CSI 16261 - Static Uninterruptible Power Supply Systems Liebert UPStation GXT UPS GUIDE SPECIFICATIONS 6,000 and 10,000 VA Single - Phase Uninterruptible Power Supply System 1.0 1.1 GENERAL SUMMARY This specification defines the electrical and mechanical characteristics and requirements for a continuous-duty single-phase, solid-state, uninterruptible power system. The uninterruptible power system, hereafter referred to as the UPS, shall provide high-quality AC power for sensitive electronic equipment loads. 1.2 STANDARDS The UPS shall be designed in accordance with the applicable sections of the current revision of the following documents. Where a conflict arises between these documents and statements made herein, the statements in this specification shall govern. 208V and 240V Units UL 1778 FCC Part 15, Class A C-UL (to CSA 22.2 No. 107.1) National Electrical Code (NFPA 70) IEC 801-2, Level 4 IEC 801-3, Level 3 IEC 801-4, Level 4 IEEEc62.41 ISTA Procedure 1B 230V Units EN 50091-1 CE compliance mark, For both Low Voltage and EMC Directives TUV/GS Listed EN 55022, Class A EMC- EN50091-2 (Incorporating) IEC 801-2, Level 4 IEC 801-3, Level 3 IEC 801-4, Level 4 IEC 801-5, Level 3 ISTA Procedure 1B Liebert GXT UPS 6,000/10,000 VA 1 Guide Specification SLI-23145 (10/ 99) Rev. 6 1.3. SYSTEM DESCRIPTION 1.3.1 Modes of Operation The UPS shall be designed to operate as a true on-line system in the following modes: A. Normal - The critical AC load is continuously supplied by the UPS inverter. The input converter derives power from a utility / mains AC source and supplies DC power to the inverter. The battery charger shall maintain a float-charge on the battery. B. Battery - Upon failure of utility / mains AC power, the critical AC load is supplied by the inverter, which obtains power from the battery. There shall be no interruption in power to the critical load upon failure or restoration of the utility / mains AC source. C. Recharge - Upon restoration of utility / mains AC power, after a utility / mains AC power outage, the input converter shall automatically restart and assume supplying power to the inverter; and the battery charger shall recharge the battery. D. Automatic Restart - Upon restoration of utility / mains AC power, after a utility / mains AC power outage and complete battery discharge, the UPS shall automatically restart and assume supplying power to the critical load; and the battery charger shall automatically recharge the battery. E. Bypass - The integral bypass shall be a static make-before-break type, and perform an automatic transfer of the critical AC load from the inverter to the bypass source, in the event of overload, over temperature, or internal fault conditions. The UPS shall perform an automatic retransfer of the critical AC load from the bypass source to the inverter, upon return to nominal ratings from overload or over temperature condition. The UPS shall include provisions to allow for manual activation of the bypass by the user. 1.3.2 Design Requirements A. Voltage: Nominal input/output specifications of the UPS shall be: Input: The UPS shall accept the following voltages without damage: 0 - 320 VAC, 50/60 Hz, single-phase, 2-wire-plus- ground. Output: 230 VAC +3%, 50/60 Hz, single-phase, 2-wire-plus-ground, switch selectable (208V, 220V, 230V, 240V); with optional internal isolation transformers for 230V L-N or 208/120V or 240/120V applications. B. Output Load Capacity: Specified output load capacity of the UPS at 0.7 lagging power factor shall be: Liebert GXT UPS 6,000/10,000 VA 2 Guide Specification SLI-23145 (10/ 99) Rev. 6 MODEL Output Voltage Output Capacity GXT10000T 220/230/240 or 220/110, 230/115, 240/120 10 kVA/7kW GXT10000T 208 or 208/120 9 kVA/6.3kW GXT6000T 220/230/240 or 220/110, 230/115, 240/120 6 kVA/4.2kW GXT6000T 208 or 208/120 5.4 kVA/3.8kW C. Internal Battery: The battery shall consist of valve regulated, non-spillable, lead acid cells. D. Reserve Time: Minimum 10 minutes for 10kVA units and minimum 7 minutes for 6kVA units, at full resistive load with ambient temperature 25°C (77°F). E. Battery Recharge: The UPS shall contain a battery recharge rate designed to prolong battery life. Recharge time shall be seven (7) hours maximum to 95% capacity after a complete discharge into full load. 1.3.3 Performance Requirements 1.3.3.1 AC Input to UPS A. Voltage Configuration: The UPS shall operate at these values (+5VAC) without drawing power from the batteries. 