T T ROAD NEW BC HYDRO TRANSFORMER ON EXISTING POLE O/H 125mm RIGID PVC DUCT TO STUB AT TOP OF APPROACH, UNDER DECKING M U/G A LP-1 200A 600/347V SERVICE DROP TO PANEL & UTILITY METER PRO ACH GUY WIRE & ANCHOR AP R NDE R TSTERUCTION O F N ED R CO 016 I S SDUO NOT USESaFveOd: May 9, 2 A LP-2 REFER TO CECO SHOP DRAWING #CE45R14/CE45R20 FOR SIDE-MOUNT BRACKET DETAILS. (TYP. OF 3) Last 'C-LP' (CABLE TO LIGHT POLES) 'C-CDP' STRAP CABLE TO UNDERSIDE OF DECK A LP-3 B 200A CENTRAL DISTRIBUTION PANEL (CDP) MAY 20 2016 LP-4 'C-LP' (CABLE TO LIGHT POLES) 'C-TC-A' 'C-TC-B' 'C-TC-C' C LP-5 'C-TC-A' 'C-TC-B' T TC-C RC-6 'C-TC-A' TC-A RC-1 TC-B 'C-RC-3' 'C-RC-4' 'C-RC-5' RC-3 T 'C-xx-x' FLOAT C 'C-RC-4' 'C-RC-5' 'C-RC-1' 'C-RC-2' TYPE A 'C-RC-5' B RC-2 RC-5 C FLOAT A 1 FLOAT B 10 0m 10 TRANSFORMER CABINET (TC) w/ LED CANOPY LIGHT c/w FOUR (4) 15A RECEPTACLES & FOUR (4) 30A RECEPTACLES CABLES FASTENED TO UNDERSIDE OF DECK STRUCTURE. TAG CABLES AT BOTH ENDS ACCORDING TO LABEL SHOWN LUMINAIRE & POLE SCHEDULE RC-4 'C-RC-2' LUMINAIRE TYPE. REFER TO LUMINAIRE SCHEDULE. POWER RECEPTACLE CABINET (RC) w/ LED CANOPY LIGHT RC-3 c/w FOUR (4) 15A RECEPTACLES & FOUR (4) 30A RECEPTACLES TC-B T LP-6 T A 'C-RC-6' R PIE C SITE PLAN SYMBOL LEGEND LP-1 LUMINAIRE c/w POLE. LP-# DENOTES ID. REFER TO LUMINAIRE SCHEDULE. GANGWAY Scale 1:1,000 20 30 POLE HEIGHT 14' c/w SIDE-MOUNT BRACKET 20' MOUNTED TO HORIZONTAL SURFACE OF DECK 14' MOUNTED TO HORIZONTAL SURFACE OF DECK 40 50 SITE PLAN Scale: SCALE BAR POLE MFR & CATALOGUE NUMBER LUMINAIRE DESCRIPTION CECO #CE45R14 38W, 120-277V, DISTRIBUTION TYPE 2, 3000K LED, FIELD ADJUSTABLE WATTAGE SELECTOR (FAWS) PHILIPS ROADFOCUS RFS-35W16LED3K-T-R2M-UNIV LUMEC RFS -DMG-FAWS-RCD-PH9-GY3 CECO #CE45R20 54W, 120-277V, DISTRIBUTION TYPE 2, 3000K LED, FIELD ADJUSTABLE WATTAGE SELECTOR (FAWS) PHILIPS ROADFOCUS RFS-54W16LED3K-T-R2M-UNIV LUMEC RFS -DMG-FAWS-RCD-PH9-GY3 CECO #CE45R14 38W, 120-277V, DISTRIBUTION TYPE 2, 3000K LED, FIELD ADJUSTABLE WATTAGE SELECTOR (FAWS) PHILIPS ROADFOCUS RFS-35W16LED3K-T-R2M-UNIV LUMEC RFS -DMG-FAWS-RCD-PH9-GY3 MFR. MODEL CATALOGUE NUMBER RC-# 100A, 120/208V, 3ɸ, 4W,RC-# 18 CCT 100A, 120/208V, 3ɸ, 4W, 18 CCT 30A 30A 30A 30A 15A 15A 15A 15A 15A 