25.5 25 Molded Case Circuit Breakers Specialty Breakers Contents Engine Generator Circuit Breakers Description 25 Page Engine Generator Circuit Breakers Catalog Number Selection . . . . . . . . . . . . . . . . Product Selection . . . . . . . . . . . . . . . . . . . . . . . Accessories Selection Guide and Ordering Information . . . . . . . . . . . . . . . . . . . Options and Accessories . . . . . . . . . . . . . . . . . Technical Data and Specifications . . . . . . . . . . . Dimensions and Weights . . . . . . . . . . . . . . . . . Direct Current Circuit Breakers . . . . . . . . . . . . . . . E2 Mining Service Circuit Breakers . . . . . . . . . . . . Classic Mining Breakers. . . . . . . . . . . . . . . . . . . . . Add-On Ground Fault Protection—Type GFR . . . . . 25 25 25 25 25 25 Learn Online 25 V4-T25-505 V4-T25-506 V4-T25-508 V4-T25-508 V4-T25-509 V4-T25-509 V4-T25-510 V4-T25-521 V4-T25-544 V4-T25-558 Drawings Online 25 25 Engine Generator Circuit Breakers 25 Product Description Application Description Standards and Certifications Eaton’s engine generator molded case circuit breakers are designed specifically for application on diesel engine powered standby generators where high interrupting circuit breakers are not required. The JG through NG breakers are equipped with a special trip unit, that includes standard thermal (overload) protection and special low magnetic pickup range (FG includes a fixed thermalmagnetic pickup). The standard thermal trip unit provides overload protection for conductors per the National Electrical Code®. The low magnetic pickup range is approximately two to five times the continuous rating and provides closer low-level short-circuit protection when applied on generators that have very low short-circuit capacity. This combination allows the user to customize the breaker to the generator output. Engine generator circuit breakers are suitable for reverse feed application. Engine generator molded case circuit breakers are designed to conform with the following standards: 25 25 25 25 25 25 25 25 25 25 25 25 25 ● ● ● Underwriters Laboratories Standard UL 489, Molded Case Circuit Breakers and Circuit Breaker Enclosures File E7819 Canadian Standards Association Standard C22.2 No. 5, Service Entrance and Branch Circuit Breakers International Electrotechnical Commission Recommendations IEC 947-2, Circuit Breakers Conformance with these standards satisfies most local and international codes, assuming user acceptability and simplified application. 25 25 25 25 25 V4-T25-504 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 Molded Case Circuit Breakers Specialty Breakers 25.5 Catalog Number Selection This information is presented only as an aid to understanding catalog numbers. It is not to be used to build catalog numbers for circuit breakers. ● FG breakers include both line and load side terminals ● ● JG, KG, LG and NG breakers with W catalog number suffix do not include any terminals JG, KG, LG and NG breakers without W catalog number suffix include both line and load terminals ● ● 25 Contact Eaton for additional ratings and internal/external accessories Reverse feed 25 25 25 25 Circuit Breakers FG, JG, KG, LG and NG 25 FG 3 100 W Frame FG Number of Poles 3 = Three-pole Trip Amperes 015 020 025 030 035 040 045 050 060 070 080 090 100 125 150 175 200 225 25 25 Suffix W = Without terminals 25 25 25 25 25 25 25 JG 175 200 225 250 25 300 350 400 25 25 KG LG 25 450 500 600 25 NG 700 800 900 1000 1200 25 25 25 25 25 25 25 25 25 25 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com V4-T25-505 For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 25.5 25 25 25 Molded Case Circuit Breakers Specialty Breakers Product Selection The following table lists FG through NG engine generator breakers with the maximum generator kVA and kW rating. Engine generator breakers are applied at 115% of the generator full load current rating (FLA). The maximum kW rating is based on threephase generators at 80% power factor. 25 25 Thermal-Magnetic 25 Engine Generator Breaker Magnetic Pickup Range Maximum Generator Rating 60 Hz 240 Vac kVA kW 480 Vac kVA kW 600 Vac kVA kW Catalog Number Fixed 5 4 11 9 14 11 FG3015 Fixed 7 6 14 12 18 14 FG3020 Fixed 9 7 18 14 23 18 FG3025 Fixed 11 9 22 17 27 22 FG3030 25 Fixed 13 10 25 20 32 25 FG3035 Fixed 14 12 29 23 36 29 FG3040 25 Fixed 16 13 32 26 41 32 FG3045 Fixed 18 14 36 29 45 36 FG3050 Fixed 22 17 43 35 54 43 FG3060 Fixed 25 20 51 40 63 51 FG3070 Fixed 29 23 58 46 72 58 FG3080 25 Fixed 32 26 65 52 81 65 FG3090 Fixed 36 29 72 58 90 72 FG3100 25 Fixed 40 32 79 64 99 79 FG3110 Fixed 45 36 90 72 113 90 FG3125 Fixed 54 43 108 87 135 108 FG3150 25 Fixed 63 51 126 101 158 126 FG3175 Fixed 72 58 144 116 181 144 FG3200 25 Fixed 81 65 162 130 203 162 FG3225 350–700 63 51 126 101 158 126 JG3175W 350–700 63 51 126 101 158 126 JG3175 350–700 72 58 144 116 181 144 JG3200W 350–700 72 58 144 116 181 144 JG3200 25 350–700 81 65 162 130 203 162 JG3225W 350–700 81 65 162 130 203 162 JG3225 25 350–700 90 72 181 144 226 181 JG3250W 350–700 90 72 181 144 226 181 JG3250 500–1000 108 87 217 173 271 217 KG3300W 500–1000 108 87 217 173 271 217 KG3300 500–1000 126 101 253 202 316 253 KG3350W 500–1000 126 101 253 202 316 253 KG3350 1000–2000 144 116 289 231 361 289 KG3400 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 Notes Breaker continuous current is based on 115% of the generator full load ampere rating. Based on three-phase generators at 80% power factor. FG, JG, KG include thermal-magnetic trip units, LG and NG include electronic trip units. Breaker includes line and load terminals. Without terminals. The following catalog numbers have center tap studs for dual voltage applications: JG3070CT, JG3100CT, JG3125CT, KG3175CT, LG3300CTW. 25 V4-T25-506 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 Molded Case Circuit Breakers Specialty Breakers 25.5 Electronic Engine Generator Breaker Maximum Generator Rating 60 Hz Magnetic Pickup Range 240 Vac kVA kW kVA 480 Vac kW kVA 600 Vac kW Catalog Number 500–2500 162 130 325 260 406 325 LG3450 25 25 25 500–2500 181 144 361 289 451 361 LG3500 500–2500 217 173 433 347 542 433 LG3600 500–2500 253 202 505 404 632 505 NG3700 500–2500 289 231 578 462 722 578 NG3800 1250–5000 325 260 650 520 812 650 NG3900 1250–5000 361 289 722 578 903 722 NG31000 1250–5000 433 347 867 693 1083 867 NG31200 25 25 25 25 25 Notes Breaker continuous current is based on 115% of the generator full load ampere rating. Based on three-phase generators at 80% power factor. FG, JG, KG include thermal-magnetic trip units, LG and NG include electronic trip units. Breaker includes line and load terminals. 25 25 The following catalog numbers have center tap studs for dual voltage applications: JG3070CT, JG3100CT, JG3125CT, KG3175CT, LG3300CTW. 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com V4-T25-507 For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 25.5 25 25 Options and Accessories Enclosures Type 1 General Purpose Standard Terminals 25 25 ● 25 25 25 25 25 25 25 25 ● Type 3R Rainproof Surface Mounting 25 ● 25 25 25 Surface or flush mounting 15–1200 ampere range 600 Vac, 500 Vdc Type 1 enclosed breakers are designed for use in commercial buildings, apartment buildings and other areas where a general purpose enclosure is applicable. The breaker is front operable and is capable of being padlocked in either the ON or OFF position. Ratings through 1200 amperes are listed with Underwriters Laboratories as approved for service entrance application. Both surface and flush mounted enclosures are available. ● 25 Specialty Breakers Accessories Selection Guide and Ordering Information ● 25 Molded Case Circuit Breakers ● Interchangeable hubs (through 400 amperes) 15–1200 ampere range 600 Vac, 500 Vdc This general purpose outdoor service center employs a circuit breaker inside a weatherproof sheet steel breaker enclosure to serve as a main disconnect and protective device for feeder circuits. Ratings through 1200 amperes are listed by Underwriters Laboratories as suitable for service entrance application. Breaker Frame Max. Amp Rating AWG Wire Range FG 100 FG 150 JG Type 12 Dustproof Surface Mounting ● ● ● No knockouts or other openings 15–1200 ampere range 600 Vac, 500 Vdc The Type 12 enclosure is designed in line with specifications for special industry applications where unusually severe conditions involving oil, coolant, dust and other foreign materials exist in the operating atmosphere. The handle padlocks in the OFF position and the cover is interlocked with the handle mechanism to prevent opening the cover with the circuit breaker in the ON position. Ratings through 1200 amperes are listed by Underwriters Laboratories as suitable for service entrance application. Metric Wire Range mm2 Catalog Number 14–1/0 2.5–50 3T100FB 4–4/0 25–95 3TA225FD 250 4–350 kcmil 25–185 TA250KB KG 350 250–500 kcmil 120–240 TA350K KG 400 3/0–250 kcmil (2) 95–120 3TA400K LG 600 250–500 kcmil (2) 120–240 3TA603LDK NG 700 1–500 kcmil (2) 50–300 TA700NB1 NG 1000 3/0–400 kcmil (3) 95–185 TA1000NB1 NG 1200 4/0–500 kcmil (4) 120–300 TA1200NB1 Neutral Kits, Insulated and Groundable Max. Enclosure Rating (Amperes) Main Lug Number Size Cu/Al Ground Lug Size Cu/Al Catalog Number 100 (1) 14–1/0 (1) 14–1/0 INK100 250 (1) 6–350 kcmil (1) 4–300 kcmil INK250 400 (1) 4–750 kcmil or (2) 1/0–250 kcmil (1) 4–300 kcmil INK400 600 (2) 250–500 kcmil (1) 4–300 kcmil INK600 1200 (3) 1/0 to 750 kcmil or (4) 1/0 to 750 kcmil (1) 6–250 kcmil INK1200 Internal Accessories Auxiliary Switch Breaker Frame Factory Mounted 1A-1B Field Kit Catalog Number Factory Mounted 2A-2B Field Kit Catalog Number FG A06 A1X1PK A13 A2X1RPK Enclosure Selection Data JG A06 A1X2PK A13 A2X2PK KG A06 A1X3PK A13 A2X3PK 25 Breaker Frame Amperes LG A06 A1X4PK A13 A2X4PK FG 15–225 NG A06 A1X5PK A13 A2X5PK 25 25 25 25 25 JG 175–250 KG 300–400 25 25 LG 450–600 25 25 NG 700–1200 25 Enclosure Type Class Catalog Number Type 1 SFDN225 Type 3R RFDN225 Type 12 JFDN225 Type 1 SJDN250 Type 3R RJDN250 Type 12 JJDN250 Type 1 SKDN400 Type 3R RKDN400 Type 12 JKDN400 Type 1 SLDN600 Type 3R RLDN600 Type 12 JLDN600 Type 1 SNDN1200 Type 3R RNDN1200 Type 12 JNDN1200 Shunt Trip Breaker Frame Rating Factory Mounted Field Kit Catalog Number FG 12–24 Vdc S02 SNT1LP03K JG 12–24 Vdc S42 SNT2P04K KG 12–24 Vdc S42 SNT3P04K LG 12–24 Vdc S02 SNT4LP03K NG 12–24 Vdc S02 SNT5LP03K Notes Package of three terminals. Other accessories are available. Same as standard frame breakers. Field installation on the FG Frame is not UL listed. 25 V4-T25-508 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 Molded Case Circuit Breakers Specialty Breakers 25.5 Technical Data and Specifications 25 25 UL 489 Interrupting Capacity Ratings Volts AC (50/60 Hz) Interrupting Capacity (Symmetrical Amperes) 240 18,000 480 14,000 600 10,000 25 25 25 IEC 947-2 Interrupting Capacity Ratings Volts AC (50/60 Hz) Interrupting Capacity (Symmetrical Amperes) 220, 240 18,000/ 9,000 380, 415 14,000/ 7,000 660, 690 18,000/ 9,000 14,000/ 7,000 10,000/5,000 25 25 25 25 25 Dimensions and Weights Approximate Dimensions in Inches (mm) 25 Enclosure Selection Data 25 Breaker Frame Amperes Enclosure Type Class A B C D E Approx. Weight Lbs (kg) Conduit Sizes, Inches FG 15–225 Type 1 23.25 (590.6) 8.41 (213.6) 6.28 (159.5) 18.75 (476.3) 1.20 (30.5) 15 (7) 0.25, 0.50, 0.75, 1, 1.25, 1.50, 2, 2.50 SFDN225 Type 3R 25.66 (651.8) 8.84 (224.7) 9.31 (236.5) 24.28 (616.7) 1.70 (43.2) 19 (9) 0.25, 0.50, 0.75, 1, 1.25, 1.50, 2, 2.50 RFDN225 Type 12 25.66 (651.8) 8.84 (224.7) 9.31 (236.5) 24.28 (616.7) 1.70 (43.2) 18 (8) — JFDN225 JG 175–250 Type 1 34.70 (881.4) 10.92 (277.4) 7.20 (182.9) 30.00 (762.0) 1.88 (47.8) 31 (14) 0.25, 0.50, 2, 2.50, 3 SJDN250 Type 3R 37.50 (952.5) 11.56 (293.6) 10.22 (259.6) 35.77 (908.6) 1.94 (49.3) 40 (18) 0.25, 0.50, 2, 2.50, 3 RJDN250 Type 12 37.53 (953.3) 11.56 (293.6) 10.22 (259.6) 35.77 (908.6) 1.94 (49.3) 37 (17) — JJDN250 KG 300–400 Type 1 38.81 (985.8) 11.06 (280.9) 10.94 (277.9) 34.00 (863.6) 2.28 (57.9) 53 (24) 0.25, 0.50, 0.75, 1.50, 2, 2.50, 3, 3.50 SKDN400 Type 3R 41.69 (1058.9) 11.75 (298.5) 14.06 (357.1) 39.90 (1013.5) 1.97 (50.0) 60 (27) 0.25, 0.50, 0.75, 2.50, 3, 3.50 RKDN400 Type 12 41.69 (1058.9) 11.75 (298.5) 14.06 (357.1) 39.90 (1013.5) 1.97 (50.0) 53 (24) — JKDN400 Type 1 45.88 (1165.4) 14.31 (363.5) 12.38 (314.5) 46.56 (1182.6) 1.91 (48.5) 81 (37) 0.25, 0.50, 0.75, 3, 3.50, 4 SLDN600 Type 3R 48.31 (1227.1) 14.91 (378.7) 15.50 (393.7) 46.56 (1182.6) 1.92 (48.8) 84 (38) 0.25, 0.50, 0.75, 3, 3.50, 4 RLDN600 Type 12 48.31 (1227.1) 14.91 (378.7) 15.50 (393.7) 46.56 (1182.6) 1.92 (48.8) 81 (37) — JLDN600 Type 1 61.22 (1555.0) 21.44 (544.6) 15.41 (391.4) 61.84 (1570.7) 1.97 (50.0) 178 (81) — SNDN1200 Type 3R 63.59 (1615.2) 22.00 (558.8) 17.63 (447.8) 61.84 (1570.7) 1.97 (50.0) 175 (79) — RNDN1200 Type 12 63.59 (1615.2) 22.00 (558.8) 17.63 (447.8) 61.84 (1570.7) 1.97 (50.0) 170 (77) — JNDN1200 LG 450–600 NG 700–1200 Type 1 Surface Mounted Type 3R Rainproof E E B E 25 25 25 25 25 25 25 25 25 25 25 Type 12, 12K Dustproof C C Catalog Number 25 C 25 25 ON A D A D D ON OFF OFF 25 A 25 25 B B 25 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com V4-T25-509 For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 25.5 25 Molded Case Circuit Breakers Specialty Breakers Contents Direct Current Circuit Breakers Description 25 Engine Generator Circuit Breakers . . . . . . . . . . . . . Direct Current Circuit Breakers Product Selection . . . . . . . . . . . . . . . . . . . . . . . Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . E2 Mining Service Circuit Breakers . . . . . . . . . . . . Classic Mining Breakers. . . . . . . . . . . . . . . . . . . . . Add-On Ground Fault Protection—Type GFR . . . . . 25 25 25 25 Page V4-T25-504 V4-T25-513 V4-T25-518 V4-T25-519 V4-T25-520 V4-T25-521 V4-T25-544 V4-T25-558 25 25 25 25 25 Direct Current Circuit Breakers 25 Product Description 25 25 25 25 25 25 25 25 25 DC (direct current) systems and applications are becoming commonplace as alternative energy sources have expanded and the number of DC devices and data centers using DC power has swelled. Eaton offers molded case circuit breakers and switches to meet circuit protection and switching requirements for a host of different DC end use requirements. Applications include UPS battery supply circuits, solar systems and electric vehicle charging, as well as commercial and industrial distribution. 25 25 25 Current ratings are available from 15 to 2500A, with a full scale of voltage and interrupting ratings to address needs ranging from standard to the highest performance. Optional internal accessories provide remote tripping and indication of breaker status. The DC breaker family is UL 489 listed and exceeds the requirements in UL 489 Supplement SC for UPS applications. Eaton breakers may be applied in both ungrounded and select grounded applications, with poles connected in series to operate at the maximum voltages shown on Page V4-T25-511. To use DC circuit breakers on 600V grounded systems, three poles in series must be connected on the ungrounded leg. The HFDDC through HMDLDC DC breakers use the same internal and external accessories as their Series C or Series G AC frame equivalents. NBDC and PBDC use the same internal and external accessories as standard NB and PB breakers. Many of the Eaton AC molded case circuit breakers carry 250V DC ratings for ungrounded systems. Refer to Page V4-T25-139 and Page V4-T25-253 for these interrupting tables. 