14 Journal of International Council on Electrical Engineering Vol. 2, No. 1, pp. 14~19, 2012 A Self-healing Scheme of Single-phase-to-ground Fault in Smart Power Distribution System Shen-Xing Shi† and Xin-Zhou Dong* Abstract – The paper presents a self-healing scheme of single-phase-to-ground fault in smart power distribution system. The scheme consists of three parts: single-phase-to-ground fault detection, faulted feeder selection and faulted feeder isolation. Fault detection is based on power-frequency voltage measured by a voltage transducer. A single-phase-to-ground fault is detected when measured voltage is greater than threshold. A fault generated current traveling waves are used to identify faulted feeder. The feeder with different initial traveling wave’s polarity to other feeders is selected as faulted feeder. When faulted feeder is identified, the interconnection switch between different bus-bar is switched on firstly, then the switch at the load side of faulted feeder is switched off to isolate the load from the fault, the switch at the power source side of faulted feeder is switched off to isolate the source from the fault lastly. Simulation studies show that the scheme can meet the requirements of isolating single-phase-to-ground fault without affecting power supply to the load. Keywords: Smart power distribution system, Single-phase-to-ground, Transient traveling waves, Fault isolation 1. Introduction Fault self-healing is the key to smart power system[1-3]. As far as power distribution system is concerned, fault selfhealing means to isolate the faulted equipment without affecting power supply to the load. Unfortunately, until now, there has been no fault self-healing technology. Any fault in power system should be detected and processed by protective relaying, which will trip the fault as soon as possible when the fault is confirmed. And when the fault in power distribution system is isolated, power supply to the load has to be interrupted [4-6]. In power distribution system, the power grid is radial and feeders are connected with load directly to supply power. The reliability of power supply to the load depends on safe and reliable operation of feeders. However, the fault in the feeders is inevitable. When a fault occurs, the faulted feeder will be isolated and power supply to the load will be interrupted. And most of the fault in power distribution system is single-phase-to-ground. According to the statistics from power utilities in china, more than 70% fault in power distribution system is single-phase-to-ground. In order to improve the reliability of power supply to the load, the † Corresponding Author: Dept. of Electrical Engineering, Tsinghua University, China (shishenxing@tsinghua.edu.cn) * Dept. of Electrical Engineering, Tsinghua University, China (xzdong @tsinghua.edu.cn) Received: December 6, 2011; Accepted: December 28, 2011 neutral in power distribution system is always ungrounded or grounded through Peterson Coil in china. In such power distribution system, single-phase-to-ground fault can’t affect power supply to the load instantly for phase-to-phase voltage is still symmetrical and there is no short circuit current flowing in the system. At the same time, singlephase-to-ground fault generated current is so small that over-current protection relays used in power distribution system can’t detect the fault, which will lead to phase-tophase fault. When a phase-to-phase fault occurs, overcurrent protection will trip the circuit breaker as soon as possible to isolate the fault. To reduce the time of power supply recovery, two or more feeders to one load are built in typical urban power distribution system in china. Focusing on the fault in urban power distribution system with neutral none-effectively grounded, much technology has been proposed and used in the field. Feeder automation technology has been presented to respond to short-circuit fault like phase-to-phase fault; while faulted feeder selection technology has been proposed to process single-phaseto-ground fault. Feeder automation technology detects short-circuit fault based on over-current and trips the corresponding circuit breaker to isolate the faulted feeder. Single-phase-to-ground fault feeder selection technology selects the faulted feeder when the fault occurs. And the faulted feeder is isolated by operating staffs. Whatever the fault is, has power supply to the load to be interrupted before the backup power supply is switched on. Therefore, Shen-Xing Shi and Xin-Zhou Dong the existed technology corresponding to the fault in power distribution system can’t meet the requirements of fault self-healing, the key to smart grid. The paper discusses a novel single-phase-to-ground fault processing scheme and presents a fault self-healing scheme in smart power distribution system. The