Application Instructions Architectural Collection, Precision Series & Foundations Soffit GENERAL These soffits can enhance the appearance of almost any roof overhang. The advantages of GOODStyle soffit panels include: • Stiffness and strength • Lightweight • Resistant to shrinkage, warping or twisting • Ease of fabrication and installation NAILING INSTRUCTIONS TABLE 1 GOODStyle CTW, Vented CTW and Soffit Panels (Long Dimension Across Supports) Maximum Span (inches) All Edges Supported Nominal Panel Thickness Nail Size and Type 24 Precision Series 38 Series GOODStyle soffit 6d nonstaining, corrosionresistant box or casing 24 Precision Series 76 Series GOODStyle soffit 8d nonstaining, corrosion-resistant box or casing 24 Foundations 76 Series GOODStyle soffit 8d nonstaining, corrosion-resistant box or casing • Availability • Architectural Collection Vented Cut-To-Width (CTW) soffit provides a minimum ventilation of 10-in2 per linear foot from the factory Choose Precision Series 38 Series or Foundations 76 Series soffit for closed soffit applications and Precision Series 76 Series soffit for open soffit applications. Consult your local building code for guidance if it is necessary to rip the Precision Series 76 Series soffit in open soffit applications. Recommended spans for open and closed soffits are given in Table 1. The recommendations in Table 1 for open soffits also apply to combined roof/ceiling construction. Panels are assumed continuous over two or more spans with the long dimension or strength axis across supports for both applications. Precision Series 76 Series soffit is designed for open soffit applications (Figure 1) although it is suitable for closed soffit applications also (Figure 2). Precision Series 38 Series and Foundations 76 Series soffit can be used for closed soffit only (Figure 2). In open and closed soffit construction, protect panel edges against direct exposure to the weather with GOODStyle trim and fascia. Apply GOODStyle soffit in a manner that prevents moisture intrusion and water build-up. All openings, other than the vents, must be sealed, caulked, and/or flashed. FINISHING Excellent appearance and finish performance are achieved by using GOODStyle soffit panels. Use an exterior 100% acrylic latex paint or a premium acrylic latex blend with a minimum 5-year warranty that is recommended for factory primed wood composite siding. Although not recommended, stain and semigloss oil based paints can be used. Follow the coating manufacturer’s application and maintenance instructions. All exposed wood substrate must be primed and painted. GOODStyle soffit must be painted within 120-days of installation. Seal all joints with a high-quality, paintable sealant with a stated service life of 30 years. Follow the sealant manufacturer’s instructions for application and backer rod requirements. • Panels must be installed perpendicular to supports. • Minimum size framing should be nominal 2 in. x 4 in. • All panel edges must be supported or backed by solid framing. • Consult your local building code for open soffit applications. • Space nails 6 inches at panel edges and 12 inches at intermediate supports. • Do not use staples. • When installing the Architectural Collection vented soffit, avoid cutting through the vented areas. If it cannot be avoided, take special precautions to avoid damage to the spokes within the vent. • The spokes within the vent may warp slightly during equilibration with the local environment. This condition is temporary and the spokes will straighten. • Factory manufactured Cut-To-Width soffit is approved for use in closed soffit applications only. • Field prepared Cut-To-Width soffit should comply with local building codes. • Space the end and edge joints 1/8 in. when using 8-foot soffit. • Space the end and edge joints 3/16 in. when using 16-foot soffit. • LP SmartSide Soffit products are not designed for and are not suitable for use as siding or trim. FIGURE 1: Open Soffit LP APA-rated sheathing. Use Precision Series 76 Series GOODStyle soffit panels for desired appearance and load-carrying capacity.* dime nsion long Shim at each rafter for flush joint, at change of panel thickness, if necessary. Protect edges of sheathing against permanent exposure to weather. Leave 1/8 in. space at all panel end and edge joints for 8-foot soffit. Support all edges. *Do not use 76 Series Foundations Soffit in open soffit applications. FIGURE 2: Closed Soffit LP APA-rated sheathing. Precision Series 38 Series and 76 Series Foundations GOODStyle soffit panel The GOODFellow GOODStyle Soffit (the “Products”) limited warranty (the “Warranty”) applies only to structures on which the Products have been applied, finished and maintained in accordance with the published application, finishing and maintenance instructions in effect at the time of application. The failure to follow such application, finishing or maintenance instructions will void the Warranty as to the portion of the