25 25 25 25 25 25 V4-T25-510 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 25.5 Molded Case Circuit Breakers Specialty Breakers Quick Reference Direct Current Circuit Breakers 25 UL 489 Interrupting Capacity Ratings Circuit Breaker Type Maximum Amperes Interrupting Capacity (Symmetrical kA) Volts DC Poles in 125 Series 250 HFDDC HJDDC HKDDC LGEDC LGSDC LGHDC HLDDC HLDDC HMDLDC NBDC PBDC 225 250 400 600 600 600 600 1200 800 1200 2500 42 42 42 22 22 42 42 42 42 42 42 1 1 1 1 1 1 1 1 1 1 1 25 50 50 50 22 22 42 50 50 50 50 65 Poles in Series 600 Poles in Series 750 Poles in Series 2 2 2 2 2 2 2 2 2 2 2 42 42 42 35 50 65 35 — 35 50 65 3 3 3 3 3 3 3 — 3 3 3 42 — — — — — — — — — — 4 — — — — — — — — — — 25 25 25 25 25 25 IEC 60947-2 Interrupting Capacity Ratings Circuit Breaker Type Maximum Amperes 125 Volts DC Icu HJDDC LGEDC LGSDC LGHDC HLDDC HMDLDC 250 600 600 600 600 800 — 22 22 42 — — Ics Poles in Series 250 Volts DC Icu — 22 22 42 — — — 1 1 1 — — — 22 22 42 — — 25 25 Ics Poles in Series 600 Volts DC Icu Ics Poles in Series — 22 22 42 — — — 2 2 2 — — 20 — — — 20 20 10 — — — 10 10 3 — — — 3 3 Notes DC ratings apply to substantially non-inductive circuits. Time constants per UL 489. HFDDC through HMDLDC have been tesetd up to 300 Vdc to allow for battery charging voltages. 750 Vdc is common in transportation applications. HFDDC, four-pole 750 Vdc is available up to 150A maximum. 300 Vdc and 750 Vdc are not UL 489 listed voltage ratings. Four-pole frame with two-poles connected in parallel. 25 25 25 25 25 25 See Page V4-T25-519 for series connection diagrams. Use NEC rated cable to connect/short poles in series as shown. 25 25 25 25 25 25 25 25 25 25 25 25 25 25 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com V4-T25-511 For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 25.5 Molded Case Circuit Breakers Specialty Breakers 25 Catalog Number Selection 25 DC Circuit Breaker HFDDC 3 150 W 25 25 HFDDC HJDDC HKDDC LGEDC LGSDC LGHDC HLDDC HMDLDC NBDC PBDC 25 25 25 25 25 25 25 25 25 25 25 25 25 = = = = = = = = = = Frame Series C—F (225A max.) Series C—J (250A max.) Series C—K (400A max.) Series G—L (600A max.) Series G—L (600A max.) Series G—L (600A max.) Series C—L (1200A max.) Series C—M (800A max.) NB (1200A max.) PB (2500A max.) Number of Poles 1 = Single-pole 2 = Two-pole 3 = Three-pole 4 = Four-pole Trip Unit Ampere Rating 015 = 15A 020 = 20A 025 = 25A 030 = 30A 035 = 35A 040 = 40A 045 = 45A 050 = 50A 060 = 60A 070 = 70A 080 = 80A 090 = 90A 100 = 100A 110 = 110A 125 = 125A 150 = 150A 175 = 175A 200 = 200A 225 = 225A 250 = 250A 300 = 300A 350 = 350A 400 = 400A 450 = 450A 500 = 500A 600 = 600A 700 = 700A 800 = 800A 900 = 900A 1000 = 1000A 1200 = 1200A 1600 = 1600A 2000 = 2000A 2500 = 2500A K L MW W = = = = Suffix Molded case switch Line and load terminals, F-Frame 135% magnetic trip unit, without terminals Without terminals 25 25 25 25 25 25 25 25 25 25 25 25 25 V4-T25-512 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 25.5 Molded Case Circuit Breakers Specialty Breakers Product Selection HFDDC 25 Type HFDDC DC Circuit Breakers— Three-Pole High Interrupting Capacity 42 kAIC at 600 Vdc 25 Maximum Continuous Ampere Rating at 40°C Complete Circuit Breaker with Line and Load Terminals Single-Pole Two-Pole Catalog Catalog Number Number Three-Pole Catalog Number Four-Pole Catalog Number 15 HFDDC1015L HFDDC2015L HFDDC3015L HFDDC4015L 20 HFDDC1020L HFDDC2020L HFDDC3020L HFDDC4020L 25 HFDDC1025L HFDDC2025L HFDDC3025L HFDDC4025L 30 HFDDC1030L HFDDC2030L HFDDC3030L HFDDC4030L 35 HFDDC1035L HFDDC2035L HFDDC3035L HFDDC4035L 40 HFDDC1040L HFDDC2040L HFDDC3040L HFDDC4040L 45 HFDDC1045L HFDDC2045L HFDDC3045L HFDDC4045L 50 HFDDC1050L HFDDC2050L HFDDC3050L HFDDC4050L 60 HFDDC1060L HFDDC2060L HFDDC3060L HFDDC4060L 70 HFDDC1070L HFDDC2070L HFDDC3070L HFDDC4070L 80 HFDDC1080L HFDDC2080L HFDDC3080L HFDDC4080L 90 HFDDC1090L HFDDC2090L HFDDC3090L HFDDC4090L 100 HFDDC1100L HFDDC2100L HFDDC3100L HFDDC4100L 110 HFDDC1110L HFDDC2110L HFDDC3110L HFDDC4110L 125 HFDDC1125L HFDDC2125L HFDDC3125L HFDDC4125L 150 HFDDC1150L HFDDC2150L HFDDC3150L HFDDC4150L 175 — HFDDC2175L HFDDC3175L — 200 — HFDDC2200L HFDDC3200L — 225 — HFDDC2225L HFDDC3225L — 25 25 25 25 25 25 25 25 25 25 25 25 25 25 HJDDC3250 Type HJDDC DC Circuit Breakers— Three-Pole High Interrupting Capacity 42 kAIC at 600 Vdc Circuit Breaker Frame Only 25 Catalog Number Thermal-Magnetic Trip Unit Catalog Number Standard Terminals Catalog Number 70 HJDDC3250F JT3070T TA250KB 90 HJDDC3250F JT3090T TA250KB 100 HJDDC3250F JT3100T TA250KB 125 HJDDC3250F JT3125T TA250KB 150 HJDDC3250F JT3150T TA250KB 175 HJDDC3250F JT3175T TA250KB 200 HJDDC3250F JT3200T TA250KB 225 HJDDC3250F JT3225T TA250KB 250 HJDDC3250F JT3250T TA250KB Maximum Continuous Ampere Rating at 40°C 25 25 25 25 25 25 25 Notes For breaker without terminals, replace "L" with "W" at end of catalog number. For complete breaker, order individual frame, trip unit and terminals for field installation. 25 25 25 25 25 25 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com V4-T25-513 For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 25.5 25 HKDDC3400 Molded Case Circuit Breakers Specialty Breakers Type HKDDC DC Circuit Breakers— Three-Pole High Interrupting Capacity 42 kAIC at 600 Vdc Maximum Continuous Ampere Rating at 40°C Circuit Breaker Frame Only Catalog Number Thermal-Magnetic Trip Unit Catalog Number Standard Terminals Catalog Number 100 HKDDC3400F KT3100T TA300K 125 HKDDC3400F KT3125T TA300K 25 150 HKDDC3400F KT3150T TA300K 175 HKDDC3400F KT3175T TA300K 25 200 HKDDC3400F KT3200T TA300K 225 HKDDC3400F KT3225T TA300K 250 HKDDC3400F KT3250T TA350K 300 HKDDC3400F KT3300T TA350K 350 HKDDC3400F KT3350T TA350K 400 HKDDC3400F KT3400T 3TA400K 25 25 25 25 25 25 25 Type LGEDC DC Circuit Breakers— Three-Pole High Interrupting Capacity 35 kAIC at 600 Vdc 25 25 Maximum Continuous Ampere Rating at 40°C Complete Breaker Catalog Number Circuit Breaker Frame Only Catalog Number Thermal-Magnetic Trip Unit Catalog Number Standard Terminals Catalog Number 25 250 LGEDC3250FAG LGEDC3630NN LT3250FA TA350LK 25 300 LGEDC3300FAG LGEDC3630NN LT3300FA TA350LK 350 LGEDC3350FAG LGEDC3630NN LT3350FA TA350LK 25 400 LGEDC3400FAG LGEDC3630NN LT3400FA TA350LK 500 LGEDC3500FAG LGEDC3630NN LT4500FA 3TA632LK 25 600 LGEDC3600FAG LGEDC3630NN LT3600FA 3TA632LK 25 Type LGSDC DC Circuit Breakers— Three-Pole High Interrupting Capacity 50 kAIC at 600 Vdc 25 25 25 25 25 25 25 Maximum Continuous Ampere Rating at 40°C Complete Breaker Catalog Number Circuit Breaker Frame Only Catalog Number Thermal-Magnetic Trip Unit Catalog Number Standard Terminals Catalog Number 250 LGSDC3250FAG LGSDC3630NN LT3250FA TA350LK 300 LGSDC3300FAG LGSDC3630NN LT3300FA TA350LK 350 LGSDC3350FAG LGSDC3630NN LT3350FA TA350LK 400 LGSDC3400FAG LGSDC3630NN LT3400FA TA350LK 500 LGSDC3500FAG LGSDC3630NN LT4500FA 3TA632LK 600 LGSDC3600FAG LGSDC3630NN LT3600FA 3TA632LK Notes For complete breaker, order individual frame, trip unit and terminals for field installation. Three-pole kit. 25 25 25 25 25 25 V4-T25-514 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 25.5 Molded Case Circuit Breakers Specialty Breakers Type LGHDC DC Circuit Breakers— Three-Pole High Interrupting Capacity 65 kAIC at 600 Vdc 25 Maximum Continuous Ampere Rating at 40°C Complete Breaker Catalog Number Circuit Breaker Frame Only Catalog Number Thermal-Magnetic Trip Unit Catalog Number Standard Terminals Catalog Number 250 LGHDC3250FAG LGHDC3630NN LT3250FA TA350LK 300 LGHDC3300FAG LGHDC3630NN LT3300FA TA350LK 350 LGHDC3350FAG LGHDC3630NN LT3350FA TA350LK 400 LGHDC3400FAG LGHDC3630NN LT3400FA TA350LK 25 25 25 25 500 LGHDC3500FAG LGHDC3630NN LT4500FA 3TA632LK 600 LGHDC3600FAG LGHDC3630NN LT3600FA 3TA632LK 25 25 HLDDC 25 Type HLDDC DC Circuit Breakers— Three-Pole High Interrupting Capacity 35 kAIC at 600 Vdc Maximum Continuous Ampere Rating at 40°C Circuit Breaker Frame Only Catalog Number Thermal-Magnetic Trip Unit Catalog Number Standard Terminals Catalog Number 25 300 HLDDC3600F LT3300T TA602LD 350 HLDDC3600F LT3350T TA602LD 25 400 HLDDC3600F LT3400T TA602LD 450 HLDDC3600F LT3450T TA602LD 500 HLDDC3600F LT3500T TA602LD 600 HLDDC3600F LT3600T 3TA603LDK Type HLDDC DC Circuit Breakers— Two-Pole High Interrupting Capacity 50 kAIC at 250 Vdc Maximum Continuous Ampere Rating at 40°C Complete Breaker Catalog Number 600 HLDDC20600 700 HLDDC20700 800 HLDDC20800 900 HLDDC20900 1000 HLDDC21000 1200 HLDDC21200 25 25 25 25 25 25 25 25 25 25 25 Notes For complete breaker, order individual frame, trip unit and terminals for field installation. Three-pole kit. Includes breaker frame, trip unit and terminals. Four-pole breaker with two poles wired in parellel. 25 25 25 25 25 25 25 25 25 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com V4-T25-515 For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 25.5 25 HMDLDC3800F Molded Case Circuit Breakers Specialty Breakers Type HMDLDC DC Circuit Breakers— Three-Pole High Interrupting Capacity 35 kAIC at 600 Vdc Maximum Continuous Ampere Rating at 40°C Circuit Breaker Frame Only Catalog Number Thermal-Magnetic Trip Unit Catalog Number Standard Terminals Catalog Number 300 HMDLDC3800F MT3300T TA700MA1 350 HMDLDC3800F MT3350T TA700MA1 25 400 HMDLDC3800F MT3400T TA700MA1 450 HMDLDC3800F MT3450T TA700MA1 25 500 HMDLDC3800F MT3500T TA700MA1 600 HMDLDC3800F MT3600T TA700MA1 700 HMDLDC3800F MT3700T TA700MA1 800 HMDLDC3800F MT3800T TA800MA2 25 25 25 25 25 25 Type NBDC DC Circuit Breakers— Three-Pole High Interrupting Capacity 50 kAIC at 600 Vdc 25 25 25 25 25 Maximum Continuous Ampere Rating at 40°C Complete Circuit Breaker Factory Assembled without Terminals Catalog Includes Magnetic Number Trip Unit Calibrated at 135% Standard Terminals Catalog Number 700 NBDC3700MW Included TA1000NB1 800 NBDC3800MW Included TA1000NB1 900 NBDC3900MW Included TA1000NB1 1000 NBDC31000MW Included TA1000NB1 1200 NBDC31200MW Included TA1200NB1 25 Type PBDC DC Circuit Breakers— Three-Pole High Interrupting Capacity 65 kAIC at 600 Vdc 25 25 25 25 25 25 Maximum Continuous Ampere Rating at 40°C Complete Circuit Breaker Factory Assembled without Terminals Catalog Number Includes Magnetic Trip Unit Calibrated at 135% Standard Rear Connectors Catalog Number 1600 PBDC31600W Included BA2000PB 2000 PBDC32000W Included BA2000PB 2500 PBDC32500W Included BA2500PB Notes Includes frame and trip unit. Order terminals or connectors separately. For complete breaker, order individual frame, trip unit and terminals for field installation. 25 25 25 25 25 25 25 25 25 V4-T25-516 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 25.5 Molded Case Circuit Breakers Specialty Breakers DC Breaker Terminal Wire Ranges Breaker Frame Maximum Breaker Ampacity Terminal Body Material Wire Type AWG Wire Range/ Number of Conductors Metric Wire Range mm2 Number of Terminals Included Standard Terminal Catalog Number HFDDC 20 Steel Cu/Al 14–10 (1) 2.5–4 (1) 3 3T20FB 100 Steel Cu/Al 14–1/0 (1) 2.5–50 (1) 3 3T100FB 225 Aluminum Cu/Al 4–4/0 (1) 25–95 (1) 3 3TA225FD HJDDC 250 Aluminum Cu/Al 4–350 kcmil (1) 25–185 (1) 1 TA250KB HKDDC 225 Aluminum Cu/Al 3–350 kcmil (1) 35–185 (1) 1 TA300K 350 Aluminum Cu/Al 250–500 kcmil (1) 120–240 (1) 1 TA350K 400 Aluminum Cu/Al 3/0–250 kcmil (2) 95–120 (1) 3 3TA400K 500 Aluminum Cu/Al 3/0–350 kcmil (2) 95–150 (2) 1 TA602LD 600 Aluminum Cu/Al 400–500 kcmil (2) 185–240 (2) 3 3TA603LDK 400 Aluminum Cu/Al 2–500 (1) 35–240 (1) 1 TA350LK 630 Aluminum Cu/Al 2–500 kcmil (2) 35–240 (2) 3 3TA632LK 500 Aluminum Cu/Al 3/0–350 kcmil (2) 95–150 (2) 1 TA602LD 600 Aluminum Cu/Al 400–500 kcmil (2) 185–240 (2) 3 3TA603LDK LGEDC, LGSDC, LGHDC HLDDC HMDLDC NBDC 600 Aluminum Cu/Al 1–500 kcmil (2) — 1 TA700MA1 800 Aluminum Cu/Al 3/0–400 kcmil (3) — 1 TA800MA2 700 Aluminum Cu/Al 3/0–400 kcmil (3) 95–185 (3) 1 TA1000NB1 800 Aluminum Cu/Al 3/0–400 kcmil (3) 95–185 (3) 1 TA1000NB1 900 Aluminum Cu/Al 3/0–400 kcmil (3) 95–185 (3) 1 TA1000NB1 1000 Aluminum Cu/Al 3/0–400 kcmil (3) 95–185 (3) 1 TA1000NB1 1200 Aluminum Cu/Al 4/0–500 kcmil (4) 120–240 (4) 1 TA1200NB1 25 25 25 25 25 25 25 25 25 25 25 25 25 25 Molded Case Switches Eaton’s DC molded case switches are used in applications requiring a compact, high-capacity disconnect. They are UL 489 listed and have automatic high instantaneous current protection. These devices do not provide overload protection. 25 Molded Case Switches 25 Maximum Continuous Ampere Rating at 40°C With Line and Load Terminals Without Line and Load Terminals Interrupting Capacity (Volts DC) Poles in Series Catalog Number Catalog Number 100 42 3 HFDDC2100KL HFDDC2100KW 150 42 3 HFDDC2150KL HFDDC2150KW 225 42 3 HFDDC2225KL HFDDC2225KW 250 42 3 HJDDC3250K HJDDC3250KW 25 25 600 Vdc Maximum 400 600 800 35 3 HKDDC3400K HKDDC3400KW 65 3 LGKDC3400KSG LGKDC3400KSW 65 3 LGKDC3630KSG LGKDC3630KSW 35 3 HLDDC3600K HLDDC3600WK 35 3 HMDLDC3800K HMDLDC3800WK 50 HLDDC21200K HLDDC21200WK 25 25 25 25 25 25 250 Vdc Maximum 1200 25 25 Note Four-pole frame with two-pole connected in parallel. 25 25 25 25 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com V4-T25-517 For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 25.5 Molded Case Circuit Breakers Specialty Breakers 25 Accessories 25 Internal Accessories 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 Description Factory Installation (HFDDC) Right-Pole Mounting Auxiliary switch 1A-1B A06 2A-2B A13 Alarm switch 1 make/1 break B06 Auxiliary and alarm combo 1A-1B, 1 make/1 break C05 Left-Pole Mounting Shunt trip 12 Vdc S02 24 Vdc S02 48 Vdc S06 60 Vdc S06 125 Vdc S10 250 Vdc S14 120 Vac S06 Undervoltage release 12 Vdc U30 24 Vdc U34 48 Vdc U38 125 Vdc 250 Vdc 120 Vac U42 U46 U14 Field Installation Kits HFDDC HJDDC HKDDC LGEDC, LGSDC, LGHDC HLDDC HMDLDC NBDC PBDC A1X1PK A2X1RPK A1X2PK A2X2PK A1X13PK A2X3PK AUX1A1BPK AUX2A2BPK A1X4PK A2X4PK A1X4PK A2X4PK 4980D16G05 4980D16G06 2602D32G14 2602D32G15 A1L1RPK A1L2RPK A1L3RPK ALM1M1BJPK A1L4RPK A1L4RPK — — AAL1RPK AAL2RPK AAL3RPK AUXALRMJPK AA114RPK AA114RPK — — SNT1LP03K SNT1LP03K SNT1LP08K SNT1LP08K SNT1LP12K SNT1LP18K SNT1LP12K SNT2P04K SNT2P04K SNT2P06K SNT2P06K SNT2P11K SNT2P14K SNT2P11K SNT3P04K SNT3P04K SNT3P06K SNT3P06K SNT3P11K SNT3P14K SNT3P11K SNT012CPK SNT060CPK SNT060CPK SNT060CPK SNT120CPK — SNT120CPK SNT4LP03K SNT4LP03K SNT4LP23K SNT4LP23K SNT4LP26K SNT4LP14K SNT4LP11K SNT4LP03K SNT4LP03K SNT4LP23K SNT4LP23K SNT4LP26K SNT4LP14K SNT4LP11K 2606D58G14 2606D58G13 2606D58G12 2606D58G11 2606D58G10 2606D58G09 2060D58G05 2606D59G28 2606D59G27 2606D59G26 2606D59G25 2606D59G24 2606D59G23 2060D59G19 UVH1LP20K UVH1LP21K UVH1LP22K UVH2LP20K UVH2LP21K UVH2LP22K UVH3LP20K UVH3LP21K UVH3LP22K UVR012DPK UVR024DPK UVR048DPK UVH4LP20K UVH4LP21K UVH4LP22K UVH4LP20K UVH4LP21K UVH4LP22K 372D032G06 372D032G07 372D032G08 4976D85G11 4976D85G12 4976D85G13 UVH1LP26K UVH1LP28K UVH1LP08K UVH2LP26K UVH2LP28K UVH2LP08K UVH3LP26K UVH3LP28K UVH3LP08K UVR125DPK UVR250DPK UVR120APK UVH4LP26K UVH4LP28K UVH4LP08K UVH4LP26K UVH4LP28K UVH4LP08K 372D032G09 372D032G10 373D632G05 4976D85G17 4976D85G18 5674D29G01 Note F-Frame circuit breakers are factory sealed. Underwriters Laboratories requires that internal accessories be installed at the factory. Internal accessories are UL listed for factory installation under E7819. Where local codes and standards permit and UL listing is not required, internal accessories can be field installed. Accessory installation should be done before the circuit breaker is mounted and connected. One accessory can be mounted per pole, per breaker. Factory installation of accessories available. Contact Eaton for assistance with part number configuration. 