Copyright © 2010 PowerShield Ltd. Sentinel Battery Monitor settings for 90NET UPS in PFC Mode Introduction The Sentinel battery monitoring system was designed to monitor stationary batteries in float applications like UPS systems. The PFC mode uses an intermittent charging regime instead of float charging and the Sentinel was not suited to handle the charger off state and the large monoblock voltage fluctuations that can occur when the string goes on charge. The Sentinel system has been enhanced to handle intermittent battery charging regime to ensure the appropriate limits are applied with respect to battery state. Please perform the following procedure to change a Sentinel system from float charging to intermittent charging. Procedure Step 1 - Upgrade Sentinel Firmware Via Hyper terminal or the PowerShield upgrader update the firmware on the Sentinels to version 5.4.40. Step 2 – Obtain a new version of Config Upgrade your computer with a new version of Config version 2.0.0.x or version 2.1.0.x. Step 3 – Format Sentinel memory Connect with Config to the Sentinel and format the memory. Page 1 of 6 6300-074A 15 July 2010 - DRAFT Copyright © 2010 PowerShield Ltd. Step 4 – Set charging regime Set the charging regime to ‘Intermittent charge’ on the Monitor system tab as show below. Page 2 of 6 6300-074A 15 July 2010 - DRAFT Copyright © 2010 PowerShield Ltd. Step 5 – Update String Configuration Set Ohmic measurement string state option and monoblock type. The settings are highlighted below by the red eclipses. Repeat the above for all the strings on the system. Page 3 of 6 6300-074A 15 July 2010 - DRAFT Copyright © 2010 PowerShield Ltd. Step 6 – Update String limits Update the ‘Minimum String Voltage – Float Mode’ limit to a value using the following formulae: Minimum String Voltage – Float Mode = N° of monoblocks in string x 13.45V Update the ‘Minimum Voltage – Idle mode’ limit to 6 x 2.05V/Cell = 12.30V Below is an example of a configuration with 40 12V monoblocks per string. Repeat this step for each configured string. Page 4 of 6 6300-074A 15 July 2010 - DRAFT Copyright © 2010 PowerShield Ltd. Step 7 – Update Monoblock limits Update the existing monoblock voltage limits using the Monoblock Limits dialog. The Create Limits panel provides some suggested values. Adjust the maximum ‘Float’ limit to be the same value is the maximum ‘Discharge’ limit. Below an example of suggested monoblock limits for 12V VRLA battery. Page 5 of 6 6300-074A 15 July 2010 - DRAFT Copyright © 2010 PowerShield Ltd. Step 8 – Current transducer settings 1. Select the current transducer that is installed, the new version of Sentinel firmware now retains the current transducer selection. 2. Recalibrate the current if required by clicking the ‘Calibrate’ button. 3. Check the ‘Discharge Threshold’ and ‘Float Threshold and Limit’ values and adjust them to the values shown below. Repeat the above steps for all the used current inputs on the Sentinel system (Master and slaves). Step 9 – Save Sentinel configuration Go to the monitor system page and click “Save Configuration”. Page 6 of 6 6300-074A 15 July 2010 - DRAFT