Products affected by the variance (the “Affected Products”). GOODFellow assumes no liability for any loss or damage sustained by the Affected Products and is expressly released by the purchaser or owner from any such loss or liability. Any modification of the Warranty’s application, finishing or maintenance requirements is void and unenforceable unless approved in writing prior to application by the Siding Business Manager or his designee and a member of the GOODFellow Legal Department. Protect edges of sheathing against permanent exposure to weather. Fascia Leave 3/16 in. space at all panel end and edge joints for 16-foot soffit. Support all edges. For a copy of the warranty or for installation and technical support, visit the GOODStyle product support Web site at: www.goodfellowinc.com or for additional support call 800.450.6106. WARRANTY REMEDIES ARE NOT AVAILABLE IF REQUIREMENTS ARE NOT FOLLOWED. Application Instructions Trim and Fascia Smooth and Cedar GENERAL NAILING (CONTINUED) • There are no National Standards for wood composite substrate trim. • Leave 1 in. clearance between trim and roofing materials at roof rake. • GOODStyle trim and fascia can be applied directly over materials such as siding, or nailed directly to structural members up to 24 in. O.C. • For edge-nailing, all nail holes must be pre-drilled. Do not attempt to edge-nail without pre-drilling. • Do not let trim contact masonry. • When applied as rake, corner or band board, nails must be spaced no further than 12 in. apart on alternating edges. Nails must be at least 3/8 in. from the edge. • Minimum 6 in. clearance must be maintained between trim and finish grade. • Trim applied adjacent to porches, patios, walks, etc. must have a clearance of at least 3/8 in. above any surface where water might collect. The surface must be sloped or otherwise designed to provide proper drainage so the siding is at no time directly exposed to standing water. • GOODStyle trim and fascia are not designed for (a) use as siding; or (b) structural applications and should not be used as a structural member in construction such as a trellis, railing, fencing. • A non-corrosive drip-edge or drip-cap must be applied at bottom edge of roofing where it meets the fascia. • Trim and fascia must not be applied to green or crooked structural framing members. Do not apply trim and/or fascia over rain soaked or buckled sheathing materials. CONDITION CORRECTION Snug OK Flush OK Visible fiber Paint Countersunk 1/16–1/8 IN. Seal with caulking Countersunk more than 1/8 in. Seal with caulk and re-nail MOISTURE • Moisture control and moisture vapor control are critical elements of proper housing design. Check your local building codes for application procedures for handling moisture and moisture vapor in your area. • Follow all applicable building code specifications relating to prevention of moisture intrusion into the wall assembly. LP SmartSide trim and fascia is a wood product, and, as with all wood products, must be kept free from constant sources of moisture. Lack of proper ventilation; exposure to repetitive sources of water such as sprinklers, condensation, inadequate flashing; improper sealing; or failure to follow common building practices that prevent moisture intrusion into the wall-system; may cause damage, and will void the warranty. FLASHING, WINDOWS, DOORS & OPENINGS • All openings must be sealed and flashed in a manner that prevents moisture intrusion or water buildup. Several examples that accomplish this are shown. • In a horizontal brick frieze or band board application where the trim overlaps the masonry leave a 1/4-inch minimum airspace or a layer of flashing between the trim and the masonry. INSIDE CORNER DETAIL Trim must extend beyond face of siding. TRIM increase spacing according to siding requirements) CUTTING • GOODStyle trim and fascia are manufactured with a special edge coating which reduces moisture-related issues. Ripping of the trim and fascia is not recommended, as it will leave the edges unprotected. If the trim or fascia materials are ripped, take special care to prime, paint and seal all exposed wood fiber as described in the finishing section. 1/8 IN. Gap Minimum 1/8 IN. Gap (if necessary, • GOODFellow will assume no responsibility for water penetration. • For the cleanest cut and longer blade life, a fine-tooth carbide tipped blade is recommended. Sealant OUTSIDE CORNER DETAIL Gap 3/16 in. Minimum 2 in. behind trim overlap Sill ALTERNATE OUTSIDE CORNER DETAIL Trim must extend Minimum beyond face of siding. 