NEC Code - PEMBA Lighting and Automation

advertisement
NEC Code Changes
®
Overview of 2011
Related to Electrical
Wiring Devices
Cablofil
Pass & Seymour
Wiremold
104 P Street Belle Chasse, LA 70037
504-394-4132, fax 504-394-6922
www.pembaserv.com
Legrand/Pass & Seymour®: your source for safety.
Today’s NEC® regulations have new
safety requirements. We have new
ways to help you meet them.
In 1971, Pass & Seymour introduced
the first in-wall GFCI receptacle. Soon,
our invention was preventing injuries
and saving lives throughout North
America.
Today, you’ll find P&S innovations
and safety throughout a broad range
of GFCI products – products that offer
new versatility, save installation time
and solve problems. And products that
continue a proud safety tradition that
we began over 35 years ago.
Choose P&S GFCI products for
innovation – and for all your groundfault protection needs.
P&S Tamper-Resistant Receptacles
- the full line to meet the NEC® and
enhance child safety.
P&S Tamper-Resistant Receptacles
protect children by letting plugs in,
but keeping keys and other objects
out with automatic shutters that block
access. Safer and more convenient
than plastic outlet caps, this proven
safety solution provides a simple way
to prevent painful injuries. And because
tamper-resistant receptacles provide a
real solution to a real problem, they’re
required in new residential construction
by the National Electrical Code®.
You’ll find everything you’re looking
for in the broad P&S TamperResistant Receptacle line. Protection
and traditional style in our 3232
TradeMaster® Duplex Receptacle.
Unique models like the P&S
Nightlight/GFCI Combination. Fresh
style in our P&S Signature™ choices.
And much more!
For more information, ask your
Pass & Seymour distributor or visit
www.legrand.us/passandseymour.
Page i
TABLE OF CONTENTS
NEC SECTION
210.7
210.8
210.8(A)(7)
210.8(B)(5)
210.8(B)(6)
210.8(B)(7)
210.8(B)(8)
210.12(A)
210.12(B)
210.52(A)(2)(1)
210.52(A)(4)
210.52(C)(4)
210.52(C)(5) & 210.52(D)
210.52(E)(3)
210.52(G)
210.52(I)
285.25
310
314.24
314.27(A)
314.27(C)
380.1 & 380.23
390.2
404.2(C)
404.9(B)
DESCRIPTION
Disconnection of Multiple Branch Circuits and
Multiwire Branch Circuits
Readily Accessible GFCIs
GFCI Protection of Receptacles Near Sinks in Dwellings
Exception no. 2 to (5) GFCI Protection of Receptacles
Near Sinks in Health Care Facilities
GFCI Protection of Indoor Wet Location Receptacles
GFCI Protection of Receptacles in Locker Rooms
GFCI Protection for Receptacles in Commercial Garages
Exception 1 & 2 Arc Fault Circuit Interrupter (AFCI)
Protection of Outlets in Dwellings
Arc Fault Circuit Interrupter (AFCI) Protection of
Outlets in Dwellings
Receptacle Spacing in Dwelling Units
Countertop Receptacles
Separate Countertop Spaces
Receptacles in Kitchen and Bathroom Countertops
Receptacles on Balconies, Decks and Porches
Receptacles in Basements, Garages and
Accessory Buildings
Receptacle Outlets in Dwelling Unit Foyers
Type 3 Surge-Protective Devices
(Transient Voltage Surge Suppressors)
Conductors for General Wiring
Outlet and Device Box Depth
Outlet Boxes for Luminaires
Outlet Boxes for Ceiling Fans
Multioutlet Assemblies
Underfloor Raceways
Switches Controlling Lighting Loads
Exceptions nos. 1, 2, & 3 Grounding of Snap Switches,
National Electrical Code ® and NEC ® are registered trademarks of the National Fire Protection Association, Inc., Quincy, MA 02269.
PAGE
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
Page 1
Page ii
SECTION 210.7
TABLE OF CONTENTS
NEC SECTION
404.14(F)
406.2 & 406.14
406.4(D)(4)
406.4(D)(5)
406.4(D)(6)
406.6
406.9(B)(1)
406.12
406.13
430.42(C), 430.81(B),
430.109(F)
517.13(B)(1)(2)
517.16
517.18(B) & 517.19(B)(2)
517.20(A)
518.3(B)
525.23
550.13(B)
550.13(F)(1)
550.25
551.47(L) & 552.48 (K)
552.59(A)
590.4(D)(2)
604.6(A)(5)
625
680.21(C)
680.32
Dimmers and Similar Control Switches
DESCRIPTION
Snap Switch Rating for Plug and Cord Connected Loads
Tamper-Resistant Receptacles in Child Care Areas
Arc Fault Circuit Interrupter Protection of
Replacement Receptacles
Tamper-Resistant Replacement Receptacles
Weather-Resistant Replacement Receptacles
Recessed Receptacle Faceplates
Receptacles in Wet Locations
Tamper-Resistant Receptacles for Dwelling Units
Tamper-Resistant Receptacles in Guest Rooms
and Guest Suites
Cord and Plug Connected Motors
Grounding of Receptacles in Patient Care Areas of
Health Care Facilities
Isolated Ground Receptacles in Health Care Facilities
Patient Bed Location Receptacles in Health Care Facilities
Receptacles in Wet Procedure Location Patient Care Areas
Temporary Wiring in Exhibition Halls
GFCI Protection for Carnivals, Circuses, Fairs
GFCI Protection of Receptacles in
Mobile/Manufactured Homes
Receptacles Near Bathtubs and Shower Stalls in
Mobile/Manufactured Homes
AFCI Protection of Branch Circuits in
Mobile/Manufactured Homes
Receptacle Faceplates in Recreational Vehicles
and Park Trailers
Park Trailer Outdoor Receptacles and Switches
Receptacles in Temporary Installations
Manufactured Wiring Systems
Electric Vehicle Charging System
GFCI Protection of Pool Pump Motors
Receptacles Near Storable Pools
PAGE
26
27
28
Disconnection of Multiple Branch Circuits and
Multiwire Branch Circuits
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
■ Ungrounded conductors must be simultaneously disconnected when two or
more branch circuits supply devices on the same yoke.
