SECTION V: TECHNICAL SPECIFICATIONS TECHNICAL SPECIFICATION FOR RECLAMATION OF OUTDOOR TYPE DISTRIBUTION TRANSFORMERS 11 KV / 6.6KV/433 – 250 V. SCOPE: 1. This specification covers reclamation as per design, engineering, assembly, stage testing, inspection and testing before dispatch of oil Immersed naturally cooled 3 phase 11 kV/6.6KV/433 - 250 V distribution transformers for outdoor use. a) It is not the intent to specify completely herein all the details of the design and reconstruction of Equipment. However the equipment shall conform in all respects to high standards of engineering and workmanship and shall be capable of performing in continuous commercial operation, in a manner acceptable to the authority for placing orders (Department/Division) for repairs who will interpret the meanings of specifications and shall have the power to reject any work or material which, in his judgment is not in accordance therewith. The reclaimed transformer shall be complete with all components necessary for their effective and trouble free operation. such components shall be deemed to be within the scope of bidder's supply irrespective of whether those are specifically brought out in this specification and' or the commercial order or not. b) The transformer and accessories shall be reclaimed to facilitate the operation, inspection, maintenance and repairs. The repair shall incorporate every precaution and provision for the safety of equipment as well as staff engaged in operation and maintenance of equipment. c) All outdoor apparatus, including bushing insulators with their mountings, shall be repaired so as to avoid any accumulation of water. 2. STANDARD RATINGS: a) The standard ratings shall be 25, 63, 100, 250, 400, 500 & 630 KVA for 11 KV/6.6KV /440 volt distribution transformers. However any other Ratings not included in standard Ratings required to be repaired is deemed to be included. 3. STANDARDS: a) Unless otherwise modified in the specification, the Reclaimed transformers shall comply with the requirement of ISS: 2026 (latest issue) or any equivalent International Standards and REC specification 2/1973 and ISS: 2099 (latest issue) or any equivalent International Standards. The bushings used shall conform to ISS: 2099 (latest issue) or any equivalent International Standards except as modified herein. b) The materials to be used for reclamation shall conform in all respects to the relevant Indian /International Standards, with latest amendments thereof unless otherwise specified herein. Some of them are listed below: 1 Indian Standard Title 1S -2026 (Part I- IV) Specification for Power Transformers Outdoor distribution Transformer up to IS – 1 180 ( Part I & II) and including 100KVA IS- 12444 Specification for Copper wire rod IS-335 Specification for Transformer Oil IS-5 Specification for colors for ready mixed paints Ready mixed paint. brushing zinc chromate, priming Classification of insulating materials for Electrical machinery and apparatus in relation to their thermal stability in service. Specification for high voltage porcelain bushing Testing for steel sheets and strips and magnetic circuits Dimensions for clamping arrangements for bushings Specification for Low Voltage bushings Specification for Outdoor Bushings Specification for Al Wire rods Specification for Insulating Kraft Paper Specification for Insulating Press Board Guide for loading of oil Immersed Transformers Determination of water content in 011 for porcelain bushing of transformer Paper covered aluminum conductor Rectangular Electrical conductor for electrical machines Electrical power connector Testing of specific resistance of electrical insulating Method of test for power factor and dielectric constant of electrical insulating liquids Determination of electrical strength of insulating oil Installation and maintenance of transformers. Revised Guidelines of Bureau of Energy Efficiency IS-104 IS 1271 IS-2099 IS-649 IS-457 IS-7421 IS-.347 IS-5484 IS-9335 IS- 576 IS-6600 I S-2362 IS-6162 IS-6160 IS-5561 IS-6103 IS-6262 IS-6792 IS-10028 International and Internationally recognized standards IEC 76 ASTM 8-49 BS 148, 0-1473, D-15331934, IEC Pub296 DIN 42531 to 33 ASTM B – 233 IEC554 IEC 641 IEC76 Material conforming to other internationally accepted standards which ensure equal or better quality than the standards mentioned above would also be acceptable. In case the bidders who wish to utilize material conforming to other standard, the bidder shall clearly bring out the salient points of difference between the standards adopted and the specific standards in relevant schedule. Four copies of such standards with authentic English translation shall be furnished along with the offer. 