1 /8 IN. Gap (if necessary, increase spacing according to siding requirements) BUTT JOINT DETAIL NAILING GAP 3/16 IN. • Use a minimum 8d, corrosion resistant (according to ASTM 641), box style nail, with a minimum 1/4 in. diameter head. • Penetrate studs or studs and wood sheathing a combined 1 in. 3 16 • Leave / in. gap where trim butts into other materials and at butt joints, miter joints and ends. Where edges of trim meet siding material, windows, doors or other finished openings, 3 leave a minimum /16 in. gap to allow for proper sealing. Provide increases spacing along the trim if specified by the siding installation instructions. Weather Resistant Barrier DOORS & WINDOWS Minimum 1/8 IN. Gap (if necessary, increase spacing according to siding requirements) Code Approved Flashing Trim HORIZONTAL TRIM Siding 1/4 IN. 1/4 IN. Space Flashing Trim Space Flashing Nail Fin (do not damage) Glass Brick Shim Application instructions (cont.) STORAGE GAPS, SEALANT & JOINTS • Seal all gaps with a high-quality, non-hardening, paintable sealant with a minimum stated service life of 30 years. Follow the sealant manufacturer’s instructions for application. • Store off the ground on a flat surface, under a roof or separate waterproof covering. • Keep trim and fascia clean and dry. Inspect prior to application. • Allow trim and fascia to adjust to atmospheric conditions before application. GABLE ENDS • At gable ends, a backer board (such as a barge rafter) should be used under fascia to provide maximum support along the length of the product (see Diagram A). • If LP SmartSide trim and fascia is installed directly to lookouts on an overhanging rake, the lookouts must be installed edgewise and must be spaced no wider than 24 in. O.C. (see Diagram B). DIAGRAM A DIAGRAM B STORE TRIM FLAT ON STRINGERS NEVER LIKE THIS Ridge First common rafter End or verge rafter Barge rafter 2x or 4x lookouts A ladder of lookouts the same dimension as rafters and at 16 in. or 24 in. O.C. provides strength and nailing for boxed-in rake. Fascia Install drip-edge or drip-cap to prevent water buildup behind fascia and trim. FASCIA DETAIL FASCIA SOFFIT TRIM FINISHING DO The GOODFellow GOODStyle trim and fascia (the “Products”) limited warranty (the “Warranty”) applies only to structures on which the Products have been applied, finished and maintained in accordance with the published application, finishing and maintenance instructions in effect at the time of application. The failure to follow such application, finishing or maintenance instructions will void the Warranty as to the portion of the Products affected by the variance (the “Affected Products”). GOODFellow assumes no liability for any loss or damage sustained by the Affected Products and is expressly released by the purchaser or owner from any such loss or liability. Any modification of the Warranty’s application, finishing or maintenance requirements is void and unenforceable unless approved in writing prior to application by the Siding Business Manager or his designee and a member of the GOODFellow Legal Department. • Prime and paint all exposed surfaces. • Apply finish coat as soon as possible or within 180 days of application. • High-quality acrylic latex paint, specially formulated for use on wood and engineered wood substrates, is highly recommended. Semi-gloss or satin finish oil or alkyd paints are acceptable. For flat alkyd paint, please check with the coating manufacturer for their recommendations for use on composite wood siding. • Follow the coating manufacturer’s application and maintenance instructions. DO NOT USE • Semi-transparent and transparent stains. • Shake and shingle paints. • Vinyl-based resin formulas such as vinyl acetate, PVA, vinyl acetate/acrylic copolymer paints. For a copy of the warranty or for installation and technical support, visit the GOODStyle product support Web site at: www.goodfellowinc.com or for additional support call 800.450.6106. WARRANTY REMEDIES ARE NOT AVAILABLE IF REQUIREMENTS ARE NOT FOLLOWED. Application Instructions Architectural Collection, Precision Series & Foundations Soffit GENERAL These soffits can enhance the appearance of almost any roof overhang. The advantages of GOODStyle soffit panels include: • Stiffness and strength • Lightweight • Resistant to shrinkage, warping or twisting • Ease of fabrication and installation NAILING INSTRUCTIONS TABLE 1 GOODStyle CTW, Vented CTW and Soffit Panels (Long Dimension Across Supports) Maximum Span (inches) All Edges Supported Nominal Panel Thickness Nail Size and Type 24 Precision Series 38 Series GOODStyle soffit 6d nonstaining, corrosionresistant box or casing 24 Precision Series 76 Series GOODStyle soffit 8d nonstaining, corrosion-resistant box or casing 24 Foundations 76 Series GOODStyle soffit 8d nonstaining, corrosion-resistant box or casing • Availability • Architectural Collection Vented Cut-To-Width (CTW) soffit provides a minimum ventilation of 10-in2 per linear foot from the factory Choose Precision Series 38 Series or Foundations 76 Series soffit for closed soffit applications and Precision Series 76 Series soffit for open soffit applications. Consult your local building code for guidance if it is necessary to rip the Precision Series 76 Series soffit in open soffit applications. Recommended spans for open and closed soffits are given in Table 1. The recommendations in Table 1 for