25 25 25 25 25 25 25 25 25 25 25 25 25 V4-T25-518 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 Molded Case Circuit Breakers Specialty Breakers 25.5 Wiring Diagrams 25 Series Connection Diagrams for DC Application 25 25 250 Vdc Maximum—Two Poles in Series 25 25 25 25 Load Load 25 (A) Suitable for use on ungrounded systems, or grounded systems that have one end of load (A) connected to grounded terminal, opposite poles in series connection. 25 Suitable for use on ungrounded systems only. 25 25 600 Vdc Maximum—Three Poles in Series 25 Load 25 25 25 Load 25 (A) Suitable for use on ungrounded systems, or grounded systems that have one end of load (A) connected to grounded terminal, opposite poles in series connection. 25 Suitable for use on ungrounded systems only. 25 25 750 Vdc Maximum—Four Poles in Series 25 25 25 25 25 Load Load 25 (A) Suitable for use on ungrounded systems, or grounded systems that have one end of load (A) connected to grounded terminal, opposite poles in series connection. Suitable for use on ungrounded systems only. 25 25 Notes Poles in series connection is customer supplied. Use rated cable per NEC. For grounded systems, all poles in series must be connected on non-grounded terminal, with load connected to grounded terminal. 25 25 25 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com V4-T25-519 For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 25.5 25 Molded Case Circuit Breakers Specialty Breakers Dimensions Approximate Dimensions in Inches (mm) 25 DC Breaker Dimensions 25 Frame 25 HFDDC 25 25 25 25 25 HJDDC HKDDC LGEDC, LGSDC, LGHDC 600A Max. HLDDC 1200A Max. HLDDC HMDLDC NBDC PBDC Number of Poles Width Height Depth 1 2 3 4 2, 3 2, 3 3 2, 3 4 2, 3 3 3 1.38 (35.1) 2.75 (70.0) 4.13 (105.0) 5.50 (139.7) 4.13 (105.0) 5.50 (139.7) 5.48 (139.2) 8.25 (209.6) 11.00 (279.4) 8.25 (209.6) 8.25 (209.6) 12.06 (306.3) 6.00 (152.4) 6.00 (152.4) 6.00 (152.4) 6.00 (152.4) 10.00 (254.0) 10.13 (257.3) 10.13 (257.3) 10.75 (273.1) 10.75 (273.1) 16.00 (406.4) 16.00 (406.4) 22.06 (560.3) 3.38 (86.0) 3.38 (86.0) 3.38 (86.0) 3.38 (86.0) 4.06 (103.1) 4.10 (104.1) 4.09 (103.9) 4.06 (103.1) 4.06 (103.1) 4.06 (103.1) 5.50 (139.7) 9.06 (230.1) 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 V4-T25-520 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 25.5 Molded Case Circuit Breakers Specialty Breakers Contents E2 Mining Service Breakers Description Page Engine Generator Circuit Breakers . . . . . . . . . . . . . Direct Current Circuit Breakers. . . . . . . . . . . . . . . . E2 Mining Service Breakers Product Selection . . . . . . . . . . . . . . . . . . . . . . . Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . Classic Mining Breakers . . . . . . . . . . . . . . . . . . . . . Add-On Ground Fault Protection—Type GFR . . . . . V4-T25-504 V4-T25-510 V4-T25-525 V4-T25-541 V4-T25-544 V4-T25-558 25 25 25 25 25 25 25 25 25 25 25 E2 Mining Service Breakers Product Overview State-of-the-art E2 mining service breakers incorporate the rigid specifications and testing procedures developed by a focus group led by engineers from several large coal companies and Eaton design engineers. Additionally, the performance of these breakers was proven and verified during hundreds of hours of field testing in harsh mine environments. E2 mining breakers are available in 600 Vac and l000Y/ 577 Vac. Interchangeable trip units can be used on either 600 or 1000 Vac frames. The E2 mining breaker family is designed especially for trailing cable application per MSHA 30 CFR 75. Field interchangeable electronic rms sensing trip units are available from 150 to 2000 amperes with instantaneous pickup settings conforming to the code of Federal Regulations 30 CFR 75.601-2. Electromechanical trip units are also available with a wide range of magnetic pickup ranges. E2 electronic trip units are the first to provide the mining industry with true rms sensing, made possible by the custom ASIC microprocessor in each electronic trip unit. E2 breakers are designed to be physically and electrically interchangeable with Classic Mining Service Breakers and supersede Series C® Mining Service Breakers. The table to the right outlines direct replacements. 600 Vac Mining Breaker Replacement Chart 1000 Vac Mining Breaker Replacement Chart Classic Series C E2 Classic Series C E2M FBM FDBM E2F HFBM FDM E2F HFM — E2FM — JDCM E2JM HFDM (mag. only) E2F HKAM KDCM E2KM JDM E2J — HLAM LDCM E2LM KAM KDM E2K HLCM LDCM E2LM KAMH KDM E2K HMAM — E2MM LAM LDM E2L HMCM — E2MM LAMH LDM E2L HNBM — E2NM LCM LDM E2L HNBMH — E2NM LCMH LDM E2L HNCM — E2NM MAM — E2M HLCLM — E2NM MAMH — E2M HPBM — E2RM MCM — E2M MCMH — E2M NBM — E2N NBMH — E2N NCM — E2N NCMH — E2N 25 25 25 25 25 25 25 25 25 25 25 25 25 25 Additional Information on Mining Breakers Source Description TD01217001E E2 Mining Circuit Breaker Dimensional Data BR01217001E E2 Mining Circuit Breaker Brochure TC01217001E E2 Mining Circuit Breaker Time Current Curves www.eaton.com/mining Mining and Metals 25 25 25 Note E2R/E2RM is a new frame physically different than the HPBM. See DS29-170MS. 25 25 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com V4-T25-521 For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 25.5 25 25 25 25 25 25 25 Specialty Breakers Eaton’s mining service circuit breakers provide short circuit protection as specified in the code of Federal Regulations 30 CFR 75.601-2. E2 225/400 ampere K frame and 400/600 ampere L frame electronic trip units feature specifically designed instantaneous pickup settings to conform exactly with the code of Federal Regulations 30 CFR 75.601-2. Electromechanical trip units are also available with a wide range of magnetic pickup ranges. The tables below list the conductor size maximum allowable circuit breaker instantaneous setting and the E2 breaker that meets that setting. Auxiliary Switch Electrical Rating Data Interrupting Capacity Rating 25 25 Molded Case Circuit Breakers Circuit Breaker Type Interrupting Capacity (Symmetrical kA) Vac (50/60 Hz) 240 480 600 1000Y/577 Vdc 250 E2F 65 10 25 18 — E2J 65 35 18 — 10 E2K 65 35 25 — 10 E2LME 100 65 35 — 42 25 E2L 65 35 25 — 22 E2M 65 35 25 — 22 25 E2N 65 50 25 — — E2R 125 65 50 — — E2FM 65 25 18 10 10 E2JM 65 35 18 10 22 E2KM 65 35 25 14 10 25 25 25 25 25 25 25 E2LMZ 100 65 35 10 42 E2LM — 35 25 18 22 E2MM E2NM E2RM — 35 25 18 22 — 50 25 25 — — 65 50 25 — Conductor Size E2/E2M Instantaneous Only Setting 14 50 15 E2K 150A A 12 75 20 E2K 150A B 25 10 150 30 E2K 150A C 8 200 50 E2K 225A A 25 6 300 65 E2K 225A B 4 500 85 E2K 225A/E2L 400A C/A D/B 3 600 100 E2K 225A/E2L 400A 2 800 115 E2K 225A/E2L 400A E/C 1 1000 130 E2K 225A/E2L 400A F/D 1/0 1250 150 E2K 225A/E2L 400A G/E 2/0 1500 175 E2K 225A/E2L 400A H/F 25 3/0 2000 200 E2L 400A G 4/0 2500 230 E2L 400A H 25 250 2500 255 E2L 400A H 300 2500 285 E2L 400A H 25 350 2500 310 E2L 400A H 400 2500 335 E2L 400A H 500 2500 380 E2L 400A H 25 25 25 600 50/60 Hz 6.0 125 DC 0.5 (non-inductive load) 250 DC 0.25 (non-inductive load) Maximum Voltage Frequency Maximum Current Amperes 600 50/60 Hz 6.0 125 DC 0.5 (non-inductive load) 250 DC 0.25 (non-inductive load) Notes Two poles in series. DC rating applies to breakers with thermal-magnetic trip unit. Breakers with electronic trip units are not DC rated. Series rated for application with Eaton’s E2KM and E2LM breakers. Maximum Ampere 75°C Insulated Conductor 25 Maximum Current Amperes Alarm (Signal/Lockout Switch) Electrical Rating Data Maximum Breaker Instantaneous Setting 25 Frequency Trailing Cable Setting Per 30 CFR 75 25 25 Maximum Voltage V4-T25-522 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 Molded Case Circuit Breakers Specialty Breakers 25.5 Undervoltage Release Mechanism Electrical Rating Data Breaker Type Supply Voltage Dropout Voltage Minimum E2F/E2FM 110 Vac 44.5 E2J/E2JM Maximum VA 77 93.5 1.3 120 Vac 1.5 127 Vac 1.7 110 Vdc 1.5 120 Vdc 1.7 125 Vdc 1.9 110 Vac 44.5 77 93.5 2.1 127 Vac 2.4 110 Vdc 1.6 120 Vdc 1.9 E2LME/E2LMZ 110 Vac 77 93.5 2.1 2.4 110 Vdc 1.6 120 Vdc 1.9 125 Vdc 2.2 44.5 77 93.5 1.13 127 Vac 1.25 43.8 77 93.5 E2N/E2NM 77 93.5 127 Vac 2.4 110 Vdc 1.6 120 Vdc 1.9 125 Vdc 2.2 44.5 77 93.5 25 25 25 25 25 25 25 25 25 25 25 1.8 120 Vac 2.1 127 Vac 2.4 110 Vdc 1.6 120 Vdc 1.9 25 25 25 2.2 44.5 77 93.5 120 Vac 3.3 25 3.6 127 Vac 110 Vdc 25 1.8 2.1 110 Vac 25 1.21 44.5 125 Vdc E2R/E2RM 25 0.94 120 Vac 110 Vac 25 1.12 125 Vdc 110 Vac 25 0.96 120 Vac 120 Vdc E2L/E2LM/E2M/ E2MM 25 1.8 127 Vac 110 Vdc 25 2.2 44.5 120 Vac 110 Vac 25 1.8 120 Vac 125 Vdc E2K/E2KM 25 Pickup Voltage Maximum 25 3.8 43.8 77 93.5 3.3 120 Vdc 3.6 125 Vdc 3.8 25 25 25 25 25 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com V4-T25-523 For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 25.5 25 25 Molded Case Circuit Breakers Specialty Breakers Shunt Trip Electrical Rating Data Breaker Type Supply Voltage Operating Voltage Minimum VA Breaker Type Supply Voltage Operating Voltage Minimum E2F/E2FM 48 Vac 33.6 92 E2L/E2LM/E2M/ E2MM 48 Vac 34 25 25 60 Vac 140 60 Vac 110 Vac 480 110 Vac 120 Vac 570 120 Vac 640 127 Vac 180 48 Vdc 25 127 Vac 25 220 Vac 200 60 Vdc 230 Vac 240 110 Vdc 100 120 Vdc 160 125 Vdc 208 Vac 25 48 Vdc 146 33.6 VA 830 1280 60 100 120 140 34 710 1105 77 110 130 25 60 Vdc 25 120 Vdc 66 120 Vac 120 125 Vdc 71 127 Vac 140 66 110 Vdc 84 120 Vdc 25 110 Vdc E2J/E2JM 127 Vac 110 Vdc 25 125 Vdc E2K/E2KM 110 Vac 60 120 Vac 25 127 Vac 25 120 Vdc 110 Vdc 25 77 140 60.5 330 110 Vdc 120 120 Vdc 440 140 390 125 Vdc 480 430 77 370 110 18 139 210 60 83 92 117 25 120 25 60 Vdc 25 110 Vac 127 Vac 24 Vdc 110 Vdc 125 Vdc E2R/E2RM 110 130 100 127 Vac 25 77 100 150 140 48 Vdc 140 60 120 Vac 41 120 Vac 25 110 Vac 138 24 Vac 110 Vac E2N/E2NM 130 60 Vac E2LME/E2LMZ 112 125 Vdc 48 Vac 25 55 102 77 120 Vdc 25 25 60.5 120 Vac 25 25 110 Vac 77 18 475 720 82 99 120 Vdc 120 125 Vdc 121 25 25 25 25 25 25 V4-T25-524 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 Molded Case Circuit Breakers Specialty Breakers 25.5 Product Selection 25 E2F/E2FM 25 Thermal-Magnetic Circuit Breakers—Sealed Breakers with Non-Interchangeable Trip Unit— Include Line/Load Terminals E2F/E2FM 25 600 Vac Maximum, 250 Vdc, 25 kA at 480 Vac, Three-Pole 25 Maximum Continuous Ampere Rating at 40°C Catalog Number 25 15 E2F3015 20 E2F3020 25 25 E2F3025 30 E2F3030 35 E2F3035 40 E2F3040 45 E2F3045 50 E2F305 60 E2F3060 70 E2F3070 80 E2F3080 90 E2F3090 100 E2F3100 125 E2F3125 150 E2F3150 25 25 25 25 25 25 25 25 25 1000Y/577 Vac Maximum, 250 Vdc, 10 kA at 1000 Vac, Three-Pole Maximum Continuous Ampere Rating at 40°C Catalog Number 25 15 — 25 20 E2FM3020 25 E2FM3025 30 — 35 — 40 E2FM3040 45 — 50 E2FM3050 60 E2FM3060 70 E2FM3070 80 E2FM3080 90 E2FM3090 100 E2FM3100 125 E2FM3125 150 E2FM3150 25 25 25 25 25 25 25 25 Note For two-pole application, use outer poles. 25 25 25 25 25 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com V4-T25-525 For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 25.5 25 25 25 Molded Case Circuit Breakers Specialty Breakers E2F/E2FM Magnetic Only Circuit Breakers—Sealed Breakers with Non-Interchangeable Trip Unit— Include Line/Load Terminals 600 Vac Maximum, 250 Vdc, 25 kA at 480 Vac, Three-Pole 25 Maximum Continuous Ampere Rating at 40°C Magnetic Trip Range Catalog Number 25 3 9–30 E2F003AM 7 21–70 E2F007CM 15 45–150 E2F015EM 25 25 30 25 50 25 25 25 90–300 E2F030HM 50–150 E2F030EM 150–500 E2F050KM 66–190 E2F050YM 70 210–700 E2F070MM 100 150–500 E2F100KM 300–1000 E2F100RM 450–1500 E2F150TM 750–2500 E2F150UM 150 25 25 25 25 25 25 1000Y/577 Vac Maximum, 250 Vdc, 10 kA at 1000 Vac, Three-Pole Maximum Continuous Ampere Rating at 40°C Magnetic Trip Range Catalog Number 3 9–30 — 7 21–70 — 15 45–150 — 30 90–300 — 50–150 — 150–500 E2FM050KM 66–190 E2FM050YM 70 210–700 E2FM070MM 100 150–500 E2FM100KM 300–1000 E2FM100RM 450–1500 E2FM150TM 750–2500 E2FM150UM 50 25 25 25 150 25 25 25 25 25 25 25 25 25 25 V4-T25-526 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 Molded Case Circuit Breakers Specialty Breakers 25.5 E2J/E2JM 25 Circuit Breakers with Interchangeable Thermal-Magnetic Trip Unit 25 25 600 Vac Maximum, 250 Vdc, 35 kA at 480 Vac, Three-Pole Maximum Continuous Ampere Rating at 40°C Complete Breaker Frame Only Trip Unit Only Magnetic Trip Range Catalog Number Catalog Number Catalog Number 70 300–650 E2J3070W E2J3250F E2J3070T 90 450–900 E2J3090W E2J3250F E2J3090T 100 500–1000 E2J3100W E2J3250F E2J3100T 125 625–1250 E2J3125W E2J3250F E2J3125T 150 750–1500 E2J3150W E2J3250F E2J3150T 175 875–1750 E2J3175W E2J3250F E2J3175T 200 1000–2000 E2J3200W E2J3250F E2J3200T 225 300–650 E2J3225AW E2J3250F E2J3225TA 500–1000 E2J3225DW E2J3250F E2J3225TD 1125–2250 E2J3225W E2J3250F E2J3225T 1250–2500 E2J3250W E2J3250F E2J3250T 250 25 25 25 25 25 25 25 25 25 E2J/E2JM 1000Y/577 Vac Maximum, 250 Vdc, 10 kA at 1000 Vac, Three-Pole Maximum Continuous Ampere Rating at 40°C 25 Complete Breaker Frame Only Trip Unit Only Magnetic Trip Range Catalog Number Catalog Number Catalog Number 25 70 300–650 E2JM3070W E2JM3250F E2J3070T 25 90 450–900 E2JM3090W E2JM3250F E2J3090T 100 500–1000 E2JM3100W E2JM3250F E2J3100T 125 625–1250 E2JM3125W E2JM3250F E2J3125T 150 750–1500 E2JM3150W E2JM3250F E2J3150T 175 875–1750 E2JM3175W E2JM3250F E2J3175T 200 1000–2000 E2JM3200W E2JM3250F E2J3200T 225 250 300–650 E2JM3225AW E2JM3250F E2J3225TA 500–1000 E2JM3225DW E2JM3250F E2J3225TD 1125–2250 E2JM3225W E2JM3250F E2J3225T 1250–2500 E2JM3250W E2JM3250F E2J3250T 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com V4-T25-527 For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 25.5 25 25 25 25 25 Molded Case Circuit Breakers Specialty Breakers E2J/E2JM Circuit Breakers with Interchangeable Magnetic Only Trip Unit 600 Vac Maximum, 250 Vdc, 25 kA at 480 Vac, Three-Pole Maximum Continuous Ampere Rating at 40°C 250 Complete Breaker Frame Only Trip Unit Only Magnetic Trip Range Catalog Number Catalog Number Catalog Number 300–650 E2J3250MAW E2J3250F E2J3250TMA 450–900 E2J3250MCW E2J3250F E2J3250TMC 500–1000 E2J3250MDW E2J3250F E2J3250TMD 625–1250 E2J3250MFW E2J3250F E2J3250TMF 750–1500 E2J3250MGW E2J3250F E2J3250TMG 875–1750 E2J3250MJW E2J3250F E2J3250TMJ 25 1000–2000 E2J3250MKW E2J3250F E2J3250TMK 1125–2250 E2J3250MLW E2J3250F E2J3250TML 25 1250–2500 E2J3250MW E2J3250F E2J3250TM 25 25 25 25 25 25 25 1000Y/577 Vac Maximum, 250 Vdc, 10 kA at 1000 Vac, Three-Pole Maximum Continuous Ampere Rating at 40°C 250 25 25 25 25 Complete Breaker Frame Only Trip Unit Only Magnetic Trip Range Catalog Number Catalog Number Catalog Number 300–650 E2JM3250MAW E2JM3250F E2J3250TMA 450–900 E2JM250MCW E2JM3250F E2J3250TMC 500–1000 E2JM3250MDW E2JM3250F E2J3250TMD 625–1250 E2JM3250MFW E2JM3250F E2J3250TMF 750–1500 E2JM3250MGW E2JM3250F E2J3250TMG 875–1750 E2JM3250MJW E2JM3250F E2J3250TMJ 1000–2000 E2JM3250MKW E2JM3250F E2J3250TMK 1125–2250 E2JM3250MLW E2JM3250F E2J3250TML 1250–2500 E2JM3250MW E2JM3250F E2J3250TM 25 25 25 25 25 25 25 25 25 25 25 25 V4-T25-528 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 Molded Case Circuit Breakers Specialty Breakers 25.5 E2K/E2KM 25 Circuit Breakers with Interchangeable Thermal-Magnetic Trip Unit 25 25 600 Vac Maximum, 250 Vdc, 35 kA at 480 Vac, Three-Pole E2K/E2KM Maximum Continuous Ampere Rating at 40°C Complete Breaker Frame Only Trip Unit Only Magnetic Trip Range Catalog Number Catalog Number Catalog Number 100 500–1000 E2K3100W E2K3400F E2K3100T 125 625–1250 E2K3125W E2K3400F E2K3125T 150 750–1500 