fire alarm/security system part 1

advertisement
GLMV #10093.000
DIL009
Larned, KS
SECTION 28 31 00 - FIRE ALARM/SECURITY SYSTEM
PART 1 - GENERAL
1.1
SUMMARY
A.
Section includes
1.
Fire alarm/security system:
a.
b.
c.
2.
1.2
Insure that each of the devices listed in this specification are incorporated into the
design of the fire alarm system and the security alarm system.
Provide one control panel for the fire alarm system and a separate control panel for
the security alarm system. Combining of the systems will not be permitted.
Provide fire alarm wiring to fire alarm system devices and wiring to make
connection between fire alarm panel and HVAC control system panel to shut down
all air handlers
Upgrade of Existing Fire and Security Systems: Any equipment or wiring to be reused
must be compatible with the new Bosch control panel. Reuse of any existing equipment
must be approved by Owner in writing prior to Bid Date.
SYSTEM DESIGN
A.
The design drawing and subsequent installation drawings of the fire alarm system shall be
designed to obtain the minimum compliance and installed in accordance with the latest edition
of NFPA 72. In addition, the design drawing and subsequent installation drawings shall meet
the requirements of this Section, the authority having jurisdiction and complete in all respects
and in operating condition including its supervision.
B.
The design drawing and subsequent installation drawings of the security system shall cover all
areas of the buildings and shall meet the requirements of this Section and be installed complete
in all respects and in operating condition including its supervision.
C.
In the absence of design drawings in the Construction Documents, the fire alarm and security
system shall be designed to obtain the minimum compliance and installed in accordance with
the latest edition of NFPA 72 and specifications Section 28 31 00. All components, materials,
and methods shall be in accordance with NFPA 72 and as listed by Underwriters Laboratories,
Inc. or FM Global, or the requirements of “The Kroger Co.”
D.
Construction Documents and Shop Drawings should include a floor plan with device locations
and room identification, a graphic symbol legend, a riser diagram, a matrix of operations,
applicable general notes, a description of the secondary power supply, and other data necessary
for the fabrication and installation of the fire alarm/security system, and any required changes or
revisions thereof necessary to obtain approval from the authority having jurisdiction.
FIRE ALARM/SECURITY SYSTEM
283100_FireAlarmSecuritySystem_10-19-10.doc
ADDENDUM NO. 1
28 31 00 - 1
GLMV #10093.000
E.
1.3
DIL009
Larned, KS
No extra charges will be allowed for changes to drawings required to conform to NFPA 72, the
Owner’s requirements, of the authority having jurisdiction, the Owner's underwriter, or with
conflict with other trades. Design drawings become the property of the Owner.
STANDARDS
A.
The equipment and installation shall comply with the current applicable provisions of the
following standards:
1.
2.
NFPA 70, The National Electrical Code (including Article 760)
National Fire Protection Standards (including but not limited to):
a.
b.
c.
d.
3.
4.
5.
B.
Central Station Signaling Systems-Protected Premises Unit
National Fire Alarm and Signaling Code
Automatic Fire Detectors
Life Safety Code
Local and State building codes;
Requirements of the Local Authority Having Jurisdiction (AHJ);
Underwriters Laboratories, Inc.
The system and all components shall be listed by Underwriters Laboratories, Inc. for use in Fire
Protective Signaling Systems under the following standards as applicable. Not all of the
standards will apply to all projects, see Drawings for more information:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
1.4
NFPA 71
NFPA 72
NFPA 72
NFPA 101
UL 864
Control Units for Fire Protective Signaling Systems (including
UUKL sublisting)
UL 268
Smoke Detectors for Fire Protective Signaling Systems
UL 268A
Smoke Detectors for Duct Applications
UL 217
Smoke Detectors, Single and Multiple Station
UL 521
Heat Detectors for Fire Protective Signaling Systems
UL 228
Door Closers-Holders for Fire Protective Signaling Systems
UL 464
Audible Signaling Appliances
UL 1638
Visual Signaling Appliances
UL 1971
Signaling Devices for the Hearing Impaired
UL 38
Manually Actuated Signaling Boxes
UL 346
Water flow Indicators for Fire Protective Signaling Systems
UL 1481
Power supplies for Fire Protective Signaling Systems.