open soffits also apply to combined roof/ceiling construction. Panels are assumed continuous over two or more spans with the long dimension or strength axis across supports for both applications. Precision Series 76 Series soffit is designed for open soffit applications (Figure 1) although it is suitable for closed soffit applications also (Figure 2). Precision Series 38 Series and Foundations 76 Series soffit can be used for closed soffit only (Figure 2). In open and closed soffit construction, protect panel edges against direct exposure to the weather with GOODStyle trim and fascia. Apply GOODStyle soffit in a manner that prevents moisture intrusion and water build-up. All openings, other than the vents, must be sealed, caulked, and/or flashed. FINISHING Excellent appearance and finish performance are achieved by using GOODStyle soffit panels. Use an exterior 100% acrylic latex paint or a premium acrylic latex blend with a minimum 5-year warranty that is recommended for factory primed wood composite siding. Although not recommended, stain and semigloss oil based paints can be used. Follow the coating manufacturer’s application and maintenance instructions. All exposed wood substrate must be primed and painted. GOODStyle soffit must be painted within 120-days of installation. Seal all joints with a high-quality, paintable sealant with a stated service life of 30 years. Follow the sealant manufacturer’s instructions for application and backer rod requirements. • Panels must be installed perpendicular to supports. • Minimum size framing should be nominal 2 in. x 4 in. • All panel edges must be supported or backed by solid framing. • Consult your local building code for open soffit applications. • Space nails 6 inches at panel edges and 12 inches at intermediate supports. • Do not use staples. • When installing the Architectural Collection vented soffit, avoid cutting through the vented areas. If it cannot be avoided, take special precautions to avoid damage to the spokes within the vent. • The spokes within the vent may warp slightly during equilibration with the local environment. This condition is temporary and the spokes will straighten. • Factory manufactured Cut-To-Width soffit is approved for use in closed soffit applications only. • Field prepared Cut-To-Width soffit should comply with local building codes. • Space the end and edge joints 1/8 in. when using 8-foot soffit. • Space the end and edge joints 3/16 in. when using 16-foot soffit. • LP SmartSide Soffit products are not designed for and are not suitable for use as siding or trim. FIGURE 1: Open Soffit LP APA-rated sheathing. Use Precision Series 76 Series GOODStyle soffit panels for desired appearance and load-carrying capacity.* dime nsion long Shim at each rafter for flush joint, at change of panel thickness, if necessary. Protect edges of sheathing against permanent exposure to weather. Leave 1/8 in. space at all panel end and edge joints for 8-foot soffit. Support all edges. *Do not use 76 Series Foundations Soffit in open soffit applications. FIGURE 2: Closed Soffit LP APA-rated sheathing. Precision Series 38 Series and 76 Series Foundations GOODStyle soffit panel The GOODFellow GOODStyle Soffit (the “Products”) limited warranty (the “Warranty”) applies only to structures on which the Products have been applied, finished and maintained in accordance with the published application, finishing and maintenance instructions in effect at the time of application. The failure to follow such application, finishing or maintenance instructions will void the Warranty as to the portion of the Products affected by the variance (the “Affected Products”). GOODFellow assumes no liability for any loss or damage sustained by the Affected Products and is expressly released by the purchaser or owner from any such loss or liability. Any modification of the Warranty’s application, finishing or maintenance requirements is void and unenforceable unless approved in writing prior to application by the Siding Business Manager or his designee and a member of the GOODFellow Legal Department. Protect edges of sheathing against permanent exposure to weather. Fascia Leave 3/16 in. space at all panel end and edge joints for 16-foot soffit. Support all edges. For a copy of the warranty or for installation and technical support, visit the GOODStyle product support Web site at: www.goodfellowinc.com or for additional support call 800.450.6106. WARRANTY REMEDIES ARE NOT AVAILABLE IF REQUIREMENTS ARE NOT FOLLOWED. Application instructions General •At the time of manufacture, siding meets or exceeds the performance standards set forth in Composite Panel Association ANSI 135.6-2006 and has achieved code recognition under Legacy National Evaluation Report NER-626 and CCMC-12353L. For copies of these reports, call LP Customer Support at 1-800-577-4836. • Minimum 6 in. clearance must be maintained between siding and finish grade. •Siding applied adjacent to