30A 1P 30A 1P 30A 1P 30A 1P 15A 1P 15A 1P 15A 1P 15A 1P 15A 1P 1P 1P 1P 1P 1P 1P 1P 1P 1P PEC PEC 30A LOCKING RECEPTACLE (L5-30R) 30A LOCKING RECEPTACLE (L5-30R) 15A LOCKING RECEPTACLE (L5-15R) 15A LOCKING RECEPTACLE (L5-15R) 3000K LED CANOPY LIGHT 3000K LED CANOPY LIGHT 2 BC HYDRO BC HYDRO POLE-MOUNTED XFMR BC HYDRO OVERHEAD SERVICE CONDUCTOR NOTES NOTES 1. BALANCE RECEPTACLE LOADS 1. BALANCE RECEPTACLE BETWEEN PHASES LOADS FOR EACH FEEDER BETWEEN PHASES FOR EACH FEEDER R NDE R TSTERUCTION O F N ED R CO 016 I S SDUO NOT USSEavFeOd: May 11, 2 PRESSURE TREATED WOOD POLE c/w GUY WIRE 4c #3/0 Cu RW90 Last MAIN DISCONNECT ENCLOSURE POLE MOUNTED 200A 3P 22kAIC RECEPTACLE CABINET (RC) SLD - TYPICAL FOR RC-1 to RC-6 MAIN BREAKER ENCLOSURE 4c #3/0 Cu RW90 NOTES: 1. ALL BREAKERS TO BE LOCKABLE EXTEND NEUTRAL TO METER SOCKET STUB AT TOP OF APPROACH M 2. ALL BREAKERS RATED AT 10kAIC UNLESS OTHERWISE SPECIFIED 3c 250MCM TECK Cu CENTRAL DISTRIBUTION PANEL 200A 3P 10kAIC REFER TO DWG E3 FOR GROUNDING 60A 3P 10kAIC 225A 600V 3ɸ 3W 60A 3P 10kAIC 40A 3P 10kAIC 15A 3P 10kAIC 15A 2P 10kAIC LIGHTING AUTO-XFMR 1000VA MIN. 600:240V POWER FACTOR CORRECTION 'C-TC-A' 3c #6 TYPE G TX-A 45kVA 600:120/208V 4c #3/0 RW90 Cu 100A 3P 30A 1P 30A 1P 30A 1P 15A 1P 15A 1P 15A 1P 15A 1P 15A 1P 'C-RC-2' RC-2 4c #3 TYPE G 'C-RC-3' 4c #3 TYPE G RC-3 100A 3P 100A 3P 100A 3P 30A 1P 30A 1P SINGLE LINE DIAGRAM 30A 1P 30A 1P 15A 1P 15A 1P 15A 1P 15A 1P 15A 1P 225A 120/208V 3ɸ 4W 30 CCT 100A 3P 30A 1P 30A 1P PEC RC-4 POLE LIGHTING LP-1 to LP-6 TC-C 225A 120/208V 3ɸ 4W 30 CCT 30A 1P 30A 1P 15A 1P 15A 1P 15A 1P 15A 1P 15A 1P PEC 'C-RC-5' 'C-RC-6' RC-5 4c #3 TYPE G RC-6 4c #3 TYPE G 'C-RC-4' 4c #3 TYPE G 1 'C-LP' 2c #8 TECK Cu 'C-TC-C' 3c #6 TYPE G 4c #3/0 RW90 Cu PEC 'C-RC-1' 4c #3 TYPE G RC-1 PEC, LED RATED TX-C 30kVA 600:120/208V 4c #3/0 RW90 Cu 30A 1P NOT IN CONTRACT TC-B 225A 120/208V 3ɸ 4W 30 CCT 100A 3P 'C-TC-B 3c #6 TYPE G TX-B 45kVA 600:120/208V TC-A MAY 20 2016 TYPE G CABLE c/w TYPE G CABLE c/w GROUND CONDUCTOR GROUND CONDUCTOR RC-# 100A, 120/208V, 3ɸ, 4W,RC-# 18 CCT 100A, 120/208V, 3ɸ, 4W, 18 CCT 30A 30A 30A 30A 15A 15A 15A 15A 15A 30A1P 30A1P 30A1P 30A 1P 15A 1P 15A 1P 15A 1P 15A 1P 15A 1P 1P 1P 1P 1P 1P 