Section 210.7 is intended to reduce the likelihood of unexpected shock
hazards for persons working on devices on the same yoke that are
connected to multiple branch circuits.
A means to simultaneously disconnect the ungrounded conductors must be
provided at the point where the branch circuits originate when two or more
branch circuits supply devices on the same yoke. Although the title in the
2011 NEC® for Section 210.7 has changed to clearly state this section deals
with Multiple Branch Circuits, the requirement remains the same.
Section 210.4(B) addresses a similar hazard when a multiwire branch circuit
supplies devices on the same yoke. The ungrounded conductors must also
be simultaneously disconnected at the point where the branch circuit
originates.
An informational note was added to Section 404.8(C) as a reminder that
Section 210.7 applies if multiple circuits are supplying a multipole switch.
P&S Cat. #s: 5262, 3232, 8200HI
Technical Support 800-223-4185
www.legrand.us
Page 3
Page 2
SECTION 210.8
SECTION 210.8(A)(7)
Readily Accessible GFCIs
GFCI protection of Receptacles Near Sinks in Dwellings
6'
■ 15A and 20A, 125V receptacles within 6 feet of a sink in a dwelling must
be GFCI protected.
■ GFCIs installed per 210.8 must be readily accessible.
Ground Fault Circuit Interrupters that provide protection for
receptacles as specified in Sections 210.8 (A), (B) and (C) must now
be installed in a readily accessible location. GFCIs are marked “test
monthly” and are provided with a test button that must be operated
monthly to insure that the GFCI is functioning properly. Locating a
GFCI where it is accessible will increase the likelihood that the GFCI
will be tested by the user. A location that is Readily Accessible is
defined in Article 100 of the NEC®.
P&S Cat. #s: 1595, 2095v
Technical Support 800-223-4185
www.legrand.us
GFCI protection must be provided for receptacles within 6 feet of all sinks
in a dwelling. Previously, the requirement applied only to laundry, wet bar
and utility sinks. This revision to the 2011 NEC® parallels the requirement
in Section 210.8(B)(5) to provide GFCI protection for receptacles within
6 feet of sinks in commercial and other non-dwelling installations. The
code now insures that the same level of GFCI protection is provided for
receptacles near sinks in all installations.
Although Section 210.8(A)(7) states that the requirement applies to sinks
other than those in kitchens, the intent is not to exempt countertop
receptacles near kitchen sinks from having GFCI protection. Kitchen
countertop receptacles are to required to have GFCI protection per Section
210.8(A)(6). As a result, receptacles that serve countertops located near
kitchen sinks will have GFCI protection. The wording of Section 210.8(A)(7)
is intended to make it clear that other receptacles, such as dishwasher and
disposal receptacles that may be within 6 feet of a kitchen countertop sink,
are not required to have GFCI protection.
P&S Cat #s: 1595, 2095
Technical Support 800-223-4185
www.legrand.us
Page 5
Page 4
SECTION 210.8(B)(5) Exception No.2 to (5)
SECTION 210.8(B)(6)
GFCI Protection of Receptacles Near Sinks in
Health Care Facilities
GFCI Protection of Indoor Wet Location Receptacles
PZ1624
■ GFCI protection is required for 15A and 20A, 125V receptacles within 6
feet of sinks except in patient bed locations in general care or critical
care areas.
The exception to Section 210.8(B)(5) has been revised to make it clear
that GFCI protection is not required for receptacles located near sinks
in patient bed locations of general care or critical care areas. There is
concern that receptacles located near hand washing sinks in these
areas may be used for patient care life support, monitoring, and other
portable patient care equipment that should not be plugged into a
receptacle protected by a GFCI.
Patient Bed Locations, Critical Care Areas and General Care Areas are
defined in Article 517 of the code.
■ 15A and 20A, 125V receptacles located in indoor wet locations are
required to be GFCI protected.
This new section has been added to the 2011 NEC® to require GFCI
protection for receptacles located in indoor wet locations in other than
dwellings. An indoor wet location is an area such as a car wash or food
processing facility.
Receptacles located in indoor wet locations are exposed to the same
potentially hazardous conditions that exist in outdoor wet locations.
Section 210.8(B)(4) requires outdoor receptacles to be GFCI protected.
This new requirement will insure that receptacles in indoor wet
locations are provided with the same level of GFCI protection.
This exception does not apply to other locations in Health Care
Facilities. The exception is specific to General and Critical Care Areas.
A receptacle located within 6 feet of a sink in other areas must be
GFCI protected.
P&S Cat #s: 1595HG, 2095HG
Technical Support 800-223-4185
www.legrand.us
P&S Cat #s: 1595, 2095
Technical Support 800-223-4185
www.legrand.us
Page 7
Page 6
SECTION 210.8(B)(7)
SECTION 210.8(B)(8)
GFCI Protection of Receptacles in Locker Rooms
GFCI Protection for Receptacles in Commercial Garages
■ 15A and 20A, 125V receptacles in garages where electrical diagnostic
■ 15A and 20A, 125V receptacles located in a locker room with an
equipment, electrical hand tools or portable lighting equipment is used
must be GFCI protected.
associated shower facility must be GFCI protected.
GFCI protection is now required for receptacles located in locker
rooms that have an associated shower facility. A shower located near
a locker room may create a hazardous condition. The damp and wet
conditions in a locker room due to proximity to a shower, the use of
electrical personal grooming equipment, such as a hair dryer, people
with bare feet exposed to the damp tile floor of a locker room, all
contribute to the increased risk of electrical shock. GFCI protected
receptacles will provide a significantly increased level of safety in this
type of environment.
P&S Cat #s: 1595, 2095
Technical Support 800-223-4185
www.legrand.us
GFCI protection for receptacles in dwelling unit garages is required
by Section 210.8(A)(2). Section 511.12 requires GFCI protection for
receptacles in commercial service and repair garages where volatile
flammable liquids or gases are used for vehicle fuel or power.
