TECHNICAL DATA GENERAL
Climate Wizard air-conditioners operate with a high coefficient of
performance and are characterized by the provision of cool fresh
air that has had NO additional moisture added to the supply air
stream, and that is delivered at extremely low energy cost.
The air-conditioners comprise one (1) supply air fan, an indirect
heat exchanger pack, water reservoir and pump(s), complete
with all components for satisfactory operation.
Climate Wizard Air Conditioners comply with AS 2913-2000
where applicable and are capable of functioning continuously in
ambient temperatures up to 55°C (131°F).
CABINET
The cabinet is constructed from coated marine grade aluminum
incorporating the motor/fan assembly, non-corrodible heat
exchange core and other ancillary equipment mounted on a
heavy gauge base frame for structural stability. Fork lift tine
channels are provided within the frame to facilitate transport and
lifting. Components are effectively treated to ensure corrosion
resistance and mechanical fasteners are zinc coated,stainless
steel or aluminum. Connection surfaces are provided for inlet,
outlet and exhaust ductwork to be fitted using established
industry practices.
FAN ASSEMBLY
The fan is a multi blade, centrifugal type with backward curved
blades and single inlet. It has galvanized steel rotor and
aluminum impeller and is statically and dynamically balanced.
The fan is directly mounted to the electric motor. The electric
motor is high efficiency, electronically commutated and
responsive to pulse width modulation to implement speed control
that delivers optimum efficiency at lower speed operation.
HEAT EXCHANGE CORE
The heat exchange core is designed to facilitate heat exchange
between the wet air passages and the dry air passages such that
high efficiency heat transfer takes place without the addition of
any additional moisture. It is designed to provide long life and
consistent, long term high efficiency.
ES E061-H
CW-H10, CW-H15
RESERVOIR
The reservoir is a one piece molded polymer construction to ensure
durability, life-long corrosion eradication, and to provide excellent
sound deadening properties. The reservoir is provided with integrated
housings for the water pumps, level control, chlorinators, and salinity
monitoring water management system. The design of the reservoir
ensures that no water remains after draining.
ELECTRICAL CABINET AND CONTROLS
Control equipment including supply connection terminals, motor
control hardware, interface electronics, contactors, external control
wiring, and any ancillary equipment is factory mounted and wired and
contained within an approved enclosure meeting the requirements for
outdoor mounting. The air conditioner is not provided with an isolation
switch. The air-conditioner requires 3 phase power plus neutral and
earth (ground) for Australia and Europe, or 3 phase plus earth
(ground) - no neutral - for USA.
WATER MANAGEMENT SYSTEM
The water supply connection is a ½” BSP fitting that connects directly
to the internally mounted electric water solenoid. Core saturation is
achieved through internally mounted pumps delivering water to a
specially designed non clog water distribution system guaranteeing
continuous uniform flow, fitted at the top of each bank of heat
exchanger cores. The pumps are manufactured from engineering
plastics, with stainless steel shafts and fully encapsulated
synchronous motors with thermal overload protection. They are
provided with an easily cleanable strainer within the reservoir section.
The air-conditioner is fitted ex-factory with an electronic water
management system that controls the maximum salinity level of the
reservoir water through continuous monitoring and replenishment as
determined by the control system.
The air-conditioner is fitted with an electrically operated drain valve
that responds to the water management control system.
AIR FILTER
Intake air is filtered through replacable pleated filters. The assembly
includes a safety screen to protect the fan and a cover to minimise
intrusion of rain.