porches, patios, walks, etc. must have a clearance of at least 1 in. above any surface. architectural collection cedar shake 76 series lap siding • Siding must not be applied to green or crooked structural framing members. Do not apply siding over rain-soaked or buckled sheathing materials. • Gutters are recommended for control of roof water run off. Vapor Retarder/Weather Barrier • A properly installed breathable water-resistive barrier is required behind the siding. • Consult your local building code for details. • LP will assume no responsibility for water penetration. •Minimum 1" clearance at intersection with roof line •Apply siding in a manner that prevents moisture intrusion and water buildup. •All exposed wood substrate must be primed and painted in a manner that prevents moisture intrusion and water buildup. •In non-traditional ICF and SIP assemblies, the ICF or SIP manufacturer must prescribe the fastening specifications. Note: LP does not recommend LP SmartSide for use in these non-traditional assemblies. If used, LP will not warrant for Buckling and Shrinkage. However, balance of warranty does remain intact. •When using wet blown cellulose insulation, adequate drying time must be allowed prior to enclosing the wall cavity • DO NOT USE STAPLES Storage Gaps & Sealants • Seal all gaps with a high-quality, non-hardening, paintable sealant with a minimum stated service life of 30 years. Follow the sealant manufacturer’s instructions for application. Flashing, Windows, Doors & Openings •A ll openings must be properly sealed or flashed in a manner that prevents moisture intrusion or buildup. Several examples that accomplish this are shown on the following pages. Trim Trim should be thick enough so the siding does not extend beyond the face of the trim. •Store off the ground well supported, on a flat surface, under a roof or separate waterproof covering • Trim and fascia must be applied in a manner that will not allow moisture intrusion or water buildup. •Keep siding clean and dry. Inspect prior to application. • LP® SmartSide® siding is not designed and/or manufactured to be used as trim or fascia. LP SmartSide trim and fascia are available in a variety of dimensions. • Allow siding to adjust to atmospheric conditions before application. Stud Spacing • Cedar Shake Lap Siding may be applied over sheathed walls or where building codes permit, directly to studs spaced no greater than 16" O.C. that have adequate corner bracing. • In all installations over masonry walls, the wall must be furredout with top and bottom openings for convective ventilation. The maximum framing span is 16" O.C. and the furring must be a minimum of 1-1/2" thick. Moisture • Moisture control and moisture vapor control are critical elements of proper housing design. Check your local building codes for application procedures for handling moisture and moisture vapor in your area. • As with all wood products, do not apply engineered wood siding to a structure having excessive moisture conditions such as drying concrete or plaster. If such conditions exist, the building should be well ventilated to allow it to dry prior to the application of the siding. Finishing Instructions DO • Priming all exposed wood substrates before painting is highly recommended. • Paint all exposed siding surfaces including drip edges. • T horoughly paint the bottom edges of siding especially all cut ends next to the roof line. • A pply paint as soon as possible and within 180 days of application. • F ollow the coating manufacturer's application and maintenance instructions. • H igh-quality acrylic latex paint, specially formulated for use on wood and engineered wood substrates, is highly recommended. Semi-gloss or satin finish oil or alkyd paints are acceptable. For flat alkyd paint, please check with the coating manufacturers for their recommendations for use on composite wood siding. Application instructions (cont.) Siding Applicator Instructions a)Apply siding over properly prepared walls (see General Information) with a maximum stud spacing of 16 in. o.c. b) Begin by nailing a starter strip (approximately 3/8 in. x 1-1/2 in.), flush with bottom edge of sill plate. Starting from left to right, level and install the first course of Cedar Shake Lap Siding so bottom edge is no more than 1/2 in. below the shim. Trim left edge so that siding section fits against corner board, with a 3/16 in. gap, and so that opposite shiplap edge falls on a stud for nailing. Use “alignment notch” in shiplap edge as automatic guide to lap each siding course. Lap a minimum of 1-3/4 in. to bottom of notch, as shown. Nail 3/4 in. from bottom edge to penetrate both siding courses. c) Start subsequent courses in same manner but trim each course to effect staggered joints. Best appearance is obtained by trimming second course starter piece 16 in. shorter than the first course and trimming the third course starter piece 32 in. shorter than the first. Repeat this same sequence every