scheme comprises single-phase-to-ground fault detection, faulted feeder selection and single-phase-to-ground fault isolation. The paper proposes basic principle at first, then presents scheme implementation, verifies the scheme by simulation studies, and draws a simple conclusion at last. 2. Basic Principle The neutral in power distribution system is always noneffectively grounded, including neutral ungrounded, neutral grounded through Peterson coil or neutral grounded through high resistances. In such a power distribution system, when a single-phase-to-ground fault occurs, it is not necessary to trip the faulted feeder instantly for limited fault current. And it provides the possibility to achieve fault self-healing. In order to achieve fault self-healing function, fault detection and fault isolation are indispensable. Therefore, the scheme presented will detect the fault, then determines the faulted feeder and isolates the faulted feeder without affecting power supply to the load. The basic principle of fault detection, faulted feeder selection and faulted feeder isolation will be analyzed in details. 2.1 Single-phase-to-ground fault detection In power distribution system with neutral non-effectively grounded, three phase voltages are symmetrical, and zerosequence voltage is close to zero when the system is in normal operation. However, when a single-phase-to-ground fault occurs, the voltage in the faulted phase decreases while the other two phases voltages increase. For a solid fault, the faulted phase voltage decreases to zero and the other two phases voltages increase to phase-to-phase voltage, 3 times phase-to-ground voltage. Therefore, the single-phase-to-ground fault can be detected by using voltages. In the paper, the voltage at the open delta side of voltage transducer in the bus-bas is used to detect the fault. The voltage setting is set to avoid the maxim asymmetrical voltage when the system is in normal operation. When the measured voltage is higher than the setting, the fault is detected. 2.2 Single-phase-to-ground fault feeder selection 15 When a single-phase-to-ground fault occurs in one feeder, fault generated traveling waves will propagate from fault point along the feeder to the system. Arriving at the point where wave impedance changes, for example, bus-bar in the substation, the traveling wave will be reflected and refracted. At the instant current traveling waves arrived at the point, the current traveling waves inflow to the point are equal to the current traveling waves outflow, because they satisfy Kirchhoff's current law. As far as the bus bar is concerned, the current traveling wave in the faulted feeder is inflow current, while the current traveling wave in the healthy feeder is outflow current. For the number of faulted feeder is only one, and the number of healthy feeder is at least two, the current traveling wave in the faulted feeder is equal to the sum of current traveling waves in healthy feeders connected to the bus bar. If the current reference direction in all feeders is defined as the same, like from the bus bar to the feeder, the polarity of the current traveling wave in the faulted feeder is reverse to the wave in the healthy feeder. Thus, when a single-phase-to-ground fault occurs, it is the faulted feeder with the highest current traveling wave and different polarity to the others, which is the basic principle to identify single-phase-to-ground fault feeder in power distribution system with the neutral noneffectively grounded [7-10]. 2.3 Single-phase-to-ground fault isolation Fault isolation is the core to fault self-healing scheme. In a radial power grid, to isolate the fault can be done by tripping the circuit breaker at the power source side of the faulted feeder, which will interrupt the power supply to all load in the downstream of the faulted feeder. In order to reduce the blackout area the switchgear at the load side of the faulted feeder can be tripped. To recover the power supply, the backup power source can be put into operation by closing the switchgear at the open-ring point. At present, it is to trip the circuit breaker at the power source side firstly and then to open the switchgear at the load side to isolate the fault, which will inevitably interrupt the power supply to the load. As a single-phase-to-ground fault will not lead to high fault current and phase-to-phase voltage change, it is possible to close the switchgear at the openring point when a fault occurs. Therefore, in the new scheme, single-phase-to-ground fault isolation is achieved by closing the switchgear at the open-ring point at first, then opening the switchgear at the load side of the faulted feeder, opening the switchgear at the power source side of the faulted feeder at last, which will guarantee the power supply to the load. 16 A Self-healing