2 4. DESIGN AND STANDARDIZATION: a. b. c. d. e. f. g. h. The reclaimed transformers and accessories shall be reclaimed to facilitate operation, inspection, maintenance and repairs. All apparatus shall also be reclaimed to ensure satisfactory operation under such sudden variations of load and voltage as may be met with under working conditions on the system, including those due to short circuits. The reclamation shall incorporate every reasonable precaution and provision for the safety of all those concerned in the operation and maintenance of the equipment keeping in view the requirement of Indian Electricity Rules and Acts. All material including bought out items like bushings, oil, conductor and insulating materials used shall be of the best quality and of the class most suitable for working under the conditions specified and shall withstand the variation of temperature and atmospheric conditions arising under working conditions without undue distortion or deterioration or setting up of undue stresses in any part and also without affecting the strength and suitability of the various parts for the work which they have to perform. Corresponding parts liable to replacement shall be interchangeable. All outdoor apparatus, including bushing insulators with their mounting shall be replaced so as to avoid external pockets in which water can collect and internally air could trap. All taper pins used in any mechanism shall be of the split type complying with IS: 2593 or any equivalent International Standards for these items. All connections and contacts shall be of ample section and surface for carrying continuously them specified currents without heating and fixed connection shall be secured by bolts or set screw of common size adequately locked against vibration. Lock nuts shall be used on stud connections carrying current. All apparatus shall be replaced to minimize the risk of accidental short circuit caused by animals, birds or vermin. 5. SERVICE CONDITIONS a) The distribution transformers to be reclaimed against this Specification shall be suitable for satisfactory continuous operation under the following climatic conditions as per IS- 2026 (Part-I) i) Location ii) Maximum ambient air temperature Minimum average daily ambient air temperature (°C) Maximum average daily ambient air Temperature (°C) Maximum yearly weighted average Ambient temperature (°C) iii) iv) v) vi) At various locations in Jammu Division. 45 10 40 32 95% (Sometimes approaches saturation point). Maximum relative humidity 6. PRINCIPAL PERAMETERS a) The reclaimed transformers shall be suitable for outdoor installation with three phase 50 Hz 11 KV or 6.6 KV system in which the neutral is effectively earthed and they should be for service with fluctuations in supply voltage upto plus 12.5% to minus 12.5%. b) The reclaimed transformers shall conform to the following specific parameters: 3 S.No Item 01. 02. 03. 04. 05. 06. 07. 08. 09. System voltage (max.) Rated Voltage HV Rated Voltage LV Frequency No. of Phase Connection HV Connection LV Vector group Type of Cooling 11 KV Distribution Transformers 12 KV 11 KV 433-250 V* 50 Hz +/-5% Three Delta Star(neutral brought out) Dyn-11 ONAN 6.6 KV Distribution Transformers 7 KV 6.6 KV 433-250 V* 50 Hz +/-5% Three Delta Star(neutral brought out) Dyn-11 ONAN *The voltage level can be specified as 415-240 V/400-230 V volts as per the requirements of the Department / Division. Audible sound level (decibels) at rated voltage and frequency for liquid immersed distribution transformers shall be below (NEMA Standards): KVA Rating Audible sound Levels(Decibels) 0-50 51-100 101-300 301-500 45 50 55 60 7. CONTINUOUS MAXIMUM RATING: The reclaimed transformers shall have a continuous maximum rating at the specified normal ratio, frequency and temperature rise. a.) Reclaimed transformers shall be capable of operation continuously in accordance with IS loading guide at their continuous maximum rating and at any ratio without exceeding temperature rise. b.) Reclaimed Transformers with tapping ranges extending more than 9% below normal voltage shall meet the temperature rise limits specified in IS: 2026 or any International Standard. On other tapings, they shall operate continuously without injurious heating. The loading of the transformers is to be in accordance with IS: 6600 - guide for loading of oil immersed transformers natural cooled units or any international standards. c.) The reclaimed transformers shall be capable of operation without danger at other than rated voltage and frequency in accordance with clause 4.3 and 4.4 of IS: 2026 (Part I) 1977 or any international standards. 