jackson center one

advertisement
1111 Jackson Street
Oakland, California
JACKSON CENTER ONE
717 Market Street
Suite 500
San Francisco, CA 94103
TEL
415.489.7240
FAX 415.489.7289
www.interfaceengineering.com
SHEET TITLE
SYMBOL LIST,
GENERAL NOTES ELECTRICAL
REVISIONS
DRAWN BY
CR
CHECKED BY
Kevin Kuang
JOB NO.
2014-0284
DATE
DATE
SHEET NUMBER
E0.1
717 Market Street
Suite 500
San Francisco, CA 94103
TEL
415.489.7240
FAX 415.489.7289
www.interfaceengineering.com
1111 Jackson Street
Oakland, California
JACKSON CENTER ONE
PB
SHEET TITLE
SYMBOL LIST,
GENERAL NOTES TECHNOLOGY
REVISIONS
DRAWN BY
CR
CHECKED BY
Jason Nguyen
JOB NO.
2014-0284
DATE
DATE
SHEET NUMBER
E0.2
1111 Jackson Street
Oakland, California
JACKSON CENTER ONE
717 Market Street
Suite 500
San Francisco, CA 94103
TEL
415.489.7240
FAX 415.489.7289
www.interfaceengineering.com
SHEET TITLE
BASEMENT PLAN POWER & SIGNAL
REVISIONS
DRAWN BY
CR
CHECKED BY
Kevin Kuang
JOB NO.
2014-0284
1 BASEMENT PLAN - POWER & SIGNAL
DATE
DATE
SHEET NUMBER
E2.0
717 Market Street
Suite 500
San Francisco, CA 94103
TEL
415.489.7240
FAX 415.489.7289
www.interfaceengineering.com
LAN
SECURITY DESK
main streeet
coffee
bar
graphic
phone
QUEUEING
WAITING
(20 SEATS)
INT 1
SELF-SERVE
INT 3
AAMS PHONES
SELF-SERVE
Lunch Room
1111 Jackson Street
Oakland, California
Pantry
JACKSON CENTER ONE
storage
SHEET TITLE
INT 2
INT 4
CLERKS
FIRST THRU
EIGHTH FLOOR
PLAN - POWER &
SIGNAL
REVISIONS
DRAWN BY
CR
CHECKED BY
Kevin Kuang
JOB NO.
2014-0284
DATE
DATE
SHEET NUMBER
E2.1
1111 Jackson Street
Oakland, California
JACKSON CENTER ONE
717 Market Street
Suite 500
San Francisco, CA 94103
TEL
415.489.7240
FAX 415.489.7289
www.interfaceengineering.com
SHEET TITLE
ROOF FLOOR PLAN
- POWER & SIGNAL
REVISIONS
DRAWN BY
CR
CHECKED BY
Kevin Kuang
JOB NO.
2014-0284
DATE
DATE
SHEET NUMBER
E2.2
717 Market Street
Suite 500
San Francisco, CA 94103
TEL
415.489.7240
FAX 415.489.7289
www.interfaceengineering.com
LAN
2 FIRST FLOOR IDF PLAN - LIGHTING
LAN
1111 Jackson Street
Oakland, California
JACKSON CENTER ONE
1 BASEMENT MDF PLAN - LIGHTING
TYPICAL SECOND FLOOR IDF PLAN
3 - LIGHTING (3F - 8F SIMILAR)
SHEET TITLE
MDF AND IDF
ENLARGED PLANS
- LIGHTING &
POWER
REVISIONS
DRAWN BY
CR
4 BASEMENT MDF PLAN - POWER
5 FIRST FLOOR IDF PLAN - POWER
TYPICAL SECOND FLOOR IDF PLAN
6 - POWER (3F - 8F SIMILAR)
CHECKED BY
Kevin Kuang
JOB NO.
2014-0284
DATE
DATE
SHEET NUMBER
E3.0
717 Market Street
Suite 500
San Francisco, CA 94103
TEL
415.489.7240
FAX 415.489.7289
www.interfaceengineering.com
LAN
1111 Jackson Street
Oakland, California
JACKSON CENTER ONE
QUEUEING
SHEET TITLE
ENLARGED PLANS
AND ELEVATIONS TECHNOLOGY
REVISIONS
DRAWN BY
CR
CHECKED BY
Jason Nguyen
JOB NO.
2014-0284
DATE
DATE
SHEET NUMBER
E3.1
403
717 Market Street
Suite 500
San Francisco, CA 94103
TEL
415.489.7240
FAX 415.489.7289
www.interfaceengineering.com
304
404
504
PANEL
EL6
PANEL
EL3
504
504
1004
1004
1111 Jackson Street
Oakland, California
JACKSON CENTER ONE
504
SHEET TITLE
1004
SINGLE LINE
DIAGRAM - UPS &
EMERGENCY
POWER SYSTEM
PANEL
EL0
REVISIONS
1004
4004
2254
DRAWN BY
BATTERY
UPS
PANEL
EL
1753
CR
4004X
504
PANEL
EH
PANEL
EH1
PANEL
EL2
PANEL
EL1
CHECKED BY
Kevin Kuang
JOB NO.
2014-0284
(E)
DATE
(E)
(E)
DATE
SHEET NUMBER
E4.0
5"
1.2
EIA-TIA EQUIPMENT
FRAME
.5"
12
5"
1.2
"
75
"
1/2"x 16 HEX NUT
1/2" SPLIT LOCK WASHER
1/2" FENDER WASHER
1/2" x 3-3/4" HILTI
QUICK BOLT TZ
CONCRETE ANCHOR
EQUIPMENT RACK
FLOOR PEDISTAL
CONCRETE PAD
DRILL 1/2" HOLE A
MINIMUM OF 4" DEEP IN
CONCRETE. DRIVE
ANCHOR IN WITH A
MINIMUM EMBEDMENT
OF 3-1/4". MINIMUM
ANCHOR TORQUE - 40
LBS. PER ICC-ES 1917
REPORT
1111 Jackson Street
Oakland, California
16
JACKSON CENTER ONE
1.8
717 Market Street
Suite 500
San Francisco, CA 94103
TEL
415.489.7240
FAX 415.489.7289
www.interfaceengineering.com
SHEET TITLE
DETAILS TECHNOLOGY
REVISIONS
DRAWN BY
CR
CHECKED BY
Jason Nguyen
JOB NO.
2014-0284
DATE
DATE
SHEET NUMBER
E4.1
1111 Jackson Street
Oakland, California
JACKSON CENTER ONE
717 Market Street
Suite 500
San Francisco, CA 94103
TEL
415.489.7240
FAX 415.489.7289
www.interfaceengineering.com
SHEET TITLE
PANEL
SCHEDULES ELECTRICAL
REVISIONS
DRAWN BY
CR
CHECKED BY
Kevin Kuang
JOB NO.
2014-0284
DATE
DATE
SHEET NUMBER
E5.0
GENERAL
C.
1.1 SUMMARY
A.
B.
ELECTRICAL SYSTEMS REQUIRED FOR THIS WORK INCLUDES LABOR, MATERIALS,
EQUIPMENT, AND SERVICES NECESSARY TO COMPLETE INSTALLATION OF ELECTRICAL
WORK SHOWN ON DRAWINGS, SPECIFIED HEREIN OR REQUIRED FOR A COMPLETE
OPERABLE FACILITY AND NOT SPECIFICALLY DESCRIBED IN OTHER SECTIONS OF
THESE SPECIFICATIONS. AMONG THE ITEMS REQUIRED ARE:
1. SERVICE AND DISTRIBUTION EQUIPMENT SHOWN ON DRAWINGS.
2. FEEDERS TO UNINTERRUPTIBLE POWER SUPPLY, DISTRIBUTION PANELS, HEATING,
VENTILATING AND AIR CONDITIONING (HVAC) EQUIPMENT, OWNER-PROVIDED
EQUIPMENT, AND OTHER EQUIPMENT AS DETAILED.
3. BRANCH CIRCUIT WIRING FROM NORMAL, EMERGENCY AND UNINTERRUPTIBLE
POWER SUPPLY DISTRIBUTION PANELS FOR LIGHTING, RECEPTACLES, MOTORS,
SIGNAL SYSTEMS AND OTHER DETAILED CIRCUIT WIRING.
4. LUMINAIRES, CONTROL SWITCHES, RECEPTACLES, RELAYS, SUPPORTS AND
OTHER ACCESSORY ITEMS.
5. WIRING AND POWER CONNECTIONS FOR MOTORS INSTALLED FOR HEATING,
COOLING AND VENTILATION.
FEES:
1. PAY FEES LEVIED BY SERVING ELECTRIC UTILITY TO PROVIDE SERVICE TO THIS
PROJECT.
2. OBTAIN FEES FROM SERVING ELECTRIC UTILITY PRIOR TO SUBMITTING A BID.
3. OBTAIN AND PAY FOR ELECTRICAL PERMITS, PLAN REVIEW, AND INSPECTIONS
FROM LOCAL AUTHORITY HAVING JURISDICTION (AHJ).
D.
FOLLOWING IS A LIST OF ABBREVIATIONS GENERALLY USED IN THIS DIVISION:
1. ADA
AMERICANS WITH DISABILITIES ACT.
2. AHJ
AUTHORITY HAVING JURISDICTION.
3. CBC
CALIFORNIA BUILDING CODE.
4. CEC
CALIFORNIA ELECTRICAL CODE.
5. CFC
CALIFORNIA FIRE CODE.
6. CEC T24CALIFORNIA ENERGY CODE TITLE 24.
7. HVAC HEATING, VENTILATING AND AIR CONDITIONING.
8. IEEE
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS.
9. IES
ILLUMINATING ENGINEERING SOCIETY
10. UL
UNDERWRITERS LABORATORIES INC.
B.
PROVIDE: TO FURNISH AND INSTALL, COMPLETE AND READY FOR THE INTENDED USE.
C.
FURNISH: SUPPLY AND DELIVER TO THE PROJECT SITE, READY FOR UNPACKING,
ASSEMBLY AND INSTALLATION.
D.
A.
RIGID METAL CONDUIT (RMC): HOT-DIP GALVANIZED AFTER THREAD CUTTING.
MANUFACTURED IN CONFORMANCE WITH UL 6, ANSI C80.1. UNIFORM FINISH COAT
WITH CHROMATE FOR ADDED PROTECTION. MANUFACTURERS: ALLIED TUBE &
CONDUIT, BECK MANUFACTURING WL, PICOMA, OR APPROVED EQUIVALENT.
B.
INTERMEDIATE METAL CONDUIT (IMC): HOT-DIP GALVANIZED AFTER THREAD CUTTING.
MANUFACTURED IN CONFORMANCE WITH UL 6, ANSI C80.6. UNIFORM FINISH COAT
WITH CHROMATE FOR ADDED PROTECTION. MANUFACTURERS: ALLIED TUBE &
CONDUIT, BECK MANUFACTURING WL, PICOMA, OR APPROVED EQUIVALENT.
C.
ELECTRICAL METALLIC TUBING (EMT): STEEL GALVANIZED TUBING. MANUFACTURED IN
CONFORMANCE WITH UL 797, ANSI C80.3. MANUFACTURERS: ALLIED TUBE & CONDUIT,
BECK MANUFACTURING WL, PICOMA, OR APPROVED EQUIVALENT.
D.
FLEXIBLE METAL CONDUIT (FMC): INTERLOCKED STEEL CONSTRUCTION.
MANUFACTURED IN CONFORMANCE WITH UL 1. MANUFACTURERS: AFC CABLE
SYSTEMS INC., ELECTRI-FLEX COMPANY, INTERNATIONAL METAL HOSE, OR APPROVED
EQUIVALENT.
E.
SURFACE METAL RACEWAY SYSTEMS
1. TWO CHANNEL SURFACE RACEWAY: ONE CHANNEL FOR POWER, THE OTHER
CHANNEL FOR SIGNAL. PROVIDE 20 AMP MULTI-OUTLET AS INDICATED ON
DRAWINGS. PROVIDE DIVIDER BETWEEN CHANNELS. WIREMOLD 4000 SERIES OR
APPROVED EQUIVALENT.
2. PROVIDE ENDCAPS, CORNER JOINTS, TEES, TRANSITION FITTINGS, AND THE LIKE,
FOR A COMPLETE INSTALLATION.
F.
INSTALL: INCLUDES UNLOADING, UNPACKING, ASSEMBLING, ERECTING, INSTALLATION,
APPLYING, FINISHING, PROTECTING, CLEANING AND SIMILAR OPERATIONS AT THE
PROJECT SITE AS REQUIRED TO COMPLETE ITEMS OF WORK FURNISHED BY OTHERS.
1.3 SUBMITTALS
A.
B.
C.
OPERATION AND MAINTENANCE DOCUMENTATION: PROVIDE COPIES OF CERTIFICATES
OF CODE AUTHORITY ACCEPTANCE, TEST DATA, PRODUCT DATA, GUARANTEES,
WARRANTIES, AND THE LIKE.
SHOP DRAWINGS: PROVIDE SHOP DRAWINGS WHICH INCLUDE PHYSICAL
CHARACTERISTICS, ELECTRICAL CHARACTERISTICS, DEVICE LAYOUT PLANS, WIRING
DIAGRAMS, AND THE LIKE. PROVIDE PRODUCT SUBMITTALS AND SHOP DRAWINGS IN
EITHER PAPER FORMAT OR ELECTRONIC FORMAT. ELECTRONIC FORMAT MUST BE
SUBMITTED VIA EMAIL OR FTP SITE. FOR PAPER HARDCOPY, PROVIDE ONE COMPLETE
BINDER WITH TABBED DIVIDERS CONTAINING A SEPARATE SUBMITTAL FOR EACH
SPECIFICATIONS SECTION. FOR ELECTRONIC FORMAT, PROVIDE ONE ZIP FILE PER
SPECIFICATION DIVISION CONTAINING A SEPARATE FILE FOR EACH SPECIFICATIONS
SECTION. INDIVIDUAL SUBMITTALS SENT PIECEMEAL IN A PER SPECIFICATION SECTION
METHOD WILL BE RETURNED WITHOUT REVIEW OR COMMENT. COPY ARCHITECT ON
ALL SUBMISSIONS.
1. IDENTIFY EACH SUBMITTAL IN DETAIL. NOTE WHAT DIFFERENCES, IF ANY, EXIST
BETWEEN THE SUBMITTED ITEM AND THE SPECIFIED ITEM. FAILURE TO IDENTIFY
THE DIFFERENCES WILL BE CONSIDERED CAUSE FOR DISAPPROVAL. IF
DIFFERENCES ARE NOT IDENTIFIED AND/OR NOT DISCOVERED DURING THE
SUBMITTAL REVIEW PROCESS, CONTRACTOR REMAINS RESPONSIBLE FOR
PROVIDING EQUIPMENT AND MATERIALS THAT MEET THE SPECIFICATIONS AND
DRAWINGS.
2. PROVIDE THE FOLLOWING INFORMATION FOR LIGHTING SUBMITTALS: INCLUDE
ELECTRICAL RATINGS, DIMENSIONS, MOUNTING, MATERIAL, REQUIRED
CLEARANCES, TERMINATIONS, WIRING AND CONNECTION DIAGRAMS,
PHOTOMETRIC DATA, DIFFUSERS, LOUVERS, BALLAST TYPE AND QUANTITIES,
LAMP TYPE AND QUANTITIES.
3. MAXIMUM OF TWO REVIEWS OF COMPLETE SUBMITTAL PACKAGE. ARRANGE FOR
ADDITIONAL REVIEWS AND/OR EARLY REVIEW OF LONG-LEAD ITEMS; BEAR COSTS
OF THESE ADDITIONAL REVIEWS AT ENGINEER'S HOURLY RATES. INCOMPLETE
SUBMITTAL PACKAGES/SUBMITTALS WILL BE RETURNED TO CONTRACTOR
WITHOUT REVIEW.
RECORD DRAWINGS: SHOW CHANGES AND DEVIATIONS FROM THE DRAWINGS.
INCLUDE WRITTEN ADDENDUM AND CHANGE ORDER ITEMS. MAKE CHANGES TO
DRAWINGS IN ELECTRONIC FORMAT. OBTAIN ELECTRONIC COPY FROM ARCHITECT,
USE THE SAME VERSION OF AUTOCAD TO PREPARE RECORD DRAWINGS AS WAS USED
BY THE ARCHITECT. PROVIDE ELECTRONIC COPY AND HARD COPY TO ARCHITECT FOR
REVIEW.
1.4 QUALITY ASSURANCE
A.
CONFORM TO THE LATEST ADOPTED VERSION OF THE CALIFORNIA ELECTRIC CODE
(CEC), WITH LOCAL AMENDMENTS.
B.
FURNISH PRODUCTS LISTED BY UNDERWRITERS LABORATORIES INC. (UL) OR OTHER
TESTING FIRM ACCEPTABLE TO AHJ.
C.
D.
A.
FOR THE PROPER EXECUTION OF THE WORK, COOPERATE WITH OTHER CRAFTS AND
CONTRACTS AS NEEDED.
B.
TO AVOID INSTALLATION CONFLICTS, THOROUGHLY EXAMINE THE COMPLETE SET OF
CONTRACT DOCUMENTS. RESOLVE CONFLICTS PRIOR TO INSTALLATION.
C.
BUILDING GROUND ELECTRODE: COORDINATE PLACEMENT OF GROUND RODS AND
GROUNDING ELECTRODE CONDUCTOR IN BASE OF BUILDING FOOTING PRIOR TO
PLACEMENT OF CONCRETE. COORDINATE BONDING OF REBAR WITH REBAR
INSTALLER PRIOR TO ROUGH-IN.
D.
PRIOR TO INSTALLATION OF FEEDERS TO EQUIPMENT REQUIRING ELECTRICAL
CONNECTIONS, EXAMINE THE MANUFACTURER'S SHOP DRAWINGS, WIRING DIAGRAMS,
PRODUCT DATA, AND INSTALLATION INSTRUCTIONS. VERIFY THAT THE ELECTRICAL
CHARACTERISTICS DETAILED IN THE CONTRACT DOCUMENTS ARE CONSISTENT WITH
THE ELECTRICAL CHARACTERISTICS OF THE ACTUAL EQUIPMENT BEING INSTALLED.
B.
C.
D.
PART 2 -
GUARANTEE ELECTRICAL WORK AGAINST FAULTY MATERIAL OR WORKMANSHIP FOR A
PERIOD OF ONE YEAR FROM THE DATE OF FINAL COMPLETION BY THE OWNER.
COPPER PADS: DRILLED AND TAPPED FOR MULTIPLE CONDUCTOR TERMINALS.
B.
LUGS: COMPRESSION TYPE FOR USE WITH STRANDED BRANCH CIRCUIT OR CONTROL
CONDUCTORS; MECHANICAL LUGS NOT ACCEPTABLE. MANUFACTURERS: ANDERSON,
ILSCO, PANDUIT, THOMAS & BETTS, 3M, OR APPROVED EQUIVALENT.
C.
D.
LAMP WARRANTY: 30 DAYS FOR INCANDESCENT, 12 MONTHS FOR COMPACT
FLUORESCENT, 36 MONTHS FOR FLUORESCENT AND 12 MONTHS FOR HID LAMPS.
PRODUCTS
A.
B.
C.
D.
E.
B.
BASE CONTRACT UPON FURNISHING MATERIALS AS SPECIFIED. MATERIALS,
EQUIPMENT, AND FIXTURES USED FOR CONSTRUCTION ARE TO BE NEW, LATEST
PRODUCTS AS LISTED IN MANUFACTURER'S PRINTED CATALOG DATA AND ARE TO BE
UL APPROVED OR HAVE ADEQUATE APPROVAL OR BE ACCEPTABLE BY STATE,
COUNTY, AND CITY AUTHORITIES. EQUIPMENT/FIXTURE SUPPLIER IS RESPONSIBLE
FOR OBTAINING STATE, COUNTY, AND CITY ACCEPTANCE ON EQUIPMENT/FIXTURE NOT
UL APPROVED OR NOT LISTED FOR INSTALLATION.
INCLUDE SPECIAL FEATURES, FINISHES, ACCESSORIES, AND OTHER REQUIREMENTS
AS DESCRIBED IN THE CONTRACT DOCUMENTS REGARDLESS OF THE ITEM'S LISTED
CONDUCTOR BRANCH CIRCUITS: WIRE NUTS WITH INTEGRAL SPRING CONNECTORS
FOR CONDUCTORS 18 THROUGH 8AWG. PUSH-IN TYPE CONNECTORS WHERE
CONDUCTORS ARE NOT REQUIRED TO BE TWISTED TOGETHER ARE NOT ACCEPTABLE.
MANUFACTURERS: 3M, IDEAL, OR APPROVED EQUIVALENT.
FLUORESCENT LUMINAIRE DISCONNECT: POLYCARBONATE HOUSING, TIN-PLATED
BRASS CONTACTS, INSULATED 18AWG, FACTORY-INSTALLED SOLID COPPER LEADS,
105C TEMPERATURE RATING, UL94-V2 FLAMMABILITY, 4A, 600V. CEC ARTICLE 410
COMPLIANT. FINGER-SAFE LINE SIDE. PUSH-AND-CLICK CONNECTOR. THOMAS &
BETTS STA-KON, LITHONIA OR APPROVED EQUIVALENT.
LUMINAIRE OUTLET: 4-INCH OCTAGONAL BOX, 1-1/2 INCHES DEEP WITH 3/8-INCH
LUMINAIRE STUD IF REQUIRED. PROVIDE RAISED COVERS ON BRACKET OUTLETS AND
ON CEILING OUTLETS. MANUFACTURER: HUBBELL, THOMAS & BETTS, OR APPROVED
EQUIVALENT.
DEVICE OUTLET: INSTALLATION OF ONE OR TWO DEVICES AT COMMON LOCATION,
MINIMUM 4-INCH SQUARE, MINIMUM 1-1/2 INCHES DEEP. SINGLE- OR TWO-GANG FLUSH
DEVICE RAISED COVERS. MANUFACTURER: HUBBELL, THOMAS & BETTS, OR
APPROVED EQUIVALENT.
CONSTRUCTION: FOR INTERIOR LOCATIONS, PROVIDE GALVANIZED STEEL OUTLET
WIRING BOXES, OF THE TYPE, SHAPE AND SIZE, INCLUDING DEPTH OF BOX, TO SUIT
EACH RESPECTIVE LOCATION AND INSTALLATION; CONSTRUCTED WITH STAMPED
KNOCKOUTS IN BACK AND SIDES, AND WITH THREADED HOLES WITH SCREWS FOR
SECURING BOX COVERS OR WIRING DEVICES. PROVIDE OUTLET BOX ACCESSORIES
FOR EACH INSTALLATION, INCLUDING MOUNTING BRACKETS, WALLBOARD HANGERS,
EXTENSION RINGS, LUMINAIRE STUDS, CABLE CLAMPS AND METAL STRAPS FOR
SUPPORTING OUTLET BOXES, COMPATIBLE WITH OUTLET BOXES BEING USED AND
MEETING REQUIREMENTS OF INDIVIDUAL WIRING SITUATIONS.
JUNCTION AND PULL BOXES: ANSI 49 GRAY ENAMEL PAINTED SHEET STEEL JUNCTION
AND PULL BOXES, WITH SCREW-ON COVERS; OF THE TYPE SHAPE AND SIZE, TO SUIT
EACH RESPECTIVE LOCATION AND INSTALLATION; WITH WELDED SEAMS AND
EQUIPPED WITH STEEL NUTS, BOLTS, SCREWS AND WASHERS. INSTALL JUNCTION
BOXES ABOVE ACCESSIBLE CEILINGS FOR DROPS INTO WALLS FOR RECEPTACLE
OUTLETS FROM OVERHEAD. INSTALL JUNCTION BOXES AND PULL BOXES TO
FACILITATE THE INSTALLATION OF CONDUCTORS AND LIMITING THE ACCUMULATED
ANGULAR SUM OF BENDS BETWEEN BOXES, CABINETS AND APPLIANCES TO 270
DEGREES. MANUFACTURER: B-LINE, HOFFMAN, OR APPROVED EQUIVALENT.
BOX EXTENSION ADAPTER: INSTALL OVER FLUSH WALL OUTLET BOXES TO PERMIT
FLEXIBLE RACEWAY EXTENSION FROM FLUSH OUTLET TO FIXED OR MOVABLE
EQUIPMENT. MANUFACTURER: BELL 940 SERIES, RED DOT IHE4 SERIES, OR APPROVED
EQUIVALENT.
2.6 WIRING DEVICES
A.
FINISH: MATCH BUILDING STANDARD OR STANDARD COLOR AS SELECTED BY THE
ARCHITECT. RED FINISH FOR DEVICES CONNECTED TO EMERGENCY CIRCUITS
B.
WALL SWITCHES: DECORATIVE AC ROCKER SWITCHES CHARACTERISTICS: QUIET
ACTING, 20 AMP, 120/277 VOLT, UL LISTED FOR MOTOR LOADS UP TO 80 PERCENT OF
RATED AMPERAGE. WHERE SWITCHES ARE GANGED TOGETHER, PROVIDE A SINGLE
MULTI-GANG COVERPLATE. COOPER, HUBBELL, LEVITON, PASS & SEYMOUR, OR
APPROVED EQUIVALENT.
C.
D.
E.
RECEPTACLES: STRAIGHT PARALLEL BLADE, 125 VOLT, 2 POLE, 3 WIRE GROUNDING.
1. COMMERCIAL GRADE: RIVETED. BACK AND SIDE WIRED. BRASS GROUND
CONTACT ON STEEL MOUNTING STRAP. NYLON FACE AND NYLON BASE. 20 AMP.
COOPER 5362, HUBBELL 5362, BRYANT 5362, LEVITON 5362S, PASS & SEYMOUR
5362 15 AMP. COOPER 5352, HUBBELL 5352, BRYANT 5352, LEVITON 5352, PASS &
SEYMOUR 5352.
WHILE-IN-USE WEATHERPROOF COVERS: NEMA 3R WHEN CLOSED OVER ENERGIZED
PLUG. VERTICAL MOUNT FOR DUPLEX RECEPTACLE. PROVIDE CONTINUOUS USE
COVER WITH COVER CAPABLE OF CLOSING OVER ENERGIZED CORD CAP WITH
BOTTOM APERTURE FOR CORD EXIT. UV STABILIZED POLYCARBONATE COVER WITH
CLOSED CELL NEOPRENE FOAM GASKET. PASS & SEYMOUR WIUC10, LEVITON 5977,
HUBBELL WP826MP, COOPER 4966, OR APPROVED EQUIVALENT. DIE CAST ALUMINUM
COVER WITH CLOSED CELL NEOPRENE FOAM GASKET. INTERMATIC WP1010MC OR
APPROVED EQUIVALENT.
C.
CONCRETE INSERTS: CAST IN CONCRETE FOR SUPPORT FASTENERS FOR LOADS UP
TO 800 LBS. MANUFACTURERS: B-LINE, KINDORF, SUPERSTRUT, UNISTRUT, OR
APPROVED EQUIVALENT.
D.
PIPE STRAPS: TWO-HOLE GALVANIZED OR MALLEABLE IRON.
E.
LUMINAIRE CHAIN: CAMPBELL CHAIN 75031 OR APPROVED EQUIVALENT, 90 LB. TEST
WITH STEEL HOOKS.
F.
ROOFTOP CONDUIT SUPPORTS: CURB BASED MADE OF 100 PERCENT RECYCLED
RUBBER AND POLYURETHANE PREPOLYMER WITH A UNIFORM LOAD. CAPACITY OF 500
POUNDS PER LINEAR FOOT OF SUPPORT. UV RESISTANT. STEEL FRAME, 14GA STRUT
GALVANIZED PER ASTM A653 OR 12GA STRUT GALVANIZED PER ASTM A653 FOR
BRIDGE SERIES. CONTINUOUS BLOCK CHANNEL SUPPORTS WITH 1 INCH GAPS TO
ALLOW WATER FLOW, BRIDGE CHANNEL SUPPORTS, EXTENDABLE HEIGHT CHANNEL
SUPPORTS AND ELEVATED SINGLE CONDUIT SUPPORTS. BLACK FINISH WITH SAFETY
YELLOW STRIPING. MANUFACTURER: COOPER B-LINE DURA-BLOCK ROOFTOP
SUPPORT BASE OR APPROVED EQUIVALENT.
A.
TOGGLE TYPE DISCONNECT SWITCHES: 120 VOLT, 1-POLE, 20 AMP, 1 HP MAXIMUM.
NEMA 1 ENCLOSURE FOR INDOORS, NEMA 3R ENCLOSURE FOR OUTDOORS.
B.
MANUAL MOTOR STARTERS: QUICK-MAKE, QUICK-BREAK. THERMAL OVERLOAD
PROTECTION. DEVICE LABELED WITH MAXIMUM VOLTAGE, CURRENT, AND
A.
B.
PROVIDE NEMA 1 ENCLOSURE FOR INDOORS, NEMA 3R ENCLOSURE FOR OUTDOORS.
LABELS: ADHESIVE TAPE WITH 18 POINT BLACK LETTERS ON CLEAR BACKGROUND.
USE ONLY FOR IDENTIFICATION OF INDIVIDUAL WALL SWITCHES AND RECEPTACLES,
CONTROL STATIONS, AND TELECOMMUNICATION OUTLETS. INDICATE DEVICE NAME,
SOURCE PANEL, AND SOURCE CIRCUITS. DO NOT PROVIDE DYMO TAPE STYLE LABELS.
MANUFACTURER: KROY, BRADY, OR APPROVED EQUIVALENT.
CONDUCTOR NUMBERS: VINYL-CLOTH SELF-ADHESIVE TYPE WIRE MARKERS. EACH
CONDUCTOR AT PULLBOXES, PANELBOARDS, OUTLET BOXES, JUNCTION BOXES, AND
EACH LOAD CONNECTION. BRANCH CIRCUIT OR FEEDER NUMBERS AS INDICATED ON
DRAWINGS AND SOURCE PANEL. MANUFACTURER: BRADY, PANDUIT, SUMITOMO, OR
APPROVED EQUIVALENT.
D.
BRANCH CIRCUIT SCHEDULES: PROVIDE BRANCH CIRCUIT IDENTIFICATION
SCHEDULES, TYPEWRITTEN, CLEARLY FILLED OUT, TO IDENTIFY LOAD CONNECTED TO
EACH CIRCUIT AND LOCATION OF LOAD. NUMBERS TO CORRESPOND TO NUMBERS
ASSIGNED TO EACH CIRCUIT BREAKER POLE POSITION.
2.10 GROUNDING MATERIALS
A.
B.
C.
GROUNDING CONNECTORS: HYDRAULIC COMPRESSION TOOL APPLIED CONNECTORS
OR EXOTHERMIC WELDING PROCESS CONNECTORS OR POWDER ACTUATED
COMPRESSION TOOL APPLIED CONNECTORS. MECHANICAL TYPE OF CONNECTORS
ARE NOT ACCEPTABLE. MANUFACTURERS: BURNDY HYGROUND COMPRESSION
SYSTEM, ERICO/CADWELD, AMP AMPACT GROUNDING SYSTEM OR APPROVED
EQUIVALENT.
PIPE GROUNDING CLAMP: MECHANICAL GROUND CONNECTOR WITH CABLE PARALLEL
OR PERPENDICULAR TO PIPE. BURNDY GAR SERIES, O_Z GEDNEY, THOMAS & BETTS
OR APPROVED EQUIVALENT.
TELECOMMUNICATIONS GROUNDING BUSBAR (TGB): 1/4-INCH THICK BY 4-INCH HIGH
BY 12-INCH LONG COPPER GROUND BAR WITH INSULATORS THAT MEET ANSI
J-STD-607-A SPECIFICATIONS. UL 467 LISTED. HOLE PATTERNS IN BUSBAR TO
ACCOMMODATE TWO-HOLE LUGS. MANUFACTURERS: CHATSWORTH, ERICO, SQUARE
D, PANDUIT OR APPROVED EQUIVALENT.
A.
SUSPENDED LUMINAIRES: PROVIDE MINIMUM 24-INCH ADJUSTABILITY IN AIRCRAFT
CABLE LENGTH WHERE USED.
C.
FINISHES: MANUFACTURER'S STANDARD FINISH (UNLESS OTHERWISE INDICATED)
OVER CORROSION RESISTANT PRIMER. WHITE OR SPECULAR FINISH WITH NOT LESS
THAN 85 PERCENT REFLECTANCE FOR INTERIOR LUMINAIRES.
D.
FLUORESCENT LUMINAIRES:
1. PROVIDE OPEN LAMP FLUORESCENT LUMINAIRES WITHOUT DIFFUSERS OR
GUARDS WITH TURRET TYPE, SPRING LOADED SOCKETS.
2. TO FACILITATE MULTILEVEL LAMP SWITCHING, WIRE LAMPS WITHIN LUMINAIRE
WITH OUTERMOST LAMP AT BOTH SIDES OF LUMINAIRE ON THE SAME BALLAST,
THE NEXT INWARD PAIR ON ANOTHER BALLAST AND SO ON TO INNERMOST LAMP
(OR PAIR OF LAMPS).
2.14BALLASTS
A.
B.
MAXIMUM TEMPERATURE RISE AT FULL LOAD: 150 DEGREES ABOVE 40C AMBIENT
TEMPERATURE. NEMA TP-1 COMPLIANT.
C.
PROVIDE EACH COIL LAYER WITH END FILLERS OR TIE-DOWNS TO PROVIDE MAXIMUM
MECHANICAL STRENGTH. BRAZE TAP TERMINATIONS TO MAGNET WIRE. PRIMARY AND
SECONDARY MAGNET WIRE TO BE BRAZED DIRECTLY TO BUS STUBS OR LUGS FIRMLY
MOUNTED.
D.
E.
PROVIDE COPPER WINDINGS CONTINUOUS FROM START TO FINISH. SPLICING IS
UNACCEPTABLE. MATERIALS INCORPORATED MUST HAVE AT LEAST A MINIMUM OF 1
YEAR OF PROVEN FIELD USAGE. ACCELERATED LABORATORY TEST NOT ACCEPTABLE.
CORES MANUFACTURED FROM A HIGH-GRADE, NONAGING SILICON STEEL WITH HIGH
MAGNETIC PERMEABILITY, LOW HYSTERESIS AND EDDY CURRENT LOSSES. MAGNETIC
FLUX DENSITIES ARE KEPT WELL BELOW SATURATION TO ALLOW FOR A MINIMUM OF 10
PERCENT OVER-VOLTAGE EXCITATION.
A.
PROVIDE LAMPS FOR LUMINAIRES. PROVIDE LAMP CATALOGED FOR SPECIFIED
LUMINAIRE TYPE.
B.
MANUFACTURERS: OSRAM/SYLVANIA, GENERAL ELECTRIC, PHILIPS, VENTURE, USHIO
(MR ONLY), OR APPROVED EQUIVALENT UNLESS SPECIFIC MANUFACTURER IS
INDICATED IN THE LUMINAIRE SCHEDULE.
C.
FLUORESCENT:
1. PROVIDE 3500K FLUORESCENT LAMPS UNLESS NOTED IN LUMINAIRE SCHEDULE.
2. LINEAR FLUORESCENT:
a. T-8: BI-PIN BASE, TRI-PHOSPHOR COATED. INITIAL 3100 LUMEN OUTPUT. CRI
EQUAL TO OR EXCEEDING 85. 36000 HOURS RATED ON 3 HOUR SWITCHING
CYCLE AND 42000 HOURS RATED ON 12 HOUR SWITCHING CYCLES WHEN USED
WITH PROGRAMMED START BALLAST. COMPATIBLE WITH DIMMING BALLASTS.
LENGTH AND WATTAGE AS INDICATED IN THE LUMINAIRE SCHEDULE.
A.
PROVIDE COMPLETE CONDUIT/RACEWAY AND BACKBOX FOR COMMUNICATION AND
DATA SYSTEMS AS SHOWN ON THE DRAWINGS AND AS DESCRIBED HEREIN.
B.
INSTALL MINIMUM 2-1/8-INCH DEEP DOUBLE-GANG (4- BY 4-INCH) BOX WITH A
SINGLE-GANG PLASTER RING AND MINIMUM 1-INCH CONDUIT TO ACCESSIBLE SPACE
FOR ALL VOICE AND DATA OUTLETS. USE DOUBLE-GANG TRIM RING WHERE REQUIRED
FOR 4- TO 6-JACK INSTALLATION IN ONE WALL BOX.
C.
PULL TAPE: MEASURING/PULLING TAPE WITH PLASTIC JACKET PRINTED WITH
SEQUENTIAL FOOTAGE MARKS.
D.
PROVIDE SLEEVES THROUGH RATED WALLS.
E.
J-HOOKS: ERICO CADDY CABLE CAT CLIPS, INCLUDES TEE GRID OR DROP WIRE STYLE.
PART 3 -
B.
CLARIFICATION:
1. THE DRAWINGS GOVERN IN MATTERS OF QUANTITY, THE SPECIFICATION IN
MATTERS OF QUALITY. IN EVENT OF CONFLICT ON DRAWINGS OR IN THE
SPECIFICATIONS, THE GREATER QUANTITY AND THE HIGHER QUALITY APPLY.
2. SHOULD THE ELECTRICAL DOCUMENTS INDICATE A CONDITION CONFLICTING WITH
THE GOVERNING CODES AND REGULATIONS, REFRAIN FROM INSTALLING THAT
PORTION OF THE WORK UNTIL CLARIFIED BY ARCHITECT.
A.
CONNECT EQUIPMENT, WHETHER FURNISHED BY OWNER OR OTHER DIVISIONS OF THE
CONTRACT, ELECTRICALLY COMPLETE. DO NOT INSTALL ELECTRICAL EQUIPMENT OR
WIRING ON MECHANICAL EQUIPMENT WITHOUT APPROVAL OF ARCHITECT.
B.
PROVIDE MOISTURE TIGHT EQUIPMENT WIRING AND SWITCHES IN DUCTS OR PLENUMS
USED FOR ENVIRONMENTAL AIR.
C.
CONNECT MOTOR BRANCH CIRCUITS COMPLETE FROM PANEL TO MOTOR/EQUIPMENT
AS REQUIRED BY CODE.
D.
MOTOR STARTERS FOR EQUIPMENT, MOTOR START CONTROL DEVICES, AND WIRING
FURNISHED BY OTHER DIVISIONS PROVIDED BY EQUIPMENT INSTALLER FOR
INSTALLATION BY THIS DIVISION, UNLESS NOTED ON DRAWINGS.
H.
PROVIDE LIFTING BRACKETS ON SIZES.
F.
I.
DESIGN VENTILATED OPENINGS IN A MANNER AS TO PREVENT ACCIDENTAL ACCESS
TO LIVE PARTS.
APPLIANCE/UTILIZATION EQUIPMENT: PROVIDE APPROPRIATE CABLE AND CORD CAP
FOR FINAL CONNECTION UNLESS EQUIPMENT IS PROVIDED WITH SAME. VERIFY
SPECIAL PURPOSE OUTLET NEMA CONFIGURATION AND AMPERE RATING WITH
EQUIPMENT SUPPLIER PRIOR TO ORDERING DEVICES AND COVERPLATES.
J.
DEGREASE, CLEAN, PHOSPHATIZE, PRIME AND FINISH ENCLOSURES WITH A GRAY
BAKED ENAMEL. VISIBLY GROUND THE CORE OF THE TRANSFORMER TO THIS
ENCLOSURE BY MEANS OF A FLEXIBLE GROUND STRAP.
N.
TRANSFORMER SUPPORTS: PROVIDE ADDITIONAL VIBRATION ISOLATION HANGERS
AND PADS, BRACKETS AND SUPPORTS AS MAY BE REQUIRED FOR A COMPLETE
INSTALLATION.
O.
WINDING TAPS:
1. LESS THAN 15KVA: 4_2_1/2 PERCENT FCBN, FCAN.
2. 15KVA AND LARGER: 4_2_1/2 PERCENT_2+2_.
P.
A.
COORDINATE WITH OWNER SO THAT WORK CAN BE SCHEDULED NOT TO INTERRUPT
OPERATIONS, NORMAL ACTIVITIES, BUILDING ACCESS, ACCESS TO DIFFERENT AREAS.
THE OWNER WILL COOPERATE TO THE BEST OF THEIR ABILITY TO ASSIST IN A
COORDINATED SCHEDULE, BUT WILL REMAIN THE FINAL AUTHORITY AS TO TIME OF
WORK PERMITTED.
B.
COORDINATE THE EXACT LOCATION OF EXISTING UTILITIES AND EQUIPMENT PRIOR TO
COMMENCEMENT OF WORK. COMPENSATE THE OWNER FOR DAMAGES CAUSED BY
THE FAILURE TO LOCATE AND PRESERVE UTILITIES. REPLACE DAMAGED ITEMS WITH
NEW MATERIAL TO MATCH EXISTING. VERIFY THAT ABANDONED WIRING AND
EQUIPMENT SERVE ONLY ABANDONED FACILITIES.
C.
Q. PROVIDE NONVENTILATED TRANSFORMER WHERE SHOWN IN AREAS WHERE
AIRBORNE COMBUSTIBLE OR CONDUCTIVE PARTICLES ARE PRESENT, WHERE
TRANSFORMER IS SUBJECT TO SPRAY FROM ANY DIRECTION, OR WHERE DUST
CONDITIONS ARE EXTREME.
LUGS: PROVIDE COMPRESSION TYPE LUGS FOR CONDUCTOR TERMINATIONS.
S.
MANUFACTURERS: EATON ELECTRICAL, POWERSMITHS, GENERAL ELECTRIC,
SIEMENS, SQUARE D.
2.12DISTRIBUTION PANELBOARDS
A.
BREAKER TYPE. MAXIMUM ENCLOSURE DEPTH FOR BRANCH CIRCUIT PANELBOARD:
6-INCHES SURFACE MOUNTED, 5-3/4 INCHES FOR FLUSH MOUNTED. MAXIMUM BRANCH
CIRCUIT PANELBOARD ENCLOSURE WIDTH: 20 INCHES. PROVIDE GALVANIZED METAL
FINISH. FURNISH SURFACE MOUNTED CABINET BOXES WITHOUT KNOCKOUTS.
B.
C.
INTERIOR: COPPER BAR WITH SUITABLE ELECTROPLATING (TIN) FOR CORROSION
CONTROL AT CONNECTION. PROVIDE COPPER GROUND BUS TO ACCOMMODATE
SPECIFIED TERMINAL LUGS. PREDRILL BUS FOR BOLT-ON TYPE CIRCUIT BREAKERS.
PROVIDE DOUBLE LUGS AND/OR FEED-THROUGH LUGS FOR FEED THROUGH FEEDERS.
PROVIDE INTEGRATED EQUIPMENT RATING GREATER THAN THE AVAILABLE FAULT
CURRENT. SERIES RATED PANELBOARDS ARE NOT ACCEPTABLE. SEE DRAWINGS FOR
AVAILABLE FAULT CURRENT. MINIMUM RATING OF 10,000 AMPS FOR 208V
PANELBOARDS AND 14,000 AMPS FOR 480V PANELBOARDS.
BRANCH CIRCUIT BREAKERS:
1. THERMAL MAGNETIC TRIP CIRCUIT BREAKERS. BOLT-ON TYPE WITH COMMON TRIP
HANDLE FOR POLES, UL LISTED. DO NOT USE TANDEM CIRCUIT BREAKERS.
2. UL LISTED TO ACCEPT SOLID OR STRANDED, ALUMINUM OR COPPER
CONDUCTORS. LUGS SUITABLE FOR 90C RATED WIRE SIZED ACCORDING TO THE
75C TEMPERATURE RATING PER CEC.
3. UL LISTED FOR USE WITH THE FOLLOWING FACTORY INSTALLED ACCESSORIES, AS
4.
5.
EXECUTION:
1. REMOVE EXISTING LUMINAIRES, SWITCHES, RECEPTACLES, AND OTHER
ELECTRICAL EQUIPMENT AND DEVICES AND ASSOCIATED WIRING FROM WALLS,
CEILINGS, FLOORS, AND OTHER SURFACES SCHEDULED FOR REMODELING,
RELOCATION, OR DEMOLITION UNLESS SHOWN AS RETAINED OR RELOCATED ON
DRAWINGS.