Scheme of Single-phase-to-ground Fault in Smart Power Distribution System 3. Scheme Implementation The scheme will be implemented by self-healing system, which is made up of self-healing devices. Self-healing devices are installed in a power substation and power switch stations. Self-healing devices in the power substation and power switch stations are called master and slave machines respectively. And the master machine and slave machines will exchange the decision result by communication. The self-healing device collects bus-bar voltages, zero-sequence currents in all feeders and switches’ or circuit breakers’ status information in real time. Based on the voltage information, the self-healing device determines whether a single-phase-to-ground fault occurs in the system. At the same time, the device identifies which feeder the disturbance is from. When a single-phase-to-ground fault is determined and the faulted feeder is identified by the device, the self-healing device will send a signal to the other selfhealing device in the faulted feeder and waits for the signal from other self-healing device. If the received signal shows the same faulted feeder as the master self-healing device determines, the faulted feeder is confirmed. And based on the switches or circuit breakers status, the self-healing device installed at the load side of the faulted feeder at first output the signal to close bus tie circuit breaker, and then trips the circuit breaker at the load side of the faulted feeder, which will isolate the fault from the load. After a fixed delay, the self-healing device in the power substation will trip the circuit breaker to isolate the fault from the power source. The whole flowchart is as shown in Fig. 1. As far as hardware is concerned, the self-healing device is made up of communication unit, input unit, central processing unit and output unit. The communication unit sends the result of faulted feeder determined to the other device installed at the other terminal of the faulted feeder, and receives the result of the faulted feeder from the other devices to confirm whether the protected feeder is faulted. The input unit inputs the signals from current transducers of the protected feeders and voltage transducers of the bus-bar, and the status signals from circuit breakers or switches. The central processing unit analyzes the signals from the input unit and determines whether a single-phase-to-ground fault occurs and which feeder is faulted. The output unit outputs the signals to trip or close the corresponding circuit breakers or switches. The hardware of self-healing device is as shown in Fig. 2. Fig. 2. The hardware of self-healing device. 4. Simulation Demo Fig. 1. The scheme flowchart. A radial power distribution network is described in Fig. 3. Two transformers SZ9-10000/35 are installed in power substation with the ratio of 35/10.5kV. And two groups of capacitances with the capacity 2000kVA are installed. Feeders are the mix of cable and overhead lines, with the cable in the power substation and overhead line outside of the substation. For the length of the cable is so short, it is omitted in the simulation. When the system is under normal operation, the bus tie switches both in power substation and switch station are open. In the system, the overhead lines are LGJ-70, LGJ-90 and LGJ-120 respectively, with the length from 1km to 5km. The load current is from 50A to Shen-Xing Shi and Xin-Zhou Dong 100A. The simulation is based on EMTP. Suppose a singlephase-to-ground fault occurs in Feeder L123, the simulation results are as shown in Fig. 4-Fig. 7. 17 tripped the switch B921, and the fault was isolated from the switch station and the load supplied by Feeder L123 was transferred. At T3, when the switch B921 was tripped, the self-healing device in the switch station sent a signal to the device in the power substation to trip the switch B123 to isolate the fault. Thus, the system went back to normal operation. 3i0 / A L111 L112 L113 Fig. 3. A simulation power distribution system. L114 t/ s a) Busbar I Fig. 4. Voltages at open delta side measured by voltage transducers in the substation. When a phase A-to-ground fault occurs at F1 in Feeder L123 at T0, the voltage at open delta side of voltage transducer connecting to bus bar II increases significantly in power substation, as shown in Fig. 4, and fault generated traveling waves can be measured by zero-sequence current transducers installed in Feeder L121—L124, as shown in Fig. 5. At the same time, the voltage and the current traveling waves in the switch station have the same changes, as shown in Fig. 6 and Fig. 7 respectively. Wherever it is in the power substation or in the switch station, the current traveling wave in Feeder L123 is reverse to the traveling waves in other feeders. Therefore, the fault