Vaults and Boxes DESIGN REQUIREMENTS APPROVED HANDHOLE HANDHOLE BOX MANUFACTURER COVER Armorcast A6001640PC A6001947-NP PB24-1730-18NP PC04-1730-02NPKTL CDR Quazite PG1730B509 PG1730H50179 Polycrete (Rockway) R-RS-1 C-RS-1 Oldcastle PC 1730-18 1730-D T15 TOLERANCES: a = +1/16", -1/16" b = +1/2", -1/2" c = +1/8", -1/4" d = +1/32", -1/32" e = +1/16", -0" f = +1/4", -0" g = +1/2", -1/4" Top Frame 2'-6 3/4"a Bottom Frame 2'-1/2"a 3/4" Top Frame 1'-5 3/4"a Bottom Frame 1'-5 1/2"a 1 5/8"e 6 3/4"a 3 /4"f 1'-1 1/4"a 2 Stainless Steel Inserts ½”-13 Only in Box 1/2"e 1'-6" ELECTRIC K-20 1 1/2"e 4” Supplier Logo Top Cover 1'-5 1/2"d Bottom Cover 1'-5 1/4"d f 1'-6"b Cover 2"d Frame 2" d 1/2"a 2" Min. 3 1/ 2" Max. Lifting Slots Top Cover 2'-6 1/2"d Bottom Cover 2'-6 1/4"d Cover Handhole Box 1'-3 1/2"b 2'-4 1/2"b 1/4"c 1 1/2"g 1/4"c 2'-5 1/2"b 1 1/2"g 1'-4 1/2"b RS-1 HANDHOLE NOTES: 1. The handhole shall meet specification RS-G1. Electric Service Requirements Drawn: Eng: Appr: Date: SC SC DA 7/12 Handhole: Secondary Junction RS-1 Revision: 2 Page 1 of 4 Vaults and Boxes Back of Sidewalk 8" Min. clearance around handhole All conduits at one end. Services must be located at either side(s), secondary must be installed in the center. (Notes 7 and 9) 18" 4 Conduits Maximum Curb SIDEWALK INSTALLATION DETAIL Electric Service Requirements Drawn: Eng: Appr: Date: SC SC DA 7/12 Handhole: Secondary Junction RS-1 Revision: 2 Page 2 of 4 Vaults and Boxes NOTES: 1. The NVE Inspector will place a grade stripe on the pole and stake location of handhole relative to the residential service pole riser. 2. If this structure does not meet all requirements or exhibits poor workmanship, it shall be rejected by NVE. 3. 51” minimum is for the handhole only. 4. A 3” PVC stubout is required if a future residential CIC system service or a 4” stubout for commercial service will be installed. The stubout must pass adjacent to the pole as illustrated. 5. Cable must be trained and cut so that the backs of the connector blocks are a minimum of 1” from the end of handhole wall as illustrated. 6. For backfill requirements see RT-1. 7. Stubouts for future services must be placed per “Sidewalk Installation Detail”. 8. 9There shall be a minimum 6’ clearance from the handhole to the center of a fire hydrant. 9. There shall be a minimum 1” separation between conduits to facilitate the installation of debris seals. Electric Service Requirements Drawn: Eng: Appr: Date: SC SC DA 7/12 Handhole: Secondary Junction RS-1 Revision: 2 Page 3 of 4 Vaults and Boxes APPROVED CIC ROUTING HANDHOLE 1 8” 1 5 8” Sidewalk 2 2 5 10' Min. Back of Curb Street 3 5 Note: Circled numbers reference notes below JUNCTION BOX PLACED PARALLEL WITH 3’ MINIMUM SIDEWALK 1 1 1 8” 5 10' Min. 8” 4 2 4 2 5 4 Street 3 5 8” Sidewalk 2 Less Than 10' Back of Curb 4 5 Note: Circled numbers reference notes below JUNCTION BOX PLACED PERPENDICULAR WITH 4’ MINIMUM SIDEWALK NOTES: 1. 2. 3. 4. 5. If there are future services, the customer shall install a 3”, 36” radius, 90 Schedule 40 PVC Bend stubout for each future CIC service. This will prevent undermining the sidewalk and dislocating the handhole. There shall be a minimum of 8” of concrete around the handhole in the sidewalk. If the customer installs a street crossing conduit, it shall be a 4” Schedule 40 PVC conduit for each secondary. If a street crossing conduit is extended into a handhole (or a pull box), a 3”, 36” radius, Schedule 40 PVC bend is required. Installed secondary CIC. Electric Service Requirements Drawn: Eng: Appr: Date: SC SC DA 7/12 Handhole: Secondary Junction RS-1 Revision: 2 Page 4 of 4