2. PROVIDE TEMPORARY WIRING AND CONNECTIONS TO MAINTAIN ELECTRICAL
CONTINUITY OF EXISTING SYSTEMS DURING CONSTRUCTION. REMOVE OR
RELOCATE ELECTRICAL BOXES, CONDUIT, WIRING, EQUIPMENT, LUMINAIRES, AS
ENCOUNTERED IN REMOVED OR REMODELED AREAS IN THE EXISTING
CONSTRUCTION AFFECTED BY THIS WORK.
3. REMOVE AND RESTORE WIRING WHICH SERVES USABLE EXISTING OUTLETS
CLEAR OF THE CONSTRUCTION OR DEMOLITION
4. IF EXISTING JUNCTION BOXES WILL BE MADE INACCESSIBLE, OR IF ABANDONED
OUTLETS SERVE AS FEED THROUGH BOXES FOR OTHER EXISTING ELECTRICAL
EQUIPMENT WHICH IS BEING RETAINED, PROVIDE NEW CONDUIT AND WIRE TO
BYPASS THE ABANDONED OUTLETS.
5. IF EXISTING CONDUITS PASS THROUGH PARTITIONS OR CEILING WHICH ARE BEING
REMOVED OR REMODELED, PROVIDE NEW CONDUIT AND WIRE TO REROUTE
CLEAR OF THE CONSTRUCTION OR DEMOLITION AND MAINTAIN SERVICE TO THE
EXISTING LOAD.
6. PROVIDE TEMPORARY SUPPORT FOR ELECTRICAL SYSTEMS THAT REMAIN IN
PLACE.
7. REMOVE ABANDONED WIRING TO SOURCE OF SUPPLY.
WIRES AND CABLES:
1. CONDUCTOR INSTALLATION: INSTALL CONDUCTORS WITH CARE TO AVOID
DAMAGE TO INSULATION. DO NOT APPLY GREATER TENSION ON CONDUCTORS
THAN RECOMMENDED BY MANUFACTURER DURING INSTALLATION.
2. CONDUCTOR SIZE AND QUANTITY: INSTALL NO CONDUCTORS SMALLER THAN
12AWG UNLESS OTHERWISE SHOWN. PROVIDE REQUIRED CONDUCTORS FOR A
FULLY OPERABLE SYSTEM.
H.
BOXES:
1. ANCHORING: SECURE BOXES RIGIDLY TO THE SUBSTRATE UPON WHICH THEY ARE
BEING MOUNTED.
2. COORDINATE ELECTRICAL DEVICE LOCATIONS AND ELEVATIONS (SWITCHES AND
RECEPTACLES) WITH ARCHITECTURAL DRAWINGS TO PREVENT MOUNTING
DEVICES IN MIRRORS, BACK SPLASHES, AND BEHIND CABINETS.
3. PROVIDE WEATHERPROOF OUTLETS FOR LOCATIONS EXPOSED TO WEATHER OR
MOISTURE.
4. KNOCKOUT CLOSURES: PROVIDE KNOCKOUT CLOSURES TO CAP UNUSED
KNOCKOUT HOLES WHERE BLANKS HAVE BEEN REMOVED.
5. CODE COMPLIANCE: COMPLY WITH CEC AS APPLICABLE TO CONSTRUCTION AND
INSTALLATION OF ELECTRICAL BOXES AND FITTINGS AND SIZE BOXES ACCORDING
TO CEC, EXCEPT AS NOTED OTHERWISE.
6. MOUNT CENTER OF OUTLET BOXES AS REQUIRED BY AMERICANS WITH
DISABILITIES ACT (ADA), OR NOTED ON DRAWINGS, THE FOLLOWING DISTANCE
ABOVE THE FLOOR:
a. CONTROL SWITCHES: 46 INCHES.
b. RECEPTACLES: 18 INCHES.
c. WALL PHONES: 46 INCHES.
d. TELECOM OUTLETS: 18 INCHES.
e. OTHER OUTLETS: AS INDICATED IN OTHER SECTIONS OF SPECIFICATIONS OR
AS DETAILED ON DRAWINGS.
J.
3.4 CONTINUITY OF SERVICE
A.
NO INTERRUPTION OF SERVICES TO ANY PART OF EXISTING FACILITIES WILL BE
PERMITTED WITHOUT EXPRESS PERMISSION IN EACH INSTANCE FROM THE OWNER.
REQUESTS FOR OUTAGES SHALL STATE THE SPECIFIC DATES AND HOURS AND THE
MAXIMUM DURATIONS, WITH THE OUTAGES KEPT TO THESE SPECIFIC DATES AND
HOURS AND THE MAXIMUM DURATIONS. OBTAIN WRITTEN PERMISSION FROM THE
OWNER FOR ANY INTERRUPTION OF POWER, LIGHTING OR SIGNAL CIRCUITS AND
SYSTEMS.
3.5 INSTALLATION
A.
INSTALL ELECTRICAL EQUIPMENT COMPLETE AS DIRECTED BY MANUFACTURER'S
INSTALLATION INSTRUCTIONS. OBTAIN INSTALLATION INSTRUCTIONS FROM
MANUFACTURER PRIOR TO ROUGH-IN OF THE ELECTRICAL EQUIPMENT, EXAMINE THE
INSTRUCTIONS THOROUGHLY. WHEN REQUIREMENTS OF INSTALLATION INSTRUCTIONS
CONFLICT WITH CONTRACT DOCUMENTS, REQUEST CLARIFICATION FROM ARCHITECT
PRIOR TO PROCEEDING WITH INSTALLATION. THIS INCLUDES PROPER INSTALLATION
METHODS, SEQUENCING, AND COORDINATION WITH OTHER TRADES AND DISCIPLINES.
USE THREADED TYPE FITTINGS IN WET LOCATIONS, HAZARDOUS LOCATIONS, AND
DAMP OR RAIN-EXPOSED LOCATIONS WHERE CONDUIT SIZE IS GREATER THAN 2
INCHES.
PROVIDE CORROSION-RESISTANT PUNCHED-STEEL BOX KNOCKOUT CLOSURES,
CONDUIT LOCKNUTS AND PLASTIC CONDUIT BUSHINGS OF THE TYPE AND SIZE TO
SUIT EACH RESPECTIVE USE AND INSTALLATION.
USE INSULATED TYPE BUSHINGS WITH GROUND PROVISION AT SWITCHBOARDS,
PANELBOARDS, SAFETY DISCONNECT SWITCHES, JUNCTION BOXES AND THE LIKE
THAT HAVE FEEDERS 60 AMPERES AND GREATER.
G.
I.
K.
3.
L.
PROVIDE CEC-REQUIRED DISCONNECT SWITCHES WHETHER SPECIFICALLY SHOWN ON
DRAWINGS OR NOT. PROVIDE DISCONNECT SWITCH AT EACH MOTOR LOCATION
WITHIN 5 FEET UNLESS OTHERWISE NOTED. LOCATE DISCONNECT MEANS IN VIEW OF
AND NOT INSIDE OF EQUIPMENT, SUCH THAT TOOLS ARE NOT NEEDED TO REMOVE
COVERS OF ENERGIZED EQUIPMENT TO ACCESS THE DISCONNECTING MEANS.
COORDINATE FUSE AMPERE RATING WITH INSTALLED EQUIPMENT. FUSE AMPERE
RATING VARIANCE BETWEEN ORIGINAL DESIGN INFORMATION AND INSTALLED
EQUIPMENT, SIZE IN ACCORDANCE WITH BUSSMANN FUSETRON 40C
RECOMMENDATIONS. DO NOT PROVIDE FUSES OF LOWER AMPERE RATING THAN
MOTOR STARTER THERMAL UNITS. PROVIDE ARC FLASH LABELS.
SUPPORTING DEVICES:
1. SAFETY FACTOR OF 4 REQUIRED FOR EVERY FASTENING DEVICE OR SUPPORT
FOR ELECTRICAL EQUIPMENT INSTALLED. SUPPORT TO WITHSTAND FOUR TIMES
WEIGHT OF EQUIPMENT IT SUPPORTS. PROVIDE SEISMIC BRACING PER CBC
REQUIREMENTS FOR THIS BUILDING LOCATION.
2. PROVIDE VERTICAL SUPPORT MEMBERS FOR EQUIPMENT AND LUMINAIRES,
STRAIGHT AND PARALLEL TO BUILDING WALLS. PROVIDE HORIZONTAL SUPPORT
MEMBERS STRAIGHT AND PARALLEL TO CEILINGS OR FINISHED FLOOR, UNLESS
OTHERWISE NOTED.
3. PROVIDE INDEPENDENT SUPPORTS TO STRUCTURAL MEMBER FOR LUMINAIRES,
ELECTRICAL MATERIALS, OR EQUIPMENT INSTALLED IN OR ON CEILING, WALLS OR
IN VOID SPACES OR OVER FURRED OR SUSPENDED CEILINGS.
4. DO NOT USE OTHER TRADE'S FASTENING DEVICES AS SUPPORTING MEANS FOR
LUMINAIRES, ELECTRICAL MATERIALS, OR EQUIPMENT.
5. DO NOT FASTEN SUPPORTS TO PIPES, DUCTS, MECHANICAL EQUIPMENT OR
CONDUIT.
6. DO NOT USE SUPPORTS OR FASTENING DEVICES TO SUPPORT OTHER THAN ONE
PARTICULAR ITEM.
7. SUPPORT CONDUITS WITHIN 18 INCHES OF OUTLETS, BOXES, PANELS, CABINETS
AND DEFLECTIONS. MAXIMUM DISTANCE BETWEEN SUPPORTS NOT TO EXCEED 8
FOOT SPACING.
8. SECURELY SUSPEND JUNCTION BOXES, PULL BOXES OR OTHER CONDUIT
TERMINATING HOUSINGS LOCATED ABOVE SUSPENDED CEILING FROM THE FLOOR
ABOVE OR ROOF STRUCTURE TO PREVENT SAGGING AND SWAYING.
9. PROVIDE SEISMIC BRACING PER CBC REQUIREMENTS.
10. INSTALL SUPPORTS FOR ROOFTOP RACEWAYS TO RAISE RACEWAYS A MINIMUM
OF 4-INCHES ABOVE THE ROOF STRUCTURE UNLESS OTHERWISE NOTED.
ELECTRICAL IDENTIFICATION:
1. CONDUCTOR IDENTIFICATION: APPLY MARKERS ON EACH CONDUCTOR FOR
POWER, CONTROL, SIGNALING AND COMMUNICATIONS CIRCUITS.
2. PROVIDE AN ENGRAVED LABEL ON EACH MAJOR UNIT OF ELECTRICAL EQUIPMENT
INDICATING BOTH EQUIPMENT NAME AND CIRCUIT SERVING EQUIPMENT,
INCLUDING BUT NOT LIMITED TO THE FOLLOWING ITEMS: DISCONNECT SWITCHES,
RELAYS, CONTACTORS, TIME SWITCHES, OVERRIDE SWITCHES, SERVICE
DISCONNECTS, DISTRIBUTION SWITCHES, SWITCHBOARDS, BRANCH CIRCUIT
PANELBOARDS, AND TRANSFORMERS.
INSTALL ENGRAVED LABEL ON THE INSIDE OF FLUSH PANELS, VISIBLE WHEN DOOR
IS OPENED. INSTALL LABEL ON OUTSIDE OF SURFACE PANEL. SECURE
NAMEPLATES TO INSIDE SURFACE OF DOOR ON PANELBOARD THAT IS RECESSED
IN FINISHED LOCATIONS.
SERVICE AND DISTRIBUTION: VERIFY UTILITY REQUIREMENTS PRIOR TO BIDDING AND
PROVIDE ASSOCIATED WORK REQUIRED BY LOCAL UTILITY INCLUDING BUT NOT
LIMITED TO: SERVICE UNDERGROUND PRIMARY INCLUDING CONDUIT, PULL CORD,
EXCAVATION AND BACKFILL, UNDERGROUND PULL VAULTS, POLE RISERS,
TRANSFORMER PADS, VAULTS, AND THE LIKE. SECONDARY SERVICE LATERAL
INCLUDING CONDUIT, AND CONDUCTORS. GROUNDING OF TRANSFORMERS. SERVICE
METERING EQUIPMENT.
M. GROUNDING:
1. PERFORMANCE REQUIREMENTS: SUPPLEMENT THE GROUNDED NEUTRAL OF THE
SECONDARY DISTRIBUTION SYSTEM WITH AN EQUIPMENT GROUNDING SYSTEM TO
PROPERLY SAFEGUARD THE EQUIPMENT AND PERSONNEL. INSTALL EQUIPMENT
GROUNDING SUCH THAT METALLIC STRUCTURES, ENCLOSURES, RACEWAYS,
JUNCTION BOXES, OUTLET BOXES, CABINETS, MACHINE FRAMES, PORTABLE
EQUIPMENT AND OTHER CONDUCTIVE ITEMS IN CLOSE PROXIMITY WITH
ELECTRICAL CIRCUITS OPERATE CONTINUOUSLY AT GROUND POTENTIAL AND
PROVIDE A LOW IMPEDANCE PATH FOR POSSIBLE GROUND FAULT CURRENTS.
2. RACEWAY GROUNDING:
a. GROUND METALLIC RACEWAY SYSTEMS. BOND TO GROUND TERMINAL WITH
CODE SIZE JUMPER EXCEPT WHERE CODE SIZE OR LARGER GROUNDING
CONDUCTOR IS INCLUDED WITH CIRCUIT, USE GROUNDING BUSHING WITH
LAY-IN LUG.
b. CONNECT METAL RACEWAYS, WHICH TERMINATE WITHIN AN ENCLOSURE BUT
WITHOUT MECHANICAL CONNECTION TO THE ENCLOSURE, BY GROUNDING
BUSHINGS AND GROUND WIRE TO THE GROUNDING BUS.
c. WHERE EQUIPMENT SUPPLY CONDUCTORS ARE IN FLEXIBLE METALLIC
CONDUIT, INSTALL STRANDED COPPER EQUIPMENT GROUNDING CONDUCTOR
FROM OUTLET BOX TO EQUIPMENT FRAME.
d. INSTALL EQUIPMENT GROUNDING CONDUCTOR, CODE SIZE MINIMUM IN
RACEWAY SYSTEMS.
3. BOXES, CABINETS, ENCLOSURES AND PANELBOARDS:
a. BOND GROUNDING CONDUCTORS TO ENCLOSURE WITH SPECIFIED
CONDUCTORS AND LUGS. INSTALL LUGS ONLY ON THOROUGHLY CLEANED
CONTACT SURFACES.
b. BOND SECTIONS OF SERVICE EQUIPMENT ENCLOSURE TO SERVICE GROUND
BUS.
4. TELECOMMUNICATIONS BACKBOARD: PROVIDE TELECOMMUNICATIONS
GROUNDING BAR AT EACH TELECOMMUNICATIONS BACKBOARD. MOUNT
TELECOMMUNICATIONS GROUNDING BAR 96-INCHES ABOVE FINISHED FLOOR.
BOND THE GROUNDING BAR TO SERVICE GROUNDING BAR IN THE MAIN SERVICE
EQUIPMENT WITH A 6AWG COPPER EQUIPMENT GROUNDING CONDUCTOR.
5. MOTORS, EQUIPMENT AND APPLIANCES: INSTALL CODE SIZE EQUIPMENT
GROUNDING CONDUCTOR FROM OUTLET BOX TO (MOTOR) EQUIPMENT FRAME OR
MANUFACTURER'S DESIGNATED GROUND TERMINAL.
6. RECEPTACLES: CONNECT GROUND TERMINAL OF RECEPTACLE TO EQUIPMENT
GROUND SYSTEM BY NO. 14 CONDUCTOR BOLTED TO OUTLET BOX. SELF
GROUNDING NATURE OF RECEPTACLE DEVICES DOES NOT ELIMINATE
CONDUCTOR BOLTED TO OUTLET BOX.
N.
CONDUIT FITTINGS:
1. USE SET SCREW TYPE FITTINGS ONLY IN DRY LOCATIONS. WHEN SET SCREW
FITTINGS ARE UTILIZED, PROVIDE INSULATED CONTINUOUS EQUIPMENT GROUND
CONDUCTOR IN CONDUIT, FROM OVER CURRENT PROTECTION DEVICE TO OUTLET.
2. USE COMPRESSION FITTINGS IN DRY LOCATIONS, DAMP AND RAIN-EXPOSED
LOCATIONS. MAXIMUM SIZE PERMITTED IN DAMP LOCATIONS AND LOCATIONS
3.
3.3 DEMOLITION
PROVIDE WEATHER RESISTANT ENCLOSURE AND FACTORY RATING FOR EXTERIOR
WHERE SHOWN AT EXTERIOR LOCATIONS.
R.
F.
3.2 MOTORS/APPLIANCE/UTILIZATION BRANCH CIRCUIT WIRING
INSTALL FEEDER CIRCUIT TO PACKAGED HVAC EQUIPMENT. TERMINATE FEEDER
CONDUCTORS AT LINE TERMINALS AS DIRECTED BY EQUIPMENT MANUFACTURER.
SOUND LEVELS GUARANTEED BY MANUFACTURER, 45DB THROUGH 150KVA AND 50DB
THROUGH 300KVA.
CONDUIT:
1. CONDUIT JOINTS: ASSEMBLE CONDUITS CONTINUOUS AND SECURE TO BOXES,
PANELS, AND EQUIPMENT WITH FITTINGS TO MAINTAIN CONTINUITY.
2. CONCEAL CONDUITS. EXPOSED CONDUITS ARE PERMITTED ONLY IN THE
FOLLOWING AREAS:
a. MECHANICAL ROOMS, ELECTRICAL ROOMS OR SPACES WHERE WALLS,
CEILINGS AND FLOORS WILL NOT BE COVERED WITH FINISHED MATERIALS.
3. DO NOT INSTALL CONDUITS ACROSS FLOORS. WHERE EXPOSED CONDUITS ARE
PERMITTED, INSTALL PARALLEL AND PERPENDICULAR TO WALLS, TIGHT TO
FINISHED SURFACES AND NEATLY OFFSET INTO BOXES.
4. KEEP CONDUITS A MINIMUM OF 12-INCHES AWAY FROM STEAM OR HOT WATER
RADIANT HEATING LINES (AT OR ABOVE 104 DEGREES F) OR 3-INCHES AWAY FROM
WASTE OR WATER LINES.
5. KEEP 277/480 VOLT WIRING INDEPENDENT OF 120/208 VOLT WIRING. KEEP POWER
WIRING INDEPENDENT OF COMMUNICATION SYSTEM WIRING.
6. MAXIMUM BENDS: INSTALL NO MORE THAN EQUIVALENT OF THREE 90 DEGREE
BENDS BETWEEN ELECTRICAL BOXES. INSTALL NO MORE THAN EQUIVALENT OF
TWO 90 DEGREE BENDS BETWEEN TELECOMMUNICATION BOXES. USE CONDUIT
BODIES TO MAKE SHARP CHANGES IN DIRECTION, AS AROUND BEAMS.
7. FLEXIBLE CONDUIT: INSTALL 12 INCH MINIMUM SLACK LOOP ON FLEXIBLE
METALLIC CONDUIT AND LIQUIDTIGHT FLEXIBLE METALLIC CONDUIT.
8. CONDUIT SIZE: MINIMUM TRADE SIZE 3/4 INCH.
9. CONDUIT USE LOCATIONS:
a. OUTDOOR LOCATIONS ABOVE GRADE: RMC OR IMC.
b. WET LOCATIONS: RMC OR IMC.
c. DAMP LOCATIONS: RMC, IMC, OR EMT UP TO 2 INCHES IN DIAMETER.
d. DRY, PROTECTED: RMC, IMC, EMT.
e. SHARP BENDS AND ELBOWS: RMC, EMT USE FACTORY ELBOWS.
f. INSTALL TWO PULL STRINGS/TAPES IN EMPTY RACEWAYS. SECURE PULL
STRINGS/TAPES AT EACH END.
g. ELBOW FOR LOW ENERGY SIGNAL SYSTEMS: USE LONG RADIUS FACTORY
ELLS WHERE LINKING SECTIONS OF RACEWAY FOR INSTALLATION OF SIGNAL
CABLE.
h. FOR MOTORS, RECESSED LUMINAIRES AND EQUIPMENT CONNECTIONS
SUBJECT TO MOVEMENT OR VIBRATION, USE FLEXIBLE METALLIC CONDUIT.
i.
FOR MOTORS AND EQUIPMENT CONNECTIONS SUBJECT TO MOVEMENT OR
VIBRATION AND SUBJECTED TO THE FOLLOWING CONDITIONS; EXTERIOR
LOCATION, MOIST OR HUMID ATMOSPHERE, WATER SPRAY, OIL OR GREASE:
USE PVC COATED LIQUID TIGHT FLEXIBLE METALLIC CONDUIT.
10. BRANCH CIRCUITS: DO NOT CHANGE THE INTENT OF THE BRANCH CIRCUITS OR
CONTROLS WITHOUT APPROVAL. HOMERUNS FOR 20 AMP BRANCH CIRCUITS MAY
BE COMBINED TO A MAXIMUM OF SIX CONDUCTORS IN A HOMERUN. APPLY
DERATING FACTORS. INCREASE CONDUCTOR SIZE AS NEEDED.
DRAWINGS ARE DIAGRAMMATIC WITH SYMBOLS REPRESENTING ELECTRICAL
EQUIPMENT, OUTLETS, LUMINAIRES, AND WIRING. EXAMINE THE ENTIRE SET OF
DRAWINGS TO AVOID CONFLICTS WITH OTHER SYSTEMS. DETERMINE EXACT ROUTE
AND INSTALLATION OF ELECTRICAL WIRING AND EQUIPMENT WITH CONDITIONS OF
CONSTRUCTION.
E.
M.
E.
3.1 EXAMINATION
CLAMP CORES WITH STRUCTURAL ANGLES AND BOLTED TO ENCLOSURE TO PREVENT
DAMAGE DURING SHIPMENT OR ROUGH HANDLING.
MAXIMUM CASE TEMPERATURE, 35C ABOVE AMBIENT.
FIRESTOPPING: COORDINATE LOCATION AND PROTECTION LEVEL OF FIRE AND/OR
SMOKE RATED WALLS, CEILINGS, AND FLOORS. WHEN THESE ASSEMBLIES ARE
PENETRATED, SEAL AROUND CONDUIT AND EQUIPMENT WITH APPROVED
FIRESTOPPING MATERIAL. INSTALL FIRESTOPPING MATERIAL COMPLETE AS DIRECTED
THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. MEET REQUIREMENTS OF ASTM
E814, STANDARD TEST METHOD FOR FIRE TESTS OF THROUGH-PENETRATION FIRE
STOPS.
EXECUTION
G.
L.
D.
2.16 TELEPHONE/DATA RACEWAY SYSTEM
CUT LAMINATIONS WITH DIRECTION OF GRAIN AND BE FREE FROM BURRS, CORE
PLATED, AND STACKED WITHOUT GAPS.
MOUNT TRANSFORMERS, CORE AND COIL, ON VIBRATION MOUNTING PADS DESIGNED
TO SUPPRESS TRANSMISSION OF 120 CYCLE FREQUENCIES AND HARMONICS
THEREOF. ARRANGE AND SELECT PADS IN CONSIDERATION OF CORE AND COIL
WEIGHT. PROVIDE ADDITIONAL NOISE SUPPRESSING MOUNTINGS EXTERNAL TO
TRANSFORMERS WHERE TRANSFORMERS ARE LOCATED IN MECHANICAL SPACES.
INSTALL EQUIPMENT REQUIRING ACCESS (I.E. JUNCTION BOXES, LUMINAIRES, POWER
SUPPLIES, MOTORS, ETC.) SO THAT THEY MAY BE SERVICED, RESET, REPLACED OR
RECALIBRATED BY SERVICE PEOPLE WITH NORMAL SERVICE TOOLS AND EQUIPMENT.
DO NOT INSTALL ELECTRICAL EQUIPMENT IN OBVIOUS PASSAGES, DOORWAYS,
SCUTTLES OR CRAWL SPACES WHICH WOULD IMPEDE OR BLOCK THE INTENDED
USAGE.
BALLASTS, GENERAL:
1. PROVIDE BALLASTS UL RATED FOR SPECIFIED LAMPS,.
2. THERMAL PROTECTION: INTERNAL UL CLASS `P' WITH AUTOMATIC RESET.
3. SOUND RATINGS: CLASS 'A'. WHERE NOT AVAILABLE AS STANDARD PRODUCT
FROM ANY SPECIFIED MANUFACTURER, PROVIDE QUIETEST RATING AVAILABLE.
4. TOTAL HARMONIC DISTORTION: NOT TO EXCEED 20 PERCENT OF THE INPUT
CURRENT UNLESS OTHERWISE INDICATED.
5. INPUT VOLTAGE: PROVIDE UNIVERSAL VOLTAGE BALLAST MATCHING BRANCH
CIRCUIT SUPPLY VOLTAGE.
6. PROVIDE QUANTITY OF BALLASTS TO PROVIDE SWITCHING AS INDICATED ON
DRAWINGS. PROVIDE FACTORY PRINTED WIRING DIAGRAM ON BALLAST HOUSING.
7. COMPLY WITH FCC RULES AND REGULATIONS PART 18, CLASS A CONCERNING
GENERATION OF BOTH ELECTROMAGNETIC INTERFERENCE AND RADIO
FREQUENCY INTERFERENCE.
F.
K.
C.
2.15LAMPS
EQUIPMENT GROUNDING CONDUCTOR: GREEN INSULATED; INSULATION TYPE TO
MATCH THAT OF ASSOCIATED FEEDER OR BRANCH CIRCUIT WIRING, SIZE AS
INDICATED ON DRAWINGS.
PROVIDE TRANSFORMER COILS OF THE CONTINUOUS WIRE WOUND CONSTRUCTION
AND IMPREGNATE WITH NONHYGROSCOPIC, THERMOSETTING VARNISH PRIOR TO
BAKING.
DELIVERY, STORAGE AND HANDLING: INSPECT AND REPORT CONCEALED DAMAGE TO
CARRIER WITHIN THEIR REQUIRED TIME PERIOD. STORE IN A CLEAN, DRY
ENVIRONMENT. MAINTAIN FACTORY PACKAGING, AND IF REQUIRED, PROVIDE AN
ADDITIONAL HEAVY CANVAS OR HEAVY PLASTIC COVER TO PROTECT ENCLOSURE(S)
FROM DIRT, WATER, CONSTRUCTION DEBRIS, AND TRAFFIC.
LUMINAIRES: REFER TO DESCRIPTION AND MANUFACTURERS IN LUMINAIRE
SCHEDULE.
B.
2.11DRY_TYPE TRANSFORMERS
A.
B.
2.13LUMINAIRES
A.
D.
D.
SAFETY SWITCHES: HEAVY DUTY, FUSIBLE AND NON-FUSIBLE TYPE (AS INDICATED ON
DRAWINGS), DUAL RATED, QUICK-MAKE, QUICK-BREAK WITH FUSE REJECTION
FEATURE FOR USE WITH CLASS R FUSES ONLY. DEVICE LABELED WITH MAXIMUM
VOLTAGE, CURRENT, AND HORSEPOWER. OPERABLE HANDLE INTERLOCKED TO
NAMEPLATES: ENGRAVING STOCK MELAMINE OR LAMICOID PLASTIC LAMINATE,
FEDERAL SPECIFICATION L-P-387, IN THE SIZE AND THICKNESSES INDICATED,
ENGRAVED WITH ENGRAVER'S STANDARD LETTER STYLE, MINIMUM 1/2-INCH HIGH
LETTERS, BLACK WITH WHITE CORE (LETTER COLOR), PUNCHED FOR MECHANICAL
FASTENING EXCEPT WHERE ADHESIVE MOUNTING IS NECESSARY BECAUSE OF
SUBSTRATE. PROVIDE 1/8-INCH THICK MATERIAL. USE SELF TAPPING STAINLESS STEEL
SCREWS. MANUFACTURER: B&I NAMEPLATES, INTELLICUM, JBR ASSOCIATES, OR
APPROVED EQUIVALENT.
C.
FOR INDOORS, NEMA 3R ENCLOSURE FOR OUTDOORS. SQUARE D CLASS 2510,
SIEMENS, GENERAL ELECTRIC, EATON, OR APPROVED EQUIVALENT.
C.
CALLED OUT ON DRAWINGS: ARC-FAULT CIRCUIT INTERRUPTION (AFCI), CLASS A
GROUND FAULT CIRCUIT INTERRUPTION (GFCI).
2.9 ELECTRICAL IDENTIFICATION
FINISH PLATES: MATCH BUILDING STANDARD.
2.7 SAFETY DISCONNECTS
2.1 MATERIALS
A.
ANCHORS: CORROSION-RESISTANT MATERIALS OF SIZE AND TYPE ADEQUATE TO
CARRY THE LOADS OF EQUIPMENT AND CONDUIT, INCLUDING WEIGHT OF WIRE IN
CONDUIT. MANUFACTURERS: ANCHOR IT, EPCON SYSTEM, HILTI-HIT SYSTEM, POWER
FAST SYSTEM, OR APPROVED EQUIVALENT.
2.5 BOXES
BALLAST MANUFACTURER'S WARRANTY: NOT LESS THAN 5 YEARS FOR ELECTRONIC
TYPE BALLASTS, BASED ON DATE OF SUBSTANTIAL COMPLETION. INCLUDE NORMAL
COST OF LABOR FOR REPLACEMENT OF BALLAST.
LINEAR T8 LAMP AND BALLAST COMBINATION WARRANTY: PROVIDE BALLAST AND
LAMP COMBINATIONS WHICH WILL RESULT IN WRITTEN FACTORY WARRANTY
COVERING LAMPS FOR 3 YEARS AND BALLASTS FOR 5 YEARS, BASED ON DATE OF
SUBSTANTIAL COMPLETION.
COPPER, 600 VOLT RATED THROUGHOUT. CONDUCTORS 14AWG TO 10AWG, SOLID.
CONDUCTORS 8AWG AND LARGER, STRANDED. PHASE COLOR TO BE CONSISTENT AT
FEEDER TERMINATIONS; A-B-C, TOP TO BOTTOM, LEFT TO RIGHT, FRONT TO BACK.
CONDUCTORS 3AWG AND LARGER, MINIMUM INSULATION RATING OF 75C. INSULATION
TYPES THWN, THHN OR XHHW. MINIMUM INSULATION RATING OF 90C FOR BRANCH
CIRCUITS. MANUFACTURERS: CAROL, GENERAL CABLE, OKONITE, SOUTHWIRE, OR
APPROVED EQUIVALENT.
A.
1.6 WARRANTY
A.
CONDUIT FITTINGS:
1. BUSHINGS: INSULATED TYPE FOR THREADED RIGID, CONDUIT OR RACEWAY
CONNECTORS WITHOUT FACTORY INSTALLED PLASTIC THROAT CONDUCTOR
PROTECTION. MANUFACTURERS: THOMAS & BETTS 1222 SERIES, O-Z GEDNEY B
SERIES, OR APPROVED EQUIVALENT.
2. GROUND BUSHINGS: INSULATED GROUNDING TYPE FOR THREADED RIGID,
CONDUIT OR RACEWAY CONNECTORS. MANUFACTURERS: O-Z GEDNEY BLG
SERIES OR APPROVED EQUIVALENT.
3. RACEWAY CONNECTORS AND EMT COUPLINGS:
a. STEEL CONNECTORS, COUPLINGS, AND CONDUIT BODIES WITH ZINC
ELECTROPLATE.
b. CONNECTOR LOCKNUTS ARE ZINC ELECTROPLATED STEEL, WITH THREADS
MEETING ASTM TOLERANCES.
c. CONNECTOR THROATS HAVE FACTORY INSTALLED PLASTIC INSERTS
PERMANENTLY INSTALLED. FOR NORMAL CABLE OR CONDUCTOR EXITING
ANGLES FROM RACEWAY, THE CABLE JACKET OR CONDUCTOR INSULATION
BEARS ONLY ON PLASTIC THROAT INSERT.
4. EXPANSION/DEFLECTION FITTINGS:
a. EMT: USE O_Z GEDNEY TYPE TX, OR APPROVED EQUIVALENT.
b. RMC: USE O_Z GEDNEY TYPE AX, DX AND AXDX, OR APPROVED EQUIVALENT.
HANGERS, SUPPORTS, THREADED ROD AND FASTENERS: CORROSION-RESISTANT
MATERIALS OF SIZE AND TYPE ADEQUATE TO CARRY THE LOADS OF EQUIPMENT AND
CONDUIT, INCLUDING WEIGHT OF WIRE IN CONDUIT. MANUFACTURERS: B-LINE,
KINDORF, SUPERSTRUT, UNISTRUT, OR APPROVED EQUIVALENT.
B.
2.4 CONNECTORS
1.5 SEQUENCING AND SCHEDULING
A.
A.
2.3 WIRES AND CABLES
USE MANUFACTURER'S PUBLISHED TESTING AND ADJUSTING PROCEDURES TO
ADJUST SENSORS' TIME DELAY, DAYLIGHT SENSITIVITY, AND PASSIVE INFRARED
SENSITIVITY TO SATISFACTION OF THE OWNER.
REGULATORY REQUIREMENTS:
1. PROVIDE LUMINAIRES ACCEPTABLE TO CODE AUTHORITY FOR APPLICATION AND
LOCATION AS INDICATED.
2. COMPLY WITH APPLICABLE ANSI STANDARDS.
3. COMPLY WITH APPLICABLE NEMA STANDARDS.
4. PROVIDE LUMINAIRES AND LAMPHOLDERS THAT COMPLY WITH UL STANDARDS
AND HAVE BEEN LISTED AND LABELED FOR LOCATION AND USE INDICATED BY A
TESTING AGENCY ACCEPTABLE BY THE AHJ (E.G. UL, ETL, AND THE LIKE).
5. COMPLY WITH CEC AS APPLICABLE TO INSTALLATION AND CONSTRUCTION OF
LUMINAIRES.
6. COMPLY WITH FALLOUT AND RETENTION REQUIREMENTS OF CBC FOR DIFFUSERS,
BAFFLES, AND LOUVERS.
7. PROVIDE SIMILAR LAMPS AND BALLASTS FROM COMMON MANUFACTURER (E.G.
ALL FLUORESCENT LAMPS FROM OSRAM/SYLVANIA, AND ALL MR LAMPS FROM
USHIO) UNLESS INDICATED OTHERWISE IN THE LUMINAIRE SCHEDULE.
FIRESTOPPING FOAM SEALANT: FOAM SEALANT FOR USE AROUND CONDUIT
PENETRATIONS TO PREVENT PASSAGE OF SMOKE, FIRE, TOXIC GAS OR WATER.
MAINTAIN SEAL BEFORE, DURING AND AFTER FIRE. IN AND AROUND CONDUIT FOR
THERMAL BREAK AT PENETRATION OF BARRIER BETWEEN HEATED AND UNHEATED
SPACES. HILTI, 3M, CHASE TECHNOLOGY CORPORATION CTC PR-855, FIRE FOAM,
THOMAS & BETTS, OR APPROVED EQUIVALENT.
2.8 SUPPORTING DEVICES
2.2 RACEWAYS
1.2 DEFINITIONS
A.
PROVIDE INCIDENTALS NOT SPECIFICALLY MENTIONED HEREIN OR NOTED ON
DRAWINGS, BUT NEEDED TO COMPLETE THE SYSTEM OR SYSTEMS, IN A SAFE AND
SATISFACTORY WORKING CONDITION.
MANUFACTURERS: EATON, GENERAL ELECTRIC, SQUARE D, SIEMENS, OR APPROVED
EQUIVALENT.
TRANSFORMERS:
1. PROVIDE TRANSFORMERS WITH CONCRETE WORKING OR HOUSEKEEPING PAD
MINIMUM 8 INCHES LARGER THAN TRANSFORMER AND MINIMUM 3 INCHES ABOVE
FINISH GRADE. INSTALL PLUMB AND LEVEL. PROVIDE EXTERIOR PADS OF 2500 TO
3000 PSI CONCRETE REINFORCED WITH 8 GAUGE WIRE FABRIC OR NO. 6
REINFORCING BARS ON 12-INCH CENTERS. PROVIDE 10-INCH THICK BASE OF
GRAVEL BELOW PAD FOR SUPPORT. PAD EXTENDS 6 INCHES ON SIDES FROM THE
EXTERIOR MOST PROMINENT DIMENSION. PROVIDE 3/4-INCH BY 10-FOOT GROUND
ROD AT EACH CORNER THERMALLY BONDED TO NO. 2 COPPER GROUND
CONDUCTOR, BONDED TO TRANSFORMER, AND CONCRETE REINFORCEMENT.
2. DO NOT MOUNT TRANSFORMERS CLOSER TO COMBUSTIBLE MATERIALS THAN
ALLOWED BY CEC. PROVIDE ADEQUATE VENTILATION; MOUNT TRANSFORMERS
AWAY FROM ADJACENT SURFACES AS RECOMMENDED BY MANUFACTURER.
3. PROVIDE TRANSFORMERS WITH 8-INCH ROUND BY 24-INCH (ABOVE AND BELOW
GRADE) CONCRETE AND STEEL BOLLARDS WHERE SUBJECT TO VEHICULAR
TRAFFIC.
4. MOUNT TRANSFORMERS ON VIBRATION ISOLATING PADS SUITABLE FOR ISOLATING
THE TRANSFORMER HOUSING FROM BUILDING STRUCTURE.
5. USE FLEXIBLE CONDUIT, 18 INCHES MINIMUM LENGTH, FOR CONNECTIONS TO
TRANSFORMER CASE. MAKE CONNECTIONS TO SIDE PANEL OR BOTTOM OF
ENCLOSURE. INCLUDE GROUND CONDUCTOR IN FLEX.
6. PROVIDE SEISMIC RESTRAINTS PER LOCAL REQUIREMENTS.
7. MOUNT WALL MOUNTED TRANSFORMERS WITH A MINIMUM OF 6'-6" HEADROOM
BELOW UNIT.
8. PROVIDE ARC FLASH LABELS.
O. FUSES: FOR EACH CLASS AND AMPERE RATING OF FUSE INSTALLED, PROVIDE THREE
SPARE FUSES.
P.
CIRCUIT BREAKERS:
1. PROVIDE GROUND FAULT INTERRUPTER CIRCUIT BREAKERS FOR EQUIPMENT IN
DAMP OR WET LOCATIONS.
2. PROVIDE HANDLE GUARDS ON CIRCUITS SUPPLYING CONSTANT LOADS SUCH AS
FIRE ALARM, SECURITY, LIGHTING CONTROLS, REFRIGERATORS AND FREEZERS,
FIRE PROTECTION, ETC.
3. PROVIDE A HANDLE TIE TO BRANCH CIRCUIT BREAKERS OF MULTI-WIRE BRANCH
CIRCUITS FOR SIMULTANEOUS DISCONNECTION OF CIRCUITS. THE HANDLE TIE
WILL BE IDENTIFIED FOR USE WITH THE CIRCUIT BREAKERS PROVIDED.
RECONFIGURE ASSIGNED CIRCUITS AS NECESSARY SO THAT CIRCUIT BREAKERS
ASSOCIATED WITH MULTI-WIRE BRANCH CIRCUITS ARE PHYSICALLY ADJACENT;
RECORD CHANGES IN PANELBOARD SCHEDULES FOR AS-BUILT DRAWINGS.
Q. LIGHTING:
1. INSTALL LUMINAIRES SECURELY, IN NEAT AND WORKMANLIKE MANNER.
2. INSTALL LUMINAIRE OF TYPES INDICATED WHERE SHOWN AND AT INDICATED
HEIGHTS; IN ACCORDANCE WITH MANUFACTURER'S WRITTEN INSTRUCTIONS AND
WITH RECOGNIZED INDUSTRY PRACTICES TO ENSURE THAT LUMINAIRES COMPLY
WITH REQUIREMENTS AND SERVE INTENDED PURPOSES.
3. ALIGN, MOUNT AND LEVEL LUMINAIRES UNIFORMLY. USE BALL HANGERS FOR
SUSPENDED STEM MOUNTED LUMINAIRES.
4. AVOID INTERFERENCE WITH AND PROVIDE CLEARANCE FOR EQUIPMENT. WHERE
THE INDICATED LOCATIONS FOR THE LUMINAIRES CONFLICT WITH LOCATIONS FOR
EQUIPMENT, CHANGE LOCATIONS FOR THE LUMINAIRE AS DIRECTED BY
ARCHITECT.
5. SUSPENDED LUMINAIRES: MOUNTING HEIGHTS INDICATE CLEARANCES BETWEEN
BOTTOM OF LUMINAIRE AND FINISHED FLOORS.
6. SUPPORT LUMINAIRES: ANCHOR SUPPORTS TO STRUCTURAL SLAB OR TO
STRUCTURAL MEMBERS WITHIN A PARTITION, OR ABOVE A SUSPENDED CEILING.
MAINTAIN LUMINAIRE POSITIONS AFTER CLEANING AND RELAMPING. SUPPORT
LUMINAIRES WITHOUT CAUSING CEILING OR PARTITION TO DEFLECT.
7. RELAMP LUMINAIRES WHICH HAVE FAILED LAMPS AT SUBSTANTIAL COMPLETION.
8. REPLACE BALLASTS DEEMED AS EXCESSIVELY NOISY BY ARCHITECT, ENGINEER,
OR OWNER.
9. INSTALL SUSPENDED LUMINAIRES AND EXIT SIGNS USING PENDANTS SUPPORTED
FROM SWIVEL HANGERS. PROVIDE PENDANT LENGTH REQUIRED TO SUSPEND
LUMINAIRE AT INDICATED HEIGHT.
10. INSTALL SURFACE MOUNTED LUMINAIRES AND EXIT SIGNS PLUMB AND ADJUST TO
ALIGN WITH BUILDING LINES AND WITH EACH OTHER. SECURE TO PREVENT
MOVEMENT.
11. MAKE WIRING CONNECTIONS TO BRANCH CIRCUIT USING BUILDING WIRE WITH
INSULATION SUITABLE FOR TEMPERATURE CONDITIONS WITHIN LUMINAIRE.
12. WHERE REMOTE BALLASTS OR DRIVERS ARE REQUIRED, INSURE ADEQUATE
ACCESSIBILITY. UPSIZE CONDUCTORS BETWEEN LUMINAIRE AND BALLAST/DRIVER
TO ACCOMMODATE VOLTAGE DROP.
R.
ROUTE MAIN J-HOOK PATHS SO THAT NO OUTLET IS MORE THAN 30 FEET
HORIZONTALLY FROM A J-HOOK SUPPORT. WHEREVER POSSIBLE, ROUTE J-HOOKS
PARALLEL OR PERPENDICULAR TO INTERIOR PARTITION LINES. THE DRAWINGS DO
NOT INDICATE THE EXACT NUMBER OF J-HOOKS REQUIRED. PROVIDE THE
CORRECT QUANTITY REQUIRED BY CEC. ADJUST LOCATION AND ROUTING TO
ACCOMMODATE WORK AND TO PREVENT INTERFERENCES.
3.6 FIELD QUALITY CONTROL
B.
SHEET TITLE
SPECIFICATION ELECTRICAL
REVISIONS
J-HOOKS:
1. ATTACH J-HOOK SUPPORTS SECURELY TO METAL STUDS OR STRUCTURAL METAL
DECK ABOVE USING THREADED RODS (SLIP RODS ARE NOT PERMITTED).
2.
3.
ABOVE.
4. PROVIDE A MINIMUM CLEARANCE AROUND J-HOOK CABLE PATH WITH A MINIMUM
5.
A.
717 Market Street
Suite 500
San Francisco, CA 94103
TEL
415.489.7240
FAX 415.489.7289
www.interfaceengineering.com
1111 Jackson Street
Oakland, California
PART 1 -
CATALOG NUMBER.
JACKSON CENTER ONE
SECTION 26 0000 - ELECTRICAL
TESTS: CONDUCT TESTS OF EQUIPMENT AND SYSTEMS TO DEMONSTRATE
COMPLIANCE WITH REQUIREMENTS SPECIFIED IN THIS DIVISION. REFER TO INDIVIDUAL
SPECIFICATION SECTIONS FOR REQUIRED TESTS. DOCUMENT TESTS AND INCLUDE IN
CLOSEOUT DOCUMENTS. DURING SITE EVALUATIONS BY ARCHITECT, PROVIDE AN
ELECTRICIAN WITH TOOLS TO REMOVE AND REPLACE TRIMS, COVERS, DEVICES, AND
THE LIKE, SO THAT A PROPER EVALUATION OF THE INSTALLATION CAN BE
PERFORMED.
