SITE PLAN 1 - Buyandsell.gc.ca

advertisement
T
T
ROAD
NEW BC HYDRO
TRANSFORMER ON
EXISTING POLE
O/H
125mm RIGID PVC DUCT
TO STUB AT TOP OF
APPROACH, UNDER
DECKING
M
U/G
A
LP-1
200A 600/347V SERVICE DROP
TO PANEL & UTILITY METER
PRO
ACH
GUY WIRE &
ANCHOR
AP
R
NDE
R TSTERUCTION
O
F
N
ED
R CO
016
I S SDUO NOT USESaFveOd: May 9, 2
A
LP-2
REFER TO CECO SHOP DRAWING
#CE45R14/CE45R20 FOR SIDE-MOUNT
BRACKET DETAILS. (TYP. OF 3)
Last
'C-LP'
(CABLE TO LIGHT POLES)
'C-CDP'
STRAP CABLE TO
UNDERSIDE OF DECK
A
LP-3
B
200A CENTRAL
DISTRIBUTION PANEL (CDP)
MAY 20 2016
LP-4
'C-LP'
(CABLE TO LIGHT POLES)
'C-TC-A'
'C-TC-B'
'C-TC-C'
C
LP-5
'C-TC-A'
'C-TC-B'
T
TC-C
RC-6
'C-TC-A'
TC-A
RC-1
TC-B
'C-RC-3'
'C-RC-4'
'C-RC-5'
RC-3
T
'C-xx-x'
FLOAT
C
'C-RC-4'
'C-RC-5'
'C-RC-1'
'C-RC-2'
TYPE
A
'C-RC-5'
B
RC-2
RC-5
C
FLOAT
A
1
FLOAT
B
10
0m
10
TRANSFORMER CABINET (TC) w/ LED CANOPY LIGHT c/w
FOUR (4) 15A RECEPTACLES & FOUR (4) 30A RECEPTACLES
CABLES FASTENED TO UNDERSIDE OF DECK STRUCTURE.
TAG CABLES AT BOTH ENDS ACCORDING TO LABEL SHOWN
LUMINAIRE & POLE SCHEDULE
RC-4
'C-RC-2'
LUMINAIRE TYPE. REFER TO LUMINAIRE SCHEDULE.
POWER RECEPTACLE CABINET (RC) w/ LED CANOPY LIGHT
RC-3 c/w FOUR (4) 15A RECEPTACLES & FOUR (4) 30A
RECEPTACLES
TC-B
T
LP-6
T
A
'C-RC-6'
R
PIE
C
SITE PLAN SYMBOL LEGEND
LP-1
LUMINAIRE c/w POLE. LP-# DENOTES ID. REFER TO
LUMINAIRE SCHEDULE.
GANGWAY
Scale 1:1,000
20
30
POLE HEIGHT
14' c/w
SIDE-MOUNT
BRACKET
20' MOUNTED TO
HORIZONTAL
SURFACE OF DECK
14' MOUNTED TO
HORIZONTAL
SURFACE OF DECK
40
50
SITE PLAN
Scale: SCALE BAR
POLE MFR &
CATALOGUE NUMBER
LUMINAIRE DESCRIPTION
CECO #CE45R14
38W, 120-277V, DISTRIBUTION TYPE 2, 3000K LED,
FIELD ADJUSTABLE WATTAGE SELECTOR (FAWS)
PHILIPS ROADFOCUS RFS-35W16LED3K-T-R2M-UNIV
LUMEC
RFS
-DMG-FAWS-RCD-PH9-GY3
CECO #CE45R20
54W, 120-277V, DISTRIBUTION TYPE 2, 3000K LED,
FIELD ADJUSTABLE WATTAGE SELECTOR (FAWS)
PHILIPS ROADFOCUS RFS-54W16LED3K-T-R2M-UNIV
LUMEC
RFS
-DMG-FAWS-RCD-PH9-GY3
CECO #CE45R14
38W, 120-277V, DISTRIBUTION TYPE 2, 3000K LED,
FIELD ADJUSTABLE WATTAGE SELECTOR (FAWS)
PHILIPS ROADFOCUS RFS-35W16LED3K-T-R2M-UNIV
LUMEC
RFS
-DMG-FAWS-RCD-PH9-GY3
MFR.
