NYC Department of Education
Building Condition Assessment Survey 2014-2015
Mechanical Inspection
K039
P.S. 39 - BROOKLYN, 417 6TH AVENUE, BROOKLYN, NY, 11215
School:
InspectionId
Inspection Type
489 MECHANICAL
Time In
Last Edited
2014-10-27 10:58AM
2014-11-05 03:57PM
Asset Data
Question
Answer
Have any Systems/Major Building Components been upgraded?
Systems:
Years:
Systems:
Years:
Systems:
MDF Room - Dedicated A/C Equipment ( Window
A/C )
2013
Fixtures - Student: Sinks; Urinals; Toilets; Gas Fired
Domestic Water Heater; Climate Control System:
Temperature Control Thermostats; Exhaust Fans (3 of
9)
2010
Exhaust Fans (2 of 9)
Are there fuel tanks?
Total # of above ground tanks
Total capacity of all above ground tanks in gal.
Total # of below ground tanks
Total capacity of all below ground tanks in gal.
Total # of water main service entries to the asset
Years:
Yes
2
3,000
0
0
2
2008
MERs/Fan Rooms Locations
Basement MER
Priority Condition
Priority Condition
Exist Last Year?
Priority
Category
Condition
Description
Component
Affected
Location
Description
Person(s) Notified
Person(s) Title
PhotoImage
No condition recorded
Inspection
Question
Response
Mechanical
AIR CONDITIONING
Does not exist
CENTRAL ACID WASTE NEUTRALIZING TANK
Does not exist
CLIMATE CONTROL SYSTEM
Inspected
BMS
Does not exist
Electric System
Does not exist
Hybrid System
Does not exist
Pneumatic System
Inspected
Instance
Throughout
3- Fair
Instance Condition
Instance Quantity
1
EACH
Instance Quantity Uom
Building Area Covered by Operational System
21-40%
Deficiency
Deficiency Location/Instance
Deficiency Quantity
DEFECTIVE TERMINAL UNIT CONTROL VALVE
Various Locations
30
EACH
MAINTENANCE
PRIORITY 3
LEVEL 2
No violations recorded
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
COMPACTOR
Does not exist
CONVEYING
Does not exist
DOMESTIC WATER SYSTEM
Inspected
Domestic Cold Water System
Inspected
Gravity System
Does not exist
Pressure Booster System
Does not exist
Water Service
Inspected
Mobile Validity Version 2.0 (P)
Page 1 of 7
Print Date: 6/16/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Mechanical Inspection
K039
Question
Response
DOMESTIC WATER SYSTEM
Domestic Cold Water System
Water Service
Instance
Basement - South
3- Fair
Instance Condition
Instance Quantity
2
EACH
Instance Quantity Uom
Deficiency
WATER MAIN:MISSING BACKFLOW PREVENTION
DEVICE
Basement - South
1
EACH
INSTALL
PRIORITY 3
LEVEL 2
No violations recorded
Deficiency Location/Instance
Deficiency Quantity
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
Inspected
Domestic Hot Water System
Domestic Hot Water Remote Storage Tank
Does not exist
Domestic Water Heat Exchanger
Does not exist
Electric Domestic Water Heater
Does not exist
Gas Fired Domestic Water Heater
Inspected
Instance
Boiler Room
1- Good
Instance Condition
Instance Quantity
Instance Quantity Uom
1
EACH
Manufacturer
EquipmentId
Capacity/Size Quantity
Capacity/Size UOM
Capacity/Size 2 Quantity
Capacity/Size 2 UOM
Source of Capacity/Size
Installation Year
Source of Installation Year
Rheem / Ruud
N/A
80
MBH Input
100
Gallons
Documented
2010
Documented
Deficiency
No deficiencies recorded
Does not exist
Oil Fired Domestic Water Heater
Inspected
Domestic Water Distribution Piping
3- Fair
Condition
Deficiency
No deficiencies recorded
Inspected
DRAIN/WASTE/VENT AND STORM SYSTEM
Interior Storm Piping
Does not exist
Sewage Ejector Pump
Does not exist
Sewage/Waste/Vent Piping
Inspected
3- Fair
Condition
Deficiency
No deficiencies recorded
Inspected
Sump Pump
3- Fair
Condition
Deficiency
No deficiencies recorded
DUAL TEMPERATURE SYSTEM (CHILLED AND HOT WATER)
Does not exist
Enclosed IDF Room
Does not exist
FIXTURES
Inspected
Staff And Other
Inspected
Janitor Sink
Inspected
Condition
3- Fair
Deficiency
Mobile Validity Version 2.0 (P)
No deficiencies recorded
Page 2 of 7
Print Date: 6/16/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Mechanical Inspection
K039
Question