E2K3150W E2K3400F E2K3150T 175 875–1750 E2K3175W E2K3400F E2K3175T 200 1000–2000 E2K3200W E2K3400F E2K3200T 225 300–650 E2K3225AW E2K3400F E2K3225TA 500–1000 E2K3225DW E2K3400F E2K3225TD 1125–2250 E2K3225W E2K3400F E2K3225T 250 1250–2500 E2K3250W E2K3400F E2K3250T 300 1500–3000 E2K3300W E2K3400F E2K3300T 350 1750–3500 E2K3350W E2K3400F E2K3350T 400 2000–4000 E2K3400W E2K3400F E2K3400T 25 25 25 25 25 25 25 25 25 25 1000Y/577 Vac Maximum, 250 Vdc, 14 kA at 1000 Vac, Three-Pole Maximum Continuous Ampere Rating at 40°C Complete Breaker Frame Only Trip Unit Only Magnetic Trip Range Catalog Number Catalog Number Catalog Number 100 500–1000 E2KM3100W E2KM3400F E2K3100T 125 625–1250 E2KM3125W E2KM3400F E2K3125T 150 750–1500 E2KM3150W E2KM3400F E2K3150T 175 875–1750 E2KM3175W E2KM3400F E2K3175T 200 1000–2000 E2KM3200W E2KM3400F E2K3200T 225 300–650 E2KM3225AW E2KM3400F E2K3225TA 500–1000 E2KM3225DW E2KM3400F E2K3225TD 1125–2250 E2KM3225W E2KM3400F E2K3225T 250 1250–2500 E2KM3250W E2KM3400F E2K3250T 300 1500–3000 E2KM3300W E2KM3400F E2K3300T 350 1750–3500 E2KM3350W E2KM3400F E2K3350T 400 2000–4000 E2KM3400W E2KM3400F E2K3400T 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com V4-T25-529 For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 25.5 25 25 25 25 25 Molded Case Circuit Breakers Specialty Breakers E2K/E2KM Circuit Breakers with Interchangeable Magnetic Only Trip Unit 600 Vac Maximum, 250 Vdc, 35 kA at 480 Vac, Three-Pole Maximum Continuous Ampere Rating at 40°C 400 Complete Breaker Frame Only Trip Unit Only Magnetic Trip Range Catalog Number Catalog Number Catalog Number E2K3400TMA 300–650 E2K3400MAW E2K3400F 500–1000 E2K3400MDW E2K3400F E2K3400TMD 625–1250 E2K3400MFW E2K3400F E2K3400TMF 750–1500 E2K3400MGW E2K3400F E2K3400TMG 875–1750 E2K3400MJW E2K3400F E2K3400TMJ 1000–2000 E2K3400MKW E2K3400F E2K3400TMK 25 1125–2250 E2K3400MLW E2K3400F E2K3400TML 1250–2500 E2K3400MWW E2K3400F E2K3400TMW 25 1500–3000 E2K3400MNW E2K3400F E2K3400TMN 1750–3500 E2K3400MRW E2K3400F E2K3400TMR 2000–4000 E2K3400MW E2K3400F E2K3400TM 25 25 25 25 25 25 25 25 1000Y/577 Vac Maximum, 250 Vdc, 14 kA at 1000 Vac, Three-Pole Maximum Continuous Ampere Rating at 40°C 400 Complete Breaker Frame Only Trip Unit Only Magnetic Trip Range Catalog Number Catalog Number Catalog Number 300–650 E2KM3250MAW E2KM3400F E2K3400TMA 500–1000 E2KM3400MDW E2KM3400F E2K3400TMD 625–1250 E2KM3400MFW E2KM3400F E2K3400TMF 750–1500 E2KM3400MGW E2KM3400F E2K3400TMG 875–1750 E2KM3400MJW E2KM3400F E2K3400TMJ 25 1000–2000 E2KM3400MKW E2KM3400F E2K3400TMK 1125–2250 E2KM3400MLW E2KM3400F E2K3400TML 25 1250–2500 E2KM3400MWW E2KM3400F E2K3400TMW 1500–3000 E2KM3400MNW E2KM3400F E2K3400TMN 1750–3500 E2KM3400MRW E2KM3400F E2K3400TMR 2000–4000 E2KM3400MW E2KM3400F E2K3400TM 25 25 25 25 25 25 25 25 25 25 25 25 25 V4-T25-530 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 Molded Case Circuit Breakers Specialty Breakers 25.5 E2K/E2KM 25 Circuit Breakers with Interchangeable Electronic Trip Unit, Long/Instantaneous 25 25 600 Vac Maximum, 35 kA at 480 Vac, Three-Pole Maximum Continuous Ampere Rating at 40°C Complete Breaker Frame Only Trip Unit Only Magnetic Trip Range Catalog Number Catalog Number Catalog Number 100 50–800 E2KE3100W E2K3400F KEM3100T 125 50–800 E2KE3125W E2K3400F KEM3125T 150 50–800 E2KE3150W E2K3400F KEM3150T 200 200–1500 E2KE3200W E2K3400F KEM3200T 225 200–1500 E2KE3225W E2K3400F KEM3225T 500–2500 E2KE32252W E2K3400F KEM3225T2 200–1500 E2KE3400W E2K3400F KEM3400T 500–2500 E2KE34002W E2K3400F KEM3400T2 400 25 25 25 25 25 25 25 1000Y/577 Vac Maximum, 14 kA at 1000 Vac, Three-Pole Maximum Continuous Ampere Rating at 40°C 25 Complete Breaker Frame Only Trip Unit Only Magnetic Trip Range Catalog Number Catalog Number Catalog Number 100 50–800 E2KEM3100W E2KM3400F KEM3100T 125 50–800 E2KEM3125W E2KM3400F KEM3125T 150 50–800 E2KEM3150W E2KM3400F KEM3150T 200 200–1500 E2KEM3200W E2KM3400F KEM3200T 225 200–1500 E2KEM3225 E2KM3400F KEM3225T 500–2500 E2KEM32252W E2KM3400F KEM3225T2 200–1500 E2KEM3400W E2KM3400F KEM3400T 500–2500 E2KEM34002W E2KM3400F KEM3400T2 400 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com V4-T25-531 For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 25.5 25 25 25 25 25 25 25 25 25 25 25 Specialty Breakers E2K/E2KM Circuit Breakers with Interchangeable Electronic Trip Unit, Instantaneous Only 600 Vac Maximum, 35 kA at 480 Vac, Three-Pole Maximum Continuous Ampere Rating at 40°C Complete Breaker Frame Only Trip Unit Only Magnetic Trip Range Catalog Number Catalog Number Catalog Number 150 50–800 E2KE3150MW E2K3400F KEM3150TM 225 200–1500 E2KE3225MW E2K3400F KEM3225TM 500–2500 E2KE3225M2W E2K3400F KEM3225TM2 200–1500 E2KE3400MW E2K3400F KEM3400TM 500–2500 E2KE3400M2W E2K3400F KEM3400TM2 Complete Breaker Frame Only Trip Unit Only 400 25 25 Molded Case Circuit Breakers 1000Y/577 Vac Maximum, 14 kA at 1000 Vac, Three-Pole Maximum Continuous Ampere Rating at 40°C Magnetic Trip Range Catalog Number Catalog Number Catalog Number 150 50–800 E2KEM3150MW E2KM3400F KEM3150TM 225 200–1500 E2KEM3225MW E2KM3400F KEM3225TM 500–2500 E2KEM3225M2W E2KM3400F KEM3225TM2 200–1500 E2KEM3400MW E2KM3400F KEM3400TM 500–2500 E2KEM3400M2W E2KM3400F KEM3400TM2 400 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 V4-T25-532 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 Molded Case Circuit Breakers Specialty Breakers 25.5 E2LME/E2LMZ (Series G) 25 Circuit Breakers with Magnetic Only Trip Unit 25 25 600 Vac Maximum, 250 Vdc, 65 kA at 480 Vac, Three-Pole Maximum Continuous Ampere Rating at 40°C 400 Magnetic Trip Range Complete Breaker Catalog Number Frame Only Catalog Number Trip Unit Only Catalog Number 25 3600–4400 E2LME3400KMW E2LME3400NN LT3400KM 25 25 1000Y/577 Vac Maximum, 250 Vdc, 10 kA at 1000 Vac, Three-Pole Maximum Continuous Ampere Rating at 40°C Magnetic Trip Range Complete Breaker Catalog Number Frame Only Catalog Number Trip Unit Only Catalog Number 400 3600–4400 E2LMZ3400KMW E2LMZ3400NN LT3400KM 25 25 25 25 Circuit Breakers with Interchangeable Electronic Trip Unit 25 600 Vac Maximum, 65 kA at 480 Vac, Three-Pole Maximum Continuous Ampere Rating at 40°C Magnetic Trip Range Complete Breaker Catalog Number Frame Only Catalog Number Trip Unit Only Catalog Number 160 320–1920 E2LME340031W E2LME3400NN LT340031M 200 400–2400 E2LME340031W E2LME3400NN LT340031M 225 450–2700 E2LME340031W E2LME3400NN LT340031M 250 500–3000 E2LME340031W E2LME3400NN LT340031M 300 600–3600 E2LME340031W E2LME3400NN LT340031M 315 630–3780 E2LME340031W E2LME3400NN LT340031M 350 700–4200 E2LME340031W E2LME3400NN LT340031M 400 800–4800 E2LME340031W E2LME3400NN LT340031M 25 25 25 25 25 25 25 25 1000Y/577 Vac Maximum, 10 kA at 1000 Vac, Three-Pole Maximum Continuous Ampere Rating at 40°C Magnetic Trip Range Complete Breaker Catalog Number Frame Only Catalog Number Trip Unit Only Catalog Number 160 320–1920 E2LMZ340031W E2LMZ3400NN LT340031M 200 400–2400 E2LMZ340031W E2LMZ3400NN LT340031M 225 450–2700 E2LMZ340031W E2LMZ3400NN LT340031M 250 500–3000 E2LMZ340031W E2LMZ3400NN LT340031M 300 600–3600 E2LMZ340031W E2LMZ3400NN LT340031M 315 630–3780 E2LMZ340031W E2LMZ3400NN LT340031M 350 700–4200 E2LMZ340031W E2LMZ3400NN LT340031M 400 800–4800 E2LMZ340031W E2LMZ3400NN LT340031M 25 25 25 25 25 25 25 25 25 25 25 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com V4-T25-533 For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 25.5 25 25 25 25 25 25 25 25 Molded Case Circuit Breakers Specialty Breakers E2L/E2LM Circuit Breakers with Interchangeable Thermal-Magnetic Trip Unit 600 Vac Maximum, 250 Vdc, 35 kA at 480 Vac, Three-Pole Maximum Continuous Ampere Rating at 40°C Complete Breaker Frame Only Trip Unit Only Magnetic Trip Range Catalog Number Catalog Number Catalog Number 300 1500–3000 E2L3300W E2L3600F E2L3300T 350 1750–3500 E2L3350W E2L3600F E2L3350T 400 2000–4000 E2L3400W E2L3600F E2L3400T 450 2250–4500 E2L3450W E2L3600F E2L3450T 500 2500–5000 E2L3500W E2L3600F E2L3500T 600 3000–6000 E2L3600W E2L3600F E2L3600T 25 25 1000Y/577 Vac Maximum, 250 Vdc, 18 kA at 1000 Vac, Three-Pole 25 Maximum Continuous Ampere Rating at 40°C 25 Complete Breaker Frame Only Trip Unit Only Magnetic Trip Range Catalog Number Catalog Number Catalog Number 300 1500–3000 E2LM3300W E2LM3600F E2L3300T 350 1750–3500 E2LM3350W E2LM3600F E2L3350T 400 2000–4000 E2LM3400W E2LM3600F E2L3400T 25 450 2250–4500 E2LM3450W E2LM3600F E2L3450T 500 2500–5000 E2LM3500W E2LM3600F E2L3500T 25 600 3000–6000 E2LM3600W E2LM3600F E2L3600T 1125–2250 — E2LM3600F E2L3600TL 25 25 25 Note 600 ampere thermal 1125–2250 T.A. 25 25 25 25 25 25 25 25 25 25 25 25 25 V4-T25-534 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 Molded Case Circuit Breakers Specialty Breakers 25.5 E2L/E2LM 25 Circuit Breakers with Interchangeable Magnetic Only Trip Unit 25 25 600 Vac Maximum, 250 Vdc, 35 kA at 480 Vac, Three-Pole Maximum Continuous Ampere Rating at 40°C 600 Complete Breaker Frame Only Trip Unit Only Magnetic Trip Range Catalog Number Catalog Number Catalog Number 1125–2250 E2L3600MLW E2L3600F E2L3600TML 1500–3000 E2L3600MNW E2L3600F E2L3600TMN 1750–3500 E2L3600MRW E2L3600F E2L3600TMR 2000–4000 E2L3600MXW E2L3600F E2L3600TMX 2250–4500 E2L3600MYW E2L3600F E2L3600TMY 2500–5000 E2L3600MPW E2L3600F E2L3600TMP 3000–6000 E2L3600MW E2L3600F E2L3600TM 25 25 25 25 25 25 25 1000Y/577 Vac Maximum, 250 Vdc, 18 kA at 1000 Vac, Three-Pole Maximum Continuous Ampere Rating at 40°C 600 Complete Breaker Frame Only Trip Unit Only Magnetic Trip Range Catalog Number Catalog Number Catalog Number 1125–2250 E2LM3600MLW E2LM3600F E2L3600TML 1500–3000 E2LM3600MNW E2LM3600F E2L3600TMN 1750–3500 E2LM3600MRW E2LM3600F E2L3600TMR 2000–4000 E2LM3600MXW E2LM3600F E2L3600TMX 2250–4500 E2LM3600MYW E2LM3600F E2L3600TMY 2500–5000 E2LM3600MPW E2LM3600F E2L3600TMP 3000–6000 E2LM3600MW E2LM3600F E2L3600TM 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com V4-T25-535 For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 25.5 25 25 25 25 25 25 Specialty Breakers E2L/E2LM Circuit Breakers with Interchangeable Electronic Trip Unit, Long/Instantaneous 600 Vac Maximum, 35 kA at 480 Vac, Three-Pole Maximum Continuous Ampere Rating at 40°C Complete Breaker Frame Only Trip Unit Only Magnetic Trip Range Catalog Number Catalog Number Catalog Number 300 500–2500 E2LE3300W E2L3600F LEM3300T 350 500–2500 E2LE3350W E2L3600F LEM3350T 400 500–2500 E2LE3400W E2L3600F LEM3400T 1000–4000 E2LE34002W E2L3600F LEM3400T2 500–2500 E2LE3600W E2L3600F LEM3600T 2500–5000 E2LE36002W E2L3600F LEM3600T2 Complete Breaker Frame Only Trip Unit Only 25 25 Molded Case Circuit Breakers 600 25 25 1000Y/577 Vac Maximum, 18 kA at 1000 Vac, Three-Pole 25 Maximum Continuous Ampere Rating at 40°C Magnetic Trip Range Catalog Number Catalog Number Catalog Number 25 300 500–2500 E2LEM3300W E2LM3600F LEM3300T 350 500–2500 E2LEM3350W E2LM3600F LEM3350T LEM3400T 25 25 400 600 25 25 500–2500 E2LEM3400W E2LM3600F 1000–4000 E2LEM34002W E2LM3600F LEM3400T2 500–2500 E2LEM3600W E2LM3600F LEM3600T 2500–5000 E2LEM36002W E2LM3600F LEM3600T2 Circuit Breakers with Interchangeable Electronic Trip Unit, Instantaneous Only 25 25 600 Vac Maximum, 35 kA at 480 Vac, Three-Pole 25 Maximum Continuous Ampere Rating at 40°C 25 25 400 600 25 25 25 25 Complete Breaker Frame Only Trip Unit Only Magnetic Trip Range Catalog Number Catalog Number Catalog Number LEM3400TM 500–2500 E2LE3400MW E2L3600F 1000–4000 E2LE3400M2W E2L3600F LEM3400TM2 500–2500 E2LE3600MW E2L3600F LEM3600TM 1000–4000 E2LE3600M2W E2L3600F 1483D53G50 Complete Breaker Frame Only Trip Unit Only Magnetic Trip Range Catalog Number Catalog Number Catalog Number LEM3400TM 1000Y/577 Vac Maximum, 18 kA at 1000 Vac, Three-Pole Maximum Continuous Ampere Rating at 40°C 25 400 25 600 500–2500 E2LEM3400MW E2LM3600F 1000–4000 E2LEM3400M2W E2LM3600F LEM3400TM2 500–2500 E2LEM3600MW E2LM3600F LEM3600TM 1000–4000 E2LEM3600M2W E2LM3600F 1483D53G50 25 25 25 V4-T25-536 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 Molded Case Circuit Breakers Specialty Breakers 25.5 E2M/E2MM 25 Circuit Breaker with Interchangeable Thermal-Magnetic Trip Unit 25 25 600 Vac Maximum, 250 Vdc, 35 kA at 480 Vac, Three-Pole E2M/E2MM Maximum Continuous Ampere Rating at 40°C Complete Breaker Frame Only Trip Unit Only Magnetic Trip Range Catalog Number Catalog Number Catalog Number 600 1500–3000 E2M3600W E2M3800F E2M3600TN 800 2000–4000 E2M3800W E2M3800F E2M3800TX 25 25 25 25 1000Y/577 Vac Maximum, 250 Vdc, 18 kA at 1000 Vac, Three-Pole Complete Breaker Frame Only Trip Unit Only 25 Magnetic Trip Range Catalog Number Catalog Number Catalog Number 25 600 1500–3000 E2MM3600W E2MM3800F E2M3600TN 800 2000–4000 E2MM3800W E2MM3800F E2M3800TX 25 Maximum Continuous Ampere Rating at 40°C 25 25 25 Circuit Breaker with Interchangeable Magnetic Only Trip Unit 25 25 600 Vac Maximum, 250 Vdc, 35 kA at 480 Vac, Three-Pole Maximum Continuous Ampere Rating at 40°C 800 Complete Breaker Frame Only Trip Unit Only Magnetic Trip Range Catalog Number Catalog Number Catalog Number 1500–3000 E2M3800MNW E2M3800F E2M3800TMN 2000–4000 E2M3800MXW E2M3800F E2M3800TMX 2500–5000 E2M3800MPW E2M3800F E2M3800TMP 3000–6000 E2M3800MWW E2M3800F E2M3800TMW 25 25 25 25 25 1000Y/577 Vac Maximum, 250 Vdc, 18 kA at 1000 Vac, Three-Pole Maximum Continuous Ampere Rating at 40°C 800 Complete Breaker Frame Only Trip Unit Only Magnetic Trip Range Catalog Number Catalog Number Catalog Number 1500–3000 E2MM3800MNW E2MM3800F E2M3800TMN 2000–4000 E2MM3800MXW E2MM3800F E2M3800TMX 2500–5000 E2MM3800MPW E2MM3800F E2M3800TMP 3000–6000 E2MM3800MWW E2MM3800F E2M3800TMW 25 25 25 25 25 25 25 25 25 25 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com V4-T25-537 For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 25.5 25 25 25 25 25 25 25 25 Specialty Breakers E2M/E2MM Circuit Breaker with Interchangeable Electronic Trip Unit, Long/Instantaneous 600 Vac Maximum, 35 kA at 480 Vac, Three-Pole Maximum Continuous Ampere Rating at 40°C 800 25 25 Molded Case Circuit Breakers Complete Breaker Frame Only Trip Unit Only Magnetic Trip Range Catalog Number Catalog Number Catalog Number 500–2500 E2ME3800W E2M3800F MEM3800T 1000–4000 E2ME38002W E2M3800F MEM3800T2 Complete Breaker Frame Only Trip Unit Only Magnetic Trip Range Catalog Number Catalog Number Catalog Number 500–2500 E2MEM3800W E2MM3800F MEM3800T 1000–4000 E2MEM38002W E2MM3800F MEM3800T2 1000Y/577 Vac Maximum, 18 kA at 1000 Vac, Three-Pole Maximum Continuous Ampere Rating at 40°C 800 25 25 25 25 25 25 Circuit Breaker with Interchangeable Electronic Trip Unit, Instantaneous Only 600 Vac Maximum, 35 kA at 480 Vac, Three-Pole Maximum Continuous Ampere Rating at 40°C 800 Complete Breaker Frame Only Trip Unit Only Magnetic Trip Range Catalog Number Catalog Number Catalog Number 500–2500 E2ME3800MW E2M3800F MEM3800TM 1000–4000 E2ME3800M2W E2M3800F MEM3800TM2 Complete Breaker Frame Only Trip Unit Only Magnetic Trip Range Catalog Number Catalog Number Catalog Number 500–2500 E2MEM3800MW E2MM3800F MEM3800TM 1000–4000 E2MEM3800M2W E2MM3800F MEM3800TM2 25 25 25 25 1000Y/577 Vac Maximum, 18 kA at 1000 Vac, Three-Pole Maximum Continuous Ampere Rating at 40°C 800 25 25 25 25 25 25 25 25 25 25 V4-T25-538 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 Molded Case Circuit Breakers Specialty Breakers 25.5 E2N/E2NM 25 Circuit Breakers with Electronic Trip Unit, Long/Instantaneous 25 25 600 Vac Maximum, 50 kA at 480 Vac, Three-Pole Frame Maximum Continuous Ampere Rating at 40°C Magnetic Trip Range Catalog Number 400 500–2500 E2N3400W 500 500–2500 E2N3500W 600 500–2500 E2N3600W 700 500–2500 E2N3700W 800 500–2500 E2N3800W 900 1250–5000 E2N3900W 1000 1250–5000 E2N310W 1200 1250–5000 E2N312W 25 25 25 25 25 25 1000Y/577 Vac Maximum, 25 kA at 1000 Vac, Three-Pole Frame 25 Maximum Continuous Ampere Rating at 40°C Magnetic Trip Range Catalog Number 25 400 500–2500 E2NM3400W 500 500–2500 E2NM3500W 25 600 500–2500 E2NM3600W 700 500–2500 E2NM3700W 800 500–2500 E2NM3800W 900 1250–5000 E2NM3900W 1000 1250–5000 E2NM310W 1200 1250–5000 E2NM312W 25 25 25 25 25 Circuit Breakers with Electronic Trip Unit, Instantaneous Only 25 600 Vac Maximum, 50 kA at 480 Vac, Three-Pole Frame Maximum Continuous Ampere Rating at 40°C Magnetic Trip Range Catalog Number 800 500–2500 E2N3800MW 1200 1250–5000 E2N312MW 25 25 25 25 1000Y/577 Vac Maximum, 25 kA at 1000 Vac, Three-Pole Frame Maximum Continuous Ampere Rating at 40°C Magnetic Trip Range Catalog Number 25 800 500–2500 E2NM3800MW 25 1200 1250–5000 E2NM312MW 25 25 25 25 25 25 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com V4-T25-539 For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 25.5 25 25 Molded Case Circuit Breakers Specialty Breakers E2R/E2RM Circuit Breakers with Electronic Trip Unit, Long/Instantaneous (Does Not Include Rating Plugs) 25 600 Vac Maximum, 50 kA at 480 Vac, Three-Pole Frame 25 Maximum Continuous Ampere Rating at 40°C Magnetic Trip Range Catalog Number 1600 2–8 x In E2R316T33W 25 2000 2–8 x In E2R320T33W 25 1600 2–8 x In E2R316T32W 2000 2–8 x In E2R320T32W 25 LS LSI 25 25 1000Y/577 Vac Maximum, 25 kA at 1000 Vac, Three-Pole Frame Magnetic Trip Range Catalog Number 1600 2–8 x In E2RM316T33W 25 2000 2–8 x In E2RM320T33W 25 1600 2–8 x In E2RM316T32W 2000 2–8 x In E2RM320T32W 25 25 25 25 Maximum Continuous Ampere Rating at 40°C LS LSI Note Rating plugs: 1600 amperes 16RES16T; 2000 amperes 20RES20T. 