This new Section, 210.8(B)(8), ensures that the same level of GFCI
protection for receptacles will be provided in all garages, service bays
and similar areas where electrical diagnostic equipment, electrical
hand tools and portable lighting equipment are used. An example of
a garage or service area not previously covered is a service facility for
plug-in electric hybrid vehicles.
P&S Cat #s: 1595, 2095
Technical Support 800-223-4185
www.legrand.us
Page 9
Page 8
SECTION 210.12(A) Exception 1&2
SECTION 210.12(B)
Arc-Fault Circuit Interrupter (AFCI) Protection of
Outlets in Dwellings
Arc-Fault Circuit Interrupter (AFCI) Protection of
Outlets in Dwellings
■ A Circuit Breaker or Receptacle Type AFCI must provide protection of
■ A Receptacle Type AFCI may provide protection of the branch circuit.
In the 2008 NEC® the definition for an AFCI was in section 210.12(A). The definition
has been relocated to Article 100 in the 2011 NEC®.
As a result of moving the AFCI definition to article 100, the requirements for AFCI
protection that were stated in Section 210.12(B) in the 2008 NEC® have been
moved to section 210.12(A). Section 210.12(A) in the 2011 NEC® requires AFCI
protection for 120 volt, 15 and 20 amp branch circuits supplying outlets in family
rooms, dining rooms, living rooms, parlors, libraries, dens, bedrooms, sunrooms,
recreation rooms, closets, hallways, or similar rooms or areas.
The exceptions to 210.12(A) permit a receptacle type Outlet Branch Circuit AFCI to
provide the required protection when located at the first outlet of the branch
circuit under the following conditions:
Exception No. 1 – The branch circuit conductors from the origin of the branch
circuit to the first outlet are installed in RMC, IMC, EMT, MC cable or steel
armored AC cable. Metal outlet and junction boxes must also be used between the
origin of the branch circuit and the first outlet.
Exception No. 2 – The branch circuit conductors from the branch circuit
overcurrent device to the first outlet are installed in listed metal or nonmetallic
conduit or tubing encased in at least 2 inches of concrete.
Technical Support 800-223-4185
www.legrand.us
branch circuit extensions and modifications.
Section 210.12(A) in the 2011 NEC® requires AFCI protection for
120 volt, 15 and 20 amp branch circuits supplying outlets in family
rooms, dining rooms, living rooms, parlors, libraries, dens, bedrooms,
sunrooms, recreation rooms, closets, hallways, or similar rooms
or areas.
A new section, 210.12(B), has been added to require AFCI protection
for branch circuit modifications and extensions of the circuits specified
in Section 210.12(A). The AFCI protection for the modified or extended
circuits may be a listed Combination AFCI at the origin of the branch
circuit or a listed Outlet Branch Circuit AFCI located at the first
receptacle outlet of the circuit.
The Combination AFCI located at the origin of the branch circuit is
typically a circuit breaker AFCI. The Outlet Branch Circuit AFCI located
at the first receptacle outlet will be a receptacle type AFCI. Either
device may be used to meet the requirements of 210.12(B).
Technical Support 800-223-4185
www.legrand.us
Page 11
Page 10
SECTION 210.52(A)(2)(1)
SECTION 210.52(A)(4)
Receptacle Spacing in Dwelling Units
Countertop Receptacles
■ Fixed cabinets are not included in determining the unbroken wall
space for receptacle spacing.
■ Receptacles serving countertops are not considered as meeting the
general provisions for receptacle spacing.
Section 210.52(A) provides the spacing requirements for the
installation of receptacles in dwellings. When measured horizontally
along the floor line of a wall space no point may be more than 6 feet
from a receptacle. Section 210.52(A)(2)(1) defines a wall space as any
space that is at least 2 feet wide and is uninterrupted along the floor
line by an opening. In addition to openings, this section has been
revised to include fixed cabinets. This insures that fixed cabinets, such
as kitchen cabinets, are taken into account and are not included when
determining the unbroken width of a wall space.
P&S Cat #s: 885, 3232, 885TR, 3232TR
Technical Support 800-223-4185
www.legrand.us
A new section, 210.52(A)(4), has been added to make it clear that the
countertop receptacles installed to comply with Section 210.52(C) may
not be considered as the receptacles that meet the general provision
installation requirements for receptacles in Section 210.52(A). The
countertop receptacles are intended to serve the appliances that are
used on a countertop space.
P&S Cat #s: 885, 3232, 885TR, 3232TR
Technical Support 800-223-4185
www.legrand.us
Page 13
Page 12
SECTION 210.52(C)(4)
SECTION 210.52(C)(5) and 210.52(D)
Separate Countertop Spaces
Receptacles in Kitchen and Bathroom Countertops
■ Listed receptacle assemblies may be installed in kitchen and bathroom
■ Receptacles are required in separate countertop spaces.
countertops.
The conditions describing when a countertop space is divided into
separate countertop spaces by a counter-mounted cooking unit,
range or sink have been moved from the general Section 210.52(C) to
subsection 210.52(C)(4). Although the requirement has not changed, it
was recognized that Section 210.52(C)(4) is the section that deals with
separate countertop spaces.
P&S Cat #s: 1595, 2095
Technical Support 800-223-4185
www.legrand.us
Section 406.4(E) prohibits the installation of receptacles in a face up
position in countertops. However, sections 210.52(C)(5) and 210.52(D)
have been revised to permit listed receptacle outlet assemblies to be
installed in kitchen and bathroom countertops. This change has been
made to allow the installation of receptacle assemblies in the top
surface of a countertop. The receptacle assemblies must be listed to
insure that they have been evaluated to function properly when
exposed to conditions likely to be encountered in countertop
installations, such as liquid spills and splashing. A typical receptacle
assembly for this application is a pop up type of receptacle having a
cover that is flush with the countertop when not in use and pops up
when operated to reveal the receptacle face.
