Aerosphere Midibus Air Conditioning System Operation Manual Aerosphere Midibus 05/2013 P.N. 10000038A To receive the best performance from the air conditioning system, we suggest carefully reading this manual before operating the unit. Keep this manual in the vehicle for future reference. Aerosphere Midibus Table of Contents 12- 3- 4- 567- INTRODUCTION………………………………………………………………………………. SAFETY PRECAUTIONS……………………………………………………………………... SPECIFIC WARNINGS………………………………………………………………………... EQUIPMENT GENERAL ARRANGEMENT………………………………………………… 1.1 - MIDIBUS AIR CONDITIONING COMPONENTS………………………………….. CONTROLS AND INDICATORS……………………………………………………………... 2.1 - FUNCTION OF THE DIGITAL DASH CONTROL ………………………………… 2.2 - FUNCTION OF THE DIGITAL DASH CONTROL AND INDICATOR……….…… EQUIPMENT OPERATION…………………………………………………………………… 3.1 - COMMAND DESCRIPTION – NORMAL OPERATION…………………………… 3.2 - COMMAND DESCRIPTION – FAILURE MODE…………………………………… 3.3 - COMMAND DESCRIPTION – TEST MODE……………………………………….. 3.4 - ELECTRICAL MALFUNCTIONS…………………………………………………….. 3.5 - AIR CONDITIONING SYSTEM MALFUNCTIONS………………………………… 3.6 - REFRIGERATION CIRCUIT MALFUNCTIONS……………………………………. PREVENTIVE MAINTENANCE ACTIVITIES……………………………………………….. 4.1 - GENERAL……………………………………………………………………………… 4.2 - AUXILIARY DATA VISULIZATION MODE…………………………………………. 4.3 - PREVENTIVE MAINTENANCE SCHEDULE………………………………………. TECHNICAL SPECIFICATIONS……………………………………………………………… FAILURE DIAGNOSIS TABLE……………………………………………………………….. ELECTRICAL SCHEMATICS OF RELAY BOARD AND DIGITAL DASH CONTROL…. 7.1 - RELAY AND FUSE LOCATION……………………………………………………… 7.2 - RELAY BOARD (GL-W134) CONNECTIONS……………………………………… 7.3 - RELAY BOARD FUNCTION LED’s…………………………………………………. 7.4 - SCHEMATIC FOR DIGITAL DASH CONTROL AND RELAY BOARD………….. Page 2 3 4 6 6 7 7 8 9 9 13 14 15 15 16 17 17 18 19 20 21 23 23 24 25 26 1 Aerosphere Midibus INTRODUCTION At Spheros, we develop our products with the goal of providing a comfortable environment for vehicle passengers. We are always looking for the best air condition concepts that provide the highest performance at the best possible value. The compact systems are simple to operate and provide high cooling capacities at low noise levels. This manual was developed with the purpose of presenting critical functional aspects, describing the ease of operation and recommended maintenance necessary to obtain the best performance from the Spheros Air Conditioning system. To ensure a long, useful and problem free life from the equipment it is essential that the operation and maintenance instructions described in this manual are followed routinely and thoroughly. All system controls provided by Spheros, are duly illustrated and explained in this manual. It is important that the operator reads and understands the operation instructions carefully before starting the air conditioning equipment. Spheros makes every effort to maintain a network of authorized service professionals trained to perform any type of maintenance within the quality standard. Thank you for choosing Spheros Air Conditioning products. If you have any questions or concerns with our products, please contact us or the nearest authorized service provider. Spheros Climate Systems, LLC 5536 Research Drive Canton, MI 48188 Phone 1-734-218-7350 Toll free 1-888-960-4849 2 Aerosphere Midibus SAFETY PRECAUTIONS GENERAL SAFETY NOTICES The following safety notices supplement warnings and cautions appearing elsewhere in this manual. The following are recommended precautions that must be understood and applied during operation and maintenance of the equipment. Failure to adhere to warnings and cautions may result in damage to equipment, fire, personal injury and even death. OPERATING PRECAUTIONS Keep hands, clothing and tools clear of the evaporator and condenser fans. No work should be performed on the system unless battery power is disconnected. In case of severe vibration or unusual noise, stop the system and investigate. MAINTENANCE PRECAUTIONS Always wear protective eye wear (safety glasses or goggles) and appropriate safety wear. Never perform any maintenance or service on your equipment before consulting with authorized service personnel. Always unplug unit before attempting any maintenance. Avoid breathing any refrigerant vapor, lubricant vapor, or mist. Exposure to these, particularly PAG oil mist may irritate your eyes, nose, or throat. Never use compressed air (shop-air) to leak-test or pressure test a R134A system. Under certain conditions, pressurized mixtures of R134A and air can be combustible. In addition, shop air will inject moisture into the system. Always use mineral oil to lubricate “O” Rings, hoses, and fittings on R134A systems. PAG oils absorb moisture and become very acidic and corrosive. Mineral oil does not absorb moisture and thus prevents corrosion. Always wear gloves when working with PAG (Polyalkylene Glycol) and Ester (POE or Polyester) lubricants to prevent irritation to your skin. R134A lubricants can damage vehicles paint, plastic parts, engine drive belts and coolant hoses. Beware of unannounced starting of the evaporator and condenser fans. Do not remove the evaporator/condenser cover without disconnecting the vehicle battery cable. Be sure power is turned off before working on motors, controllers, and electrical control switches. Tag system controls and vehicle battery to prevent accidental energizing of the system. In case of electrical fire, extinguish with CO2 (never use water). Disconnect vehicle battery power if possible. 