UL 609, 1610, 1635 Commercial Fire and Intrusion Alarm systems.
FIRE ALARM SYSTEM OPERATION
A.
When a fire alarm condition is detected by one of the system initiating devices, the following
functions shall occur simultaneously.
1.
2.
3.
System point shall be shown on the panel by type of device, location and time of day.
The audio-visual alarm devices shall activate throughout out the building.
The digital dialer shall notify the monitoring company (as listed in the execution portion
of this specification) that an alarm condition exists.
FIRE ALARM/SECURITY SYSTEM
283100_FireAlarmSecuritySystem_10-19-10.doc
ADDENDUM NO. 1
28 31 00 - 2
GLMV #10093.000
4.
5.
B.
DIL009
Larned, KS
Shut down all air handlers, unless specifically forbidden by the authority having
jurisdiction.
Low air pressure monitoring of air compressor of any dry pipe system.
When a trouble or supervisory condition occurs, the following functions shall occur
simultaneously.
1.
2.
3.
System point shall be shown on the panel by type of device, location and time of day.
A distinct trouble sound shall occur at the panel.
The digital dialer shall notify the monitoring company (as listed in the execution portion
of this specification) that a trouble condition exists.
C.
Whenever a smoke, duct or heat detector is tripped, alarm verification shall function and a timer
shall start. After a program time delay compliant with prevailing codes, the horn strobes shall
sound if the detector is still in alarm.
D.
The system shall monitor for head sensitivity and give a warning message if the smoke or duct
detector needs cleaning.
E.
The system shall be fully field-programmable with the equipment on site or a programmer.
While programming, the system shall continue to operate, polling devices currently in the
program.
F.
Other features of the system shall include the following.
1.
2.
3.
4.
5.
6.
7.
8.
1.5
Walk test
Enable disable of device
Read status of any point
Field programmable at keyboard
Multiple password protection
Manual on/off for any output point
Time of day clock
Calibrated smoke detector test
SUBMITTALS
A.
General:
1.
2.
3.
B.
Pay application fees and obtain approval of submittals in writing from the State Fire
Marshal's office and/or the local authority having jurisdiction prior to submittal to
Owner’s Representative for review.
Submit fire alarm submittals to the Owner’s Representative within 30 calendar days after
award of Contract.
Permit Drawings and other Submittals shall be prepared by a fire alarm installer certified
by the approved manufacturer of the fire alarm system.
Product Data: Complete documentation for the fire alarm system showing the model number,
type, rating, size, style, manufacturer's names, and manufacturer's catalog data sheets for items
to ensure compliance with these specifications.
FIRE ALARM/SECURITY SYSTEM
283100_FireAlarmSecuritySystem_10-19-10.doc
ADDENDUM NO. 1
28 31 00 - 3
GLMV #10093.000
C.
DIL009
Larned, KS
Shop Drawings
1.
2.
3.
Complete set of permit drawings showing conduit sizes and number of conductors
required to components plus detailed wiring connections required at each type of device
based on the level of the fire alarm system indicated in the Contract Documents.
Detailed drawings showing the intended location of field devices and their connections to
the system along with room identification and a graphic symbol legend. Prepare
submittal drawings utilizing AutoCad Release 2009 or newer Computer Aided Drafting
system.
Detailed wiring diagrams and riser diagrams showing color-coding of wiring per
manufacturer recommendations. Include calculations showing adequate capacity of the
standby batteries, where applicable, as required by prevailing codes.
D.
Monitoring Data Form: Complete per the directions and in coordination with Owner and return
to the addresses shown a minimum of 30 days prior to system testing and activation.
E.
Technician Install/Conversion Form: Complete per the directions and return to the addresses
shown a minimum of 30 days prior to system testing and activation.
1.6
QUALITY ASSURANCE
A.
Installer Qualifications: A qualified firm that is approved, authorized, or licensed by fire
alarm/security system manufacturer to install manufacturer's product and that is eligible to
receive manufacturer's special warranty.
B.
The alarm control unit shall be supplied with all cards and future expansion slots needed for a
complete operating system.
C.
Provide system with a 3-year warranty for the control panel starting from the time this system is
operational.
1.7
PROJECT CONDITIONS
A.
Upgrade of Existing Fire and Security Systems:
1.
2.