MODEL
CATALOGUE NUMBER
RC-#
100A, 120/208V, 3ɸ, 4W,RC-#
18 CCT
100A, 120/208V, 3ɸ, 4W, 18 CCT
30A
30A
30A
30A
15A
15A
15A
15A
15A
30A 1P 30A 1P 30A 1P 30A 1P 15A 1P 15A 1P 15A 1P 15A 1P 15A 1P
1P
1P
1P
1P
1P
1P
1P
1P
1P
PEC
PEC
30A LOCKING RECEPTACLE (L5-30R)
30A LOCKING RECEPTACLE (L5-30R)
15A LOCKING RECEPTACLE (L5-15R)
15A LOCKING RECEPTACLE (L5-15R)
3000K LED CANOPY LIGHT
3000K LED CANOPY LIGHT
2
BC
HYDRO
BC HYDRO POLE-MOUNTED XFMR
BC HYDRO OVERHEAD
SERVICE CONDUCTOR
NOTES
NOTES
1. BALANCE RECEPTACLE LOADS
1. BALANCE
RECEPTACLE
BETWEEN
PHASES LOADS
FOR EACH FEEDER
BETWEEN PHASES FOR EACH FEEDER
R
NDE
R TSTERUCTION
O
F
N
ED
R CO
016
I S SDUO NOT USSEavFeOd: May 11, 2
PRESSURE TREATED WOOD
POLE c/w GUY WIRE
4c #3/0 Cu RW90
Last
MAIN DISCONNECT ENCLOSURE
POLE MOUNTED
200A
3P
22kAIC
RECEPTACLE CABINET (RC) SLD - TYPICAL FOR RC-1 to RC-6
MAIN BREAKER
ENCLOSURE
4c #3/0 Cu RW90
NOTES:
1. ALL BREAKERS TO BE LOCKABLE
EXTEND NEUTRAL TO
METER SOCKET
STUB AT TOP OF
APPROACH
M
2.
ALL BREAKERS RATED AT 10kAIC
UNLESS OTHERWISE SPECIFIED
3c 250MCM TECK Cu
CENTRAL DISTRIBUTION PANEL
200A
3P
10kAIC
REFER TO DWG E3
FOR GROUNDING
60A
3P
10kAIC
225A 600V 3ɸ 3W
60A
3P
10kAIC
40A
3P
10kAIC
15A
3P
10kAIC
15A
2P
10kAIC
LIGHTING AUTO-XFMR
1000VA MIN.
600:240V
POWER
FACTOR
CORRECTION
'C-TC-A'
3c #6 TYPE G
TX-A
45kVA
600:120/208V
4c #3/0 RW90 Cu
100A
3P
30A
1P
30A
1P
30A
1P
15A
1P
15A
1P
15A
1P
15A
1P
15A
1P
'C-RC-2'
RC-2 4c #3 TYPE G
'C-RC-3'
4c #3 TYPE G RC-3
100A
3P
100A
3P
100A
3P
30A
1P
30A
1P
SINGLE LINE DIAGRAM
30A
1P
30A
1P
15A
1P
15A
1P
15A
1P
15A
1P
15A
1P
225A 120/208V 3ɸ 4W 30 CCT
100A
3P
30A
1P
30A
1P
PEC
RC-4
POLE LIGHTING
LP-1 to LP-6
TC-C
225A 120/208V 3ɸ 4W 30 CCT
30A
1P
30A
1P
15A
1P
15A
1P
15A
1P
15A
1P
15A
1P
PEC
'C-RC-5'
'C-RC-6'
RC-5 4c #3 TYPE G
RC-6 4c #3 TYPE G
'C-RC-4'
4c #3 TYPE G
1
'C-LP'
2c #8 TECK Cu
'C-TC-C'
3c #6
TYPE G
4c #3/0 RW90 Cu
PEC
'C-RC-1'
4c #3 TYPE G RC-1
PEC, LED RATED