8. MAXIMUM TEMPERATURE RISE: The maximum temperature rise in reclaimed transformer tested at its continuous maximum rating shall not exceed the following limit with reference to ambient air temperature. a.) Temperature of oil by thermometer: 45 degree C +50 degree C ambient. b.) Temperature of winding by test resistance: 50 degree C +50 degree C ambient. 9. NO LOAD VOLTAGE RATIO: The No load voltage ratio corresponding to the principal tapping shall be 11,000/440Volts,6,600/440volts as the case may be (in case of Distribution Transformers). 4 10. MAXIMUMCURRENT DENSITY: The current density for HV and LV winding should not exceed 2.5 Amps/mm2. KVA Rating Audible sound Levels (Decibels) 0-50 45 51-100 50 101-300 55 3301-500 60 11. MAXIMUM GUARANTEED NO LOAD AND LOAD LOSSES: a.) Not withstanding anything, the department / division reserves the right to reject the transformers for the losses exceeding guaranteed losses beyond tolerance limit losses as well as in case of temperature rise of oil and winding exceed nameplate value and or impedance value differ from nameplate value including tolerance, the manufacturer / repair agency shall have to reclaim the transformer afresh within a reasonable period, as decided by the department / division at no extra cost. b.) While the Tenderers may offer their own design for reclamation it may be noted that the transformer losses at 75ºC should not exceed the prescribed limit as already specified in foregoing para. 12. WINDING CONNECTION VECTORS: a.) The primary winding shall be connected delta and secondary winding star as per vector symbol Dy.11 (IS: 2026) so as to produce positive displacement of 30o from the primary to the secondary vector of the same phase (vector rotation assumed counter-clock wise). b.) The neutral point of the secondary (LV winding) is intended for solidly earthed system and should be brought out to a separate insulated terminal. c.) All windings of reclaimed transformers shall have uniform insulation when tested in accordance with ISS: 2026/1977 or any equivalent international standards. The minimum basic impulse withstands level of windings for 1.2/50 micro sec. Full wave shall be as given below: i) 11 KV - 75 KV Peak 13. TECHNICAL REQUIRMENTS: a) CORE MATERIAL – CRGO / AMORPHOUS METAL (Wherever to be utilized to replace the damaged/Burnt core) The shortfall of core shall be constructed from high grade, non-ageing, low loss cold rolled super grain oriented silicon steel lamination of HI-B grade steel or better. All stipulations under clause-8 be considered while selecting material of core. b) CRGO Material c) The core shall be stack / wound type of high grade cold rolled grain oriented annealed steel lamination, as per applicable Indian/ International standards, having low loss and good grain properties, coated with hot oil proof insulation, bolted together and to the frames firmly to prevent vibration or noise. d) No-load current shall not exceed 3% of full load current and will be measured by energizing the transformer at 433 volts, 50 Hz on the secondary. Increase of voltage of 433 volts by 12.5% shall not increase the no-load current by 6% (maximum) of full load current. 5 14. WINDINGS: a.) Material: b.) HV and LV windings shall be wound from Super Enamel covered / Double Paper covered. Aluminum conductor for 250 KVA and below. c.) HV and LV windings shall be wound from Super Enamel covered / Double Paper covered copper conductor for winding for ratings above 250 KVA. d.) Inter layer insulation shall be Nomex / Epoxy dotted Kraft Paper e.) Proper bonding of Inter layer insulation with the conductor shall be ensured. Test or bonding strength shall be conducted. f.) Dimensions of winding coils are very critical. Dimensional tolerances for winding coils shall be within limits. g.) Current density for HV and LV winding should not be more than 2.8 Ampere per sq mm for copper and 1.6 Ampere per sq mm for Aluminium Conductor. h.) Joints in the winding shall be avoided. However, if jointing is necessary the Joints shall be properly brazed and the resistance of the joints shall be less than that of parent conductor. In case of foil windings, welding of leads to foil can be done within the winding. 