3.
4.
5.
Reuse as much existing wiring and equipment as possible.
Obtain Owner’s written permission for any existing fire and security alarm panels to
remain in use as part of final design incorporating separate panels.
Existing fire and security alarm systems should remain in operation during remodel
projects to insure protection.
Should a fire alarm system need to be shut down for more than an hour a standard fire
watch must be put in place until the system is reactivated. All system shut downs must
have owner’s prior written permission and it will be the contractor’s responsibility to
notify the local fire department, authority having jurisdiction and KCAC prior to shut
down. Notify KCAC when systems are being reactivated.
Reuse only smoke detectors that are intelligent addressable duct mounted photoelectric
smoke detectors and compatible with new panel.
FIRE ALARM/SECURITY SYSTEM
283100_FireAlarmSecuritySystem_10-19-10.doc
ADDENDUM NO. 1
28 31 00 - 4
GLMV #10093.000
DIL009
Larned, KS
PART 2 - PRODUCTS
2.1
MANUFACTURERS
A.
Manufacturer: Provide products identified in other Part 2 articles by Bosch Security Systems,
Inc. (Fire and Intrusion). Contact Wayne Bidwell at 734-255-5500 cell or 800-289-0096 office
for questions regarding the equipment and/or applications. No substitutions are allowed.
1.
2.
2.2
This specification requires that a Bosch certified security dealer be contracted to install a
complete system, honor the warranty, provide the training and service the system after
the warranty period expires. Bosch should not be contacted for project bids or to provide
equipment to the electrical installers.
Products (other than products by Bosch Security Systems, Inc.) identified as Basis of
Design in other Part 2 articles are identified to set the standard of quality for equipment
used.
APPROVED INSTALLERS
A.
Local installer certified by equipment manufacturer:
B.
National certified installers:
1.
Carter Brothers LLC - A Certified Minority Business Enterprise.
a.
b.
2.
Checkpoint Systems, Inc.
a.
3.
Ross Balano: (913) 208-0899,ross.balano@niscayah.us.
Vector Security, Inc.
a.
b.
2.3
DeeAnna Duncan: (678) 288-3811, deeanna.duncan@coliantsolutions.com.
Jeff Cullop: (678) 288-3810, jeff.cullop@coliantsolutions.com.
Niscayah Group.
a.
5.
Terry Petrucci: (248) 303-6220 terry.petrucci@checkpt.com.
CoLiant Solutions.
a.
b.
4.
Steve Board: (404) 391-7176, sboard@carterbrothers.com.
Scott Dexter: (404) 227-5479, sdexter@carterbrothers.com.
Rich Brostrom: (949) 433-2141, rbrostrom@vectorsecurity.com.
Ted Day Jr: (949) 933-3450, teday@vectorsecurity.com.
GENERAL
A.
Incorporate each of the devices listed in this specification into the design of the Fire Alarm
System and the Security Alarm System.
FIRE ALARM/SECURITY SYSTEM
283100_FireAlarmSecuritySystem_10-19-10.doc
ADDENDUM NO. 1
28 31 00 - 5
GLMV #10093.000
DIL009
Larned, KS
B.
Provide a complete addressable fire alarm system throughout the building as shown on the
drawings and in accordance with NFPA 72 and authorities having jurisdiction. Equipment shall
be UL listed.
C.
Each smoke detector shall be addressable for the exact location in the building and provide
“dirty” maintenance type messages at the annunciator, central station and remote programming
software. Manual stations, sprinkler devices and all other "contact only" closing devices shall be
addressable.
D.
If existing raceways, cables and outlet boxes are suitable for re-use, they may be reused after
demonstrating to Owner’s representative that they have been tested and proven to be suitable.
Include existing cable used in three year warranty.
2.4
PANELS
A.
Main Fire Alarm Control Panel (FACP/FAP)
1.
Main Control Panel:
a.
2.
Bosch Security Systems: Model FPD7024 or D7412/9412GV2 and shall be located
in the ECR room.
Equip control panel to provide the following capacities:
a.
b.
c.
d.
e.
Data loops: 2
On-board points: 4 or 8
Addressable points: 255 or 238
Programmable horn circuits: 2 or 3
Integrated network communications capable, dialer capture module will not be
accepted
1)
f.
3.