Response
FIXTURES
Staff And Other
Inspected
Lavatory/Sink
Condition
3- Fair
Deficiency
No deficiencies recorded
Inspected
Toilet
Condition
3- Fair
Deficiency
No deficiencies recorded
Does not exist
Urinal
Inspected
Student
Inspected
Drinking Fountain
Condition
3- Fair
Deficiency
No deficiencies recorded
Inspected
Lavatory/Sink
Condition
1- Good
Deficiency
No deficiencies recorded
Locker Room Shower
Does not exist
Sink And Fountain Combo Unit
Does not exist
Toilet
Inspected
Condition
1- Good
Deficiency
No deficiencies recorded
Inspected
Urinal
Condition
1- Good
Deficiency
No deficiencies recorded
GAS FIRED FURNACE
Does not exist
GAS SERVICE
Inspected
Inspected
CO/Gas Leak Detection
Instance
Boiler Room, Gas Meter Room
3- Fair
Instance Condition
Instance Quantity
Instance Quantity Uom
1
EACH
Installation Year
Source of Installation Year
2001
Documented
Deficiency
No deficiencies recorded
Inspected
Gas Distribution Piping
1- Good
Condition
Deficiency
No deficiencies recorded
Inspected
Gas Meter Room Exhaust Fan
2- Between Good and Fair
Condition
Deficiency
No deficiencies recorded
Inspected
Gas Meter Room Vent
1- Good
Condition
Deficiency
No deficiencies recorded
Does not exist
Gas Pressure Booster
Inspected
HEATING
Heating Coil In Ductwork
Does not exist
Hydronic Heating
Does not exist
Radiator/Convector/Fin Tube
Inspected
3- Fair
Condition
Deficiency
No deficiencies recorded
Inspected
Steam Heating
Inspected
F&T/Steam Drip Trap
Condition
5- Poor
Deficiency
Mobile Validity Version 2.0 (P)
DEFECTIVE/DETERIORATED
Page 3 of 7
Print Date: 6/16/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Mechanical Inspection
K039
Question
Response
HEATING
Steam Heating
F&T/Steam Drip Trap
Deficiency Location/Instance
Deficiency Quantity
Basement MER and Cafeteria
10
EACH
REPLACE
PRIORITY 3
LEVEL 2
No violations recorded
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
Inspected
MER Steam and Condensate Piping
Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Inspected
Steam Condensate Return Piping
Condition
3- Fair
Deficiency
No deficiencies recorded
Inspected
Steam Condensate Return Pumping System
Condition
3- Fair
Deficiency
Deficiency Location/Instance
Deficiency Quantity
DEFECTIVE MOTOR
Boiler Room
1
EACH
REPLACE
PRIORITY 3
LEVEL 2
No violations recorded
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
Inspected
Steam Piping
Condition
3- Fair
Deficiency
No deficiencies recorded
Inspected
Terminal Unit Thermostatic Trap
Condition
5- Poor
Deficiency
Deficiency Location/Instance
Deficiency Quantity
DEFECTIVE/DETERIORATED
Throughout
40
EACH
REPLACE
PRIORITY 3
LEVEL 2
No violations recorded
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
Steam supplied by External Sources
Does not exist
Unit Heater/Cabinet Heater
Inspected
2- Between Good and Fair
Condition
Deficiency
No deficiencies recorded
HEATING PLANT
Replacement Quantity
3,466
MBH Net
Replacement Uom
Inspected
Dual Fuel (Gas / Oil)
2
Instance on Basement
Burner Type
Heating Plant Oil Number
Boiler Auxiliaries
Inspected
Instance on Basement
Boiler Auxiliary Piping
Instance on Basement
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Boiler Emergency Stop Switch
Mobile Validity Version 2.0 (P)
Page 4 of 7
Print Date: 6/16/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Mechanical Inspection
K039
Question
Response
HEATING PLANT
Boiler Auxiliaries
Boiler Emergency Stop Switch
Instance on Basement
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Boiler Feedwater System
Instance on Basement
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Boiler Feedwater Treatment(Automatic)
Instance on Basement
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Boiler Flue Exhaust
Instance on Basement
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Boiler Make-up Water Backflow Preventer
Instance on Basement
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Boiler Room Steam And Condensate Piping