1P 1P 1P 1P PEC PEC 30A LOCKING RECEPTACLE (L5-30R) 30A LOCKING RECEPTACLE (L5-30R) 15A LOCKING RECEPTACLE (L5-15R) 15A LOCKING RECEPTACLE (L5-15R) 3000K LED CANOPY LIGHT 3000K LED CANOPY LIGHT 2 BC HYDRO BC HYDRO POLE-MOUNTED XFMR SYSTEM GROUND ELECTRODE BC HYDRO OVERHEAD SERVICE CONDUCTOR NOTES NOTES 1. BALANCE RECEPTACLE LOADS 1. BALANCE RECEPTACLE LOADS BETWEEN PHASES FOR EACH FEEDER BETWEEN PHASES FOR EACH FEEDER R NDE R TSTERUCTION O F N ED R CO 016 I S SDUO NOT USESaFveOd: May 9, 2 PRESSURE TREATED WOOD POLE c/w GUY WIRE 4c #3/0 Cu RW90 Last MAIN DISCONNECT ENCLOSURE POLE MOUNTED 200A 3P 22kAIC RECEPTACLE CABINET GROUNDING - TYPICAL FOR RC-1 to RC-6 2 RECEPTACLE CABINET GROUNDING - TYPICAL FOR RC-1 to RC-6 MAIN BREAKER ENCLOSURE 4c #3/0 Cu RW90 M #3 AWG Cu GREEN. DO NOT ROUTE GROUND CONDUCTOR THROUGH METER BASE ENCLOSURE. NOTES: 1. ALL BREAKERS TO BE LOCKABLE EXTEND NEUTRAL TO METER SOCKET STUB AT TOP OF APPROACH 2. ALL BREAKERS RATED AT 10kAIC UNLESS OTHERWISE SPECIFIED 3c 250MCM TECK Cu CENTRAL DISTRIBUTION PANEL 200A 3P 10kAIC 60A 3P 10kAIC TYPE G CABLE c/w GROUND CONDUCTOR (TYP.) TX-A 45kVA 600:120/208V #6 GREEN INSULATED GROUND 4c #3/0 RW90 Cu 225A 120/208V 3ɸ 4W 30 CCT 100A 3P 100A 3P 30A 1P 30A 1P 30A 1P 30A 1P 15A 1P 15A 1P 15A 1P 15A 1P #6 GREEN INSULATED GROUND 15A 1P 100A 3P 30A 1P 30A 1P PEC 'C-RC-1' 4c #3 TYPE G RC-1 'C-RC-2' RC-2 4c #3 TYPE G 'C-RC-3' 4c #3 TYPE G RC-3 GROUNDING DIAGRAM 30A 1P 15A 1P 15A 1P 15A 1P RC-4 15A 2P 10kAIC LIGHTING AUTO-XFMR 1000VA MIN. 600:240V 15A 1P 15A 1P 'C-LP' 2c #8 TECK Cu APPROACH LIGHTING LP-1 to LP-4 TX-C 30kVA 600:120/208V #6 GREEN INSULATED GROUND TC-C 4c #3/0 RW90 Cu 225A 120/208V 3ɸ 4W 30 CCT 100A 3P 30A 1P 30A 1P PEC 30A 1P 30A 1P 15A 1P 15A 1P 15A 1P 15A 1P 15A 1P PEC 'C-RC-5' 'C-RC-6' RC-5 4c #3 TYPE G RC-6 4c #3 TYPE G 'C-RC-4' 4c #3 TYPE G 1 30A 1P 15A 3P 10kAIC 'C-TC-C' 3c #6 TYPE G TC-B 225A 120/208V 3ɸ 4W 30 CCT 100A 3P 40A 3P 10kAIC PEC, LED RATED 4c #3/0 RW90 Cu 100A 3P 60A 3P 10kAIC 'C-TC-B 3c #6 TYPE G TX-B 45kVA 600:120/208V TC-A 225A 600V 3ɸ 3W POWER FACTOR CORRECTION 'C-TC-A' 3c #6 TYPE G MAY 20 2016 NEW BC HYDRO TRANSFORMER ON EXISTING POLE T T ROAD O/H M U/G 125mm RIGID PVC DUCT TO STUB AT TOP