B.
Number of Boards (i.e. “cards”) determined by system designer.
Real Time clock
Provide fire alarm system with the capability to communicate with a digital receiver such
as the Bosch/Radionics D6600 receiver.
Main Fire Alarm Control Panel: Include the following:
1.
CPU (Central Processing Unit): For fire alarm programming including the following:
a.
b.
c.
2.
Programming protection in the event of a power failure.
Addressable communication transmission.
History of the least 499 - 1000 activities.
DIA Display Interface Board:
a.
b.
c.
32 or 16-character liquid crystal display command center.
Local or remote programming.
Two different passwords required for programming.
FIRE ALARM/SECURITY SYSTEM
283100_FireAlarmSecuritySystem_10-19-10.doc
ADDENDUM NO. 1
28 31 00 - 6
GLMV #10093.000
DIL009
Larned, KS
d.
LEDs for AC Power, Fire Alarm, Security Alarm, Supervisory signal, System
Trouble, Disabled points and Alarm Silenced.
Main power supply for the panel and for peripheral devices with 120VAC 60HZ
input power or transformer and an integral charger for batteries usable for
peripherals.
SIC data loop board(s) capable of handling 255 or 120 detectors/modules per
board.
A serial interface board for printer or display terminal.
Ceiling mounted smoke detector located above the Fire Alarm Control Panel
(FACP).
Battery backup shall comply with Section 1-5.2.6 of NFPA -72.
e.
f.
g.
h.
i.
2.5
CIRCUITS
A.
Provide a Class B wiring system.
B.
Provide 15 percent capacity for future expansion of A/V alarm device and data loop circuits.
C.
For line voltage circuits, use standard 14 ga. copper wire with THHN insulation.
D.
For low voltage circuits, use twisted shielded 16 ga. stranded copper wire.
2.6
MANUAL PULL STATIONS
A.
Bosch Security Systems; FMM-7045-D or FMM-462-D.
B.
Mount in accordance with local building codes and as called out in NFPA 72.
C.
The unit shall be dual action (i.e. requiring two motions to activate the station) and shall be
addressable for connections to the fire alarm control panel(s).
D.
Unit shall meet UL 38, standard for manually actuated signaling boxes.
2.7
CEILING/WALL SMOKE DETECTORS
A.
Bosch Security Systems; D7050 with D7050-B6 base or F220 series smoke with F220-B6PM/S
POPIT bases.
B.
Provide base for all applications where auxiliary contacts are required.
2.8
DUCT SMOKE DETECTORS
A.
Intelligent Addressable Duct Mounted Photoelectric Smoke Detectors:
1.
Bosch Security Systems; D343 Series Duct Detector Housings.
a.
If used with 9000 Series panel provide D9127U addressable single point module.
FIRE ALARM/SECURITY SYSTEM
283100_FireAlarmSecuritySystem_10-19-10.doc
ADDENDUM NO. 1
28 31 00 - 7
GLMV #10093.000
DIL009
Larned, KS
b.
If used with the D7024 or FPD7024 provide D7044M addressable single point
module.
2.
3.
4.
5.
6.
7.
Provide UL 268A listed unit with two LEDs that will provide local alarm indication and a
remote alarm output will be required for use with auxiliary devices.
Operating Velocities: 300 to 4000 feet/minute (91 to 1219-m/minute).
Provide sampling tube per NFPA, test station and all other required accessories.
The shut down of air handlers shall occur via a signal from the Fire Alarm Panel should
any smoke detector be activated, unless specifically forbidden by the authority having
jurisdiction, in which case provide auxiliary contact as required to shut down equipment
and wire into the stop circuit of the associated air handler starter.
Provide remote magnetically or key activated test station (with status/alarm/trouble
indicating LEDs), on the ceiling, column, or wall beneath the duct detector as indicated
on Drawings or as determined in field. Provide engraved (or approved equivalent
method) plate at each remote station to read: “#### Duct Smoke Detector”, where ####
is the equipment identification used on Drawings. Install test stations at 80-inches (2032mm) above finish floor (AFF).
Provide required power and control wiring so that upon detection of smoke, the following
sequence of operations occurs where applicable:
a.
b.
c.
2.9
A supervisory alarm signal is sent to the fire alarm control panel and to the
monitoring central station.