TEST CONDUCTOR INSULATION ON FEEDERS OF 100 AMP AND GREATER FOR
CONFORMITY WITH 1000 VOLT MEGOHMMETER. USE INSULATED CABLE ENGINEERS
ASSOCIATION TESTING PROCEDURES. MINIMUM INSULATION RESISTANCE
ACCEPTABLE IS 1 MEGOHM FOR SYSTEMS 600 VOLTS AND BELOW. NOTIFY ARCHITECT
IF INSULATION RESISTANCE IS LESS THAN 1 MEGOHM.
C.
VERIFY ELECTRICAL CHARACTERISTICS OF EQUIPMENT PRIOR TO INSTALLATION OF
CONDUITS AND WIRING FOR EQUIPMENT.
D.
COORDINATE HVAC VOLTAGE REQUIREMENTS WITH DRAWINGS AND EQUIPMENT
SUBMITTALS PRIOR TO ROUGH IN.
DRAWN BY
CR
CHECKED BY
Kevin Kuang
JOB NO.
2014-0284
DATE
DATE
SHEET NUMBER
E6.0
F.
VERIFICATION OF CONDITIONS: VERIFY CEILING CONSTRUCTION, RECESSING DEPTH
AND OTHER CONSTRUCTION DETAILS PRIOR TO RELEASE OF LUMINAIRE FOR
SHIPMENT.
E.
F.
G.
3.7 CLEANING
A.
B.
C.
D.
REMOVE DIRT AND DEBRIS CAUSED BY THE EXECUTION OF THE ELECTRICAL WORK.
LEAVE THE ENTIRE ELECTRICAL SYSTEM INSTALLED IN CLEAN, DUST-FREE AND
PROPER WORKING ORDER.
THOROUGHLY CLEAN EXPOSED PORTIONS OF EQUIPMENT, REMOVING TEMPORARY
LABELS AND TRACES OF FOREIGN SUBSTANCES. THROUGHOUT WORK, REMOVE
CONSTRUCTION DEBRIS AND SURPLUS MATERIALS ACCUMULATED DURING WORK.
PART 1 -
6.
SPARE PARTS SUPPORT: PARTS SUPPLIES SHALL BE LOCATED IN THE FIELD TO
PROVIDE 80 PERCENT OF ALL EMERGENCY NEEDS. THE FACTORY SHALL SERVE AS
THE CENTRAL STOCKING FACILITY WHERE A DEDICATED SUPPLY OF ALL PARTS SHALL
BE AVAILABLE WITHIN 24 HOURS.
PRODUCT ENHANCEMENT PROGRAM: THE UPS MANUFACTURER SHALL MAKE
AVAILABLE FEATURE UPGRADE SERVICE OFFERINGS TO ALL USERS AS THEY ARE
DEVELOPED. THESE UPGRADES SHALL BE AVAILABLE AS OPTIONAL
FIELD-INSTALLABLE KITS.
MAINTENANCE CONTRACTS: A COMPLETE RANGE OF PREVENTATIVE AND
CORRECTIVE MAINTENANCE CONTRACTS SHALL BE PROVIDED AND OFFERED WITH
THE PROPOSAL. UNDER THESE CONTRACTS, THE MANUFACTURER SHALL MAINTAIN
THE USER'S EQUIPMENT TO THE LATEST FACTORY REVISIONS.
A.
WHERE FINISH OF LUMINAIRES OR ENCLOSURES IS DAMAGED, TOUCH UP FINISH WITH
MATCHING PAINT IN ACCORDANCE TO MANUFACTURER'S SPECIFICATIONS AND
INSTALLATION INSTRUCTIONS.
CLEAN PAINT SPLATTERS, DIRT, DUST, FINGERPRINTS, AND DEBRIS FROM LUMINAIRES.
A.
THE UPS SHALL WITHSTAND ANY COMBINATION OF THE FOLLOWING EXTERNAL
ENVIRONMENTAL CONDITIONS WITHOUT OPERATIONAL DEGRADATION.
1. OPERATING TEMPERATURE: 0 DEGREES C TO + 40 DEGREES C (32 DEGREES F TO
104 DEGREES F) WITHOUT DE-RATING (EXCLUDING BATTERIES).
2. STORAGE TEMPERATURE: - 25 DEGREES C TO + 60 DEGREES C (-13 DEGREES F TO
140 DEGREES F). PROLONGED STORAGE ABOVE + 40 DEGREES C (104 DEGREES F)
WILL CAUSE RAPID BATTERY SELF-DISCHARGE.
3. RELATIVE HUMIDITY (OPERATING AND STORAGE): 95 PERCENT MAXIMUM
NON-CONDENSING.
4. ELEVATION:
a. OPERATIONAL: 6600 FT (2000 M) MAXIMUM WITHOUT DE-RATING.
b. TRANSPORTATION: CAPABLE OF AIR TRANSPORT.
GENERAL
1.7 SAFETY
1.1 SUMMARY
A.
A.
THIS SPECIFICATION DESCRIBES A THREE-PHASE CONTINUOUS DUTY, ON-LINE,
DOUBLE CONVERSION, SOLID-STATE UNINTERRUPTIBLE POWER SYSTEM, HEREAFTER
REFERRED TO AS THE UPS. THE UPS SHALL OPERATE IN CONJUNCTION WITH THE
EXISTING BUILDING ELECTRICAL SYSTEM TO PROVIDE POWER CONDITIONING,
BACK_UP AND DISTRIBUTION FOR CRITICAL ELECTRICAL LOADS. THE UPS SHALL
CONSIST OF, AS REQUIRED BY THE PROJECT, THE UPS MODULE, BATTERY CABINET(S),
AND ACCESSORY CABINET(S) FOR TRANSFORMERS, MAINTENANCE BYPASS, PARALLEL
TIE, AND DISTRIBUTION APPLICATIONS, AND OTHER FEATURES AS DESCRIBED IN THIS
SPECIFICATION.
1.2 UPS SYSTEM DESCRIPTION
A.
B.
UPS SYSTEM COMPONENTS: THE UPS SYSTEM SHALL CONSIST OF THE FOLLOWING
MAIN COMPONENTS:
1. UPS MODULE CONTAINING A RECTIFIER, INVERTER, BATTERY CHARGER, STATIC
BYPASS, AND ASSOCIATED CONTROL AND MONITOR PANEL.
2. BATTERY STRING(S) IN LINE-AND-MATCH BATTERY CABINETS.
3. NON-MATCHING WALL MOUNTED OR FLOOR STANDING MAINTENANCE BYPASS
CABINETS.
UPS MODULE MODES OF OPERATION: THE UPS MODULE SHALL OPERATE AS AN
ON-LINE, FULLY AUTOMATIC SYSTEM IN THE FOLLOWING MODES:
1. NORMAL: UTILIZING COMMERCIAL AC POWER, THE CRITICAL LOAD SHALL BE
CONTINUOUSLY SUPPLIED BY THE INVERTER. THE INVERTER SHALL POWER THE
LOAD WHILE REGULATING BOTH VOLTAGE AND FREQUENCY. THE RECTIFIER
SHALL DERIVE POWER FROM THE COMMERCIAL AC SOURCE AND SHALL SUPPLY
DC POWER TO THE INVERTER. SIMULTANEOUSLY, THE BATTERY CHARGER SHALL
CHARGE THE BATTERY.
2. BATTERY: UPON FAILURE OF THE COMMERCIAL AC POWER, THE CRITICAL LOAD
SHALL CONTINUE TO BE SUPPLIED BY THE INVERTER, WHICH SHALL OBTAIN
POWER FROM THE BATTERIES WITHOUT ANY OPERATOR INTERVENTION. THERE
SHALL BE NO INTERRUPTION TO THE CRITICAL LOAD UPON FAILURE OR
RESTORATION OF THE COMMERCIAL AC SOURCE.
3. RECHARGE: UPON RESTORATION OF THE AC SOURCE, THE CHARGER SHALL
RECHARGE THE BATTERIES AND SIMULTANEOUSLY THE RECTIFIER SHALL
PROVIDE POWER TO THE INVERTER. THIS SHALL BE AN AUTOMATIC FUNCTION
AND SHALL CAUSE NO INTERRUPTION TO THE CRITICAL LOAD.
4. BYPASS: IF THE UPS MODULE MUST BE TAKEN OUT OF THE NORMAL MODE FOR
OVERLOAD, LOAD FAULT, OR INTERNAL FAILURES, THE STATIC BYPASS SWITCH
SHALL AUTOMATICALLY TRANSFER THE CRITICAL LOAD TO THE COMMERCIAL AC
POWER. RETURN FROM BYPASS MODE TO NORMAL MODE OF OPERATION SHALL
BE AUTOMATIC. NO-BREAK TRANSFER TO AND FROM BYPASS MODE SHALL BE
CAPABLE OF BEING INITIATED MANUALLY FROM THE FRONT PANEL.
5. ENERGY SAVER: THE UPS SHALL CONTINUOUSLY MONITOR THE VOLTAGE AND
FREQUENCY OF THE BYPASS SOURCE. WHEN THE SOURCE PARAMETERS ARE
WITHIN ACCEPTABLE LIMITS, THE UPS WILL UTILIZE A MINIMAL/OPTIMAL
COMBINATION OF ITS INTERNAL SUBSYSTEMS TO ENSURE ACCEPTABLE POWER IS
ALWAYS DELIVERED TO THE CRITICAL LOAD, AT A SYSTEM EFFICIENCY OF 99
PERCENT OR GREATER, OVER THE RANGE OF 10 PERCENT TO 100 PERCENT LOAD.
THE ENERGY SAVER SYSTEM SHALL BE ENABLED BY THE USER, AND SHALL BE
(WITHOUT USER INTERVENTION) PROVIDE MAXIMUM POWER CONDITIONING ANY
TIME BYPASS SOURCE VARIATION LEVELS EXCEED PRESET, ADJUSTABLE LIMITS.
WHEN ENERGY SAVER SYSTEM IS UTILIZED, THE UPS MUST ATTENUATE ANSI
C62.41-TYPE LINE TRANSIENTS TO WITHIN IEC AND ITIC LIMITS. THE ENERGY
SAVER SYSTEM SHALL BE ABLE TO DISTINGUISH BETWEEN UPSTREAM (UTILITY)
FAULTS AND DOWNSTREAM (LOAD) FAULTS, AND REACT APPROPRIATELY TO
PROTECT AND SUPPORT THE CRITICAL LOAD, WITHOUT INTERRUPTION.
1.3 REFERENCES
A.
UL 1778 (UNDERWRITERS LABORATORIES) - STANDARD FOR UNINTERRUPTIBLE
POWER SUPPLY EQUIPMENT. PRODUCT SAFETY REQUIREMENTS FOR THE UNITED
STATES.
B.
CSA C22.2 NO 107.1(CANADIAN STANDARDS ASSOCIATION) - COMMERCIAL AND
INDUSTRIAL POWER SUPPLIES. PRODUCT SAFETY REQUIREMENTS FOR CANADA.
C.
NEMA PE-1 - (NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION) UNINTERRUPTIBLE POWER SYSTEMS STANDARD.
D.
IEC 62040-1-1 (INTERNATIONAL ELECTROTECHNICAL COMMISSION) - UNINTERRUPTIBLE
POWER SYSTEMS (UPS) - PART 1-1: GENERAL AND SAFETY REQUIREMENTS FOR UPS
USED IN OPERATOR ACCESS AREAS.
LICT WITH LOCATIONS FOR
E.
F.
B.
THE UPS SHALL BE CERTIFIED BY UNDERWRITERS LABORATORIES IN ACCORDANCE
WITH UL 1778.
THE UPS SHALL BE CERTIFIED BY THE CANADIAN STANDARDS ASSOCIATION IN
ACCORDANCE WITH CSA C22.2 NO.107.1-M91.
PART 2 -
PRODUCTS
2.1 MANUFACTURERS
A.
EATON CORPORATION/POWERWARE
B.
LIEBERT
C.
TOSHIBA
D.
MITSUBISHI
E.
OR APPROVED EQUIVALENT.
2.2 UPS MODULE STANDARD FEATURES
A.
THE UPS MODULE SHALL CONSIST OF THE FOLLOWING STANDARD COMPONENTS:
1. RECTIFIER/CHARGER: THE RECTIFIER/CHARGER SHALL CONVERT INCOMING AC
POWER TO REGULATED DC OUTPUT FOR SUPPLYING THE INVERTER AND FOR
CHARGING THE BATTERY. THE RECTIFIER/CHARGER SHALL BE A HIGH-FREQUENCY
PWM DESIGN, USING INSULATED GATE BI-POLAR TRANSISTORS (IGBTS). THE
MODULAR DESIGN OF THE UPS SHALL PERMIT SAFE AND FAST REMOVAL AND
REPLACEMENT OF THE RECTIFIER/CHARGER MODULE. MEAN TIME TO REPAIR
(MTTR) FOR THE MODULE SHALL BE NO MORE THAN 30 MINUTES IN ORDER TO
RETURN UPS TO NORMAL MODE. THE RECTIFIER/CHARGER MODULE SHALL ALSO
PROVIDE THE FOLLOWING:
a. THE RECTIFIER SHALL BE CAPABLE OF DRAWING POWER FROM THE UTILITY
WITH A POWER FACTOR OF 0.99 UNDER NOMINAL CONDITIONS.
b. THE RECTIFIER SHALL FEATURE PROTECTION CIRCUITRY THAT PREVENTS THE
IGBTS FROM SOURCING CURRENT IN EXCESS OF THEIR PUBLISHED RATINGS.
c. AN OPTION SHALL BE PROVIDED TO ALLOW THE RECTIFIER TO BE CAPABLE OF
OPERATING FROM A DELTA TRANSFORMER OUTPUT OR HIGH IMPEDANCE
GROUNDED TRANSFORMER (480V SYSTEMS ONLY).
2. INVERTER: THE INVERTER SHALL FEATURE AN IGBT PULSE-WIDTH-MODULATION
(PWM) DESIGN WITH HIGH SPEED SWITCHING. THE INVERTER SHALL ALSO HAVE
THE FOLLOWING FEATURES:
a. THE INVERTER SHALL BE CAPABLE OF PROVIDING THE SPECIFIED QUALITY
OUTPUT POWER WHILE OPERATING FROM ANY DC SOURCE VOLTAGE
(RECTIFIER OR BATTERY) WITHIN THE SPECIFIED DC OPERATING RANGE.
b. THE MODULAR DESIGN OF THE UPS SHALL PERMIT SAFE AND FAST REMOVAL
AND REPLACEMENT OF THE INVERTER MODULE. MEAN TIME TO REPAIR
(MTTR) FOR THE MODULE SHALL BE NO MORE THAN 30 MINUTES IN ORDER TO
RETURN UPS TO NORMAL MODE.
c. THE INVERTER SHALL FEATURE PROTECTION CIRCUITRY THAT PREVENTS THE
IGBTS FROM SOURCING CURRENT IN EXCESS OF THEIR PUBLISHED RATINGS.
3. STATIC BYPASS: THE BYPASS SHALL SERVE AS AN ALTERNATIVE SOURCE OF
POWER FOR THE CRITICAL LOAD WHEN AN ABNORMAL CONDITION PREVENTS
OPERATION IN NORMAL MODE. THE BYPASS SHALL CONSIST OF A FULLY RATED,
CONTINUOUS DUTY, NATURALLY COMMUTATED STATIC SWITCH FOR HIGH-SPEED
TRANSFERS. THE BYPASS SHALL FEATURE THE FOLLOWING TRANSFER AND
OPERATIONAL CHARACTERISTICS.
a. TRANSFERS TO BYPASS SHALL BE AUTOMATICALLY INITIATED FOR THE
FOLLOWING CONDITIONS:
1) OUTPUT OVERLOAD PERIOD EXPIRED.
2) CRITICAL BUS VOLTAGE OUT OF LIMITS.
3) INTERNAL OVER TEMPERATURE PERIOD EXPIRED.
4) TOTAL BATTERY DISCHARGE.
5) UPS FAILURE.
b. UNINTERRUPTED AUTOMATIC RE-TRANSFER SHALL TAKE PLACE WHENEVER
THE INVERTER IS CAPABLE OF ASSUMING THE CRITICAL LOAD.
c. UNINTERRUPTED AUTOMATIC RE-TRANSFERS SHALL BE INHIBITED FOR THE
FOLLOWING CONDITIONS:
1) WHEN TRANSFER TO BYPASS IS ACTIVATED MANUALLY OR REMOTELY.
2) IN THE EVENT OF MULTIPLE TRANSFERS/RE-TRANSFER OPERATIONS THE
IEC 62040-1-2 (INTERNATIONAL ELECTROTECHNICAL COMMISSION) - UNINTERRUPTIBLE
POWER SYSTEMS (UPS) - PART 1-2: GENERAL AND SAFETY REQUIREMENTS FOR UPS
USED IN RESTRICTED ACCESS LOCATIONS.
IEC 62040-3 (INTERNATIONAL ELECTROTECHNICAL COMMISSION) - UNINTERRUPTIBLE
POWER SYSTEMS (UPS) - PART 3: METHOD OF SPECIFYING THE PERFORMANCE AND
TEST REQUIREMENTS.
G. IEEE 587 (ANSI C62.41) CATEGORY A & B (INTERNATIONAL ELECTRICAL AND
ELECTRONICS ENGINEERS) - RECOMMENDED PRACTICES ON SURGE VOLTAGES IN
LOW VOLTAGE POWER CIRCUITS.
H.
I.
CISPR 22: FCC RULES AND REGULATIONS 47, PART 15, CLASS A (FEDERAL
COMMUNICATIONS COMMISSION) - RADIO FREQUENCY DEVICES (PRIOR TO FEB 16,
2006).
MIL-HDBK-217E (MILITARY HANDBOOK) - RELIABILITY PREDICTION OF ELECTRONICS
EQUIPMENT
1.4 SUBMITTALS
A.
POSSIBLE, ROUTE J-HOOKS
ION. REFER TO INDIVIDUAL
THE UPS SHALL BE SUPPLIED WITH SUFFICIENT DOCUMENTATION, INCLUDING THE
FOLLOWING MANUALS:
1. INSTALLATION AND OPERATION MANUAL: ONE COPY OF THE INSTALLATION AND
OPERATION MANUAL SHALL BE FURNISHED. IT SHALL POSSESS SUFFICIENT
DETAIL AND CLARITY TO ENABLE THE OWNER'S TECHNICIANS OR
REPRESENTATIVES TO INSTALL AND OPERATE THE UPS EQUIPMENT AND
ACCESSORIES. THE MANUAL SHALL INCLUDE THE FOLLOWING MAJOR ITEMS:
a. UPS DESCRIPTION
b. UPS SITE PLANNING AND UNPACKING
c. UPS INSTALLATION
d. OPTIONAL ACCESSORY INSTALLATION
e. UPS THEORY OF OPERATION
f. OPERATING PROCEDURES
g. SYSTEM EVENTS
h. UPS MAINTENANCE
i.
PERFORMANCE AND TECHNICAL SPECIFICATIONS
j.
WIRING REQUIREMENTS AND RECOMMENDATIONS
k. PHYSICAL FEATURES AND REQUIREMENTS
l.
CABINET DIMENSIONS
1.5 QUALIFICATIONS
A.
THE UPS MANUFACTURER SHALL HAVE A MINIMUM OF FORTY YEARS' EXPERIENCE IN
THE DESIGN, MANUFACTURE AND TESTING OF SOLID-STATE UPS SYSTEMS. A LIST OF
INSTALLED UPS SYSTEMS OF THE SAME TYPE AS THE MANUFACTURER PROPOSES TO
FURNISH FOR THIS APPLICATION SHALL BE SUPPLIED UPON REQUEST.
B.
THE UPS MANUFACTURER SHALL HAVE ISO 9001 CERTIFICATION FOR
ENGINEERING/R&D, MANUFACTURING FACILITIES AND SERVICE ORGANIZATION.
C.
THE UPS MANUFACTURER SHALL MAINTAIN A STAFFED 7X24X365 CALL CENTER FOR
TECHNICAL AND EMERGENCY SUPPORT.
D.
FIELD ENGINEERING SUPPORT: THE UPS MANUFACTURER SHALL DIRECTLY EMPLOY A
NATIONWIDE FIELD SERVICE DEPARTMENT STAFFED BY FACTORY-TRAINED FIELD
4.
5.
ANY TEN-MINUTE PERIOD. THE FOURTH TRANSFER SHALL LOCK THE
CRITICAL LOAD ON THE BYPASS SOURCE.
3) UPS FAILURE.
d. UNINTERRUPTED MANUAL TRANSFERS SHALL BE INITIATED FROM THE
CONTROL PANEL. UNINTERRUPTED MANUAL TRANSFERS TO BYPASS AND
FROM BYPASS SHALL BE POSSIBLE WITH THE INVERTER LOGIC. DURING
MANUAL TRANSFERS TO BYPASS MODE, THE INVERTER MUST VERIFY PROPER
BYPASS OPERATIONS BEFORE TRANSFERRING THE CRITICAL LOAD TO THE
BYPASS.
e. ALL TRANSFERS TO BYPASS SHALL BE INHIBITED FOR THE FOLLOWING
CONDITIONS:
1) BYPASS VOLTAGE OUT OF LIMITS (+/- 10 PERCENT OF NOMINAL).
2) BYPASS FREQUENCY OUT OF LIMITS (+/- 3 HZ, ADJUSTABLE, FACTORY
SET).
3) BYPASS OUT OF SYNCHRONIZATION.
4) BYPASS PHASE ROTATION / INSTALLATION ERROR.
f. STATIC TRANSFER TIME: NO BREAK, COMPLETE IN LESS THAN 4MS.
g. THE BYPASS SHALL BE MANUALLY ENERGIZED USING THE CONTROL PANEL OR
REMOTELY THROUGH A BUILDING ALARM INPUT.
MONITORING AND CONTROL COMPONENTS: THE FOLLOWING COMPONENTS SHALL
PROVIDE MONITOR AND CONTROL CAPABILITY:
a. CONTROL PANEL WITH STATUS INDICATORS.
b. ALARM AND METERING DISPLAY.
c. BUILDING ALARM MONITORING.
d. COMMUNICATION PORTS.
BATTERY MANAGEMENT SYSTEM: THE UPS SHALL CONTAIN A BATTERY
MANAGEMENT SYSTEM WHICH HAS THE FOLLOWING FEATURES:
a. THE BATTERY MANAGEMENT SYSTEM SHALL PROVIDE BATTERY TIME
REMAINING WHILE OPERATING IN NORMAL MODE AND BATTERY MODE.
BATTERY TIME AVAILABLE INFORMATION SHALL BE DISPLAYED REAL-TIME,
EVEN UNDER CHANGING LOAD CONDITIONS. UPON COMMISSIONING, BATTERY
RUNTIME INFORMATION SHALL BE AVAILABLE.
b. THE BATTERY MANAGEMENT SYSTEM SHALL AUTOMATICALLY TEST THE
BATTERY STRING(S) TO ENSURE THAT THE BATTERY IS CAPABLE OF
PROVIDING GREATER THAT 80 PERCENT OF ITS RATED CAPACITY. TESTING
THE BATTERIES SHALL NOT JEOPARDIZE THE OPERATION OF THE CRITICAL
LOAD. UPON DETECTION OF THE BATTERY STRING(S) NOT CAPABLE OF
PROVIDING 80 PERCENT, THE UPS SYSTEM WILL ALARM THAT THE BATTERY
NEEDS ATTENTION/REPLACEMENT. THE BATTERY TEST SHALL BE ABLE TO
DETECT THE FOLLOWING:
1)
OPEN BATTERY STRING.
2)
SHORTED BATTERY STRING.
3)
BATTERY CAPACITY.
c. THE UPS SHALL COMMUNICATE BATTERY TEST AND MONITORING DATA TO THE
UPS MANUFACTURER'S REMOTE MONITORING SITE. BATTERY LIFE REMAINING,
CAPACITY, AND NUMBER OF ON-BATTERY EVENTS SHALL BE PROVIDED IN A
MONTHLY REPORT.
d. AN OPTIONAL TEMPERATURE SENSOR SHALL BE AVAILABLE TO MONITOR THE
AMBIENT TEMPERATURE INTERNAL TO THE BATTERY CABINET. IF THE
AMBIENT TEMPERATURE INCREASES, THE UPS SYSTEM CHARGER SHALL
AUTOMATICALLY REDUCE THE CHARGING VOLTAGE TO A LEVEL
RECOMMENDED BY THE BATTERY MANUFACTURER. IF THE AMBIENT
TEMPERATURE IS DECREASED THE UPS SHALL AUTOMATICALLY INCREASE
THE BATTERY CHARGE VOLTAGE TO THAT RECOMMENDED BY THE BATTERY
MANUFACTURER.
WIRING TERMINALS: FOR 208VAC 4-WIRE OUTPUT CONFIGURATIONS, THE
NEUTRAL OUTPUT COMPRESSION TERMINAL SHALL BE SIZED FOR 200 PERCENT OF
UPS MODULE RATED CURRENT TO ACCOMMODATE HIGHER NEUTRAL CURRENTS
ASSOCIATED WITH NON-LINEAR LOADS. THE UPS MODULE SHALL CONTAIN
MECHANICAL COMPRESSION TERMINALS (ADEQUATELY SIZED TO ACCOMMODATE
90 DEGREE C WIRING) FOR SECURING USER WIRING TO THE FOLLOWING
LOCATIONS:
a. RECTIFIER/CHARGER INPUT CONNECTIONS (3-WIRE PLUS GROUND).
b. BYPASS INPUT CONNECTIONS (3-WIRE PLUS GROUND FOR 3-WIRE PLUS
GROUND OUTPUT CONFIGURATION (480VAC), OR 4-WIRE PLUS GROUND FOR
4-WIRE PLUS GROUND OUTPUT CONFIGURATION).
c. DC LINK CONNECTIONS FOR BATTERY CABINETS (POSITIVE AND NEGATIVE).
d. AC OUTPUT CONNECTIONS (3 OR 4 WIRES PLUS GROUND).
2)
b.
2)
8.
THE UPS SYSTEM SHALL CONSIST OF THE FOLLOWING OPTIONS AND ACCESSORIES AS
REQUIRED:
1. INTEGRATED MAINTENANCE BYPASS SHALL BE PROVIDED THAT INCLUDES:
a. ALL HARDWARE AND INTERCONNECTING CABLE FOR CONNECTION TO UPS
MODULE.
b. MANUAL MAINTENANCE BYPASS SWITCH TO ISOLATE UPS MODULE FROM
COMMERCIAL AC INPUT AND CRITICAL LOAD. SWITCH SHALL PROVIDE
COMPLETE ISOLATION OF UPS FOR SERVICING AND, IF NECESSARY,
COMPLETE REMOVAL AND REPLACEMENT OF UPS WHILE STILL PROVIDING
BYPASS POWER TO CRITICAL LOAD. SWITCH SHALL BE MAKE-BEFORE-BREAK,
INTERLOCKED BETWEEN UPS AND BYPASS TO PROHIBIT IMPROPER
OPERATION.
2. SNMP NETWORK ADAPTER AND UPS POWER MONITORING SOFTWARE: SNMP
ADAPTERS SHALL PROVIDE A COMMUNICATIONS INTERFACE BETWEEN THE UPS
MODULE AND SNMP-COMPATIBLE NETWORK MANAGEMENT SYSTEMS. THIS
CAPABILITY SHALL ALLOW THE UNIT TO BE MONITORED REMOTELY OVER AN
ETHERNET NETWORK USING A STANDARD WEB BROWSER.
a. UPS POWER MONITORING SOFTWARE: THIS SYSTEM SHALL CONTINUOUSLY
MONITOR CRITICAL POWER ELEMENTS ASSOCIATED WITH THE UPS, USING
THE COMMUNICATIONS PORT ON EACH MODULE AND A CUSTOMER FURNISHED
PC. THE SYSTEM SHALL AUTOMATICALLY ALARM IF ANY PROBLEMS ARISE AND
NOTIFY LOCAL OR REMOTE PERSONNEL OF THE ALARM CONDITION VIA EMAIL,
PAGE, OR TEXT MESSAGE.
3. BATTERY CABINET: THE BATTERY CABINET SHALL FEATURE VALVE REGULATED,
HIGH-RATE DISCHARGE, LEAD-ACID BATTERIES WHICH PROVIDE ENERGY TO THE
SUPPORT THE CRITICAL LOAD DURING A MOMENTARY LOSS OF INPUT POWER TO
THE RECTIFIER. THE BATTERIES SHALL BE FLAME RETARDANT IN ACCORDANCE
WITH UL 94V2 REQUIREMENTS. THE BATTERY CABINET SHALL HAVE THE
FOLLOWING FEATURES:
a. THE BATTERY CABINET SHALL BE THE SAME DEPTH AND HEIGHT AS THE UPS
MODULE.
b. THE BATTERY CABINET SHALL FEATURE A MECHANICAL ENCLOSURE OF LIKE
APPEARANCE TO THE UPS MODULE AND SHALL FEATURE CASTERS. EACH
BATTERY CABINET SHALL REQUIRE FRONT ACCESS ONLY FOR INSTALLATION,
SERVICE AND MAINTENANCE. THE BATTERY CABINET SHALL PROVIDE TOP
AND BOTTOM CABLE ENTRY.
c. POWER WIRING INTERNAL TO EACH BATTERY CABINET SHALL BE FACTORY
PROVIDED. EACH BATTERY CABINET SHALL FEATURE UP TO 10 BATTERY
TRAYS WHICH CAN BE INDIVIDUALLY DISCONNECTED FROM THE BATTERY
CABINET POWER WIRING WITH QUICK DISCONNECT DEVICES. EACH BATTERY
TRAY SHALL BE FIRMLY SECURED TO THE BATTERY CABINET FRAME WITH
FASTENERS. EACH BATTERY TRAY SHALL BE REMOVABLE FROM THE FRONT
OF THE BATTERY CABINET.
d. EACH BATTERY CABINET SHALL FEATURE A DC RATED CIRCUIT BREAKER. THE
CIRCUIT BREAKER WITHIN THE BATTERY CABINET SHALL ONLY PROVIDE
PROTECTION TO THE BATTERY STRING WITHIN THAT BATTERY CABINET. FOR
BATTERY CONFIGURATIONS INVOLVING MULTIPLE BATTERY CABINETS, A
BATTERY STRING IN ONE BATTERY CABINET MAY BE ISOLATED FROM THE DC
LINK VIA ITS CIRCUIT BREAKER WITHOUT REMOVING OTHER BATTERY STRINGS
FROM THE DC LINK AND THE UPS MODULE.
e. THE CIRCUIT BREAKER IN EACH BATTERY CABINET SHALL FEATURE AN A/B
AUXILIARY SWITCH. THE UPS MODULE SHALL BE CAPABLE OF MONITORING
AND ALARMING AN OPEN BATTERY CABINET CIRCUIT BREAKER CONDITION.
f.
THE CIRCUIT BREAKER IN EACH BATTERY CABINET SHALL FEATURE A 48VDC
UNDER VOLTAGE RELEASE DEVICE. THE UV DEVICE SHALL OPERATE TO TRIP
THE BATTERY BREAKER(S) FOR AN EMERGENCY POWER OFF COMMAND OR
BATTERY DISABLE COMMAND.
g. POWER AND CONTROL WIRING BETWEEN THE BATTERY CABINET AND THE UPS
SHALL BE FACTORY PROVIDED WITH COMPRESSION TYPE CONNECTORS
BETWEEN CABINETS.
h. THE BATTERIES SHALL BE CONFIGURED WITH A 1/4-INCH SPADE TYPE
CONNECTOR FOR ATTACHING SENSE LEADS TO EACH JAR TO FACILITATE THE
FUTURE ADDITION OF A BATTERY MONITORING SYSTEM.
i.
EXPECTED BATTERY LIFE: 200 COMPLETE FULL LOAD DISCHARGE CYCLES
WHEN OPERATED AND MAINTAINED WITHIN SPECIFICATIONS.
E.
D.
AUTOMATIC (TIME BASED) OR MANUAL (USER INITIATED)
EQUALIZATION AVAILABLE
THE ABSOLUTE MINIMUM OPERATIONAL VOLTAGE IS 1.67 V PER CELL
(ADJUSTABLE).
THE UPS MODULE WILL AUTOMATICALLY DISCONNECT THE BATTERY SYSTEM IN
CASE OF FULL BATTERY DISCHARGE FOLLOWED BY PROLONGED UTILITY AC
VOLTAGE FAILURE. THE TIME WINDOW BEFORE BATTERY DISCONNECTION
OCCURS SHALL BE PROGRAMMABLE FOR BOTH TIME AND VOLTAGE.
TRANSIENT VOLTAGE RESPONSE SHALL BE < +/- 5 PERCENT FROM NOMINAL
VOLTAGE FOR 100 PERCENT LOAD STEP, FULL LOAD RE-TRANSFERS AND FULL
LOAD DROP ON BATTERY.
3.
BATTERY: THIS SHALL INDICATE THAT THE COMMERCIAL AC UTILITY OR
GENERATOR SOURCE HAS FAILED AND THE BATTERY IS SUPPLYING POWER TO
THE INVERTER, WHICH IS SUPPORTING THE LOAD. A TEXT MESSAGE SHALL
INDICATE IF THE BATTERY CHARGE IS LOW OR IF THE BATTERY IS INSTALLED BUT
DISCONNECTED.
LINEAR LOAD HARMONIC DISTORTION CAPABILITY: OUTPUT VOLTAGE THD OF
LESS THAN 2 PERCENT FOR 100 PERCENT LINEAR LOAD.
6.
NON-LINEAR LOAD HARMONIC DISTORTION CAPABILITY: OUTPUT VOLTAGE THD OF
LESS THAN 5 PERCENT FOR 100 PERCENT NON-LINEAR LOAD WHEN TESTED USING
THE NON-LINEAR LOAD DESCRIBED IN IEC 62040-3 CONNECTED LINE TO NEUTRAL.
7.
MANUAL OUTPUT VOLTAGE ADJUSTMENT SHALL BE +/- 3 PERCENT FROM NOMINAL.
8.
LINE SYNCHRONIZATION RANGE SHALL BE +/- 3HZ, ADJUSTABLE TO +/- 5HZ.
9.
FREQUENCY REGULATION SHALL BE +/- 0.01HZ FREE RUNNING.
a.
BALANCED LINEAR LOAD SHALL BE +/- 1 DEGREE FROM NOMINAL 120 DEGREES
b.
UNBALANCED LINEAR LOADS SHALL LESS THAN +/- 5 DEGREES FROM
AVERAGE PHASE VOLTAGE FOR 100 PERCENT LOAD UNBALANCE.
a.
BALANCED LINEAR LOADS SHALL BE +/- 1 PERCENT FROM AVERAGE PHASE
VOLTAGE
b.
UNBALANCED LINEAR LOADS SHALL BE LESS THAN +/- 5 PERCENT FOR 100
PERCENT LOAD UNBALANCED
-65DB UP TO 20KHZ, -40DB UP TO 100KHZ
b.
> 100DB WITH ISOLATION TRANSFORMER
EXTERNAL BYPASS INDICATOR CONNECTION: A CONNECTION POINT SHALL BE
PROVIDED TO ACKNOWLEDGE THAT AN EXTERNAL MAINTENANCE BYPASS HAS
BEEN CLOSED AROUND THE UPS, PLACING THE CRITICAL LOAD ON UTILITY POWER.
7.
THE SYSTEM SHALL HAVE OPTIONS TO ADD FOUR (4) ADDITIONAL BUILDING
ALARMS, 384 LOGGED EVENTS, 4 ADDITIONAL LANGUAGES, MANDARIN OR RUSSIAN
AS A PRIMARY LANGUAGE.
NOMINAL OUTPUT VOLTAGE 208 VAC, 3-PHASE, 3 WIRE OR 4-WIRE (OR 480V,
3-PHASE, 3-WIRE OR 4-WIRE) PLUS GROUND AT THE OUTPUT OF THE INTEGRATED
DISTRIBUTION AND BYPASS CABINET. OUTPUT WIRING CONFIGURATION IS BASED
UPON INPUT WIRING CONFIGURATION FOR SYSTEMS WITHOUT INTERNAL
TRANSFORMERS.
3.
STEADY-STATE VOLTAGE REGULATION SHALL BE WITHIN +/- 10 PERCENT FROM
NOMINAL OUTPUT VOLTAGE.
4.
LINE SYNCHRONIZATION RANGE SHALL BE +/- 3HZ, ADJUSTABLE TO +/- 5HZ.
5.
FREQUENCY REGULATION SHALL BE +/-3HZ WHEN BYPASS SOURCE IS WITHIN THE
LIMITS IN (1) ABOVE, AND +/- 0.01HZ FREE RUNNING,
6.
OVERLOAD CURRENT CAPABILITY (WITH BYPASS SOURCE WITHIN THE LIMITS OF
(1) ABOVE) 1000 PERCENT FOR 20MSEC, 600 PERCENT FOR 50 MS
7.
STATIC TRANSFER TIME: NO BREAK, COMPLETED IN LESS THAN 2MS, INCLUDING
DETECTION TIME.
8.
ACOUSTICAL NOISE: NOISE GENERATED BY THE UPS UNDER NORMAL OPERATION
SHALL NOT EXCEED 65DBA AT ONE METER FROM ANY OPERATOR SURFACE,
MEASURED AT 25 DEGREES C (77 DEGREES F) AND FULL LOAD.
SYNCHRONIZING BYPASS VOLTAGE RANGE SHALL BE +/- 10 PERCENT OF AVERAGE
NOMINAL INPUT VOLTAGE.
2.
SYNCHRONIZING BYPASS FREQUENCY RANGE IS CENTERED ON THE NOMINAL
FREQUENCY.
3.
BYPASS AND RECTIFIER INPUTS CAN BE SUPPLIED FROM OUT OF PHASE SOURCES
IF REQUIRED.
4.
INPUT SURGE WITHSTAND CAPABILITY: THE UPS SHALL BE IN COMPLIANCE WITH
IEEE 587 (ANSI C62.41), CATEGORY A & B (6KV).
2.
NOMINAL DC VOLTAGE SHALL BE VARIABLE BETWEEN 384VDC TO 480VDC FOR
208V INPUT, AND BETWEEN 432VDC TO 480VDC FOR 480V INPUT.
STEADY STATE VOLTAGE REGULATION SHALL BE +/- 0.5 PERCENT.
3.
VOLTAGE RIPPLE SHALL BE LESS THAT 0.5 PERCENT (PEAK-TO-PEAK).
4.
CAPACITY: THE RECTIFIER/CHARGER SHALL SUPPORT A FULLY LOADED INVERTER
AND RECHARGE THE BATTERY TO 90 PERCENT OF ITS FULL CAPACITY WITHIN 10
TIMES THE DISCHARGE WHEN INPUT CURRENT LIMIT IS SET AT MAXIMUM.
5.
6.
7.
LOW LINE OPERATION: THE RECTIFIER/CHARGER SHALL BE CAPABLE OF SHARING
THE DC LOAD WITH THE BATTERY WHEN THE INPUT VOLTAGE FALLS BELOW THE
SPECIFIED OPERATION INPUT VOLTAGE RANGE, THE ON BATTERY INDICATOR
SHALL ENUNCIATE OPERATION IN THIS MODE.
DC SENSING: REDUNDANT DC VOLTAGE SENSING METHODS SHALL BE
INCORPORATED FOR PROVIDING BATTERY OVER-VOLTAGE PROTECTION.
2.
A CHARGING MODE THAT INCREASES BATTERY LIFE BY ALLOWING THE
BATTERY TO REST, REDUCING POSITIVE PLATE CORROSION
EMI SUPPRESSION: THE UPS SHALL MEET FCC RULES AND REGULATION 47, PART
15, FOR CLASS A DEVICES PRIOR TO FEB 16, 2006.
A.
B.
C.
D.
E.
F.
UPS MODULES SHALL BE CAPABLE OF BEING PARALLELED TO INCREASE SYSTEM
POWER LEVELS OR TO PROVIDE REDUNDANT POWER. A TOTAL OF EIGHT (8) UPS
MODULES SHALL BE CAPABLE OF PARALLEL OPERATION, EITHER FOR CAPACITY
OR REDUNDANT SYSTEMS. IT SHALL BE POSSIBLE TO PARALLEL UP TO SIX (6) UPS
MODULES WITHOUT A CENTRAL BYPASS CABINET. THE PARALLEL SYSTEM SHALL
HAVE INTELLIGENCE TO AUTOMATICALLY RECOGNIZE THE NEED FOR CAPACITY
AND/OR REDUNDANCY. PARALLEL SYSTEMS SHALL UTILIZE AUTONOMOUS UPS
POWER MODULES THAT DO NOT RELY ON ANY CONTROL INTERCONNECTIONS FOR
SYNCHRONIZED OPERATION. THE INDIVIDUAL MODULES SHALL OPERATE IN A
PEER-TO-PEER MANNER TO PROVIDE AUTOMATIC LOAD SHARING,
THE PARALLEL SYSTEM SHALL UTILIZE A COMMUNICATIONS NETWORK TO
PROVIDE SYSTEM INFORMATION AND STATUS, SUCH AS OPERATING MODE AND
METER DATA. THIS NETWORK SHALL PROVIDE INDIVIDUAL MODULE INFORMATION
AS WELL AS TOTAL SYSTEM INFORMATION, AND INDIVIDUAL MODULE INFORMATION
SHALL BE AVAILABLE FROM ANY MODULE'S FRONT PANEL DISPLAY. THE LOSS OF
THIS SYSTEM INFORMATION NETWORK SHALL NOT CAUSE THE PARALLEL UNITS TO
TRANSFER TO BYPASS OR DROP THE CRITICAL LOAD.
ENCLOSURES: THE UPS SHALL BE HOUSED IN FREE-STANDING DOUBLE FRONT
ENCLOSURES (SAFETY SHIELDS BEHIND DOORS) EQUIPPED WITH CASTERS AND
LEVELING FEET. THE ENCLOSURES SHALL BE DESIGNED FOR COMPUTER ROOM
APPLICATIONS. FRONT DOORS SHALL HAVE LOCKS TO PREVENT UNAUTHORIZED
ENTRY.
VENTILATION: THE UPS SHALL BE DESIGNED FOR FORCED-AIR COOLING. AIR INLETS
SHALL BE ON THE FRONT OF THE UNIT. AIR OUTLETS SHALL BE ON THE TOP.
EIGHTEEN INCHES OF CLEARANCE OVER THE UPS OUTLETS SHALL BE REQUIRED FOR
PROPER AIR CIRCULATION. AIR FILTERS SHALL BE COMMONLY AVAILABLE SIZES.
NO BACK OR SIDE CLEARANCE OR ACCESS SHALL BE REQUIRED FOR THE SYSTEM.
THE BACK AND SIDE ENCLOSURE COVERS SHALL BE CAPABLE OF BEING LOCATED
DIRECTLY ADJACENT TO A WALL.
CABLE ENTRY: STANDARD CABLE ENTRY FOR THE UPS CABINET SHALL BE THROUGH
EITHER THE ENCLOSURE BOTTOM OR TOP. A DEDICATED WIREWAY SHALL BE
PROVIDED WITHIN THE UPS CABINET FOR ROUTING USER INPUT AND OUTPUT WIRING.
FRONT ACCESS: ALL SERVICEABLE SUBASSEMBLIES SHALL BE MODULAR AND
CAPABLE OF BEING REPLACED FROM THE FRONT OF THE UPS (FRONT ACCESS ONLY
REQUIRED). SIDE OR REAR ACCESS FOR INSTALLATION, SERVICE, REPAIR OR
MAINTENANCE OF THE UPS SYSTEM SHALL NOT BE REQUIRED.
SERVICE AREA REQUIREMENTS: THE 208VAC SYSTEM SHALL REQUIRE NO MORE THAN
THIRTY-SIX (36) INCHES OF FRONT SERVICE ACCESS ROOM AND SHALL NOT REQUIRE
SIDE OR REAR ACCESS FOR SERVICE OR INSTALLATION. THE 480VAC SYSTEM SHALL
REQUIRE NO MORE THAN FORTY-TWO (42) INCHES OF FRONT SERVICE ACCESS ROOM
AND SHALL NOT REQUIRE SIDE OR REAR ACCESS FOR SERVICE OR INSTALLATION.
2.6 CONTROLS AND INDICATORS
A.
COMMUNICATIONS BAY: THE UPS SHALL BE EQUIPPED WITH FIELD CONFIGURABLE
COMMUNICATIONS BAYS THAT WILL ACCOMMODATE FOUR (4) COMMUNICATION
DEVICES
REMOTE MONITORING:
1.