OF APPROACH, UNDER DECKING 1 E4 WEATHERPROOF SERVICE HEAD, WIRING TO SERVICE HEAD TO INCLUDE SLACK FOR DRIP LOOP. KEY PLAN 10.7m [35'] CLASS 4 TREATED WESTERN RED CEDAR POLE 500mm [21"] MINIMUM DIAMETER AT TOP. 825mm [321 2"] MINIMUM DIAMETER AT POINT 1.8m [6'] FROM BUTT. GAIN MARK 3.66m [12'] FROM BUTT. PLATE AND EXPANDING ANCHORS SHALL BE INSTALLED AGAINST AN UNDERCUT TO BEAR ON FIRM UNDISTURBED SOIL. 2. GUY ASSEMBLY SHALL BE INSTALLED BEFORE ANY CONDUCTORS ARE ATTACHED TO THE POLE AND LOCATED SO THAT THE GUY WILL NOT BE ABRADED BY RUBBING AGAINST ANY WIRE, POLE, OR STRUCTURE. 3. GUY LOCATED SUCH THAT THERE IS A POSSIBILITY OF CONTACT WITH SUPPLY CONDUCTORS DUE TO THE FAILURE OF THE GUY OR CONDUCTORS SHALL BE EFFECTIVELY INSULATED. 4. ALL DOWN GUYS SHALL BE FITTED WITH A HIGHLY VISIBLE GUARD AND HAVE AT LEAST ONE STRAIN INSULATOR INSTALLED. 5. GUY STRAIN INSULATORS SHALL BE INSTALLED SO THAT: 5.1. IF THE GUY IS HANGING VERTICALLY, THE LOWEST INSULATOR WILL BE AT LEAST 2.5 m (8') ABOVE GROUND; AND 5.2. IF THE GUY SHOULD BREAK LOOSE FROM ITS ANCHOR, THERE WILL BE AN INSULATOR BETWEEN ANY TRANSMISSION, PRIMARY AND SECONDARY OR NEUTRAL CONDUCTORS SO AS TO PREVENT A GUY WIRE SHORT CIRCUIT PATH BETWEEN CONDUCTORS. EAD DR BC HY 78mm RIGID PVC CONDUIT MAY 20 2016 200A MAIN SERVICE BREAKER. LOCKABLE WEATHERPROOF ENCLOSURE TYPE 3R. MOUNT ON OPPOSITE SIDE OF METER BC HYDRO APPROVED SELF-CONTAINED METER SOCKET - COLD STYLE 7-JAW. MIN. DIMENSIONS: 480mm H x 295mm W x 135mm D. FACE AWAY FROM ROAD. ℄ GROUND GUY ACCORDING TO CANADIAN ELECTRICAL CODE. 1.5m - 1.8m 6. 5m #3 AWG Cu GREEN. DO NOT ROUTE GROUND CONDUCTOR THROUGH METER BASE ENCLOSURE. 3m COPPER GROUND ROD OR PLATE ELECTRODE AT 600mm BELOW GRADE 0.8m WHARF 1.5m 1.9m DUCT TO STUB UP AT TOP OF APPROACH. CAP DUCT AND STRAP TO UNDERSIDE OF WALKWAY. 1 DUCT STUB-UP ELEVATION (LOOKING NORTH) Scale: NTS 2 Last RH O OVE 150mm COMPLETE GUY & ANCHOR ASSEMBLY INSTALLED IN LINE WITH BC HYDRO OVERHEAD CONDUCTORS. THE FOLLOWING COMPONENTS OR APPROVED EQUIVALENTS TO BE INCLUDED: · GALVANIZED STRAND GUY WIRE, 10500 lb BREAKING STRENGTH · HEAVY DUTY SINGLE DOWN GUY ASSEMBLY (THROUGH BOLT) · 120 in2 PLATE ANCHOR SUBMIT ANCHORING DESIGN AND COMPONENT SHOP DRAWINGS TO ENGINEER FOR APPROVAL PRIOR TO CONSTRUCTION. R NDE R TSTERUCTION O F N ED R CO 016 I S SDUO NOT USESaFveOd: May 9, 2 INSERT BOLT THROUGH CLEVIS TO ACCOMMODATE ATTACHMENT OF BC HYDRO SERVICE LINE. POINT OF ATTACHMENT NOT TO EXCEED 7m ABOVE GRADE. Scale: NTS GUY AND ANCHOR INSTALLATION 1. 