3 Aerosphere Midibus SPECIFIC WARNINGS AND CAUTIONS WARNING Be aware of unannounced starting of the evaporator and condenser fans. The unit may cycle the fans and compressor unexpectedly as control requirements dictate. WARNING The refrigerant contained in the air conditioning system when in direct contact with skin and eyes can cause frostbite, severe burns or blindness. WARNING Be sure to observe warning listed in the safety precautions in the front of this manual before performing maintenance on the air conditioning system. WARNING Never use air for leak testing. Pressurized, air-rich mixtures of refrigerants and air are combustible when exposed to ignition source. 4 Aerosphere Midibus SPECIFIC WARNINGS AND CAUTIONS WARNING Do not use a nitrogen cylinder without a pressure regulator. Do not use oxygen in or near a refrigeration system as an explosion may occur. WARNING The filter-drier may contain liquid refrigerant. Slowly open the fitting nuts and avoid contact with exposed skin or eyes. CAUTION Unless there was a catastrophic failure, such as a blown or ruptured refrigerant hose, additional oil may not be needed. CAUTION Use only the exact oil specified by the compressor manufacturer. Use of oil other than that specified will void the compressor warrant 5 Aerosphere Midibus 1. Equipment General Arrangement 1.1 Midibus Air Conditioner Components The Midibus air conditioner and its main components are shown in Fig. 1. 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. Evaporator Blowers, Right Electrical Interface with Fuse Array Shut off Valve Filter Drier Sight Glass Solenoid Valve Receiver Expansion Valve Bleed Valve – Heater Core Evaporator Blowers, Left Heater Core Evaporator Air Filter Condenser Condenser Fan Fresh Air Dampers Main Relay Board Heating Board Fig. 1 – Main Components 6 Aerosphere Midibus 2. Controls and Indicators 2.1 Functions of the Digital Dash Control Panel The air conditioner control panel has all controls and indicators for system settings, mode switching and and provides visual display of operation status. The control panel and its controls and indicators are shown in Fig. 2. 1 2 15 3 14 4 13 5 12 6 11 7 10 8 9 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. Internal/External Temperature Key External Temperature LED Display Smart Air LED Auto Mode Key Auto Mode LED Ventilation Speed LED’s Ventilation Key Reheat LED Reheat Key Fresh Air / Recirculated Air Fresh Air LED Down Key Up Key Internal Temperature LED Fig. 2 - Digital Dash Control Panel 7 Aerosphere Midibus 2.2 Function of Digital Dash Control and Indicators The function of the controls and indicators is shown in Fig. 3. Note: All keys have backlit red LED’s, Index Fig. 3 1 2 Control / Indicator Internal / External Temperature Key External Temperature Key Setting / Indication Pressed Lit °F 3 Display Number or Code 4 Smart Air LED Lit 5 AUTO Key Pressed 6 7 AUTO Mode LED Ventilation Speed LED 1, 2, 3 Ventilation Key Lit 1, 2,or 3 Lit Lit Pressed Pressed 12 13 Reheat LED Reheat Key Fresh Air / Recirculated Air Key Fresh Air LED Down Key 14 Up Key Pressed 15 Internal Temperature LED Lit 8 9 10 11 Pressed Lit Pressed Function Selects internal or external temperature indication and displays for 5 seconds. External temperature indication selected and displays for 5 seconds. Ignition on, system in standby for activation by pressing the AUTO key. Ventilation only is possible by pressing ventilation key. Indication of temperatures, ventilation speed, failure codes and status information depending on system operational mode and indication selections. See “Command Description” for details. Smart air mode on. In AUTO mode the system adjusts to best comfort and thermal balance by opening fresh air damper for 10 seconds every 10 minutes AUTO mode on or off. When on, system automatically controls heating and/or cooling to obtain the set temperature. With AUTO mode on, system operates in AUTO mode. Indication of ventilation speed selected. AUTO mode LED is off. Manual selection of blower speeds with up / down keys to override AUTO mode ventilation speed. Indication of Reheat mode selected. Selects Reheat mode for cabin dehumidification. Opens or closes fresh air damper to override AUTO mode fresh air damper position. Reheat Mode ON Down control for system settings and readings of the