All HVAC units shut down (including applicable dampers).
Associated smoke dampers close (wired to automatically re-open on duct detector
reset).
HEAT DETECTORS
A.
Addressable Heat Detectors:
1.
2.
2.10
Bosch Security Systems; F220 series detectors with applicable base.
Provide both rate of rise and fixed temperature with 135 degrees F. (57 degrees C.) alarm
threshold.
FIRE ALARM DEVICES
A.
General: Alarm devices listed below shall meet requirements of the NEC and NFPA-72.
B.
Horn/Strobe Units
1.
2.
3.
4.
5.
6.
Basis of Design: Wheelock or Gentex
Comply with ANSI S3.41 temporal code, when required by authority having jurisdiction.
Synchronize strobe units wherever required by authority having jurisdiction, including
ADAAG.
Color: Red
Strobe: Minimum 75 candela ADA-compliant.
Mounting: Semi-flush mounting plates, ceiling or bottom of open steel structure
whenever possible, wall mounted (only when required) at 80-inches (2032-mm) as shown
on Drawings.
FIRE ALARM/SECURITY SYSTEM
283100_FireAlarmSecuritySystem_10-19-10.doc
ADDENDUM NO. 1
28 31 00 - 8
GLMV #10093.000
C.
Strobe-Only Units
1.
2.
3.
4.
5.
6.
2.11
A.
Remote Annunciators
4.
5.
2.12
A.
Sprinkler tamper and flow switches will be provided by the fire protection installer.
Provide a monitor module approved for use with system that will be connected to the data
loop of the fire alarm system.
Monitor Modules
1.
D.
Bosch model D7036 or D1256
Remote annunciator shall be provided with a liquid crystal display.
Provide with two 32 or 16 character displays with an audible signal to show alarms and
troubles.
Locate remote annunciator at constantly attended location (customer service office);
exact location shall be coordinated with Owner and local fire department.
Locate additional remote annunciator in or near the main entrance when required by the
local fire department.
Sprinkler Devices
1.
C.
Basis of Design: Wheelock or Gentex
Comply with ANSI S3.41 temporal code, when required by authority having jurisdiction.
Synchronize strobe units wherever required by authority having jurisdiction, including
ADAAG.
Color: Red.
Luminous Intensity: Minimum candela units as required to comply with ADA and/or the
equivalent NFPA 72 requirements resulting in the minimum number of devices.
Mounting: On ceiling or to the bottom of open steel structure whenever possible, Wall
mounted (only when required) at 80-inches (2032-mm) as shown on Drawings.
ACCESSORY DEVICES
1.
2.
3.
B.
DIL009
Larned, KS
Provide as required to interface "non-intelligent" devices into the system as shown on the
Drawings (i.e. Sprinkler Flow Switches, Tamper Switches, Pressure Switches, Kitchen
Hoods, etc. as applicable).
Provide required relays for auxiliary devices including door closures and supervised control
functions such as air handler shut-downs.
DIGITAL COMMUNICATOR (“DIALER”)
Description: Digital communicator programmed to report to the Owner’s UL LISTED
CENTRAL STATION monitoring agency via two non-dedicated telephone lines or via the store
(WAN) Wide Area Network and one backup PBX extension. Do not install network module
unless directed by Owner.
FIRE ALARM/SECURITY SYSTEM
283100_FireAlarmSecuritySystem_10-19-10.doc
ADDENDUM NO. 1
28 31 00 - 9
GLMV #10093.000
1.
2.
3.
B.
2.13
A.
SECURITY ALARM SYSTEM
Security Alarm Control Panel
4.
Product: Bosch Security Systems; D1255.
Provide separate keypads for each area of the system.
Keypad installation shall be located at constantly attended location (customer service
office), exact location shall be field verified with Owner.
Provide an additional keypad inside the pharmacy beyond reach from the security grille
to control the pharmacy alarm, verify exact location with Owner.
Keypads: DSD door location.
1.
2.
D.
Main Control Panel: Bosch Security Systems; D7412/9412GV2.
Configure system to accommodate the needs of this store. Supply panel with all security
modules and future expansion slots needed for a complete operating system.
Keypads: Pharmacy and customer service office locations.
1.
2.
3.
C.
Product: Bosch D9068 DACT.