TX-C
30kVA
600:120/208V
4c #3/0 RW90 Cu
30A
1P
NOT IN
CONTRACT
TC-B
225A 120/208V 3ɸ 4W 30 CCT
100A
3P
'C-TC-B
3c #6
TYPE G
TX-B
45kVA
600:120/208V
TC-A
MAY 20 2016
TYPE G CABLE c/w
TYPE
G CABLE
c/w
GROUND
CONDUCTOR
GROUND CONDUCTOR
RC-#
100A, 120/208V, 3ɸ, 4W,RC-#
18 CCT
100A, 120/208V, 3ɸ, 4W, 18 CCT
30A
30A
30A
30A
15A
15A
15A
15A
15A
30A1P 30A1P 30A1P 30A 1P 15A 1P 15A 1P 15A 1P 15A 1P 15A 1P
1P
1P
1P
1P
1P
1P
1P
1P
1P
PEC
PEC
30A LOCKING RECEPTACLE (L5-30R)
30A LOCKING RECEPTACLE (L5-30R)
15A LOCKING RECEPTACLE (L5-15R)
15A LOCKING RECEPTACLE (L5-15R)
3000K LED CANOPY LIGHT
3000K LED CANOPY LIGHT
2
BC
HYDRO
BC HYDRO POLE-MOUNTED XFMR
SYSTEM GROUND
ELECTRODE
BC HYDRO OVERHEAD
SERVICE CONDUCTOR
NOTES
NOTES
1. BALANCE RECEPTACLE LOADS
1. BALANCE
RECEPTACLE
LOADS
BETWEEN
PHASES FOR
EACH FEEDER
BETWEEN PHASES FOR EACH FEEDER
R
NDE
R TSTERUCTION
O
F
N
ED
R CO
016
I S SDUO NOT USESaFveOd: May 9, 2
PRESSURE TREATED WOOD
POLE c/w GUY WIRE
4c #3/0 Cu RW90
Last
MAIN DISCONNECT ENCLOSURE
POLE MOUNTED
200A
3P
22kAIC
RECEPTACLE CABINET GROUNDING - TYPICAL FOR RC-1 to RC-6
2 RECEPTACLE CABINET GROUNDING - TYPICAL FOR RC-1 to RC-6
MAIN BREAKER
ENCLOSURE
4c #3/0 Cu RW90
M
#3 AWG Cu GREEN. DO NOT ROUTE GROUND
CONDUCTOR THROUGH METER BASE ENCLOSURE.
NOTES:
1. ALL BREAKERS TO BE LOCKABLE
EXTEND NEUTRAL TO
METER SOCKET
STUB AT TOP OF
APPROACH
2.
ALL BREAKERS RATED AT 10kAIC
UNLESS OTHERWISE SPECIFIED
3c 250MCM TECK Cu
CENTRAL DISTRIBUTION PANEL
200A
3P
10kAIC
60A
3P
10kAIC
TYPE G CABLE c/w
GROUND CONDUCTOR
(TYP.)
TX-A
45kVA
600:120/208V
#6 GREEN
INSULATED
GROUND
4c #3/0 RW90 Cu
225A 120/208V 3ɸ 4W 30 CCT
100A
3P
100A
3P
30A
1P
30A
1P
30A
1P
30A
1P
15A
1P
15A
1P
15A
1P
15A
1P
#6 GREEN
INSULATED
GROUND
15A
1P
100A
3P
30A
1P
30A
1P
PEC
'C-RC-1'
4c #3 TYPE G RC-1
'C-RC-2'
RC-2 4c #3 TYPE G
'C-RC-3'
4c #3 TYPE G RC-3
GROUNDING DIAGRAM
30A
1P
15A
1P
15A
1P
15A
1P
RC-4
15A
2P
10kAIC
LIGHTING AUTO-XFMR
1000VA MIN.