operational modes including testing and system status. Up control for system settings and readings of the operational modes including testing and system status. Internal temperature indication selected and on display for 5 seconds. Fig. 3 - Function of Controls and Indicators 8 Aerosphere Midibus 3. Equipment Operation 3.1 Command Description – Normal Operation Display The two digit numeric display is used for informing the operator about the selected set temperature. With the vehicle ignition ON, the display will show °F/°C to indicate standby for A/C operation which can be activated by pressing the key and selecting the desired temperature. When AUTO mode is off, it is possible to have just ventilation by pressing the key. Automatic Mode 1 - To select the Automatic Mode press the key. The display shows the set-point temperature and the system activates the required function (cooling or heating) according to the internal temperature, external temperature, set-point and parameters. 2 – To disable the Automatic Mode, press the key again. Set-Point The set-point is the desired temperature inside the vehicle. To change the set point temperature the AUTO mode must be selected. The set-point temperature will be shown in the display and may be adjusted by pressing the or keys. Auto Mode with Blower Speed Priority In the AUTO mode the blower speed is determined automatically. The operator may set the blower speed manually as follows: - Turn on the AUTO mode by pressing the key. - Press the key. The blower speed will be shown on the display for a few seconds. - If the operator presses the or key while the speed is displayed, the speed LED will come on indicating manual speed mode. - Use the and keys to select the desired speed. - To return to automatic mode, press the key. This mode is useful when it is convenient to maintain a constant blower speed. It may be used for driving at night with sleeping passengers at a constant blower speed of 1 to reduce the noise with a minimum A/C function. 9 Aerosphere Midibus Ventilation Mode The Ventilation function is activated by pressing the key. There are three operation speeds. Press the key and the speed will be shown and may be adjusted by pressing the or key. When you select the ventilation function, the fresh air damper (air renewal) is automatically opened. To close the fresh air damper, the operator must press the key and the key. SPEED DISPLAY INDICATION LED’s Off Low Medium High Fig. 4 – Indication of Ventilation Mode Internal / External Temperature Press the key - internal temperature (LED 15, Fig. 3) Press the key two times – external temperature (LED 2, Fig. 3) The desired temperature will be displayed for 5 seconds. The display will then return automatically to the set temperature. Compressor The compressor is activated based on temperature, the pressure switches and programmed values of the set-point. The compressor will start 10 seconds after the condenser motors are activated. The controller provides a fixed time delay of 60 seconds for restarting the compressor. When the external temperature is below 59°F/15°C in cooling mode, the system tries to cool down with fresh air and the clutch may be disengaged. 10 Aerosphere Midibus Condenser Motors The condenser motors will start every time there is the need to turn on the compressor. They will always run for 10 seconds before the compressor clutch is engaged. System Pressure Switches The system monitors pressure by means of a high and low pressure switch in series with the clutch. In case of a pressure failure, the clutch will be disengaged immediately. The system will detect a failure after 2 seconds and will start indicating on the display alternating with the temperature reading. Once the pressure fault disappears and the AUTO mode is on and the other conditions have been met, the system will delay for 3 minutes before allowing the compressor to start. This failure condition is constantly monitored whether system is on or off. If the failure occurs 6 times or more within 30 minutes, the alarm will be activated to indicate a serious system failure and A/C operation will not be allowed. To reset the system it will be necessary to turn the vehicle ignition off and then on again. Evaporator Freeze Protection The system is monitored by a thermostat which senses icing of the evaporator coil. When the thermostat responds (opens contacts) the compressor clutch disengages and the evaporator motors remain on to allow the coil to defrost. While the thermostat is activated, the display will show the failure code alternating with the temperature display. After defrosting the thermostat will return to normal operation. With the AUTO mode ON the system will delay for 3 minutes before the compressor will restart. Evaporators The system controls an evaporator with 3 speed blowers. The blowers always start in Low speed in the AUTO mode and if necessary the