These prote cto rs are intended for indoor use on communication loop circuits wh ich have been iso lated from the Publ ic Switch Tel ephone
Netwo rk.
The communication loop circuits shall not be ex p osed to accidental co ntact with the electric light or power co nd ucto rs. The protectors
shall be installed per the applicable requirem ents of the National Elect ric Code, ANSI/NFPA 70.
Ordering Information
How to Specify the Appropriate Model
APPLICATION:
RS485, RS422:
PC642C-008LC & PCB1B
RS232:
PC642C-020 & PCB1B
E- N ET, 10 BASE T:
PC642C-030LC & PCB1B
4–20ma:
PC642C-036 & PCB1B
OPTION:
DIN Rail Kit Available
Order Pa rt # 11604KIFPC
Emerson Network Power.
The global leader in enabling
Business-Critical ContinuityTM.
AC Power
E m b e dded Comput i ng
Outside Plant
Racks and Integrated Cabinets
Co n n e ct iv i ty
E m b e dded Power
Power Sw i tch i ng& Control
Serv ices
DC Power
Mo n i to ri ng
Precision Cooling
S u r geProtection
Emerson Network Power Contact information
Headquarters
Surge Protection
328 Water Street
Binghamton, NY 13901
T: (607) 721-8840
T: (800) 288-6169
F: (607) 722-8713
E: contactsurge@emerson.com
IO-50105 1/09 Rev. 2 Printed in USA
www.emersonnetworkpower.com
650 SW 27th Avenue
Ocala, FL 34471
T: (352) 732-3029
T: (800) 648-4076
F: (352) 867-1237
Business- C ri t ical Cont i nu i ty, Emerson Netwo rk Power and the Emerson Netwo rk Power
l o goare trad ema rks and serv ice ma rks of Emerson Elect ric Co. ©2009 Emerson Elect ric Co.
Download