Provide one duplex telephone outlet connected to a non-dedicated telephone line (with two
RJ31X connecting block jacks) within two feet (610-mm) of the Fire Alarm Panel/Digital
Communicator for back up connection to telephone system.
1.
2.
B.
UL station will be the Owner’s central alarm control monitoring company (KCAC
04002/31A). COMPLETE THE CENTRAL ALARM CONTROL MONITORING
DATA FORM INCLUDED AT THE END OF THIS SPECIFICATION.
The dialer and/or network module will be UL listed for fire alarm use.
Mounting: Mount in single equipment housing containing battery charger and battery
with coupler cable.
Equip fire alarm systems that are being upgraded with a new communicator and tie to (KCAC).
1.
C.
DIL009
Larned, KS
Product: Bosch Security Systems; D279A- Independent zone control.
Configure to shunt a 24-hour point on the system, all users to use the same code.
Door Switch
1.
2.
Basis of Design: GE Security; Sentrol
Provide at doors that enter the space. When door is equipped with a delayed egress device
utilize activation contact and delete door switch. Typical areas include but are not limited
to the following:
a.
b.
c.
d.
e.
f.
Customer entrances
Employee entrances
Emergency egress doors
Dock rolling and other delivery doors
ECR or Data room
Roof hatch
FIRE ALARM/SECURITY SYSTEM
283100_FireAlarmSecuritySystem_10-19-10.doc
ADDENDUM NO. 1
28 31 00 - 10
GLMV #10093.000
g.
3.
E.
2.
Install wiring for door switch in conduit to a junction box adjacent to door jam. Install
wiring from junction box to door switch in surface raceway or flexible conduit depending
on the installation.
Bosch Security Systems; ISC-PDL1-WA18G wall-mount motion, DS9360 (up to 17 feet)
and DS9370 (above 17 feet) ceiling mount motions.
Install on ceiling or on wall 80 inches (2032 mm) above finish floor in locations shown
on the Drawings. Other typical areas include but are not limited to the following:
a.
b.
Basis of Design: GE Security; Sentrol.
Install on other areas where operation of entry gates/grilles or hatches may be desired.
Typical locations would include but are not limited to the following:
a.
Pharmacy rolling gate, one on each gate.
Glass Break Sensors
1.
2.
H.
Pharmacy: Provide sensors above and below ceiling to detect motion.
Entrance vestibule
Contact Switch
1.
2.
G.
Emergency egress door from Fred Meyer Jewelry Store, when indicated.
Motion Sensors
1.
F.
DIL009
Larned, KS
Basis of Design: Intellisense-N FG-730 25’ Wall/Ceiling Glass break-Square
Equip each display window with a glass break sensor, install so that cable is not
exposed and the detector and is hidden from customer view.
Security System Monitoring Devices
1.
2.
Basis of Design: GE Security; Sentrol.
Provide in selective equipment as indicated. The equipment typically monitored using
the security system include but are not limited to the following:
a.
b.
3.
CPC refrigeration failure.
Generator fault indicator.
Monitoring of the specialized equipment will require coordination with the equipment
manufacturers. Provide supplemental equipment needed to monitor this equipment for a
complete and operational system.
PART 3 - EXECUTION
3.1
GENERAL
A.
The Authority Having Jurisdiction (AHJ) shall be notified prior to installation or alteration of
equipment and wiring.
FIRE ALARM/SECURITY SYSTEM
283100_FireAlarmSecuritySystem_10-19-10.doc
ADDENDUM NO. 1
28 31 00 - 11
GLMV #10093.000
3.2
DIL009
Larned, KS
INSTALLATION
A.
Connect 120VAC power for fire alarm equipment to emergency panels where applicable.
B.
Provide required 20A/120VAC power as required to energize components of the security and
fire alarm system. Include home-runs for fire alarm control panels as well as home-runs and
wiring for any accessory devices such as remote power supplies/panels, printer, dialer, etc. as
applicable.
1.
2.
C.
Smoke or Heat Detector Locations:
1.
2.
3.
D.
E.
1.
Duct smoke detectors are typically shown schematically at the respective air handling
unit on the Drawings, but shall actually be installed maximizing the distances between
ductwork offsets, and installed ahead of the first branch duct take-off. Coordinate with
HVAC installer and fire alarm manufacturer’s representative in field.