speed is increased to the calculated speed. This extends the blower’s life and reduces the noise level. The control of the evaporator motor speed is automatic according to the temperatures in the AUTO mode. When the temperature approaches the set temperature, speed is reduced and increased again in order to approach the set temperature (except in heating mode). Roof Heating (optional) Heating will only be available when unit is equipped with a heating board. A valve controls the flow of hot water passing through the heater core. A water pump is turned on each time the valve is opened to a certain extent. When in the heating mode, the blowers always work at LO speed in AUTO mode. If necessary, it is possible to change the speed manually to MED or HI. 11 Aerosphere Midibus Fresh Air / Air Recirculation There are two system operation modes: - Smart Air - Manual Mode (temporary) Fresh air operates in both modes. The Smart mode automatically controls operation according to the temperature conditions of internal, external and for exchanging the air inside the vehicle. The manual mode allows the driver to control the external air quantity manually. When the AUTO mode is activated, Smart Air is selected as indicated on the control panel by the Smart Air LED. This function enables air renewal to operate so it adjusts to meet comfort and thermal balance conditions as well as saving fuel. To change the fresh air damper position press , the control panel will show the damper position. INDICATION FRESH AIR Open Closed When the fresh air damper position is shown, press to open or to close the fresh air damper. The display point will disappear and the manual mode is initiated. After 10 minutes the system returns to the Smart Air mode of operation. In the Smart Air mode the fresh air damper opens and closes automatically with the air damper open for 10 seconds every 10 minutes. This will only occur when the internal temperature sensor senses between 3° over and 3° below the set temperature. Reheat Mode (optional with roof heating) This mode only operates when heating is included in the system. This mode enables dehumidification inside the vehicle. To turn on Reheat press the key and the mode will be active for 10 minutes. During reheat operation the fresh air damper is closed. If the driver tries to open the fresh air damper and the system refuses, the panel will display . In the reheat mode the air conditioning system is activated including the condenser, evaporator and compressor. At the same time the roof duct heating is enabled to reach the set temperature. The simultaneous operation of both the air conditioning system and the roof system is how dehumidification is accomplished. This mode operates only when the set-point temperature is higher than or is equal to the internal temperature and the external temperature exceeds 46°F/8°C. Any other condition prevents the driver from selecting the Reheat Mode. The display will show when the external temperature is less than 46°F/8°C and when the set-point temperature exceeds the internal temperature. This mode of operation is particularly recommended in inter-seasonal periods when the air is extremely humid. 12 Aerosphere Midibus 3.2 Command Description – Failure Operation Failure Operation – Control Panel Functions The system indicates failure codes on the display. The possible failure codes and their meanings are shown in Fig. 5. FAILURE POSSIBLE CAUSE OPERATIONAL BEHAVIOR Communication failure between control panel and main relay board Internal sensor failure The system automatically activates the A/C AUTO function using a previously stored set-point. The system defaults at an internal temperature value of 71°F/22°C. For heating the driver must program a set-point temperature > 71°F/22°C. If cooling is necessary, the driver must select a set-point ≤ 71°F/22°C. Control takes place regarding the return air temperature, with the parameter value equal to 0. The system uses an external air temperature value of 71°F/22°C. The reheat and the smart air modes are disabled. The condenser and compressor are turned off. When the failure disappears the system is reactivated with a delay of 3 minutes. The system will only operate in the ventilation or heating mode. In order to start the A/C again, the control must be reset by turning system off and back on. The compressor and condenser fans are turned off. When the coil is defrosted the system will delay for 3 minutes and resume operation. All functions are disabled. To restore operation press the auto key and 10 seconds later press auto key again. The compressor and condenser are turned off and system operates in low speed ventilation mode. When the alternator reaches the normal range the system will resume operation. All functions are disabled. To restore operation press the auto key and 10 seconds later press auto key again. When temperature rises above 46°F/8°C