230 VAC nominal; single phase, 2 wire plus ground; variable based upon output loading: LOAD 6000/10000 VA MODELS 100 - 90% 186 VAC to 280 VAC 90 - 70% 159 VAC to 280 VAC 70 - 30% 139 VAC to 280 VAC 30 - 0% 119 VAC to 280 VAC B. Frequency: UPS auto senses input frequency and will operate within the following frequency specifications without drawing power from the batteries. 50 Hz Applications: 46.6 – 52.4 Hz 60 Hz Applications: 57.1 – 62.9 Hz Liebert GXT UPS 6,000/10,000 VA 3 Guide Specification SLI-23145 (10/ 99) Rev. 6 C. Input Power Factor: 0.98 lagging minimum at rated load and nominal input voltage. D. Surge Protection: The UPS units shall sustain input surge without damage per criteria listed in IEEEc62.41 for 208V and 240V units, and IEC 801 - 5, Level 3 for 230V units. E. Input Current Distortion (THD): <15% THD at rated load at nominal input voltage. 1.3.3.2 AC Output, UPS Inverter A. Voltage Configuration: 230 VAC nominal, 50/60 Hz, single-phase, 2-wire-plus-ground, switch selectable (208V, 220V, 230V, 240V); with optional internal isolation transformers and appropriate output terminal blocks for 230V L-N or 208/120V or 240/120V applications. B. Voltage Regulation: + 3% steady state, +7% steady state with optional transformer. C. Frequency Regulation: 50Hz Nominal: -7%/+5% Synchronized to mains. 60Hz Nominal: + 5% Synchronized to utility. + 0.1 Hz free running or on battery operation. D. Frequency Slew Rate: 1.0 Hz per second maximum. E. Voltage Distortion: Without optional transformer: <4% total harmonic distortion (THD) typical into a 100% linear load, <7% THD typical into a 100% nonlinear load with crest factor ratio of 3:1. With optional transformer: <5% total harmonic distortion (THD) typical into a 100% linear load, <8% THD typical into a 100% nonlinear load with crest factor ratio of 3:1. F. Load Power Factor Range: 0.65 lagging to 1.0 (unity). G. Output Power Rating: Rated VA at 0.7 lagging power factor. H. Inverter Overload Capability: 112 - 130% of full load for 10 seconds, 131 - 200% of full load for 8 cycles. Automatic transfer to bypass shall occur if these parameters are exceeded. I. Voltage Transient Response: + 11% maximum in line mode, + 15% maximum in battery mode for any load step up to and including 100% of the UPS rating. J. Transient Recovery Time: To steady state output voltage within 90 milliseconds. Liebert GXT UPS 6,000/10,000 VA 4 Guide Specification SLI-23145 (10/ 99) Rev. 6 1.4 ENVIRONMENTAL CONDITIONS A. Ambient Temperature Operating: 0O C to +40O C (+32O F to +104O F) for altitudes 0 to 1500 meters (0 to 5,000 ft.) above sea level 0O C to +35O C (+32O F to +95O F) for altitudes 1500 to 3000 meters (5,000 to 10,000 ft.) above sea level 25O C (+ 77O F) for optimum battery performance Storage: -15O C to +50O C (+ 5O F to +122O F) 20O C (+ 68O F) for optimum battery storage. B. Relative Humidity Operating: 0 to 95% non-condensing. Storage: 0 to 95% non-condensing. C. Altitude: 3,000 m (10,000 ft. max.), without power derating when operated within the temperature specified in section 1.4.A. D. Audible Noise Noise generated by the UPS under any condition of normal operation shall not exceed 55dB for 6kVA units, and 65dB for 10kVA units; when measured at 1 meter from the surface of the UPS, “A” weighted. E. Electrostatic Discharge The UPS shall be able to withstand an electrostatic discharge compliant to IEC 801- 2, level 4 (15 kV through air, 8 kV contact) without damage and shall not affect the connected load. 1.5 USER DOCUMENTATION The specified UPS system shall be supplied with one (1) user's manual. Manuals shall include installation drawings and instructions, a functional description of the equipment with block diagrams, safety precautions, illustrations, step by step operating procedures, and general maintenance guidelines. 1.6 WARRANTY The UPS manufacturer shall warrant the UPS against defects in materials and workmanship for two (2) years. The warranty shall cover all parts and in-factory labor. Optional full coverage on site maintenance contracts and optional full coverage on site extended maintenance contracts shall be available from Liebert Corporation. Liebert GXT UPS 6,000/10,000 VA 5 Guide Specification SLI-23145 (10/ 99) Rev. 6 1.7 QUALITY ASSURANCE 1.7.1 Manufacturer Qualifications A minimum of twenty year's experience in the design, manufacture, and testing of solid-state UPS systems is required. The manufacturer shall be certified to ISO 9001. 