2.
Install duct smoke detectors in the return air duct/plenum of the respective air handling
equipment. Where more than one detector is indicated associated with a particular piece
of air handling equipment, there are special reasons for the additional detectors (i.e. split
returns, return risers serving multiple floors, etc.); coordinate all locations for same with
the HVAC installer.
Digital Communicator (Dialer) Installation
2.
Connect each jack to a separate phone line and install as the first in-house device tied to
the respective phone line. Do not connect the jacks to a party line or a “ground start”
telephone circuit.
Connect digital communicator to operate from three sets of dry contacts on fire alarm
control panel; one set each for alarm, trouble and supervisory (existing conventional fire
panels only).
Delayed Egress Electronic Exit Door Locking System Connection
1.
3.3
Do not exceed the rated coverage of the detector.
Install no more than 15-feet (4.6-m) from a wall or 30-feet (9-m) apart.
Do not install within 3-feet (1-m) of a supply air diffuser.
Duct Smoke Detector Installation:
1.
F.
This requirement applies whether or not such power work is shown on the Drawings.
Dedicate branch circuits serving fire alarm equipment to fire alarm equipment only.
Connect wiring to each door control to automatically unlatch the lock instantly in the
event of a fire emergency.
FIELD QUALITY CONTROL
A.
Manufacturer's Field Service:
Engage a factory-authorized service representative to
inspect, test, and adjust field-assembled components and equipment installation, including
connections, and to assist in field testing.
FIRE ALARM/SECURITY SYSTEM
283100_FireAlarmSecuritySystem_10-19-10.doc
ADDENDUM NO. 1
28 31 00 - 12
GLMV #10093.000
DIL009
Larned, KS
B.
Upon completion of installation, the system shall be checked and tested by a fire alarm
inspector that is State-Licensed, NICET Level II Certified, or approved equivalent. Contact
system manufacturer for this service if installer cannot provide on their own.
C.
After making tests and corrections, conduct a system demonstration for Owner and the authority
having jurisdiction.
3.4
ADJUSTING
A.
Occupancy Adjustments: When requested within 12 months of date of Substantial Completion,
provide on-site assistance in adjusting system to suit actual occupied conditions. Provide up to
two visits to Project outside normal occupancy hours for this purpose.
B.
Follow-Up Tests and Inspections: After date of Substantial Completion, test the fire alarm
system complying with testing and visual inspection requirements in NFPA 72. Perform tests
and inspections listed for three monthly, and one quarterly, periods.
3.5
DEMONSTRATION
A.
Engage a factory-authorized service representative to train Owner's personnel to operate the fire
alarm system.
1.
2.
Provide factory training and onsite or online training at no cost to Owner.
Provide 24 hour/7 days per week/365 days per year technical support at no cost to Owner.
FIRE ALARM/SECURITY SYSTEM
283100_FireAlarmSecuritySystem_10-19-10.doc
ADDENDUM NO. 1
28 31 00 - 13
GLMV #10093.000
DIL009
Larned, KS
Central Alarm Control
1-800-982-2749
503-797-3160
Monitoring Data Form
All fields marked with * must be completed to enable monitoring service
*Store Name:______________________________*Division #:____ *Store #:____*Dept: ____________
*Address: _________________________________________________________*Time Zone ________
*City:__________________________________________________ *State:______ *Zip Code: _______
*Store Main Phone Number: ________________________________*Alarm Panel Type ____________
Does your jurisdiction require an alarm permit? ________ If Yes, what is the permit # _______________
Department Specific Phone #: ___________________________________ Description: _______________
*Local Fire Dispatch # (Not 911): ________________________________________________________
*Local Police Dispatch # (Not 911): _______________________________________________________
Secondary Police and/or Fire Dispatch #, if available: _________________________________________
Electric Company: ___________________________ Gas Company: _____________________________
Water Company: ____________________________ Other: ____________________________________
*Store Manager Name:_____________________________________ Password/EUID#:
_____________
Home # ___________________________________________Cell #: _____________________________
Pager #_______________________________________ Other: __________________________________
*Business Hours: __________________________________ Type of Business: Retail Facility 
*Is the Store/Loc. occupied 24 hours a day? Yes  No  Comments: __________________________