the system will resume operation. Air duct sensor failure External sensor failure Pressure switch failure Pressure switch failure occurred 6 times within 30 minutes Icing of the evaporator coil Alternator voltage above 33 Volts Alternator voltage below 21 Volts Alternator voltage below 18 Volts External Temperature below minimum of 46°F/8°C with reheat mode enabled. Fig. 5 - Failure Code Indications 13 Aerosphere Midibus 3.3 Command Description – Test Operation This mode is used to diagnose the system by checking the inputs (Fig. 6) and activating the outputs (Fig. 7). To access this mode, perform the following steps: - Press the keys + . The display will indicate --, asking for the access password. The access password is “14”. Use the key for increasing the first digit and the key for decreasing the second digit until the correct password is displayed. Press to confirm. If the password is incorrect, the display will indicate the vehicle internal temperature. After verifying the password, the display will indicate for inputs to be tested. Press for alternating between the inputs and the outputs. By pressing the key, the display will indicate or , depending on whether it is an input or an output. When it is an input the ventilation LED speed 2 will display the input status. If it is blinking the input is “off” and not blinking indicates “on”. When you select an output , press to turn it on and/or off. The ventilation LED speed 2 will be on indicating output is on. Press or for alternating between other inputs or outputs. When you alternate the output function, the previous function will be turned off. Press to exit a selected input or output mode and move to another or press the second time to exit the test mode. The function allows the A/C system to operate without considering internal temperature. This function is used when it is necessary to turn on the A/C for testing when the temperature inside the bus will not allow the A/C to operate. All other protections are enabled in this mode. INPUT LED “ON” LED “BLINKING” Pressure Switches Input DESCRIPTION Both Pressure switches are OK or in the closed position Evaporator coil Ice Sensor Input Ice Sensor OK Input indicating the Heating system is enabled Heating control board GL-W002 is installed, enabled and operating One or both Pressure Switches in fail status or in the open position. Check connections and pressure switches. Ice sensor indicates that the evaporator coil is blocked with ice. Check Ice Sensor and connections. Heating control board GL-W002 not installed. Fig. 6 - Test Operation Input Readings 14 Aerosphere Midibus OUTPUT DESCRIPTION Turns blowers on at Low speed Turns blowers on at Medium speed Turns blowers on at High speed Opens air flap Turns on fans (condenser motors) Turns on water pump Opens heating valve (30%) (If heating option is installed) Opens Heating valve (65%) (If heating option is installed) Opens Heating valve (99%) (If heating option is installed) Refrigerant charge function, allows refrigeration to take place independently of the control conditions Fig. 7 – Test Operation Output Readings 3.4 Electrical Malfunctions The individual circuits are to be checked systematically in accordance with the wiring diagram. The plug connections and electrical components such as switches, relay, etc. should be checked. The following are possible causes of electrical malfunctions and should always be checked first so they can be excluded as the cause of the failure: - Corroded plug contacts - Loose plug contacts - Corroded wires - Corroded battery terminals - Broken wires - Defective fuses 3.5 Air Conditioning System Malfunctions The following failures may occur in the air conditioning system and may lead to a fault lockout of the system: - Activated freeze protection sensor - Activated high / low pressure switch - Defective compressor - Defective evaporator or condenser fans - Refrigerant loss due to leaks - Plugged air filter or dirty heat exchanger fins - Restricted refrigeration circuit (filter drier) - Defective expansion valve 15 Aerosphere Midibus 3.6 Refrigeration Circuit Malfunctions If malfunctions occur in the refrigeration circuit of the air conditioning system, the system must be checked and properly repaired by an authorized air conditioning service professional. CAUTION The refrigerant is not allowed to be released to the atmosphere. Regulatory requirements mandate that individuals who open a system or container containing a controlled refrigerant be certified. Check the refrigerant charge in the system: - After the air conditioning system has been operating for approx. 5 min. with the electromagnetic clutch activated and the engine running at a rapid idle, the refrigerant should flow through the sight glass without forming any bubbles. During the cold season: - To prevent the shaft seal of the compressor from drying out and leaking, operate the air conditioning system for approx. 