OPTIONAL WEB/SNMP COMMUNICATION CAPABILITIES WILL BE AVAILABLE FOR ALL
SYSTEMS.
2.
THE UPS SHALL BE ABLE TO BE MONITORED REMOTELY VIA COMMUNICATIONS
DEVICES. UPS MANUFACTURER SHALL PROVIDE OPTIONAL COMMUNICATIONS
DEVICES CAPABLE OF COMMUNICATING VIA VARIOUS INDUSTRY STANDARD
PROTOCOLS SUCH AS RS232 AND MODBUS. MONITORING OF UPS STATUS MAY
ALSO BE PERFORMED THROUGH ISOLATED DRY CONTACT FORM C RELAYS.
3.
REMOTE MONITORING OF THE UPS SHALL ALSO BE POSSIBLE THROUGH STATUS
INDICATORS ELSEWHERE IN THE SAME FACILITY THROUGH A DEVICE THAT
REPLICATES THESE INDICATORS.
4.
THE UPS COMMUNICATION CAPABILITY SHOULD BE ABLE TO INTEGRATE INTO ANY
INDUSTRY STANDARD BUILDING MANAGEMENT SYSTEM (BMS) AND/OR NETWORK
MANAGEMENT SYSTEM (NMS). THE UPS MUST ALSO BE ABLE TO BE MONITORED
VIA ANY STANDARD INTERNET BROWSER (I.E. INTERNET EXPLORER AND
NETSCAPE).
5.
MAINTAINS POWER TO CRITICAL APPLICATIONS WHILE CHANGING INTERFACES).
C.
MICROPROCESSOR CONTROLLED CIRCUITRY: THE UPS CONTROLS SHALL HAVE THE
SHUTDOWN:
1.
D.
2.5 MECHANICAL DESIGN
THE CHARGER SHALL BE CAPABLE OF BEING CONFIGURED FOR SEVERAL
CHARGE MODES INCLUDING:
1)
B.
CONFIGURATIONS ARE NOT ACCEPTABLE.
BATTERY CHARGER CHARACTERISTICS: THE UPS BATTERY CHARGING SYSTEM
SHALL HAVE THE FOLLOWING CHARACTERISTICS:
a.
A.
UPS IN PARALLEL CONFIGURATIONS:
1.
RECTIFIER/CHARGER OUTPUT:
1.
2.7 COMMUNICATIONS
THERE SHALL BE A MECHANISM THAT PROVIDES GRACEFUL, ORDERLY,
UNATTENDED, SEQUENTIAL SHUTDOWN OF ONE OR MULTIPLE COMPUTERS
POWERED BY ONE UPS. THIS SHUTDOWN SHALL BE PERFORMED VIA IN-NETWORK
OR OUT-OF-NETWORK MEANS. THE ORDER OF SHUTDOWN SHALL BE
USER-DEFINED, ALLOWING THE MAXIMIZATION OF RUNTIME ON BATTERY FOR
MORE CRITICAL SYSTEMS.
2.
SHUTDOWN OF AS/400 COMPUTERS SHALL BE POSSIBLE THROUGH
OPEN-COLLECTOR RELAY CONTACTS OR ISOLATED, DRY CONTACT, FORM-C
RELAYS.
3.
THE UPS SHALL ALSO BE CAPABLE OF INTERFACING WITH AN OPERATING
SYSTEM'S BUILT-IN SHUTDOWN ROUTINE, E.G. WINDOWS NT. THIS SHALL BE DONE
THROUGH A CABLE CONNECTION TO THE OPTIONAL SERIAL PORT ON THE UPS.
b.
OBSERVE THE TYPE OF VENTILATION, THE CLEANLINESS OF THE ROOM, THE
USE OF PROPER SIGNS, AND ANY OTHER SAFETY RELATED FACTORS.
MECHANICAL INSPECTION:
a.
CHECK ALL THE POWER CONNECTIONS FOR TIGHTNESS.
b.
CHECK ALL THE CONTROL WIRING TERMINATIONS AND PLUGS FOR TIGHTNESS
OR PROPER SEATING.
ELECTRICAL PRE-CHECK:
a.
CHECK THE DC BUS FOR A POSSIBLE SHORT CIRCUIT.
b.
CHECK INPUT AND BYPASS POWER FOR PROPER VOLTAGES AND PHASE
ROTATION.
c.
CHECK ALL LAMP TEST FUNCTIONS.
717 Market Street
Suite 500
San Francisco, CA 94103
TEL
415.489.7240
FAX 415.489.7289
www.interfaceengineering.com
INITIAL UPS STARTUP:
b.
ENERGIZE THE UPS MODULE AND VERIFY THE PROPER DC, WALKUP, AND AC
PHASE ON.
c.
CHECK THE DC LINK HOLDING VOLTAGE, AC OUTPUT VOLTAGES, AND OUTPUT
WAVEFORMS.
d.
CHECK THE FINAL DC LINK VOLTAGE AND INVERTER AC OUTPUT. ADJUST IF
REQUIRED.
e.
CHECK FOR THE PROPER SYNCHRONIZATION.
f.
CHECK FOR THE VOLTAGE DIFFERENCE BETWEEN THE INVERTER OUTPUT
AND THE BYPASS SOURCE.
g.
OPTIONAL ON SITE FULL-LOAD, STEP-LOAD, AND BATTERY DISCHARGE TESTS
USING SUPPLIER FURNISHED LOAD BANK, SHALL ALSO BE OFFERED.
OPERATIONAL TRAINING: BEFORE LEAVING THE SITE, THE FIELD SERVICE
ENGINEER SHALL FAMILIARIZE RESPONSIBLE PERSONNEL WITH THE OPERATION
OF THE UPS. THE UPS EQUIPMENT SHALL BE AVAILABLE FOR DEMONSTRATION OF
THE MODES OF OPERATION.
ALL COMPONENTS OF THE UPS SYSTEM SHALL BE COVERED BY A STANDARD
ONE-YEAR LIMITED FACTORY WARRANTY AND SERVICE PROTECTION PACKAGE.
B.
ONE-YEAR LIMITED FACTORY WARRANTY SHALL INCLUDE REPLACEMENT COVERAGE
FOR THE UPS PARTS FOR A PERIOD OF 18 MONTHS FROM SHIPMENT OR 12 MONTHS
FROM START-UP, WHICHEVER OCCURS SOONER.
C.
ONE-YEAR SERVICE PROTECTION PACKAGE SHALL INCLUDE 7X24 ON-SITE
REPAIR/REPLACEMENT LABOR FOR UPS PARTS AND BATTERIES; 7X24 TECHNICAL
SUPPORT COVERAGE; AND 7X24 REMOTE MONITORING SERVICE (WITH MONTHLY
REPORTS FOR UPS AND BATTERY PERFORMANCE). STANDARD RESPONSE TIME SHALL
BE 8 HOURS FROM RECEIPT OF CALL. MANUFACTURER SHALL ALSO OFFER, AS AN
OPTION, 7X24 ON-SITE SERVICE SUPPORT WITH GUARANTEED RESPONSE TIMES OF 4,
OR 2 HOURS IN CERTAIN MAJOR METROPOLITAN AREAS. ADDITIONAL PREVENTIVE
MAINTENANCE VISITS SHALL BE AVAILABLE AS AN OPTION FOR BOTH UPS AND
BATTERY COMPONENTS.
D.
MANUFACTURER SHALL ALSO INCLUDE START-UP SERVICES CONSISTING OF: 5X8
START-UP SERVICE OF UPS AND BATTERIES, WITH OPTION FOR 7X24 START-UP.
ON-SITE USER TRAINING, SITE AUDIT, INSTALLATION AND COMMISSIONING OF
MONITORING SERVICE, AND VALIDATION OF ONE-YEAR LIMITED FACTORY WARRANTY
WILL BE PERFORMED DURING THE START-UP.
E.
MANUFACTURER SHALL ALSO OFFER AN OPTIONAL SERVICE PLAN TO PROVIDE 7X24
ON-SITE COVERAGE (PREVENTIVE AND CORRECTIVE) FOR UPS AND BATTERIES,
GUARANTEED RESPONSE TIME, REMOTE MONITORING, WEB ACCESS TO SERVICE SITE
HISTORY, ANNUAL SITE AUDIT, UPS AND BATTERY PREVENTIVE MAINTENANCE VISIT,
AND DISCOUNTS ON UPGRADE AND MODIFICATION KITS. MANUFACTURER SHALL ALSO
PROVIDE AN OPTIONAL BATTERY SERVICE PLAN TO PROVIDE PARTS-AND-LABOR
COVERAGE FOR PARTIAL AND FULL BATTERY STRINGS, EITHER WITH PREVENTIVE
MAINTENANCE OR REPLACEMENT COVERAGE.
TO ALL UNIT OPERATION INFORMATION.
11. EFFICIENCY: THE UPS EFFICIENCY SHALL GREATER THAN 99 PERCENT, OVER THE
RANGE OF 10 TO 100 PERCENT LOAD. (98.5 PERCENT FOR 208V UNITS)
BYPASS INPUT:
RS232 (EIA / TIA-232) COMMUNICATIONS INTERFACE: CIRCUITRY SHALL BE
PROVIDED FOR ONE RS232 (EIA / TIA-232) COMMUNICATION PORT FOR
CONNECTION TO AUTOMATED SERVICE DEPARTMENT DIAGNOSTIC TOOLS. THIS
VISUALLY INSPECT ALL EQUIPMENT FOR SIGNS OF DAMAGE OR FOREIGN
MATERIALS.
A.
OF SUPPLYING BOTH N/O AND N/C CONTACTS. CONTACT RATINGS SHALL BE 5A
MAX AT A VOLTAGE NOT TO EXCEED 28VDC OR 277VAC.
2.
a.
3.3 WARRANTY
ALARM CONTACT: A DRY CONTACT FOR ANNUNCIATING A SUMMARY ALARM SHALL
6.
ON GENERATOR INPUT CURRENT LIMIT: THE UPS SHALL HAVE THE FOLLOWING
PROGRAMMABLE INPUT CURRENT LIMIT SETTINGS WHILE OPERATING IN NORMAL
MODE ON GENERATOR:
1.
1.
UPS OUTPUT WITH ENERGY SAVER SYSTEM OPTION
2.
5.
INTERFACE PANEL: THE UPS SHALL BE EQUIPPED WITH AN INTERFACE PANEL,
LOCATED BEHIND A PROTECTIVE COVER, WHICH PROVIDES THE FOLLOWING SIGNALS
AND COMMUNICATION FEATURES IN A CLASS 2 ENVIRONMENT:
BATTERY CONTROL CONTACTS: CONTACTS SHALL BE PROVIDED TO CONNECT THE
BATTERY UVR AND AUXILIARY SIGNALS FROM A BATTERY BREAKER OR BATTERY
DISCONNECT SWITCH.
NORMAL INPUT CURRENT LIMIT: THE UPS SHALL HAVE THE FOLLOWING
PROGRAMMABLE INPUT CURRENT LIMIT SETTINGS WHILE OPERATING IN NORMAL
MODE:
POWER WALK-IN: RAMP-UP TO FULL UTILITY LOAD ADJUSTABLE FROM 3 SECONDS
TO 60 SECONDS.
RETURN: CONFIRMS SELECTION OR RETURNS TO PREVIOUS SCREEN.
5.
INPUT POWER FACTOR 0.99 LAGGING.
8.
5.
20. EFFICIENCY: THE UPS EFFICIENCY SHALL BE UP TO 94 PERCENT.
4.
INPUT CURRENT TOTAL HARMONIC DISTORTION (THD) SHALL BE LESS THAN 4.5
PERCENT.
SETUP: ALLOWS DISPLAY CONTRAST, DATE AND TIME INFORMATION SERIAL
COMMUNICATION PORT CONFIGURATION AND DISPLAY OF FIRMWARE REVISION
NUMBERS.
EXTERNAL EPO CONTACTS: SHALL BE PROVIDED TO CONNECT AN EXTERNAL
REMOTE EMERGENCY POWER OFF SWITCH TO SHUTDOWN THE UPS AND
DE-ENERGIZE THE CRITICAL LOAD.
5.
7.
4.
4.
10. ELECTROSTATIC DISCHARGE (ESD): THE UPS SHALL MEET IEC 801-2
SPECIFICATIONS. THE UPS SHALL WITHSTAND A 25 KV PULSE WITHOUT DAMAGE
AND WITH NO DISTURBANCE OR ADVERSE EFFECT TO THE CRITICAL LOAD.
BATTERY RECHARGE INPUT CURRENT LIMIT SHALL BE ADJUSTABLE FROM 10
PERCENT TO 15 PERCENT OF THE UPS FULL LOAD INPUT CURRENT
REGARDLESS OF THE ACTUAL LOAD ON THE UPS.
CONTROLS: DISPLAYS A SYSTEM CONTROLS SCREEN. ALLOWS SELECTION OF
OPERATING MODE, NORMAL, BYPASS, CHARGER ON/OFF AND POWER MODULE
ON/OFF.
19. ELECTROSTATIC DISCHARGE (ESD): THE UPS SHALL MEET IEC 801-2
SPECIFICATIONS. THE UPS SHALL WITHSTAND A 25 KV PULSE WITHOUT DAMAGE
AND WITH NO DISTURBANCE OR ADVERSE EFFECT TO THE CRITICAL LOAD.
FOR 60HZ SYSTEMS, OPERATING INPUT FREQUENCY RANGE SHALL BE 55 TO 65HZ.
G.
METERS: DISPLAYS PERFORMANCE METERS FOR THE SYSTEM OR CRITICAL LOAD.
WHEN SELECTED, THE FRONT DISPLAY SHALL SHOW INDIVIDUAL SCREENS OF
INPUT PARAMETERS, OUTPUT PARAMETERS OR BYPASS PARAMETERS INCLUDING;
VOLTAGE, CURRENT AND FREQUENCY. IN ADDITION, THE BATTERY DISPLAY SHALL
SHOW RUNTIME REMAINING.
VISUAL INSPECTION:
a.
EVENTS: DISPLAYS THE LIST OF ACTIVE SYSTEM EVENTS AND A HISTORICAL LOG
OF SYSTEM EVENTS. HISTORICAL LOGS SHALL INCLUDE A DETAILED TIME
STAMPED LIST OF THE LATEST 128 EVENTS.
3.
18. EMI SUPPRESSION: THE UPS SHALL MEET FCC RULES AND REGULATION 47, PART
15, FOR CLASS A DEVICES PRIOR TO FEB 16, 2006, CISPR .
3.
b.
E.
4.
ALARM: THIS SHALL INDICATE THAT THE UPS DETECTS AN ALARM CONDITION,
OUTLINED IN DETAIL IN THE OPERATOR'S MANUAL.
BUILDING ALARMS: TWO INPUTS SHALL BE PROVIDED FOR MONITORING THE
STATUS OF EXTERNAL DRY CONTACTS. BUILDING ALARMS SHALL BE SET UP
THROUGH THE UPS CONFIGURATION MODE FUNCTION ON THE RS232 (EIA / TIA-232)
PORT.
THE ENERGY SAVER SYSTEM ACTS TO OPTIMIZE THE INTERNAL COMPONENTS OF
THE UPS POWER TRAIN TO MAXIMIZE SYSTEM EFFICIENCY WHEN THE BYPASS
SOURCE IS WITHIN THE FOLLOWING (ADJUSTABLE) LIMITS: VOLTAGE: +/-10
PERCENT, AND FREQUENCY: +/-3HZ.
2.
NORMAL: THIS SHALL INDICATE THAT THE COMMERCIAL AC UTILITY OR
GENERATOR SOURCE IS SUPPLYING POWER TO THE RECTIFIER AND THE
INVERTER IS SUPPORTING THE CRITICAL LOAD. A TEXT MESSAGE SHALL INDICATE
IF THE BYPASS LINE IS NOT WITHIN TOLERANCE.
3.
9.
RECTIFIER/CHARGER INPUT CURRENT LIMIT SHALL BE ADJUSTABLE FROM 100
PERCENT TO 115 PERCENT OF FULL-LOAD INPUT CURRENT.
2.
17. ACOUSTICAL NOISE: NOISE GENERATED BY THE UPS UNDER NORMAL OPERATION
SHALL NOT EXCEED 65DBA AT ONE METER FROM ANY OPERATOR SURFACE,
MEASURED AT 25 DEGREES C (77 DEGREES F) AND FULL LOAD.
1.
THE FOLLOWING PROCEDURES AND TESTS SHALL BE PERFORMED BY FIELD SERVICE
PERSONNEL DURING THE UPS STARTUP:
CONTROL PANEL CONTROLS: THE UPS CONTROL PANEL SHALL PROVIDE THE
FOLLOWING FUNCTIONS FROM FRONT PANEL PUSH BUTTONS:
1.
16. COMMON MODE NOISE ATTENUATION:
OPERATING INPUT VOLTAGE RANGE: +10 PERCENT, -15 PERCENT OF AVERAGE
NOMINAL INPUT VOLTAGE WITHOUT BATTERY DISCHARGE.
a.
D.
15. STATIC TRANSFER TIME: NO BREAK, COMPLETED IN LESS THAN 4MS.
2.
BATTERY INPUT CURRENT LIMIT SHALL BE ADJUSTABLE FROM 10 PERCENT TO
15 PERCENT OF THE UPS FULL LOAD INPUT CURRENT REGARDLESS OF THE
ACTUAL LOAD ON THE UPS.
4.
14. FAULT CLEARING CURRENT CAPABILITY: 150 PERCENT PHASE-TO-PHASE FOR 10
CYCLES; 300 PERCENT PHASE-TO-NEUTRAL FOR UP TO 10 CYCLES
a.
POST-START-UP VISIT FOR ALARM NOTIFICATION CONFIGURATION, OPERATOR
TRAINING, GENERATOR TESTING, ETC.
CONTROL PANEL INDICATORS: THE UPS CONTROL PANEL SHALL PROVIDE THE
FOLLOWING MONITORING FUNCTIONS WITH INDICATOR LEDS:
3.
5.
2.
3.
C.
BYPASS: THIS SHALL INDICATE THAT THE UPS HAS TRANSFERRED THE LOAD TO
THE BYPASS CIRCUIT.
TRANSIENT VOLTAGE RECOVERY SHALL BE 25MS TO WITHIN +/- 1 PERCENT OF
STEADY STATE.
PRE-ENERGIZE VISIT TO INSPECT INSTALLATION AND PROVIDE GUIDANCE TO
INSTALLERS AS REQUIRED.
1.
DIGITAL FRONT PANEL DISPLAY: THE UPS CONTROL PANEL SHALL BE A DIGITAL FRONT
PANEL DISPLAY THAT FEATURES AN 8X40 (8 LINES, EACH WITH 40 CHARACTERS)
BACKLIT LCD DISPLAY. THE LCD SHALL DISPLAY UPS STATUS, METERING, BATTERY
STATUS, ALARM/EVENT QUEUE, ACTIVE ALARMS AND UPS CONFIGURATIONS. THE
FRONT PANEL DISPLAY SHALL SHOW A SYSTEM MIMIC DIAGRAM WITH AN OUTLINED
POWER PATH, CURRENT OPERATING MODE AND EVENT LOGS.
2.
4.
B.
1.
START-UP AND TRANSFERS SHALL BE AUTOMATIC FUNCTIONS.
STEADY-STATE VOLTAGE REGULATION (IN INVERTER) SHALL BE WITHIN +/- 1
PERCENT AVERAGE FROM NOMINAL OUTPUT VOLTAGE.
13. OVERLOAD CURRENT CAPABILITY (WITH NOMINAL LINE AND FULLY CHARGED
BATTERY): THE UNIT SHALL MAINTAIN VOLTAGE REGULATION FOR UP TO 110
PERCENT OF RESISTIVE/INDUCTIVE LOAD FOR 10 MINUTES, UP TO 125 PERCENT
FOR 30 SECONDS, AND UP TO 150 PERCENT FOR 10 SECONDS.
F.
ALL OPERATING AND PROTECTION PARAMETERS SHALL BE FIRMWARE
CONTROLLED, THUS ELIMINATING A NEED FOR MANUAL ADJUSTMENTS. THE LOGIC
SHALL INCLUDE SYSTEM TEST CAPABILITY TO FACILITATE MAINTENANCE AND
TROUBLESHOOTING. PRINTED CIRCUIT BOARD REPLACEMENT SHALL BE POSSIBLE
WITHOUT REQUIRING CALIBRATION.
2.
NOMINAL THREE PHASE INPUT VOLTAGE: 208 VAC: 3-WIRE PLUS GROUND FOR
3-WIRE PLUS GROUND OUTPUT CONFIGURATION.
b.
B.
12. PHASE VOLTAGE CONTROL:
RECTIFIER/CHARGER INPUT:
RECTIFIER/CHARGER INPUT CURRENT LIMIT SHALL BE ADJUSTABLE FROM 100
TO 115 PERCENT OF FULL-LOAD INPUT CURRENT.
3.
11. PHASE ANGLE CONTROL:
UPS RATING (MAX) IS THE MAXIMUM OUTPUT POSSIBLE FROM THE UPS (FOR A
LOAD POWER FACTOR RANGE OF 0.9 LAGGING TO 0.9 LEADING). THE UPS SHALL
NOT REQUIRE DE-RATING WHEN SUPPORTING A LEADING POWER FACTOR LOAD
OF 0.9 OR GREATER. THE UPS MAY BE ORDERED WITH ANY OF THE THREE (3)
OPTIONAL RATINGS (WHERE AVAILABLE) AND LATER UPGRADED TO ITS
CORRESPONDING FULL UPS RATING (MAX).
a.
2.
THE UPS MODULE SHALL AUTOMATICALLY ADJUST THE FINAL DISCHARGE
VOLTAGE BETWEEN 1.67 AND 1.75 VOLTS PER CELL BASED ON THE
EXISTING LOAD AND THE RATE AND LENGTH OF DISCHARGE.
1.
6.
C.
c)
10. FREQUENCY SLEW RATE SHALL BE 1 HZ/SECOND MAXIMUM (ADJUSTABLE).
UPS RATING (MAX)OPTIONAL RATING (1)OPTIONAL RATING (2) OPTIONAL RATING (3)
40KVA/36KW30KVA/27KW20KVA/18KWN/A 80KVA/72KW60KVA/54KW50KVA/45KW40KVA/
36KW120KVA/108KW100KVA/90KWN/AN/A 160KVA/144KW120KVA/108KW100KVA/90KWN/A
B.
EQUALIZING VOLTAGE: 2.38 V MAXIMUM PER CELL (ADJUSTABLE).
FULLY AUTOMATIC OPERATION OF THE UPS SHALL BE PROVIDED THROUGH THE
USE OF MICROPROCESSOR CONTROLLED DIGITAL SIGNAL PROCESSING. DSP
SHALL ELIMINATE VARIANCES FROM COMPONENT TOLERANCE OR DRIFT, AND
PROVIDE CONSISTENT OPERATIONAL RESPONSES.
1.
UPS CONTINUOUS RATINGS. THE UPS SHALL BE RATED:
1.
NOMINAL FLOAT VOLTAGE: 2.25 V PER CELL.
1.
NOMINAL OUTPUT VOLTAGE 208 VAC, 3-PHASE, 4-WIRE PLUS GROUND AT THE
OUTPUT OF THE INTEGRATED DISTRIBUTION AND BYPASS CABINET. OUTPUT
WIRING CONFIGURATION IS BASED UPON INPUT WIRING CONFIGURATION FOR
SYSTEMS WITHOUT INTERNAL TRANSFORMERS.
2.4 UNINTERRUPTIBLE POWER SUPPLY RATINGS AND OPERATING CHARACTERISTICS
A.
a)
b)
UPS OUTPUT IN NORMAL MODE
1.
FOLLOWING DESIGN AND OPERATING CHARACTERISTICS:
A CHARGING MODE FLOATING THE BATTERY AT A SET LEVEL, WHICH CAN
BE ADJUSTED VIA SOFTWARE, USED FOR FLOODED CELL APPLICATIONS
UPS MODULE WILL AUTOMATICALLY ADJUST BATTERY SHUTDOWN BASED
UPON LOADING AND BATTERY CAPACITY.
1)
2.3 UPS MODULE OPTIONS AND ACCESSORIES
1.6 ENVIRONMENTAL REQUIREMENTS
SECTION 26 3353 - STATIC UNINTERRUPTIBLE POWER SUPPLY
S SUITABLE FOR ISOLATING
ELOW. NOTIFY ARCHITECT
USE MANUFACTURER'S PUBLISHED TESTING AND ADJUSTING PROCEDURES TO
ADJUST SENSORS TIME DELAY, DAYLIGHT SENSITIVITY, AND PASSIVE INFRARED
SENSITIVITY TO SATISFACTION OF THE OWNER.
G. FOCUS AND ADJUST FLOODLIGHTS, SPOTLIGHTS AND OTHER ADJUSTABLE
LUMINAIRES, WITH ARCHITECT, AT SUCH TIME OF DAY OR NIGHT AS REQUIRED. ALIGN
LUMINAIRES THAT ARE NOT STRAIGHT AND PARALLEL/PERPENDICULAR TO
STRUCTURE. POSITION EXIT SIGN DIRECTIONAL ARROWS AS INDICATED.
H.
SERVICE ENGINEERS DEDICATED TO STARTUP, MAINTENANCE, AND REPAIR OF UPS
EQUIPMENT. THE ORGANIZATION SHALL CONSIST OF LOCAL OFFICES MANAGED FROM
A CENTRAL LOCATION. FIELD ENGINEERS SHALL BE DEPLOYED IN KEY POPULATION
AREAS TO PROVIDE ON-SITE EMERGENCY RESPONSE WITHIN 24 HOURS. A MAP OF
THE UNITED STATES SHOWING THE LOCATION OF ALL FIELD SERVICE OFFICES MUST
BE SUBMITTED WITH THE PROPOSAL. THIRD-PARTY MAINTENANCE WILL NOT BE
ACCEPTED.
WIRING DEVICE TESTS: TEST WIRING DEVICES TO ENSURE ELECTRICAL CONTINUITY
OF GROUNDING CONNECTIONS, AND AFTER ENERGIZING CIRCUITRY, TO
DEMONSTRATE COMPLIANCE WITH REQUIREMENTS. TEST RECEPTACLES FOR LINE TO
NEUTRAL, LINE TO GROUND AND NEUTRAL TO GROUND FAULTS. CORRECT DEFECTIVE
WIRING.
END OF ELECTRICAL SPECIFICATIONS
1111 Jackson Street
Oakland, California
T GROUNDING SYSTEM TO
E.
JACKSON CENTER ONE
NELS, VISIBLE WHEN DOOR
SHEET TITLE
SPECIFICATION ELECTRICAL
NOTIFICATION:
1.
THERE SHALL BE A MECHANISM TO SEND ALERTS TO KEY PERSONNEL VIA EMAIL
OR SNMP TRAPS. AN ALARM NOTIFICATION MAY ALSO BE SENT BY A NETWORK
MESSAGE.
2.
DIAL-OUT TO A COMPUTER FOR ALARM NOTIFICATION MAY BE PERFORMED. THE
USER MAY RESPOND BY DIALING-IN TO RETRIEVE ALARM HISTORY AND A
SUMMARY OF CURRENT METER STATUS.
3.
MANAGEMENT: A REMOTE BATTERY TEST MAY BE PERFORMED VIA AN ETHERNET
NETWORK. THE UPS SHALL BE TESTED THROUGH INVOKING A SINGLE COMMAND.
REVISIONS
2.8 UPS MODULE PROTECTION
A.
RECTIFIER/CHARGER AND BYPASS PROTECTION SHALL BE PROVIDED THROUGH
INDIVIDUAL FUSING OF EACH PHASE.
B.
BATTERY PROTECTION SHALL BE PROVIDED BY THERMAL-MAGNETIC MOLDED-CASE
CIRCUIT BREAKERS IN EACH BATTERY CABINET (IF STANDARD BATTERY PACK IS
PROVIDED) OR EXTERNAL PROTECTIVE DEVICE FOR AN EXTERNAL BATTERY.
DRAWN BY
C.
ELECTRONIC CURRENT LIMITING CIRCUITRY AND FUSES IN THE INVERTER CIRCUIT
SHALL PROVIDE OUTPUT PROTECTION.
CHECKED BY
D.
TO COMPLY WITH AGENCY SAFETY REQUIREMENTS, THE UPS MODULE SHALL NOT
RELY UPON ANY DISCONNECT DEVICES OUTSIDE OF THE UPS MODULE TO ISOLATE
THE BATTERY CABINET FROM THE UPS MODULE.
PART 3 -
CR
Kevin Kuang
JOB NO.
2014-0284
EXECUTION
DATE
3.1 INSTALLATION
A.
DATE
INSTALL IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.
SHEET NUMBER
3.2 COMMISSIONING
A.
FACTORY START-UP SHALL BE PROVIDED ON A 5X8 BASIS (7 X 24 OPTIONAL).
START-UP SERVICE SHALL BE PROVIDED AT NO EXTRA CHARGE AND SHALL INCLUDE
ONE VISIT TO PERFORM ALL PROCEDURES AND TESTS SPECIFIED WITHIN UPS
INSTALLATION AND OPERATION MANUAL. UPS MANUFACTURER SHALL ALSO OFFER
THE FOLLOWING OPTIONAL SERVICES:
E6.1
1.01 SECTION INCLUDES
A. WORK INCLUDED IN 27 00 00, COMMUNICATIONS BASIC REQUIREMENTS APPLIES TO DIVISION 27, COMMUNICATIONS WORK TO
PROVIDE MATERIALS, LABOR, TOOLS, PERMITS, INCIDENTALS, AND OTHER SERVICES TO PROVIDE AND MAKE READY FOR OWNER'S USE
OF COMMUNICATIONS SYSTEMS FOR PROPOSED PROJECT.
B. CONTRACT DOCUMENTS INCLUDE, BUT ARE NOT LIMITED TO, SPECIFICATIONS INCLUDING DIVISION 00, PROCUREMENT AND
CONTRACTING REQUIREMENTS AND DIVISION 01, GENERAL REQUIREMENTS, DRAWINGS, ADDENDA, OWNER/ARCHITECT AGREEMENT,
AND OWNER/CONTRACTOR AGREEMENT. CONFIRM REQUIREMENTS BEFORE COMMENCEMENT OF WORK.
C. DEFINITIONS:
1. PROVIDE: TO FURNISH AND INSTALL, COMPLETE AND READY FOR INTENDED USE.
2. FURNISH: SUPPLY AND DELIVER TO PROJECT SITE, READY FOR UNPACKING, ASSEMBLY AND INSTALLATION.
3. INSTALL: INCLUDES UNLOADING, UNPACKING, ASSEMBLING, ERECTING, INSTALLATION, APPLYING, FINISHING, PROTECTING, CLEANING
AND SIMILAR OPERATIONS AT PROJECT SITE AS REQUIRED TO COMPLETE ITEMS OF WORK FURNISHED.
4. APPROVED OR APPROVED EQUIVALENT: TO POSSESS THE SAME PERFORMANCE QUALITIES AND CHARACTERISTICS AND FULFILL THE
UTILITARIAN FUNCTION WITHOUT ANY DECREASE IN QUALITY, DURABILITY OR LONGEVITY. FOR EQUIPMENT/PRODUCTS DEFINED BY THE
CONTRACTOR AS "EQUIVALENT," SUBSTITUTION REQUESTS MUST BE SUBMITTED TO ENGINEER FOR CONSIDERATION, IN ACCORDANCE
WITH DIVISION 01, GENERAL REQUIREMENTS, AND APPROVED BY THE ENGINEER PRIOR TO SUBMITTING BIDS FOR
SUBSTITUTED ITEMS.
5. AUTHORITY HAVING JURISDICTION (AHJ): INDICATES REVIEWING AUTHORITIES, INCLUDING LOCAL FIRE MARSHAL, OWNER'S
INSURANCE UNDERWRITER, OWNER'S REPRESENTATIVE, AND OTHER REVIEWING ENTITY WHOSE APPROVAL IS REQUIRED TO OBTAIN
SYSTEMS ACCEPTANCE.
6. ENTRANCE FACILITY (EF): AREA OR LOCATION THAT CONTAINS ENTRANCE POINT (DEMARCATION) CABLE AND ASSOCIATED
EQUIPMENT FOR TELECOMMUNICATION SERVICES ENTERING THE BUILDING.
7. EQUIPMENT ROOM (ER): AREA OR LOCATION THAT CONTAINS BACKBONE CABLING ASSOCIATED WITH INTERBUILDING CABLE OR
CABLE THAT CONNECTS BUILDINGS TOGETHER IN A CAMPUS ENVIRONMENT. ERS MAY CONTAIN MAIN CROSS-CONNECTS,
INTERMEDIATE CROSS-CONNECTS, HORIZONTAL CROSS-CONNECTS, AND TELECOMMUNICATION ROOMS.
8. MAIN CROSS-CONNECT (MC): AREA OR LOCATION THAT CONTAINS TELECOMMUNICATIONS EQUIPMENT FOR CONNECTING BACKBONE
CABLE TO/FROM INTERMEDIATE CROSS-CONNECTS AND HORIZONTAL CROSS-CONNECTS. ACTIVE TELECOMMUNICATIONS EQUIPMENT
WILL OFTEN BE CONTAINED IN THIS AREA TO SERVE AS THE TELECOMMUNICATIONS HUB OR HEADEND. BACKBONE CABLE FROM LOCAL
EXCHANGE CARRIER'S POINT OF DEMARCATION WILL CONNECT TO BUILDING BACKBONE CABLE OR ACTIVE TELECOMMUNICATIONS
EQUIPMENT AT THIS LOCATION.
9. INTERMEDIATE CROSS-CONNECT (IC): AREA OR LOCATION THAT CONTAINS TELECOMMUNICATIONS EQUIPMENT FOR CONNECTING
BACKBONE CABLE FROM THE MC TO BACKBONE CABLE DISTRIBUTING TO ONE OR MANY HORIZONTAL CROSS-CONNECTS. THIS
LOCATION MAY CONTAIN ACTIVE TELECOMMUNICATIONS EQUIPMENT.
10. HORIZONTAL CROSS-CONNECT (HC): AREA OR LOCATION THAT CONTAINS TELECOMMUNICATIONS EQUIPMENT, CABLE
TERMINATIONS AND CROSS-CONNECT WIRING. HC IS THE RECOGNIZED CONNECTION POINT BETWEEN BACKBONE AND HORIZONTAL
PATHWAY FACILITIES.
11. TELECOMMUNICATIONS ROOM (TR): AREA OR LOCATION CONTAINING TELECOMMUNICATIONS EQUIPMENT, CABLE TERMINATIONS
AND CROSS-CONNECT WIRING. THREE APPLICATIONS SERVICED BY TRS ARE HORIZONTAL CABLE CONNECTIONS, BACKBONE SYSTEM
INTERCONNECTION AND ENTRANCE FACILITIES. THE TR PROVIDES FACILITIES (SPACE, POWER, GROUNDING, ETC.) FOR HOUSING
TELECOMMUNICATIONS EQUIPMENT. TR MAY CONTAIN A MC, IC OR HC AND A DEMARCATION POINT OR AN INTERBUILDING ENTRANCE
FACILITY.
12. INTERBUILDING CABLE: BACKBONE CABLE ASSOCIATED WITH CONNECTING BUILDINGS TOGETHER IN A MULTIBUILDING OR CAMPUS
ENVIRONMENT.
13. Intrabuilding Cable: Backbone cable associated with connecting Entrance Facility, Equipment Rooms, Main Cross-Connects, Intermediate
Cross-Connects, Horizontal Cross-Connects, and Telecommunication Rooms together on single floor or multifloor
building.
1.02 RELATED SECTIONS
A. CONTENTS OF SECTION APPLIES TO DIVISION 27, COMMUNICATIONS CONTRACT DOCUMENTS.
B. RELATED WORK:
1. ADDITIONAL CONDITIONS APPLY TO THIS DIVISION INCLUDING, BUT NOT LIMITED TO:
A. SPECIFICATIONS INCLUDING DIVISION 00, PROCUREMENT AND CONTRACTING REQUIREMENTS AND DIVISION 01, GENERAL
REQUIREMENTS.
B. DRAWINGS
C. ADDENDA
D. OWNER/ARCHITECT AGREEMENT
E. OWNER/CONTRACTOR AGREEMENT
F. CODES, STANDARDS, PUBLIC ORDINANCES AND PERMITS
C. RELATED PRODUCTS/SYSTEMS WITHIN DIVISION 28, ELECTRONIC SAFETY AND SECURITY:
1. SECTION 28 10 00, ACCESS CONTROL AND INTRUSION DETECTION
2. SECTION 28 23 00, VIDEO SURVEILLANCE
1.03 REFERENCES AND STANDARDS
A. REFERENCES AND STANDARDS PER DIVISION 00, PROCUREMENT AND CONTRACTING REQUIREMENTS AND
DIVISION 01, GENERAL REQUIREMENTS, INDIVIDUAL DIVISION 27, COMMUNICATIONS SECTIONS AND THOSE
LISTED IN THIS SECTION.
B. CODES TO INCLUDE LATEST ADOPTED EDITIONS, INCLUDING CURRENT AMENDMENTS, SUPPLEMENTS AND LOCAL
JURISDICTION REQUIREMENTS IN EFFECT AS OF THE DATE OF THE CONTRACT DOCUMENTS, OF/FROM:
1. STATE OF CALIFORNIA:
A. CBC CALIFORNIA BUILDING CODE
B. CEC CALIFORNIA ELECTRICAL CODE
C. CEC T24 CALIFORNIA ENERGY CODE TITLE 24
D. CFC CALIFORNIA FIRE CODE
E. CMC CALIFORNIA MECHANICAL CODE
F. CPC CALIFORNIA PLUMBING CODE
G. CSFM CALIFORNIA STATE FIRE MARSHAL
H. DSA DIVISION OF STATE ARCHITECT REGULATIONS AND REQUIREMENTS
I. OSHPD OFFICE OF STATEWIDE HEALTH PLANNING & DEVELOPMENT
C. REFERENCE STANDARDS AND GUIDELINES INCLUDE BUT ARE NOT LIMITED TO THE LATEST ADOPTED EDITIONS
FROM:
1. ABA ARCHITECTURAL BARRIERS ACT
2. ADA AMERICANS WITH DISABILITIES ACT
3. ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
4. ANSI/TIA-568-C.0 GENERIC TELECOMMUNICATIONS CABLING FOR CUSTOMER PREMISES
5. ANSI/TIA-568-C.1 COMMERCIAL BUILDING TELECOMMUNICATIONS CABLING STANDARD
6. ANSI/TIA-568-C.2 BALANCED TWISTED-PAIR TELECOMMUNICATIONS CABLING AND COMPONENTS STANDARD
7. ANSI/TIA-568-C.3 OPTICAL FIBER CABLING COMPONENTS STANDARD. COMMERCIAL BUILDING TELECOMMUNICATING CABLING
STANDARD
8. ANSI/TIA-569-B COMMERCIAL BUILDING STANDARD FOR TELECOMMUNICATIONS PATHWAYS AND SPACES
9. ANSI/TIA-570-B RESIDENTIAL TELECOMMUNICATIONS INFRASTRUCTURE
10. ANSI/TIA-942 TELECOMMUNICATIONS INFRASTRUCTURE STANDARD FOR DATA CENTERS
11. ANSI/TIA/EIA-606-A ADMINISTRATION STANDARD FOR COMMERCIAL TELECOMMUNICATIONS INFRASTRUCTURE
12. ANSI-J-STD-607-A Commercial Building Grounding (Earthing) and Bonding Requirements for Telecommunications
13. APWA AMERICAN PUBLIC WORKS ASSOCIATION
14. ASCE AMERICAN SOCIETY OF CIVIL ENGINEERS
15. ASHRAE GUIDELINE 0, THE COMMISSIONING PROCESS
16. ASTM ASTM INTERNATIONAL
17. BICSI BUILDING INDUSTRY CONSULTING SERVICE INTERNATIONAL
18. BICSI TDMM TELECOMMUNICATIONS DISTRIBUTION METHODS MANUAL
19. BICSI ESSDRM ELECTRONIC SAFETY & SECURITY DESIGN REFERENCE MANUAL
20. BICSI AVDRM AV DESIGN REFERENCE MANUAL
21. CFR CODE OF FEDERAL REGULATIONS
22. CSA CSA INTERNATIONAL
23. EIA ELECTRONIC INDUSTRIES ASSOCIATION
24. EPA ENVIRONMENTAL PROTECTION AGENCY
25. ETL ELECTRICAL TESTING LABORATORIES
26. FCC FEDERAL COMMUNICATIONS DIVISION
27. FDA FOOD & DRUG ADMINISTRATION
28. FM FM GLOBAL
29. IBC INTERNATIONAL BUILDING CODE
30. IEC INTERNATIONAL ELECTROTECHNICAL COMMISSION
31. IEEE INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS
32. ISO INTERNATIONAL ORGANIZATION FOR STANDARDIZATION
33. LEED LEADERSHIP IN ENERGY AND ENVIRONMENTAL DESIGN
34. MSS MANUFACTURERS STANDARDIZATION SOCIETY
35. NEC NATIONAL ELECTRIC CODE
36. NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION
37. OSHA OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION
38. TIA TELECOMMUNICATIONS INDUSTRY ASSOCIATION
39. UBC UNIFORM BUILDING CODE
40. UL UNDERWRITERS LABORATORIES INC.
41. USDA UNITED STATES DEPARTMENT OF AGRICULTURE
D. SEE DIVISION 27, COMMUNICATIONS INDIVIDUAL SECTIONS FOR ADDITIONAL REFERENCES.
E. WHERE CODE REQUIREMENTS ARE AT VARIANCE WITH CONTRACT DOCUMENTS, MEET CODE REQUIREMENTS AS A MINIMUM
REQUIREMENT AND INCLUDE COSTS NECESSARY TO MEET THESE IN CONTRACT. MACHINERY AND EQUIPMENT ARE TO COMPLY WITH
OSHA REQUIREMENTS, AS CURRENTLY REVISED AND INTERPRETED FOR EQUIPMENT MANUFACTURER REQUIREMENTS. INSTALL
EQUIPMENT PROVIDED PER MANUFACTURER RECOMMENDATIONS.
F. WHENEVER THIS SPECIFICATION CALLS FOR MATERIAL, WORKMANSHIP, ARRANGEMENT OR CONSTRUCTION OF HIGHER QUALITY
AND/OR CAPACITY THAN THAT REQUIRED BY GOVERNING CODES, HIGHER QUALITY AND/OR CAPACITY TAKE PRECEDENCE.
G. MAXIMUM OF TWO REVIEWS OF COMPLETE SUBMITTAL PACKAGE. ARRANGE FOR ADDITIONAL REVIEWS AND/OR EARLY REVIEW OF
LONG-LEAD ITEMS; BEAR COSTS OF ADDITIONAL REVIEWS AT ENGINEER'S HOURLY RATES. INCOMPLETE SUBMITTAL
PACKAGES/SUBMITTALS WILL BE RETURNED TO CONTRACTOR WITHOUT REVIEW.
H. STRUCTURAL/SEISMIC: PROVIDE WEIGHTS, DIMENSIONS, MOUNTING REQUIREMENTS AND LIKE INFORMATION REQUIRED FOR
MOUNTING, SEISMIC BRACING, AND SUPPORT. INDICATE MANUFACTURER'S INSTALLATION AND SUPPORT REQUIREMENTS TO MEET
ASCE 7-10 REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS PROVIDE ENGINEERED SEISMIC DRAWINGS AND EQUIPMENT SEISMIC
CERTIFICATION. EQUIPMENT IMPORTANCE FACTOR AS SPECIFIED IN PART 3 OF THIS SECTION.
I. TRADE COORDINATION: INCLUDE PHYSICAL CHARACTERISTICS, ELECTRICAL CHARACTERISTICS, DEVICE LAYOUT PLANS, WIRING
DIAGRAMS, AND CONNECTIONS AS REQUIRED PER DIVISION 27, COMMUNICATIONS COORDINATION DOCUMENTS. FOR EQUIPMENT WITH
ELECTRICAL CONNECTIONS, FURNISH COPY OF APPROVED SUBMITTAL FOR INCLUSION IN DIVISION 26, ELECTRICAL SUBMITTALS.
J. MAKE PROVISIONS FOR OPENINGS IN BUILDING FOR ADMITTANCE OF EQUIPMENT PRIOR TO START OF CONSTRUCTION OR ORDERING
OF EQUIPMENT.