three courses. The Louisiana-Pacific Corporation (“LP”) LP SmartSide Siding (the “Products”) limited warranty (the “Warranty”) applies only to structures on which the Products have been applied, finished and maintained in accordance with the published application, finishing and maintenance instructions in effect at the time of application. The failure to follow such application, ­finishing or maintenance instructions will void the Warranty as to the portion of the Products affected by the variance (the “Affected Products”). LP assumes no liability for any loss or damage sustained by the Affected Products and is expressly released by the purchaser or owner from any such loss or liability. Any modification of the Warranty’s application, finishing or maintenance requirements is void and unenforceable unless approved in writing prior to application by the Siding General Manager or his designee and a member of the LP Legal Department. For a copy of the warranty or for installation and technical support, visit the LP SmartSide product s­ upport Web site at: www.lpcorp.com or for additional support call 800.450.6106. Warranty remedies are not available if requirements are not followed. DO NOT OVERDRIVE NAILS. Nail head should seat firmly to face of siding, but not be overdriven to distort the siding surface. All siding joints must fall on studs. At shiplap edges, double nailing is required. Nailing d) NAILS MUST PENETRATE FRAMING MEMBERS AT LEAST 1-1/2 in. For best performance use hot-dipped galvanized nails with a minimum 1/4 in. diameter head. Nail at all special framing members around openings (maximum spacing 16 in. o.c.). Shim, if necessary, to provide solid backing for siding fitted around windows, doors, and at rake cuts on gable ends. e) When installing siding over maximum 1 in. foam sheathing, care must be taken not to drive nails so hard as to compress the foam and distort the siding surface. f)LP SmartSide siding should be sawn face up with a fine-tooth handsaw, or face down with a combination blade power saw. g)Where siding butts window trim, door casing, masonry, etc., leave a 3/16 in. gap and seal. © 2010 Louisiana-Pacific Corporation. All rights reserved. LP and SmartSide are registered trademarks of Louisiana-Pacific Corporation. Printed in U.S.A. NOTE: Louisiana-Pacific Corporation periodically updates and revises its product i­ nformation. To verify that this version is current, call 800-450-6106. LPZB0507 roof flashing detail joint treatment 1 in. Trim 3/8 in. over openings flash, shim, gap 3/16 in. ensure complete paint coverage of the drip edge Min. 3/16 in. gap 4 in. min. flashing Paint bottom edges 1 in. min. clearance from roofing Breathable weather resistant barrier gap 3/16 in. and seal gap 3/16 in. and seal starter strip outside corner detail inside corner detail bottom course detail 1-1/2 in. minimum 1-3/4 in. Breathable weather resistant barrier exposure 10 in. 3/4 in. nailing detail 1 in. 1-1/4 in. alignment notch detail 3/4 in. 1-1/4 in. ends of shakes must fall on studs Application instructions precision series 38 series, 76 series, 190 series primed panel siding Including Silvertech & SmartFinish (smooth square edge panel siding is approved for use with Carrara Stucco Finish ONLY) General • At the time of manufacture, LP's Precision Series primed panel siding meets or exceeds the performance standards set forth in ICC-ES acceptance criteria ACC321 and has achieved code recognition under the ICC-ES Report ESR-1301, and HUD recognition under HUD-MR-1318. For copies of ESR-1301, call LP Customer Support at 1-800-648-6893 or go on-line at http://www.icc-es. org/reports/pdf_files/ICC-ES/ESR-1301.pdf. • Minimum 6 in. clearance must be maintained between siding and finish grade. Moisture • Moisture control and moisture vapor control are critical elements of proper housing design. Check your local building codes for application procedures for handling moisture and moisture vapor in your area. • As with all wood products, do not apply engineered wood siding to a structure having excessive moisture conditions such as drying concrete or plaster. If such conditions exist, the building should be well ventilated to allow it to dry prior to the application of the siding. • S iding applied adjacent to porches, patios, walks, etc. must have a clearance of at least 1 in. mm above any surface. • Siding must not be applied to green or crooked structural framing members. Do not apply siding over rain-soaked or buckled sheathing materials. • Minimum 1 in. clearance at intersection with roof line • Gutters are recommended for control of roof water run off. • A pply siding in a manner that prevents moisture intrusion and water buildup. Secondary Weather Resistant Barrier • All exposed wood substrate must be sealed in a manner that prevents moisture intrusion and water buildup. • A properly installed breathable water-resistive barrier is required behind the siding. • I n non-traditional ICF