15 min. twice a month at ambient temperatures above 46°F (8°C). The refrigerant receiver as well as all components of the air conditioning system should be visually inspected during the maintenance activities. Special attention should be directed to any signs of corrosion and mechanical damage. All components that are not in perfect condition must be replaced for safety reasons. CAUTION The pressure vessels directive requires the operator to have the refrigerant receiver checked by an authorized service professional at regular intervals. Note To ensure trouble free operation of the air conditioner, the refrigeration oil and filter drier must be replaced 6 months after the initial operation of the vehicle or if there is a change in color of oil. a) Yellow – Normal oil b) Black – Carbonized oil c) Brown – Copper Corrosion, due to moisture in system d) Metallic Gray – Suspended metallic particles The filter drier should be replaced every year at the beginning of the season or every time system is exposed to contamination. These activities must be performed by an authorized service company which should also perform a functional check of the air conditioner as well as a leak test of the system. Warranty claims can only be accepted if the claimant can prove that the maintenance and safety instructions have been strictly observed. 16 Aerosphere Midibus 4. Preventative Maintenance Activities 4.1 General An air-conditioning system just as all other parts of the vehicle subjected to constant mechanical strain and stress. To ensure trouble-free operation of the system and to avoid any damage to its parts, it is important that all required service activities on the air conditioning system are performed by trained and qualified personnel who are knowledgeable in the field of refrigeration. The proper handling of the system including proof of the service activities record is a prerequisite for acceptance of any warranty claims in the event of damage to parts subject to maintenance. Warranty replacement parts and out of warranty replacement parts must be supplied by Spheros Climate System, LLC to assure the quality and reliability of the product. Regardless of the maintenance intervals specified in the maintenance and service schedule, all attachments of the unit and the connections of the refrigerant lines must be checked for tightness within the first four weeks following the initial start-up of the airconditioning system or the vehicle. Even if the air-conditioning system is not in operation, wear caused by normal aging or the strain and stress occurring during the driving operation of the bus may occur on individual components. All checks listed in the maintenance and service schedule need to be independent of the operation hours of the system. Loss of refrigerant is possible even if the refrigerant connections are tight due to the structure of the material of the refrigerant lines and the ambient temperatures. In the event of a relatively high refrigerant loss within short intervals, leaks in the system can be assumed. During long periods of non-use, the air-conditioning system should be operated for about 15 minutes at least twice a month in order to prevent the shaft seals of the compressor from hardening. The drive pulley of the electromagnetic clutch is continuously rotating when the vehicle engine is in operation. Bearing wear or possible damage to the clutch may occur and should be inspected independently of maintenance intervals based on the operating time of the air-conditioning system. It is imperative that the clutch be checked for correct lubrication, belt tension etc. CAUTION - The refrigerant receiver is subject to the Pressure Equipment Directive. Check the receiver every 6 months for cracks, mechanical damage or corrosion. The receiver must be replaced if any defects are found. - The maintenance intervals indicated in the maintenance and service schedule are based on the operation hours of the vehicle, with the exception of the compressor assembly, which are based on the air-conditioning unit’s hours of operation. - These time intervals are empirical values that may vary widely depending on the type of system and type of bus concerned 17 Aerosphere Midibus 4.2 Auxiliary Data Visualization Mode The system presents an auxiliary data visualization mode. For entering this mode, press the display will indicate the first auxiliary which is total hours of compressor operation. and keys for 3 seconds. The Example: Example indicates 129 thousand 128 hours of total compressor operating hours. Press or keys to alternate between the various indications as listed in Fig. 8. To exit this mode press the key. The following table shows the Auxiliary Data Indications with their description: INDICATION DESCRIPTION Total hours of compressor operation shown in the format 00 00 00 Alternator voltage displayed in VDC Temperature