1.7.2 Factory Testing Before shipment, the system shall be fully and completely tested to assure compliance with the specification. These tests shall include operational discharge and recharge tests on the internal battery to assure performance. 2.0 PRODUCT 2.1 FABRICATION All materials and components making up the UPS shall be new, of current manufacture, and shall not have been in prior service except as required during factory testing. The UPS shall be constructed of replaceable subassemblies. All relays shall be provided with dust covers. 2.1.2 Wiring Wiring practices, materials, and coding shall be in accordance with the requirements the standards listed in section 1.2 and other applicable codes and standards. All wiring shall be copper. 2.1.3 Cabinet The UPS unit comprised of: input rectifier, battery charger, inverter, and battery consisting of the appropriate number of sealed battery cells; shall be housed in a NEMA type 1 enclosure and meet the requirements of IP20. The UPS cabinet shall be cleaned, primed, and painted with the manufacturer's standard color. Dimensions and weight shall be: MODEL GXT6000T-230 GXT6000T-230X GXT6000T-240X GXT6000T-208X Liebert GXT UPS 6,000/10,000 VA DIMENSIONS (W x D x H) 260mm x 558mm x 800mm (10.3” x 22.0” x 31.5”) 260mm x 558mm x 800mm (10.3” x 22.0” x 31.5”) 260mm x 558mm x 800mm (10.3” x 22.0” x 31.5”) 260mm x 558mm x 800mm (10.3” x 22.0” x 31.5”) 6 WEIGHT 99kg (218lbs.) 139kg (306lbs.) 139kg (306lbs.) 142kg (313lbs.) Guide Specification SLI-23145 (10/ 99) Rev. 6 GXT6000T-208 GXT10000T-230 GXT10000T-230X GXT10000T-240X GXT10000T-208X GXT10000T-208 2.1.4 260mm x 558mm x 800mm (10.3” x 22.0” x 31.5”) 340mm x 640mm x 965mm (13.4” x 25.3” x 38.0”) 340mm x 640mm x 965mm (13.4” x 25.3” x 38.0”) 340mm x 640mm x 965mm (13.4” x 25.3” x 38.0”) 340mm x 640mm x 965mm (13.4” x 25.3” x 38.0”) 340mm x 640mm x 965mm (13.4” x 25.3” x 38.0”) 99kg (218lbs.) 187kg (412lbs.) 244kg (538lbs.) 244kg (538lbs.) 247kg (544lbs.) 187kg (412lbs.) Cooling The UPS shall be forced air cooled by internally mounted, two-speed fans. Fan power shall be provided from the internal DC supply. Air intake shall be through the front of the unit and exhausted out the rear. 2.2 COMPONENTS 2.2.1 Input Converter 2.2.1.1 General Incoming AC power shall be converted to a regulated DC output by the input converter for supplying DC power to the inverter. The input converter shall provide input power factor correction and input current distortion reduction. 2.2.1.2 AC Input Current Limit The input converter shall be provided with AC input current limiting whereby the maximum input current shall be limited to 125% of the full load input current rating. 2.2.1.3 Input Protection The UPS shall have built-in protection against undervoltage, overcurrent, and overvoltage conditions including low-energy lightning surges, introduced on the primary AC source. The UPS shall sustain input surges without damage per criteria listed in IEC 801 - 05, Level 3. Additionally, the UPS clamping voltage shall be 320V peak and energy dissipation shall be 80 joules, for 2 milliseconds. The UPS shall have input circuit protectors. Liebert GXT UPS 6,000/10,000 VA 7 Guide Specification SLI-23145 (10/ 99) Rev. 6 2.2.1.4 Battery Recharge The UPS shall contain a battery recharge rate designed to prolong battery life. The battery shall be constant current charged to restore capacity, and then shall be constant voltage charged to maintain the battery in a fully charged state. Recharge time shall be seven (7) hours maximum to 95% capacity. There shall be DC overvoltage protection so that if the DC voltage exceeds the pre-set limit, the UPS shall shutdown automatically and the critical load shall be transferred to bypass. 2.2.2 Inverter 2.2.2.1 General The UPS inverter shall be a pulse-width-modulated (PWM) design capable of providing the specified AC output. The inverter shall convert DC power from the input converter output, or the battery, into precise sine wave AC power for supporting the critical AC load. 2.2.2.2 Overload The inverter shall be capable of supplying current and voltage for overloads exceeding 100% and up to 200% of full load current. A visual indicator and audible alarm shall indicate overload operation. For greater currents or longer time duration, the inverter shall have electronic current-limiting protection to prevent damage to components. The inverter shall be self-protecting against any magnitude of connected output overload. Inverter control logic shall sense and disconnect the inverter from the critical AC load without the requirement to clear protective fuses. 