PHYSICAL FACILITIES 2015 Consultant’s Handbook Division 33 UTILITIES 7726 MEDIUM VOLTAGE SWITCHGEAR 1 2 2.10 References Switch & fuse integrated ratings • NFPA 70 National Electric Code Rated Maximum Voltage (KV) 13.8 • IEEE C2 Code National Electric Safety Rated Withstand Impulse BIL (KV) 95 • IEEE C37.20.3 Metal-Enclosed Interrupter Switchgear Continuous and Load Interrupting Current (A) 600 • ANSI C57.12.28 Switchgear & Transformer – Pad-Mounted Equipment Enclosure Integrity Short-Circuit Interrupting Current (kA rms Sym) 34.6 Duty-Cycle Fault-Close Current (kA Asym) 40 Load Interrupter Switchgear 2.1 The quality of components is to be that represented by S & C Electric Co. 2.2 Provide an Incoming Termination section with surge protection and copper bus connection. 2.3 Provide a switch and fuse combination section for each transformer, flange connected to the transformer, with a transition section if necessary. 2.4 Load interrupter switch shall be a threepole, single-throw, metal-enclosed type with manual stored energy operator which shall simultaneously disconnect or connect ungrounded conductors. The moveable blade of the switch shall be de-energized when in the open position. The mechanism shall enable the switch to close against a fault equal to the momentary rating of the switch without affecting its continuous current carrying or load interrupting ability. 3 Pad Mounted, Metal-Enclosed Switchgear 3.1 The quality of components is to be that represented by: 3.1.1 “PMU Pad-Mounted Switchgear” per specification 662-451 as modified for PMU features as manufactured by the S & C Electric Co. 3.2 The basic configuration for transformer is PMU-5 and for two is PMU-7. one 3.3 The switchgear shall be configured with one incoming compartment for radial-feed, equipped with air-insulated, load-interrupter switch. The outgoing compartment shall be provided with fused disconnects. 3.3 Switches shall be provided with a manual, handle-type operator utilizing a stored-energy (spring-driven) mechanism to simultaneously open or close all phases. 2.5 A ground bus shall extend the width of the switch enclosure and shall be bolted directly thereto. Connect frame of unit to ground bus and provide for attachment to ground grid at each end. 3.4 The switchgear shall be configured so that the switch actuator is padlockable, but may be accessed without opening the switch compartment doors. 2.6 The door shall have an inspection window to allow full view of the position of the three switch blades. 3.5 Fused compartments shall be disconnect non-load break type hook-stick removable. 2.7 Switch shall have provision for padlocking in the open and closed positions. 2.8 Switch shall be fused, with fuses mounted on a single frame below switch. 2.9 Fuse rating shall be appropriate to provide 125 percent of the transformer full-load rating, sustain no damage from magnetizing in-rush current, and provide protection against thermal damage. 3.6 Switchgear enclosures shall be of freestanding, self-supporting construction provided with separate incoming and outgoing compartments configured for bottom cable entry. Enclosures shall be of live-front construction, provided with a hinged door for access to each compartment. Page 1 of 2 PHYSICAL FACILITIES 2015 Consultant’s Handbook Division 33 UTILITIES 7726 MEDIUM VOLTAGE SWITCHGEAR 3.7 Switch & Fuse Integrated Ratings Rated Maximum Voltage (KV) 13.8 Rated Withstand Impulse BIL (KV) 95 Continuous and Load Interrupting Current (A) 600 Short-Circuit Interrupting Current (kA rms Sym) 25 Duty-Cycle Fault-Close Current (kA Asym) 40 Page 2 of 2