15. TAPS: a.) No tapping shall be provided for transformers up to 100 KVA rating b.) For ratings above 100 KVA and up to 200 KVA, tapping shall be provided. if required by the Department / Division, on the higher voltage winding for variation of HV voltage. c.) For ratings higher than 200 KVA, tapping shall be provided on the higher voltage winding for variation of HV voltage if required by the division. 16. TERMINAL ARRANGEMENT: a.) The reclaimed transformers shall be fitted with shaded porcelain bushings of outdoor type suitable for solder less connectors on HV as well as LV side if need be. The HV/LV bushing shall not be provided with arcing horns. Aluminum bushing stems and aluminum metal parts will not be accepted. The HV/LV bushings shall have the characteristics as per IS: 2099 (latest issue). LV neutral bushing requirement is identical to LV line bushing in all respect. The electrical characteristics of bushing insulators shall be in accordance with IS: 2099 as amended from time to time. All routine tests shall be carried out in accordance with IS: 20991986. b.) Bushing studs of 11KV should be of copper and conforming to IS: 3347 with latest amendment. 17. VIBRATIONS AND NOISE: Every care shall be taken to ensure that the refitting and manufacture of all transformers and accessories shall be such as to reduce noise and vibration to the level obtained in good modern practice. 18. INTERNAL EARTHING ARRANGEMENT: a.) General: - All metal parts of the transformer to be reclaimed with the exception of the individual core laminations, core bolts and associated individual clamping plates shall be maintained at some fixed potential. b.) Earthing of core clamping structure: - The top main core clamping structure shall be connected to the tank body by a copper strip. The bottom clamping structure shall be earthed y one or more of the following methods. 1. By connection through vertical tie rods to the top structures. 2. By direct metal-to-metal contact with the tank base maintained by the weight of the core and the windings. 3. By a connection to the top structures on the same side of the core as the main earth connection to the tank. 6 c.) Earthing of magnetic circuit: The magnetic circuit shall be earthed to the clamping structure at one point only through a disconnectable link placed in an accessible position beneath an inspection opening in the tank cover plate. The connection to the link shall be on the same side of that core and the main earth connection. d.) Size of earthing connections: All earthing connections with the exception of those from the individual cell clamping rings shall have a cross sectional area of not less than 0.8 sq.mm. e.) Leads from winding to bushing and intercake connection: The leads from winding to bushing and intercake connection should be rigid enough to withstand normal vibration and transportation shocks and short circuit stresses. They should be spaced in such a way that necessary clearances are maintained not only in air but also with oil medium at the lowest permissive electrical strength as per relevant ISS over the period of normal service. 19. OVER LOAD CAPACITY: a.) Reclaimed transformer shall be capable of carrying sustained over loads as stated in ISS:6600. b.) Type of load: - The Re c l a ime d transformer will supply a mixed power and lighting load within varying power factor from 0.6 lag to 0.8 lead due to capacitors. 20. INSULATION LEVELS: S.No. Voltage (KV) Impluse Voltage (KV Peak) Power frequency Voltage (KV) 01. 0.433 -- 3 02. 11/6.6 95 28 21. OIL: a.) The Insulating oil shall comply with the requirements of IS 335 or BS 148 Use of recycled oil is not acceptable. The specific resistance of the oil shall not be less than 2.5 X 1012 ohmcm at 27°C when tested as per IS 6103. b.) Oil shall be filtered and tested for break down voltage (BDV) and moisture content before filling. c.) The oil shall be filled under vacuum. d.) The design and all materials and processes used in the repair of the transformer shall be such as to reduce to a minimum the risk of the development of acidity in the oil. 22. LOSSES : a.) The bidder shall guarantee individually the no-load loss and load loss without any positive tolerance. b.) For transformers of other rating the following maximum allowable losses at rated voltage and frequency and 75°C shall be taken: Distribution Transformers: Voltage Rating KVA Max. losses at 50% loading (Watts) Max. losses at 100% loading (Watts) 11000/433-250 V 250 1050 3320 11000/433-250 V 400 1450 4630 11000/433-250 V 500 1600 5500 7 23. TOLERANCES: a.) No positive tolerance shall be allowed on the maximum losses displayed on the label for both 50% and 100%, loading values. 