Wiremold Cat. #s: KP2345, KP9999
Technical Support 800-223-4185
www.legrand.us
Page 15
Page 14
■
SECTION 210.52(E)(3)
SECTION 210.52(G)
Receptacles on Balconies, Decks and Porches
Receptacles in Basements, Garages and Accessory Buildings
The receptacle must be located within the perimeter of the balcony,
deck or porch.
At least one 125 volt, 15 or 20 amp outdoor receptacle must be
provided to serve a balcony, deck or porch of a dwelling. The
receptacle must be located within the perimeter of the balcony, deck
or porch. This requirement is intended to avoid the use of extension
cords routed from an inside receptacle through windows or doorways
to supply holiday lighting and other electrically operated products used
outdoors. The 2008 NEC® had an exception stating that for areas less
than 20 ft2 a receptacle was not required. The 2011 NEC® has deleted
this exception recognizing that electrically operated products could be
used on decks, porches and balconies having an area less than
specified in the exception.
■ At least one receptacle outlet is required in each basement, garage and
accessory building in one family dwellings.
Accessory buildings have been added as a location where at least
one receptacle must be installed. Many dwellings have additional
buildings, other than garages, where electrical equipment is utilized.
Section 210.8(A)(2) requires the receptacle to be GFCI protected.
P&S Cat #s: 1595TRWR, 2095TRWR, 1595DS, 2095DS, WIUC10
P&S Cat #s: 1595TRWR, 2095TRWR, 1595DS, 2095DS
Technical Support 800-223-4185
Technical Support 800-223-4185
www.legrand.us
www.legrand.us
Page 17
Page 16
SECTION 210.52(I)
SECTION 285.25
Receptacle Outlets in Dwelling Unit Foyers
Type 3 Surge-Protective Devices
(Transient Voltage Surge Suppressors)
■ Type 3 SPDs are permitted to be installed on the load side of the branch
■ Receptacles must be installed in foyers.
circuit overcurrent protection.
Receptacle outlets will now be required in foyers. This change
recognizes that many homes are built with large foyers. Lamps and
other cord and plug connected electrical equipment will be located
in these foyers and receptacles are required for connection of this
equipment. A foyer having an area of greater than 60 ft² must have a
receptacle located in each continuous wall that has a width of at least
3 ft that is unbroken by a floor to ceiling window, a door or other
similar opening.
Type 3 Surge Protective Devices (SPD) installed on the load side of the branch
circuit overcurrent protection were required by Section 285.25 of the 2008 NEC® to
be located at least 30 feet from the service. In the 2011 NEC® this section has been
revised to state that the requirement to install the Type 3 SPD at least 30 feet from
the service is necessary only when specified in the manufacturers instructions. This
change recognizes that a Type 3 SPD that has been subjected to additional testing
may be installed anywhere in the branch circuit on the load side of the overcurrent
protection. UL 1449, the Standard for Surge Protective Devices, requires a Type 3
SPD that has not been evaluated by the additional testing to be marked “CAUTION –
Do not install this device if there is not at least 10 meters (30 feet) or more of wire
between the electrical outlet and the electrical service panel.” If this marking does
not appear on the SPD or in the instruction sheet the Type 3 SPD may be installed
anywhere in the branch circuit.
Type 3 SPDs are typically cord connected power strips or receptacle type devices.
P&S Cat. #s: 5362GRYSP, TR5362GRYSP, PT5362GRYSP
Wiremold Cat. #s: M6BZ, M6S
P&S Cat #s: 885TR, 3232TR
Technical Support 800-223-4185
www.legrand.us
Technical Support 800-223-4185
www.legrand.us
Page 19
Page 18
ARTICLE 310
SECTION 314.24
Conductors for General Wiring
Outlet and Device Box Depth
■ A box must have sufficient depth for the installation of a large device or
■ Article 310 has been reorganized and renumbered.
utilization equipment.
The reorganization of Article 310 has resulted in the renumbering
of most of the sections and tables and the relocation of some of
the requirements. One notable change is that Table 310.16 for the
allowable ampacities of conductors is now Table 310.15(B)(16) in the
2011 NEC®. The ambient temperature correction factors have been
removed from the allowable ampacity Tables and now appear
relocated to new section 310.15(B)(2) and Tables 310.15(B)(2)(a)
and 310.15(B)(2)(b). There have also been changes to the allowable
ampacities for several different conductor sizes in Table 310.15(B)(16).
Wiremold Cat #s: V2400D, MC-V2400BC
Technical Support 800-223-4185
www.legrand.us
This section of the code requires boxes to have sufficient depth to
prevent damage to the conductors when devices or utilization
equipment are installed as intended in the box. Section 314.24 has
been revised for the 2011 NEC® to include devices. This requirement
previously applied only to utilization equipment. Section 314.24
specifies the depth of the box and the required clearance, taking into
consideration a variety of conductor sizes.
P&S Cat #s: S118R,
S122R,
Technical Support 800-223-4185
P118R,
P122R
www.legrand.us
Page 20
Page 21
SECTION 314.27(A)
SECTION 314.27(C)
Outlet Boxes for Luminaires
Outlet Boxes for Ceiling Fans
■ A box listed for support of a ceiling-suspended fan must be installed
■ Outlet boxes are permitted to support luminaires in walls and ceilings.
Section 314.27(A) has been revised to more clearly state the outlet box
requirements for supporting luminaires at wall and ceiling outlets.
Ceiling outlet boxes intended to support a luminaire must be able to
support at least 50 pounds. A box may be used to support a luminaire
weighing more than 50 pounds if the box is listed and marked for the
maximum luminaire weight to be supported.
when a spare ungrounded conductor is provided.
When a ceiling box is installed in a location where a ceiling-suspended
fan may be installed and when a spare, separately switched,
ungrounded conductor is provided, the box must be listed for support
of a fan. Section 314.27(C) has been revised to recognize that when a
ceiling box is installed under these conditions it is likely that a ceilingsuspended fan will be installed on the box. This requirement applies
only to single and multi-family dwellings.