600:240V
15A
1P
15A
1P
'C-LP'
2c #8 TECK Cu
APPROACH LIGHTING LP-1 to LP-4
TX-C
30kVA
600:120/208V
#6 GREEN
INSULATED
GROUND
TC-C
4c #3/0 RW90 Cu
225A 120/208V 3ɸ 4W 30 CCT
100A
3P
30A
1P
30A
1P
PEC
30A
1P
30A
1P
15A
1P
15A
1P
15A
1P
15A
1P
15A
1P
PEC
'C-RC-5'
'C-RC-6'
RC-5 4c #3 TYPE G
RC-6 4c #3 TYPE G
'C-RC-4'
4c #3 TYPE G
1
30A
1P
15A
3P
10kAIC
'C-TC-C'
3c #6
TYPE G
TC-B
225A 120/208V 3ɸ 4W 30 CCT
100A
3P
40A
3P
10kAIC
PEC, LED RATED
4c #3/0 RW90 Cu
100A
3P
60A
3P
10kAIC
'C-TC-B
3c #6
TYPE G
TX-B
45kVA
600:120/208V
TC-A
225A 600V 3ɸ 3W
POWER
FACTOR
CORRECTION
'C-TC-A'
3c #6 TYPE G
MAY 20 2016
NEW BC HYDRO TRANSFORMER ON
EXISTING POLE
T
T
ROAD
O/H
M
U/G
125mm RIGID PVC DUCT TO STUB AT
TOP OF APPROACH, UNDER DECKING
1
E4
WEATHERPROOF SERVICE HEAD, WIRING TO SERVICE
HEAD TO INCLUDE SLACK FOR DRIP LOOP.
KEY PLAN
10.7m [35'] CLASS 4 TREATED WESTERN RED CEDAR POLE
500mm [21"] MINIMUM DIAMETER AT TOP. 825mm [321 2"] MINIMUM
DIAMETER AT POINT 1.8m [6'] FROM BUTT. GAIN MARK 3.66m
[12'] FROM BUTT.
PLATE AND EXPANDING ANCHORS SHALL BE INSTALLED AGAINST AN UNDERCUT TO
BEAR ON FIRM UNDISTURBED SOIL.
2.
GUY ASSEMBLY SHALL BE INSTALLED BEFORE ANY CONDUCTORS ARE ATTACHED TO
THE POLE AND LOCATED SO THAT THE GUY WILL NOT BE ABRADED BY RUBBING
AGAINST ANY WIRE, POLE, OR STRUCTURE.
3.
GUY LOCATED SUCH THAT THERE IS A POSSIBILITY OF CONTACT WITH SUPPLY
CONDUCTORS DUE TO THE FAILURE OF THE GUY OR CONDUCTORS SHALL BE
EFFECTIVELY INSULATED.
4.
ALL DOWN GUYS SHALL BE FITTED WITH A HIGHLY VISIBLE GUARD AND HAVE AT
LEAST ONE STRAIN INSULATOR INSTALLED.
5. GUY STRAIN INSULATORS SHALL BE INSTALLED SO THAT:
5.1. IF THE GUY IS HANGING VERTICALLY, THE LOWEST INSULATOR WILL BE AT LEAST
2.5 m (8') ABOVE GROUND; AND
5.2. IF THE GUY SHOULD BREAK LOOSE FROM ITS ANCHOR, THERE WILL BE AN
INSULATOR BETWEEN ANY TRANSMISSION, PRIMARY AND SECONDARY OR NEUTRAL
CONDUCTORS SO AS TO PREVENT A GUY WIRE SHORT CIRCUIT PATH BETWEEN
CONDUCTORS.
EAD
DR
BC HY
78mm RIGID PVC CONDUIT
MAY 20 2016
200A MAIN SERVICE BREAKER. LOCKABLE
WEATHERPROOF ENCLOSURE TYPE 3R.
MOUNT ON OPPOSITE SIDE OF METER
BC HYDRO APPROVED SELF-CONTAINED METER
SOCKET - COLD STYLE 7-JAW. MIN. DIMENSIONS:
480mm H x 295mm W x 135mm D. FACE AWAY
FROM ROAD.
℄
GROUND GUY ACCORDING TO CANADIAN ELECTRICAL CODE.
1.5m - 1.8m
6.
5m
#3 AWG Cu GREEN. DO NOT ROUTE GROUND
CONDUCTOR THROUGH METER BASE ENCLOSURE.
3m COPPER GROUND ROD
OR PLATE ELECTRODE AT
600mm BELOW GRADE
0.8m
WHARF
1.5m
1.9m
DUCT TO STUB UP AT TOP
OF APPROACH. CAP DUCT
AND STRAP TO UNDERSIDE
OF WALKWAY.