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 V4-T25-540 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 Molded Case Circuit Breakers Specialty Breakers 25.5 Accessories 25 Line and Load Terminals Breaker Type Maximum Breaker Amperes Wire Type AWG Wire Range (No. Conductors) Catalog Number E2F/E2FM 100 Cu/AI #14–1/0 (1) 3T100FB (package of three) 150 Cu #4–4/0 (1) 3T150FB (package of three) E2J/E2JM 250 Cu #4–350 (1) T250KB E2K/E2KM 225 Cu #3–350 (1) T300K 350 Cu 250–500 (1) T350K 400 Cu 2/0–250 (2) 3T400K (three-pole kit) E2LME/E2LMZ 400 Cu/AI 500–750 (1) 3TA631LK E2L/E2LM 400 Cu/AI 4/0–600 (1) 3TA401LDK (three-pole kit) 600 Cu 250–350 (2) T602LD 600 Cu (2) 2/0–500 kcmil T600MA1 600 Cu/AI (2) 1–500 kcmil TA700MA1 800 std. Cu/AI (3) 3/0–400 kcmil TA800MA2 800 Cu/AI (2) 500–750 kcmil TA801MA E2M/E2MM E2N/E2NM 800 Cu (3) 3/0–300 kcmil T800MA1 700 Cu 2/0–500 (2) T700NB1 1000 Cu 3/0–500 (3) T1000NB1 1200 Cu 3/0–400 (4) T1200NB3 1600 Cu/AI 500–1000 (4) TA1600RD 2000 Cu/AI 2–600 (6) TA2000RD 25 25 25 25 25 25 25 25 25 25 25 25 25 25 End Cap Terminals—For Use with Ring Type Terminals Breaker Type Maximum Breaker Amperes Catalog Number Metric Catalog Number Imperial E2F/E2FM 150 KPEK1 KPEMK1 — E2J/E2JM 250 KPEK2 KPEMK2 — E2K/E2KM 400 KPEK3 KPEMK3 — 25 E2LME/E2LMZ 400 — L3RTWK — E2L/E2LM 600 KPEK4 KPEMK4 — 25 25 25 25 External Accessories 25 Padlockable Handle Lock Hasp Breaker Type 25 Catalog Number E2F/E2FM PLK1 E2J/E2JM PLK3 E2K/E2KM PLK3 E2LME/E2LMZ LPHL E2L/E2LM HLK4 E2M/E2MM HLK4 E2N/E2NM PLK5 E2R/E2RM HLK6 25 25 25 25 25 25 25 25 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com V4-T25-541 For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 25.5 25 25 25 25 Specialty Breakers Internal Accessories Undervoltage Release Breaker Type UVR Type Voltage Rating Mounting Location Catalog Number Factory Modification Code E2F/E2FM Handle reset 208–240 Vac Left pole UVH1LP11K (thermal/magnetic only) U18 Handle reset 110–127 Vdc Left pole UVH1LP26K (thermal/magnetic only) U42 Handle reset 110–127 Vac Left pole UVH2LP08K U18 Handle reset 208–240 Vac Left pole UVH2LP11K U22 Handle reset 110–125 Vdc Left pole UVH2LP26K T14 120 volt handle reset with LED 120 Vac Left pole UVM3LP08K E2J/E2JM 25 25 Molded Case Circuit Breakers E2K/E2KM U66 25 120 volt handle reset with LED 120 Vac Left pole UVM3LP08KT Handle reset 110–127 Vac Left pole UVH3LP08K U18 25 Handle reset 208–240 Vac Left pole UVH3LP11K U22 Handle reset 110–125 Vdc Left pole UVH3LP26K T14 Handle reset 110–127 Vac Left pole UVR120APK U5 Handle reset 110–125 Vdc Left pole UVR125DPK U6 120 volt handle reset with LED 120 Vac Left pole UVM4LP08K U66 25 120 volt handle reset with LED 120 Vac Left pole UVM4LP08KT U68 Handle reset 110–127 Vac 25 Handle reset 208–240 Vac Handle reset 25 E2LME/E2LMZ 25 E2L/E2LM/E2M/E2MM 25 E2N/E2NM 25 25 25 E2R/E2RM 25 25 25 25 25 U68 Left pole UVH4LP08K U18 Left pole UVH4LP11K U22 110–125 Vdc Left pole UVH4LP26K T14 120 volt handle reset with LED 120 Vac Left pole UVM5LP08K U66 120 volt handle reset with LED 120 Vac Left pole UVM5LT08K U68 Handle reset 110–127 Vac Left pole UVH5LP08K U18 Handle reset 208–240 Vac Left pole UVH5LP11K U22 Handle reset 110–125 Vdc Left pole UVH5LP26K T14 120 volt handle reset with LED 120 Vac Right pole UVM6RP08K Handle reset 110–127 Vac Right pole UVH6RP08K U58 U49 Handle reset 208–240 Vac Right pole UVH6RP11K U53 Handle reset 110–125 Vdc Right pole UVH6RP26K T33 Notes Contact Eaton for internal accessory voltage ratings not listed. LH (RH also available). Pigtail leads. Terminal blocks. RH only. 25 25 25 25 25 25 25 25 25 V4-T25-542 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 Molded Case Circuit Breakers Specialty Breakers Shunt Trip 25.5 Alarm (Signal/Lockout Switch) Breaker Type Voltage Rating E2F/E2FM 48–127 Vac or 48–60 Vdc E2J/E2JM Mounting Location Left pole Factory Modification Code Catalog Number SNT1LP08K 208–230 Vac or 110–127 Vdc Left pole SNT1LP12K 110–240 Vac or 110–125 Vdc Left pole SNT2P11K S06 Breaker Type E2F/E2FM S10 E2J/E2JM S10 E2K/E2KM Number of Sets of Contacts (Make and Mounting Break) Location 25 Catalog Number Factory Modification Code 1 Right A1L1LPK/A1L1RPK B06 2 Right A2L1LPK/A2L1RPK B13 1 Right A1L2LPK/A1L2RPK B06 1 Right A1L3LPK/A1L3RPK B06 2 Right A2L3LPK/A2L3RPK B13 E2K/E2KM 110–240 Vac or 110–125 Vdc Left pole SNT3P11K 1 Right ALM1M1BJPK B1 E2LME/E2LMZ 24–60 Vac/Vdc Left pole SNT060CPK S1 2 Right ALM2M2BJPK B3 110–240 Vac/Vdc Left pole SNT120CPK S2 E2L/E2LM/E2M/E2MM 1 Right A1L4LPK/A1L4RPK B06 48–60 Vac Left pole SNT4LP05K S06 2 Right A2L4LPK/A2L4RPK B13 48–60 Vdc Left pole SNT4LP23K S86 1 Right A1L5LPK/A1L5RPK B06 110–240 Vac Left pole SNT4LP11K S10 2 Right A2L5LPK/A2L5RPK B13 110–125 Vdc Left pole SNT4LP26K S42 1 Right A1L6RPK B05 110–240 Vac Left pole SNT5LP11K S10 2 Right A2L6RPK B12 110–125 Vdc Left pole SNT5LP26K S42 110–240 Vac Right pole SNT6P11K S29 110–125 Vdc Right pole SNT6P26K S45 E2L/E2LM/E2M/E2MM E2N/E2NM E2R/E2RM S10 E2LME/E2LMZ E2N/E2NM E2R/E2RM Notes Contact Eaton for internal accessory voltage ratings not listed. LH (RH also available). LH or RH. RH only. E2F/E2FM E2J/E2JM E2K/E2KM E2LME/E2LMZ E2L/E2LM/E2M/E2MM E2N/E2NM E2R/E2RM 25 25 25 25 25 25 25 25 25 25 25 Auxiliary Switch Breaker Type 25 Number of Sets of Contacts Mounting (1A and 1B) Location Catalog Number Factory Modification Code 25 25 1 Right A1X1PK A06 2 Right A2X1RPK A13 1 Right A1X2PK A06 2 Right A2X2PK A13 1 Right A1X3PK A06 2 Right A2X3PK A13 1 Right AUX1A1BPK A1 2 Right AUX2A2BPK A2 1 Right A1X4PK A06 2 Right A2X4PK A13 1 Right A1X5PK A06 2 Right A2X5PK A13 2 Right A2X6RPK A12 4 Right A4X6RPK A19 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com V4-T25-543 For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 25.5 Molded Case Circuit Breakers Specialty Breakers 25 Contents 25 E2 Mining Service Breakers . . . . . . . . . . . . . . . . . . Product Overview . . . . . . . . . . . . . . . . . . . . . . Product Selection . . . . . . . . . . . . . . . . . . . . . . . Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . Classic Mining Breakers. . . . . . . . . . . . . . . . . . . . . Product Selection . . . . . . . . . . . . . . . . . . . . . . . Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . Reference Information . . . . . . . . . . . . . . . . . . . . . . Description 25 25 25 25 Page V4-T25-521 V4-T25-521 V4-T25-525 V4-T25-541 V4-T25-544 V4-T25-546 V4-T25-551 V4-T25-553 25 25 25 25 25 Classic Mining Breakers 25 Product Overview 25 25 25 Classic mining service circuit breakers continue to be manufactured and are primarily applied to achieve an exact physical and electronic replacement of previously Cutler-Hammer installed Westinghouse equipment. To upgrade to the current offering of E2 mining circuit breakers, consult the cross reference information on Page V4-T25-553. 25 25 25 25 25 AC Interrupting Capacity, Symmetrical Amperes Breaker Type 60 Hz AC Volts KAM LAM, MAM, NBM HKAM HLAM All Other 1000 Volt Breakers 240 25,000 42,000 — — — 480 22,000 30,000 — — — 600 22,000 22,000 — — — 1000 — — 10,000 12,000 14,000 25 25 Special DC Interrupting Capacity Interrupting Capacity (Amperes) at 300–330 Vdc 25 25 25 25 25 25 25 Two Poles in Series Single-Pole Breaker Type Maximum Ampere Rating 0.0–0.15 mH Inductance 0.15–0.5 mH Inductance 0.5–0.9 mH Inductance 2.4 mH Inductance KAM 225 15,000 10,000 15,000 5000 LAM 400/600 15,000 10,000 15,000 5000 MAM 800 15,000 10,000 15,000 5000 NBM 1200 15,000 10,000 15,000 5000 Notes Based on circuit power factor of 50% or greater. HLAM must be rear stud connected. If front connected, interrupting capacity rating is 10,000 amperes. Resistive circuit. Two poles in electrical series in ungrounded leg of circuit. 25 V4-T25-544 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 Molded Case Circuit Breakers Specialty Breakers 25.5 Classic Circuit Breakers For Mining Service 25 Undervoltage Release Data Undervoltage releases are calibrated to pick up at 72 to 85% of rated voltage dropout between 35 to 70% of rated voltage. Breaker Type Volts Line Amperes Series Resistors Total VA KAM, HKAM 480/60 0.021 10,000 10.1 240/60 0.019 — 4.6 120/60 0.021 — 2.5 120/60 0.13 — 15.6 480/60 0.033 12,000 15.9 240/60 0.028 6,000 6.7 LAM, HLAM, MAM, HMAM, NBM, HNBM 120/60 0.029 — 3.5 120/60 0.13 — 15.6 25 25 25 25 25 25 25 25 Shunt Trip Coil Data Breaker Type KAM, HKAM, LAM, HLAM, MAM, HMAM, NBM, HNBM 25 Volts Amperes VA 480/60 0.085 40.8 240/60 1.7 408 120/60 0.88 105.6 48 DC 8.0 384 25 25 25 Notes Supplied for external customer mounting. New design electrical reset UVR. 16,000 for Type MAM and HMAM. 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com V4-T25-545 For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 25.5 25 25 Molded Case Circuit Breakers Specialty Breakers Product Selection For reference only. Replace these frames with E2 Series. See Cross-Reference information beginning on Page V4-T25-553. Classic Mining Service Circuit Breakers 25 Breaker Type Frame Style Numbers Poles Amperes Trip Type Accessories (Included in Frame) 25 KAM 2609D60G64 2 180 M None 200–400 1291C26G07 2 180 M UVR 200–400 2609D60G66 2 180 M Standard shunt trip 200–400 25 1291C26G01 2 225 TM UVR 300–700 1291C26G02 2 225 TM UVR 500–1000 25 2609D60G67 3 180 M None 200–400 1291C26G08 3 180 M UVR 200–400 25 2609D60G69 3 180 M Standard shunt trip 200–400 5685D48G75 3 225 TM None 300–700 5685D48G74 3 225 TM None 500–1000 1291C26G03 3 225 TM UVR 300–700 1291C26G04 3 225 TM UVR 500–1000 2609D60G01 3 225 TM Standard shunt trip 300–700 2609D60G02 3 225 TM Standard shunt trip 500–1000 2609D60G40 3 225 M None 300–700 2609D60G41 3 225 M None 500–700 25 25 25 25 25 25 25 LAM 25 25 25 25 25 25 25 Magnetic Trip Range, Amperes 1291C26G05 3 225 M UVR 1291C26G06 3 225 M UVR 500–1000 1291C32G01 2 400 TM UVR 500–1000 2609D60G61 2 400 M Shunt trip (48 Vdc) 750–1500 1291C32G03 3 400 TM UVR 500–1000 5685D48G73 3 400 TM None 800–1600 1291C32G02 3 400 TM UVR 800–1600 2609D60G03 3 400 TM Standard shunt trip 800–1600 2609D60G44 3 400 M None 800–1600 1291C32G04 3 400 M UVR 800–1600 300–700 Notes Terminals not included in style number. All breakers listed are complete with accessories indicated. Rated 120 volts/60 Hz: undervoltage release is handle reset type. UVR is auto-reset type, 120 Vac. M = magnetic only; TM = thermal-magnetic. 25 25 25 25 25 25 25 25 25 V4-T25-546 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 25.5 Molded Case Circuit Breakers Specialty Breakers For reference only. Replace these frames with E2 Series. See Cross-Reference information beginning on Page V4-T25-553. Classic Mining Service Circuit Breakers, continued Breaker Type Frame Style Numbers Poles Amperes Trip Type Accessories (Included in Frame) Magnetic Trip Range, Amperes MAM 2609D60G17 2 600 TM UVR 750–1500 1000–2000 2000–4000 NBM 2609D60G18 2 800 TM UVR 2609D60G63 3 400 TM UVR 5685D48G72 3 600 TM None 1500–3000 2609D60G19 3 600 TM UVR 1500–3000 2609D60G04 3 600 TM Standard shunt trip 1500–3000 2000–4000 2609D60G05 3 800 TM Standard shunt trip 5685D48G71 3 800 TM None 2000–4000 2609D60G20 3 800 TM UVR 2000–4000 2609D60G46 3 800 M None 1500–3000 2609D60G47 3 800 M UVR 1500–3000 2609D60G48 3 800 M None 2000–4000 2609D60G49 3 800 M UVR 2000–4000 1229C37G13 2 1000 TM UVR 1500–3000 1229C37G14 2 1200 TM UVR 2000–4000 1227C36G10 3 1000 TM None 2500–5000 1229C37G15 3 1000 TM UVR 2500–5000 1227C36G13 3 1000 TM Standard shunt trip 2500–5000 1227C36G14 3 1200 TM Standard shunt trip 2500–5000 1227C36G09 3 1200 TM None 2500–5000 1229C37G16 3 1200 TM UVR 2500–5000 1227C36G19 3 1200 M None 2500–5000 1229C37G17 3 1200 M UVR 2500–5000 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 Notes Terminals not included in style number. All breakers listed are complete with accessories indicated. Rated 120 volts/60 Hz: undervoltage release is handle reset type. UVR is auto-reset type, 120 Vac. 25 M = magnetic only; TM = thermal-magnetic. 25 25 25 25 25 25 25 25 25 25 25 25 25 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com V4-T25-547 For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 25.5 Molded Case Circuit Breakers Specialty Breakers 1000 Volt Classic Mining Service Circuit Breakers 25 Breaker Type Frame Style Numbers Poles Amperes Trip Type Accessories (Included in Frame) HKAM 2609D60G70 3 180 M None 200–400 1291C26G16 3 180 M UVR 200–400 5685D48G87 3 225 TM None 300–700 1291C26G12 3 225 TM UVR 300–700 5685D48G86 3 225 TM None 500–1000 1291C26G13 3 225 TM UVR 500–1000 1291C26G14 3 225 M UVR 300–700 1291C26G15 3 225 M UVR 500–1000 5685D48G85 3 400 TM None 800–1600 1291C32G07 3 400 TM UVR 800–1600 1291C32G09 3 400 M UVR 800–1600 5685D48G84 3 600 TM None 1500–3000 25 2609D60G28 3 600 TM UVR 1500–3000 5685D48G83 3 800 TM None 2000–4000 25 2609D60G29 3 800 TM UVR 2000–4000 2609D60G57 3 800 M UVR 1500–3000 2609D60G58 3 800 M UVR 2000–4000 1227C36G12 3 1000 TM None 2500–5000 1229C37G19 3 1000 TM UVR 2500–5000 1227C36G11 3 1200 TM None 2500–5000 1229C37G20 3 1200 TM UVR 2500–5000 1229C37G18 3 1200 M UVR 2500–5000 25 HKAM 25 25 25 25 Magnetic Trip Range, Amperes 25 25 HLAM HLAM 25 25 25 25 HMAM HMAM 25 25 25 25 HNBM HNAM 25 25 25 25 25 Notes The magnetic trip range does not change when rating plug is changed. 120 volt, 60 Hz electrical reset type. Rated 120 volts, 60 Hz; undervoltage release is handle reset type. 25 25 M = magnetic only; TM = thermal-magnetic. 