Instance on Basement
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Boiler Safety Valve
Instance on Basement
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Boiler System
Inspected
Instance on Basement
Coal-fired Boiler
Does not exist
Instance on Basement
Hot Water Boiler
Does not exist
Instance on Basement
Modular Boiler
Does not exist
Instance on Basement
Steam Boiler
Instance on Basement
Inspected
Instance
Boiler Room
2- Between Good and Fair
Instance Condition
Instance Quantity
Instance Quantity Uom
1,733
MBH Net
Manufacturer
EquipmentId
Capacity/Size Quantity
Capacity/Size UOM
Source of Capacity/Size
Installation Year
Source of Installation Year
H. B. Smith Co., Inc.
13097-01
1733
MBH Net
Documented
2001
Documented
Deficiency
No deficiencies recorded
Instance
Instance Condition
Boiler Room
2- Between Good and Fair
Instance Quantity
1,733
Mobile Validity Version 2.0 (P)
Page 5 of 7
Print Date: 6/16/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Mechanical Inspection
K039
Question
Response
HEATING PLANT
Boiler System
Steam Boiler
Instance Quantity Uom
MBH Net
Manufacturer
EquipmentId
Capacity/Size Quantity
Capacity/Size UOM
Source of Capacity/Size
Installation Year
Source of Installation Year
H. B. Smith Co., Inc.
13097-02
1733
MBH Net
Documented
2001
Documented
Deficiency
No deficiencies recorded
Fuel System
Inspected
Instance on Basement
Boiler Fresh Air Louver/Damper
Instance on Basement
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Burner/Burner Control Panel
Instance on Basement
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Fuel Oil Storage/Supply System
Instance on Basement
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
Deficiency Location/Instance
Deficiency Quantity
OVERFILL ALARM BY OIL FILL:DEFECTIVE
Outside at Oil Fill
1
EACH
MAINTENANCE
PRIORITY 3
LEVEL 4
2-609601
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
Gas Trains And Vent At The Boiler
Instance on Basement
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
KITCHEN
Inspected
Instance on Basement
CO Detector
Not required
Instance on Basement
Gas System
Does not exist
Instance on Basement
Grease Trap
Instance on Basement
Does not exist
Instance on Basement
Does not exist
Hood
Hood Exhaust Ductwork
Does not exist
Instance on Basement
Hood Exhaust Fan
Does not exist
Instance on Basement
Hood Fire Suppression System
Does not exist
Instance on Basement
Hot Water Temperature Booster
Does not exist
Instance on Basement
Mobile Validity Version 2.0 (P)
Page 6 of 7
Print Date: 6/16/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Mechanical Inspection
K039
Question
Response
KITCHEN
Kitchen Sink
Instance on Basement
Inspected
Instance Condition
3- Fair
Deficiency
No deficiencies recorded
MDF Room
Inspected
Instance on Room 302
Dedicated A/C Equipment
Instance on Room 302
Inspected
Instance Condition
1- Good
Deficiency
No deficiencies recorded
SCIENCE DEMO ROOM
Does not exist
SCIENCE LAB
Does not exist
SCIENCE PREP ROOM
Does not exist
SPRINKLERS, STANDPIPE, FIRE SYSTEM
Inspected
Dry Sprinkler Alarm Valve Assembly
Does not exist
Fire Booster Pump Assembly
Does not exist
Roof Tank
Does not exist
Siamese Connection
Does not exist
Sprinkler Head
Inspected
3- Fair
Condition
Deficiency
No deficiencies recorded
Inspected
Sprinkler Piping
3- Fair
Condition
Deficiency
No deficiencies recorded
Standpipe System
Does not exist
Water Gong
Does not exist
Wet Sprinkler Alarm Valve Assembly
Does not exist
SWIMMING POOL
Does not exist
VENTILATION
Inspected
Exhaust Fan
Inspected
2- Between Good and Fair
Condition
Approximate Total # of Fans
Deficiency
1-25
No deficiencies recorded
Heating And Ventilating Unit
Does not exist
Metal Ductwork
Inspected
2- Between Good and Fair
Condition
Deficiency
No deficiencies recorded
Supply Fan
Does not exist
Unit Ventilator
Does not exist
Mobile Validity Version 2.0 (P)
Page 7 of 7
Print Date: 6/16/2015