B. PROVIDE DRAWINGS IN FORMAT AND SOFTWARE RELEASE EQUAL TO THE DESIGN DOCUMENTS. DRAWINGS TO BE THE SAME SHEET
SIZE AND SCALE AS THE CONTRACT DOCUMENTS.
C. "NO EXCEPTION TAKEN" CONSTITUTES THAT REVIEW IS FOR GENERAL CONFORMANCE WITH THE DESIGN CONCEPT EXPRESSED IN
THE CONTRACT DOCUMENTS FOR THE LIMITED PURPOSE OF CHECKING FOR CONFORMANCE WITH INFORMATION GIVEN. ANY ACTION IS
SUBJECT TO THE REQUIREMENTS OF THE CONTRACT DOCUMENTS. CONTRACTOR IS RESPONSIBLE FOR THE DIMENSIONS AND
QUANTITY AND WILL CONFIRM AND CORRELATE AT THE JOB SITE, FABRICATION PROCESSES AND TECHNIQUES OF CONSTRUCTION,
COORDINATION OF THE WORK WITH THAT OF ALL OTHER TRADES, AND THE SATISFACTORY PERFORMANCE OF THE WORK.
D. PROVIDE PRODUCT SUBMITTALS AND SHOP DRAWINGS IN ELECTRONIC FORMAT ONLY. ELECTRONIC FORMAT MUST BE SUBMITTED
VIA ZIP FILE VIA E-MAIL. FOR ELECTRONIC FORMAT, PROVIDE ONE ZIP FILE PER SPECIFICATION DIVISION CONTAINING A SEPARATE FILE
FOR EACH SPECIFICATION SECTION. INDIVIDUAL SUBMITTALS SENT PIECEMEAL IN A PER SPECIFICATION SECTION METHOD WILL BE
RETURNED WITHOUT REVIEW OR COMMENT. COPY ARCHITECT ON ALL TRANSMISSIONS/SUBMISSIONS.
E. PRODUCT DATA: PROVIDE MANUFACTURER'S DESCRIPTIVE LITERATURE FOR PRODUCTS SPECIFIED IN DIVISION 27,
COMMUNICATIONS SECTIONS.
2.01 MANUFACTURERS
3.06 EQUIPMENT SELECTION AND SERVICEABILITY
A. PROVIDE LIKE ITEMS FROM ONE MANUFACTURER, INCLUDING BUT NOT LIMITED TO JACKS, PATCH PANELS, EQUIPMENT CONNECTION
CORDS AND WALL PLATES.
A. REPLACE OR REPOSITION EQUIPMENT WHICH IS TOO LARGE OR LOCATED INCORRECTLY TO PERMIT SERVICING, AT NO ADDITIONAL
COST TO OWNER.
2.02 MATERIALS
A. BASE CONTRACT UPON FURNISHING MATERIALS AS SPECIFIED. MATERIALS, EQUIPMENT, AND FIXTURES USED FOR CONSTRUCTION
ARE TO BE NEW, LATEST PRODUCTS AS LISTED IN MANUFACTURER'S PRINTED CATALOG DATA AND ARE TO BE UL, ETL, OR CSA
APPROVED OR HAVE ADEQUATE APPROVAL OR BE ACCEPTABLE BY STATE, COUNTY, AND CITY AUTHORITIES. EQUIPMENT/FIXTURE
SUPPLIER IS RESPONSIBLE FOR OBTAINING STATE, COUNTY, AND CITY ACCEPTANCE ON EQUIPMENT/FIXTURE NOT UL OR CSA
APPROVED OR NOT LISTED FOR INSTALLATION.
3.07 DELIVERY, STORAGE AND HANDLING
B. ARTICLES, FIXTURES, AND EQUIPMENT OF A KIND TO BE STANDARD PRODUCT OF ONE MANUFACTURER.
C. NAMES AND MANUFACTURER'S NAMES DENOTE CHARACTER AND QUALITY OF EQUIPMENT DESIRED AND ARE NOT TO BE CONSTRUED
AS LIMITING COMPETITION.
D. HAZARDOUS MATERIALS:
1. COMPLY WITH LOCAL, STATE OF CALIFORNIA, AND FEDERAL REGULATIONS RELATING TO HAZARDOUS MATERIALS.
2. COMPLY WITH DIVISION 00, PROCUREMENT AND CONTRACTING REQUIREMENTS AND DIVISION 01, GENERAL REQUIREMENTS FOR THIS
PROJECT RELATING TO HAZARDOUS MATERIALS.
3. DO NOT USE ANY MATERIALS CONTAINING A HAZARDOUS SUBSTANCE. IF HAZARDOUS MATERIALS ARE ENCOUNTERED, DO NOT
DISTURB; IMMEDIATELY NOTIFY OWNER AND ARCHITECT. HAZARDOUS MATERIALS WILL BE REMOVED BY OWNER UNDER SEPARATE
CONTRACT.
2.03 ACCESS PANELS
K. SUBSTITUTIONS AND VARIATION FROM BASIS OF DESIGN:
1. THE BASIS OF DESIGN DESIGNATED PRODUCT ESTABLISHES THE QUALITIES AND CHARACTERISTICS FOR THE EVALUATION OF ANY
COMPARABLE PRODUCTS BY OTHER LISTED ACCEPTABLE MANUFACTURERS IF INCLUDED IN THIS SPECIFICATION OR INCLUDED IN AN
APPROVED SUBSTITUTION REQUEST AS JUDGED BY THE DESIGN PROFESSIONAL.
2. IF SUBSTITUTIONS AND/OR EQUIVALENT EQUIPMENT/PRODUCTS ARE BEING PROPOSED, IT IS THE RESPONSIBILITY OF PARTIES
CONCERNED, INVOLVED IN, AND FURNISHING THE SUBSTITUTE AND/OR EQUIVALENT EQUIPMENT TO VERIFY AND COMPARE THE
CHARACTERISTICS AND REQUIREMENTS OF THAT FURNISHED TO THAT SPECIFIED AND/OR SHOWN. IF GREATER CAPACITY AND/OR
MORE MATERIALS AND/OR MORE LABOR IS REQUIRED FOR THE ROUGH-IN, CIRCUITRY OR CONNECTIONS THAN FOR THE ITEM SPECIFIED
AND PROVIDED FOR, THEN PROVIDE COMPENSATION FOR ADDITIONAL CHARGES REQUIRED FOR THE PROPER ROUGH-IN, CIRCUITRY
AND CONNECTIONS FOR THE EQUIPMENT BEING FURNISHED. NO ADDITIONAL CHARGES ABOVE THE BASE BID WILL BE ALLOWED FOR
SUCH REVISIONS. COORDINATE WITH THE REQUIREMENTS OF "SUBMITTALS." FOR ANY PRODUCT MARKED "OR APPROVED
EQUIVALENT," A SUBSTITUTION REQUEST MUST BE SUBMITTED TO ENGINEER FOR APPROVAL PRIOR TO PURCHASE, DELIVERY OR
INSTALLATION.
L. SHOP DRAWINGS:
1. PROVIDE COORDINATED SHOP DRAWINGS WHICH INCLUDE PHYSICAL CHARACTERISTICS OF ALL SYSTEMS, DEVICE LAYOUT PLANS,
AND CONTROL WIRING DIAGRAMS. REFERENCE INDIVIDUAL DIVISION 27, COMMUNICATIONS SPECIFICATION SECTIONS FOR ADDITIONAL
REQUIREMENTS FOR SHOP DRAWINGS OUTSIDE OF THESE REQUIREMENTS.
2. PROVIDE SHOP DRAWINGS INDICATING ACCESS PANEL LOCATIONS, SIZE AND ELEVATION FOR APPROVAL
PRIOR TO INSTALLATION.
A. SEE DIVISION 01, GENERAL REQUIREMENTS AND DIVISION 08, OPENINGS FOR PRODUCTS AND INSTALLATION REQUIREMENTS.
B. CONFIRM ACCESS PANEL REQUIREMENTS IN DIVISION 01, GENERAL REQUIREMENTS AND 08. IN ABSENCE OF SPECIFIC
REQUIREMENTS, COMPLY WITH INDIVIDUAL DIVISION 27, COMMUNICATIONS SECTIONS AND THE FOLLOWING:
1. PROVIDE FLUSH MOUNTING ACCESS PANELS FOR SERVICE OF SYSTEMS, EQUIPMENT AND INDIVIDUAL COMPONENTS REQUIRING
MAINTENANCE OR INSPECTION. WHERE ACCESS PANELS ARE LOCATED IN FIRE-RATED ASSEMBLIES OF BUILDING, RATE ACCESS
PANELS ACCORDINGLY.
A. CEILING ACCESS PANELS TO BE MINIMUM OF 24-INCH BY 24-INCH REQUIRED AND APPROVED SIZE.
B. WALL ACCESS PANELS TO BE MINIMUM OF 12-INCH BY 12-INCH REQUIRED AND APPROVED SIZE.
C. PROVIDE SCREWDRIVER OPERATED CATCH.
D. MANUFACTURERS AND MODELS:
1) DRYWALL: KARP KDW.
2) PLASTER: KARP DSC-214PL.
3) MASONRY: KARP DSC-214M.
4) 2 HOUR RATED: KARP KPF-350FR.
5) MANUFACTURERS: KARP, MILCOR, ELMDOR, ACUDOR, OR APPROVED EQUIVALENT.
N. RESUBMISSION REQUIREMENTS:
1. MAKE ANY CORRECTIONS OR CHANGE IN SUBMITTALS WHEN REQUIRED. PROVIDE SUBMITTALS AS SPECIFIED. THE ENGINEER WILL
NOT BE REQUIRED TO EDIT AND/OR INTERPRET THE CONTRACTOR'S SUBMITTALS. CHANGES MADE FOR THE RESUBMITTAL WILL BE
INDICATED IN A COVER LETTER WITH REFERENCE TO PAGE(S) CHANGED AND WILL REFERENCE RESPONSE TO COMMENT. INDICATE
CHANGES FOR THE RESUBMITTAL IN A COVER LETTER WITH REFERENCE TO PAGE(S) CHANGED AND REFERENCE
RESPONSE TO COMMENT. CLOUD CHANGES IN THE SUBMITTALS.
2. RESUBMIT FOR REVIEW UNTIL REVIEW INDICATES NO EXCEPTIONS TAKEN, OR "MAKE CORRECTIONS AS NOTED."
3. WHEN SUBMITTING DRAWINGS FOR ENGINEERS RE-REVIEW, CLEARLY INDICATE CHANGES ON DRAWINGS AND "CLOUD" ANY
REVISIONS. SUBMIT A LIST DESCRIBING EACH CHANGE.
O. OPERATION AND MAINTENANCE MANUALS, OWNERS INSTRUCTIONS:
1. SUBMIT, AT ONE TIME, ELECTRONIC FILES (PDF FORMAT) ON CD/DVD OF MANUFACTURER'S OPERATION AND MAINTENANCE
INSTRUCTION MANUALS AND PARTS LISTS FOR EQUIPMENT OR ITEMS REQUIRING SERVICING. SUBMIT DATA WHEN WORK IS
SUBSTANTIALLY COMPLETE AND IN SAME ORDER FORMAT AS SUBMITTALS. INCLUDE NAME AND LOCATION OF SOURCE PARTS AND
SERVICE FOR EACH PIECE OF EQUIPMENT.
A. INCLUDE COPY OF APPROVED SUBMITTAL DATA ALONG WITH SUBMITTAL REVIEW LETTERS RECEIVED FROM ENGINEER. DATA TO
CLEARLY INDICATE INSTALLED EQUIPMENT MODEL NUMBERS. DELETE OR CROSS OUT DATA PERTAINING TO OTHER EQUIPMENT NOT
SPECIFIC TO THIS PROJECT.
B. INCLUDE COPY OF MANUFACTURER'S STANDARD OPERATIONS AND MAINTENANCE FOR EQUIPMENT. AT FRONT OF EACH TAB,
PROVIDE ROUTINE MAINTENANCE DOCUMENTATION FOR SCHEDULED EQUIPMENT. INCLUDE MANUFACTURER'S RECOMMENDED
MAINTENANCE SCHEDULE AND HIGHLIGHT MAINTENANCE REQUIRED TO MAINTAIN WARRANTY. FURNISH LIST OF ROUTINE MAINTENANCE
PARTS, INCLUDING PART NUMBERS, SIZES, QUANTITIES, RELEVANT TO EACH PIECE OF EQUIPMENT: BATTERIES, LAMP LENSES,
SPEAKERS AND FILTERS.
C. INCLUDE WARRANTY PER DIVISION 00, PROCUREMENT AND CONTRACTING REQUIREMENTS AND DIVISION 01, GENERAL
REQUIREMENTS, SECTION 27 00 00, COMMUNICATIONS BASIC REQUIREMENTS AND INDIVIDUAL SECTIONS.
D. INCLUDE PRODUCT CERTIFICATES OF WARRANTIES AND GUARANTEES.
E. INCLUDE COPY OF COMPLETE PARTS LIST FOR EQUIPMENT. INCLUDE AVAILABLE EXPLODED VIEWS OF ASSEMBLIES AND
SUBASSEMBLIES.
F. INCLUDE COPY OF BURN-IN AND TEST REPORTS SPECIFIC TO EACH PIECE OF EQUIPMENT.
G. INCLUDE COPY OF SOFTWARE/APPLIANCE PROGRAMMING.
H. INCLUDE COMMISSIONING REPORTS.
I. ENGINEER WILL RETURN INCOMPLETE DOCUMENTATION WITHOUT REVIEW. ENGINEER WILL PROVIDE ONE SET OF REVIEW COMMENTS
IN SUBMITTAL REVIEW FORMAT. CONTRACTOR MUST ARRANGE FOR ADDITIONAL REVIEWS; CONTRACTOR TO BEAR COSTS FOR
ADDITIONAL REVIEWS AT ENGINEER'S HOURLY RATES.
2. THOROUGHLY INSTRUCT OWNER IN PROPER OPERATION OF EQUIPMENT AND SYSTEMS. WHERE NOTED IN INDIVIDUAL SECTIONS,
TRAINING WILL INCLUDE CLASSROOM INSTRUCTION WITH APPLICABLE TRAINING AIDS AND SYSTEMS DEMONSTRATIONS. SUBMIT COPY
OF MATERIAL USED FOR OWNER INSTRUCTION. FIELD INSTRUCTION PER SECTION 27 00 00, COMMUNICATIONS BASIC REQUIREMENTS
ARTICLE TITLED "DEMONSTRATION."
3. COPIES OF CERTIFICATES OF CODE AUTHORITY INSPECTIONS, ACCEPTANCE, CODE REQUIRED ACCEPTANCE TESTS, LETTER OF
CONFORMANCE AND OTHER SPECIAL GUARANTEES, CERTIFICATES OF WARRANTIES, SPECIFIED ELSEWHERE OR INDICATED ON
DRAWINGS.
B. INSTALL EQUIPMENT REQUIRING ACCESS (I.E., AMPLIFIERS, TAPS, ZONE CONTROLLERS, VOLUME CONTROLS, AND STORAGE DEVICES)
SO THAT THEY MAY BE SERVICED, RESET, REPLACED OR RECALIBRATED BY SERVICE PEOPLE WITH NORMAL SERVICE TOOLS AND
EQUIPMENT. DO NOT INSTALL EQUIPMENT IN OBVIOUS PASSAGEWAYS, DOORWAYS, SCUTTLES OR CRAWLSPACES WHICH WOULD
IMPEDE OR BLOCK INTENDED USAGE.
C. INSTALL EQUIPMENT AND PRODUCTS COMPLETE AS DIRECTED BY MANUFACTURER'S INSTALLATION INSTRUCTIONS. OBTAIN
INSTALLATION INSTRUCTIONS FROM MANUFACTURER PRIOR TO ROUGH-IN OF EQUIPMENT AND EXAMINE INSTRUCTIONS THOROUGHLY.
WHEN REQUIREMENTS OF INSTALLATION INSTRUCTIONS CONFLICT WITH CONTRACT DOCUMENTS, REQUEST CLARIFICATION FROM
ARCHITECT PRIOR TO PROCEEDING WITH INSTALLATION. THIS INCLUDES PROPER INSTALLATION METHODS, SEQUENCING AND
COORDINATION WITH OTHER TRADES AND DISCIPLINES.
D. EARTHWORK:
1. CONFIRM EARTHWORK REQUIREMENTS IN CONTRACT DOCUMENTS. IN ABSENCE OF SPECIFIC REQUIREMENTS, COMPLY WITH
INDIVIDUAL DIVISION 27, COMMUNICATIONS SECTIONS AND THE FOLLOWING:
A. PERFORM EXCAVATION, DEWATERING, SHORING, BEDDING, AND BACKFILL REQUIRED FOR INSTALLATION OF WORK IN THIS DIVISION IN
ACCORDANCE WITH RELATED EARTHWORK DIVISIONS. CONTACT UTILITIES AND LOCATE EXISTING UTILITIES PRIOR TO EXCAVATION.
REPAIR ANY WORK DAMAGED DURING EXCAVATION OR BACKFILLING.
B. EXCAVATION: DO NOT EXCAVATE UNDER FOOTINGS, FOUNDATION BASES, OR RETAINING WALLS.
C. PROVIDE PROTECTION OF UNDERGROUND SYSTEMS. REVIEW THE PROJECT GEOTECHNICAL REPORT FOR REFERENCES TO
CORROSIVE OR DELETERIOUS SOILS WHICH WILL REDUCE THE PERFORMANCE OR SERVICE LIFE OF UNDERGROUND SYSTEMS
MATERIALS.
E. FIRESTOPPING:
1. CONFIRM FIRESTOPPING REQUIREMENTS IN DIVISION 07, THERMAL AND MOISTURE PROTECTION. IN ABSENCE OF SPECIFIC
REQUIREMENTS, COMPLY WITH INDIVIDUAL DIVISION 27, COMMUNICATIONS SECTIONS AND THE FOLLOWING:
A. COORDINATE LOCATION AND PROTECTION LEVEL OF FIRE AND/OR SMOKE RATED WALLS, CEILINGS, AND FLOORS. WHEN THESE
ASSEMBLIES ARE PENETRATED, SEAL AROUND PIPING, DUCTWORK AND EQUIPMENT WITH APPROVED FIRESTOPPING MATERIAL.
INSTALL FIRESTOPPING MATERIAL COMPLETE AS DIRECTED BY MANUFACTURER'S INSTALLATION INSTRUCTIONS. MEET REQUIREMENTS
OF ASTM E814, STANDARD TEST METHOD FOR FIRE TESTS OF THROUGH-PENETRATION FIRE STOPS.
F. PLENUMS:
1. IN PLENUMS, PROVIDE PLENUM RATED MATERIALS THAT MEET THE REQUIREMENTS TO BE INSTALLED IN PLENUMS. IMMEDIATELY
NOTIFY ARCHITECT/ENGINEER OF DISCREPANCY.
3.02 SEISMIC CONTROL
A. CONFIRM SEISMIC CONTROL REQUIREMENTS IN DIVISION 01, GENERAL REQUIREMENTS, SECTION 27 00 00, COMMUNICATIONS BASIC
REQUIREMENTS AND INDIVIDUAL DIVISION 27 COMMUNICATIONS SECTIONS.
CHANGES TO ORIGINAL DOCUMENTS BY REFERENCING REVISION DOCUMENT, AND INCLUDE BURIED ELEMENTS, LOCATION OF CONDUIT,
AND LOCATION OF CONCEALED COMMUNICATION ITEMS. INCLUDE ITEMS CHANGED BY FIELD ORDERS, SUPPLEMENTAL INSTRUCTIONS,
AND CONSTRUCTED CONDITIONS.
2. RECORD DRAWINGS ARE TO INCLUDE EQUIPMENT AND FIXTURE/CONNECTION SCHEDULES THAT ACCURATELY REFLECT "AS
CONSTRUCTED OR INSTALLED" FOR PROJECT.
3. AT COMPLETION OF PROJECT, INPUT CHANGES TO ORIGINAL PROJECT ON CAD DRAWINGS AND MAKE ONE SET OF BLACK-LINE
DRAWINGS CREATED FROM CAD FILES IN VERSION/RELEASE EQUAL TO CONTRACT DRAWINGS. SUBMIT CAD DISK AND DRAWINGS UPON
SUBSTANTIAL COMPLETION.
4. INVERT ELEVATIONS AND DIMENSIONED LOCATIONS FOR INCOMING UTILITIES AND SITE RACEWAYS BELOW GRADE EXTENDING TO
5-FEET OUTSIDE BUILDING LINE.
5. SEE DIVISION 27, COMMUNICATIONS INDIVIDUAL SECTIONS FOR ADDITIONAL ITEMS TO INCLUDE IN RECORD DRAWINGS.
C. CONFIRM BUILDING OCCUPANCY CATEGORY AND SEISMIC DESIGN CATEGORY WITH ARCHITECT.
B. DRAWINGS ARE INTENDED TO BE DIAGRAMMATIC AND REFLECT THE BASIS OF DESIGN MANUFACTURER'S EQUIPMENT. THEY ARE NOT
INTENDED TO SHOW EVERY ITEM IN ITS EXACT DIMENSIONS, OR DETAILS OF EQUIPMENT OR PROPOSED SYSTEMS LAYOUT. VERIFY
ACTUAL DIMENSIONS OF SYSTEMS (I.E., CONDUIT) AND EQUIPMENT PROPOSED TO ASSURE THAT SYSTEMS AND EQUIPMENT WILL FIT IN
AVAILABLE SPACE. CONTRACTOR IS RESPONSIBLE FOR DESIGN AND CONSTRUCTION COSTS INCURRED FOR EQUIPMENT OTHER THAN
BASIS OF DESIGN, INCLUDING, BUT NOT LIMITED TO, ARCHITECTURAL, STRUCTURAL, ELECTRICAL, HVAC, FIRE SPRINKLER, AND
PLUMBING SYSTEMS.
C. MANUFACTURER'S INSTRUCTIONS: FOLLOW MANUFACTURER'S WRITTEN INSTRUCTIONS. IF IN CONFLICT WITH CONTRACT
DOCUMENTS, OBTAIN CLARIFICATION. NOTIFY ENGINEER/ARCHITECT, IN WRITING, BEFORE STARTING WORK.
D. ITEMS SHOWN ON DRAWINGS ARE NOT NECESSARILY INCLUDED IN SPECIFICATIONS OR VICE VERSA. CONFIRM REQUIREMENTS IN
ALL CONTRACT DOCUMENTS.
E. UL AND CSA COMPLIANCE: PROVIDE PRODUCTS WHICH ARE UL AND CSA LISTED.
F. CONTRACTOR QUALIFICATIONS:
1. MINIMUM OF FIVE YEARS EXPERIENCE IN THE DESIGN, INSTALLATION, TESTING AND MAINTENANCE OF COMMUNICATIONS SYSTEMS.
2. MUST EMPLOY AT LEAST ONE FULL TIME BICSI CERTIFIED REGISTERED COMMUNICATIONS DISTRIBUTION DESIGNER (RCDD) WHO IS
INVOLVED IN REVIEWING WORK PERFORMED BY CONTRACTOR ON THIS PROJECT.
3. MAINTAIN A LOCAL SERVICE FACILITY WHICH STOCKS SPARE DEVICES AND/OR COMPONENTS FOR SERVICING SYSTEMS.
4. HAVE PERFORMED SUCCESSFUL INSTALLATION AND MAINTENANCE OF AT LEAST THREE PROJECTS SIMILAR IN SCOPE AND SIZE. BE
ABLE TO PROVIDE PROJECT REFERENCES FOR THESE THREE PROJECTS, INCLUDING SCOPE OF WORK, PROJECT TYPE, OWNER/USER
CONTACT NAME AND TELEPHONE NUMBER.
5. THE CONTRACTOR SELECTED FOR THIS PROJECT MUST BE CERTIFIED BY THE MANUFACTURER OF THE APPROVED PRODUCTS AND
UTILIZE THESE COMPONENTS FOR COMPLETION OF WORK.
1.06 WARRANTY
A. PROVIDE WRITTEN WARRANTY COVERING THE WORK FOR A PERIOD OF ONE YEAR FROM DATE OF SUBSTANTIAL COMPLETION IN
ACCORDANCE WITH DIVISION 00, PROCUREMENT AND CONTRACTING REQUIREMENTS AND DIVISION 01, GENERAL REQUIREMENTS,
SECTION 27 00 00, COMMUNICATIONS BASIC REQUIREMENTS AND INDIVIDUAL DIVISION 27, COMMUNICATIONS SECTIONS.
B. SECTIONS UNDER THIS DIVISION CAN REQUIRE ADDITIONAL AND/OR EXTENDED WARRANTIES THAT APPLY BEYOND BASIC WARRANTY
UNDER DIVISION 01, GENERAL REQUIREMENTS AND THE GENERAL CONDITIONS. CONFIRM REQUIREMENTS IN ALL CONTRACT
DOCUMENTS.
D. EARTHQUAKE RESISTANT DESIGNS FOR COMMUNICATIONS (DIVISION 27) EQUIPMENT AND DISTRIBUTION, I.E. CABINETS AND RACKS,
CEILING ASSEMBLIES, RACEWAYS, LADDER RACKING, ETC. CONFORM TO REGULATIONS OF JURISDICTION HAVING AUTHORITY.
E. RESTRAINTS WHICH ARE USED TO PREVENT DISRUPTION OF FUNCTION OF PIECE OF EQUIPMENT BECAUSE OF APPLICATION OF
HORIZONTAL FORCE TO BE SUCH THAT FORCES ARE CARRIED TO FRAME OF STRUCTURE IN SUCH A WAY THAT FRAME WILL NOT BE
DEFLECTED WHEN APPARATUS IS ATTACHED TO A MOUNTING BASE AND EQUIPMENT PAD, OR TO STRUCTURE IN NORMAL WAY,
UTILIZING ATTACHMENTS PROVIDED. SECURE EQUIPMENT AND DISTRIBUTION SYSTEMS TO WITHSTAND A FORCE IN DIRECTION EQUAL
TO VALUE DEFINED BY JURISDICTION HAVING AUTHORITY.
F. PROVIDE STAMPED SHOP DRAWINGS FROM LICENSED STRUCTURAL ENGINEER OF SEISMIC BRACING AND SEISMIC MOVEMENT
ASSEMBLIES FOR CABINETS, RACKS, MAJOR EQUIPMENT AND OVERHEAD RACEWAYS. ENGINEER TO DESIGN AND PROVIDE STAMPED
SHOP DRAWINGS CABINETS, RACKS, MAJOR EQUIPMENT AND OVERHEAD RACEWAY. SUBMIT SHOP DRAWINGS ALONG WITH EQUIPMENT
SUBMITTALS.
G. PROVIDE STAMPED SHOP DRAWINGS FROM LICENSED STRUCTURAL ENGINEER OF SEISMIC FLEXIBLE JOINTS FOR PIPING AND
CROSSING BUILDING EXPANSION OR SEISMIC JOINTS. SUBMIT SHOP DRAWINGS ALONG WITH SEISMIC BRACING DETAILS. COORDINATE
EXACT DESIGN REQUIREMENTS WITH PROJECT STRUCTURAL ENGINEER.
H. EQUIPMENT: PROVIDE MEANS TO PROHIBIT EXCESSIVE MOTION OF EQUIPMENT DURING EARTHQUAKE.
3.03 REVIEW AND OBSERVATION
A. CONFIRM REVIEW AND OBSERVATION REQUIREMENTS IN DIVISION 00, PROCUREMENT AND CONTRACTING REQUIREMENTS AND
DIVISION 01, GENERAL REQUIREMENTS, SECTION 27 00 00, COMMUNICATIONS BASIC REQUIREMENTS AND INDIVIDUAL DIVISION 27,
COMMUNICATIONS SECTIONS.
B. NOTIFY ARCHITECT, IN WRITING, AT FOLLOWING STAGES OF CONSTRUCTION SO THAT THEY MAY, AT THEIR OPTION, VISIT SITE FOR
REVIEW AND CONSTRUCTION OBSERVATION:
1. UNDERGROUND CONDUIT INSTALLATION PRIOR TO BACKFILLING.
2. PRIOR TO CEILING COVER/INSTALLATION.
3. WHEN MAIN SYSTEMS, OR PORTIONS OF, ARE BEING TESTED AND READY FOR INSPECTION BY AHJ.
C. FINAL PUNCH: COSTS INCURRED BY ADDITIONAL TRIPS REQUIRED DUE TO INCOMPLETE SYSTEMS WILL BE THE RESPONSIBILITY OF
THE CONTRACTOR.
3.04 CONTINUITY OF SERVICE
A. CONFIRM REQUIREMENTS IN DIVISION 00, PROCUREMENT AND CONTRACTING REQUIREMENTS AND DIVISION 01, GENERAL
REQUIREMENTS. IN ABSENCE OF SPECIFIC REQUIREMENTS, COMPLY WITH INDIVIDUAL DIVISION 27, COMMUNICATIONS SECTIONS AND
THE FOLLOWING:
1. DURING REMODELING OR ADDITION TO EXISTING STRUCTURES, OR ADDITION OF A STRUCTURE TO EXISTING STRUCTURE, WHILE
EXISTING STRUCTURE IS OCCUPIED, CURRENT SERVICES TO REMAIN INTACT UNTIL NEW CONSTRUCTION, FACILITIES OR EQUIPMENT IS
INSTALLED.
2. PRIOR TO CHANGING OVER TO NEW SERVICE, VERIFY THAT EVERY ITEM IS THOROUGHLY PREPARED. INSTALL NEW WIRING TO POINT
OF CONNECTION.
3. COORDINATE TRANSFER TIME TO NEW SERVICE WITH OWNER. IF REQUIRED, PERFORM TRANSFER DURING OFF PEAK HOURS. ONCE
CHANGEOVER IS STARTED, PURSUE TO ITS COMPLETION TO KEEP INTERFERENCE TO A MINIMUM. IF OVERTIME IS NECESSARY, THERE
WILL BE NO ALLOWANCE MADE BY OWNER FOR EXTRA EXPENSE FOR SUCH OVERTIME OR SHIFT WORK.
4. ORGANIZE WORK TO MINIMIZE DURATION OF POWER INTERRUPTION.
3.05 CUTTING AND PATCHING
1.07 COORDINATION DOCUMENTS
A. PRIOR TO CONSTRUCTION, COORDINATE INSTALLATION AND LOCATION OF HVAC EQUIPMENT, DUCTWORK, GRILLES, DIFFUSERS,
PIPING, PLUMBING EQUIPMENT/FIXTURES, FIRE SPRINKLERS, PLUMBING, LIGHTS, CABLE TRAYS AND ELECTRICAL SERVICES WITH
ARCHITECTURAL AND STRUCTURAL REQUIREMENTS, AND OTHER TRADES (INCLUDING CEILING SUSPENSION AND TILE SYSTEMS), AND
PROVIDE MAINTENANCE ACCESS REQUIREMENTS. COORDINATE WITH SUBMITTED ARCHITECTURAL SYSTEMS (I.E. ROOFING, CEILING,
FINISHES) AND STRUCTURAL SYSTEMS AS SUBMITTED, INCLUDING FOOTINGS AND FOUNDATION. IDENTIFY ZONE OF INFLUENCE FROM
FOOTINGS AND ENSURE SYSTEMS ARE NOT ROUTED WITHIN THE ZONE OF INFLUENCE.
B. ADVISE ARCHITECT IN EVENT A CONFLICT OCCURS IN LOCATION OR CONNECTION OF EQUIPMENT. BEAR COSTS RESULTING FROM
FAILURE TO PROPERLY COORDINATE INSTALLATION OR FAILURE TO ADVISE ARCHITECT OF CONFLICT.
C. VERIFY IN FIELD EXACT SIZE, LOCATION, INVERT, AND CLEARANCES REGARDING EXISTING MATERIAL, EQUIPMENT AND APPARATUS,
AND ADVISE ARCHITECT OF DISCREPANCIES BETWEEN THAT INDICATED ON DRAWINGS AND THAT EXISTING IN FIELD PRIOR TO
INSTALLATION RELATED THERETO.
B. UPON COMPLETION OF WORK AND ADJUSTMENT OF EQUIPMENT AND TEST SYSTEMS, DEMONSTRATE TO OWNER'S REPRESENTATIVE,
ARCHITECT AND ENGINEER THAT EQUIPMENT FURNISHED AND INSTALLED OR CONNECTED UNDER PROVISIONS OF THESE
SPECIFICATIONS FUNCTIONS IN MANNER REQUIRED. PROVIDE FIELD INSTRUCTION TO OWNER'S MAINTENANCE STAFF AS SPECIFIED IN
DIVISION 01, GENERAL REQUIREMENTS, SECTION 27 00 00, COMMUNICATIONS BASIC REQUIREMENTS AND INDIVIDUAL DIVISION 27,
COMMUNICATIONS SECTIONS.
C. MANUFACTURER'S FIELD SERVICES: FURNISH SERVICES OF A QUALIFIED PERSON AT TIME APPROVED BY OWNER, TO INSTRUCT
MAINTENANCE PERSONNEL, CORRECT DEFECTS OR DEFICIENCIES, AND DEMONSTRATE TO SATISFACTION OF OWNER THAT ENTIRE
SYSTEM IS OPERATING IN SATISFACTORY MANNER AND COMPLIES WITH REQUIREMENTS OF OTHER TRADES THAT MAY BE REQUIRED TO
COMPLETE WORK. COMPLETE INSTRUCTION AND DEMONSTRATION PRIOR TO FINAL JOB SITE OBSERVATIONS.
3.09 CLEANING
A. CONFIRM CLEANING REQUIREMENTS IN DIVISION 00, PROCUREMENT AND CONTRACTING REQUIREMENTS, DIVISION 01, GENERAL
REQUIREMENTS, SECTION 27 00 00, COMMUNICATIONS BASIC REQUIREMENTS AND INDIVIDUAL DIVISION 27, COMMUNICATIONS
SECTIONS.
B. UPON COMPLETION OF INSTALLATION, THOROUGHLY CLEAN EXPOSED PORTIONS OF EQUIPMENT, REMOVING TEMPORARY LABELS
AND TRACES OF FOREIGN SUBSTANCES. THROUGHOUT WORK, REMOVE CONSTRUCTION DEBRIS AND SURPLUS MATERIALS
ACCUMULATED DURING WORK.
A. CONFIRM INSTALLATION REQUIREMENTS IN DIVISION 00, PROCUREMENT AND CONTRACTING REQUIREMENTS AND DIVISION 01,
GENERAL REQUIREMENTS, SECTION 27 00 00, COMMUNICATIONS BASIC REQUIREMENTS AND INDIVIDUAL DIVISION 27, COMMUNICATIONS
SECTIONS.
B. EQUIPMENT IMPORTANCE FACTOR: 1.0.
A. REGULATORY REQUIREMENTS: WORK AND MATERIALS INSTALLED TO CONFORM WITH ALL LOCAL, STATE, FEDERAL AND OTHER
APPLICABLE LAWS AND REGULATION.
A. CONFIRM DEMONSTRATION REQUIREMENTS IN DIVISION 00, PROCUREMENT AND CONTRACTING REQUIREMENTS AND DIVISION 01,
GENERAL REQUIREMENTS, SECTION 27 00 00, COMMUNICATIONS BASIC REQUIREMENTS AND INDIVIDUAL DIVISION 27, COMMUNICATIONS
SECTIONS.
3.01 ACCESSIBILITY AND INSTALLATION
A. CONFIRM ACCESSIBILITY AND INSTALLATION REQUIREMENTS IN DIVISION 00, PROCUREMENT AND CONTRACTING REQUIREMENTS,
DIVISION 01, GENERAL REQUIREMENTS, SECTION 27 00 00, COMMUNICATIONS BASIC REQUIREMENTS AND INDIVIDUAL DIVISION 27,
COMMUNICATIONS SECTIONS.
A. CONFIRM CUTTING AND PATCHING REQUIREMENTS IN DIVISION 00, PROCUREMENT AND CONTRACTING REQUIREMENTS AND DIVISION
01, GENERAL REQUIREMENTS. IN ABSENCE OF SPECIFIC REQUIREMENTS, COMPLY WITH INDIVIDUAL DIVISION 27, COMMUNICATIONS
SECTIONS AND THE FOLLOWING:
1. PROPOSED FLOOR CUTTING/CORE DRILLING/SLEEVE LOCATIONS TO BE APPROVED BY PROJECT STRUCTURAL ENGINEER. SUBMIT
PROPOSED LOCATIONS TO ARCHITECT/PROJECT STRUCTURAL ENGINEER. WHERE SLABS ARE OF POST TENSION CONSTRUCTION,
PERFORM X-RAY SCAN OF PROPOSED PENETRATION LOCATIONS AND SUBMIT SCAN RESULTS INCLUDING PROPOSED PENETRATION
LOCATIONS TO PROJECT STRUCTURAL ENGINEER/ARCHITECT FOR APPROVAL. WHERE SLABS ARE OF WAFFLE TYPE CONSTRUCTION,
SHOW COLUMN CAP EXTENT AND CELL LOCATIONS RELATIVE TO PROPOSED PENETRATION(S).
2. CUTTING, PATCHING AND REPAIRING FOR WORK SPECIFIED IN THIS DIVISION INCLUDING PLASTERING, MASONRY WORK, CONCRETE
WORK, CARPENTRY WORK, AND PAINTING INCLUDED UNDER THIS SECTION WILL BE PERFORMED BY SKILLED CRAFTSMEN OF EACH
RESPECTIVE TRADE IN CONFORMANCE WITH
APPROPRIATE DIVISION OF WORK.
3. ADDITIONAL OPENINGS REQUIRED IN BUILDING CONSTRUCTION TO BE MADE BY DRILLING OR CUTTING. USE OF JACK HAMMER IS
SPECIFICALLY PROHIBITED. PATCH OPENINGS IN AND THROUGH CONCRETE AND MASONRY WITH GROUT.
4. RESTORE NEW OR EXISTING WORK THAT IS CUT AND/OR DAMAGED TO ORIGINAL CONDITION. PATCH AND REPAIR SPECIFICALLY
717 Market Street
Suite 500
San Francisco, CA 94103
TEL
415.489.7240
FAX 415.489.7289
www.interfaceengineering.com
3.08 DEMONSTRATION
3.10 INSTALLATION
P. RECORD DRAWINGS:
1.05 QUALITY ASSURANCE
A. CONFIRM REQUIREMENTS IN DIVISION 00, PROCUREMENT AND CONTRACTING REQUIREMENTS AND DIVISION 01, GENERAL
REQUIREMENTS. IN ABSENCE OF SPECIFIC REQUIREMENTS, COMPLY WITH INDIVIDUAL DIVISION 27, COMMUNICATIONS SECTIONS AND
THE FOLLOWING:
1. HANDLE MATERIALS DELIVERED TO PROJECT SITE WITH CARE TO AVOID DAMAGE. STORE MATERIALS ON SITE INSIDE BUILDING OR
PROTECTED FROM WEATHER, DIRT AND CONSTRUCTION DUST. INSULATION AND LINING THAT BECOMES WET FROM IMPROPER
STORAGE AND HANDLING TO BE REPLACED BEFORE INSTALLATION. PRODUCTS AND/OR MATERIALS THAT BECOME DAMAGED DUE TO
WATER, DIRT AND/OR DUST AS A RESULT OF IMPROPER STORAGE TO BE REPLACED BEFORE INSTALLATION.
2. PROTECT ALL EQUIPMENT AND CONDUIT TO AVOID DAMAGE. CLOSE CONDUIT OPENINGS WITH CAPS OR PLUGS. KEEP MOTORS AND
BEARINGS IN WATERTIGHT AND DUSTPROOF COVERS DURING ENTIRE COURSE OF INSTALLATION.
PART 3 - EXECUTION
M. SAMPLES: PROVIDE SAMPLES WHEN REQUESTED BY INDIVIDUAL SECTIONS.
1.04 SUBMITTALS
A. SEE DIVISION 01, GENERAL REQUIREMENTS FOR SUBMITTAL PROCEDURES.
PART 2 - PRODUCTS
WHERE EXISTING ITEMS HAVE BEEN REMOVED. THIS INCLUDES REPAIRING AND PAINTING WALLS, CEILINGS, ETC. WHERE EXISTING
CONDUIT AND DEVICES ARE REMOVED AS PART OF THIS PROJECT. WHERE ALTERATIONS DISTURB LAWNS, PAVING, AND WALKS,
SURFACES TO BE REPAIRED, REFINISHED AND LEFT IN CONDITION MATCHING EXISTING PRIOR TO COMMENCEMENT OF WORK.
5. ADDITIONAL WORK REQUIRED BY LACK OF PROPER COORDINATION WILL BE PROVIDED AT NO ADDITIONAL COST TO THE OWNER.
D. SUBMIT FINAL COORDINATION DRAWINGS WITH CHANGES AS RECORD DRAWINGS AT COMPLETION OF PROJECT.
B. INSTALL EQUIPMENT AND DEVICES IN ACCORDANCE WITH MANUFACTURER'S INSTALLATION INSTRUCTIONS, PLUMB AND LEVEL AND
FIRMLY SECURED TO MOUNTING SURFACES. MAINTAIN MANUFACTURER'S RECOMMENDED CLEARANCES.
C. START UP EQUIPMENT, IN ACCORDANCE WITH MANUFACTURER'S START-UP INSTRUCTIONS, AND IN PRESENCE OF MANUFACTURER'S
REPRESENTATIVE. TEST OPERATION AND DEMONSTRATE COMPLIANCE WITH REQUIREMENTS. REPLACE DAMAGED OR
MALFUNCTIONING EQUIPMENT.
D. PROVIDE MISCELLANEOUS SUPPORTS/METALS REQUIRED FOR INSTALLATION OF EQUIPMENT.
3.11 PAINTING
A. CONFIRM PAINTING REQUIREMENTS IN DIVISION 01, GENERAL REQUIREMENTS AND DIVISION 09, FINISHES. IN ABSENCE OF SPECIFIC
REQUIREMENTS, COMPLY WITH INDIVIDUAL DIVISION 27, COMMUNICATIONS SECTIONS AND THE FOLLOWING:
1. FERROUS METAL: AFTER COMPLETION OF COMMUNICATIONS WORK, THOROUGHLY CLEAN AND PAINT EXPOSED SUPPORTS
CONSTRUCTED OF FERROUS METAL SURFACES IN TELECOMMUNICATIONS ROOMS, I.E., HANGERS, HANGER RODS, EQUIPMENT STANDS,
WITH ONE COAT OF BLACK ASPHALT VARNISH FOR EXTERIOR OR BLACK ENAMEL FOR INTERIOR, SUITABLE FOR HOT SURFACES.
2. IN A TELECOMMUNICATIONS ROOM, ON ROOF OR OTHER EXPOSED AREAS, EQUIPMENT NOT PAINTED WITH ENAMEL TO RECEIVE TWO
COATS OF PRIMER AND ONE COAT OF RUSTPROOF ENAMEL, COLORS AS SELECTED BY ARCHITECT.
3. SEE INDIVIDUAL EQUIPMENT SPECIFICATIONS FOR OTHER PAINTING.
4. STRUCTURAL STEEL: REPAIR DAMAGE TO STRUCTURAL STEEL FINISHES OR FINISHES OF OTHER MATERIALS DAMAGED BY CUTTING,
WELDING OR PATCHING TO MATCH ORIGINAL.
5. CONDUIT: CLEAN, PRIMER COAT AND PAINT INTERIOR CONDUIT EXPOSED IN FINISHED AREAS WITH TWO COATS PAINT SUITABLE FOR
METALLIC SURFACES. COLOR SELECTED BY ARCHITECT.
6. COVERS: COVERS SUCH AS MANHOLES, VAULTS AND THE LIKE WILL BE FURNISHED WITH FINISHES WHICH RESIST CORROSION AND
RUST.
3.12 ACCESS PANELS
A. CONFIRM ACCESS PANEL REQUIREMENTS IN DIVISION 01, GENERAL REQUIREMENTS. IN ABSENCE OF SPECIFIC REQUIREMENTS,
COMPLY WITH INDIVIDUAL DIVISION 27, COMMUNICATIONS SECTIONS AND THE FOLLOWING:
1. COORDINATE LOCATIONS/SIZES OF ACCESS PANELS WITH ARCHITECT PRIOR TO WORK.
3.13 DEMOLITION
A. CONFIRM REQUIREMENTS IN DIVISION 01, GENERAL REQUIREMENTS AND DIVISION 02, EXISTING CONDITIONS. IN ABSENCE OF
SPECIFIC REQUIREMENTS, COMPLY WITH INDIVIDUAL DIVISION 27, COMMUNICATIONS SECTIONS AND THE FOLLOWING:
1. SCOPE:
A. IT IS THE INTENT OF THESE DOCUMENTS TO PROVIDE NECESSARY INFORMATION AND ADJUSTMENTS TO COMMUNICATIONS SYSTEMS
REQUIRED TO MEET CODE AND ACCOMMODATE INSTALLATION OF NEW WORK.