25 25 25 25 25 V4-T25-548 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 25.5 Molded Case Circuit Breakers Specialty Breakers Classic Mining Service Breaker Frames Only Breaker Type Frame Size, Amperes Style Number of Poles Numbers Breaker Type Frame Size, Amperes Style Number of Poles Numbers KAM 225 2 MAM 800 2 2600D43G11 225 3 2602D86G12 800 3 2600D43G12 KAMH 225 2 2602D86G13 800 2 2600D43G13 225 3 2602D86G14 800 3 2600D43G14 HKAM 225 3 1264C99G05 HMAM 800 3 1264C99G03 LAM 400 2 2602D99G05 NBM 1200 2 2610D64G07 400 3 2602D99G06 1200 3 2610D64G08 400 2 2602D99G07 1200 2 2610D64G09 400 3 2602D99G08 1200 3 2610D64G10 1200 3 2610D64G13 LAMH 2602D86G11 400 3 1264C99G02 LAM3600F 600 3 2603D48G07 LAMH3600F 600 3 2603D48G08 HLAM3600F 600 3 2603D48G09 HLAM MAMH NBMH HNBM 25 25 25 25 25 25 25 25 25 25 Trip Units for Classic Mining Circuit Breakers Breaker Type HKAM HLAM HLAM600 HMAM HNBM Conductor Size Magnetic Trip Range, Amperes Maximum Continuous Amperes Thermal-Magnetic Three-Pole Style Numbers Magnetic Only Three-Pole Style Numbers #6 150–400 180 — 2609D99G22 #4–#3 300–700 225 5685D48G40 2611D75G01 #4–#1 500–1000 225 5685D48G34 2611D75G02 #4–#1 750–1500 400 5685D48G97 2609D99G21 #2–#2/0 800–1600 400 5685D48G28 2611D75G03 #2–2/0 750–1500 600 2609D99G20 — 2/0–500 kcmil 1500–3000 600 2609D99G19 — 25 25 25 25 25 25 #2–#2/0 750–1500 600 — — 2/0–500 kcmil 1500–3000 600 5685D48G22 2611D75G04 #1–3/0 1000–2000 800 — — 3/0–500 kcmil 2000–4000 800 5685D48G16 2611D75G05 2/0–500 kcmil 1500–3000 1000 — — 4/0–500 kcmil 2500–5000 1000 5685D48G10 — 3/0–500 kcmil 2000–4000 1200 — — 4/0–500 kcmil 2500–5000 1200 5685D48G04 2611D75G07 25 25 25 25 Notes Frame modified for left-hand mounting of UVR attachment. Frame modified for right-hand mounting of UVR attachment. Three-pole trip units only are suitable for replacement in 1000 volt mining service circuit breakers. 800 amperes. 25 25 25 25 25 25 25 25 25 25 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com V4-T25-549 For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 25.5 25 25 25 Molded Case Circuit Breakers Specialty Breakers Terminals For Classic Mining Service Breakers Terminals are UL listed for wire type and range listed below. When used with aluminum conductors, use joint compound. Breaker Type FBM, HFBM 25 Terminal Type Maximum Amperes Package of 3 Line Terminals Style Number Wire Range, Type Style pressure type terminals 100 624B100G02 #14–1/0 Al/Cu Optional Al/Cu pressure terminals 50 624B100G10 #14–#4 Al/Cu 100 624B100G17 # 4–4/0 Al/Cu 25 25 25 Terminals For Mining Service Breakers Breaker Type Terminal Type KAM, HKAM 25 25 LAM 25 25 MAM, HMAM, MAMH 225 T225LA (1) #6–350 kcmil 225 TA225LA1 (1) #6–350 kcmil Cu, or (1) #4–350 kcmil Al Standard copper pressure terminals 225 T225LA (1) #6–350 kcmil Cu 400 T401LA (1) #4–250 kcmil Cu plus (1) 3/0–600 kcmil Cu 225 TA225LA1 (1) #6–350 kcmil Cu, or (1) #4–350 kcmil Al 400 TA400LA1 (1) #4–250 kcmil Al/Cu, plus (1) 3/0–600 kcmil Al/Cu 400 TA401LA (1) 600–750 kcmil Al Standard copper pressure terminals 600 T600LA (2) 250–500 kcmil Cu Optional Al/Cu pressure terminals 600 TA600LA (2) 250–500 kcmil Al/Cu Standard copper pressure terminals 350 T350MA (1) #1–600 kcmil Cu 600 T600MA1 (2) 2/0–500 kcmil Cu 800 T800MA1 (3) 3/0–300 kcmil Cu 600 TA700MA1 (2) #1–500 kcmil Al/Cu 800 TA800MA2 (3) 3/0–400 kcmil Al/Cu 800 TA801MA (2) 500–750 kcmil Al/Cu 1000 T1000NB1 (3) 3/0–500 kcmil Cu 1200 T1200NB1 (4) 3/0–400 kcmil Cu 1000 TA1000NB1 (3) 3/0–400 kcmil Al/Cu 1200 TA1200NB1 (4) 4/0–500 kcmil Al/Cu 1200 TA1201NB1 (3) 500–750 kcmil Al/Cu 25 Optional Al/Cu pressure terminals 25 25 NBM, HNBM, NBMH 25 Standard copper pressure terminals Optional Al/Cu pressure terminals 25 Wire Range, Type Number of Cables Standard pressure terminals (copper only) 25 25 Terminal Catalog Number Optional Al/Cu pressure terminals Optional Al/Cu pressure terminals LAM-600, LAMH-600, HLAM-600 Maximum Amperes 25 25 25 25 25 25 25 25 25 25 25 25 V4-T25-550 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 Molded Case Circuit Breakers Specialty Breakers 25.5 Accessories 25 Classic Mining Circuit Breakers Rear Connected Studs For complete stud assembly, order a stud and tube based on thickness of customer’s mounting panel. A short stud must be assembled adjacent to a long stud to maintain Mounting Panel Thickness In Inches (mm) Stud Length Style Numbers 25 Rear Connected Studs For Insulated Panels Only: Two Per Pole clearances required by Underwriters Laboratories. Two studs required per pole. For List Prices, see Eaton’s Price and Availability Digest. Tube Length In Inches (mm) Style Numbers Stud Style Numbers 0.50 (12.7)–13 3.22 (81.8) 1241 345 0.50 (12.7)–13 6.28 (159.5) 1241 346 225 0.50 (12.7)–13 4.97 (126.2) 1241 392 400 0.75 (19.1)–16 5.47 (138.9) 05B7383G22 0.75 (19.1)–16 7.97 (202.4) 05B7383G23 656D565G01 0.84 (21.3) 0.75 (19.1)–16 10.47 (265.9) 05B7383G24 1.00 (25.4)–12 5.91 (150.1) 314C960G16 1.00 (25.4)–12 8.41 (213.6) 314C960G17 1.00 (25.4)–12 10.91 (277.1) 314C960G18 25 25 225 456D983H05 Long 656D565G02 3.78 (96.0) 456D983H08 0.50 (12.7)–0.75 (19.1) Short 656D565G01 1.09 (27.7) 456D983H06 Long 656D565G02 4.03 (102.4) 456D983H09 0.25 (6.4)–0.50 (12.7) Diameter, In Inches (mm) and Thread 25 LAM, HLAM Breakers KAM, HKAM Breakers 0.75 (19.1)–1.00 (25.4) Short 25 Extension Back of Breaker In Inches (mm) Stud Ampere Number 600 Short 656D565G01 1.34 (34.0) 456D983H07 MAM, HMAM, MAMH Breakers Long 656D565G02 4.28 (108.7) 456D983H10 225 0.50 (12.7)–13 3.66 (93.0) 314C960G01 400 0.75 (19.1)–16 5.91 (150.1) 314C960G04 0.75 (19.1)–16 8.41 (213.6) 314C960G05 0.75 (19.1)–16 10.91 (277.1) 314C960G06 1.00 (25.4)–12 5.91 (150.1) 314C960G07 1.00 (25.4)–12 8.41 (213.6) 314C960G08 1.00 (25.4)–12 10.91 (277.1) 314C960G09 600 800 1200 25 25 25 25 25 25 4.91 (124.7) 314C960G10 8.41 (213.6) 314C960G11 1.13 (28.7)–12 10.91 (277.1) 314C960G12 25 1.13 (28.7)–12 5.50 (139.7) 623B222G01 25 1.13 (28.7)–12 8.00 (203.2) 623B222G02 1.13 (28.7)–12 10.50 (266.7) 623B222G03 1.25 (31.8)–12 5.50 (139.7) 373B375G04 1.25 (31.8)–12 10.50 (266.7) 373B375G03 25 25 25 25 Breaker Type Description Style Numbers KAM Line terminals 1261C93G01 Load terminals 1262C46G01 Line terminals 1261C95G01 Load terminals 1262C48G01 Line terminals 1261C97G01 Load terminals 1261C97G02 MAM 25 1.13 (28.7)–12 Line and Load Terminal Shields LAM-400 25 1.13 (28.7)–12 NBM, HNBM, NBMH Breakers 800 25 Notes Not UL Iisted. 400 ampere LA studs of the same length have sufficient clearance; however, customer connections may make it necessary to use a short stud adjacent to a long stud. 150, 300 and 400 ampere frames only. This is a special stud that includes six contact nuts for use where bus contact nuts must be used. For breakers used with terminals and cable connections. Sold in packages of 10. 25 25 25 25 25 25 25 25 25 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com V4-T25-551 For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 25.5 Molded Case Circuit Breakers Specialty Breakers Standard Handle Reset Undervoltage Release For Classic breakers field when voltage drops below mountable on special frames 35 to 70% of coil rating. Picks listed on Page V4-T25-553, up and seals in at 72 to 85% or replacement on breakers of coil rating. For line voltages originally equipped with this up to 250 Vdc or 600 Vac. type UVR. Externally mounted resistors are supplied for certain ratings. For undervoltage protection. Standard leads extend 18.00 A solenoid device mounts inches (457.2 mm) outside of within breaker case. Coil breaker. Longer leads may must be energized before be specified. closing breaker. Trips breaker Shunt Trips For tripping breaker from a remote point. A solenoid device mounts within breaker case. Breaker trips when coil is energized. A cutoff switch breaks the circuit to the momentary rated coil when breaker opens. Available for 25 Breaker Type KAM, HKAM Volts Style Numbers 25 Right-Hand Mounting 120 Vac 4995D12G11 LAM, HLAM 120 Vac 25 25 25 25 25 25 LAM, HLAM 25 25 25 MAM, HMAM, MAMH 25 25 25 NBM, HNBM, NBMH 25 25 Breaker Type 25 25 Volts (50–60 Hz) Style Numbers Right-Hand Mounting 480 Vac 2605D15G16 240 Vac 2605D15G17 120 Vac 2605D15G19 480 Vac 2606D56G16 1228C76G03 240 Vac 2606D56G17 240 Vac 4995D12G13 120 Vac 2606D56G19 480 Vac 4995D12G14 48 Vdc 2606D56G07 125 Vdc 4995D12G09 480 Vac 2606D57G16 120 Vac 5672D69G11 240 Vac 2606D57G17 120 Vac — 120 Vac 2606D57G19 240 Vac 5672D69G13 480 Vac 2606D58G16 480 Vac 5672D69G14 240 Vac 2606D58G17 120 Vac 4995D11G11 120 Vac 2606D58G19 120 Vac 1229C35G03 Left-Hand Mounting 240 Vac 4995D11G13 KAM, HKAM 480 Vac 4995D11G14 MAM, HMAM, MAMH NBM, HNBM, NBMH Left-Hand Mounting KAM, HKAM control voltages up to 250 Vdc or 600 Vac. Voltage and frequency must be specified. Standard leads extend 18.00 inches (457.2 mm) outside of breaker. Longer leads may be specified. 480 Vac 2605D15G02 240 Vac 2605D15G03 120 Vac 2605D15G05 480 Vac 2606D56G02 120 Vac 4995D10G01 120 Vac 1228C76G03 240 Vac 2606D56G03 240 Vac 4995D10G03 120 Vac 2606D56G05 480 Vac 4995D10G04 480 Vac 2606D57G02 240 Vac 2606D57G03 120 Vac 2606D57G05 480 Vac 2606D58G02 240 Vac 2606D58G03 120 Vac 2606D58G05 25 25 LAM, HLAM MAM, HMAM, MAMH NBM, HNBM, NBMH 25 Notes Electrical reset UVR. Auto reset type. 25 25 25 25 25 25 25 25 25 V4-T25-552 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 Molded Case Circuit Breakers Specialty Breakers 25.5 Reference Information E2 25 Cross-Reference Series C Mining Superseded by E2 Mining Series C Mining Superseded by E2 Mining 1491D72G31 E2J3070T FDBM3040 E2F3040 1491D72G32 E2J3090T FDBM3045 E2F3045 1491D72G33 E2J3100T FDBM3050 E2F3050 1491D72G37 E2J3200T FDBM3050U62 E2F3050U62 6622C87G27 E2K3225AWU66 FDBM3050WU62 E2F3050WU62 6622C87G28 E2K3225DWU66 FDBM3060 E2F3060 6622C87G32 E2K3400GWU66 FDBM3070 E2F3070 E2KM3100 E2KEM3100W FDBM3070WU62 E2F3070WU62 E2KM3100U66 E2KEM3100WU66 FDBM3080 E2F3080 E2KM3125 E2KEM3125W FDBM3090 E2F3090 E2KM3125U66 E2KEM3125WU66 FDBM3100 E2F3100 E2KM3150 E2KEM3150W FDBM3100LM04U62 E2F3100M04U62 E2KM3150MU66 E2KEM3150WU66 FDBM3125 E2F3125 E2KM3150TM E2KEM3150MW FDBM3150 E2F3150 E2KM3150U66 E2KEM3150MWU66 FDBM3150L E2F3150L E2KM3200 E2KEM3200W FDM3015 E2F3015 E2KM3200U66 E2KEM3200WU66 FDM3015L E2F3015L E2KM3225 E2KEM3225W FDM3015LU62 E2F3015LU62 E2KM3225F E2KM3400F FDM3020 E2F3020 E2KM3225FUV E2KM3400F FDM3020LU62 E2F3020LU62 E2KM3225MU66 E2KEM3225MWU66 FDM3025 E2F3025 E2KM3225TM E2KEM3225TM FDM3025L E2F3025L E2KM3225U66 E2KEM3225WU66 FDM3025LS22 E2F3025LS22 E2LM3300U66 E2LEM3300WU66 FDM3025LU62 E2F3025LU62 E2LM3350U66 E2LEM3350WU66 FDM3030 E2F3030 E2LM34002U66 E2LEM34002WU66 FDM3030LS22 E2F3030LS22 E2LM3400F E2LM3600F FDM3040 E2F3040 E2LM3400FUV E2LM3600F FDM3040L E2F3040L E2LM3400M2U66 E2LEM3400M2WU66 FDM3040LU62 E2F3040LU62 E2LM3400MU66 E2LEM3400MWU66 FDM3050 E2F3050 E2LM3400U66 E2LEM3400WU66 FDM3050LU62 E2F3050LU62 FDBM3015 E2F3015 FDM3050U62 E2F3050U62 FDBM3015WU62 E2F3015WU62 FDM3060 E2F3060 FDBM3020 E2F3020 FDM3060LU62 E2F3060LU62 FDBM3025 E2F3025 FDM3070 E2F3070 FDBM3025U62 E2F3025U62 FDM3070A02U62 E2F3070A02U62 FDBM3030 E2F3030 FDM3080 E2F3080 FDBM3030U62 E2F3030WU62 FDM3090 E2F3090 FDBM3030WU62 E2F3030WU62 FDM3100 E2F3100 FDBM3035 E2F3035 FDM3100LS22 E2F3100LS22 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com V4-T25-553 For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 25.5 25 Molded Case Circuit Breakers Specialty Breakers E2 Cross-Reference, continued Superseded by E2 Mining Series C Mining Superseded by E2 Mining FDM3100LU62 E2FLU62 JDCM3150W E2JM3150W FDM3125 E2F3125 JDCM3175W E2JM3175W FDM3125LU62 E2F3125LU62 JDCM3200W E2JM3200W FDM3150 E2F3150 JDCM3225A5W E2JM3225AW HFDM003AM E2F003AM JDCM3225D5W E2JM3225DW 25 HFDM003AMLU62 E2F003AMLU62 JDCM3225W E2JM3225W HFDM007CM E2F007CM JDCM3250A5MW E2JM3250MAW 25 HFDM007CMU62 E2F007CMU62 JDCM3250A5MWU18 E2JM3250MAWU18 HFDM015EM E2F015EM JDCM3250A5W E2JM3250AW HFDM015EMA02 E2F015EMA02 JDCM3250C5MW E2JM3250MCW 25 HFDM015EMLU62 E2F015EMLU62 JDCM3250D5MW E2JM3250MDW HFDM015EMU62 E2F015EMU62 JDCM3250D5MWA06 E2JM3250MDWA06 25 HFDM030HM E2F030HM JDCM3250D5W E2JM3250DW HFDM030HMLU62 E2F030HMLU62 JDCM3250D5WS10 E2JM3250DWS10 25 HFDM030HMU62 E2F030HMU62 JDCM3250F E2JM3250F HFDM050KM E2F050KM JDCM3250F5MD01 E2JM3250MFD01 HFDM050KML E2F050KML JDCM3250F5MW E2JM3250MFW 25 HFDM050KMLU62 E2F050KMLU62 JDCM3250G5MW E2JM3250MGW HFDM050KMU62 E2F050KMU62 JDCM3250G5WA02D01 E2JM3250MGA02D01 25 HFDM070MM E2F070MM JDCM3250J5MW E2JM3250MJW HFDM070MMU62 E2F070MMU62 JDCM3250J5MWA02 E2JM3250MJA02 HFDM1001M E2F1001M JDCM3250J5WA02D01 E2JM3250MJA02D01 HFDM1001MS22 E2F1001MS22 JDCM3250J5WD01 E2JM3250MJD01 HFDM100LM E2F100LM JDCM3250K5MW E2JM3250MKW 25 HFDM100LMA02 E2F100LMA02 JDCM3250L5MW E2JM3250MLW HFDM100LMU62 E2F100LMU62 JDCM3250MW E2JM3250MW 25 HFDM 100RM E2F100RM JDCM3250W E2JM3250W HFDM100RML E2F100RML JDCMAA2D1 E2JM3250MM02D01 HFDM100RMS22 E2F100RMS22 JDCMDD1S30 E2JM3250MDS30D01 25 HFDM100RMU62 E2F100RMU62 JDCMFD01 E2JM3250MFD01 HFDM150TM E2F150TM JDCMGA02D1 E2JM3250MGA02D01 25 HFDM150TML E2F150TML JDCMJA2D1 E2JM3250MJA02D01 HFDM150TMU62 E2F150TMU62 JDCMJD01 E2JM3250MJD01 25 HFDM150UM E2F150UM JDM2250F E2JM3250F JCDA2D1S30 E2JM250MDA2D1S30 JDM3070W E2J3070W JCMA2D1S30 E2JM250MFA2D1S30 JDM3090W E2J3090W 25 JDCM3070W E2JM3070W JDM3100W E2J3100W JDCM3090W E2JM3090W JDM3125W E2J3125W 25 JDCM3100W E2JM3100W JDM3150W E2J3150W JDCM3125W E2JM3125W JDM3150WU18 E2J3150WU18 25 25 25 25 25 25 25 25 25 Series C Mining 25 25 25 25 25 25 V4-T25-554 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 Molded Case Circuit Breakers Specialty Breakers 25.5 E2 Cross-Reference, continued Series C Mining Superseded by E2 Mining Series C Mining Superseded by E2 Mining JDM3175W E2J3175W JM3250TL5M_1125-2250 E2J3250TML JDM3200W E2J3200W JM3250TM E2J3250TM JDM3200WA06 E2J3200WA06 KDCM3100W E2KM3100W JDM3225A5W E2J3225AW KDCM3125W E2KM3125W JDM3225D5W E2J3225DW KDCM3150W E2KM3150W JDM3225W E2J3225W KDCM3175W E2KM3175W JDM3250A5MW E2J3250MAW KDCM3200W E2KM3200W JDM3250A5W E2J3250AW KDCM3225A5MW E2KM3200MAW JDM3250C5MW E2J3250CW KDCM3225D5MW E2KM3200MDW JDM3250D5MW E2J3250MDW KDCM3225W E2KM3225W JDM3250D5W E2J3250DW KDCM3250W E2KM3250W JDM3250F E2J3250F KDCM3250WU18 E2KM3250WU18 JDM3250F5MW E2J3250MFW KDCM3300W E2KM3300W JDM3250G5MW E2J3250MGW KDCM3350W E2KM3350W JDM3250J5MW E2J3250MJW KDCM3400D5MA02D09H04 E2KM3400MDA02D09H04 JDM3250K5MW E2J3250MKW KDCM3400D5MW E2KM3400MDW JDM3250L5MW E2J3250MLW KDCM3400D5MWA02D07 E2KM3400MDA02D07 JDM3250MW E2J3250MW KDCM3400D5W E2KM3400DW JDM3250W E2J3250W KDCM3400D5WD09 E2KM3400DD09 JDM3250WS10 E2J3250WS10 KDCM3400F E2KM3400F JM2225T1125-2250 E2J3225T KDCM3400F5MW E2KM3400MFW JM3070T E2J3070T KDCM3400FD09G04 E2KM3400MFD09G04 JM3090T E2J3090T KDCM3400G5MW E2KM3400MGD09G05 JM3100T E2J3100T KDCM3400G5MWD09H04 E2KM3400MGD09H04 JM3125T E2J3125T KDCM3400G5W E2KM3400MGW JM3150T E2J3150T KDCM3400G5WD07 E2KM3400MGD07 JM3175T E2J3175T KDCM3400J5MA02D09 E2KM3400MJA02D09 JM3200T E2J3200T KDCM3400J5MA2D9G4S30 E2KM3400MJA2D9G4S30 JM3225T E2J3225T KDCM3400J5MD09 E2KM3400MJD09 JM3225TA5 E2J3225TA KDCM3400J5MD09H04S30 E2KM3400MJD09H04S30 JM3225TD5 E2J3225TD KDCM3400J5MW E2KM3400MJW JM3250T E2J3250T KDCM3400J5MWA02D07 E2KM3400MJA02D07 JM3250TA5 E2J3250TA KDCM3400J5MWA06 E2KM3400MJWA06 JM3250TA5M_350-700 E2J3250TMA KDCM3400J5MWD07S30 E2KM3400MJD07S30 JM3250TC5M E2J3250TMC KDCM3400J5WD07 E2KM3400MJD07 JM3250TD5_500-1000 E2J3250TMD KDCM3400K5MW E2KM3400MKW JM3250TF5M_625-1250 E2J3250TMF KDCM3400K5MWS10 E2KM3400MKWS10 JM3250TG5M_750-1500 E2J3250TMG KDCM3400K5MWU18 E2KM3400MKWU18 JM3250TJ5M_875-1750 E2J3250TMJ KDCM3400L5MW E2KM3400MLW JM3250TK5M_1000-2000 E2J3250TMK KDCM3400L5MWD09H04 E2KM3400MLD09H04 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com V4-T25-555 For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 25.5 25 Molded Case Circuit Breakers