24. PERCENTAGE IMPEDANCE. a.) The value of impedance of transformers at 75°C shall be 4.5% for transformers up to and 200 KVA and ,for ratings above 200 KVA shall be in accordance with IS 2026. 25. TEMPERATURE RISE: The temperatures rise over ambient shall not exceed the limits given below: a.) Top oil temperature rise measured by thermometer : 35 °C b.) Winding temperature rise measured by resistance method : 40 °C Bids not meeting the above limits of temperature rise will be treated as nonresponsive. c.) The reclaimed transformer shall be capable of giving continuous rated output without exceeding the specified temperature rise. Bidder shall submit the calculation sheet in this regard. 26. INSULATION MATERIAL: a.) Electrical grade insulation epoxy dotted Kraft Paper / Nomex and pressboard shall be of standard make or any other superior material. b.) All spacers, axial wedges / runners used in windings shall be made of pre- compressed Pressboard-solid, conforming to type 8 3.1 of: EC 641 -3-2. In case of cross-over coil winding of HV all spacers shall be properly sheared and dovetail punched to ensure proper locking. All axial wedges/ runners shall be properly milled to dovetail shape so that they pass through the designed spacers freely. Insulation shearing, cutting, milling and punching operations shall be carried out in such a way, that there should not be any burr and dimensional variations. 27. SURFACE PREPARATION AND PAINTING: GENERAL a.) All paints, when applied in a normal full coat, shall be free from runs. sags, wrinkles, patchiness. Brush marks or other defects, b.) All primers shall be well marked into the surface. Particularity in areas where painting is evident and the first priming coat shall be applied as soon as possible after cleaning. c.) Inner paintings shall be made of highly zinc chromite. 28. PROTECTIVE COATING: As soon as all items have been cleaned and within four hours of the subsequent drying they shall be given suitable anti-corrosion protection. 29. FASTENERS: a.) All bolts studs, screw threads, pipe threads, bolt heads and nuts shall comply with the appropriate Indian Standards for metric threads or the technical equivalent. b.) Bolts or studs shall not be less than 6 mm in diameter except when used for small wiring terminals. c.) All nuts and pins shall be adequately locked. d.) Wherever possible bolts shall be fitted in such a manner that in the event of failure of locking resulting in the nuts working loose and falling off, the bolt will remain in position. 30. TESTS: a.) Before dispatch each of the completely assembled transformer shall be subjected to the routine tests at the manufacturer's works as listed in IS 2026. 8 31. a.) b.) c.) d.) e.) f.) g.) h.) i.) ROUTINE TESTS: Ratio, polarity, phase sequence and vector group. No Load current and losses at service voltage and normal frequency. Load losses at rated current and normal frequency. 34.4 Impedance voltage test. Insulation resistance. Neutral current measurement-The value of zero sequence current in the neutral of the star winding shall not be more than 2% of the full load current. Oil samples (one sample per lot) to comply with IS 1866. Measurement of no load losses and magnetizing current at rated frequency and 90%, 100% and 110% rated voltage. The repaired transformer shall be accepted only after routine tests are done successfully. It may also be noted that the Department / Division reserves the right to conduct short Circuits lest and impulse voltage withstand test in accordance with the IS. 32. TESTS AT SITE: a.) The Department reserves the right to conduct all tests on transformer after arrival at site and the repairing agency shall guarantee test certificate figures under actual service conditions. b.) The stage inspection shall be carried out once the coils (HV & LV) are ready for assembling, in the premises of the manufacturer / repair agency. c.) In case of any defective workmanship observed at any stage by the Inspecting Officer, the same shall be pointed out to the firm in writing for taking remedial measures. Further processing should only be done after clearance from the Inspecting Officer. d.) All tests and inspection shall be carried out at the place of site of the bidder, unless