AU 1502
TECHNICAL DATA TOP VIEW
CW-H10, CW-H15
Dimensions CW-H10
Overall
CW-H15
Width:
1230mm (48.4”)
Height *
1610mm -0 (63.4”- 0
Length
1985mm (78.2”)
+20
1825mm (71.8”)
+0.75”
)
1610mm
+20
-0
+0.75”
(63.4” - 0
)
1985mm (78.2”)
(With Control Box handle)
Mounting Plinth
Width
Length
1206mm (47.5”)
1300mm (51.2”)
1800mm (70.9”)
1300mm (51.2”)
Inlet Duct
Outlet Duct
500mm (19.7”)W x 500mm (19.7”)H
500mm (19.7”)W x 500mm (19.7”)H
500mm (19.7”)W x 500mm (19.7”)H
500mm (19.7”)W x 500mm (19.7”)H
Center line of outlet duct above base
667mm (26.3”)
SUPPLY
AIR
(Cool & Dry)
EXHAUST
AIR
(Warm & Moist)
INLET
(AMBIENT)
AIR
667mm (26.3”)
*Overall height can vary as shown due to manufacturing and material tolerances.
REAR VIEW
SIDE VIEW
130mm (5.1”) Drain Outlet position
364mm (14.3”)
(CW-H10)
664mm (26.1”)
(CW-H15)
145mm
(5.7”)
180mm
(7.1”)
500mm
(19.7”)
500mm
(19.7”)
410
(16.1”)
500
(19.7”)
410
(16.1”)
493
(19.4”)
452mm (17.8”)
500mm
(19.7”)
+20
-0
+0.75”
*(35.8” - 0 )
*910mm
250mm (9.8”)
*Overall height can vary as shown due to manufacturing
and material tolerances.
610mm (24”)
ELECTRICAL SUPPLY
TERMINATIONS MADE
INSIDE CONTROL BOX
ACCESS COVER
FOR DRAIN VALVE
CONNECTION
ES E061-H
806mm (31.7”)
WATER CONNECTION
1/2” (15mm) BSP NIPPLE
(Water connection may
require an adaptor to
suit local pipe sizes)
319mm (12.6”)
130mm
(5.1”)
AU 1502
TECHNICAL DATA -
CW-H10, CW-H15
SPECIFICATIONS
General
Electrical supply
CW-H10
3-phase, 380-480, 50/60 Hz, 10 amps
3-phase, 380-480, 50/60 Hz, 10 amps
Water supply
1/2” BSP male connection,
min 100 kPa, max 800 kPa, 20 L/min
(min 15psi, max 115psi, 5.3gal/min)
1/2” BSP male connection,
min 100 kPa, max 800 kPa, 20 L/min
(min 15psi, max 115psi, 5.3gal/min)
Max. operating temperature
55°C (131°F) ambient (shade)
55°C (131°F) ambient (shade)
Airflow at high speed
800 L/sec - at 0 - 200 Pa
(1695cfm - at 0 - 0.8” static)
1100 L/sec - at 0 - 200 Pa
(2330cfm - at 0 - 0.8” static)
(Inches Static Pressure Water Gauge)
(Inches Static Pressure Water Gauge)
73.5 dB(A) at 1m on centerline
from discharge
79 dB(A) at 1m on centerline
from discharge
Fan
Integral with motor,
backward curved aluminium or platic impellor
500mm (19.7”) dia x 285mm (11.2”) w
560mm (19.7”) dia x 285mm (11.2”) w
Motor
IP 54 die-cast aluminium housing.