can be detected by the zero-sequence voltage, and the faulted feeder can be selected by current traveling waves measured by zerosequence current transducers. The self-healing device in the power substation selected the faulted Feeder L123, and the device in the power switch selected the same feeder as the faulted feeder. The self-healing devices exchanged the fault result, and confirmed the fault feeder. At T1, the selfhealing device in the switch station closed the bus tie circuit breaker. At T2, the self-healing device in the switch station 3i0 / A L121 L122 L123 L124 b) Busbar II Fig. 5. Current traveling waves measured by zero-sequence current transducers of feeders in the substation. Fig. 6. Voltages at open delta side measured by voltage transducers in the switch substation. 18 A Self-healing Scheme of Single-phase-to-ground Fault in Smart Power Distribution System source terminal will be tripped, which is different to the traditional feeder automation scheme. Acknowledgements The authors would like to thank National Natural Science Foundation of China under Grant 50937003, Ministry of Education of China under Grant 20090002120028 and The Chinese Society for Electrical Engineering under Youth Foundation 2009 for their supports to finish the work. a) Busbar I b) Busbar II Fig. 7. Current traveling waves measured by zero-sequence current transducers of feeders in the switch substation. 5. Conclusion The paper presents a self-healing scheme of singlephase-to-ground fault in smart power distribution system. The scheme includes fault detection and fault processing. Some conclusions can be drawn from the study: 1. Single-phase-to-ground fault self-healing is available in smart power distribution system; 2. Single-phase-to-ground fault self-healing should be supported by primary equipments in power distribution system. In the scheme, one load can be supplied power by two or more feeders; 3. Single-phase-to-ground fault self-healing should be supported by smart protection and control scheme in power distribution system. In the scheme, the switchgear at the load terminal of the faulted feeder should be tripped at first, then the switchgear at the power References [1] Yu Yixin. “Intelli-D-Grid for the 21st Century”, Southern Power System Technology Research, vol.2, no.6, pp.14-16,2006. [2] Guo zhizhong. “Scheme of Self-healing Control Frame of Power Grid”, Automation of Electric Power Systems, vol.29, no.10, pp.85-91, 2005. [3] Xu Bingyin. “Feeder Automation”, Power System Technology, vol.22, no.3, pp. 54-60, 1998 [4] Chen Yong, Hai Tao. “Voltage Type Feeder Automation System”, Power System Technology, vol.23, no.7, pp: 31-33, 1999. [5] Sun Fujie, He Junjia, Zhou Jiyan. “Study and Application of Power Supply Techniques for 10kV Loop Networks based on Recloser and Section Switch”. Power System Technology, vol.24, no.7, pp. 33-36, 2000. [6] Liu Jian, Zhang Wei, Cheng Hongli. “The Parameter of Feeder Automation System based on Mutual Coordination of Recloser with Voltage-Time Type of Sectionalizers”, Power System Technology, vol.30, no. 16, pp. 45-49, 2006. [7] Su Qian-li, Dong Xin-zhou, Shi Shen-xing. “A new principle of fault line selection for distribution”, in proceedings of International Conference on 7Th Developments in Power System and Protection, Netherlands, 2001 [8] Dong Xin-zhou, Bi Jian-guang. “Analysis on transient travelling wave and study on fault lines selection for distribution lines”. Proceeding of the CSEE, vol.25, no.4, pp. 1-6, 2005. [9] Wang kan, Shi shenxing, Yang jianming, Dong xinzhou. “Transient-traveling-wave-based grounding line selec-tor and its field tests”. Electric Power Automation, vol.28, no.6, pp. 118-121, 2008. [10] Dong Xinzhou, Shi Shenxing. “Identifying Single- Shen-Xing Shi and Xin-Zhou Dong phase-to-ground fault feeder in neutral non-effectively grounded distribution system using wavelet transform”, IEEE transaction on Power Delivery, vol.23, no.4, pp. 1829-1837, 2008 Shen-Xing Shi received the B.S. and Ph.D. degree in electrical engineering from Northeast Institute of Electrical Power, Jilin, and Tsinghua University, Beijing, China, in 1999 and 2006, respectively. His research interests are power system analysis and power system protection. Xin-Zhou Dong was born in Shanxi Province, China, in 1963. He received his bachelor’s degree in 1983, his master’s degree in 1991 and a Ph.D. degree in 1996 from the Department of Electrical Engineering, Xi’an Jiaotong University, China. He furthered his post-doctoral research at the Electrical Engineering Station of Tianjin University from 1997 to 1998. At present, he serves as a professor of Tsinghua University. His research interests include protective relaying, fault location and application of wavelet transforms in power systems. He is author or co-author of more than 100 journal papers. 19