otherwise specifically agreed upon by the bidder and the Department / Division at the time of dispatch. The repairing agency / bidder shall offer the Inspector representing the Department /Division all reasonable facilities, without charges, to satisfy him that the material is being supplied in accordance with this specification. This will include Stage Inspection during manufacturing/repairing stage. e.) The manufacturer/ bidder shall provide all services to establish and maintain Quality of workman ship in his works and that of his sub-contractors to ensure the mechanical/electrical performance of components, identification and acceptability of all materials, parts and equipment as per latest quality standards. f.) The Department / Division shall have every right to appoint a third party inspection to carryout the Inspection process. g.) The Department / Division has the right to have the test carried out at his own cost by independent agency wherever there is a dispute regarding the quality. 33. ACCEPTANCE TEST: T he D e p a r t m e n t a l / D i v i s i o n a l /Representative at the firm’s works shall witness the following tests: a.) All the routine tests as mentioned in above on each and every reclaimed transformer. b.) Further, the department / Division Inspector reserves the right to carry out any other test for acceptance of reclaimed transformers as per relevant specifications. 34. INSPECTION: All tests and inspection shall be carried out at the place of manufacture unless otherwise specifically agreed upon by the manufacturer and department / Division at the time of delivery. The manufacturer shall offer the Inspection representative of the department / Division with all reasonable facilities without charges to satisfy him that the material is being supplied in accordance with this specification. This will include Stage Inspection during manufacturing stage as well as Active Part Inspection during acceptance tests. The department / Division has all the rights to conduct the test including type tests at his own cost by an independent agency whenever there is dispute regarding the quality of supply or 9 interpretation of test results. In the event of failure of reclaimed transformer in such tests, the expenses incurred in testing and cost of reclamation r etc. shall be to the manufacturer’s/ repair agencies account. 35. QUALITY ASSURANCE PLAN: a.) In order to ensure use of quality material as per specified/ applicable standards, the department reserves the right to inspect the quality and quantity of material at works of the bidder firm before or during the reclamation process. b.) The bidder shall invariably furnish following information along with his bid, failing which 'his bid shall be liable for rejection. c.) Statement giving list of important raw materials, names of sub-suppliers for the raw materials, list of standards according to which the raw materials are tested, list of tests normally carried out on raw materials in the presence of bidder's representative, copies of test certificates. d.) Information and copies of test certificates as above in respect of bought out accessories. e.) List of manufacturing facilities available. f.) Level of automation achieved and list of areas where manual processing exists g.) List of areas in manufacturing process, where stage inspections are normally carried out for quality control and details of such tests and inspection, h.) List of testing equipment available with the bidder for final testing of equipment along with valid calibration reports. These shall be furnished with the bid. Manufacturer shall posses 0.1 accuracy class instruments for measurement of losses. 36. GUARANTEE: The manufacturer / Repair Agency shall among other things warranty the following: a.) Quality and strength of material used, both electrical and mechanical. b.) Satisfactory operation during the guarantee period of 12 months from the date of final Inspection( On successful completion of all routine tests for the delivery of Reclaimed Transformer) or 09 months from the date of commissioning. This period will be reckoned from the day all accessories are received enabling assembly testing, commissioning and commercial operation of transformers. 37. DEVIATIONS: The bidders are not allowed to deviate from the principal requirements of the Specifications and conditions as laid in the e-NIT. -SdExecutive Engineer, Electric Workshop Division Jammu Accepted Signature with Stamp/seal of Firm/Tenderer/Contractor 10