Specialty Breakers E2 Cross-Reference, continued Series C Mining Superseded by E2 Mining Series C Mining KDCM3400L5MWS10 E2KM3400MLWS10 KDM3300WS10 E2K3300WS10 KDCM3400L5WD07 E2KM3400MLD07 KDM3350W E2K3350W KDCM3400MW E2KM3400MW KDM3400D5MW E2K3400MDW KDCM3400N5MW E2KM3400MNW KDM3400D5W E2K3400DW KDCM3400N5MWA06 E2KM3400MNWA06 KDM3400D5WU18 E2K3400DWU18 25 KDCM3400N5WA02D07 E2KM3400MNA02D07 KDM3400F E2K3400F KDCM3400R5MW E2KM3400MRW KDM3400F5MW E2K3400MFW 25 KDCM3400W E2KM3400W KDM3400FK37A06D09D18 E2KE3400A06D09D18 KDCM3400W5MW E2KM3400MWW KDM3400G5A06D09U18 E2K3400GA06D09U18 KDCMDMD07 E2KM3400MDD07 KDM3400G5A13D09U18 E2K3400GA13D09U18 25 KDCMNA2D7 E2KM3400MNA02D07 KDM3400G5MW E2K3400MGW KDM2400F E2K2400F KDM3400G5W E2K3400GW 25 KDM2400G5MS50 E2K2400MGWS50 KDM3400G5WA06 E2K3400GWS10 KDM2400G5MW E2K2400MGW KDM3400G5WS10 E2K3400GWS10 25 KDM2400W5MW E2K2400MWW KDM3400G5WU18 E2K3400GWU18 KDM2400W5MWA06D07S10 E2K2400MWA06D07S10 KDM3400J5MW E2K3400MJW KDM2400W5MWA06D10S10 E2K2400MWA06D10S10 KDM3400K5MS54 E2K3400MKWS54 25 KDM2400W5MWD07 E2K2400MWD07 KDM3400K5MW E2K3400MKW KDM2400W5MWD07S10 E2K2400MWD07S10 KDM3400L5MW E2K3400MLW 25 KDM2400W5MWD10 E2K2400MWD10 KDM3400MW E2K3400MW KDM2400W5MWD10S10 E2K2400MWD10S10 KDM3400MWA06U18 E2K3400MWA06U18 KDM2400W5MWS10 E2K2400MWWS10 KDM3400N5MW E2K3400MNW KDM3100W E2K3100W KDM3400R5MW E2K3400MRW KDM3125W E2K3125W KDM3400W E2K3400W 25 KDM3150W E2K3150W KDM3400W5MW E2K3400MWW KDM3150WA06 E2K3150WA06 KEM3100T KEM3100T 25 KDM3175W E2K3175W KEM3125T KEM3125T KDM3200W E2K3200W KEM3150T KEM3150T KDM3225A5W E2K3225AW KEM3150TM KEM3150TM 25 KDM3225D5A13D09U18 E2K3225DA13D09U18 KEM3200T KEM3200T KDM3225D5MW E2K3400MDW KEM3225T KEM3225T 25 KDM3225D5W E2K3225DW KEM3225T2 KEM3225T2 KDM3225F E2K3400F KEM3225TM KEM3225TM 25 KDM3225W E2K3225W KEM3225TM2 KEM3225TM2 KDM3225WK37 E2KE3225W KM2225TA5 E2K2225TA KDM3225WK37U18 E2KE3225WU18 KM2225TA5M E2K2400TMA 25 KDM3225WK38 E2KE3225MW KM2225TD5 E2K2225TD KDM3250W E2K3250W KM2225TD5M E2K2400TMD 25 KDM3300W E2K3300W KM2400TD5 E2K2400TD KDM3300WA06U18 E2K3300WA06U18 KM2400TD5M E2K2400TMD 25 25 25 25 25 25 25 25 25 Superseded by E2 Mining 25 25 25 25 25 25 V4-T25-556 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 Molded Case Circuit Breakers Specialty Breakers 25.5 E2 Cross-Reference, continued Series C Mining Superseded by E2 Mining Series C Mining Superseded by E2 Mining KM2400TG5M E2K2400TMG LEM3300T LEM3300T KM2400TN5M E2K2400TMN LEM3350T LEM3350T KM2400TW5M E2K2400TMW LEM3400T LEM3400T KM3100T E2K3100T LEM3400T2 LEM3400T2 KM3125T E2K3125T LEM3400TM LEM3400TM KM3150T E2K3150T LEM3400TM2 LEM3400TM2 KM3175T E2K3175T LEM3600T LEM3600T KM3200T E2K3200T LEM3600TM LEM3600TM KM3225T E2K3225T LM3600TL6M E2L3600TML KM3225TA5 E2K3225TA LM3600TN6M E2L3600TMN KM3225TA5M E2K3400TMA LM3600TP6M E2L3600TMP KM3225TD5 E2K3225TD LM3600TR6M E2L3600TMR KM3225TD5M E2K3400TMD LM3600TS6M E2L3600TM KM3250T E2K3250T LM3600TX6M E2L3600TMX KM3300T E2K3300T UVE3LP08K UVE3LP08K KM3350T E2K3350T UVE4LP08K UVE4LP08K KM3400T E2K3400T KM3400TD5 E2K3400TD Additional Information on Mining Breakers KM3400TF5M E2K3400TMF Source Description KM3400TG5M E2K3400TMG TD01217001E E2 Mining Circuit Breaker Dimensional Data BR01217001E E2 Mining Circuit Breaker Brochure TC01217001E E2 Mining Circuit Breaker Time Current Curves www.eaton.com/mining Mining and Metals KM3400TJ5M E2K3400TMJ KM3400TK5M E2K3400TMK KM3400TL5M E2K3400TML KM3400TM E2K3400TM KM3400TN5M E2K3400TMN KM3400TR5M E2K3400TMR KM3400TW5M E2K3400TMW LDCM3600EMA05W E2LEM3600MA05W LDCM3600F E2LM3600F LDM3600F E2L3600F 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com V4-T25-557 For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 25.5 25 Molded Case Circuit Breakers Specialty Breakers Contents GFR Relay Description 25 Engine Generator Circuit Breakers . . . . . . . . . . . . . Direct Current Circuit Breakers . . . . . . . . . . . . . . . E2 Mining Service Circuit Breakers . . . . . . . . . . . . Classic Mining Breakers. . . . . . . . . . . . . . . . . . . . . Add-On Ground Fault Protection—Type GFR . . . . . Product Selection Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . Technical Data and Specifications . . . . . . . . . . . 25 25 25 25 Page V4-T25-504 V4-T25-510 V4-T25-521 V4-T25-544 V4-T25-558 V4-T25-560 V4-T25-560 25 25 25 25 25 Add-On Ground Fault Protection—Type GFR 25 Product Description 25 25 25 25 25 25 A Type GFR ground fault protection system, when properly installed on a grounded electrical system, will sense phase-to-ground fault currents. When the level of fault current is in excess of the pre-selected current pickup and time delay settings, the GFR relay will initiate a trip action of a disconnect device, which will open the faulted circuit and clear the fault. 25 25 25 25 Standards and Certifications The GFR devices are UL Class I devices designed to protect electrical equipment against extensive damage from arcing ground faults. A basic Type GFR ground fault protection system consists of a ground fault relay, a ground fault current sensor and a disconnect device equipped with a shunt trip device. This disconnect device can be a molded case circuit breaker, a power circuit breaker, a bolted pressure switch or other fusible disconnect device, suitable for application with UL Class I ground fault sensing and relaying equipment. Eaton’s GFR ground fault relays, current sensors, test panels and accessory devices are UL listed by Underwriters Laboratories in accordance with their standard for ground fault sensing and relaying equipment, UL 1053, under File E48381. Note: Relays are also listed with CSA under their file number 43357. Note: Suitable for either surface or semi-flush mounting. 25 25 25 25 25 25 25 25 V4-T25-558 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 Molded Case Circuit Breakers Specialty Breakers 25.5 Product Selection Each installation requires: ● ● One relay unit (select trip ampere as required) One current sensor (select configuration required) GFR Relay ● ● 25 One circuit breaker or disconnect device with shunt trip, or a shunt trip attachment for mounting in existing breaker Test panel (optional) 25 25 25 25 GFR Relay Ground Fault Pickup Amperes 1–12 5–60 100–1200 Catalog Catalog Catalog Number Number Number GFR Relay Types 25 25 For 120 Volt 50/60 Hz Control 25 Electrical reset with zone interlocking GFR12EI GFR60EI GFR1200EI Electrical reset without zone interlocking GFR12E GFR60E GFR1200E Mechanical reset with zone interlocking GFR12MI GFR60MI GFR1200MI Mechanical reset without zone interlocking GFR12M GFR60M GFR1200M 25 Electrical reset with zone interlocking — — GFR1200EID 25 Electrical reset without zone interlocking — — GFR1200ED Mechanical reset with zone interlocking — — GFR1200MID Mechanical reset without zone interlocking — — GFR1200MD 25 For 120 Vdc Control Typical Current Sensor 25 25 25 Current Sensor Window Size in Inches (mm) 25 Catalog Number 25 Used with Relays Rated 1–12 Amperes 5.50 (139.7) I.D. 1283C45G01 25 Used with Relays Rated 5–60 Amperes 2.50 (63.5) I.D. 179C768G01 5.50 (139.7) I.D. 1256C13G01 7.81 x 11.00 (198.4 x 279.4) Rect. 1257C88G04 3.31 x 24.94 (84.1 x 760.5) Rect. 1257C92G03 25 25 25 Used with Relays Rated 100–1200 Amperes 2.50 (63.5) I.D. 179C768G02 5.50 (139.7) I.D. 1256C13G02 8.25 (209.6). I.D. 179C767G02 7.81 x 11.00 (198.4 x 279.4) Rect. 1257C88G03 9.94 x 16.94 (252.5 x 430.3) Rect. 1257C90G02 9.94 x 23.94 (252.5 x 608.1) Rect. 1257C91G02 15.94 x 19.94 (404.9 x 506.4) Rect. 1257C89G02 3.31 x 24.94 (84.1 x 633.5) Rect. 1257C92G04 6.75 x 29.64 (171.5 x 752.9) Rect. 1255C39G03 25 25 25 25 25 25 Notes Suitable for either surface or semi-flush mounting. One end removable for installation. 25 25 25 25 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com V4-T25-559 For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 25.5 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 Specialty Breakers Accessories Technical Data and Specifications Options Additional optional equipment can be added to the protection system to meet the requirements of the specifying engineer, including: ● 25 Molded Case Circuit Breakers ● ● Ground fault test panel Ground fault warning indicator relay Ground fault indicating ammeter GFR relays are available with zone selective interlocking circuitry to interlock several relays within the same system. This allows the relay which detects a ground fault to instantly clear the fault by tripping the disconnect device. The relay simultaneously sends a signal to relay units “upstream” from the fault to time delay or to block their operation completely. Current sensors in various designs provide a range of “window” sizes to accommodate standard bus and cable arrangements. Shunt trip attachments may be ordered for field mounting in Eaton’s molded case circuit breakers, or may be ordered factory installed in the breaker. Test Panel (120 Vac) Used to test the ground fault system, to give an indication the relay has tripped the breaker, and to reset the relay after tripping. These functions may be separately mounted pilot devices. Note: When a mechanically reset relay is used with a test panel, both the relay and test panel must be reset following either a simulated ground fault test or actual ground fault. Not UL listed. Test 120 Volt 50/60 Hz 120 Volt 50/60 Hz Ammeter Kit Kit Catalog Number Catalog Number 1–12 ampere 752B820G01 5–60 ampere 752B820G02 GFRTP 100–1200 ampere 752B820G03 Ground Fault Warning Indicator This is an accessory item for use with GFR relays with interlocking circuitry. At approximately 30–50% of the relay pickup setting, the indicator switches separate 120 Vac control power to a lamp or relay, (not included) to give an indication of a ground fault. The indicator is rated 110/120 Vac 50/60 Hz for a maximum indicator load of 0.5 amperes. Sensor ● Shunt Trip Attachments Use 120 Vac shunt trips. Faceplate Recommended when these relays are semi-flush mounted, to close the door cutout opening. 600 volt, 50/60 Hz maximum system voltage Electrical Ratings GFR Relay ● Ground fault detection ranges: ● 1 to 12, 5 to 60 or 100 to 1200 amperes ● Output contacts: ● 240 volt, 50/60 Hz: 3.0 amperes ● 120 volt, 50/60 Hz: 6.0 amperes ● 28 Vdc: 3.0 amperes ● 125 Vdc: 0.5 amperes ● Control power requirements: ● 120 volt, 50/60 Hz or 125 Vdc (optional) Note: Not UL listed. GFR System Used with Optional Test Panel Control Indicating Ammeter The optional indicating ammeter connects to the sensor terminals through a momentary contact pushbutton, and will indicate (in amperes) any ground fault current flowing through the sensor. Kit includes the ammeter and pushbutton. Face Plate Description Catalog Number Faceplate 752B410G01 Ground Fault Warning Indicator 25 25 25 Description Catalog Number Manual reset 1234C67G01 Self-resetting 1234C67G02 25 25 25 25 25 25 25 25 25 V4-T25-560 Volume 4—Circuit Protection CA08100005E—April 2011 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 Index A AA, 15 AAL, 15 AC, 6-7, 41 ac, 20, 22, 32, 36, 40 acceptability, 1 Accessories, 1, 5, 7, 15, 18, 38-39, 41, 43-45, 48, 57 accessories, 2, 5, 7, 15, 43-44 Accessory, 15 accessory, 15, 39-40, 55, 57 accommodate, 57 accordance, 55 achieve, 41 action, 55 actual, 57 Add, 1, 7, 18, 55 added, 57 Additional, 18, 54, 57 additional, 2 Additionally, 18 address, 7 adjacent, 48 after, 57 against, 55 AHMDLDC, 9 AI, 38 aid, 2 Al, 5, 14, 47 Alarm, 15, 19, 40 alarm, 15 ALGSDC, 9 All, 41, 43-44 all, 16 allow, 8 allowable, 19 allows, 1, 57 ALM, 15, 40 also, 18-19, 39-40, 55 alternative, 7 Aluminum, 14 aluminum, 47 AM, 23, 51 AMLU, 51 Ammeter, 57 ammeter, 57 Amp, 5 Ampacity, 14 Ampere, 9-14, 19, 22-37, 41, 48 ampere, 3-5, 19, 31, 48, 56-57 Amperes, 2, 5-6, 8, 19, 38, 41-47, 56 amperes, 5, 18, 37, 41, 46, 57 amperesGFR, 57 an, 2, 41, 57 and, 1-15, 18-19, 38, 40-42, 47-49, 54-55, 57 anel, 48 any, 2, 57 apartment, 5 APK, 15, 39 appli, 22 applicable, 5 Application, 1, 16 application, 1, 5, 18-19, 55 Applications, 7 applications, 3-5, 7-8, 14 applied, 1, 3, 7, 41 Index applies, 19 apply, 8 approved, 5 Approx, 6 Approximate, 6 approximately, 1, 57 April, 1-57 arcing, 55 are, 1, 3, 5, 7-8, 14-15, 18-19, 41-44, 46-47, 49, 55, 57 areas, 5 arrangements, 57 art, 18 as, 2, 5, 7-8, 19, 56 ASIC, 18 Assembled, 13 assembled, 48 assembly, 48 assistance, 15 Association, 1 assuming, 1 At, 57 at, 1-57 atmosphere, 5 attachment, 46, 56 Attachments, 57 attachments, 57 Auto, 49 auto, 43-44 automatic, 14 AUX, 15, 40 AUXALRMJPK, 15 Auxiliary, 5, 15, 19, 40 Availability, 48 Available, 49 available, 5, 7-8, 15, 18-19, 39-40, 57 AW, 24, 26, 51-53 AWG, 5, 14, 38 AWHFDM, 51 AWU, 50 be, 2, 7, 15-16, 18, 41, 48-49, 55, 57 becoming, 7 been, 8 before, 15, 49 beginning, 43-44 being, 5 below, 19, 47, 49 between, 42 BJPK, 15, 40 block, 57 blocks, 39 Body, 14 bolted, 55 Both, 5 both, 2, 7, 57 BPK, 15, 40 BR, 18, 54 Branch, 1 Break, 40 break, 15 Breaker, 1, 3-6, 8-14, 17-21, 24-35, 38-44, 46-49, 54 breaker, 1, 5, 7, 10-13, 15, 18-19, 49, 55-57 BreakerMaximum, 13 Breakers, 1-57 breakers, 1-3, 5, 7, 15, 18-19, 41, 43-44, 46, 48-49, 57 BreakersBreaker, 45 Breakersstandard, 1 BreakersTerminals, 47 breaks, 49 Brochure, 18, 54 build, 2 buildings, 5 bus, 48, 57 Bweatherproof, 5 by, 5, 18, 48, 50-55, 57 C B BA, 13 Back, 48 Based, 3-4, 41 based, 3-4, 48 basic, 55 battery, 7-8 CA, 1-57 Cable, 19 cable, 8, 16, 18, 48, 57 Cables, 47 Calibrated, 13 calibrated, 42 call, 1-57 can, 15, 18, 55, 57 Canadian, 1 Cap, 38 Index capable, 5 Capacity, 6, 8, 10-14, 19, 41 capacity, 1, 14, 41 carry, 7 Case, 1-57 case, 1, 7, 9, 14, 49, 55, 57 Catalog, 1-6, 9-14, 22-40, 47, 56-57 catalog, 2-4, 10 CatalogAmperes, 5 Catalogat, 25, 33, 35 Catalogin, 57 CatalogRating, 5 cation, 22 center, 3-5 centers, 7 certain, 49 Certifications, 1, 55 CFR, 18-19 change, 45 changed, 45 charging, 7-8 Chart, 18 Circuit, 1-57 circuit, 1-2, 5, 7, 15, 19, 41, 46, 49, 55-57 circuitry, 57 circuits, 5, 7-8 Class, 5-6, 55 Classic, 1, 7, 18, 41-49, 55 clear, 55, 57 clearance, 48 clearances, 48 close, 57 closer, 1 closing, 49 CM, 23, 51 CMU, 51 coal, 18 Code, 1, 40 code, 18-19 CodeE, 39 codes, 1, 15 Coil, 42, 49 coil, 49 com, 1-57 combination, 1 combo, 15 commercial, 5, 7 Commission, 1 common, 8 commonplace, 7 compact, 14 companies, 18 Complete, 10-13, 24-35 complete, 10-13, 43-44, 48 completely, 57 compound, 47 conditions, 5 Conductor, 19, 46 conductor, 19 Conductors, 14, 38 conductors, 1, 47 Conduit, 6 configuration, 15, 56 conform, 1, 19 Conformance, 1 conforming, 18 connect, 8 Connected, 48 connected, 7-8, 14-16, 41 Connection, 16 connection, 8, 16 connections, 48 Connectors, 13 connectors, 13 connects, 57 consists, 55 constants, 8 consult, 41 Contact, 2, 15, 39-40 contact, 48, 57 Contacts, 40 contacts, 57 Contents, 1, 7, 18, 41, 55 continue, 41 continued, 44, 51-54 Continuous, 10-14, 22-37, 46 continuous, 1, 3-4 ContinuousAmpere, 31, 33 Control, 56-57 control, 49, 57 coolant, 5 copper, 47 cover, 5 CPK, 15, 40 Cross, 43-44, 50-54 cross, 41 CSA, 55 CT, 3-4 CTW, 3-4 Cu, 5, 14, 38, 47 CuNBM, 47 Current, 1, 7-8, 18-19, 54-57 current, 3-4, 7, 14, 41, 55-57 currents, 55 CurrentVoltage, 19 Curves, 18, 54 Index custom, 18 customer, 16, 42, 48 customize, 1 Cutler, 41 cutoff, 49 cutout, 57 CW, 52 D DA, 53 damage, 55 Data, 1, 5-6, 18-20, 42, 54-55, 57 data, 7 DataOperating, 21 DC, 7-14, 16-17, 19, 41-42 DD, 52 delay, 55, 57 Delivery, 1-57 Depth, 17 Description, 1, 7, 15, 18, 41, 48, 54-55, 57 design, 18, 42 designed, 1, 5, 18-19, 55 designs, 57 detection, 57 detects, 57 developed, 18 device, 5, 49, 