of duct sensor for heating mode Dash Control software version Relay Control Board software version Heating valve open positions (30%, 65%, 99%) Fig. 8 – Auxiliary Data Indications 18 Aerosphere Midibus 4.3 Preventive Maintenance Schedule All preventive maintenance described below is based on typical operating conditions. The frequency outlined below is for normal operating conditions and should increase if used under more sever conditions. COOLING CIRCUIT Measure and record the refrigerant pressures and temperatures of the suction line Measure and record the refrigerant pressures and temperatures of the liquid line Visually inspect for signs of oil or refrigerant leaks After 15 minutes of operation check refrigerant level using the sight glass Visually inspect all components, tubes and hoses for signs of wear and deterioration Change the filter drier once a year or each time the system is opened Check the opening and closing pressures of the high and low pressure switches COMPRESSOR / CLUTCH Visually inspect the clutch plate Visually inspect the condition, tension and alignment of the compressor belts Clean the compressor and clutch with steam or hot water Measure the resistance and the voltage on the clutch coil Check the compressor oil level after 15 minutes of operation STRUCTURE Visually inspect for loose parts, damaged or broken wires Clean or replace the return air filters Clean the condenser and evaporator drains Clean the fins the evaporator and condenser coils with coil cleaner or soap and water Retighten all bolts on the compressor support and the unit using recommended torque MONTHLY ANNUALLY X X X X X MONTHLY QUARTERLY X ANNUALLY X X X X MONTHLY X X QUARTERLY ANNUALLY X X MONTHLY Check control panel operation, clean panel and thermostat sensor with air Check the alternator for corrosion and inspect electrical connections Visually check the alternator belt tension, check for mis-alignment and wear X Check the power cable at the relay plate, re-torque if necessary Inspect all wires and terminals for damage and corrosion X Check the ventilation of the condenser and evaporator motors Note: We recommend using this table to develop a plan for routine maintenance to you A/C System ELECTRICAL SYSTEM QUARTERLY X X QUARTERLY ANNUALLY X X X X 19 Aerosphere Midibus IMPORTANT: The return air filter and the condenser coil must be checked and cleaned weekly. As a rule, the air ducts must be cleaned every 3 months and more frequently depending on operating times of the system, the number of passengers and the severity of the environmental conditions. A cost effective preventive maintenance program can prevent costly down time and repairs and avoid cancellation of warranty due to negligence. 5. Technical Specifications The main specifications for the air conditioning system are shown in Fig. 9. Technical Data Max. Cooling Capacity (BTU/H) / (KW)* Heat Output (BTU/H) / (KW)* Dimensions: Length x Width x Height (in) / (mm) Weight (lbs) / (kg) Evaporator Air Flow (CFM) / (m³/h) Maximum Outside Temperature (°F) / (°C) Supply Voltage (VDC) Current Consumption @ 24 VDC / 12 V (AMPS) Refrigerant Type Number of Evaporator Blowers Number of Condenser Fans Aerosphere Midi 85,304 / 25 102,364 / 30 90.6 x 72.5 x 8.3 / 2,300 x 1,840 x 210 298 /135 2,472 / 4,200 140 / 60 24V 70A R-134A 4 3 *Evaporator air in 104°F / 40°C, 46% RH, Ambient 95°F / 35°C. Fig. 9 - Technical Data 20 Aerosphere Midibus 6. Failure Diagnosis Table As a troubleshooting aide, the table in Fig. 10 lists possible failure symptoms, possible causes and solutions to assist in correcting the problem. Symptoms Compressor does not work HP switch opens LP switch opens Condenser Fan not working Evaporator Blower not working Possible Cause Fuse or relay defective Magnetic clutch burned Compressor locked Low pressure switch open Overcharge of refrigerant Condenser coil dirty Condenser fan(s) not working Faulty HP switch Loss of refrigerant Plugged or defective expansion valve Dirty evaporator coil Dirty air filter Evaporator blower(s) not working Faulty low pressure switch Electrical wiring connection bad Burned fuse or defective control relay Open winding in motor Electrical wiring connection bad Burned fuse or defective control relay Open winding in motor Solution Replace fuse or relay Replace clutch Replace compressor Low on refrigerant or defective pressure switch Adjust refrigerant charge Clean condenser coil Replace fan(s) Replace HP switch Check for possible leak, adjust charge Replace the expansion valve Clean the evaporator coil Clean or replace air filter Replace blower(s) Replace low pressure switch Locate and repair connection Replace fuse and/or relay Replace fan Locate and repair connection Replace fuse and/or relay Replace blower Fig. 10 - Failure Diagnosis Table 21 Aerosphere Midibus Symptoms AC does not cool and Compressor remains on AC cools down too much and Compressor continues