B. COORDINATE WITH OWNER SO THAT WORK CAN BE SCHEDULED NOT TO INTERRUPT OPERATIONS, NORMAL ACTIVITIES, BUILDING
ACCESS OR ACCESS TO DIFFERENT AREAS.
C. EXISTING CONDITIONS: DETERMINE EXACT LOCATION OF EXISTING UTILITIES AND EQUIPMENT BEFORE COMMENCING WORK.
COMPENSATE OWNER FOR DAMAGES CAUSED BY FAILURE TO EXACTLY LOCATE AND PRESERVE UNDERGROUND UTILITIES. REPLACE
DAMAGED ITEMS WITH NEW MATERIAL TO MATCH EXISTING. PROMPTLY NOTIFY OWNER IF UTILITIES ARE FOUND WHICH ARE NOT
SHOWN ON DRAWINGS.
2. EQUIPMENT: UNLESS OTHERWISE DIRECTED, EQUIPMENT, FIXTURES, OR FITTINGS BEING REMOVED AS PART OF DEMOLITION
PROCESS ARE OWNER'S PROPERTY. REMOVE OTHER ITEMS NOT SCHEDULED TO BE REUSED OR RELOCATED FROM JOB SITE AS
DIRECTED BY OWNER.
3. UNLESS SPECIFICALLY INDICATED ON DRAWINGS, REMOVE EXPOSED, UNUSED RACEWAYS BEHIND FINISHED SURFACES (FLOOR,
WALLS, CEILINGS, ETC.). CAP RACEWAYS AND PATCH SURFACES TO MATCH SURROUNDING FINISH.
4. UNLESS SPECIFICALLY INDICATED ON DRAWINGS, REMOVE UNUSED EQUIPMENT, ELECTRICAL BOXES, FITTINGS AND CONNECTORS.
REMOVAL IS TO BE TO A POINT BEHIND FINISHED SURFACES (FLOORS, WALLS, AND CEILINGS).
5. EXAMINATION:
A. DETERMINE EXACT LOCATION OF EXISTING UTILITIES AND EQUIPMENT BEFORE COMMENCING WORK, COMPENSATE OWNER FOR
DAMAGES CAUSED BY FAILURE TO LOCATE AND PRESERVE UTILITIES. REPLACE DAMAGED ITEMS WITH NEW MATERIAL TO MATCH
EXISTING.
B. VERIFY THAT ABANDONED WIRING AND EQUIPMENT SERVE ONLY ABANDONED FACILITIES.
C. DEMOLITION DRAWINGS ARE BASED ON CASUAL FIELD OBSERVATION AND EXISTING RECORD DOCUMENTS.
1) VERIFY ACCURACY OF INFORMATION SHOWN PRIOR TO BIDDING AND PROVIDE SUCH LABOR AND MATERIAL AS IS NECESSARY TO
ACCOMPLISH WORK.
2) VERIFY LOCATION AND NUMBER OF COMMUNICATIONS OUTLETS, RACKS, PANELS, ETC. IN FIELD.
D. REPORT DISCREPANCIES TO ARCHITECT BEFORE DISTURBING EXISTING INSTALLATION.
6. PROMPTLY NOTIFY OWNER IF UTILITIES ARE FOUND WHICH ARE NOT SHOWN ON DRAWINGS.
7. EXECUTION:
A. REMOVE EXISTING CONNECTORS, BACKBOXES, WALL PLATES AND OTHER COMMUNICATIONS EQUIPMENT AND DEVICES AND
ASSOCIATED WIRING FROM WALLS, CEILINGS, FLOORS, AND OTHER SURFACES SCHEDULED FOR REMODELING, RELOCATION, OR
DEMOLITION UNLESS SHOWN AS RETAINED OR RELOCATED ON DRAWINGS.
B. PROVIDE TEMPORARY WIRING AND CONNECTIONS TO MAINTAIN COMMUNICATIONS CONTINUITY OF EXISTING SYSTEMS DURING
CONSTRUCTION. REMOVE OR RELOCATE COMMUNICATIONS BOXES, CONDUIT, WIRING, EQUIPMENT, AND THE LIKE, AS ENCOUNTERED IN
REMOVED OR REMODELED AREAS IN EXISTING CONSTRUCTION AFFECTED BY THIS WORK.
C. REMOVE AND RESTORE CABLE WHICH SERVES USABLE EXISTING OUTLETS CLEAR OF CONSTRUCTION OR DEMOLITION.
D. IF EXISTING JUNCTION BOXES WILL BE MADE INACCESSIBLE, OR IF ABANDONED OUTLETS SERVE AS FEED THROUGH BOXES FOR
OTHER EXISTING COMMUNICATIONS EQUIPMENT WHICH IS BEING RETAINED, PROVIDE NEW CONDUIT AND CABLE TO BYPASS
ABANDONED OUTLETS.
E. IF EXISTING CONDUITS PASS THROUGH PARTITIONS OR CEILING WHICH ARE BEING REMOVED OR REMODELED, PROVIDE NEW
CONDUIT AND CABLE TO REROUTE CLEAR OF CONSTRUCTION OR DEMOLITION AND MAINTAIN SERVICE TO EXISTING EQUIPMENT. IF
THESE ARE CONDUITS WHICH REQUIRE A NEW CABLE HOME RUN, E.G. TELECOM CABLE, REQUEST CLARIFICATION FROM ARCHITECT OR
ENGINEER PRIOR TO PROCEEDING WITH DEMO.
F. EXTEND CABLE SLACK AND DEVICES IN EXISTING WALLS TO BE FURRED OUT.
G. REMOVE ABANDONED CABLE TO ORIGINATING TELECOM ROOM.
H. REMOVE EXPOSED ABANDONED CONDUIT, INCLUDING ABANDONED CONDUIT ABOVE ACCESSIBLE CEILING FINISHES. CUT CONDUIT
FLUSH WITH WALLS AND FLOORS, AND PATCH SURFACES.
I. DISCONNECT ABANDONED OUTLETS AND REMOVE DEVICES. REMOVE ABANDONED OUTLETS IF CONDUIT SERVICING THEM IS
ABANDONED AND REMOVED. PROVIDE BLANK COVER FOR ABANDONED OUTLETS WHICH ARE NOT REMOVED.
J. DISCONNECT AND REMOVE ABANDONED PANELBOARDS AND DISTRIBUTION EQUIPMENT.
K. MAINTAIN ACCESS TO EXISTING COMMUNICATIONS INSTALLATIONS WHICH REMAIN ACTIVE. MODIFY INSTALLATION OR PROVIDE
ACCESS PANEL AS APPROPRIATE.
L. EXISTING COMMUNICATIONS OUTLETS AND DEVICES ARE INDICATED ON TECHNOLOGY DEMOLITION PLANS. VERIFY EXACT LOCATION
AND NUMBER OF EXISTING COMMUNICATIONS OUTLETS AND devices in field. Only partial existing communications shown. Locations of items
shown on Drawings as existing are partially based on Record and other Drawings which may contain errors. Verify accuracy of information shown prior to
bidding and provide such labor and material as is necessary to accomplish intent of Contract Documents.
m. Remove abandoned cable to leave site clean.
B. Existing Communication Systems: Maintain existing systems in service until new system is complete and ready for service. Disable system only to
make switchovers and connections.
1. Notify Owner at least 7 working days before partially or completely disabling system.
2. Make temporary connections to maintain service in areas adjacent to work area.
1111 Jackson Street
Oakland, California
PART 1 - GENERAL
F. IDENTIFY/MARK EACH SUBMITTAL IN DETAIL. NOTE WHAT DIFFERENCES, IF ANY, EXIST BETWEEN THE SUBMITTED ITEM AND THE
SPECIFIED ITEM. FAILURE TO IDENTIFY THE DIFFERENCES WILL BE CONSIDERED CAUSE FOR DISAPPROVAL. IF DIFFERENCES ARE NOT
IDENTIFIED AND/OR NOT DISCOVERED DURING THE SUBMITTAL REVIEW PROCESS, CONTRACTOR REMAINS RESPONSIBLE FOR
PROVIDING EQUIPMENT AND MATERIALS THAT MEET THE SPECIFICATIONS AND DRAWINGS.
1. LABEL SUBMITTAL TO MATCH NUMBERING/REFERENCES AS SHOWN IN CONTRACT DOCUMENTS. HIGHLIGHT AND LABEL APPLICABLE
INFORMATION TO INDIVIDUAL EQUIPMENT OR CROSS OUT/REMOVE EXTRANEOUS DATA NOT APPLICABLE TO SUBMITTED MODEL.
CLEARLY NOTE OPTIONS AND ACCESSORIES TO BE PROVIDED, INCLUDING FIELD INSTALLED ITEMS. HIGHLIGHT CONNECTIONS BY/TO
OTHER TRADES.
2. INCLUDE TECHNICAL DATA, INSTALLATION INSTRUCTIONS AND DIMENSIONED DRAWINGS FOR PRODUCTS, FIXTURES, EQUIPMENT AND
DEVICES INSTALLED, FURNISHED OR PROVIDED. REFERENCE INDIVIDUAL DIVISION 27, COMMUNICATIONS SPECIFICATION SECTIONS FOR
SPECIFIC ITEMS REQUIRED IN PRODUCT DATA SUBMITTAL OUTSIDE OF THESE REQUIREMENTS.
3. SEE DIVISION 27, COMMUNICATIONS INDIVIDUAL SECTIONS FOR ADDITIONAL SUBMITTAL REQUIREMENTS OUTSIDE OF THESE
REQUIREMENTS.
JACKSON CENTER ONE
27 0000 COMMUNICATIONS BASIC REQUIREMENTS
SHEET TITLE
SPECIFICATION TECHNOLOGY
REVISIONS
DRAWN BY
CR
CHECKED BY
Kevin Kuang
JOB NO.
3.14 ACCEPTANCE
A. CONFIRM REQUIREMENTS IN DIVISION 00, PROCUREMENT AND CONTRACTING REQUIREMENTS AND DIVISION 01, GENERAL
REQUIREMENTS. IN ABSENCE OF SPECIFIC REQUIREMENTS, COMPLY WITH INDIVIDUAL DIVISION 27, COMMUNICATIONS SECTIONS AND
THE FOLLOWING:
1. SYSTEM CANNOT BE CONSIDERED FOR ACCEPTANCE UNTIL WORK IS COMPLETED AND DEMONSTRATED TO ARCHITECT THAT
INSTALLATION IS IN STRICT COMPLIANCE WITH SPECIFICATIONS, DRAWINGS AND MANUFACTURER'S INSTALLATION INSTRUCTIONS,
PARTICULARLY IN REFERENCE TO FOLLOWING:
A. TESTING REPORTS
B. CLEANING
C. OPERATION AND MAINTENANCE MANUALS
D. TRAINING OF OPERATING PERSONNEL
E. RECORD DRAWINGS
2014-0284
DATE
DATE
SHEET NUMBER
E6.2
F. WARRANTY AND GUARANTY CERTIFICATES, INCLUDING EXTENDED MANUFACTURER'S WARRANTIES.
G. START-UP/TEST DOCUMENTS AND COMMISSIONING REPORTS
A. FIRESTOPPING: PROVIDE FIRE BARRIER PENETRATION SEALING MATERIALS AS SPECIFIED IN DIVISION 07, FIRESTOPPING SECTION.
C. SECURELY ATTACH ABOVEGROUND CONDUIT UNDER THE PROVISIONS OF THIS SECTION.
DUST-TIGHT DUCT PLUGS.
3.15 FIELD QUALITY CONTROL
2.06 PULL BOXES
D. ONLY CONDUIT SERVICING ELEVATOR EQUIPMENT CAN BE INSTALLED THROUGH ELEVATOR SHAFTS OR EQUIPMENT ROOMS. THESE
CONDUITS MAY ONLY ENTER THE ROOM AND GO DIRECTLY TO THE EQUIPMENT BEING SUPPLIED.
A. CONFIRM FIELD QUALITY CONTROL REQUIREMENTS IN DIVISION 00, PROCUREMENT AND CONTRACTING REQUIREMENTS AND DIVISION
01, GENERAL REQUIREMENTS, SECTION 27 00 00, COMMUNICATIONS BASIC REQUIREMENTS AND INDIVIDUAL DIVISION 27,
COMMUNICATIONS SECTIONS.
A. CONSTRUCTION: NEMA STANDARD NO. 250. TYPE 1 GALVANIZED STEEL ENCLOSURES DESIGNED FOR USE AS JUNCTION BOXES AND
PULL BOXES WITH FLAT SCREW-APPLIED COVERS, WITH OR WITHOUT KNOCKOUTS, AND GRAY ENAMEL FINISH.
E. KEEP POWER WIRING INDEPENDENT OF COMMUNICATION SYSTEM WIRING.
2.07 INNERDUCT
F. ARRANGE CONDUIT TO MAINTAIN HEADROOM AND PRESENT NEAT APPEARANCE.
A. INDOOR INNERDUCT: 1-1/4-INCH INSIDE DIAMETER CORRUGATED, RIBBED, OR SMOOTH WALLED, SEMI RIGID NONFLAMMABLE PVC
TUBING, WHICH MEETS UL94V-O VERTICAL FLAME TEST FOR GENERAL APPLICATIONS.
G. DO NOT INSTALL CONDUITS ON SURFACE OF BUILDING EXTERIOR, ACROSS ROOF, ON TOP OF PARAPET WALLS, OR ACROSS FLOORS,
UNLESS OTHERWISE NOTED ON DRAWINGS.
B. PLENUM-LISTED INDOOR INNERDUCT: 1-1/4-INCH INSIDE DIAMETER CORRUGATED WALLED INNERDUCT FOR USE IN PLENUM AIR
HANDLING SPACES.
H. EXPOSED CONDUITS ARE PERMITTED ONLY IN THE FOLLOWING AREAS:
1. MECHANICAL ROOMS, ELECTRICAL ROOMS OR SPACES WHERE WALLS, CEILINGS AND FLOORS WILL NOT BE COVERED WITH FINISHED
MATERIAL.
2. EXISTING WALLS THAT ARE CONCRETE OR BLOCK CONSTRUCTION.
3. WHERE SPECIFICALLY NOTED ON DRAWINGS.
4. ROUTE EXPOSED CONDUIT PARALLEL AND PERPENDICULAR TO WALLS, TIGHT TO FINISHED SURFACES AND NEATLY OFFSET INTO
BOXES.
3.16 GROUNDING
B. TESTS:
1. CONDUCT TESTS OF EQUIPMENT AND SYSTEMS TO DEMONSTRATE COMPLIANCE WITH REQUIREMENTS SPECIFIED. REFERENCE
INDIVIDUAL SPECIFICATION SECTIONS FOR REQUIRED TESTS. DOCUMENT TESTS AND INCLUDE IN OPERATION AND MAINTENANCE
MANUALS.
2. DURING SITE EVALUATIONS BY ARCHITECT OR ENGINEER, PROVIDE APPROPRIATE PERSONNEL WITH TOOLS TO REMOVE AND
REPLACE TRIMS, COVERS, AND DEVICES SO THAT PROPER EVALUATION OF INSTALLATION
CAN BE PERFORMED.
END OF SECTION
SECTION 27 1300 COMMUNICATIONS BACKBONE CABLING
C. INDOOR PLENUM-RATED TWO-CELL FABRIC INNERDUCT WITH PULL STRING. MAXCELL OR APPROVED EQUIVALENT.
3.16 LETTER OF CONFORMANCE
2.08 INNERDUCT FITTINGS
A. PROVIDE LETTER OF CONFORMANCE, COPIES OF MANUFACTURERS' WARRANTIES AND EXTENDED WARRANTIES
WITH A STATEMENT THAT COMMUNICATIONS ITEMS WERE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S
RECOMMENDATIONS, UL LISTINGS AND FM GLOBAL APPROVALS. INCLUDE LETTER OF CONFORMANCE, COPIES
OF MANUFACTURERS' WARRANTIES AND EXTENDED WARRANTIES IN OPERATION AND MAINTENANCE MANUALS.
END OF SECTION
SECTION 27 0528 PATHWAYS FOR COMMUNICATIONS SYSTEMS
PART 1 - GENERAL
A. PROVIDE GROUND CONNECTIONS AND BONDING CONTINUITY BETWEEN RACEWAY AND WIRE BASKET RUNWAY SECTIONS, BOXES,
ENCLOSURES, CABINETS, AND FITTINGS AS REQUIRED PER CODE AND INDUSTRY STANDARD.
A. COUPLINGS: METALLIC OR NONMETALLIC QUICK-CONNECT, REVERSE THREADED, AND SCHEDULE 40 COUPLINGS FOR CONNECTING
SECTIONS OF INSTALLED INNERDUCT.
B. CONDUIT PLUGS: COMPRESSION-TYPE CONDUIT PLUGS WITH LOCKING NUTS FOR SEALING AND SECURING THE OUTSIDE WALLS OF
ONE OR MORE INNERDUCT ENDS TO THE INSIDE WALL OF 4-INCH INSIDE DIAMETER CONDUITS, E.G.:
1. FOUR 1-INCH INNERDUCT CONFIGURATION.
2. THREE 1-1/4-INCH INNERDUCT CONFIGURATION.
C. INNERDUCT PLUGS: 1-1/4-INCH COMPRESSION-TYPE INNERDUCT PLUGS FOR SEALING INNERDUCTS, WITH WING NUT FOR HAND
TIGHTENING AND EYEBOLT FOR SECURING PULLTAPE.
I. DO NOT INSTALL CONDUITS OR OTHER ELECTRICAL EQUIPMENT IN OBVIOUS PASSAGES, DOORWAYS, SCUTTLES OR CRAWL SPACES
WHICH WOULD IMPEDE OR BLOCK AREA PASSAGE'S INTENDED USAGE.
1.01 SUMMARY
A. WORK INCLUDED:
1. COPPER BACKBONE CABLE
2. FIBER OPTIC BACKBONE CABLE
3. COPPER TERMINATION HARDWARE
4. FIBER OPTIC TERMINATION HARDWARE
5. COPPER PATCH (JUMPER) CORDS
6. FIBER OPTIC PATCH (JUMPER) CORDS
717 Market Street
Suite 500
San Francisco, CA 94103
TEL
415.489.7240
FAX 415.489.7289
www.interfaceengineering.com
1.02 RELATED SECTIONS
J. KEEP CONDUITS A MINIMUM OF 12-INCHES AWAY FROM STEAM OR HOT WATER RADIANT HEATING LINES (AT OR ABOVE 104 DEGREES
F) OR 3-INCHES AWAY FROM WASTE OR WATER LINES.
K. RUN EXPOSED AND CONCEALED CONDUITS PARALLEL OR PERPENDICULAR TO WALLS, STRUCTURAL MEMBERS, OR INTERSECTIONS
OF VERTICAL PLANES TO PROVIDE A NEAT APPEARANCE. FOLLOW SURFACE CONTOURS AS MUCH AS POSSIBLE.
L. NO SECTION OF CONDUIT LOCATED WITHIN BUILDINGS TO EXCEED 100-FEET IN LENGTH BETWEEN PULL POINTS AND/OR PULL BOXES.
1.01 SUMMARY
PART 1 - GENERAL
A. CONTENTS OF DIVISION 27, COMMUNICATIONS AND DIVISION 01, GENERAL REQUIREMENTS APPLY TO THIS SECTION.
1.03 REFERENCES AND STANDARDS
A. REFERENCES AND STANDARDS AS REQUIRED BY SECTION 27 00 00, COMMUNICATIONS BASIC REQUIREMENTS AND DIVISION 01,
GENERAL REQUIREMENTS.
D. INNERDUCT CAPS: REMOVABLE PUSH-IN CAPS FOR PLUGGING 1-1/4-INCH INNERDUCT.
3.01 WORKMANSHIP
A. PROVIDE, CONDITION, APPLY, INSTALL, CONNECT, AND TEST MANUFACTURED PRODUCTS, MATERIALS, EQUIPMENT, AND
COMPONENTS IN ACCORDANCE WITH THE MANUFACTURER'S SPECIFICATIONS AND PRINTED INSTRUCTIONS.
B. THIS SECTION SPECIFIES THE REQUIREMENTS TO PROVIDE COMMUNICATIONS CONDUIT RACEWAYS, BOXES, CABLE TRAYS,
INNERDUCT AND FITTINGS.
B. THE INSTALLATION OF SYSTEM COMPONENTS TO BE CARRIED OUT UNDER THE DIRECTION OF QUALIFIED PERSONNEL. APPEARANCE
TO BE CONSIDERED AS IMPORTANT AS MECHANICAL AND ELECTRICAL EFFICIENCY. WORKMANSHIP TO MEET OR EXCEED INDUSTRY
STANDARDS.
1.02 RELATED SECTIONS
C. PLACE SUPPORT FOR FRAMING, RACEWAYS, CABLE TRAYS, BACKBOARDS, EQUIPMENT RACKS, AND CABINETS.
A. CONTENTS OF DIVISION 27, COMMUNICATIONS AND DIVISION 01, GENERAL REQUIREMENTS APPLY TO THIS SECTION.
3.02 PROTECTION DURING CONSTRUCTION
1.03 REFERENCES AND STANDARDS
A. PROTECT PRODUCTS FROM THE EFFECTS OF MOISTURE, CORROSION, AND PHYSICAL DAMAGE DURING CONSTRUCTION. EXCEPT
DURING INSTALLATION ACTIVITY IN A SECTION, KEEP OPENINGS IN CONDUIT, TUBING, AND WIREWAY CAPPED WITH MANUFACTURED
SEALS DURING CONSTRUCTION.
A. REFERENCES AND STANDARDS AS REQUIRED BY SECTION 27 00 00, COMMUNICATIONS BASIC REQUIREMENTS AND DIVISION 01,
GENERAL REQUIREMENTS.
M. EXPANSION/DEFLECTION JOINTS:
1. WHERE INDICATED ON THE DRAWINGS, PROVIDE SPECIFIC PURPOSE EXPANSION/DEFLECTION FITTINGS FOR CONDUIT CROSSING
BUILDING EXPANSION/DEFLECTION JOINTS IN STRUCTURES OR CONCRETE SLABS. EXPANSION FITTINGS TO HAVE COPPER BONDING
JUMPER.
2. FOR PVC CONDUIT, PROVIDE EXPANSION/DEFLECTION JOINTS FOR 25 DEGREES F MAXIMUM TEMPERATURE VARIATION. INSTALL IN
ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.
3. FOR RIGID STEEL CONDUIT LOCATED IN EXTERIOR AREAS, PROVIDE EXPANSION/DEFLECTION JOINTS FOR MAXIMUM SITE
TEMPERATURE VARIATION, INSTALLED IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.
N. PROVIDE EACH CONDUIT PASSING FROM A NONHAZARDOUS OR NONCORROSIVE AREA TO A HAZARDOUS AREA AND EACH CONDUIT
ENTERING AN ENCLOSURE WITHIN A HAZARDOUS AREA WITH A SEALING FITTING IN ACCORDANCE WITH NEC ARTICLE 500. THE SEALING
FITTING TO BE UL LISTED AND TO BE FILLED WITH APPROVED SEALING COMPOUND OF THE SAME MANUFACTURE.
O. HUBS, BUSHINGS, AND INSULATING SLEEVES:
1. INTERIOR BOX AND CABINET CONNECTIONS: INSTALL INSULATING THROAT CONNECTORS WHEREVER CONDUIT TERMINATES IN
BOXES OR CABINETS. IN ADDITION, INSTALL BONDING TYPE LOCKNUTS AT METALLIC CONDUIT TERMINATIONS.
2. WET AND HAZARDOUS BOX AND CABINET CONNECTIONS: USE WATERTIGHT THREADED CONDUIT SEALING HUBS WITH INSULATED
THROAT AND BONDING TYPE LOCKNUTS FOR FASTENING RIGID STEEL CONDUIT TO CAST OR SHEET METAL PULL BOXES.
3. EXPOSED CONDUIT TERMINATIONS: CAP EXPOSED STEEL COMMUNICATION CONDUIT ENDS WITH BUSHINGS OR SMOOTH COLLARS TO
PROTECT CABLE SHEATH.
3.03 MINIMUM CONDUIT SIZE
1.04 SUBMITTALS
A. 4-INCH FOR UNDERGROUND APPLICATIONS UNLESS OTHERWISE INDICATED ON THE DRAWINGS.
A. SUBMITTALS AS REQUIRED BY SECTION 27 00 00, COMMUNICATIONS BASIC REQUIREMENTS AND DIVISION 01, GENERAL
REQUIREMENTS.
B. PROVIDE PLAN DRAWINGS SHOWING COMPLETIONS AND AS-BUILT CORRECTIONS WHICH INDICATE TYPE, SIZE, PLACEMENT, ROUTING,
AND/OR LENGTH FOR RACEWAY AND CABLE TRAY COMPONENTS; E.G., MANHOLES, HANDHOLES, CONDUIT, WIREWAY, BOXES,
ENCLOSURES, ETC.
1.05 QUALITY ASSURANCE
B. SIZE RECESSED CONDUITS TO SURFACE RACEWAY SERVING MULTIPLE DATA OUTLETS AS FOLLOWS. SIZING IS BASED ON TIA/EIA
569-B FOR 28 PERCENT CONDUIT FILL, ASSUMING CATEGORY 5E OR 6 CABLES (NOMINAL OUTER DIAMETER 0.24-INCH) TO EACH DATA
OUTLET. PROVIDE RECESSED BACKBOX BETWEEN SURFACE RACEWAY AND RECESSED CONDUIT SIZED FOR CONDUIT.
1 TO 6 CABLES 1-INCH CONDUIT
7 TO 10 CABLES 1-1/4-INCH CONDUIT
11 TO 15 CABLES 1-1/2-INCH CONDUIT
16 TO 20 CABLES 2-INCH CONDUIT
ABOVE 20 CABLES USE MULTIPLE RUNS OF CONDUIT FROM SURFACE RACEWAY BASED ON ABOVE TABLE
A. QUALITY ASSURANCE AS REQUIRED BY SECTION 27 00 00, COMMUNICATIONS BASIC REQUIREMENTS AND DIVISION 01, GENERAL
REQUIREMENTS.
3.04 MINIMUM BACKBONE CONDUIT REQUIREMENTS
1.06 WARRANTY
A. INSTALL THREE 4-INCH CONDUITS FROM MER TO EACH TR, UNLESS OTHERWISE NOTED ON DRAWINGS.
A. WARRANTY OF MATERIALS AND WORKMANSHIP AS REQUIRED BY SECTION 27 00 00, COMMUNICATIONS BASIC REQUIREMENTS AND
DIVISION 01, GENERAL REQUIREMENTS.
3.05 CONDUIT TYPE
1.07 DEFINITIONS
A. CABINET: A FREESTANDING FLOOR-MOUNTED MODULAR ENCLOSURE DESIGNED TO HOUSE AND PROTECT RACK-MOUNTED
ELECTRONIC EQUIPMENT.
B. CONDUIT: ROUND RACEWAY.
C. CONDUIT BODY: SEPARATE PORTION OF A CONDUIT OR TUBING SYSTEM THAT PROVIDES ACCESS THROUGH REMOVABLE COVER(S)
TO THE INTERIOR OF THE SYSTEM AT A JUNCTION OF TWO OR MORE SECTIONS OF THE SYSTEM OR AT A TERMINAL POINT OF THE
SYSTEM.
D. PULL BOX ENCLOSURE: BOX WITH A COVER INSTALLED IN ONE OR MORE RUNS OF RACEWAY TO FACILITATE PULLING CONDUCTORS
THROUGH THE RACEWAY SYSTEM. THERE ARE NO OPENINGS IN THE COVER.
E. RACEWAY: ENCLOSED CHANNEL DESIGNED EXPRESSLY FOR HOLDING WIRES OR CABLES. METAL OR INSULATING MATERIAL, AND
THE TERM INCLUDES CONDUIT, TUBING, WIREWAYS, UNDERFLOOR RACEWAYS, AND SURFACE RACEWAYS; DOES NOT INCLUDE CABLE
TRAY.
F. SURFACE RACEWAY: SURFACE-MOUNTED METAL CHANNEL OR PLASTIC DUCT WITH SNAP-IN REMOVABLE COVERS FOR HOUSING AND
PROTECTING ELECTRICAL WIRES AND CABLES. RACEWAY AND FITTINGS ARE DESIGNED SO SECTIONS CAN BE ELECTRICALLY AND
MECHANICALLY COUPLED TOGETHER WITHOUT SUBJECTING
CABLES TO ABRASION.
G. WIREWAY: SHEET METAL OR NONMETALLIC TROUGHS WITH HINGED OR REMOVABLE COVERS FOR HOUSING AND PROTECTING
ELECTRICAL WIRES AND CABLES AND IN WHICH CONDUCTORS ARE LAID IN PLACE AFTER THE WIREWAY HAS BEEN INSTALLED AS A
COMPLETE SYSTEM.
P. FLEXIBLE CONDUIT:
1. MAKE NO BENDS IN FLEXIBLE CONDUIT THAT EXCEED ALLOWABLE BENDING RADIUS OF THE CABLE TO BE INSTALLED OR THAT
SIGNIFICANTLY RESTRICTS THE CONDUIT'S FLEXIBILITY.
2. A FLEXIBLE CONDUIT SECTION TO BE LONG ENOUGH TO ALLOW THE ITEM TO WHICH IT IS CONNECTED TO BE WITHDRAWN OR MOVED
OFF ITS BASE.
3. FOR FINAL CONNECTION TO TELECOMMUNICATIONS OUTLETS OR EQUIPMENT, WHERE FLEXIBLE CONNECTION IS REQUIRED TO
MINIMIZE VIBRATION OR WHERE REQUIRED TO FACILITATE REMOVAL OR ADJUSTMENT OF EQUIPMENT, PROVIDE 12-FOOT MINIMUM
LENGTHS OF FLEXIBLE CONDUIT OR AS INDICATED ON THE DRAWINGS.
3.09 PULLTAPE AND DUCT PLUGS
A. FOLLOWING CONDUIT INSTALLATION, INSTALL PULLTAPE (MULETAPE) WITH PREPRINTED FOOT MARKERS IN EACH EMPTY CONDUIT
CONTAINING A BEND OR OVER 10-FEET IN LENGTH, EXCEPT SLEEVES, NIPPLES. TIE THE PULLTAPES SECURELY AT EACH END.
B. IMMEDIATELY AFTER PULLTAPE INSTALLATION, INSTALL REMOVABLE MANUFACTURED PLUGS IN EMPTY CONDUIT AND WIREWAY
OPENINGS. FOR UNDERGROUND CONDUIT OPENINGS, USE SCREWTIGHT, REMOVABLE, WATERTIGHT, AND DUST-TIGHT DUCT PLUGS.
C. VERIFY LENGTHS AT THE TIME OF INSTALLATION AND PROVIDE AS-BUILT DOCUMENTATION.
A. INSTALL THE FOLLOWING TYPES OF CIRCULAR COMMUNICATIONS RACEWAY IN THE LOCATIONS LISTED UNLESS OTHERWISE
INDICATED ON THE DRAWINGS.
1. INTERIOR DRY LOCATIONS, EXPOSED: EMT WITH SET SCREW FITTINGS.
2. INTERIOR DRY LOCATIONS, CONCEALED (NOT EMBEDDED IN CONCRETE): EMT WITH SET SCREW FITTINGS.
3. INTERIOR WET LOCATIONS: EMT WITH COMPRESSION FITTINGS.
4. EXTERIOR, EXPOSED INCLUDING ROOF: RIGID STEEL CONDUIT.
5. EXTERIOR, UNDERGROUND: PVC SCHEDULE 40 CONDUIT.
6. CONCRETE-ENCASED DUCT BANKS:
A. PVC SCHEDULE 40 CONDUIT.
B. RIGID STEEL CONDUIT WHEN ADDITIONAL PROTECTION IS REQUIRED.
7. FLEXIBLE CONDUIT (INTERIOR EXPOSED):
A. LIQUIDTIGHT FLEXIBLE METAL CONDUIT FOR USE WITH COPPER CABLE.
B. LIQUIDTIGHT FLEXIBLE NONMETALLIC CONDUIT FOR USE WITH FIBER OPTIC CABLE.
3.10 WIREWAY TYPE
A. INSTALL THE FOLLOWING TYPES OF WIREWAY IN THE LOCATIONS LISTED UNLESS OTHERWISE INDICATED ON THE DRAWINGS:
1. INTERIOR, EXPOSED: STEEL.
2. INTERIOR, CONCEALED: NOT APPROVED.
3. EXTERIOR, EXPOSED: STEEL OR NONMETALLIC.
3.11 WIREWAY INSTALLATION
A. INSTALL WIREWAY, AS INDICATED ON THE DRAWINGS.
PART 2 - PRODUCTS
2.01 MANUFACTURERS
A. AS SPECIFIED IN ARTICLES BELOW.
A. RACEWAYS: LABELED AND/OR LISTED AS ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION (AHJ) AS SUITABLE FOR THE USE
INTENDED.
B. TABLE 1: PRODUCT IDENTIFICATION:
PRODUCT DESIGNATION PRODUCT TYPE
EMT GALVANIZED STEEL TUBING
PVC POLYVINYLCHLORIDE CONDUIT
LMC LIQUIDTIGHT METAL CONDUIT
LNC LIQUIDTIGHT NONMETAL CONDUIT
C. THE PRODUCT IDENTIFICATION CODES USED FOR THE COMMUNICATIONS RACEWAYS AND BOXES IN PART 2, PRODUCTS, ARE
SUMMARIZED IN TABLE 1.
D. MANUFACTURERS:
1. KOPPERS BITUMASTIC
2. SCOTCHWRAP
3. OR APPROVED EQUIVALENT.
E. BITUMASTIC MATERIAL OR PLASTIC TAPE.
2.03 ELECTRICAL METALLIC TUBING AND FITTINGS
C. ATTACH WIREWAYS AND RELATED MATERIALS UNDER THE PROVISIONS OF THIS SECTION.
A. MAKE CHANGES IN DIRECTION OF COMMUNICATIONS CONDUIT RUNS WITH SWEEPS OF THE LONGEST POSSIBLE RADIUS.
D. RUN EXPOSED WIREWAYS PARALLEL OR PERPENDICULAR TO WALLS, STRUCTURAL MEMBERS, OR INTERSECTIONS OF VERTICAL
PLANES TO MAINTAIN HEADROOM AND PROVIDE A NEAT APPEARANCE.
B. IN ADDITION, PROVIDE:
1. SHOP DRAWINGS THAT INCLUDE, BUT ARE NOT LIMITED TO, THE FOLLOWING: TELECOMMUNICATION ROOM LAYOUT,
TELECOMMUNICATION ROOM WALL ELEVATIONS, EQUIPMENT RACK ELEVATIONS, CABLE ROUTING, CABLE CONNECTING DIAGRAMS,
TERMINATION PIN OUTS, SUPPORTING HARDWARE DETAILS, BLOCK DIAGRAMS, RISER DIAGRAMS AND CABLE PATHWAYS. WORK MAY
NOT BEGIN UNTIL SHOP DRAWINGS ARE APPROVED. NOTE: INTENT OF SUBMITTING SHOP DRAWINGS IS FOR CONTRACTORS TO DISPLAY
A CONCEPTUAL UNDERSTANDING OF THE ISSUED ENGINEER DRAWINGS. DO NOT SUBMIT ENGINEER DRAWINGS ON YOUR TITLE BLOCK.
2. PROCEDURES FOR CABLE LABELING AND IDENTIFICATION, LONG TERM DOCUMENTATION METHODS AND NUMBERING SCHEME IN
ACCORDANCE WITH ANSI/TIA/EIA- 606-A.
3. A COPY OF CERTIFIED INSTALLER CERTIFICATES AND WARRANTY CERTIFICATES FOR PRODUCTS PROPOSED.
1.05 QUALITY ASSURANCE
A. QUALITY ASSURANCE AS REQUIRED BY SECTION 27 00 00, COMMUNICATIONS BASIC REQUIREMENTS AND DIVISION 01, GENERAL
REQUIREMENTS.
B. MANUFACTURERS TO HAVE A RECOGNIZED CERTIFIED INSTALLER PROGRAM IN PLACE FOR SYSTEM COMPONENTS PROPOSED.
CABLE WILL BE APPROVED WITH MANUFACTURER SYSTEM INSTALLED.
1.06 WARRANTY
A. WARRANTY OF MATERIALS AND WORKMANSHIP AS REQUIRED BY SECTION 27 00 00, COMMUNICATIONS BASIC REQUIREMENTS AND
DIVISION 01, GENERAL REQUIREMENTS.
B. IN ADDITION, PROVIDE:
1. LABOR, MATERIALS, AND DOCUMENTATION ACCORDING TO SELECTED MANUFACTURER REQUIREMENTS NECESSARY TO ENSURE
THAT THE OWNER WILL BE FURNISHED WITH AN EXTENDED PRODUCT WARRANTY AND APPLICATION ASSURANCE OF A MINIMUM OF 20
YEARS IN LENGTH. THE APPLICATION ASSURANCE WARRANTY WILL COVER THE FAILURE OF THE WIRING SYSTEM TO SUPPORT
CURRENT OR FUTURE APPLICATIONS THAT ARE DESIGNED FOR THE LINK/CHANNEL SPECIFICATIONS OF ANSI/TIA/EIA-568-C. THESE
APPLICATIONS INCLUDE, BUT ARE NOT LIMITED TO, 10BASE-T, 100BASE-T, 1000BASE-T, 10GBASE-T, AND 155 MB/S ATM.
2. PROVIDE A WARRANTY ON THE PHYSICAL INSTALLATION.
3. FURNISH NECESSARY DOCUMENTATION REQUIRED BY THE MANUFACTURER IMMEDIATELY FOLLOWING 100 PERCENT TESTING OF
CABLES.
4. ADMINISTER THE WARRANTY PROCESS WITH THE RESPONSIBLE MANUFACTURER'S REPRESENTATIVE. PROVIDE WARRANTY DIRECTLY
TO THE OWNER FROM THE MANUFACTURER. ENSURE THAT THE MANUFACTURER PROVIDES THE OWNER WITH THE APPROPRIATE
WARRANTY CERTIFICATION WITHIN 90 CALENDAR DAYS OF THE FINAL PROJECT COMPLETION.
1.07 SYSTEM DESCRIPTION
A. PROVIDE A STANDARDS-BASED CABLE SYSTEM TO SERVE BACKBONE COMMUNICATION SYSTEMS REQUIREMENTS AS SPECIFIED IN
THESE SPECIFICATIONS AND SHOWN ON DRAWINGS. CLOSELY FOLLOW ANSI/TIA/EIA, IEEE AND ISO STANDARDS WHICH APPLY TO
BACKBONE COMMUNICATION SYSTEMS.
B. INSTALL INTRABUILDING BACKBONE CABLES FROM EXISTING OR ERS TO TRS THROUGH RACEWAY SYSTEMS AS SHOWN ON
DRAWINGS.
2.01 MANUFACTURERS
B. MAKE SWEEPS IN PARALLEL OR BANKED RUNS OF CONDUITS, 2-INCHES AND LARGER IN DIAMETER, FROM THE SAME CENTER OR
CENTERLINE SO THAT SWEEPS ARE PARALLEL AND OF NEAT APPEARANCE.
C. FIELD-MADE BENDS AND SWEEPS:
1. USE AN ACCEPTABLE HICKEY OR CONDUIT-BENDING MACHINE.
2. DO NOT HEAT METAL RACEWAYS TO FACILITATE BENDING.
3. BEFORE INSTALLING 4-INCH FIELD-MADE SWEEPS IN DUCT BANKS, PULL A 3-1/2-INCH DIAMETER BY 12-INCH LONG MANDREL THROUGH
DUCT SECTIONS TO VERIFY CIRCULARITY AND SWEEP RADIUS.
E. CLOSE DEAD ENDS OF WIREWAY WITH FITTINGS BY THE SAME MANUFACTURER.
F. GASKET EACH JOINT IF IN OILTIGHT GUTTER.
2.02 COPPER BACKBONE CABLE
H. MAINTAIN GROUNDING CONTINUITY BETWEEN RACEWAY COMPONENTS TO PROVIDE A CONTINUOUS GROUNDING
PATH.
3.12 RACEWAY IDENTIFICATION BANDING
E. MINIMUM INSIDE BEND RADIUS FOR COMMUNICATIONS CONDUIT BENDS, SWEEPS, BOXES, AND FITTINGS:
1. UNDERGROUND OR UNDERSLAB 4-INCH CONDUIT: 60-INCHES.
2. OTHER CONDUIT RUNS:
A. ONE-INCH CONDUIT, 11-INCHES
B. TWO-INCH CONDUIT, 21-INCHES
C. THREE-INCH CONDUIT, 36-INCHES
D. FOUR-INCH CONDUIT, 48-INCHES
E. OTHER SIZES, 10 TIMES THE INSIDE DIAMETER OF THE CONDUIT.
F. DO NOT INSTALL BOXES, BENDS, ELBOWS, TEES, CONDUIT BODIES, AND OTHER CONDUIT FITTINGS, WHICH DO NOT PROVIDE FOR THE
MINIMUM INSIDE CABLE BEND RADIUS SPECIFIED IN PARAGRAPH E ABOVE.
1. CONDUIT BODIES: IN-LINE STRAIGHT-THROUGH TYPE C CONDULET FITTINGS CAN BE USED AS PULL BOXES FOR CONDUIT UP TO A
MAXIMUM OF 2-INCHES ID. OTHER CONDUIT FITTINGS, WHICH INCLUDE DIRECTION CHANGES SUCH AS E, L, LB, LR, LL, LRT, TA, TB, AND X,
ARE NOT ALLOWED.
2. REFER DESIGN OR INSTALLATION CONFLICTS WITH THESE REQUIREMENTS TO THE ARCHITECT.
A. PROVIDE LIKE ITEMS FROM ONE MANUFACTURER, SUCH AS JACKS, PATCH PANELS, EQUIPMENT CONNECTION CORDS, AND WALL
PLATES. THE FOLLOWING MANUFACTURERS/SOLUTIONS ARE PREAPPROVED.
1. COMMSCOPE SYSTIMAX OR UNIPRISE
2. ORTRONICS/BERK-TEK
3. PANDUIT /GENERAL
4. OR APPROVED EQUIVALENT.
G. MOUNT RAINTIGHT GUTTER IN HORIZONTAL POSITION ONLY.
A. DEGREASE AND CLEAN SURFACES TO RECEIVE TAPE LABELS.
B. EXPOSED CONDUITS AND WIREWAY, INCLUDING RACEWAYS ABOVE LAY-IN OR ACCESSIBLE CEILINGS, TOGETHER WITH ASSOCIATED
PULL BOXES TO BE BANDED AT INTERVALS OF NOT OVER 10-FEET AND AT DIRECTION CHANGES. TWO-BAND IDENTIFICATION TO BE
DIFFERENT CONTRASTING COLORS AS FOLLOWS:
RACEWAY USE COLOR
GROUNDING GREEN
TELECOM/DATACOM YELLOW
CCTV WHITE
BUILDING MONITORING AND SECURITY GREY
3.13 INNERDUCT TYPE
A. INTRABUILDING: 100 OHM, CAT 3, 24 AWG, ARMM MULTI-PAIR CABLE WITH AN UNDERLYING OVERALL METALLIC SHIELD.
1. RISER RATED, CMR RATED JACKET.
2. PLENUM RATED, CMP RATED JACKET.
B. INTRABUILDING DISTRIBUTION, WITHOUT OVERALL SHIELD: 100 OHM, CAT 3, 24 AWG, MULTI-PAIR CABLE.
1. RISER RATED, CMR RATED JACKET.
2. PLENUM RATED, CMP RATED JACKET.
2.03 FIBER OPTIC BACKBONE CABLE
A. INTRABUILDING MULTIMODE RISER: 24 STRAND, 50/125 MICRON, LASER OPTIMIZED DISTRIBUTION CABLE WITH MAXIMUM
ATTENUATION OF 3.5 DB/KM AT 850 NM AND 1.5 DB/KM AT 1300 NM. MINIMUM BANDWIDTH IS 200, 500, OR 2000 MHZ-KM AT 850 NM AND 500
MHZ-KM AT 1300 NM. OFNR RATED.