and SIP assemblies, the ICF or SIP manufacturer must prescribe the fastening specifications. Note: LP does not recommend LP SmartSide Panel for use in these nontraditional assemblies. If used, LP will not warrant for Buckling and Shrinkage. However, balance of warranty does remain intact. • Consult your local building code for details. • When using wet blown cellulose insulation, the insulation must not be in direct contact with the siding and it must be allowed to dry a minimum of 24 hours or longer if specified by the insulation manufacturer. • LP will assume no responsibility for water penetration. Gaps & Sealants • Seal all gaps with a high-quality, non-hardening, paintable sealant with a minimum stated service life of 30 years. Follow the sealant manufacturer’s instructions for application. • DO NOT USE STAPLES Flashing, Windows, Doors & Openings Storage • S tore off the ground well supported, on a flat surface, under a roof or separate waterproof covering • Keep siding clean and dry. Inspect prior to application. • Allow siding to adjust to atmospheric conditions before application. Stud Spacing • Precision Series 38 Series and 76 Series panel siding must be installed on 16 in. OC framing only. When installing on 24 in. OC framing, Precision Series 190 Series panel siding is required. • All openings must be properly sealed or flashed in a manner that prevents moisture intrusion or buildup. Several examples that accomplish this are shown on the following pages. Trim Trim should be thick enough so the siding does not extend beyond the face of the trim. • Trim and fascia must be applied in a manner that will not allow moisture intrusion or water buildup. • LP® SmartSide® siding is not designed and/or manufactured to be used as trim or fascia. LP SmartSide trim and fascia are available in a variety of dimensions. Application instructions (cont.) Nailing Instructions Kick-Out Flashing • Install kick-out flashing to direct the water into the gutter • Install step flashing with minimum 4-inch upper leg • Properly integrate flashing with the secondary water-resistive barrier. Use housewrap, flashing tape, z-flashing, or other items as needed to maintain the counterflashing principle. • DO NOT extend the siding or trim into the kick-out flashing or gutter • Maintain a clearance between the end of the gutter and the adjoining wall to allow for proper maintenance of the siding • In braced wall assemblies, use minimum 6d (0.113 in. shank diameter), corrosion resistant according to ASTM 641, nails for 38 Series and 76 Series panels and minimum 8d (0.131 in. shank diameter) for 190 Series panels. Do not use electroplated fasteners. Refer to your local building code to verify the minimum allowable fastener size. • Penetrate studs or studs and wood sheathing a combined minimum of 1-1/2 in. 3/8 in. min. from edge Alignment bead • Paint ALL exposed cut edges 1/8 in. gap LP Siding Minimum 1" clearance between trim and roofing Nail penetration min. 1-1/2 in. Figure 1 Single row of nails Alignment bead 1/8 in. gap Clean rain gutter Do not run trim or siding inside of the kick out flashing Finishing Instructions DO • Prime and paint all exposed surfaces including all drip edges or where water will hang. • Apply finish coat as soon as possible or within 180 days of application. • High-quality acrylic latex paint, specially formulated for use on wood and engineered wood substrates, is highly recommended. Semi-gloss or satin finish oil or alkyd paints are acceptable. For flat alkyd paint, please check with the coating manufacturer for their recommendations for use on composite wood siding. • Follow the coating manufacturer’s application and maintenance instructions. DO NOT USE • Semi-transparent and transparent stains. • Shake and shingle paints. • Vinyl-based resin formulas such as vinyl acetate, PVA, vinyl acetate/acrylic copolymer paints. Figure 2 Double row of nails • For 38 Series panels, double nailing procedure meets wall bracing requirements and 5/16 in. shear wall design values. • For 76 Series and 190 Series panels, single nailing meets wall bracing requirements. To meet the equivalent 3/8 in. shear wall design values, double nailing procedures must be used. It may be necessary to angle drive the second nail in order to penetrate the framing. Seal nails driven below the surface. • Shear values for panels applied directly to studs shall be no greater than noted in Table 1 of the ICC-ES report ESR-1301. • Not warranted for application on SIP and ICF assemblies. CAUTION • 38 Series and 76 Series panels must be installed on 16 in. OC framing only. When installing on 24 in. OC framing, 190 Series panels are required. • Backside of panel must not come in contact with masonry foundation. • Do not force siding into place. Maintain the illustrated 1/8 in. space behind the joint to allow for expansion while the panel equilibrates with the local environment. • LP® SmartSide® Panel siding must not be attached by