to run High discharge pressure Possible Cause Low on refrigerant charge Non-Condensables in system Plugged or defective expansion valve Dirty evaporator coil Dirty air filters Incorrect temperature set point selection Temperature sensor location Overcharge of refrigerant in system Restriction in sealed system Condenser fan not working Low suction pressure Dirty condenser coil Low system charge Return air temperature too low Plugged or defective expansion valve Evaporator Blower(s) not working Restriction in sealed system Dirty air filters Dirty evaporator coils Solution Check for leaks, adjust charge Evacuate the unit to 1000 microns or less and adjust charge to correct amount Replace the expansion valve Clean the coil Clean or replace air filters Adjust desired set point temperature on control panel Check and relocate temperature sensor Adjust charge to correct amount Locate and remove restriction, compressor valve partially closed, expansion valve partially closed, filter drier plugged Refer to symptom “Condenser Fan not Working” Clean condenser coil Check for leak, adjust charge Relocate temperature sensor Replace the expansion valve Refer to symptom “Evaporator Blower(s) not Working Locate and remove restriction Clean or replace air filters Clean evaporator coils Fig. 10 - Failure Diagnosis Table 22 Aerosphere Midibus 7. Electrical Schematics of Relay Board (GL-W134) and Digital Dash Control (GL-W111) 7.1 Relay and Fuse Location GL-W134 RELAY RL1 RL2 RL3 RL4 RL5 RL6 RL7 RL8 RL9 RL10 RL11 RL12 RL13 FUNCTION Condenser Fans 1 & 2 Condenser Fan 3 Clutch Evaporator Blower 3 & 4 HI Evaporator Blower 3 & 4 LO Evaporator Blower 3 & 4 MED Evaporator Blower 1 & 2 HI Evaporator Blower 1 & 2 MED Evaporator Blower 1 & 2 LO Evaporator Blower 5 & 6 LO Evaporator Blower 5 & 6 MED Evaporator Blower 5 & 6 HI Condenser Fans 4 & 5 TYPE FUSE F1 F2 F3 F4 F5 F6 F7 F8 F9 F10 F11 F12 FUNCTION Condenser Fan 2 Condenser Fan 1 Condenser Fan 3 Clutch Evaporator Blower 3 Evaporator Blower 4 Evaporator Blower 1 Evaporator Blower 2 Evaporator Blower 5 Evaporator Blower 6 Condenser Fan 5 Condenser Fan 4 TYPE 15A 15A 15A 10A 15A 15A 15A 15A 15A 15A 15A 15A 23 Aerosphere Midibus 7.2 Relay Board 1101742A (GL-W134) Connections CN9 CN8 CN1 CN5 CN6 CN7 CN3 GL-W134 CN4 CN1 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. +24Vdc After Ignition + Ext. Relay Serial Data Com. 1 Serial Data Com. 2 Duct Temperature Sensor Internal Temperature Sensor Command Blower Med. Speed +24Vdc After Ignition + Ext. Relay GND N.C. Duct Temperature Sensor Internal Temperature Sensor External Temperature Sensor Note: CN3 Communicates with the GL-W004 Heating Module CN3 1. 2. 3. 4. 5. 6. 7. 8. 9. CN4 Command Blower LO Command Clutch Address Relay Board Command Blower MED Command Fan Serial Data Com. 3 (GL-W004) Command Blower HI GND Command Fresh Air CN7 1. 2. 3. 4. 5. 6. 7. 8. 9. CN10 +24Vdc Blower 1 N.C. +24Vdc Blower 2 Blower 1 HI Blower 1 LO Blower 1 MED Blower 2 HI Blower 2 LO Blower 2 MED 1. 2. 3. 4. 5. 6. 7. 8. 9. Condenser Fan 3 N.C. N.C. Condenser Fan 1 N.C. Condenser Fan 4 Condenser Fan 2 N.C. Condenser Fan 5 1. 2. 3. 4. 5. 6. 7. 8. 9. CN10 1. 2. 3. 4. 5. 6. 7. 8. 9. +24Vdc Blower 5 N.C +24Vdc Blower 6 Blower 5 HI Blower 5 LO Blower 5 MED Blower 6 HI Blower 6 LO Blower 6 MED CN6 CN5 Pressure Switches Ice Sensor Clutch +24Vdc Direct Battery Ice Sensor Pressure Switches +24Vdc After Ignition GND N.C. 1. 2. 3. 4. 5. 6. 7. 8. 9. CN8 1. 2. 3. 4. 5. Connection for Fresh Air Module GL-D012 +24Vdc Blower 3 N.C. +24Vdc Blower 4 Blower 3 HI Blower 3 LO Blower 3 MED Blower 4 HI Blower 4 LO Blower 4 MED CN9 1. 2. Fresh Air Motor Fresh Air Motor 24 Aerosphere Midibus 7.3 Relay Board 1101742A (GL-W134) Function LED’s LED CD CL EL EM EH FUNCTION CONDENSER FAN CLUTCH EVAPORATOR BLOWER LOW EVAPORATOR BLOWER MEDIUM EVAPORATOR BLOWER HIGH COLOR GREEN GREEN GREEN GREEN GREEN OPERATION ON WHEN OPERATING ON WHEN OPERATING ON WHEN OPERATING ON WHEN OPERATING ON WHEN OPERATING RELAY 1, 2, 13 3 5, 9, 10 6, 8, 11 4, 7, 12 GL-W134 LED RUN TX RX COLOR RED RED RED OPERATION SEE RUN TABLE BLINKING –TRANSMITTING DATA TO DASH CONTROL BLINKING – RECEIVING DATA FROM DASH CONTROL O ☼ ☼ ● RUN TABLE CPU NOT WORKING 1HZ: NORMAL OPERATION 3HZ: SYSTEM FAIL CPU NOT WORKING 25 Aerosphere Midibus 7.4 Electrical Schematic for Digital Dash Control (GL-W111) to Relay Board GL-W134 CN2 CN2 1. 2. 3. 4. 5. 6. 7. 8. 9. Serial Data Com 1 GND Convector Monitor. Input Serial Data Com 2 N.C. Air Flow Barrier (Optional) +24 VDC After Ignition Engine Increase RPM (Optional) N.C. CN1 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. +24Vdc After Ignition + Ext. Relay Serial Data Com. 1 Serial Data Com. 2 Duct Temperature Sensor Internal Temperature Sensor Command Blower Med. Speed +24Vdc After Ignition + Ext. Relay GND N.C. Duct Temperature Sensor Internal Temperature Sensor External Temperature Sensor 26 Aerosphere Midibus