B. INTRABUILDING MULTIMODE PLENUM: 24 STRAND, 50/125 MICRON, LASER OPTIMIZED DISTRIBUTION CABLE WITH MAXIMUM
ATTENUATION OF 3.5 DB/KM AT 850 NM AND 1.5 DB/KM AT 1300 NM. MINIMUM BANDWIDTH IS 200, 500, OR 2000 MHZ-KM AT 850 NM AND 500
MHZ-KM AT 1300 NM. OFNP RATED.
A. UNDERSLAB AND UNDERGROUND CONDUIT INSTALLATION: OUTDOOR INNERDUCT.
2.04 COPPER TERMINATION HARDWARE
3.07 PENETRATIONS
B. ABOVEGROUND, EXTERIOR, AND INTERIOR CONDUIT INSTALLATIONS: INDOOR INNERDUCT.
A. SEAL CONDUIT ENTERING STRUCTURES AT THE FIRST BOX OR OUTLET TO PREVENT THE ENTRANCE OF GASES, LIQUIDS, OR RODENTS
INTO THE STRUCTURE.
1. EMPTY CONDUITS: REMOVABLE SCREWTIGHT DUCT PLUGS.
2. INNERDUCT INSTALLED: SUITABLE DUCT WATER SEAL BETWEEN CONDUIT AND INNERDUCT. MANUFACTURED SEALS IN EMPTY
INNERDUCT.
3. CABLE INSTALLED: SUITABLE DUCT WATER SEAL BETWEEN CONDUIT AND CABLE, OR BETWEEN INNERDUCT AND CABLE.
C. INTERIOR EXPOSED LOCATIONS INCLUDING CABLE TRAY INSTALLATIONS:
1. NONPLENUM AREAS: INDOOR INNERDUCT.
2. PLENUM AREAS: PLENUM-LISTED INNERDUCT.
B. CONCRETE SLEEVES: CONDUITS ROUTED PERPENDICULAR THROUGH FLOORS, WALLS, OR OTHER CONCRETE STRUCTURES TO PASS
THROUGH CAST-IN-PLACE CONDUIT SLEEVE OPENINGS WHEREVER POSSIBLE, OR APPROPRIATE SIZE HOLES TO BE BORED TO
ACCOMMODATE THE INSTALLATION OF CONDUIT SLEEVES. THE SIZE AND LOCATION OF THE HOLES TO NOT IMPAIR THE STRUCTURE'S
INTEGRITY.
1. CONCRETE BORING: BORE A HOLE IN THE CONCRETE WITH A DIAMETER OF 1/2 TO 1-INCH LARGER THAN THE CONDUIT SLEEVE TO BE
INSTALLED. GROUT AROUND THE CONDUIT SLEEVE AND FINISH TO MATCH EXISTING SURROUNDINGS.
2. CONDUITS THAT RISE VERTICALLY THROUGH A SLAB TO BE STUBBED 6-INCHES ABOVE THE FLOOR AND CAPPED PENDING FUTURE
USE.
A. PULL INNERDUCT THROUGH CONDUIT AND WIREWAYS, OR PLACE INNERDUCT IN CABLE TRAYS USING CONTINUOUS UNSPLICED
LENGTHS OF INNERDUCT BETWEEN PULL BOXES, AND/OR SECTION TERMINATION POINTS AS INDICATED ON THE DRAWINGS.
A. CATEGORY 5E MODULAR PATCH PANELS:
1. 24 PORT, 8-POSITION MODULAR JACK PANEL, HIGH DENSITY, 6 PORT MODULES, ENHANCED CATEGORY 5E, IDC TERMINALS, T568A/B
WIRING SCHEME.
2. 48 PORT, 8-POSITION MODULAR JACK PANEL, HIGH DENSITY, 6 PORT MODULES, ENHANCED CATEGORY 5E, IDC TERMINALS, T568A/B
WIRING SCHEME.
3. 24 PORT, 8-POSITION MODULAR JACK PANEL, HIGH DENSITY, 8 PORT MODULES, ENHANCED CATEGORY 5E, IDC TERMINALS, T568A/B
WIRING SCHEME.
4. 48 PORT, 8-POSITION MODULAR JACK PANEL, HIGH DENSITY, 8 PORT MODULES, ENHANCED CATEGORY 5E, IDC TERMINALS, T568A/B
WIRING SCHEME.
B. CUT INNERDUCT SQUARE. DEBURR CUT ENDS.
B. WALL-MOUNT TERMINATION FIELDS: WALL-MOUNTED 110-STYLE TERMINATION FRAMES WITH LEGS.
C. BRING INNERDUCT TO THE SHOULDER OF FITTINGS AND COUPLINGS AND FASTEN SECURELY.
2.05 FIBER OPTIC TERMINATION HARDWARE
D. WIPE INNERDUCT AND FITTINGS CLEAN AND DRY BEFORE JOINING. APPLY FULL, EVEN COAT OF CEMENT TO ENTIRE AREA THAT WILL
BE INSERTED INTO FITTING. LET JOINT CURE FOR 20 MINUTES MINIMUM.
A. HIGH DENSITY FIBER TERMINATION SHELF:
1. 7-INCH HIGH SHELF DESIGNED FOR MOUNTING IN 19-INCH EQUIPMENT RACKS AND CAPABLE OF ACCEPTING 12 ADAPTER PANELS. THE
SHELF WILL CONTAIN BUILT-IN SLACK MANAGEMENT AND BE ACCESSIBLE FROM THE FRONT OR REAR WITH LOCKING DOORS.
A. 19-INCH RACK MOUNT, 13-INCHES DEEP.
B. 19-INCH RACK MOUNT, 19-INCHES DEEP.
2. 3.5-INCH HIGH SHELF DESIGNED FOR MOUNTING IN 19-INCH EQUIPMENT RACKS AND CAPABLE OF ACCEPTING 6 ADAPTER PANELS. THE
SHELF WILL CONTAIN BUILT-IN SLACK MANAGEMENT AND BE ACCESSIBLE FROM THE FRONT OR REAR WITH LOCKING DOORS.
A. 19-INCH RACK MOUNT, 13-INCHES DEEP.
B. 19-INCH RACK MOUNT, 19-INCHES DEEP.
3. FIBER ADAPTER PANELS: ADAPTER PANEL FOR HIGH DENSITY TERMINATION SHELF WITH 6 LC MULTIMODE PHOSPHOR-BRONZE
ALIGNMENT SLEEVES.
4. PRELOADED FIBER TERMINATION SHELF:
A. 1.75-INCH HIGH SHELF DESIGNED FOR MOUNTING IN 19-INCH EQUIPMENT RACKS WITH 12 LC MULTIMODE PHOSPHOR-BRONZE
ALIGNMENT SLEEVES. THE SHELF WILL CONTAIN BUILT-IN SLACK MANAGEMENT AND BE ACCESSIBLE FROM THE FRONT OR REAR.
B. 1.75-INCH HIGH SHELF DESIGNED FOR MOUNTING IN 19-INCH EQUIPMENT RACKS WITH 24 LC MULTIMODE PHOSPHOR-BRONZE
ALIGNMENT SLEEVES. THE SHELF WILL CONTAIN BUILT-IN SLACK MANAGEMENT AND BE ACCESSIBLE FROM THE FRONT OR REAR.
3.14 INNERDUCT INSTALLATION
SHEET TITLE
SPECIFICATION TECHNOLOGY
REVISIONS
A. TYPE EMT: ELECTROGALVANIZED STEEL TUBING.
B. FITTINGS AND CONDUIT BODIES:
1. GENERAL: IN-LINE STRAIGHT-THROUGH STEEL OR MALLEABLE IRON FITTINGS AND TYPE C CONDUIT BODIES ONLY; DO NOT USE
BENDS OR TEES, E.G. LBS.
2. WET AREAS: STEEL COMPRESSION-TYPE COUPLINGS AND NIPPLES.
3. DRY AREAS: SET SCREW-TYPE COUPLINGS AND NIPPLES.
4. BONDING LOCKNUTS: MALLEABLE IRON WITH SET SCREWS AND LUG SCREWS.
A. INSULATED BUSHING: MALLEABLE IRON WITH INTEGRAL INSULATED THROAT, RATED FOR 150C.
B. BONDING AND GROUNDING BUSHING: MALLEABLE IRON WITH INTEGRAL INSULATED THROAT, RATED FOR 150C, WITH SOLDERLESS
LUGS OR LUG SCREWS.
A. SUBMITTALS AS REQUIRED BY SECTION 27 00 00, COMMUNICATIONS BASIC REQUIREMENTS AND DIVISION 01, GENERAL
REQUIREMENTS.
PART 2 - PRODUCTS
3.06 CONDUIT BENDS AND SWEEPS
B. OR APPROVED EQUIVALENT.
2.02 RACEWAYS
1.04 SUBMITTALS
B. SECURELY SUPPORT WIREWAYS AT INTERVALS NOT TO EXCEED 5-FEET AND AT EACH END OR JOINT FOR INDIVIDUAL SECTIONS.
D. THE ANGULAR SUM OF THE BENDS BETWEEN PULL POINTS AND/OR PULL BOXES TO NOT EXCEED 180 DEGREES.
H. WIRE BASKET RUNWAY SYSTEMS: INCLUDES, BUT ARE NOT LIMITED TO STRAIGHT SECTIONS OF TYPE WIRE BASKET RUNWAY CABLE
TRAYS, BENDS, TEES, ELBOWS, DROP-OUTS, SUPPORTS AND ACCESSORIES.
B. MEET REQUIREMENTS OF NFPA 780, STANDARDS FOR INSTALLATION OF LIGHTNING PROTECTION SYSTEMS.
C. DRYWALL/GYPSUM BOARD SLEEVES: INSTALL INSULATING THROAT BUSHINGS ON BOTH ENDS OF CONDUIT SLEEVES PLACED IN
FIRE-RATED WALLS USING DRYWALL CONSTRUCTION.
E. PROVIDE SUITABLE INNERDUCT SLACK IN PULL BOXES, AND AT TURNS TO ENSURE THAT THERE IS NO KINKING OR BINDING OF THE
TUBING OR CABLE.
D. WHERE CONDUIT ENTERS A STRUCTURE THROUGH A CONCRETE ROOF OR MEMBRANE WATERPROOFED WALL OR FLOOR:
1. PROVIDE A WATERTIGHT SEAL.
2. WITH CONCRETE ENCASEMENT: INSTALL WATERTIGHT ENTRANCE SEAL DEVICE ON THE ACCESSIBLE SIDE.
3. SECURELY ANCHOR MALLEABLE IRON BODY OF WATERTIGHT ENTRANCE SEAL DEVICE INTO CONSTRUCTION WITH ONE OR MORE
INTEGRAL FLANGES.
4. SECURE MEMBRANE WATERPROOFING TO WATERTIGHT ENTRANCE SEAL DEVICE IN A PERMANENT, WATERTIGHT MANNER.
F. MAKE CHANGES IN DIRECTION OF COMMUNICATIONS INNERDUCT RUNS WITH SWEEPS OF THE LONGEST POSSIBLE RADIUS AND AT
LEAST 10 TIMES THE INSIDE DIAMETER OF THE INNERDUCT.
G. DURING INNERDUCT PULLING, AVOID EXCESSIVE TENSION WHICH CAN DAMAGE THE INNERDUCT. INSPECT INNERDUCT FOLLOWING
PLACEMENT AND REPLACE DAMAGED SECTIONS.
H. INDOOR CONDUIT INSTALLATION:
1. ARRANGE INNERDUCT NEATLY, CUT TO PROPER LENGTH, AND REMOVE SURPLUS. PROVIDE TRAINED AND BUNDLED INNERDUCT
PIGTAILS EXTENDING AT LEAST 18-INCHES BEYOND EXPOSED CONDUIT OPENINGS.
2. AT LOCATIONS WHERE THE ENDS OF INNERDUCT SECTIONS APPEAR IN A PULL BOX, JOIN THE PULLTAPE AND THEN SPLICE
INNERDUCT SECTIONS TOGETHER USING COUPLERS WHICH DO NOT REDUCE THE INSIDE DIAMETER OF THE INNERDUCT.
2.04 CONDUIT ACCESSORIES
E. PROVIDE CONTINUOUS SLEEVING THROUGH WALLS, FLOORS AND CEILINGS SEPARATING EACH TELECOM OUTLET FROM ITS
RESPECTIVE MER/TR ROOM, USING SLEEVE CONDUIT SIZE AS REQUIRED PER STANDARDS. RESTORE PENETRATIONS THROUGH RATED
ASSEMBLIES TO ORIGINAL FIRE RATING PER NFPA AND LOCAL CODES.
A. DUCT SPACERS: NONMETALLIC BASE AND INTERMEDIATE DUCT SPACERS WITH LOCKING KEYWAYS DESIGNED SPECIFICALLY FOR
USE WITH NONMETALLIC CONDUIT; E.G., CARLON SNAP-LOC DUCT SPACERS FOR 4-INCH DIAMETER CONDUIT WITH 1-1/2-INCH
SEPARATION.
1. BASE SPACER: S288NHN.
2. INTERMEDIATE SPACER: S289NHN.
F. LOCATE SLEEVES AS SHOWN ON DRAWINGS. WHERE SLEEVES ARE NOT SHOWN ON DRAWINGS, INSTALL SLEEVES ABOVE
SUSPENDED CEILINGS, AND LOCATE TO MINIMIZE LENGTH OF PATHWAY FOR FUTURE CABLE FROM TELECOM OUTLET TO MER/TR
ROOMS.
I. CABLE TRAY INSTALLATION: TIE WRAP OR VELCRO INNERDUCT TO ONE SIDE OF VERTICAL LADDER RACK EVERY 2-FEET MINIMUM, AND
TO ONE SIDE OF HORIZONTAL LADDER-TYPE CABLE TRAY EVERY 5-FEET MINIMUM.
2.06 COPPER PATCH (JUMPER) CORDS
G. WHERE SLEEVES ARE ROUTED BETWEEN ROOMS WITH FLOATING CEILINGS, EXTEND CONDUITS HORIZONTALLY 2-FEET OVER EDGE
OF FLOATING CEILING TO AVOID EXPOSED CABLING FROM BEING SEEN AT FLOOR LEVEL.
J. FOLLOWING INSTALLATION, VISUALLY INSPECT INNERDUCT, REMOVE BURRS AT OPENINGS, AND, IF NECESSARY, CLEAN INNERDUCT
INTERIOR.
A. CATEGORY 6 MODULAR PATCH CORDS: FACTORY TERMINATED DOUBLE ENDED, 8-POSITION TO 8-POSITION, MODULAR, STRANDED
CONDUCTORS, CATEGORY 6, 4 PAIR, COLOR BLUE: 3-FEET, 5-FEET, 7-FEET, AND 9-FEET.
JOB NO.
H. MAKE FLOOR PENETRATIONS NO MORE THAN 4-INCHES FROM WALL. INSTALL CONDUIT STUBS TO EXTEND 4-INCHES FROM FLOOR
BASE. CAP CONDUITS FOR PROTECTION.
K. USE FACTORY PULLING EYE TO PREVENT TWISTING OF INNERDUCT AND CABLE.
B. CATEGORY 5E MODULAR PATCH CORDS: FACTORY TERMINATED DOUBLE ENDED, 8-POSITION TO 8-POSITION, MODULAR, STRANDED
CONDUCTORS, CATEGORY 5E, 4 PAIR, COLOR BLUE: 3-FEET, 5-FEET, 7-FEET, AND 9-FEET.
DATE
B. EXPANSION/DEFLECTION FITTINGS: SIMILAR TO CROUSE-HINDS XD EXPANSION/DEFLECTION COUPLING OR APPLETON DF SERIES
DEFLECTION AND EXPANSION COUPLING.
C. PULLTAPE: MEASURING AND PULLING TAPE CONSTRUCTED OF SYNTHETIC FIBER WITH PLASTIC JACKET, PRINTED WITH ACCURATE
SEQUENTIAL FOOTAGE MARKS; E.G., GEORGE-INGRAHAM 1/2-INCH TAPE 9216-JK.
D. DUCT PLUGS:
1. ABOVEGROUND CONDUIT OPENINGS: TAPERED PVC PLUGS WITH TAB FOR PULLTAPE; E.G., CARLON 4-INCH PVC PLUGS WITH PULL
TAB, P258NT.
2. UNDERGROUND OR UNDERSLAB CONDUIT OPENINGS: REMOVABLE SCREWTIGHT COMPRESSION TYPE DUCT PLUGS WITH WING-NUT
AND CORROSION RESISTANT HARDWARE; E.G. VIKIMATIC 4-INCH, PART NUMBER 40D402U. USE APPROPRIATE PART NUMBER
ACCORDING TO DUCT SIZE.
2.05 PENETRATION SEALING SYSTEMS
B. MULTIMODE LC CONNECTOR: CERAMIC TIP LC STYLE CAPABLE OF BEING TERMINATED ON 50/125 FIBER WITH 900 MICRON BUFFER.
3.15 INNERDUCT PULLTAPE AND DUCT PLUG INSTALLATION
I. PROVIDE REMOVABLE HEAT-EXPANDING PILLOWS AT FIRE BARRIER PENETRATIONS AS SPECIFIED IN FIRESTOPPING SECTION, AND
DESCRIBED AS FIRESTOP MATERIAL TYPE 7 (INDICATED AS FSM-7).
1111 Jackson Street
Oakland, California
PART 3 - EXECUTION
JACKSON CENTER ONE
A. WORK INCLUDED:
1. RACEWAYS
2. ELECTRICAL METALLIC TUBING AND FITTINGS
3. CONDUIT ACCESSORIES
4. PENETRATION SEALING SYSTEMS
5. PULL BOXES
6. INNERDUCT
7. INNERDUCT FITTINGS
A. FOLLOWING INNERDUCT INSTALLATION, INSTALL PULLTAPE (MULETAPE) WITH PREPRINTED FOOT MARKERS IN INNERDUCT SECTIONS.
TIE THE PULLTAPE SECURELY AT EACH END.
C. CROSS-CONNECT WIRE: SINGLE-PAIR, 24 AWG TWISTED CROSS-CONNECT WIRE. BLUE, ORANGE, GREEN, OR BROWN. COORDINATE
COLOR WITH OWNER.
DRAWN BY
CR
CHECKED BY
Kevin Kuang
2014-0284
DATE
SHEET NUMBER
2.07 FIBER OPTIC PATCH (JUMPER) CORDS
3.08 ABOVEGROUND CONDUIT INSTALLATION
B. VERIFY LENGTHS AT THE TIME OF INSTALLATION AND PROVIDE AS-BUILT DOCUMENTATION.
A. SUPPORT CONDUIT INSTALLED IN ABOVEGROUND INTERIOR AND EXTERIOR LOCATIONS AT A MAXIMUM OF 7-FEET ON CENTER.
B. GROUP CONDUIT IN PARALLEL RUNS WHERE PRACTICAL AND USE CONDUIT RACK CONSTRUCTED OF STEEL CHANNEL WITH CONDUIT
STRAPS OR CLAMPS.
C. FOLLOWING INNERDUCT AND PULLTAPE INSTALLATION, CAP OR PLUG INNERDUCT WITH MANUFACTURED SEALS TO PREVENT
MOISTURE OR FOREIGN MATTER FROM ENTERING UNTIL CABLE INSTALLATION STARTS. SEAL DUCT OPENINGS IN UNDERGROUND OR
UNDERSLAB INNERDUCT SECTIONS IMMEDIATELY AFTER INSTALLATION USING SCREWTIGHT, REMOVABLE, WATERTIGHT, AND
A. MULTIMODE FIBER OPTIC JUMPERS: FACTORY TERMINATED DOUBLE ENDED, TWO STRAND MULTIMODE CORDAGE WITH LC
CONNECTORS ON EACH END, LENGTH AS DEFINED BY THE OWNER.
2.08 MISCELLANEOUS HARDWARE
E6.3
A. PROVIDE SUPPORTING HARDWARE, CABLE TIES, LABELS, UNDERGROUND VAULT RACKING, BULLET BONDS, GEL BLOCKING KITS, PULL
ROPE, AND OTHER MISCELLANEOUS HARDWARE FOR A COMPLETE AND OPERABLE SYSTEM.
PART 3 - EXECUTION
F. PROVIDE TEST RESULTS IN ELECTRONIC FORMAT, WITH THE FOLLOWING MINIMUM INFORMATION PER CABLE:
1. CIRCUIT ID
THE SYSTEM INSTALLATION, AND MUST BE ABLE TO PROVIDE THE MANUFACTURER'S EXTENDED WARRANTY.
D. PERFORM WORK IN A NEAT AND WORKMANLIKE MANNER.
3. DATE AND TIME OF TEST
4. PROJECT NAME
5. NVP
E. INSTALL CABLE AFTER INTERIOR OF BUILDING HAS BEEN PHYSICALLY PROTECTED FROM THE WEATHER AND MECHANICAL WORK
LIKELY TO DAMAGE CABLING HAS BEEN COMPLETED.
3.01 GENERAL
G. FIBER TEST DOCUMENTATION: PROVIDE ELECTRONIC CD DISK AND HARD COPY TEST REPORTS FROM ANSI/TIA/EIA-526-14A METHOD B
A. COMMUNICATIONS BACKBONE CABLING INCLUDES CABLES, JACKS, PATCH PANELS, CONNECTING BLOCKS, AND PATCH CORDS, AS
WELL AS THE NECESSARY SUPPORT SYSTEMS, SUCH AS CABLE MANAGERS, TIE WRAPS, AND D-RINGS.
B. FURNISH AND INSTALL MATERIALS NECESSARY FOR A COMPLETE AND WORKING SYSTEM.
C. CONTRACTOR MUST BE A CERTIFIED INSTALLER FOR SELECTED MANUFACTURER PRIOR TO, DURING, AND THROUGH COMPLETION OF
THE SYSTEM INSTALLATION, AND MUST BE ABLE TO PROVIDE THE MANUFACTURER'S EXTENDED WARRANTY.
D. PERFORM WORK IN A NEAT AND WORKMANLIKE MANNER.
E. INSTALL CABLE AFTER INTERIOR OF BUILDING HAS BEEN PHYSICALLY PROTECTED FROM THE WEATHER AND MECHANICAL WORK
LIKELY TO DAMAGE CABLING HAS BEEN COMPLETED.
MINIMUM, OTDR TEST RESULTS IN THE FORM OF A PRINTED WAVEFORM AND TEXT TABLE FOR BOTH 850 NM AND 1300 NM FOR
MULTIMODE FIBER AND 1350 NM AND 1510 NM FOR SINGLEMODE FIBER. TEST FIBERS AND CONNECTOR SYSTEMS FOR END-TO-END
ATTENUATION. PROVIDE A POWER METER TEST ON FIBER OPTIC STRANDS AT BOTH WAVELENGTHS A TO B, B TO A AND OSPL (OSPL IS
AS DEFINED AS LA + LB). INCLUDE THE RESULTS OF UNSATISFACTORY TESTS, WITH AN EXPLANATION OF HOW THE PROBLEM WAS
CORRECTED. CLEARLY LABEL CONNECTOR AND FIBER LOSS ON TEST WAVEFORMS.
H. PROVIDE AN ELECTRONIC COPY OF THE TEST RESULTS, IN THE NATIVE TESTER SOFTWARE FORMAT, TO THE ARCHITECT ALONG WITH
THE PRINTED TEST RESULTS.
F. BEFORE INSTALLING CABLING, ENSURE CABLE PATHWAYS ARE COMPLETELY AND THOROUGHLY CLEANED.
1. INSPECT CONDUIT, WIREWAY, CABLE TRAYS, AND INNERDUCT SYSTEMS PRIOR TO INSTALLATION.
2. SWAB ANY ADDITIONAL ENCLOSED RACEWAY AND INNERDUCT SYSTEMS.
G. PROVIDE PROTECTION FOR EXPOSED CABLES WHERE SUBJECT TO DAMAGE. PROVIDE ABRASION PROTECTION FOR ANY CABLE OR
WIRE BUNDLES, WHICH PASS THROUGH HOLES OR ACROSS EDGES OF SHEET METAL.
H. INSTALL CABLE TIES AND OTHER CABLE MANAGEMENT CLAMPS VIA HAND SO THAT IT FITS SNUGLY. DO NOT OVER TIGHTEN OR USE
MECHANICAL TOOLS WHICH COULD COMPRESS, CRIMP, OR OTHERWISE CHANGE THE PHYSICAL CHARACTERISTICS OF THE CABLE
JACKET OR DISTORT THE PLACEMENT OF TWISTED-PAIR COMPONENTS. REPLACE ANY CABLE EXHIBITING STRESSES DUE TO OVER
TIGHTENING OF CABLE MANAGEMENT DEVICES.
J. ANY FAILED TEST RESULTS THAT CANNOT BE REMEDIED THROUGH RETERMINATION (AS IN THE CASE OF REVERSED OR SPLIT PAIRS),
MUST BE REPORTED IN WRITING TO THE ARCHITECT IMMEDIATELY, ALONG WITH A COPY OF THE TEST RESULTS.
3.05 LABELING
J. CO-INSTALL A PULL CORD (NYLON; 1/8-INCH MINIMUM) WITH CABLE INSTALLED IN CONDUIT.
G. PROVIDE PROTECTION FOR EXPOSED CABLES WHERE SUBJECT TO DAMAGE. PROVIDE ABRASION PROTECTION FOR ANY CABLE OR
WIRE BUNDLES, WHICH PASS THROUGH HOLES OR ACROSS EDGES OF SHEET METAL.
A. LABEL CABLES USING A MACHINE PRINTED LABEL AT EACH END OF THE CABLE AT APPROXIMATELY 12-INCHES OF THE TERMINATION
POINT, AND AGAIN AT APPROXIMATELY 48-INCHES FROM THE TERMINATION POINT. DO NOT USE HANDWRITTEN LABELS.
K. LIMIT CABLE RACEWAY FILL TO LESS THAN THE TIA/EIA-569-B MAXIMUM FILL FOR THE PARTICULAR RACEWAY TYPE.
H. INSTALL CABLE TIES AND OTHER CABLE MANAGEMENT CLAMPS VIA HAND SO THAT IT FITS SNUGLY. DO NOT OVER TIGHTEN OR USE
MECHANICAL TOOLS WHICH COULD COMPRESS, CRIMP, OR OTHERWISE CHANGE THE PHYSICAL CHARACTERISTICS OF THE CABLE
JACKET OR DISTORT THE PLACEMENT OF TWISTED-PAIR COMPONENTS. REPLACE ANY CABLE EXHIBITING STRESSES DUE TO OVER
TIGHTENING OF CABLE MANAGEMENT DEVICES.
B. LABEL PATCH PANEL PORTS WITH THE CABLE IDENTIFIER.
C. PROVIDE THE FINAL CABLE ID MATRIX TO THE OWNER, ARCHITECT, OR ENGINEER ONE WEEK PRIOR TO CABLE INSTALLATION.
B. A TELECOMMUNICATIONS OUTLET WITH A 4-STRAND FIBER OPTIC CABLE INSTALLED WOULD REQUIRE ONE DUPLEX FIBER OPTIC
PATCH CORD(S) AT THE WORK AREA OUTLET AND ONE DUPLEX FIBER OPTIC PATCH CORD(S) IN THE TELECOMMUNICATIONS EQUIPMENT
ROOM FOR A TOTAL OF TWO DUPLEX FIBER OPTIC PATCH CORD(S). PROVIDE EQUAL AMOUNTS OF EACH LENGTH INDICATED IN PART 2,
PRODUCTS.
3.06 COORDINATION OF CONDITIONS
A. STRUCTURED CABLING FOR WIRELESS ACCESS POINTS OF A GIVEN DESCRIPTION MAY BE USED IN MORE THAN ONE TYPE OF CEILING
OR WALL STRUCTURE. COORDINATE CEILING CONSTRUCTION, WALL TYPES, RECESSING DEPTH AND OTHER CONSTRUCTION DETAILS
PRIOR TO ORDERING SPECIAL COMPONENTS INDICATED IN THE DETAILS FOR SHIPMENT. WHERE MATERIALS SUPPLIED DO NOT MATCH
CEILING CONSTRUCTION REPLACE THEM AT NO COST TO OWNER.
END OF SECTION
END OF TECHNOLOGY SPECIFICATIONS
I. PROVIDE A FULLY FUNCTIONAL VERSION OF THE TESTER SOFTWARE FOR USE BY THE ARCHITECT IN REVIEWING THE TEST RESULTS.
I. WHERE POSSIBLE, ROUTE CABLES IN OVERHEAD CABLE TRAYS AND INSIDE WIRE MANAGEMENT SYSTEMS ATTACHED TO THE
EQUIPMENT CABINETS AND RACKS. USE VELCRO TIES OR DUCTS TO RESTRAIN CABLING INSTALLED OUTSIDE OF WIRE MANAGEMENT
SYSTEMS ON RACKS OR IN CABINETS.
F. BEFORE INSTALLING CABLING, ENSURE CABLE PATHWAYS ARE COMPLETELY AND THOROUGHLY CLEANED:
1. INSPECT CONDUIT, WIREWAY, CABLE TRAYS, AND INNERDUCT SYSTEMS PRIOR TO INSTALLATION.
2. SWAB ANY ADDITIONAL ENCLOSED RACEWAY AND INNERDUCT SYSTEMS.
WITH FOUR CATEGORY 6 CABLES INSTALLED WOULD REQUIRE TWO CATEGORY 6 EQUIPMENT CONNECTION CORDS AT THE WORK AREA
OUTLET AND TWO CATEGORY 6 EQUIPMENT CONNECTION CORDS IN THE TELECOMMUNICATIONS EQUIPMENT ROOM FOR A TOTAL OF
FOUR CATEGORY 6 EQUIPMENT CONNECTION CORDS.
717 Market Street
Suite 500
San Francisco, CA 94103
TEL
415.489.7240
FAX 415.489.7289
www.interfaceengineering.com
L. IF A J-HOOK OR TRAPEZE SYSTEM IS USED TO SUPPORT CABLE BUNDLES, SUPPORT HORIZONTAL CABLES AT A MAXIMUM OF 48- TO
60-INCH INTERVALS. CABLES ARE PROHIBITED TO REST ON ACOUSTIC CEILING GRIDS OR PANELS.
M. BUNDLE HORIZONTAL DISTRIBUTION CABLES IN GROUPS OF NO MORE THAN 50 CABLES. CABLE BUNDLE QUANTITIES IN EXCESS OF 50
CABLES MAY CAUSE DEFORMATION OF THE BOTTOM CABLES WITHIN THE BUNDLE AND DEGRADE CABLE PERFORMANCE.
D. NOTE LABELING INFORMATION ON THE AS-BUILT DRAWINGS.
I. WHERE POSSIBLE, ROUTE CABLES IN OVERHEAD CABLE TRAYS AND INSIDE WIRE MANAGEMENT SYSTEMS ATTACHED TO THE
EQUIPMENT CABINETS AND RACKS. USE VELCRO TIES OR DUCTS TO RESTRAIN CABLING INSTALLED OUTSIDE OF WIRE MANAGEMENT
SYSTEMS ON RACKS OR IN CABINETS.
3.06 PATCH CORDS
J. CO-INSTALL A PULL CORD (NYLON; 1/8-INCH MINIMUM) WITH CABLE INSTALLED IN CONDUIT.
A. AT A MINIMUM, PROVIDE EQUIPMENT CONNECTION CORDS FOR ONE-HALF THE TOTAL NUMBER OF PORTS INSTALLED AT EACH
TERMINATION POINT. FOR EXAMPLE: A 25 PAIR CATEGORY 5E BACKBONE CABLE TERMINATED WITH ONE PAIR PER PORT WOULD
REQUIRE 12 PATCH CORDS AT EACH TERMINATION END FOR A TOTAL OF 24 CATEGORY 5E PATCH CORDS.
N. INSTALL CABLE ABOVE FIRE-SPRINKLER SYSTEMS AND ENSURE THAT THE CABLE DOES NOT ATTACH TO THE SYSTEM OR ANY
ANCILLARY EQUIPMENT OR HARDWARE. INSTALL CABLE SYSTEM AND SUPPORT HARDWARE SUCH THAT IT DOES NOT OBSCURE ANY
VALVES, FIRE ALARM CONDUIT, BOXES, OR OTHER CONTROL DEVICES.
O. DO NOT ATTACH CABLES TO CEILING GRID OR LIGHTING FIXTURE WIRES. WHERE SUPPORT FOR HORIZONTAL CABLE IS REQUIRED,
INSTALL APPROPRIATE CARRIERS TO SUPPORT THE CABLING.
K. LIMIT CABLE RACEWAY FILL TO LESS THAN THE TIA/EIA-569-B MAXIMUM FILL FOR THE PARTICULAR RACEWAY TYPE.
N. INSTALL CABLE ABOVE FIRE-SPRINKLER SYSTEMS AND ENSURE THAT THE CABLE DOES NOT ATTACH TO THE SYSTEM OR ANY
ANCILLARY EQUIPMENT OR HARDWARE. INSTALL CABLE SYSTEM AND SUPPORT HARDWARE SUCH THAT IT DOES NOT OBSCURE ANY
VALVES, FIRE ALARM CONDUIT, BOXES, OR OTHER CONTROL DEVICES.
P. ANY CABLE DAMAGED OR EXCEEDING RECOMMENDED INSTALLATION PARAMETERS DURING INSTALLATION WILL BE REPLACED BY THE
CONTRACTOR PRIOR TO FINAL ACCEPTANCE AT NO COST TO THE OWNER.
C. FIELD TERMINATED PATCH CORDS AND JUMPERS ARE NOT ALLOWED.
R. UNSHIELDED TWISTED PAIR CABLE INSTALLATION PRACTICES:
1. INSTALL CABLE IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS AND BEST INDUSTRY PRACTICES.
2. INSTALL CABLES IN CONTINUOUS LENGTHS FROM ORIGIN TO DESTINATION (NO SPLICES) EXCEPT FOR TRANSITION POINTS, OR
CONSOLIDATION POINTS.
3. INSTALL TRANSITION POINTS OR CONSOLIDATION POINTS IN ACCESSIBLE LOCATIONS AND HOUSED IN AN ENCLOSURE INTENDED AND
SUITABLE FOR THE PURPOSE, WHERE ALLOWED BY STANDARDS AND APPROVED BY THE OWNER'S REPRESENTATIVE.
4. DO NOT EXCEED THE CABLE'S MINIMUM BEND RADIUS AND MAXIMUM PULLING TENSION.
5. INSTALL UNSHIELDED TWISTED PAIR CABLE SO THAT THERE ARE NO BENDS SMALLER THAN FOUR TIMES THE CABLE OUTSIDE
DIAMETER AT ANY POINT IN THE RUN AND AT THE TERMINATION FIELD.
6. DO NOT EXCEED 25-LBF PULLING TENSION ON 4-PAIR UTP CABLE.
END OF SECTION
SECTION 27 1500 COMMUNICATIONS HORIZONTAL CABLING
O. DO NOT ATTACH CABLES TO CEILING GRID OR LIGHTING FIXTURE WIRES. WHERE SUPPORT FOR CABLE IS REQUIRED, INSTALL
APPROPRIATE CARRIERS TO SUPPORT THE CABLING.
P. ANY CABLE DAMAGED OR EXCEEDING RECOMMENDED INSTALLATION PARAMETERS DURING INSTALLATION WILL BE REPLACED BY THE
CONTRACTOR PRIOR TO FINAL ACCEPTANCE AT NO COST TO THE OWNER.
Q. UNSHIELDED TWISTED PAIR CABLE INSTALLATION PRACTICES
1. INSTALL CABLE IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS AND BEST INDUSTRY PRACTICES.
2. INSTALL CABLES IN CONTINUOUS LENGTHS FROM ORIGIN TO DESTINATION (NO SPLICES) EXCEPT FOR TRANSITION POINTS, OR
CONSOLIDATION POINTS.
3. INSTALL TRANSITION POINTS OR CONSOLIDATION POINTS IN ACCESSIBLE LOCATIONS AND HOUSED IN AN ENCLOSURE INTENDED AND
SUITABLE FOR THE PURPOSE, WHERE ALLOWED BY STANDARDS AND APPROVED BY THE OWNER'S REPRESENTATIVE.
4. DO NOT EXCEED THE CABLE'S MINIMUM BEND RADIUS AND MAXIMUM PULLING TENSION.
5. INSTALL UNSHIELDED TWISTED PAIR CABLE SO THAT THERE ARE NO BENDS SMALLER THAN FOUR TIMES THE CABLE OUTSIDE
DIAMETER AT ANY POINT IN THE RUN AND AT THE TERMINATION FIELD.
6. DO NOT EXCEED 25-LBF PULLING TENSION ON 4-PAIR UTP CABLE.
PART 1 - GENERAL
1.01 SUMMARY
A. WORK INCLUDED:
1. PATCH PANELS
2. PATCH CORDS/JUMPERS
A. REFERENCES AND STANDARDS AS REQUIRED BY SECTION 27 00 00, COMMUNICATIONS BASIC REQUIREMENTS AND DIVISION 01,
GENERAL REQUIREMENTS.
S. PROVIDE THE FOLLOWING MINIMUM SEPARATION DISTANCES BETWEEN PATHWAYS FOR COPPER COMMUNICATIONS CABLES AND
POWER WIRING OF 480 VOLTS OR LESS:
1. OPEN OR NONMETAL COMMUNICATIONS PATHWAYS:
A. 12-INCHES FROM ELECTRIC MOTORS, FLUORESCENT LIGHT FIXTURES, AND UNSHIELDED POWER LINES CARRYING UP TO 3 KVA.
B. 36-INCHES FROM ELECTRICAL EQUIPMENT AND UNSHIELDED POWER LINES CARRYING MORE THAN 5 KVA.
C. 48-INCHES FROM LARGE ELECTRICAL MOTORS OR TRANSFORMERS.
2. GROUNDED METAL CONDUIT COMMUNICATIONS PATHWAYS:
A. 2 1/2-INCHES FROM ELECTRICAL EQUIPMENT AND UNSHIELDED POWER LINES CARRYING UP TO 2 KVA.
B. 6-INCHES FROM ELECTRICAL EQUIPMENT AND UNSHIELDED POWER LINES CARRYING FROM 2 KVA TO 5 KVA.
C. 12-INCHES FROM ELECTRICAL EQUIPMENT AND UNSHIELDED POWER LINES CARRYING MORE THAN 5 KVA.
D. 3-INCHES FROM POWER LINES ENCLOSED IN A GROUNDED METAL CONDUIT (OR EQUIVALENT SHIELDING) CARRYING FROM 2 KVA TO 5
KVA.
E. 6-INCHES FROM POWER LINES ENCLOSED IN A GROUNDED METAL CONDUIT (OR EQUIVALENT SHIELDING) CARRYING MORE THAN 5
KVA.
B. MEET REQUIREMENTS OF NFPA 780, STANDARD FOR THE INSTALLATION OF LIGHTNING PROTECTION SYSTEMS.
3.02 UNSHIELDED TWISTED PAIR TERMINATION
1.04 SUBMITTALS
A. COIL CABLES IN THE IN-WALL OR SURFACE-MOUNT BOXES IF ADEQUATE SPACE IS PRESENT TO HOUSE THE CABLE COIL WITHOUT
EXCEEDING THE MANUFACTURERS BEND RADIUS. IN HOLLOW WALL INSTALLATIONS WHERE BOX-ELIMINATORS ARE USED, EXCESS
WIRE CAN BE STORED IN THE WALL. DO NOT STORE MORE THAN 12-INCHES OF UTP IN AN IN-WALL BOX, MODULAR FURNITURE
RACEWAY, OR INSULATED WALLS. LOOSELY COIL AND STORE EXCESS SLACK IN ACCESSIBLE CEILING SPACE ABOVE EACH DROP
LOCATION WHEN THERE IS NOT ENOUGH SPACE PRESENT IN THE OUTLET BOX TO STORE SLACK CABLE.
1.02 RELATED SECTIONS
A. CONTENTS OF DIVISION 27, COMMUNICATIONS AND DIVISION 01, GENERAL REQUIREMENTS APPLY TO THIS SECTION.
B. USE THIS SECTION IN CONJUNCTION WITH OTHER DIVISION 27, COMMUNICATIONS SPECIFICATIONS AND RELATED CONTRACT
DOCUMENTS TO ESTABLISH THE TOTAL GENERAL REQUIREMENTS FOR THE PROJECT COMMUNICATIONS SYSTEMS AND EQUIPMENT.
1.03 REFERENCES AND STANDARDS
R. PROVIDE THE FOLLOWING MINIMUM SEPARATION DISTANCES BETWEEN PATHWAYS FOR COPPER COMMUNICATIONS CABLES AND
POWER WIRING OF 480 VOLTS OR LESS:
1. OPEN OR NONMETAL COMMUNICATIONS PATHWAYS:
A. 12-INCHES FROM ELECTRIC MOTORS, FLUORESCENT LIGHT FIXTURES, AND UNSHIELDED POWER LINES CARRYING UP TO 3 KVA.
B. 36-INCHES FROM ELECTRICAL EQUIPMENT AND UNSHIELDED POWER LINES CARRYING MORE THAN 5 KVA.
C. 48-INCHES FROM LARGE ELECTRICAL MOTORS OR TRANSFORMERS.
2. GROUNDED METAL CONDUIT COMMUNICATIONS PATHWAYS:
A. 2 1/2-INCHES FROM ELECTRICAL EQUIPMENT AND UNSHIELDED POWER LINES CARRYING UP TO 2 KVA.
B. 6-INCHES FROM ELECTRICAL EQUIPMENT AND UNSHIELDED POWER LINES CARRYING FROM 2 KVA TO 5 KVA.
C. 12-INCHES FROM ELECTRICAL EQUIPMENT AND UNSHIELDED POWER LINES CARRYING MORE THAN 5 KVA.
d. 3-inches from power lines enclosed in a grounded metal conduit (or equivalent shielding) carrying from 2 kVA to 5 kVA.
e. 6-inches from power lines enclosed in a grounded metal conduit (or equivalent shielding) carrying more than 5 kVA.
S. SPLICE CASE INSTALLATION: PROVIDE SPLICE CASES WITHIN 50-FEET OF WHERE OSP CABLE ENTERS BUILDING IN A DUCT OR
CONDUIT SYSTEM. SIZE SPLICE CASES TO ACCOMMODATE PAIR OR STRAND COUNT OF CABLE ENTERING BUILDING. PROPERLY BOND
CABLE ENTERING AND EXITING SPLICE CASE TO MAIN TELECOMMUNICATION GROUNDING BUS BAR (TMGB). INSTALL END CAPS TO
PROPERLY SEAL CABLE FROM EXPANDING WATER BLOCKING GEL.
T. DETERMINE REQUIREMENTS FOR PLENUM RATED CABLE AND DEVICES. WHEN DOUBT EXISTS, SEEK PRIOR DETERMINATION IN
WRITING BY AHJ.
Q. DETERMINE REQUIREMENTS FOR PLENUM RATED CABLE AND DEVICES. WHEN DOUBT EXISTS, SEEK PRIOR DETERMINATION IN
WRITING BY AHJ.
A. SUBMITTALS AS REQUIRED BY SECTION 27 00 00, COMMUNICATIONS BASIC REQUIREMENTS AND DIVISION 01, GENERAL
REQUIREMENTS.
B. IN ADDITION, PROVIDE:
1. SHOP DRAWINGS THAT INCLUDE, BUT ARE NOT LIMITED TO, THE FOLLOWING: TELECOMMUNICATION ROOM LAYOUT,
TELECOMMUNICATION ROOM WALL ELEVATIONS, EQUIPMENT RACK ELEVATIONS, CABLE ROUTING, CABLE CONNECTING DIAGRAMS,
TERMINATION PIN OUTS, SUPPORTING HARDWARE DETAILS, BLOCK DIAGRAMS, RISER DIAGRAMS, CABLE PATHWAYS. WORK MAY NOT
BEGIN UNTIL SHOP DRAWINGS ARE APPROVED. NOTE: INTENT OF SUBMITTING SHOP DRAWINGS IS FOR CONTRACTORS TO DISPLAY A
CONCEPTUAL UNDERSTANDING OF THE ISSUED ENGINEER DRAWINGS. DO NOT SUBMIT ENGINEERS DRAWING ON YOUR TITLE BLOCK.