stapling. • DO NOT INSTALL OVER ALIGNMENT BEAD. Install panels in light contact to the edge of alignment bead. (see above drawing) Application instructions (cont.) Insulated Sheathings LP SmartSide Sidings may be installed over low-compression rigid foam or fiberglass sheathings. The following precautions must be followed: 1 in. Roof & Chimney Clearance a) Adequate bracing of the wall in accordance with the International Codes or other ruling building code is required. b) For rigid foam sheathing up to 1" (25.4 mm) thick, siding may be nailed directly to the foam sheathing unless a drainage plane is required by the local building code. Nail length must be increased to ensure a minimum 1-1/2” (38.1 mm) fastener penetration into the structural framing. c) For rigid foam sheathing greater than 1" (25.4 mm), a minimum 1-1/2” (38.1 mm) thick by 4” (101.6 mm) wide vertical strapping or furring strip must be installed over the sheathing to provide a solid, level nailing base for the siding. The strapping must be securely fastened to structural framing spaced no greater than 16” OC (406 mm) with a minimum nail penetration of 1-1/2 inches (38.1 mm) and a maximum nail spacing no greater than the width of the siding. Louisiana-Pacific will assume no responsibility for any damage or condition arising from the use of foam sheathing. Trim Min. 3/16 in. space at joint 4 in. min. flashing Paint bottom edges 1 in. min. clearance from roofing Figure 4 LP SmartSide Panel Siding Joint Details HORIZONTAL Wall joints Nail a min 3/8 in. from edge 12 in. max. field nail spacing 6 in. max. perimeter nail spacing Nail corner first 6 in. max. perimeter nail spacing Do not let panel contact masonry Figure 3 6 in. min. ground clearance Masonry LAP Siding BUTT & FLASH 3/8 in. min. gap Siding Blocking Blocking 1 in. min. overlap Sloped flashing (galv. or aluminum) Lap top panel over bottom panel Figure 5B Figure 5A LAPPED HORIZONTAL WALL JOINT Siding Framing (band joist, truss chord, etc.) CONDITION CORRECTION Snug OK Flush OK Visible fiber Paint Countersunk 1/16 in.-1/8 in. Seal with caulking Countersunk more than 1/8 in. Seal with caulk and renail 1 in. min. overlap Wall Framing Figure 5C HORIZONTAL beltline joints For multi-story buildings, make provisions at horizontal joints for “setting” shrinkage of framing, especially when applying siding directly to studs. Siding (4 ft. x 8 ft.) 3/8 in. gap Aluminum or galv. flashing BAND BOARD OVER PANEL FILLER 2 in. x 10 in. band board Filler Board Siding (4 ft. x 8 ft.) Figure 6 Siding Must Not Contact Masonry Stud Bottom plate OR Sill plate Floor system Extend siding below sill plate Flashing or moisture barrier Min. 1/8 in. or flashing between siding and masonry. LP assumes no liability for any loss or damage sustained by the Affected Products and is expressly released by the purchaser or owner from any such loss or liability. Any modification of the Warranty’s application, finishing or maintenance requirements is void and unenforceable unless approved in writing prior to application by the Siding General Manager or his designee and a member of the LP Legal Department. Masonry foundation Figure 7A Figure 7B or for additional support call 800.450.6106. Header Siding Code Approved Breathable Water-Resistive Barrier Casing For a copy of the warranty or for installation and technical support, visit the LP SmartSide product ­support Web site at: www.lpcorp.com Gap, Flash Doors & Windows Interior Wall Finish The Louisiana-Pacific Corporation (“LP”) LP SmartSide Siding (the “Products”) limited warranty (the “Warranty”) applies only to structures on which the Products have been applied, finished and maintained in accordance with the published application, finishing and maintenance instructions in effect at the time of application. The failure to follow such application, ­finishing or maintenance instructions will void the Warranty as to the portion of the Products affected by the variance (the “Affected Products”). Warranty remedies are not available if requirements are not followed. 3/8 in. gap Code Approved Flashing Insulation Filler Space according to the window/door manufacturer’s instruction Trim Nail fin (do not damage) Figure 8 4 ft. x 8 ft. Ungrooved Shiplap Panel Scant face width Figure 9 1/8 in. gap Space joint 1/8 in. Refer to nailing instructions 1/8 in. gap Cal. Prop 65 Warning: Use of this product may result in exposure to wood dust, known to the State of California to cause cancer. © 2012 Louisiana-Pacific Corporation. All rights reserved. LP, SmartSide, SilverTech and SmartFinish are registered trademarks of Louisiana-Pacific Corporation. Printed in U.S.A. NOTE: Louisiana-Pacific Corporation periodically updates and revises its product i­ nformation. To verify that this version is current, call 800-450-6106. LPZB0512 gap 3/16 in. and seal gap 3/16 in. and seal Figure 10B Figure 10A Figure 10 Vapor Retarder . 6 in n. 12 i 6 in. 6 in. minimum Figure 10C Figure 10E Figure 10D