A wall box intended to support a luminaire must be marked to indicate
the maximum weight of the luminaire to be supported, if other than
50 pounds. An exception allows wall type luminaires weighing
6 pounds or less to be supported by device boxes, plaster rings or
other boxes when the luminaire is secured by at least two No. 6 or
larger screws.
P&S Cat #s: 55501, S120RAC, S120HAC, C118WAC, S118W
P&S Cat #s: 55025,
Technical Support 800-223-4185
Technical Support 800-223-4185
www.passandseymour.com
55501,
22200
www.passandseymour.com
Page 23
Page 22
SECTION 380.1 and SECTION 380.23
SECTION 390.2
Multioutlet Assemblies
Underfloor Raceways
■ Field assembled Multioutlet Assemblies must comply with wire bending
space and pull box requirements.
Article 380 provides the installation requirements for Multioutlet
Assemblies. A new Section, 380.23, specifies the wire bending space and
pull requirements for conductors in field assembled multioutlet assemblies.
Section 380.23 does not apply to listed, factory assembled multioutlet
assemblies.
Section 380.23(A) requires insulated conductors installed in a field
assembled multioutlet assembly to comply with the wire bending space
specifications in Table 312.6(A). Where a multioutlet assembly is used
as a pull box for 4 AWG or larger insulated conductors, Section 380.23(B)
requires compliance with Section 314.28(A)(1) for straight pulls and Section
314.28(A)(2) for angle pulls.
■ A new definition for Underfloor Raceway has been added to the code.
Although the requirements in Article 390 for Underfloor Raceways
remain the same, Section 390.2 now provides a definition. Underfloor
Raceways are installed flush or beneath the floor surface and are
intended for the installation of conductors. The underfloor raceway
may be equipped with junction boxes for access to the conductors as
well as a wide variety of fittings such as floor boxes and pedestals that
allow power, voice and data connectivity.
Section 380.23 applies only to field assembled multioutlet assemblies.
There was concern that conductors could be damaged when installed in
field assembled multioutlet assemblies.
Another change to this Article is that Section 380.1 has been revised to add
an informational note that directs the user to the definition of a Multioutlet
Assembly in Article 100.
Wiremold Cat #s: 20GB306,
Technical Support 800-223-4185
20GB506
www.legrand.us
Wiremold Cat #s: D21210, D41210, 2-0, 4-0
Technical Support 800-223-4185
www.legrand.us
Page 24
Page 25
SECTION 404.2(C)
SECTION 404.9(B) Exceptions Nos. 1, 2, & 3
Switches Controlling Lighting Loads
Grounding of Snap Switches, Dimmers
and Similar Control Switches
■ A snap switch, dimmer or similar control switch shall be connected to the
■ A grounded circuit conductor shall be provided at the switch location.
equipment grounding conductor.
This is a new section that requires the grounded circuit conductor of the lighting
circuit to be provided at the switch location. Many lighting control devices, such as
an occupancy sensor, require low levels of stand-by current for proper operation.
In many installations, the equipment grounding conductor is the only available
conductor that can be used as a circuit conductor for this low level stand-by
current. The intent of this change in the code is to be certain that the lighting
circuit grounded conductor is available for the proper operation of the lighting
control device. This ensures that operation of the control device does not rely on
connection to the equipment grounding conductor. The result is that there will
be no undesirable current on the equipment grounding conductor. The use of
electronic lighting control devices is expected to increase due to increased
emphasis on energy efficient lighting systems.
This section requires snap switches, dimmers and similar control switches to be connected
to the equipment grounding conductor by the means specified in Section 404.9(B)(1) and
(2). This rule ensures that a metal faceplate installed on the switch will be grounded.
There are three exceptions to this requirement:
Exceptions to Section 404.2(C) allow for future installation of the grounded circuit
conductor where there is access to the switch box in cable installations or where
raceway is used to provide the conductors. In either case, the grounded circuit
conductor can be provided after the initial installation.
Exception No. 3 – a snap switch with an integral nonmetallic enclosure as described in
Section 300.15(E) is not required to be connected to the equipment grounding conductor.
This type of switch is commonly known as a self contained device (SCD).
P&S Cat #s: PTWSP250, WDT100, WSP250
Technical Support 800-223-4185
www.passandseymour.com
Exception No. 1 – A replacement switch is not required to be connected to the equipment
grounding conductor where the equipment grounding conductor is not available in the
switch enclosure. Where the replacement switch is installed 8 feet vertically or 5 feet
horizontally from ground or grounded metal objects it must have a nonconducting
faceplate secured by nonmetallic screws or the circuit must be protected by a GFCI.
Exception No. 2 – listed switch assemblies of nonmetallic construction as described in this
new exception are not required to be connected to the equipment grounding conductor.
P&S Cat #s: PS20AC1, PT20AC1, CSB15AC1, TM870, 660
Technical Support 800-223-4185
www.legrand.us
Page 27
Page 26
SECTION 404.14(F)
SECTION 406.2 and 406.14
Snap Switch Rating for Plug and Cord Connected Loads
Tamper-Resistant Receptacles in Child Care Areas
■ Snap switches must be rated not less than the rating of the overcurrent
device protecting the circuit.
■ Tamper-resistant receptacles are required in child care facilities.
This new section establishes the rating of a switch used to control
receptacle outlets. The switch must be rated not less than the rating of
the overcurrent device protecting the circuit. The exception permits the
switch to be rated not less than the receptacle rating where the switch
controls only one receptacle.
P&S Cat #s: PS20AC1, TM870, CSB15AC1, 2621, TM870, 660
Technical Support 800-223-4185
www.legrand.us
Section 406.14 has been added to the code to require that all nonlocking 125 volt, 15 and 20 amp receptacles installed in child care
facilities must be tamper-resistant. Section 406.2 defines a child care
facility as a location where educational, supervision or personal care
services are provided for more than four children under the age of
seven. This change in the code recognizes that even in supervised
facilities, such as child care areas, children have access to electrical
receptacles and the potential for shock and burn incidents exist if a
child inserts a foreign object into a receptacle.