1
DUCT STUB-UP ELEVATION (LOOKING NORTH)
Scale: NTS
2
Last
RH
O OVE
150mm
COMPLETE GUY & ANCHOR ASSEMBLY
INSTALLED IN LINE WITH BC HYDRO OVERHEAD
CONDUCTORS. THE FOLLOWING COMPONENTS OR
APPROVED EQUIVALENTS TO BE INCLUDED:
·
GALVANIZED STRAND GUY WIRE, 10500 lb
BREAKING STRENGTH
·
HEAVY DUTY SINGLE DOWN GUY
ASSEMBLY (THROUGH BOLT)
·
120 in2 PLATE ANCHOR
SUBMIT ANCHORING DESIGN AND COMPONENT
SHOP DRAWINGS TO ENGINEER FOR APPROVAL
PRIOR TO CONSTRUCTION.
R
NDE
R TSTERUCTION
O
F
N
ED
R CO
016
I S SDUO NOT USESaFveOd: May 9, 2
INSERT BOLT THROUGH CLEVIS TO
ACCOMMODATE ATTACHMENT OF BC HYDRO
SERVICE LINE. POINT OF ATTACHMENT NOT TO
EXCEED 7m ABOVE GRADE.
Scale: NTS
GUY AND ANCHOR INSTALLATION
1.
200A 600/347V SERVICE DROP
TO PANEL & UTILITY METER
GUY WIRE &
ANCHOR
MAX. 7m
-
2
E4
SERVICE POLE ELEVATION (LOOKING NORTH)
Scale: NTS
LED RATED PHOTOCELL (FACING NORTH) FOR
WHARFHEAD & APPROACH LIGHTING CONTROL
ALLOW SUFFICIENT SPACE
FOR INCOMING FEEDER BEND
203 [8"]
SPACE PROVISION FOR
FUTURE POWER FACTOR
CORRECTION CAPACITOR
MIN. 12"L x 14"W x 14"D
DOCK POWER CENTRAL DISTRIBUTION PANEL - WEATHERPROOF
MAIN BREAKER
AND PANEL
·
TYPE 3R ENCLOSURE
·
FLOOR MOUNTED POWER DISTRIBUTION CENTRE
·
MARINE GRADE (TYPE 316) STAINLESS STEEL BODY
·
HIDDEN HINGE STYLE DOOR GASKETED c/w 3-POINT
STAINLESS STEEL PADLOCKABLE HANDLE
·
OPEN BOTTOM FOR CABLE ENTRY c/w 2" INNER FLANGE
·
MACHINE-FORMED SAFETY CORNERS
·
OVERSIZED DRIPHOOD ON FRONT & FORMED DRIP GUTTER
·
TWO LIFTING EYES
·
STRAIN RELIEF CONNECTORS FOR ALL INTERIOR WIRING
·
FULLY CSA APPROVED
R
NDE
R TSTERUCTION
O
F
N
ED
R CO
016
I S SDUO NOT USESaFveOd: May 9, 2
Last
600:240V LIGHTING
AUTOTRANSFORMER.
CONSULT MANUFACTURER
FOR DIMENSIONS.
PROVIDE BELL MOUTH &
CONDUIT SLEEVES FOR
PROTECTION OF CABLES
AT PANEL ENTRY (TYP.)
MAY 20 2016
2
-
WHARFHEAD DECKING
PROVIDE 1/8" DRAINHOLE(S) ALONG
ENCLOSURE BOTTOM
1
CENTRAL DISTRIBUTION PANEL - FRONT VIEW (LESS DOOR FOR CLARITY)
Scale: NTS
PROVIDE 3/4" TYPE 316 STAINLESS STEEL PLATE
c/w BOLTS, LOCK WASHERS, FLAT WASHERS &
NUTS TO BOLT THROUGH TO BRACKET
PROVIDE MARINE GRADE TYPE 316 STAINLESS STEEL
ANCHOR BOLT HARDWARE.
DOCK STRINGER (EXISTING)
PROVIDE 4" SQ. TUBULAR TYPE 316
STAINLESS STEEL SPACER TO
ACCOMMODATE DOCK RAILING
REPLACE ALL DECK PLANKS UNDER CABINETS WITH NEW
PRESSURE TREATED (COPPER AZOLE OR ALTERNATIVE AS
APPROVED BY HARBOUR MASTER) FULL LENGTH PLANKS
MATCHING THICKNESS AND LENGTH OF EXISTING. REDUCE WIDTH
OF PLANKS TO ALLOW THREE 7/8” WIDE PORTABLE CORD
SLOTS LOCATED IN FRONT OF EACH RECEPTACLE PEDESTAL.