200A 600/347V SERVICE DROP TO PANEL & UTILITY METER GUY WIRE & ANCHOR MAX. 7m - 2 E4 SERVICE POLE ELEVATION (LOOKING NORTH) Scale: NTS LED RATED PHOTOCELL (FACING NORTH) FOR WHARFHEAD & APPROACH LIGHTING CONTROL ALLOW SUFFICIENT SPACE FOR INCOMING FEEDER BEND 203 [8"] SPACE PROVISION FOR FUTURE POWER FACTOR CORRECTION CAPACITOR MIN. 12"L x 14"W x 14"D DOCK POWER CENTRAL DISTRIBUTION PANEL - WEATHERPROOF MAIN BREAKER AND PANEL · TYPE 3R ENCLOSURE · FLOOR MOUNTED POWER DISTRIBUTION CENTRE · MARINE GRADE (TYPE 316) STAINLESS STEEL BODY · HIDDEN HINGE STYLE DOOR GASKETED c/w 3-POINT STAINLESS STEEL PADLOCKABLE HANDLE · OPEN BOTTOM FOR CABLE ENTRY c/w 2" INNER FLANGE · MACHINE-FORMED SAFETY CORNERS · OVERSIZED DRIPHOOD ON FRONT & FORMED DRIP GUTTER · TWO LIFTING EYES · STRAIN RELIEF CONNECTORS FOR ALL INTERIOR WIRING · FULLY CSA APPROVED R NDE R TSTERUCTION O F N ED R CO 016 I S SDUO NOT USESaFveOd: May 9, 2 Last 600:240V LIGHTING AUTOTRANSFORMER. CONSULT MANUFACTURER FOR DIMENSIONS. PROVIDE BELL MOUTH & CONDUIT SLEEVES FOR PROTECTION OF CABLES AT PANEL ENTRY (TYP.) MAY 20 2016 2 - WHARFHEAD DECKING PROVIDE 1/8" DRAINHOLE(S) ALONG ENCLOSURE BOTTOM 1 CENTRAL DISTRIBUTION PANEL - FRONT VIEW (LESS DOOR FOR CLARITY) Scale: NTS PROVIDE 3/4" TYPE 316 STAINLESS STEEL PLATE c/w BOLTS, LOCK WASHERS, FLAT WASHERS & NUTS TO BOLT THROUGH TO BRACKET PROVIDE MARINE GRADE TYPE 316 STAINLESS STEEL ANCHOR BOLT HARDWARE. DOCK STRINGER (EXISTING) PROVIDE 4" SQ. TUBULAR TYPE 316 STAINLESS STEEL SPACER TO ACCOMMODATE DOCK RAILING REPLACE ALL DECK PLANKS UNDER CABINETS WITH NEW PRESSURE TREATED (COPPER AZOLE OR ALTERNATIVE AS APPROVED BY HARBOUR MASTER) FULL LENGTH PLANKS MATCHING THICKNESS AND LENGTH OF EXISTING. REDUCE WIDTH OF PLANKS TO ALLOW THREE 7/8” WIDE PORTABLE CORD SLOTS LOCATED IN FRONT OF EACH RECEPTACLE PEDESTAL. REFER TO CECO DWG #CE45R14/20 FOR BRACKET DETAILS & BOLT PATTERN PROVIDE 150mm x 150mm x 200mm BLOCK TO REINFORCE EXISTING DECKING FOR PEDESTAL ANCHOR BOLTS. LUMBER SHALL BE PRESSURE TREATED WITH COPPER AZOLE PRESERVATIVE. 