P&S Cat #s: 3232TR, 885TR, TM8HWLTR, 1595TR, TR5262, TR26262
Technical Support 800-223-4185
www.passandseymour.com
Page 29
Page 28
SECTION 406.4(D)(4)
SECTION 406.4(D)(5)
Arc Fault Circuit Interrupter Protection of
Replacement Receptacles
Tamper-Resistant Replacement Receptacles
■ AFCI protection must be provided for replacement receptacles on
branch circuits that require AFCI protection.
■ Replacement receptacles must be tamper resistant where tamper-
resistant receptacles are required by the code.
This new section requires AFCI protection for a replacement receptacle.
When a replacement receptacle is installed on a branch circuit that
requires AFCI protection, the replacement receptacle must be provided
with AFCI protection. Branch circuits that require AFCI protection are
specified in Section 210.12. AFCI protection for the replacement
receptacle may be provided by one of the following methods:
- the replacement receptacle is a listed Outlet Branch Circuit type AFCI
- the replacement receptacle may be protected by a listed Outlet
Branch Circuit type AFCI receptacle located upstream from the
replacement receptacle
- a listed combination type AFCI circuit breaker providing protection of
the branch circuit
Sections 406.12, 406.13, 406.14 and 517.18(C) require the installation
of listed tamper-resistant receptacles in child care facilities, guest
rooms, guest suites, specified areas of dwelling units and pediatric
locations. Section 406.4(D)(5) is a new section that requires a
replacement receptacle to be tamper-resistant when installed in any
of the locations specified in the code that require a tamper-resistant
receptacle.
Section 406.4(D)(4) becomes effective January 1, 2014.
P&S Cat #s: 1595TR, 885TR, TM8HWLTR, 3232TR
Technical Support 800-223-4185
www.legrand.us
Technical Support 800-223-4185
www.legrand.us
Page 31
Page 30
SECTION 406.4(D)(6)
SECTION 406.6
Weather-Resistant Replacement Receptacles
Recessed Receptacle Faceplates
■ Replacement receptacles must be weather resistant where weather-
resistant receptacles are required by the code.
opening.
Section 406.9 requires the installation of listed weather-resistant
receptacles in wet and damp locations. Section 406.4(D)(6) is a new
section that requires a replacement receptacle to be a weatherresistant receptacle when installed in any of the locations specified
in the code that require a weather-resistant receptacle.
P&S Cat. #s: 1595TRWR, 2095TRWR, WIUC10
Technical Support 800-223-4185
■ Faceplates for recessed mounted receptacles must effectively close the
www.legrand.us
This new requirement has been added to section 406.6 to ensure that
faceplates for receptacles installed in a recessed box effectively close
the opening.
Wiremold Cat #s: CRFB4,
Technical Support 800-223-4185
RFB4,
RFB9,
RFB11
www.legrand.us
Page 33
Page 32
SECTION 406.9(B)(1)
SECTION 406.12
Receptacles in Wet Locations
Tamper-Resistant Receptacles for Dwelling Units
■ Extra Duty While-In-Use Covers are required when the outlet box is
Section 406.9(B)(1) requires a weatherproof cover for 15 and 20 amp,
125 and 250 volt receptacles installed in wet locations. These covers,
commonly referred to as While-In-Use covers, provide protection for
the receptacles both when a plug is inserted and when there is no plug
inserted into the receptacle. This section has been revised to require
an “Extra Duty” While-In-Use cover in installations where the box is
supported from grade in other than one and two family dwellings. The
intent of this revision in the code is to ensure that covers mounted on
boxes supported by conduit, stanchions, wood braces or other free
standing rigid supports can withstand the severe service conditions
expected in these installations. The “Extra Duty” covers are evaluated
to more demanding test requirements than general purpose covers.
The covers must be listed and marked “Extra Duty.”
P&S Cat #s: WIUCAST1, WIUC10
Technical Support 800-223-4185
■ 15A and 20A, 125V receptacles in dwellings must be listed
tamper resistant.
supported from grade.
www.legrand.us
This section was previously added to the code in response to the
numerous reported electrical injuries to children resulting from the
insertion of conductive foreign objects into receptacles. Section 406.12
requires that 15 and 20 amp, 125 volt receptacles in all areas of
dwellings specified in Section 210.52 must be tamper-resistant.
Section 406.12 has been revised to allow exceptions to the tamperresistant receptacle requirement. The exceptions include receptacles
located more than 5-1/2 feet above the floor, receptacles in a
dedicated space for appliances that cannot be easily moved and
receptacles that are part of a luminaire or appliance. The exceptions
recognize that there are receptacles that cannot be easily reached by
children and there are receptacles specified in Section 210.52 that are
not considered to meet the receptacle installation requirements in
dwellings. In addition, Section 406.12 has been revised to limit the
tamper-resistant requirement to the nonlocking type of receptacle.
P&S Cat #s: 1595TR, 885TR, TM8HWLTR, 3232TR
Technical Support 800-223-4185
www.legrand.us
Page 35
Page 34
SECTION 406.13
SECTIONS 430.42(C), 430.81(B) and 430.109(F)
Tamper-Resistant Receptacles in Guest Rooms
and Guest Suites
Cord and Plug Connected Motors
■ Motors may be connected to the branch circuit by a plug and receptacle
■ 15A and 20A, 125V receptacles in guest rooms and guest suites must be
listed tamper-resistant.
Section 406.13 is a new Section that requires nonlocking 15 and
20 amp, 125 volt receptacles in guest rooms and guest suites to be
tamper-resistant. Guest rooms and guests suites are defined in
Article 100 of the NEC®. These locations are often occupied by
children and present hazards similar to other locations such as
dwellings that require tamper-resistant receptacles.
or a cord connector. The motor disconnect may be a plug and
receptacle or a flanged surface inlet and a cord connector.
Both of these sections have been revised to recognize that a motor
may be connected to the branch circuit by not only a plug and
receptacle but also by a cord connector. Per Section 210.50(A), a cord
connector may be supplied by a permanently connected cord pendant.