REFER TO CECO DWG #CE45R14/20 FOR
BRACKET DETAILS & BOLT PATTERN
PROVIDE 150mm x 150mm x 200mm BLOCK TO REINFORCE
EXISTING DECKING FOR PEDESTAL ANCHOR BOLTS. LUMBER
SHALL BE PRESSURE TREATED WITH COPPER AZOLE
PRESERVATIVE.
2
ALL HARDWARE TO BE
MARINE GRADE TYPE 316
STAINLESS STEEL
ANCHOR BOLT DETAIL
Scale: NTS
3
SIDE-MOUNT LIGHT POLE BRACKET MOUNTING DETAIL
Scale: NTS
LED RATED
PHOTO CELL TO
FACE NORTH
LED RATED PHOTO
CELL TO FACE NORTH
LED CANOPY LIGHT MOUNTED UNDER HOOD, 3000K COLOUR
TEMPERATURE. EVERGREEN LIGHTING 7200 LED SERIES
#7200-50-BLK-3000K OR APPROVED EQUIVALENT
TWO (2) BOLT-TYPE LIFTING
HOOKS RATED FOR FULLY
ASSEMBLED CABINET WEIGHT
TWO (2) LIFTING EYES RATED FOR
FULLY ASSEMBLED CABINET WEIGHT
TYPICAL CABINET NAMEPLATE
(#=CABINET ID)
50mm H x 150mm W WITH MIN.
12mm H LETTERING
RECEPTACLE CABINET
RC-#
R
NDE
R TSTERUCTION
O
F
N
ED
R CO
016
I S SDUO NOT USESaFveOd: May 9, 2
Last
LABEL EACH BREAKER
RECEPTACLE
COMPARTMENT
__A
CCT.#
SIZE ENCLOSURE TO
ACCEPT 75kVA
TRANSFORMER
TYPICAL LABEL ABOVE
CORRESPONDING RECEPTACLE
12mm H x 70mm W WITH MIN.
5mm H LETTERING
3
TRANSFORMER
T-x
75 kVA, 600:120/208V
TRANSFORMER
MAY 20 2016
PROVIDE BELL MOUTH & CONDUIT SLEEVES FOR
PROTECTION OF CABLES AT PANEL ENTRY (TYP.)
3
-
1
TYPICAL TRANSFORMER
NAMEPLATE
(x=XFMR ID)
50mm H x 150mm W
WITH MIN. 12mm H
LETTERING
3
-
RECEPTACLE CABINET (RC-#) - FRONT VIEW (TYP)
2
TRANSFORMER/RECEPTACLE CABINET (TC-x) - FRONT VIEW (TYP)
Scale: NTS
Scale: NTS
GENERAL NOTES:
PROVIDE MARINE GRADE TYPE 316 STAINLESS STEEL
ANCHOR BOLT HARDWARE.
REPLACE ALL DECK PLANKS UNDER CABINETS WITH NEW
PRESSURE TREATED (COPPER AZOLE OR ALTERNATIVE AS
APPROVED BY HARBOUR MASTER) FULL LENGTH PLANKS
MATCHING THICKNESS AND LENGTH OF EXISTING. REDUCE WIDTH
OF PLANKS TO ALLOW THREE 7/8” WIDE PORTABLE CORD
SLOTS LOCATED IN FRONT OF EACH RECEPTACLE PEDESTAL.
PROVIDE 150mm x 150mm x 200mm BLOCK TO REINFORCE
EXISTING DECKING FOR PEDESTAL ANCHOR BOLTS. LUMBER
SHALL BE PRESSURE TREATED WITH COPPER AZOLE
PRESERVATIVE.
3
ANCHOR BOLT DETAIL (TYP)
Scale: NTS
1.
PROVIDE PANEL SCHEDULE IN EACH PEDESTAL. PROVIDE NEW LABELLING AT MAIN PANEL.
2.
CONTRACTOR TO DETERMINE WHERE EXTRA FLOATATION WILL BE REQUIRED TO BALANCE THE FLOAT FREE BOARD AND REPORT TO
CONSULTANT. FLOTATION UNIT WILL BE SUPPLIED BY OWNER.