2.2.2.3 Inverter DC Protection The inverter shall be protected by the following DC shutdown levels: DC Overvoltage Shutdown DC Undervoltage Shutdown (End of Discharge) DC Undervoltage Warning (Low Battery Reserve); factory set at 2 minutes 2.2.2.4 Output Frequency The output frequency of the inverter shall be controlled by an oscillator. The oscillator shall maintain the inverter output frequency to + 0.1 Hz of nominal when not synchronized to the utility/mains source. 2.2.2.5 Output Protection The UPS inverter shall employ electronic current limiting and an output circuit protector. Liebert GXT UPS 6,000/10,000 VA 8 Guide Specification SLI-23145 (10/ 99) Rev. 6 2.2.2.6 Battery Over Discharge Protection To prevent battery damage from over discharging and extend battery life, the UPS control logic shall automatically raise the shutdown voltage set point; dependent upon output load at the onset of battery operation. 2.2.3 Display and Controls 2.2.3.1 General The UPS shall be provided with a microprocessor-based unit status display and controls section designed for convenient and reliable user operation. The monitoring functions such as status and alarm indicators shall be displayed on an LED display. 2.2.3.2 System Indicators The UPS shall contain a row of LED's to indicate UPS load and battery capacity and five single LED's to indicate UPS status as described below: The "Fault" indicator shall illuminate red to indicate a UPS fault condition. The "Battery" indicator shall illuminate amber to indicate the UPS is operating from battery power. The "Bypass" indicator shall illuminate amber to indicate the UPS is operating on Bypass power. An audible alarm shall be provided and activated be any of the above alarm conditions. The "UPS ON" indicator shall illuminate green to indicate the UPS inverter is operating and supplying power. The "AC Input" indicator shall illuminate green to indicate the UPS is operating from utility / mains power. 2.2.3.3 Controls UPS start-up and shutdown operations shall be accomplished by the "On" and "Off" push buttons located on the front panel of the UPS. The "On" push button shall be a means to turn the UPS on and shall also serve as a means to manually test the battery, to reset active visual and audible alarms, and to allow manual transfers of the load from bypass power to the UPS inverter. The "Off" push button shall allow manual transfers of the load from the inverter to bypass power. Pressing the "Off" push button twice within a four second time period shall completely shutdown the UPS and its connected load. 2.2.4 On-Line Battery Test The UPS shall be provided with an automatic biweekly battery test feature. The test shall ensure the capability of the battery to supply power to the inverter while loaded. If the battery fails the test, the UPS shall display a warning message to indicate the batteries need replaced. The battery test feature shall be user accessible by the push button located on the front of the unit and with optional Liebert Power Surveillance software. Liebert GXT UPS 6,000/10,000 VA 9 Guide Specification SLI-23145 (10/ 99) Rev. 6 2.2.5 Bypass 2.2.5.1 General A static make-before-break type bypass circuit shall be provided as an integral part of the UPS. The bypass control logic shall contain an automatic transfer control circuit that senses the status of the inverter logic signals, and operating and alarm conditions. This control circuit shall provide a transfer of the load to the bypass source, without exceeding the transient limits specified herein, when a malfunction occurs within the UPS. 2.2.5.2 Automatic Transfers The transfer control logic shall automatically activate the bypass, transferring the critical AC load to the bypass source, after the transfer logic senses one of the following conditions: UPS overload UPS over temperature Internal Fault condition Once overload condition is reduced, the load shall be automatically transferred back to inverter power. 2.2.6 Internal Battery Valve regulated, non-spillable, lead acid cells shall be used as a stored-energy source for the specified UPS system. The battery shall be housed internal to the UPS cabinet and sized to support the inverter at rated load and power factor, with ambient temperature of 25O C (77O F); for a minimum of 7 minutes reserve time for 6kVA units, and a minimum of 10 minutes reserve time for 10kVA units. The expected life of the battery shall be 3 - 5 years or a minimum 250 complete discharge cycles. The battery shall be capable of being replaced by trained Liebert-authorized engineers. 