Section 430.109(F) has been revised to include a flanged surface inlet
and cord connector as a motor disconnect means. Previously, this
section recognized only a plug and receptacle as the disconnect
means.
P&S Cat #s: 1595TR, 885TR, TM8HWLTR, 3232TR, TR5262, TR26262
P&S Cat #s: 5262, PS5266XGCM, PS5269XGCM, 5278SS, WPG1
Technical Support 800-223-4185
Technical Support 800-223-4185
www.legrand.us
www.legrand.us
Page 37
Page 36
SECTION 517.13(B)(1)(2)
SECTION 517.16
Grounding of Receptacles in Patient Care Areas of
Health Care Facilities
Isolated Ground Receptacles in Health Care Facilities
■ This section is restructured to provide the requirements for the connection
of the insulated equipment grounding conductor in patient care areas.
The revisions to Section 517.13(B) are intended to more clearly state
the requirements for the connection of the insulated equipment
bonding conductor to receptacles, metal boxes and non-current
carrying conductive surfaces. An exception permits an equipment
bonding jumper to connect the receptacle and box to the equipment
grounding conductor.
P&S Cat #s: TRIG8300, IG8300
Technical Support 800-223-4185
www.legrand.us
■ Isolated ground receptacles are no longer permitted in patient care areas.
Section 517.16 has been revised to prohibit the use of isolated ground
receptacles in patient care areas. There was concern that the
redundant grounding required by Sections 517.13(A) and (B) may not
be adequately achieved when using isolated ground receptacles.
P&S Cat #s: TR62HI, 8300HI
Technical Support 800-223-4185
www.legrand.us
Page 39
Page 38
SECTION 517.18(B) and 517.19(B)(2)
SECTION 517.20(A)
Patient Bed Location Receptacles in Health Care Facilities
Receptacles in Wet Procedure Location Patient Care Areas
■ Patient bed location receptacles may be single, duplex or quadruplex.
The requirements for patient bed receptacles in general care areas
and critical care areas have been revised to include quadruplex
receptacles, in addition to single and duplex receptacles, as the type
of receptacles that may be installed to meet the minimum receptacle
requirements for theses areas.
P&S Cat #s: 420HI, 8201, 8200HI
Technical Support 800-223-4185
www.legrand.us
■ The power distribution system must limit the ground fault current.
Section 517.20(A), titled Receptacles and Fixed equipment, requires
the power distribution system in wet procedure patient care areas to
either limit the ground fault current due to a first fault to a low value
without interrupting the power, or, to interrupt the power supply if the
ground fault current exceeds 6 mA. The revision to this section closely
parallels the wording in NFPA 99, Section 4.3.2.2.8.1.
P&S Cat #s: 8300HI, PTTR8300, 8300W, PT8300
Technical Support 800-223-4185
www.legrand.us
Page 41
Page 40
SECTION 518.3(B)
SECTION 525.23
Temporary Wiring in Exhibition Halls
GFCI Protection for Carnivals, Circuses, Fairs
■ Ground fault circuit interrupter protection required in exhibition halls.
Temporary wiring in exhibition halls may be installed in accordance
with Article 590, with the exception that the ground fault circuit
interrupter (GFCI) requirements of 590.6 do not apply. However,
section 518.3(B) has been revised to state that all other GFCI
requirements in the code apply in this type of installation. An
additional revision to this section requires that portable GFCIs must
meet the requirements for a listed product. This effectively means that
portable GFCIs should be listed products.
P&S Cat #s 1594CMM
Technical Support 800-223-4185
www.legrand.us
■ GFCI protection is required for 15A and 20A, 125V nonlocking receptacles.
Section 525.23(A) has been rewritten to clearly state in enforceable
language the requirement for GFCI protection of 15A and 20A, 125V
receptacles.
Section 525.23(B) previously stated that receptacles are not required
to be GFCI protected if the receptacles are of the locking type and they
are used for the quick connect and disconnect of equipment. A revision
to this section includes the additional condition that the receptacles
that are unprotected by a GFCI must also not be accessible from grade
level.
P&S Cat #s: 1595, 2095
Technical Support 800-223-4185
www.legrand.us
Page 43
Page 42
SECTION 550.13(B)
SECTION 550.13(F)(1)
GFCI Protection of Receptacles in Mobile/Manufactured Homes
Receptacles Near Bathtubs and Shower Stalls in
Mobile/Manufactured Homes
■ Receptacles shall not be installed within or directly over a bathtub or
■ 15A and 20A, 125V receptacles requiring GFCI protection.
shower stall.
Section 550.13(B) specifies the receptacles that must be GFCI
protected in mobile and manufactured homes. This section has been
revised to delete the exception which allowed receptacles not to be
GFCI protected where the receptacles were installed for use with
appliances in a dedicated space. This section now references the
exceptions in Section 210.8(A) as the only permitted exceptions.
P&S Cat #s: 1595, 2095
Technical Support 800-223-4185
www.legrand.us
This section restricted the installation of a receptacle within a bathtub
or shower stall. In addition to the previous wording of the requirement,
the section has been revised to make it clear that a receptacle may not
be installed directly over a bathtub or shower stall.
P&S Cat #s: 1595, 2095
Technical Support 800-223-4185
www.legrand.us
Page 45
Page 44
SECTION 550.25
SECTION 551.47(L) and SECTION 552.48(K)
AFCI Protection of Branch Circuits in
Mobile/Manufactured Homes
Receptacle Faceplates in Recreational Vehicles
and Park Trailers
■ Additional 15 and 20A, 120V branch circuit outlets must be AFCI
■ Faceplates must comply with Section 406.5(A) and (C).
protected.
This section previously required AFCI protection for 120V branch
circuits that supply 15A and 20A receptacles installed in bedrooms.
In addition to the AFCI protection for bedroom branch circuits, Section
550.25 has been revised to require AFCI protection for 120 volt branch
circuits supplying 15A and 20A receptacles in family rooms, dining
rooms, living rooms, parlors, libraries, dens, sunrooms, recreation
rooms, closets, hallways, or similar rooms or areas. The AFCI
protection must comply with Section 210.12(B).