3.
ALL LABELS TO BE 1/8" THICK PHENOLIC LAMINATE SHEET (LAMICOID) OR LASER ENGRAVED METAL, MECHANICALLY FASTENED TO
ENCLOSURE AS SHOWN.
4.
ALL ENCLOSURES TO INCLUDE MINIMUM ONE DRAINHOLE LARGE ENOUGH TO ALLOW CONDENSATION OR INGRESSED WATER TO DRAIN
FASTER THAN IT CAN ACCUMULATE.
5.
ROOF SECTION TO BE WELDED TO ENCLOSURE. MANUFACTURER TO INSTALL LUMINAIRE CONDUCTORS INTERNALLY THROUGH ROOF
SUPPORTS.
6.
ALL CABINET LOCKS TO BE KEYED THE SAME.
7.
SECONDARY CABLE CONNECTION FROM TRANSFORMER TO PANEL COMPARTMENT TO BE PROVIDED THROUGH FLEXIBLE CONDUIT OR
ARMOURED CABLE
8.
PROVIDE STRAIN RELIEF CONNECTORS TO SUPPORT ALL INTERIOR WIRING.
456 18"
(4)WELDED
[3/4"] NUTS
ON [9"] BCD
C
B
6
132 5-3/16"
D
A
60 2-3/8" O.D.
51 2"
7
279 11"
95 3-3/4"
25[1"]
WIRE HOLE
SM1-20
SM1-20
5
ITEM
QTY.
1
1
SQ. BASE PLATE [9"] x [3/4"] PL.
DESCRIPTION
MATERIAL
44W
2
1
STD. STEEL [4"] PIPE, [4.5"] O.D. X [.188"] WALL, [14']/[20'0"] LG.
50W
3
1
HANDHOLE ASS'Y [5"] X [3'] X [1/4"] X [1-3/4"] LG. C/W COVER
44W
4
1
GROUNDSTUD [3/8"] NC X [1"] LG. C/W NUT & WASHER
5
1
BRACKET [3/4"] PL. c/w (4)
6
1
ROUND POLE CAP
7
1
8
2
9
4
PLATED
[3/4"] NUT WELDED
[4-1/2"]
44W
PP
[2-3/8"] O.D. FIXTURE ARM, [0.188"] WALL, [18"] LG., LOC. "C"
#3000[3/4"] HALF COUPLING
50W
STEEL
[3/4"] X [2"] LG. BOLT
GR.5
NOTE : i POLE FINISH HDG.
5
ii (3) CE45R14 , (1) CE45R20.
SM1-20
A
SM1-20
SM1-20
3
203 8"
4
19 3/4"
5
SM1-20
5
9
4267/6096 14'0" /[20'0"]
127 5"
A
4
2
279 11"
5
5
SM1-20
127 5"
203 8"
(4) 25 1"
BOLT HOLES
ITEM 5 - SIDE-MOUNT BRACKET DETAIL
(FOR 14' POLES, QTY. 3 ONLY)
NOTE: ALL BRACKETS, BOLTS &
FASTENERS TO BE MARINE GRADE
TYPE 316 STAINLESS STEEL
THIS DRAWING IS PROPERTY OF CECO POLES & STRUCTURES INC.
279 11"
WORK ORDER NO.
3
8
279 11"
152 6"
1
5
DRAWNN BY
FOR 14' POLES
(QTY. 3 ONLY)
(4) [3/4"] BOLT
& WASHER
ON [9"] BCD
SECTION A-A
SCALE 1 : 12
PURCHASE ORDER NO.
*
PAGE
POLES & STRUCTURES INC.
1/1
5110-56th AVENUE S.E. CALGARY, ALBERTA
T: 403 279 0530 F: 403 279 0531 EMAIIL: info@cecopoles.ca
162 6-3/8" SQ.
5
305 12"
*
BM
TITLE
STEEL STD. ROUND POLE, 14/20 FT.
DATE
APR. 08/2016
APPR.BY
SCALE
QUANTITY
CUSTOMER / JOB
NTS
4
HARBOUR WALKWAY/LSW LIGHTING/
RELUMEN ENGINEERING
REV.NO.
B
DWG.NO.
CE45R14/CE45R20
Download