2 ALL HARDWARE TO BE MARINE GRADE TYPE 316 STAINLESS STEEL ANCHOR BOLT DETAIL Scale: NTS 3 SIDE-MOUNT LIGHT POLE BRACKET MOUNTING DETAIL Scale: NTS LED RATED PHOTO CELL TO FACE NORTH LED RATED PHOTO CELL TO FACE NORTH LED CANOPY LIGHT MOUNTED UNDER HOOD, 3000K COLOUR TEMPERATURE. EVERGREEN LIGHTING 7200 LED SERIES #7200-50-BLK-3000K OR APPROVED EQUIVALENT TWO (2) BOLT-TYPE LIFTING HOOKS RATED FOR FULLY ASSEMBLED CABINET WEIGHT TWO (2) LIFTING EYES RATED FOR FULLY ASSEMBLED CABINET WEIGHT TYPICAL CABINET NAMEPLATE (#=CABINET ID) 50mm H x 150mm W WITH MIN. 12mm H LETTERING RECEPTACLE CABINET RC-# R NDE R TSTERUCTION O F N ED R CO 016 I S SDUO NOT USESaFveOd: May 9, 2 Last LABEL EACH BREAKER RECEPTACLE COMPARTMENT __A CCT.# SIZE ENCLOSURE TO ACCEPT 75kVA TRANSFORMER TYPICAL LABEL ABOVE CORRESPONDING RECEPTACLE 12mm H x 70mm W WITH MIN. 5mm H LETTERING 3 TRANSFORMER T-x 75 kVA, 600:120/208V TRANSFORMER MAY 20 2016 PROVIDE BELL MOUTH & CONDUIT SLEEVES FOR PROTECTION OF CABLES AT PANEL ENTRY (TYP.) 3 - 1 TYPICAL TRANSFORMER NAMEPLATE (x=XFMR ID) 50mm H x 150mm W WITH MIN. 12mm H LETTERING 3 - RECEPTACLE CABINET (RC-#) - FRONT VIEW (TYP) 2 TRANSFORMER/RECEPTACLE CABINET (TC-x) - FRONT VIEW (TYP) Scale: NTS Scale: NTS GENERAL NOTES: PROVIDE MARINE GRADE TYPE 316 STAINLESS STEEL ANCHOR BOLT HARDWARE. REPLACE ALL DECK PLANKS UNDER CABINETS WITH NEW PRESSURE TREATED (COPPER AZOLE OR ALTERNATIVE AS APPROVED BY HARBOUR MASTER) FULL LENGTH PLANKS MATCHING THICKNESS AND LENGTH OF EXISTING. REDUCE WIDTH OF PLANKS TO ALLOW THREE 7/8” WIDE PORTABLE CORD SLOTS LOCATED IN FRONT OF EACH RECEPTACLE PEDESTAL. PROVIDE 150mm x 150mm x 200mm BLOCK TO REINFORCE EXISTING DECKING FOR PEDESTAL ANCHOR BOLTS. LUMBER SHALL BE PRESSURE TREATED WITH COPPER AZOLE PRESERVATIVE. 3 ANCHOR BOLT DETAIL (TYP) Scale: NTS 1. PROVIDE PANEL SCHEDULE IN EACH PEDESTAL. PROVIDE NEW LABELLING AT MAIN PANEL. 2. CONTRACTOR TO DETERMINE WHERE EXTRA FLOATATION WILL BE REQUIRED TO BALANCE THE FLOAT FREE BOARD AND REPORT TO CONSULTANT. FLOTATION UNIT WILL BE SUPPLIED BY OWNER. 