Edco PC2-TEL
Two Line Telephone Protection (Modular)
The Edco PC2-TEL is a solid state, two-line telephone interface protector module.
This unit is specifically designed to protect both phone lines required by commercial
fire/security panels.
General Technical Specifications
Operating Voltage
250 VDC
Clamping Voltage
270 VDC
Operating Current
Peak Surge Current
Frequency Range
Insertion Loss
SPD Technology
Connection Type
Operating Temperature
Dimensions (in / mm)
0.15 A
160 A (10 x 1000 T & R to Ground)
0 to 20 MHz
< 0.1 dB at 20 MHz
Silicon Breakover Device w/Series PTC
Terminal block w/ compression lugs
Terminals accept up to 10 AWG
-40°C to +85°C
2.0˝ H x 1.0˝ W x 2.5˝ L
[50.8 x 25.4 x 63.5 mm]
(PC2TEL + PCB1B-WKEY Base)
Weight (oz / kg)
1 oz [0.03 kg]
Certifications
UL 497A, CUL
Warranty
EDCO PCB1B-WKEY BASE SOLD SEPARATELY
5 years
Features
■■ Tip to ring protection
■■ Tip and ring to ground protection
■■ Over-current protection
■■ Resettable solid state fuses — PTCs
■■ UL Listed 497A
■■ Requires PCB1B-WKEY base
■■ PC642PTU (Pass Thru Unit)
available for troubleshooting
Caution
Do not place this product in service on any signal line capable of continuously supplying
more than 150 mA.
Attention
Ne pas placer ce produit dans le service sur une ligne de signal capable de fournir en
permanence plus de 150 mA.
■■ 5 year warranty
Ordering Information
2 Line Telephone
PC2-TEL
Installation Instructions
VDANGER!
Only qualified personnel should install or
service this system. Electrical safety precautions must be followed when installing
or servicing this equipment. To prevent risk
of electrical shock, turn off and lock out all
power sources to the unit before making
electrical connections or servicing.
Terminal Assignments
PCB1B-WKEY
Odd Terminals
Unprotected Pair 2
{
Field Side
Unprotected Pair 1
{
Even Terminals
10
9
8
7
6
5
4
3
2
1
}
Protected Pair 2
Electronics Side
}
Protected Pair 1
Keying Pin
2.4"
[60.96]
2.125"
[53.98]
Seulement le personnel qualifié doit installer
ou maintenir ce systéme. Des précautions
de sécurité en électricité doivent être suivis
lors de l’installation ou de la maintenance
de cet equipement. Pour eviter tout risque
de choc électrique, débranchez et verouiller
toutes les sources d’alimentation de cet
equipement avant de.
1.0”
[25.40]
• Connect ground terminals, positions 1 or 10 (internally
tied together) to Building Approved Ground. (See Edco
Tech Bulletin #2015) NOT intended for shield termination.
Install ground in accordance with all applicable codes.
• Edco PCB1B-WKEY accommodates 26 to 10 AWG wire.
• Disconnect telephone line at the network interface before
installing this secondary device.
• This product is intended for indoor use only.
Emerson Network Power Contact information
www.EmersonNetworkPower.com/Surge
Surge Protection
100 Emerson Parkway
Binghamton, NY 13905
T: (607) 721-8840
T: (800) 288-6169
F: (607) 722-8713
E: SurgeTech@Emerson.com
IO-50117 12/14 Rev. 4 Printed in USA
Emerson Network Power, the Emerson Network Power logo and Edco are trademarks
and service marks of Emerson Electric Co. ©2014 Emerson Electric Co.
While every precaution has been taken to ensure accuracy and completeness herein, Emerson Network Power Surge Protection assumes no responsibility, and disclaims all liability, for damages
resulting from use of this information or for any errors or omissions. Specifications are subject to change without notice.
Download