*Emergency Call List: In case of an emergency that requires notification of store personnel after hours, who
do you want contacted? (List in order of notification preference)
*1. Responder (Name & Position)________________________________Password/EUID:____________
Home # ___________________________________________Cell #: _____________________________
Pager #_______________________________________ Order #'s are to be called: __________________
*2. Responder (Name & Position)________________________________Password/EUID:
___________
Home # ___________________________________________Cell #: _____________________________
Pager #_______________________________________ Order #'s are to be called: __________________
3. Responder (Name & Position)________________________________Password/EUID: ____________
Home # ___________________________________________Cell #: _____________________________
Pager #_______________________________________ Order #'s are to be called: __________________
Additional sheet may be attached if needed
FIRE ALARM/SECURITY SYSTEM
283100_FireAlarmSecuritySystem_10-19-10.doc
ADDENDUM NO. 1
28 31 00 - 14
GLMV #10093.000
DIL009
Larned, KS
If KCAC (Kroger Central Alarm Control) is monitoring your burglary alarm please indicate the schedule
for the following areas. Also indicate what action you would like KCAC to take for burglary alarm activity in special instructions. Fire Systems are monitored 24 hours a day. The fire department is dispatched immediately on all fire alarms. If your system is being serviced or needs to be disregarded
for any period of time, call KCAC prior to servicing.
Time ON
(ARM)
Time OFF
(Disarm)
2330 hours (11:30 PM)
0600 hours (6:00 AM)
Area
EXAMPLE: Premise (All Customer Doors)
Day of the
Week/ALL
Every Day
*
*Do you want KCAC to monitor your opening and closing signals?
Yes No 
If YES, what action do you want KCAC to take if the alarm is not turned on by the time specified above:
_____________________________________________________________________________________
_____________________________________________________________________________________
What areas do you wish to monitor?________________________________________________________
*Special Instructions:
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
If this system is currently monitored by a third party service, please complete the following:
rd
1. Who is the name of the 3 party monitoring company: _______________________________________
2. What is the monthly cost for alarm monitoring: ________(Don’t forget to cancel your old monitoring
service)
3. Who is the current equipment owned by: _________________________________________________
* _____________________________ * _______________________________ *
Name of person completing form
Signature
__________________
Date
Please fax or E-mail this completed form to:
Fax: 503-797-3172 or
Lotus Notes: Corp KCAC Alarm Control
E-Mail to: Kcacalarmcontrol.corp@kroger.com
For Additional Information Contact:
Joy & Jesse, Program & Conversion Coordinating....503-797-5411
Denise Whitney, KCAC Manager…………………..503-797-7715
Dean Uriarte, LP Technical Services Manager…….. 503-797-7439
FIRE ALARM/SECURITY SYSTEM
283100_FireAlarmSecuritySystem_10-19-10.doc
ADDENDUM NO. 1
28 31 00 - 15
GLMV #10093.000
DIL009
Larned, KS
Central Alarm Control
Toll 1-800-982-2749, Direct 503-797-3160
Conversion Scheduling # 503-797-5411, Fax # 503-797-3172
Technician Install/Conversion Form
To be completed by service company completing install or conversion - Entire form
Must be completed & submitted to KCAC a minimum of 48 hours prior to scheduled install with KCAC
Store Name:_____________________________________________Division #:_______ Store #: _______
Address: _____________________________________________________________________________
City:___________________________________________ State:______ Zip Code: _________________
Company Name:_____________________________________ Phone # ___________________________
Installer’s Name:_____________________________________ Cell # ___________________________
Panel Manufacturer: ________________________Panel Model #:___________Format : ______________
Primary Panel Phone #: ______________________ Secondary Panel Phone #:______________________
AREA
POINT #
Type of Alarm
Description
Example: Perimeter
158
Burglary
Emergency Exit in garden center
Fire
201
Fire Alarm
Man pull in hallway
100% of Fire Initiating Devices have to be tested at time of conversion
Don't forget to program the daily timer test for every 24 hours
Attach additional sheet if necessary
END OF SECTION 28 31 00
FIRE ALARM/SECURITY SYSTEM
283100_FireAlarmSecuritySystem_10-19-10.doc
ADDENDUM NO. 1
28 31 00 - 16
Download