2.2.7. Output Distribution 2.2.7.1 General Output distribution shall be via a compression-lug terminal block, located on the rear of the unit; using customer supplied wiring in accordance with national and local electric codes. 2.2.7.2 Optional Transformer Configurations Units with a suffix containing an “X” shall contain internal isolation transformers (xfmr) and shall be configured as follows: Models with a –230X suffix shall contain an isolation xfmr and shall have a 3 pole output terminal block labeled L, N, E; for 220/230/240V applications. Liebert GXT UPS 6,000/10,000 VA 10 Guide Specification SLI-23145 (10/ 99) Rev. 6 Models with a –240X suffix shall contain an isolation xfmr and shall have a 4 pole output terminal block labeled L1, L2, N, G; for 220/110, 230/115, or 240/120V applications. Models with a –208X suffix shall contain an isolation xfmr and shall have a 5 pole output terminal block labeled L1, L2, L2A, N, G; for 208/120Vapplications. 2.2.8 Communications The UPS shall contain a DB9 socket on the rear panel to allow UPS status communications to a computer system. The DB9 shall contain photo couplers to signal on battery and low battery operational status. The UPS shall also be capable of receiving a signal from the connected host system to initiate a UPS shutdown. This signal shall be a +5 V to +12 V (RS232 level) that must remain for > 1.6 second duration. Additionally, it shall also communicate via serial communications using Liebert ESP II protocol. Communications protocol shall be Liebert ESP II, level 1 compliant; with the following exceptions: Liebert ESP II, level 1 items not supported: - Input amperes - Battery amperes - Minutes - Hours - Date - Month - Input Undervoltage Startup fail - Seconds - Day of Week - Year The pin out configuration of the DB9F connector shall be: Pin 1 2 3 4 5 6 7 8 9 Assignment Description Low Battery (Open Collector: +V) UPS TxD UPS RxD Remote Shutdown (5-12V DC,1.0 mA max.); on battery operation Common Remote shutdown (Short to Pin 5); any mode operation Low Battery (Open Emitter: -V) Utility / mains Fail (Open Emitter: -V) Utility/Mains Fail (Open Collector; +V) Maximum voltage and current on pins 1, 7, 8, 9 shall be 80 VDC, 10.0 mA maximum. 2.2.9 Optional Communications The UPS shall contain one communication slot (IntellislotTM) to allow the operator to field install one optional communication card. The IntellislotTM shall be designed to provide simple installation where electrical connections are made via a 26-pin edge card connector. Separate cards shall allow the UPS to communicate via either Ethernet SNMP, connected directly to the LAN; or AS/400 (dry-contact) communications. Once the SNMP card is installed, the serial communications shall be disabled in the DB9 socket; however the photo- Liebert GXT UPS 6,000/10,000 VA 11 Guide Specification SLI-23145 (10/ 99) Rev. 6 coupler signals (on battery, and low battery) shall remain active. The AS/400 option shall contain contact closures rated for 1A at 24VDC/120VAC for the following conditions: -Line Loss -Low Battery -On Bypass -UPS Failure -Summary Alarm 2.2.10 Optional External Battery Cabinet The UPS shall allow extended battery run time capability, through a terminal block located on the rear panel to allow for connection of external battery cabinet(s). The battery cabinet(s) shall be used in parallel with the internal battery for extended power outage reserve time. Each battery cabinet shall contain valve regulated, non-spillable, lead acid cells, housed in a separate cabinet that matches the UPS cabinet styling. Each external battery cabinet shall contain a 6-pole terminal block to allow for connection to the UPS and for paralleling additional battery cabinets. The terminal block contacts shall be labeled “positive (+)”, “negative (-)”, and “ground (earth)”. For connection to the UPS, the end user will supply their own cable between the UPS and battery cabinets in accordance with national and local electric codes. Each battery cabinet shall contain a circuit breaker to provide individual cabinet overcurrent protection and isolation. The external battery cabinet(s) shall increase power outage reserve time when operating with ambient temperature of 25OC (77O F). NOTE: These Guide Specifications comply with the format outlined by the Construction Specifications Institute per CSI MP-2-1 and CSI MP-2- 2. Liebert GXT UPS 6,000/10,000 VA 12 Guide Specification SLI-23145 (10/ 99) Rev. 6