3. ALL LABELS TO BE 1/8" THICK PHENOLIC LAMINATE SHEET (LAMICOID) OR LASER ENGRAVED METAL, MECHANICALLY FASTENED TO ENCLOSURE AS SHOWN. 4. ALL ENCLOSURES TO INCLUDE MINIMUM ONE DRAINHOLE LARGE ENOUGH TO ALLOW CONDENSATION OR INGRESSED WATER TO DRAIN FASTER THAN IT CAN ACCUMULATE. 5. ROOF SECTION TO BE WELDED TO ENCLOSURE. MANUFACTURER TO INSTALL LUMINAIRE CONDUCTORS INTERNALLY THROUGH ROOF SUPPORTS. 6. ALL CABINET LOCKS TO BE KEYED THE SAME. 7. SECONDARY CABLE CONNECTION FROM TRANSFORMER TO PANEL COMPARTMENT TO BE PROVIDED THROUGH FLEXIBLE CONDUIT OR ARMOURED CABLE 8. PROVIDE STRAIN RELIEF CONNECTORS TO SUPPORT ALL INTERIOR WIRING. 456 18" (4)WELDED [3/4"] NUTS ON [9"] BCD C B 6 132 5-3/16" D A 60 2-3/8" O.D. 51 2" 7 279 11" 95 3-3/4" 25[1"] WIRE HOLE SM1-20 SM1-20 5 ITEM QTY. 1 1 SQ. BASE PLATE [9"] x [3/4"] PL. DESCRIPTION MATERIAL 44W 2 1 STD. STEEL [4"] PIPE, [4.5"] O.D. X [.188"] WALL, [14']/[20'0"] LG. 50W 3 1 HANDHOLE ASS'Y [5"] X [3'] X [1/4"] X [1-3/4"] LG. C/W COVER 44W 4 1 GROUNDSTUD [3/8"] NC X [1"] LG. C/W NUT & WASHER 5 1 BRACKET [3/4"] PL. c/w (4) 6 1 ROUND POLE CAP 7 1 8 2 9 4 PLATED [3/4"] NUT WELDED [4-1/2"] 44W PP [2-3/8"] O.D. FIXTURE ARM, [0.188"] WALL, [18"] LG., LOC. "C" #3000[3/4"] HALF COUPLING 50W STEEL [3/4"] X [2"] LG. BOLT GR.5 NOTE : i POLE FINISH HDG. 5 ii (3) CE45R14 , (1) CE45R20. SM1-20 A SM1-20 SM1-20 3 203 8" 4 19 3/4" 5 SM1-20 5 9 4267/6096 14'0" /[20'0"] 127 5" A 4 2 279 11" 5 5 SM1-20 127 5" 203 8" (4) 25 1" BOLT HOLES ITEM 5 - SIDE-MOUNT BRACKET DETAIL (FOR 14' POLES, QTY. 3 ONLY) NOTE: ALL BRACKETS, BOLTS & FASTENERS TO BE MARINE GRADE TYPE 316 STAINLESS STEEL THIS DRAWING IS PROPERTY OF CECO POLES & STRUCTURES INC. 279 11" WORK ORDER NO. 3 8 279 11" 152 6" 1 5 DRAWNN BY FOR 14' POLES (QTY. 3 ONLY) (4) [3/4"] BOLT & WASHER ON [9"] BCD SECTION A-A SCALE 1 : 12 PURCHASE ORDER NO. * PAGE POLES & STRUCTURES INC. 1/1 5110-56th AVENUE S.E. CALGARY, ALBERTA T: 403 279 0530 F: 403 279 0531 EMAIIL: info@cecopoles.ca 162 6-3/8" SQ. 5 305 12" * BM TITLE STEEL STD. ROUND POLE, 14/20 FT. DATE APR. 08/2016 APPR.BY SCALE QUANTITY CUSTOMER / JOB NTS 4 HARBOUR WALKWAY/LSW LIGHTING/ RELUMEN ENGINEERING REV.NO. B DWG.NO. CE45R14/CE45R20