ECM with PWM control
Input Power 1400W (Nominal)
Input Power 1800W (Nominal)
Pump
SI ‘Tornado’, 2-pole synchronous,
vertical centrifugal 230V, 50 or 60Hz
2 pumps, 20 L/min (5.3gal/min) @ 1m (39.4”) head
Input Power 20W ea
3 pumps, 20 L/min (5.3gal/min) @ 1m (39.4”) head
Input Power 20W ea
Chlorinator
SI low voltage, Catalytic Chlorine generator
2 chlorinators
2 chlorinators
Drain valve
SI low voltage, vertical, electric drive
1½” (40mm) BSP male
1½” (40mm) BSP male
Heat exchanger core
SI Synthetic plate type, super efficient
2 cores
3 cores
Water reservoir (full)
SI one piece, moulded polymer
45 L (11.9 gal)
65 L (17.2 gal)
Shipping - dimensions
1985mm L x 1230mm W x 1170 H
(78.1” L x 48.4” W x 46.1” H)
1985 L x 1825 W x 1170 H
(78.1” L x 71.8” W x 46.1” H)
Shipping - weight
180 kg (397 lb)
220 kg (485 lb)
Operating Weight
225 kg (496 lb)
265 kg (584 lb)
Air Filters
Type G4 standard
Size
485x345x45
600x345x45
720x485x45
Sound pressure at high speed
ES E061-H
CW-H15
Qty
1
1
1
Size
485x345x45
600x345x45
720x345x45
Qty
1
2
1
AU 1502
TECHNICAL DATA CW-H10, CW-H15
MAIN PCB
INTERFACE PCB
CHLORINATOR X 2
C8 C9 C10
C6
C4
C3
C5
T1 T2 T3
2
4
T4
T5
T6
N2
gn/y
W2
5 A1
C12
C12
C4
V2
3
1
PUMP X 2
U2
FAN CONTACTOR
C1
C17
C16
C15
C14
C7
C2
C13
C13
C10
BMS CONTROLS
C11
C11
3 PHASE
FILTER
gn/y
6 A2
E
N1
N
V1
L3
W1
U1
L1 L2
E
MAIN SUPPLY
FAN
859651-B
MAIN PCB
INTERFACE PCB
CHLORINATOR X 2
C8 C9 C10
C1
PUMP X 2
C6
C3
C4
C17
C16
C15
C14
C7
C2
C13
C13
C10
C5
BMS CONTROLS
C11
C11
C12
C12
C4
1
3
31 32 33 34 35 36 37 38
5 A1
gn/y
gn/y
T1 T2 T3 T4 T5 T6 T7
2
4
6 A2
100VA TRANSFORMER
380-480V TO 230V
PRIMARY
L1
FAN
L2
L3
E
0V
115V
0V
115V
FAN CONTACTOR
SET FOR 480V
MAIN SUPPLY
860312-A
Australian and European
Climate Wizard Control
PCB Wiring Diagram.
(3 Phase 415V)
C1 MOTOR CONTACTOR COIL
C2 FUSE T12.5A
C3 MAIN PCB POWER IN
C4 PUMP LINK
C5 DRAIN VALVE
C6 SALINITY PROBE
C7 MOTOR CONTROL SIGNAL
C8 WALL CONTROL
C9 WATER INLET SOLENOID
C10 CHLORINATOR LINK
C11 INTERFACE BOARD LINK
C12 PUMP X 2
C13 CHLORINATOR x 2
C14 BMS COOL/VENT INPUT
C15 BMS ERROR SIGNAL OUTPUT
C16 BMS REMOTE ON/OFF INPUT
C17 BMS FAN SPEED INPUT 0-10Vdc
USA
Climate Wizard Control
PCB Wiring Diagram.
(3 Phase 380 - 480V)
C1 MOTOR CONTACTOR COIL
C2 FUSE T12.5A
C3 MAIN PCB POWER IN
C4 PUMP LINK
C5 DRAIN VALVE
C6 SALINITY PROBE
C7 MOTOR CONTROL SIGNAL
C8 WALL CONTROL
C9 WATER INLET SOLENOID
C10 CHLORINATOR LINK
C11 INTERFACE BOARD LINK
C12 PUMP X 2
C13 CHLORINATOR x 2
C14 BMS COOL/VENT INPUT
C15 BMS ERROR SIGNAL OUTPUT
C16 BMS REMOTE ON/OFF INPUT
C17 BMS FAN SPEED INPUT 0-10Vdc
SEELEY INTERNATIONAL PTY LTD, 112 O’Sullivan Beach Rd, Lonsdale, South Australia, 5160. Phone No: (61) 8 83283850. Fax No: (61) 8 83283973.