Installation Instructions – Mounting
IQ3.../.../XNC/...
Controller/Interface
Important: Retain these instructions
Contents
1Installation......................................................................1
2Disposal..........................................................................2
1Installation
1
Install
2
Connect Serial Interface
Install IQ3 according to IQ3xcite Installation
Instructions - Mounting, section 3 steps 1 to 11
If /SER/.., serial interface auxiliary board, fitted
Note that only one of the RS232 or RS485 connectors can
have a cable connected at any one time in order to comply
with Class B EMC emission standard (EN61000-6-3,
residential, commercial, and light industrial environments).
WARNING: Failure to comply with this requirement will
reduce the unit to Class A (industrial environments); in a
domestic environment the unit may cause radio interference,
in which case the user may be required to take adequate
measures.
TX
RX
RTS/TXEN
CTS/RXEN
RS485
IQ3xcite Installation Instructions Mounting (TG200626)
RS232
either RS485 2 wire, RS485 4 wire, or RS422
or RS232
2 part connector with 5 screw terminals fo 0.5 to 2.5 mm2
cross section area (14 to 20 AWG) cable
either 9 way D type plug
6
RTS 7
CTS 8
9
1
2
3
4
5
RX
Note
TX
(held high)
GND
pins 1,6,9 - no connection
or RJ11 socket
If RS485 2 wire
32 devices maximum
0V A B
0V A B
1
2
3
4
5
6
0V A B
IQ3../.../SER/XNC/...
RX
CTS
RTS
GND
TX
Note pin 2 - no connection
Note that only one of the two RS232 connectors can be used
at a time
RB
RA
T
B
A
0V
120 ohm
terminator
T
If RS422
IQ3../.../SER/XNC/...
Terminator switch ON
external 100 ohm terminator
If RS485 4 wire
32 devices maximum
0V TA TB RA RB
TA
RA
TB
RA
T
0V TA TB RA RB
0V TA TB RA RB
0V
RB
B
T
A
0V
RB
100 ohm terminator
IQ3../.../SER/XNC/...
Terminator switch OFF
RB
RA
T
B
T
A
0V
120 ohm
terminators
Terminator switch ON
This diagram shows IQ3 wired as a master,
it may also be wired as a slave.
If the IQ3/XNC/SER controller and other units on the bus are
in the same cabinet using the same power supply, each device
should have a good physical earth (ground) connection.
continued next page
IQ3.../.../XNC/... Installation Instructions TG200911 Issue 4 , 09/10/20141
IQ3.../.../XNC/...
1
Installation Instructions – Mounting
Installation
(continued)
Connect Serial Interface
2
(continued)
RS485 2 wire, RS485 4 wire, or RS422 (continued)
If the IQ3/XNC/SER controller and other units on the bus are in different cabinets or use different power supplies (e.g. different
UPSs), the cabinets should be isolated from each other. If the bus is likely to suffer from surge and grounding problems, surge
protection should be added. The isolator should be connected to the earth (ground) of the nearest device, the 0V of the isolator
and the surge protector should be connected together, and earth (ground) of the surge protector’s exposed side (e.g. backbone
bus) should be connected as directly as possible to the surge ground or earth bond.
Multiple Cabinets
0V A B
0V A B
terminate at far end
A B 0V
Isolating
Repeater
A B 0V
Surge
Protection
A B 0V
A B 0V
Cabinet B
Surge Ground
or Earth Bond
Cabinet A
RB
Isolating
Repeater
RA
T
A
T
B
B
A
0V
0V
Surge
Protection
to more cabinets
A
B
A
B
A
B
0V
0V
0V
Backbone Bus
terminate at far end
Surge Ground or Earth Bond
2
IQ3.../.../XNC/... Installation Instructions TG200911 Issue 4 , 09/10/2014
Installation Instructions – Mounting
1
Installation
3
IQ3.../.../XNC/...
(continued)
Connect Trend Current Loop Network
If /LAN/.., IQ system current loop Lan auxiliary board, fitted
Network Engineering Manual, (92-1735)
Cable
9k6 baud
19k2 baud
No. of Wires
Belden 9182
1000 m (1090 yds)
700 m (765 yds)
2
Belden 9207
1000 m (1090 yds)
500 m (545 yds)
2
Trend TP/1/1/22/HF/200 (Belden 8761) 700 m (765 yds)
350 m (380 yds)
2
Trend TP/2/2/22/HF/200 (Belden 8723) 500 m (545 yds)
250 m (270 yds)
4
2 off 2 part connectors with 4 screw terminals for 0.5 to 2.5
mm2 cross section area (14 to 20 AWG) cable
TX
RX
OK
polarity independent
Using 2 wire method
Using 4 wire method
IQ LAN
IQ LAN
T-
T+
R-
R+
T-
T+
R-
R+
T-
T+
R-
R+
T-
T+
R-
R+
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
OUT
IN
earth (ground) screen
to convenient input
channel screen terminal
25 26 27
N
+
0
OUT
IN
earth (ground) screen to convenient input
channel screen terminal
25 26 27
N
+
4
0
Continue Installation
For IQ3xcite, continue installation according to IQ3xcite
Installation Instructions - Mounting TG200626, section 3 step
12.
IQ3xcite Installation Instructions
- Mounting (TG200626)
IQ3.../.../XNC/... Installation Instructions TG200911 Issue 4 , 09/10/20143
IQ3.../.../XNC/...
Installation Instructions – Mounting
2Disposal
WEEE Directive:
At the end of their useful life the packaging and
product should be disposed of by a suitable
recycling centre.
Do not dispose of with normal household waste.
Do not burn.
Please send any comments about this or any other Trend technical publication to techpubs@trendcontrols.com
© 2014 Honeywell Technologies Sàrl, ECC Division. All rights reserved. Manufactured for and on behalf of the Environmental and Combustion Controls
Division of Honeywell Technologies Sàrl, Z.A. La Pièce, 16, 1180 Rolle, Switzerland by its Authorized Representative, Trend Control Systems Limited.
Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof without obligation
to notify any person of such revisions or changes.
Trend Control Systems Limited
Albery House, Springfield Road, Horsham, West Sussex, RH12 2PQ, UK. Tel:+44 (0)1403 211888 Fax:+44 (0)1403 241608 www.trendcontrols.com
Trend Control Systems USA
6670
4
185th
Avenue
NE,
Redmond,
Washington
98052,
USA.
Tel:(425)
897-3900
Fax:(425)
869-8445
www.trendamericas.com