The title of Section 551.47(L) and Section 552.48(K) has been changed
to “Receptacle Faceplates.” Both sections have been revised to refer to
Section 406.5(A) and (C) for the specific requirements for metallic and
nonmetallic faceplates.
P&S Cat #s: 5262, TP8
Technical Support 800-223-4185
www.legrand.us
Technical Support 800-223-4185
www.legrand.us
Page 47
Page 46
SECTION 552.59(A)
SECTION 590.4(D)(2)
Park Trailer Outdoor Receptacles and Switches
Receptacles in Temporary Installations
■ Receptacles in wet locations in temporary installations must meet the
■ Switches and receptacles must meet outdoor installation requirements.
In the 2008 NEC®, outdoor receptacles on park trailers had to be
provided with a gasketed cover for use in wet locations. Section
552.59(A) has been revised to require outdoor receptacles to comply
with Sections 406.8(A) and (B). A requirement for outdoor switches
to comply with Section 404.4 has also been added to this section.
These revisions make certain that the appropriate protection is
provided for switches and receptacles installed outdoors.
Technical Support 800-223-4185
requirements in section 406.9(B)(1).
Section 509.6(D)(2) is a new section that requires receptacles that
are in wet locations in temporary installations to comply with Section
406.9(B)(1). This change in the code recognizes that receptacles in
temporary installations will be exposed to the same wet locations
environment as any other outdoor installation and must be provided
with the necessary protection to ensure continued safe operation of
the receptacle.
P&S Cat #s: WR20TR, WR5362
P&S Cat #s: WR20TR, WR5362
www.legrand.us
Technical Support 800-223-4185
www.legrand.us
Page 49
Page 48
SECTION 604.6(A)(5)
SECTION 625
Manufactured Wiring Systems
Electric Vehicle Charging System
■ Section 604.6 provides the construction requirements for Manufactured
■ Article 625 includes a definition for the Plug-In Hybrid Electric Vehicle
Wiring Systems.
Section 604.6(A)(5) is a new section that specifies listed prewired, modular,
surface raceway as one of the construction components of a manufactured
wiring system. This type of surface raceway construction when used as a
manufactured wiring system has a rating of 600 volts, 20 amps. A listed
surface raceway intended for use as a manufactured wiring system is
evaluated to UL 183, the Standard for Manufactured Wiring Systems.
The code also covers other types of surface raceway products, such as
Multioutlet Assemblies in Article 380 and Surface Metal and Nonmetallic
Raceways in Articles 386 and 388. These products are evaluated to UL5
and UL5A, the standards for metal and nonmetallic surface raceways.
A prewired, modular, surface raceway that is a component of a
Manufactured Wiring System must meet the requirements of Article 604.
Other surface raceway type products must meet the requirements of the
code article that applies, such as, Article 380, Multioutlet Assemblies,
Article 386, Surface Metal Raceways and Article 388,
Surface Nonmetallic Raceways. Article
604 applies only to Manufactured
Wiring Systems.
Wiremold Cat #s: ALA3800 Series,
Technical Support 800-223-4185
ALA4800 Series
www.legrand.us
(PHEV).
A PHEV is a type of electric vehicle powered by both an electric motor
and an internal combustion engine. Both all-electric vehicles and
PHEV’s can be charged using cord connected Electric Vehicle Supply
Equipment. These are electric vehicle chargers that have a plug for
connection to the EV inlet and also have a means for connection to
the premises wiring to provide power. The 120 volt charger is typically
a portable unit that plugs into a standard NEMA 5-15 or 5-20
receptacle. There is also a 240 volt charger that provides a faster
charge time. The NEC requires that all chargers have a number
of integral safety features, including personnel protection against
electric shock.
P&S Cat #s: L1EVSE,
L2EVSE16
Technical Support 800-223-4185
www.legrand.us
Page 51
Page 50
SECTION 680.21(C)
SECTION 680.32
GFCI Protection of Pool Pump Motors
Receptacles Near Storable Pools
20'
■ Outlets supplying pool pump motors must be GFCI protected.
■ Receptacles within 20 feet of a storable pool must be GFCI protected.
The requirement for the GFCI protection of pool pump motor outlets
has been moved from Section 680.22(B) to Section 680.21(C). The
requirement remains the same except that the voltage ratings have
been changed from 120 or 240 volt to 120 through 240 volt. GFCI
protection is required for both plug connected and direct connected
pool pump motors.
P&S Cat #s: 1595TRWR, 2095TRWR, WIUC10, 1595DS, 2095DS
Technical Support 800-223-4185
www.legrand.us
125 volt, 15 and 20 amp receptacles within 20 feet of the inside walls
of a storable pool must be GFCI protected. The change to this section
adds the 15 and 20 amp ratings of the receptacle which were not
previously specified.
P&S Cat #s: 1595TRWR, 2095TRWR, WIUC10, 1595DS, 2095DS
Technical Support 800-223-4185
www.legrand.us
Page 53
Page 52
NOTES
Technical Support 800-223-4185
NOTES
www.legrand.us
Technical Support 800-223-4185
www.legrand.us
Page 54
NOTES
Technical Support 800-223-4185
www.legrand.us
For product and application information,
please call the
Legrand/Pass & Seymour
Technical Assistance Group at
1-800-223-4185
www.legrand.us/passandseymour
©2011, Legrand/Pass & Seymour CTM1095 7/11
2/11 AGI/CGXTP
AGI/DG
designed to be better.™
For additional technical or application-specific
information, call 800-223-4185 or visit our website
at www.legrand.us/PassandSeymour. We’re eager
to put our expertise to work for you.
Distributed by:
104 P Street
Belle Chasse, LA 70037
504-394-4132
www.pembaserv.com
P.O. Box 4822
Syracuse, NY 13221-4822
800-776-4035
www.legrand.us/PassandSeymour
Legrand Canada
570 Applewood Crescent
Vaughan, ON, L4K 4B4
Phone: 905.738.9195, Fax: 905.738.9721
www.legrand.ca
Download