55-57 devices, 7, 14, 55, 57 Diagrams, 7, 16 diagrams, 8 Diameter, 48 diesel, 1 different, 7, 18 Digest, 48 Dimensional, 18, 54 Dimensions, 1, 6-7, 17 DimensionsApproximate, 17 Direct, 1, 7-8, 18, 55 direct, 7, 18 disconnect, 5, 14, 55-57 distribution, 7 do, 2, 14 Does, 37 does, 45 done, 15 door, 57 DPK, 15, 39 Drawings, 1 Dropout, 20 dropout, 42 drops, 49 DS, 18 dual, 3-4 during, 18 dust, 5 Dustproof, 5-6 DW, 24, 26, 51-53 DWKDCM, 53 DWS, 51 DWU, 50, 53 E Each, 56 each, 18 Eaton, 1-2, 7, 14-15, 18-19, 39-40, 48, 55, 57 eaton, 1-57 ED, 56 EI, 56 EID, 56 either, 5, 18, 55-57 electric, 7 Electrical, 1, 19-21, 49, 56-57 electrical, 41-42, 45, 55 electrically, 18 Electromechanical, 18-19 Electronic, 4, 28-30, 33, 35-37 electronic, 3-4, 18-19, 41 Electrotechnical, 1 EM, 23, 51 EMA, 51, 54 EMLU, 51 employs, 5 EMU, 51 enclosed, 5 Enclosure, 5-6 enclosure, 5 Enclosures, 1, 5 enclosures, 5 End, 38 end, 7, 10, 16, 56 energized, 49 energy, 7 Engine, 1, 3-4, 7, 18, 55 engine, 1, 3 Index engineer, 57 engineers, 18 Entrance, 1 entrance, 5 environments, 18 equipment, 41, 55, 57 equipped, 1, 49, 55 equivalents, 7 erminal, 14 ervice, 18 especially, 18 exact, 41 exactly, 19 exceeds, 7 excess, 55 exist, 5 existing, 56 expanded, 7 extend, 49 Extension, 48 extensive, 55 External, 38 external, 2, 7, 42 Externally, 49 F FA, 11-12 Face, 57 Faceplate, 57 factor, 3-4, 41 Factory, 5, 13, 15, 39-40 factory, 15, 57 FAG, 11-12 family, 7, 18 Fault, 1, 7, 18, 55-57 fault, 55, 57 faulted, 55 faults, 55 FB, 5, 14, 38 FBM, 18 FD, 5, 14, 52 FDBM, 18, 50 FDM, 18, 50-51 feature, 19 Federal, 18-19 feed, 1-2 feeder, 5 FG, 1-6 Field, 5, 15, 18 field, 10-13, 15, 18, 49, 57 File, 1, 55 file, 55 first, 18 five, 1 Fixed, 3 fixed, 1 FK, 53 FLA, 3 flowing, 57 FLU, 51 flush, 5, 55-57 FM, 18-23, 38-40 focus, 18 following, 1, 3-4, 57 For, 1-57 for, 1-5, 7-8, 10-13, 15-16, 18-19, 39-40, 42, 46-49, 55-57 foreign, 5 Four, 8-10, 12, 14, 16 four, 8 Frame, 2, 5-6, 9-15, 17, 24-37, 43-46 frame, 5, 7-8, 10-14, 18-19 Frames, 46 frames, 18, 43-44, 48-49 Frequency, 19 frequency, 49 from, 7, 18, 49, 55, 57 front, 5, 41 full, 3-4, 7 functions, 57 fusible, 55 FUV, 50 G GA, 53 General, 5 general, 5 Generator, 1, 3-4, 7, 18, 55 generator, 1, 3-4 generators, 1, 3-4 GFR, 1, 7, 18, 55-57 GFRTP, 57 give, 57 greater, 41 Index Ground, 1, 5, 7, 18, 55-57 ground, 55, 57 Groundable, 5 grounded, 7, 16, 55 group, 18 Guide, 1, 5 GW, 53 GWS, 53 GWU, 50, 53 hours, 18 however, 48 HPBM, 18 hubs, 5 hundreds, 18 Hz, 3-4, 6, 19, 41, 43-45, 49, 56-57 I H Hammer, 41 Hand, 49 hand, 46 Handle, 38-39, 49 handle, 5, 39, 43-45 harsh, 18 has, 7, 57 Hasp, 38 have, 1, 3-4, 7-8, 14, 16, 48 Height, 17 HFBM, 18, 47 HFDDC, 7-10, 14-15, 17 HFDM, 18, 51 HFM, 18 High, 10-13 high, 1, 14 highest, 7 HJDDC, 8-10, 14-15, 17 HKAM, 18, 41-42, 45-49 HKDDC, 8-9, 11, 14-15, 17 HLAM, 18, 41-42, 45-49 HLCLM, 18 HLCM, 18 HLDDC, 8-9, 12, 14-15, 17 HLK, 38 HM, 23, 51 HMAM, 18, 42, 45-49 HMCM, 18 HMDLDC, 7-8, 13-15, 17 HMLU, 51 HMU, 51 HNAM, 45 HNBM, 18, 42, 45-49 HNBMH, 18 HNCM, 18 host, 7 Ics, 8 Icu, 8 IEC, 1, 6, 8 If, 41 Iisted, 48 Immediate, 1-57 Imperial, 38 In, 37, 48 in, 5-8, 12, 14, 16-19, 41, 43-46, 48-49, 55-57 Inches, 6, 17, 48, 56 inches, 49 Include, 22-23, 37 include, 2-4, 7 Included, 13-14, 43-45 included, 43-44, 57 Includes, 12-13 includes, 1, 3-4, 48, 57 including, 57 incorporate, 18 indicate, 57 indicated, 43-44 Indicating, 57 indicating, 57 indication, 7, 57 Indicator, 57 indicator, 57 individual, 10-13 Inductance, 41 inductive, 8, 19 industrial, 7 industry, 5, 18 Information, 1, 5, 18, 41, 50, 54 information, 2, 41, 43-44 initiate, 55 INK, 5 inside, 5 Installation, 15 installation, 5, 10-13, 15, 56 installed, 15, 41, 55, 57 Index Instantaneous, 19, 28-29, 33, 35-37 instantaneous, 14, 18-19 instantly, 57 Insulated, 5, 19, 48 Interchangeable, 5, 18, 22-35 interchangeable, 18 interlock, 57 interlocked, 5 interlocking, 56-57 Internal, 5, 15, 39 internal, 2, 7, 15, 39-40 International, 1 international, 1 Interrupting, 6, 8, 10-14, 19, 41 interrupting, 1, 7, 41 involving, 5 is, 1-5, 7-8, 15-16, 18, 41, 43-45, 48-49, 55, 57 It, 2 it, 48 item, 57 J JCDA, 51 JCMA, 51 JDCM, 18, 51 JDCMAA, 51 JDCMDD, 51 JDCMFD, 51 JDCMGA, 51 JDCMJA, 51 JDCMJD, 51 JDM, 18, 51-52 JFDN, 5-6 JG, 1-6 JJDN, 5-6 JKDN, 5-6 JLDN, 5-6 JM, 18-21, 24-25, 38-40, 51-52 JNDN, 5-6 joint, 47 JT, 10 K kA, 8, 19, 22-37 kAIC, 10-13 KAM, 18, 41-43, 46-49 KAMH, 18, 46 KB, 5, 10, 14, 38 kcmil, 5, 14, 38, 46-47 kcmilopening, 5 KDCM, 18, 52-53 KDCMDMD, 53 KDCMNA, 53 KDM, 18, 53 KE, 28-29, 53 KEM, 28-29, 50, 53 KG, 2-6 kg, 6 ki, 38 Kit, 5, 57 kit, 11-12, 38 Kits, 5, 15 KKG, 5 KL, 14 KM, 18-21, 23, 26-30, 38-40, 50-54 KML, 51 KMLU, 51 KMParts, 1-57 KMU, 51 KMW, 30 knockouts, 5 KPEK, 38 KPEMK, 38 KSG, 14 KSW, 14 KT, 11, 39 KType, 5 kVA, 3-4 KW, 14 kW, 3-4 L LA, 47-48 Laboratories, 1, 5, 15, 48, 55 LAM, 18, 41-43, 46-49 LAMH, 18, 46-47 Index lamp, 57 large, 18 Lbs, 6 LCM, 18 LCMH, 18 LD, 12, 14, 38 LDCM, 18, 54 LDK, 5, 12, 14, 38 LDM, 18, 54 LE, 33 leads, 39, 49 Learn, 1 LED, 39 led, 18 Left, 15, 39-40, 49 left, 46 leg, 7, 41 LEM, 33, 50, 54 Length, 48 length, 48 level, 1, 55 LG, 2-6 LGEDC, 8-9, 11, 14-15, 17 LGHDC, 8-9, 12, 14-15, 17 LGKDC, 14 LGSDC, 8, 11, 14-15, 17 LH, 39-40 Line, 9-10, 14, 22-23, 38, 42, 47-48 line, 2-5, 49 List, 48 list, 19 listed, 5, 7-8, 14-15, 39-40, 43-44, 47, 49, 55, 57 listing, 15 lists, 3 LK, 11-12, 14, 38 LM, 18-21, 31-33, 38-40, 50-51, 54 LMA, 51 LME, 19-21, 30, 38-40 LMU, 51 LMZ, 19-21, 30, 38-40 Load, 10, 14, 16, 22-23, 38, 48 load, 2-4, 9, 16, 19, 57 local, 1, 15 Location, 39-40 Lock, 38 Lockout, 19, 40 Long, 28, 33, 35-37, 48 long, 48 Longer, 49 low, 1 LP, 5, 15, 39-40, 54 LPHL, 38 LPK, 40 LS, 37, 50 LSI, 37 LT, 11-12, 30, 39 LU, 50-51 Lug, 5 M MA, 13-14, 38, 47, 52, 54 made, 18 mag, 18 Magnetic, 3-4, 10-13, 22-37, 43-46 magnetic, 1, 3-4, 9, 18-19, 39, 43-45 Main, 5 main, 5 maintain, 48 Make, 40 make, 15, 48 MAM, 18, 41-42, 44, 46-49 MAMH, 18, 46-49 Manual, 57 manufactured, 41 Many, 7 Material, 14 materials, 5 MAW, 25, 27, 51-52 MAWU, 51 Max, 5, 17 max, 9 Maximum, 3-4, 8, 10-14, 16, 19-20, 22-38, 41, 46-47 maximum, 3, 7-8, 19, 57 MaximumBreaker, 19 may, 7, 48-49, 57 MCM, 18 MCMH, 18 MCW, 25, 51 MD, 51-52, 56 MDA, 51-52 MDD, 53 MDS, 51 MDW, 25, 27, 52-53 MDWA, 51 MDWHFDM, 51 ME, 35 Mechanical, 56 mechanically, 57 Mechanism, 20 mechanism, 5 Index meet, 7, 57 meets, 19 MEM, 35 Metals, 18, 54 Metric, 5, 14, 38 MFA, 51 MFD, 51-52 MFW, 25, 27, 51-53 MGA, 51 MGD, 52 MGW, 25, 27, 51-53 MGWKDM, 53 MGWS, 53 mH, 41 MI, 56 microprocessor, 18 MID, 56 mine, 18 Minimum, 20-21 Mining, 1, 7, 18, 41-48, 50-55 mining, 18-19, 41, 46, 54 MJA, 51-52 MJD, 51-52 MJW, 25, 27, 51-53 MJWA, 52 MKW, 25, 27, 51-53 MKWS, 52-53 MKWU, 52 MLD, 52-53 MLW, 25, 27, 32, 51-53 MLWS, 53 MM, 18-20, 23, 34-35, 38-40, 51 mm, 5-6, 14, 17, 48-49, 56 MMac, 21 MMMining, 18 MMU, 51 MNA, 53 MNW, 27, 32, 34, 53 MNWA, 53 Modification, 39-40 modified, 46 Molded, 1-57 molded, 1, 7, 14, 55, 57 momentary, 49, 57 most, 1 mountable, 49 Mounted, 5-6 mounted, 5, 15, 49, 57 Mounting, 5, 39-40, 48-49 mounting, 5, 42, 46, 48, 55-57 MountingAuxiliary, 15 MountingShunt, 15 mounts, 49 MPW, 32, 34 MRW, 27, 32, 53 MRWKDM, 53 MS, 18, 51, 53 MSHA, 18 MT, 13 MU, 50 must, 7, 16, 41, 48-49, 57 MW, 9, 13, 25, 27, 29, 32-33, 35-36, 50-53 MWA, 51-53 MWD, 52-53 MWS, 52-53 MWU, 50-52 MWW, 27, 34, 53 MWWS, 53 MXW, 32, 34 MYW, 32 N National, 1 NB, 5, 7, 9, 13-14, 38, 47 NBDC, 7-9, 13-15, 17 NBM, 18, 41-42, 44, 46, 48-49 NBMH, 18, 46-49 NCM, 18 NCMH, 18 NEC, 8, 16 necessary, 48 needs, 7 Neutral, 5 New, 42 new, 18 NG, 1-6 NM, 18-21, 36, 38-40 NN, 11-12, 30 No, 1, 5, 38 Non, 22-23 non, 8, 16, 19 None, 43-45 Not, 37, 48, 57 not, 1-2, 5, 8, 14-15, 19, 39-40, 43-45, 57 Note, 14-15, 18, 22, 31, 37, 55, 57 Notes, 3-5, 8, 10-13, 16, 19, 39-46, 48-49, 56 Number, 1-6, 9-14, 17, 22-40, 46-48, 56-57 number, 2, 7, 10, 15, 43-44, 55 Numbers, 43-46, 48-49 numbers, 2-4 Index nuts, 48 P O of, 2-5, 7, 9-10, 14-19, 38, 40-42, 46-49, 55, 57 OFF, 5-6 offering, 41 offers, 7 oil, 5 olts, 6 ON, 5-6 On, 1, 7, 18, 55 on, 1, 3-5, 7, 16, 18, 41, 43-44, 48-49, 54-55 One, 15, 56 one, 16 Online, 1 Only, 10-13, 19, 23-36, 46, 48 only, 2, 16, 18, 39-40, 43-48 OnlyContinuous, 29, 35 open, 55 opening, 57 openings, 5 opens, 49 operable, 5 operate, 7 Operating, 21 operating, 5 operation, 57 opposite, 16 Optional, 7, 47, 57 optional, 56-57 Options, 1, 5, 57 or, 1-57 Order, 13 order, 10-13, 48 ordered, 57 Ordering, 1, 5 originally, 49 Other, 5, 41 other, 5, 55 outdoor, 5 outer, 22 outlines, 18 Output, 57 output, 1 outside, 49 overload, 1, 14 Overview, 18, 41 Package, 5, 47 package, 38 packages, 48 Padlockable, 38 padlocked, 5 padlocks, 5 Page, 1, 7-8, 18, 41, 43-44, 49, 55 Panel, 48, 57 panel, 56-57 Panels, 48 panels, 55 parallel, 8, 14 parellel, 12 part, 15 PB, 7, 9, 13 PBDC, 7-9, 13, 15, 17 Per, 19, 48 per, 1, 8, 15-16, 18, 48 performance, 7, 18 permit, 15 phase, 3-4, 55 physical, 41 physically, 18 pick, 42 Picks, 49 Pickup, 3-4, 20, 56 pickup, 1, 18-19, 55, 57 Pigtail, 39 pilot, 57 PK, 5, 15, 40 PKBreaker, 5 Plate, 57 PLK, 38 plug, 45 Plugs, 37 plugs, 37 plus, 47 point, 49 Pole, 10-13, 15, 22-37, 41, 46, 48 pole, 2, 8-9, 11-12, 14-15, 22, 38-40, 46, 48 Poles, 2, 8-9, 14, 16-17, 41, 43-46 poles, 7-8, 12, 16, 19, 22, 41 position, 5 possible, 18 power, 3-4, 7, 41, 55, 57 powered, 1 pre, 55 presented, 2 Index pressure, 47, 55 prevent, 5 previously, 41 Price, 48 Prices, 48 primarily, 41 procedures, 18 Product, 1, 3, 7, 10, 18, 22, 41, 43, 55-56 properly, 55 protect, 55 Protection, 1-57 protection, 1, 7, 14, 19, 49, 55, 57 protective, 5 proven, 18 provide, 7, 14, 18-19, 57 provides, 1 Purpose, 5 purpose, 5 pushbutton, 57 Q Quick, 8 R Rainproof, 5-6 Range, 3-5, 14, 23-38, 43-47 range, 1, 5, 18-19, 45, 47, 57 rangeof, 5 Ranges, 14 ranges, 18-19, 57 ranging, 7 Rated, 43-45, 56 rated, 8, 16, 19, 42, 49, 57 Rating, 3-5, 9-14, 19-37, 39-41 rating, 1, 3-4, 19, 41, 45, 49 Ratings, 5-6, 8, 57 ratings, 2, 7-8, 39-40, 49 RD, 38 Rear, 13, 48 rear, 41 Recommendations, 1 Recommended, 57 Rect, 56 Refer, 7 Reference, 8, 41, 43-44, 50-54 reference, 41, 43-44 Regulations, 18-19 Relay, 55-57 relay, 55-57 relaying, 55 Relays, 55-56 relays, 55, 57 Release, 20, 39, 42, 49 release, 15, 43-45 releases, 42 remote, 7, 49 removable, 56 Replace, 43-44 replace, 10 Replacement, 18 replacement, 41, 46, 49 replacements, 18 required, 1, 15, 48, 56 requirements, 7, 57 requires, 15, 56 requiring, 14 RES, 37 Reset, 49 reset, 39, 42-45, 49, 56-57 resetting, 57 Resistive, 41 Resistors, 42 resistors, 49 Reverse, 2 reverse, 1 RFDN, 5-6 RH, 39-40 ries, 16 Right, 15, 39-40, 49 right, 18, 46 rigid, 18 Ring, 38 rip, 36, 44 RJDN, 5-6 RKDN, 5-6 RLDN, 5-6 RM, 18-21, 23, 37-40, 51 RML, 51 RMS, 51 rms, 18 RMU, 51 RNDN, 5-6 RP, 39 RPK, 5, 15, 40 RTWK, 38 Index S Same, 5 same, 7, 48, 57 satisfies, 1 SC, 7 scale, 7 Se, 16 Sealed, 22-23 sealed, 15 seals, 49 See, 8, 18, 43-44 see, 48 select, 7, 56 selected, 55 Selection, 1-2, 5-7, 9-10, 18, 22, 41, 43, 56 SelectionAccessories, 55 SelectionThe, 3 selective, 57 Self, 57 semi, 55-57 sends, 57 sense, 55 sensing, 18, 55 Sensor, 56-57 sensor, 55-57 sensors, 55, 57 separate, 57 separately, 13, 57 Series, 7-9, 14, 16, 18-19, 30, 41-44, 50-54 series, 7-8, 16, 19, 41 serve, 5 Service, 1, 7, 18, 41-47, 55 service, 5, 18-19, 41, 46 Sets, 40 Setting, 19 setting, 19, 57 settings, 18-19, 55 several, 18, 57 severe, 5 SFDN, 5-6 sheet, 5 Shields, 48 Short, 48 short, 1, 8, 19, 48 should, 15 shown, 7-8 Shunt, 5, 21, 40, 42-43, 49, 57 shunt, 43-44, 55-57 side, 2 Signal, 19, 40 signal, 57 simplified, 1 simulated, 57 simultaneously, 57 Single, 9-10 six, 48 Size, 5, 19, 46, 56 size, 19 Sizes, 6 sizes, 57 SJDN, 5-6 SKDN, 5-6 SLDN, 5-6 SNDN, 5-6 SNT, 5, 15, 40 solar, 7 Sold, 48 solenoid, 49 Source, 18, 54 sources, 7 Special, 41 special, 1, 5, 48-49 Specialty, 1-57 specifically, 1, 19 Specifications, 1, 6, 55, 57 specifications, 5, 18 specified, 19, 49 specifying, 57 Standard, 1, 5, 10-14, 43-44, 47, 49 standard, 1, 5, 7, 55, 57 Standards, 1, 55 standards, 1, 15 standby, 1 State, 18 status, 7 std, 38 Steel, 14 steel, 5 Stud, 48 stud, 41, 48 Studs, 48 studs, 3-4, 48 Style, 43-49 style, 43-44 substantially, 8 sufficient, 48 Suffix, 2, 9 suffix, 2 Suitable, 16, 55-56 suitable, 1, 5, 46, 55 supersede, 18 Superseded, 50-54 Index Supplement, 7 Supplied, 42 supplied, 16, 49 Supply, 20-21 supply, 7 Support, 1-57 Surface, 5-6 surface, 5, 55-56 swelled, 7 Switch, 5, 19, 40 switch, 9, 15, 49, 55 Switches, 14 switches, 7, 14, 57 switching, 7 Symmetrical, 6, 8, 19, 41 System, 57 system, 55, 57 systems, 7, 16 T TA, 5, 10-14, 24, 26, 38, 47, 52-54 table, 3, 18 tables, 7, 19 tap, 3-4 TC, 18, 52, 54 TD, 18, 24, 26, 52-54 Tech, 1-57 Technical, 1, 6, 55, 57 Terminal, 14, 39, 47-48 terminal, 16 Terminals, 10-14, 22-23, 38, 43-44, 47 terminals, 2-5, 9-13, 47-48, 57 TerminalsType, 5 tesetd, 8 Test, 56-57 test, 55, 57 testing, 18 TF, 52, 54 TG, 52, 54 than, 18 that, 1, 15-16, 19, 48 The, 1, 3-5, 7, 18-19, 45, 55, 57 the, 1, 3-5, 7, 15, 18-19, 41, 48-49, 55, 57 their, 7, 55, 57 Thermal, 3, 10-13, 22, 24, 26, 31, 34, 46 thermal, 1, 3-4, 19, 31, 39, 43-45 These, 14, 57 these, 1, 7, 18, 43-44, 57 They, 14 Thickness, 48 thickness, 48 This, 1-2, 5, 48, 55, 57 this, 49 Thread, 48 Three, 2, 9-13, 16, 22-37, 46 three, 3-5, 7, 38 threegenerator, 3 through, 1, 3, 5, 7-8, 57 Time, 8, 18, 54 time, 55, 57 times, 1 TJ, 52, 54 TK, 52, 54 TKDM, 53 TL, 31, 52, 54 TM, 23, 25, 27, 29, 32-33, 35, 43-45, 50-54 TMA, 25, 27, 52-54 TMC, 25, 52 TMD, 25, 27, 52-54 TMF, 25, 27, 52, 54 TMG, 25, 27, 52, 54 TMJ, 25, 27, 52, 54 TMK, 25, 27, 52, 54 TML, 25, 27, 32, 51-52, 54 TMN, 27, 32, 34, 54 TMP, 32, 34, 54 TMR, 27, 32, 54 TMU, 51 TMW, 27, 34, 54 TMX, 32, 34, 54 TMY, 32 TN, 34, 54 To, 7, 41 to, 1-2, 5, 7-8, 16, 18-19, 41-42, 48-49, 55, 57 Total, 42 TP, 54 TR, 54 Trailing, 19 trailing, 18 transportation, 8 Trip, 2, 5, 9-13, 21-37, 40, 42-46, 57 trip, 1, 3-4, 9-13, 15, 18-19, 43-46, 55-57 tripped, 57 tripping, 7, 49, 57 Trips, 49 trips, 49, 57 TripsFor, 49 true, 18 TS, 54 Tube, 48 Index tube, 48 TW, 54 Two, 9-10, 12, 16, 19, 41, 48 two, 1, 8, 12, 14, 22 TX, 34, 54 Type, 1, 5-8, 10-14, 18-21, 38-49, 55 type, 43-45, 47, 49 TypeFBM, 47 Types, 56 Typical, 56 U UL, 1, 5-8, 14-15, 47-48, 55, 57 UM, 23, 51 under, 15, 55 understanding, 2 Undervoltage, 15, 20, 39, 42, 49 undervoltage, 43-45, 49 Underwriters, 1, 5, 15, 48, 55 ungrounded, 7, 16, 41 Unit, 9-13, 22-37 unit, 1, 9-13, 18-19, 56 Units, 46 units, 3-4, 18-19, 46, 57 unusually, 5 up, 8, 42, 49 upgrade, 41 UPS, 7 upstream, 57 Use, 8, 16, 38, 57 use, 5, 7, 16, 22, 47-48, 57 Used, 56-57 used, 2, 14, 18, 47-48, 57 user, 1 using, 7 UVE, 54 UVH, 15, 39 UVM, 39 UVR, 15, 39, 42-46, 49 V VA, 20-21, 42 Vac, 3-5, 15, 18-37, 39-40, 43-44, 49, 57 various, 57 Vdc, 5, 8, 10-16, 19-27, 30-32, 34, 39-40, 43, 49, 56-57 VdcSingle, 41 vehicle, 7 verified, 18 very, 1 Volt, 45, 56-57 volt, 39, 45-46, 57 VoltAC, 41 Voltage, 19-21, 39-40, 49 voltage, 3-4, 7-8, 39-40, 42, 49, 57 voltages, 7-8, 49 Volts, 6, 8, 14, 41-42, 49 volts, 43-45 Volume, 1-57 W WA, 51-53 Warning, 57 warning, 57 was, 18 WD, 51-53 Weight, 6 Weights, 1, 6 well, 7 Westinghouse, 41 When, 47, 55, 57 when, 1, 45, 49, 55, 57 Where, 15 where, 1, 5, 48 which, 55, 57 wide, 18-19 Width, 17 will, 55, 57 Window, 56 window, 57 Wire, 5, 14, 38, 47 wire, 47 wired, 12 Wiring, 7, 16 With, 14 Index with, 1-3, 5, 7-8, 10, 12, 14-16, 18-19, 22-39, 43-44, 47-49, 55-57 within, 49, 57 Without, 2-3, 9, 14 without, 2, 9-10, 13, 56 WK, 14, 53 WLSI, 37 WS, 51-53 WU, 50-53 www, 1-57 Y YM, 23 ype, 5 Z zone, 56-57