2. PROCEDURES FOR CABLE LABELING AND IDENTIFICATION, LONG TERM DOCUMENTATION METHODS AND NUMBERING SCHEME IN
ACCORDANCE WITH ANSI/TIA/EIA-606A.
3. A COPY OF CERTIFIED INSTALLER CERTIFICATES AND WARRANTY CERTIFICATES FOR PRODUCTS PROPOSED.
B. DRESS AND TERMINATE CABLES IN ACCORDANCE WITH THE RECOMMENDATIONS MADE IN THE ANSI/TIA/EIA-568-C.1 DOCUMENT.
C. TERMINATE 4 PAIR CABLES ON THE JACK AND PATCH PANELS USING T568B WIRING SCHEME.
D. MAINTAIN THE CABLE JACKET WITHIN 1-INCH OF THE TERMINATION POINT.
E. DO NOT EXCEED 0.5-INCH OF PAIR UNTWIST AT THE TERMINATION POINT.
F. DO NOT EXCEED 4 TIMES THE OUTSIDE DIAMETER OF THE CABLE IN THE TERMINATION AREA FOR BEND RADIANCE COMPLIANCE.
U. SEAL CONDUITS ENTERING FROM OUTSIDE THE BUILDING AND INSTALL LISTED FIRESTOP MATERIAL IN CONDUITS AND SLEEVES TO
SATISFY NEC AND LOCAL CODES.
1.05 QUALITY ASSURANCE
3.02 UNSHIELDED TWISTED PAIR TERMINATION
A. QUALITY ASSURANCE AS REQUIRED BY SECTION 27 00 00, COMMUNICATIONS BASIC REQUIREMENTS AND DIVISION 01, GENERAL
REQUIREMENTS.
A. LOOSELY COIL AND STORE EXCESS SLACK IN THE CEILING ABOVE EACH TERMINATION LOCATION WHEN THERE IS NOT ENOUGH
SPACE PRESENT TO STORE SLACK CABLE.
B. MANUFACTURERS TO HAVE A RECOGNIZED CERTIFIED INSTALLER PROGRAM IN PLACE FOR SYSTEM COMPONENTS PROPOSED.
CABLE WILL BE APPROVED WITH MANUFACTURER SYSTEM INSTALLED.
B. DRESS AND TERMINATE CABLES IN ACCORDANCE WITH THE RECOMMENDATIONS MADE IN THE ANSI/TIA/EIA-568-C.1 DOCUMENT,
MANUFACTURER'S RECOMMENDATIONS AND BEST INDUSTRY PRACTICES.
1.06 WARRANTY
G. NEATLY BUNDLE AND DRESS CABLES TO THEIR RESPECTIVE PANELS OR BLOCKS. FEED EACH PANEL OR BLOCK BY AN INDIVIDUAL
BUNDLE SEPARATED AND DRESSED BACK TO THE POINT OF CABLE ENTRANCE INTO THE RACK OR FRAME.
3.03 TESTING PROCEDURES
C. TERMINATE 4 PAIR CABLES ON THE JACK AND PATCH PANELS USING T568B WIRING SCHEME.
D. MAINTAIN THE CABLE JACKET WITHIN 1-INCH OF THE TERMINATION POINT.
E. DO NOT EXCEED 0.5-INCH OF PAIR UNTWIST AT THE TERMINATION POINT.
F. DO NOT EXCEED 4 TIMES THE OUTSIDE DIAMETER OF THE CABLE IN THE TERMINATION AREA FOR BEND RADIANCE COMPLIANCE.
G. NEATLY BUNDLE AND DRESS CABLES TO THEIR RESPECTIVE PANELS OR BLOCKS. FEED EACH PANEL OR BLOCK BY AN INDIVIDUAL
BUNDLE SEPARATED AND DRESSED BACK TO THE POINT OF CABLE ENTRANCE INTO THE RACK OR FRAME.
3.03 OPTICAL FIBER CABLE INSTALLATION PRACTICES
A. WARRANTY OF MATERIALS AND WORKMANSHIP AS REQUIRED BY SECTION 27 00 00, COMMUNICATIONS BASIC REQUIREMENTS AND
DIVISION 01, GENERAL REQUIREMENTS.
B. IN ADDITION, PROVIDE:
1. LABOR, MATERIALS AND DOCUMENTATION ACCORDING TO SELECTED MANUFACTURER REQUIREMENTS NECESSARY TO ENSURE THAT
THE OWNER WILL BE FURNISHED WITH AN EXTENDED PRODUCT WARRANTY AND APPLICATION ASSURANCE OF A MINIMUM OF 20 YEARS
IN LENGTH. THE APPLICATION ASSURANCE WARRANTY WILL COVER THE FAILURE OF THE WIRING SYSTEM TO SUPPORT CURRENT OR
FUTURE APPLICATIONS THAT ARE DESIGNED FOR THE LINK/CHANNEL SPECIFICATIONS OF ANSI/TIA/EIA-568-C.1. THESE APPLICATIONS
INCLUDE, BUT ARE NOT LIMITED TO, 10BASE-T, 100BASE-T, 1000BASE-T, 10GBASE-T, AND 155 MB/S ATM.
2. A WARRANTY ON THE PHYSICAL INSTALLATION.
3. Necessary documentation required by the manufacturer immediately following 100 percent testing of cables.
C. Administer the warranty process with the responsible manufacturer's representative. Provide warranty directly to the Owner from the manufacturer.
Ensure that the manufacturer provides the Owner with the appropriate warranty certification within 90 calendar days of the final project completion.
A. PLACE FIBER OPTIC CABLE SO AS TO MAINTAIN THE MINIMUM CABLE BEND RADIUS LIMITS SPECIFIED BY THE MANUFACTURER OR TEN
TIMES THE CABLE DIAMETER, WHICHEVER IS LARGER.
1.07 SYSTEM DESCRIPTION
B. PLACE FIBER OPTIC CABLE RUNS IN INNERDUCT. USE CARE WHEN HANDLING FIBER OPTIC CABLE. CAREFULLY MONITOR PULLING
TENSION SO AS NOT TO EXCEED THE LIMITS SPECIFIED BY THE MANUFACTURER.
A. Provide a standards-based cable system to serve horizontal communication systems requirements as specified and as shown on Drawings. Closely
follow ANSI/TIA/EIA, IEEE and ISO standards.
C. TERMINATE FIBER OPTIC CABLE IN RACK-MOUNTED FIBER OPTIC TERMINATION UNITS AT EACH END USING STANDARD LC STYLE
BULKHEAD CONNECTORS.
B. The horizontal distribution subsystem refers to intrabuilding twisted-pair communications cabling connecting telecommunications rooms (TRs) to
telecommunications outlets (TOs) located at individual work areas and consists of the following:
1. Category 6 or Category 5e 100 ohm, 4-pair, unshielded twisted pair cables from the TRs to the TOs.
2. The horizontal system includes cables, jacks, patch panels, connecting blocks, patch cords, fiber connectors and jumpers as well as the necessary
support systems, such as cable managers and faceplates.
3. Cables are routed through conduit, spaces below raised floors, open ceiling areas, nonventilated spaces above ceiling tile, and through plenum
air-handling spaces above ceiling tile.
4. Furnish and install materials necessary for a complete and working system.
D. SPLICING OF FIBER OPTIC CABLE IS PROHIBITED UNLESS DIRECTED IN DRAWINGS OR APPROVED VIA RFI.
3.04 TESTING PROCEDURES
A. TEST CABLES AND TERMINATION HARDWARE FOR DEFECTS IN INSTALLATION AND TO VERIFY CABLING SYSTEM PERFORMANCE
UNDER INSTALLED CONDITIONS ACCORDING TO THE REQUIREMENTS OF ANSI/TIA/EIA-568-C. VERIFY PAIRS OF EACH INSTALLED CABLE
PRIOR TO SYSTEM ACCEPTANCE. REPAIR OR REPLACE ANY DEFECT IN THE CABLING SYSTEM INSTALLATION INCLUDING BUT NOT
LIMITED TO CABLE, CONNECTORS, FEED THROUGH COUPLERS, PATCH PANELS, AND CONNECTOR BLOCKS IN ORDER TO ENSURE 100
PERCENT USEABLE CONDUCTORS IN CABLES INSTALLED.
B. TEST CABLES IN ACCORDANCE WITH THIS DOCUMENT, THE ANSI/TIA/EIA STANDARDS, THE MANUFACTURER'S PROCEDURES AND BEST
INDUSTRY PRACTICE. IF ANY OF THESE ARE IN CONFLICT, BRING ANY DISCREPANCIES TO THE ATTENTION OF THE PROJECT TEAM FOR
CLARIFICATION AND RESOLUTION.
C. TEST UNSHIELDED TWISTED PAIR CABLES AS FOLLOWS:
1. TEST TWISTED-PAIR COPPER CABLE LINKS FOR CONTINUITY, PAIR REVERSALS, SHORTS, OPENS AND PERFORMANCE AS INDICATED
BELOW. ADDITIONAL TESTING IS REQUIRED TO VERIFY CATEGORY PERFORMANCE. TEST CABLING USING A LEVEL IV TEST UNIT FOR
CATEGORY 6 PERFORMANCE COMPLIANCE AS SPECIFIED IN ANSI/TIA/EIA-568-C.
2. CONTINUITY - TEST EACH PAIR OF EACH INSTALLED CABLE USING A TEST UNIT THAT SHOWS OPENS, SHORTS, POLARITY AND
PAIR-REVERSALS, CROSSED PAIRS AND SPLIT PAIRS. TEST SHIELDED/SCREENED CABLES WITH A DEVICE THAT VERIFIES SHIELD
CONTINUITY IN ADDITION TO THE ABOVE STATED TESTS. RECORD THE TEST AS PASS/FAIL AS INDICATED BY THE TEST UNIT IN
ACCORDANCE WITH THE MANUFACTURERS' RECOMMENDED PROCEDURES, AND REFERENCED TO THE APPROPRIATE CABLE
IDENTIFICATION NUMBER AND CIRCUIT OR PAIR NUMBER. CORRECT OR REPAIR ANY FAULTS IN THE WIRING AND RE-TEST THE CABLE
PRIOR TO FINAL ACCEPTANCE.
3. LENGTH - TEST EACH INSTALLED CABLE LINK FOR INSTALLED LENGTH USING A TDR TYPE DEVICE. TEST THE CABLES FROM PATCH
PANEL TO PATCH PANEL, BLOCK TO BLOCK, PATCH PANEL TO OUTLET OR BLOCK TO OUTLET AS APPROPRIATE. THE CABLE LENGTH
WILL CONFORM TO THE MAXIMUM DISTANCES SET FORTH IN THE ANSI/TIA/EIA-568-C STANDARD. RECORD CABLE LENGTHS,
REFERENCING THE CABLE IDENTIFICATION NUMBER AND CIRCUIT OR PAIR NUMBER. FOR MULTI-PAIR CABLES, RECORD THE SHORTEST
PAIR LENGTH AS THE LENGTH FOR THE CABLE.
PART 2 - PRODUCTS
2.01 MANUFACTURERS
A. PROVIDE LIKE ITEMS FROM ONE MANUFACTURER, SUCH AS JACKS, PATCH PANELS, EQUIPMENT CONNECTION CORDS, AND WALL
PLATES. THE FOLLOWING MANUFACTURERS/SOLUTIONS ARE PREAPPROVED.
1. COMMSCOPE SYSTIMAX OR UNIPRISE
2. ORTRONICS/BERK-TEK
3. PANDUIT/GENERAL
4. OR APPROVED EQUIVALENT.
2.02 PATCH PANELS
A. CATEGORY 6 MODULAR PATCH PANELS: 48 PORT, EIGHT-POSITION MODULAR JACK PANEL, HIGH DENSITY, 6 PORT MODULES,
CATEGORY 6, IDC TERMINALS, T568A/B WIRING SCHEME.
B. CATEGORY 5E MODULAR PATCH PANELS: 48 PORT, EIGHT-POSITION MODULAR JACK PANEL, HIGH DENSITY, 6 PORT MODULES,
CATEGORY 5E, IDC TERMINALS, T568B WIRING SCHEME.
2.03 PATCH CORDS/JUMPERS
A. CATEGORY 6 MODULAR PATCH CORDS: FACTORY TERMINATED DOUBLE ENDED, EIGHT-POSITION TO EIGHT-POSITION, MODULAR,
STRANDED CONDUCTORS, CATEGORY 6, 4 PAIR, COLOR BLUE. 3-FEET, 5-FEET, 7-FEET, AND 9-FEET.
D. FOLLOW THE STANDARDS REQUIREMENTS ESTABLISHED IN ANSI/TIA/EIA-568-C.
2.04 MISCELLANEOUS HARDWARE
E. PERFORM TESTING WITH A LEVEL IV TESTER THE BASIC TESTS REQUIRED ARE:
1. WIRE MAP
2. LENGTH
3. ATTENUATION
4. NEXT (NEAR END CROSSTALK)
5. RETURN LOSS
6. ELFEXT LOSS
7. PROPAGATION DELAY
8. DELAY SKEW
9. PSNEXT (POWER SUM NEAR-END CROSSTALK LOSS)
10. PSELFEXT (POWER SUM EQUAL LEVEL FAR-END CROSSTALK LOSS)
A. PROVIDE SUPPORTING HARDWARE, CABLE TIES, LABELS, UNDERGROUND VAULT RACKING, BULLET BONDS, GEL BLOCKING KITS, PULL
ROPE, AND OTHER MISCELLANEOUS HARDWARE FOR A COMPLETE AND OPERABLE SYSTEM.
PART 3 - EXECUTION
3.01 GENERAL
A. HORIZONTAL CABLING INCLUDES CABLES, JACKS, PATCH PANELS, CONNECTING BLOCKS, AND PATCH CORDS, AS WELL AS THE
NECESSARY SUPPORT SYSTEMS, SUCH AS CABLE MANAGERS AND FACEPLATES.
A. TEST CABLES AND TERMINATION HARDWARE FOR DEFECTS IN INSTALLATION AND TO VERIFY CABLING SYSTEM PERFORMANCE
UNDER INSTALLED CONDITIONS ACCORDING TO THE REQUIREMENTS OF ANSI/TIA/EIA-568-C. VERIFY PAIRS OF EACH INSTALLED CABLE
PRIOR TO SYSTEM ACCEPTANCE. REPAIR OR REPLACE ANY DEFECT IN THE CABLING SYSTEM INSTALLATION INCLUDING BUT NOT
LIMITED TO CABLE, CONNECTORS, FEED THROUGH COUPLERS, PATCH PANELS, AND CONNECTOR BLOCKS IN ORDER TO ENSURE 100
PERCENT USEABLE CONDUCTORS IN CABLES INSTALLED.
B. TEST CABLES IN ACCORDANCE WITH THIS DOCUMENT, THE ANSI/TIA/EIA STANDARDS, THE MANUFACTURER'S PROCEDURES AND BEST
INDUSTRY PRACTICE. IF ANY OF THESE ARE IN CONFLICT, BRING ANY DISCREPANCIES TO THE ATTENTION OF THE PROJECT TEAM FOR
CLARIFICATION AND RESOLUTION.
C. TEST UNSHIELDED TWISTED PAIR CABLES AS FOLLOWS:
1. TEST TWISTED-PAIR COPPER CABLE LINKS FOR CONTINUITY, PAIR REVERSALS, SHORTS, OPENS AND PERFORMANCE AS INDICATED
BELOW. ADDITIONAL TESTING IS REQUIRED TO VERIFY CATEGORY PERFORMANCE. TEST HORIZONTAL CABLING USING A LEVEL III TEST
UNIT FOR CATEGORY 5E OR 6 PERFORMANCE COMPLIANCE AS SPECIFIED IN ANSI/TIA/EIA-568 C.
2. CONTINUITY - TEST EACH PAIR OF EACH INSTALLED CABLE USING A TEST UNIT THAT SHOWS OPENS, SHORTS, POLARITY AND
PAIR-REVERSALS, CROSSED PAIRS AND SPLIT PAIRS. TEST SHIELDED/SCREENED CABLES WITH A DEVICE THAT VERIFIES SHIELD
CONTINUITY IN ADDITION TO THE ABOVE STATED TESTS. RECORD THE TEST AS PASS/FAIL AS INDICATED BY THE TEST UNIT IN
ACCORDANCE WITH THE
MANUFACTURERS' RECOMMENDED PROCEDURES, AND REFERENCED TO THE APPROPRIATE CABLE IDENTIFICATION NUMBER AND
CIRCUIT OR PAIR NUMBER. CORRECT OR REPAIR ANY FAULTS IN THE WIRING AND RETEST THE CABLE PRIOR TO FINAL ACCEPTANCE.
3. LENGTH - TEST EACH INSTALLED CABLE LINK FOR INSTALLED LENGTH USING A TDR TYPE DEVICE. TEST THE CABLES FROM PATCH
PANEL TO PATCH PANEL, BLOCK TO BLOCK, PATCH PANEL TO OUTLET OR BLOCK TO OUTLET AS APPROPRIATE. THE CABLE LENGTH
WILL CONFORM TO THE MAXIMUM DISTANCES SET FORTH IN THE ANSI/TIA/EIA-568-C STANDARD. RECORD CABLE LENGTHS,
REFERENCING THE CABLE IDENTIFICATION NUMBER AND CIRCUIT OR PAIR NUMBER. FOR MULTIPAIR CABLES, RECORD THE SHORTEST
PAIR LENGTH AS THE LENGTH FOR THE CABLE.
D. FOLLOW THE STANDARDS REQUIREMENTS ESTABLISHED IN ANSI/TIA/EIA-568-C.
E. PERFORM TESTING WITH A LEVEL IV TESTER. THE BASIC TESTS REQUIRED ARE:
1. WIRE MAP
2. LENGTH
3. ATTENUATION
4. NEXT (NEAR-END CROSSTALK)
5. RETURN LOSS
6. ELFEXT LOSS
7. PROPAGATION DELAY
8. DELAY SKEW
9. PSNEXT (POWER SUM NEAR-END CROSSTALK LOSS)
10. PSELFEXT (POWER SUM EQUAL LEVEL FAR-END CROSSTALK LOSS)
SHEET TITLE
SPECIFICATION TECHNOLOGY
REVISIONS
F. PROVIDE TEST RESULTS IN ELECTRONIC FORMAT, WITH THE FOLLOWING MINIMUM INFORMATION PER CABLE:
1. CIRCUIT ID
3. DATE AND TIME OF TEST
4. PROJECT NAME
5. NVP
G. PROVIDE AN ELECTRONIC COPY OF THE TEST RESULTS, IN THE NATIVE TESTER SOFTWARE FORMAT, TO THE ARCHITECT ALONG WITH
THE PRINTED TEST RESULTS.
H. PROVIDE A FULLY FUNCTIONAL VERSION OF THE TESTER SOFTWARE FOR USE BY THE ARCHITECT IN REVIEWING THE TEST RESULTS.
I. ANY FAILED TEST RESULTS THAT CANNOT BE REMEDIED THROUGH RETERMINATION (AS IN THE CASE OF REVERSED OR SPLIT PAIRS),
MUST BE REPORTED IN WRITING TO THE ARCHITECT IMMEDIATELY, ALONG WITH A COPY OF THE TEST RESULTS.
DRAWN BY
CR
CHECKED BY
Kevin Kuang
3.04 LABELING
A. LABEL HORIZONTAL CABLES USING A MACHINE PRINTED LABEL AT EACH END OF THE CABLE AT APPROXIMATELY 12-INCHES OF THE
TERMINATION POINT, AND AGAIN AT APPROXIMATELY 48-INCHES FROM THE TERMINATION POINT. DO NOT USE HANDWRITTEN LABELS.
B. LABEL PATCH PANEL PORTS AND TO PORTS WITH THE CABLE IDENTIFIER.
C. DENOTE THE TO ID, AS WELL AS THE UNIQUE CABLE NUMBER FOR THAT TO, I.E. A-001-A FOR CABLE NUMBER 1, A-001-B FOR CABLE
NUMBER 2, AND SO FORTH ON THE LABELS. PROVIDE THE FINAL CABLE ID MATRIX TO THE ARCHITECT ONE WEEK PRIOR TO CABLE
INSTALLATION.
JOB NO.
2014-0284
DATE
DATE
SHEET NUMBER
D. NOTE LABELING INFORMATION ON THE AS-BUILT DRAWINGS.
3.05 PATCH CORDS
B. FURNISH AND INSTALL MATERIALS NECESSARY FOR A COMPLETE AND WORKING SYSTEM.
C. CONTRACTOR MUST BE A CERTIFIED INSTALLER FOR SELECTED MANUFACTURER PRIOR TO, DURING, AND THROUGH COMPLETION OF
1111 Jackson Street
Oakland, California
M. CABLE SIZES ARE SHOWN ON DRAWINGS. VERIFY THAT AS A MINIMUM, TWO CABLE PAIRS ARE PROVIDED FOR EACH TELEPHONE
USER OUTLET. INSTALL SPECIFIED FIBER OPTIC CABLE BETWEEN TRS AS SHOWN ON DRAWINGS.
B. FIBER OPTIC: PROVIDE SUFFICIENT DUPLEX FIBER OPTIC JUMPERS (PATCH CORDS) AT EACH FIBER TERMINATION POINT TO
CROSS-CONNECT ONE-HALF THE NUMBER AND TYPE OF FIBERS TERMINATED THERE, ASSUME A MINIMUM OF TWO DUPLEX FIBER OPTIC
JUMPERS PER TERMINATION POINT FOR A 6-STRAND OPTICAL FIBER. PROVIDE LENGTHS FOR A NEAT APPEARANCE NOT TO EXCEED
15-FEET. SOME JUMPERS MAY REQUIRE LC TO SC, OR SC TO ST CONNECTIONS TO SUPPORT EXISTING OR READILY AVAILABLE
HARDWARE. COORDINATE CONNECTOR REQUIREMENTS WITH OWNER OR OWNER'S REPRESENTATIVE.
JACKSON CENTER ONE
L. IF A J-HOOK OR TRAPEZE SYSTEM IS USED TO SUPPORT CABLE BUNDLES, SUPPORT CABLES AT A MAXIMUM OF 48 TO 60-INCH
INTERVALS. CABLES ARE PROHIBITED TO REST ON ACOUSTIC CEILING GRIDS OR PANELS.
A. FIELD TERMINATED PATCH CORDS AND JUMPERS ARE NOT ALLOWED. AT A MINIMUM, PROVIDE EQUIPMENT CONNECTION CORDS FOR
ONE-HALF THE TOTAL NUMBER OF CABLES INSTALLED AT EACH TERMINATION POINT. FOR EXAMPLE: A TELECOMMUNICATIONS OUTLET
E6.4
NOTE: This is a standard symbol list and not all items listed may be used.
RPM
REVOLUTIONS PER MINUTE
SA
A/C
AIR CONDITION(ED)
AD
ACCESS DOOR
BACKDRAFT DAMPER
BFF
BELOW FINISHED FLOOR
SEASONAL ENERGY EFFICIENCY RATING
SF
SQUARE FEET
SH
SENSIBLE HEAT
SP
STATIC PRESSURE
CU
D
X
X
TD
TEMPERATURE DIFFERENCE
TH
TOTAL HEAT
CEILING DIFFUSER
XX-X
X
KEYED NOTE
V
VOLT
W/
WITH
DX
DIRECT EXPANSION
EAT
ENTERING AIR TEMPERATURE
EER
ENERGY EFFICIENCY RATING
H.
COORDINATE EXACT LOCATION OF CORE DRILLING, CUTTING OF FLOOR SLAB, OR WALLS OF THE
BUILDING WITH THE ARCHITECTURAL AND STRUCTURAL DRAWINGS.
I.
PROVIDE ACCESS DOOR FOR ALL EQUIPMENT, VALVES AND CLEANOUTS WHICH REQUIRE ACCESS
FOR ADJUSTMENT OR SERVICING, AND WHICH ARE LOCATED IN OTHERWISE INACCESSIBLE
LOCATIONS. OPENINGS SHALL BE LARGE ENOUGH TO PERMIT MAINTENANCE AND ADJUSTMENT
OF THE DEVICE.
J.
DUCTS STORED ON THE CONSTRUCTION SITE SHALL BE PROTECTED AND ISOLATED FROM DUST
CONTAMINATION.
K.
PITCH PIPELINES AS REQUIRED FOR PROPER DRAINAGE AND ELIMINATION OF AIR.
L.
THE PROJECT DESIGN SHOWN ON THE DRAWINGS AND SPECIFIC ITEMS REFERENCED IN THE
SPECIFICATIONS IS IN COMPLIANCE WITH THE CODES AND ORDINANCES LISTED IN DIVISION 23
SPECIFICATIONS.
M.
PROVIDE SEISMIC ANCHORAGE AND BRACING FOR MECHANICAL EQUIPMENT, PIPING AND
DUCTWORK. SEE "GENERAL SEISMIC NOTES" FOR DETAIL REQUIREMENTS.
N.
COORDINATE WITH DIVISION 26 CONTRACTOR FOR LOCATION OF POWER AND LOCAL
DISCONNECTS FOR MECHANICAL EQUIPMENT DEVICES.
O.
INSTALL ALL EQUIPMENT AND MATERIALS IN ACCORDANCE WITH MANUFACTURER
RECOMMENDATIONS UNLESS SPECIFICALLY INDICATED OTHERWISE OR WHERE THE LOCAL
CODES OR REGULATIONS TAKE PRECEDENCE.
P.
DRAWINGS ARE DIAGRAMMATIC IN NATURE AND EXISTING CONDITIONS SHALL BE FIELD VERIFIED
FOR EXACT LOCATION AND SIZES OF EXISTING UTILITIES, THE PROPOSED POINT OF
CONNECTIONS TO EXISTING SYSTEMS, AND NEW ROUTINGS. THE CONTRACTOR IS RESPONSIBLE
TO THOROUGHLY VERIFY ALL EXISTING CONDITIONS BEFORE SUBMITTING BID.
Q.
KEEP SAW CUTTING TO THE MINIMUM REQUIRED FOR PROPER EXECUTION OF WORK. BE
RESPONSIBLE FOR ALL CUTTING AND PATCHING NECESSARY FOR THE COMPLETION OF WORK.
NO CUTTING SHALL BE PERFORMED WITHOUT THE APPROVAL OF THE ARCHITECT.
R.
PROVIDE OFFSETS, ELBOWS AND TRANSITIONS IN DUCTWORK AND PIPING AS REQUIRED AT NO
ADDITIONAL COST TO THE OWNER.
S.
VERIFY ALL CONNECTIONS WITH MANUFACTURER'S CERTIFIED DRAWINGS. PROVIDE
TRANSITIONS FOR FINAL CONNECTION TO EQUIPMENT. FIELD VERIFY ALL DIMENSIONS PRIOR TO
FABRICATION OF WORK.
T.
VERIFY DIFFUSERS, GRILLS, AND REGISTER MOUNTING FRAME TYPES WITH CEILING TYPE AND
CONFIGURATION.
U.
PROVIDE DUCT ACCESS DOORS FOR ALL EQUIPMENT AS REQUIRED.
V.
PROVIDE HANGER, SUPPORT AND SWAY BRACES FOR ALL DUCTWORK AND EQUIPMENT AS
REQUIRED BY THE LATEST EDITION OF THE SMACNA GUIDELINES.
W.
DUCT SYSTEMS SHALL BE BALANCED TO CFM ON DRAWINGS. FANS SHALL BE FIELD TESTED TO
ENSURE COMPLIANCE WITH SCHEDULED FAN PERFORMANCE, AIR FLOW AT DESIGN STATIC
PRESSURE.
X.
ALL WORK AND MATERIALS SHALL BE IN COMPLIANCE WITH THE SPECIFICATIONS IN THE EVENT
OF A CONFLICT BETWEEN THE CONTRACT DRAWINGS AND THE SPECIFICATIONS, THE MOST
STRINGENT SHALL GOVERN.
Y.
INSTALL ALL PIPING AND DUCTWORK TO BEST SUIT FIELD CONDITIONS AND COORDINATE WITH
OTHER TRADES. THE DRAWINGS ARE DIAGRAMMATIC, AND SHALL NOT BE SCALED TO
DETERMINE THE EXACT LOCATIONS OF THE PIPING OR DUCTWORK.
CONTINUATION
WB
WET BULB
WC
WATER COLUMN
PIPE DROP
PIPE RISE
FIRE DAMPER
FD
TEE DOWN ON PIPE
FD
FIRE/SMOKE DAMPER
FSD
TEE UP ON PIPE
FSD
MOTORIZED DAMPER
MD
EXHAUST FAN
EFFICIENT
MD
SD
SD
RL
RS
ENTERING WATER TEMPERATURE
EXH
EXHAUST
F
FAHRENHEIT
FD
FIRE DAMPER
REFRIGERANT LIQUID
VOLUME DAMPER
ELECTRICAL
EWT
REFRIGERANT SUCTION
EXHAUST AIR
RETURN AIR
FULL LOAD AMPS
SUPPLY AIR
FEET
GAL
GALLONS
GPH
GALLONS PER HOUR
GPM
GALLONS PER MINUTE
ID
COORDINATE EXACT LOCATION OF CEILING, WALL OR FLOOR ACCESS PANELS FOR FIRE, SMOKE
OR COMBINATION FIRE SMOKE DAMPERS AND VOLUME DAMPERS WITH THE ARCHITECT.
WATT
SMOKE DAMPER
HTG
G.
DROP
DIAMETER
HP
SEAL ALL OPENINGS AROUND PIPING AND DUCTWORK PENETRATING FIRE RESISTIVE RATED
WALLS TO MAINTAIN RATING INTEGRITY.
CAP
CHECK VALVE
DIA
FT
F.
TOTAL PRESSURE
CONDENSING UNIT
DRY BULB
FLA
PROVIDE MANUAL VOLUME DAMPERS TO FACILITATE PROPER BALANCE OF THE AIR DISTRIBUTION
SYSTEM. VOLUME DAMPER AT DIFFUSERS AND REGISTERS SHALL NOT BE USED FOR AIR
BALANCING.
COEFFICIENT OF PERFORMANCE
DB
ELECT
E.
EQUIPMENT IDENTIFICATION
CONTINUATION
DECIBEL
EFF
CONTRACTOR SHALL PROVIDE DUCTWORK AND TRANSITION EQUAL TO DUCT FREE AREA OF
DUCTWORK AS SHOWN ON DRAWINGS, TO PREVENT A CONFLICT WITH EXISTING CONDITIONS OR
TO RESOLVE DUCTWORK CONFLICTS.
DETAIL NUMBER AND SHEET LOCATION
LOCATION
CONDENSATE DRAIN
DB
EF
D.
BRAKE HORSEPOWER
W
CV
CONTINUATION
12x12
100
CD-1
DIFFUSER OR GRILLE IDENTIFICATION
HORSEPOWER
ACOUSTICALLY LINED DUCT
(SIZES SHOWN ARE NET
INSIDE)
HEATING
INSIDE DIAMETER
BELLMOUTH
IE
INVERT ELEVATION
IN
INCHES
KW
KILOWATT
LAT
LEAVING AIR TEMPERATURE
LBS.
POUNDS
LH
LATENT HEAT
MA
MIXED AIR
MAX
MAXIMUM
MBH
THOUSAND BTU'S PER HOUR
MD
MINIMUM
N/A
NOT APPLICABLE
NIC
NOT IN CONTRACT
NOT TO SCALE
OA
OUTSIDE AIR
OC
ON CENTER
PRESSURE DROP
PH
PHASE
QTY
R
RA
MITERED ELBOW WITH
TURNING VANES
Z.
CONTRACTOR SHALL FIELD-VERIFY EXISTING CONDITIONS AND SHALL REPORT ANY
DISCREPANCIES AND/OR INCONSISTENCIES BETWEEN THE DRAWINGS AND EXISTING CONDITIONS
TO THE ENGINEER BEFORE COMMENCEMENT OF WORK.
AA.
CONTRACTOR SHALL BE RESPONSIBLE FOR SECURING ALL TRADE PERMITS AND INSPECTIONS.
RECTANGULAR DUCT RISER
AB.
ALL DUCTWORK SHALL BE CONSTRUCTED AND INSTALLED TO MEET SMACNA AND THE LATEST
CALIFORNIA MECHANICAL CODE.
RECTANGULAR MAIN WITH
RECTANGULAR BRANCH
AC.
ALL EXISTING DUCTWORK THAT IS TO BE REUSED SHALL BE CLEANED AFTER CONSTRUCTION.
CONTRACTOR TO VERIFY CONDITION IN FIELD, DO NOT CLEAN DUCTWORK IF DUCTS ARE LINED.
RECTANGULAR MAIN WITH
ROUND BRANCH
AD.
REFERENCE RECORD DRAWINGS FOR BID ESTIMATE.
AE.
SUPPLY DUCTWORK FROM EQUIPMENT TO BE LINED FOR 10' FROM UNIT.
RADIUSED ELBOW
RECTANGULAR DUCT DROP
SHEET TITLE
SYMBOL LIST,
GENERAL NOTES MECHANICAL
REVISIONS
RECTANGULAR OFFSET LESS
RECTANGULAR OFFSET MORE
DRAWN BY
ROUND DUCT DROP
OUTSIDE DIAMETER
PD
PSI
ECCENTRIC TRANSITION,
RECTANGULAR OR ROUND
NUMBER
NTS
OD
CONCENTRIC TRANSITION,
RECTANGULAR OR ROUND
MOTORIZED DAMPER
MIN
NO.
CONCENTRIC SQUARE TO
ROUND
1111 Jackson Street
Oakland, California
COP
ANY NEW OR EXISTING DUCT OR PIPING OFFSETS REQUIRED AS RESULT OF JOB CONDITIONS OR
LACK OF COORDINATION WITH OTHER TRADES SHALL BE PROVIDED AT NO ADDITIONAL COST TO
THE OWNER.
NEW WORK
TEMPERATURE
TP
CONT.
C.
717 Market Street
Suite 500
San Francisco, CA 94103
TEL
415.489.7240
FAX 415.489.7289
www.interfaceengineering.com
JACKSON CENTER ONE
CD
ALL MATERIALS AND WORKMANSHIP ARE SUBJECT TO APPROVAL BY OWNER. ANY DEFECTIVE
WORK SHALL BE REPLACED BY THE CONTRACTOR AS PART OF THIS CONTRACT AT NO
ADDITIONAL COST TO THE OWNER.
EXISTING WORK
T, TEMP
CD
B.
ABOVE FINISHED FLOOR
BDD
BHP
ALL NEW CONSTRUCTION SHALL CONFORM TO CURRENT CITY, STATE, AND NATIONAL CODES,
STANDARDS, AND REQUIREMENTS.
SUPPLY AIR
SEER
AFF
DEMOLISH (DASH-DOT)
A.
ROUND DUCT RISER
ROUND DUCT WITH ROUND
BRANCH
POUNDS PER SQUARE INCH
CR
M0.1
M0.2
SYMBOL LIST, GENERAL NOTES - MECHANICAL
SCHEDULES - MECHANICAL
CHECKED BY
M2.1
M2.2
PARTIAL BASEMENT PLAN AND FIRST FLOOR PLAN - MECHANICAL
PARTIAL SECOND THRU EIGHT FLOOR PLANS AND PARTIAL ROOF PLAN - MECHANICAL
JOB NO.
M3.1
PIPING PLAN - MECHANICAL
DATE
M4.1
DETAILS - MECHANICAL
M5.1
M5.2
SPECIFICATIONS - MECHANICAL
SPECIFICATIONS - MECHANICAL
QUANTITY
RISE
RETURN AIR
DEMOLISH
Jesse M Agosta
2014-0284
DATE
SHEET NUMBER
M0.1
1111 Jackson Street
Oakland, California
JACKSON CENTER ONE
717 Market Street
Suite 500
San Francisco, CA 94103
TEL
415.489.7240
FAX 415.489.7289
www.interfaceengineering.com
SHEET TITLE
SCHEDULES MECHANICAL
REVISIONS
DRAWN BY
CR
CHECKED BY
Jesse M Agosta
JOB NO.
2014-0284
DATE
DATE
SHEET NUMBER
M0.2
1111 Jackson Street
Oakland, California
2 PARTIAL FIRST FLOOR PLAN - MECHANICAL
SHEET TITLE
PARTIAL
BASEMENT PLAN
AND PARTIAL
FIRST FLOOR PLAN
- MECHANICAL
REVISIONS
1
2
3
4
5
6
7
8
9
10
A
B
DRAWN BY
COPY
STAFF
ENTRANCE
CR
C
SECURITY DESK
CHECKED BY
QUEUEING
D
WAITING
(20 SEATS)
INT 2
SELF-SERVE
INT 3
AAMS KIOSKS
SELF-SERVE
INT 1
AAMS PHONES
1 PARTIAL BASEMENT PLAN - MECHANICAL
JACKSON CENTER ONE
717 Market Street
Suite 500
San Francisco, CA 94103
TEL
415.489.7240
FAX 415.489.7289
www.interfaceengineering.com
Jesse M Agosta
INT 4
CLERKS
E
JOB NO.
2014-0284
DATE
DATE
KEY PLAN - BASEMENT
KEY PLAN - FIRST FLOOR
SHEET NUMBER
M2.1
SHEET KEYNOTES
FC-2
THRU
FC-8
1
RL/RS TO CU ON ROOF.
2
RL/RS DN TO FC'S SEE DETAIL 10/M4.1.
3
CONDENSATE PIPE TO RISER DOWN TO BASEMENT.
717 Market Street
Suite 500
San Francisco, CA 94103
TEL
415.489.7240
FAX 415.489.7289
www.interfaceengineering.com
3
M4.1
T
3
LAN
storage
GAS LINE
UP TO ROOF
(E)ENGINE/GENERATOR SET
1
pantry
equipment
CU-1
graphic
main streeet
coffee
bar
phone
2
(TYP)
ELEV. #3
2" SLEAVED
PENETRATIONS
ELEV. #2
1 PARTIAL SECOND THRU SEVENTH FLOOR PLANS - MECHANICAL
0
4'
8'
8
M4.1
2
CU-2
ELEV. #1
PENTHOUSE
16'
STAIR #2
SCALE: 1/8"=1'-0"
3
M4.1
FC-9
3
1
T
LAN
2
3 ROOF FLOOR PLAN - MECHANICAL
0
4'
8'
16'
SCALE: 1/8"=1'-0"
GAS LINE
UP TO ROOF
1111 Jackson Street
Oakland, California
JACKSON CENTER ONE
ELECTRICAL ROOM
SHEET TITLE
pantry
equipment
PARTIAL 2ND
THRU 8TH AND
PARTIAL ROOF
PLAN MECHANICAL
graphic
main streeet
coffee
bar
phone
REVISIONS
equipment
Reception
7
8
9
storage
LAN
ELEV. #3
Pantry
SUPPORT
SPACE
ELEV. #2
ELEV. #1
DRAWN BY
10
PENTHOUSE
CR
STAIR #2
2 PARTIAL EIGHTH FLOOR PLANS - MECHANICAL
0
4'
8'
phone
equipment
pantry
main streeet
coffee
bar
graphic
phone
11
CHECKED BY
16'
Jesse
Ed M
Dizon
Agosta
Lunch Room
12
JOB NO.
SCALE: 1/8"=1'-0"
T
R
1, 2
M2.2
N
M
K
H
F
E
C
2014-0284
A
3
M2.2
DATE
DATE
KEY PLAN SECOND THRU EIGTH FLOORS
KEY PLAN - ROOF
NO SCALE
NO SCALE
SHEET NUMBER
M2.2
717 Market Street
Suite 500
San Francisco, CA 94103
TEL
415.489.7240
FAX 415.489.7289
www.interfaceengineering.com
G
1111 Jackson Street
Oakland, California
JACKSON CENTER ONE
G
SHEET TITLE
PIPING DIAGRAM MECHANICAL
REVISIONS
DRAWN BY
CR
CHECKED BY
Jesse M Agosta
JOB NO.
2014-0284
DATE
DATE
SHEET NUMBER
M3.1
THESE TWO HANGERS ARE TO BE USED ON DUCTS
25" & LARGER ( MAY BE USED ON SMALLER DUCTS).
THIS HANGER IS FOR
DUCTS 24" DIA. &
SMALLER
3/8" DIA. ROD OR
1" X 16Ga. HANGER
STRAP. (TYPICAL)
1" X 16Ga.
HANGER STRAP
1/4" BOLT, NUT &
STAR WASHER (TYP.)
3/8" BOLT, NUT &
STAR WASHER
717 Market Street
Suite 500
San Francisco, CA 94103
TEL
415.489.7240
FAX 415.489.7289
www.interfaceengineering.com
NOTES:
1. REFER TO SPECIFICATIONS FOR
HANGER SPACINGS.
2. ATTACHMENTS TO OVERHEAD STRUCTURE
SHALL BE MADE IN
ACCORDANCE WITH STRUCTURAL
ENGINEERS REQUIREMENTS
AND WEIGHT LIMITATIONS. ALL ATTACHMENT
METHODS TO
STRUCTURE SHALL BE SUBMITTED TO
ARCHITECT AND
STRUCTURAL ENGINEER FOR REVIEW.
1" X 16Ga. CONTINUOUS
COLLAR DRAWN TIGHT
AROUND DUCT
NUT & LOCKNUT
EACH STRAP ADJACENT
TO ONE ANOTHER AT
HANGER LOCATION.
(TYPICAL)
3. PROVIDE SWAY & SEISMIC BRACING PER
SMACNA SEISMIC
GUIDELINES AND THE LATEST EDITION OF
CALIFORNIA
BUILDING CODE. CONTRACTOR SHALL
INDICATE LOCATIONS
OF SEISMIC BRACING ON THE SHOP DRAWING
SUBMITTALS.
ROUND DUCT HANGER
3/8" DIA. ROD, OR 1" X
16Ga. HANGER STRAP, (TYP.)
1" X 18Ga.
STRAP OVER
DUCT (TYP.)
1/2" DIA. ROD.
(TYPICAL)
4. HANGER MATERIAL SUPPORTING FLEXIBLE
DUCT SHALL IN NO
CASE BE LESS THAN 1 1/2 INCHES WIDE.
FLEXIBLE DUCT
SHALL BE SUPPORTED PER MANUFACTURER'S
RECOMMENDED
MATERIALS, BUT AT NO GREATER DISTANCE
THAN 4 FEET
MAX. PERMISSIBLE SAG IS MAX. 1/2 INCHES
PER FOOT OF
SPACING BETWEEN SUPPORTS.
2" X 2" X 1/8"
ANGLE TOP
& BOTTOM
SHEET METAL
SCREWS
(TYPICAL)
MAX
60"
ANGLE (TYP.)
61"
MAX
AND OVER
RECTANGULAR DUCT HANGER
JACKSON CENTER ONE
30"
1111 Jackson Street
Oakland, California
1" X 16Ga. HANGER
STRAP, (TYP.)
SHEET TITLE
DETAILS MECHANICAL
HEM
REVISIONS
24 GA.GALV.
FLASHING
THREAD ROD
WITH COUPLER
8" MIN.
1-1/8" X 12Ga.
SPLIT RING
COLLAR AROUND
DUCT
DRAWN BY
CR
CHECKED BY
Jesse M Agosta
JOB NO.
2014-0284
DATE
DATE
SHEET NUMBER
M4.1
1.9
PART 1 - GENERAL
RECORD DRAWINGS
A.
1.1 DEFINITIONS
FOLLOWING IS A LIST OF ABBREVIATIONS GENERALLY USED IN DIVISION 23:
1. ADA
AMERICANS WITH DISABILITIES ACT.
2. AHJ
AUTHORITY HAVING JURISDICTION.
3. ANSI
AMERICAN NATIONAL STANDARDS INSTITUTE.
4. ARI
AIR-CONDITIONING & REFRIGERATION INSTITUTE.
5. ASHRAE
AMERICAN SOCIETY OF HEATING, REFRIGERATING AND AIR-CONDITIONING ENGINEERS.
6. ASME
AMERICAN SOCIETY OF MECHANICAL ENGINEERS.
7. ASTM
AMERICAN SOCIETY FOR TESTING AND MATERIALS.
8. ASSE
AMERICAN SOCIETY OF SANITARY ENGINEERING.
9. AWWA
AMERICAN WATER WORKS ASSOCIATION.
10. CBC
CALIFORNIA BUILDING CODE.
11. CEC
CALIFORNIA ELECTRICAL CODE.
12. CMC
CALIFORNIA MECHANICAL CODE.
13. CPC
CALIFORNIA PLUMBING CODE.
14. ETL
ELECTRIC TESTING LABORATORIES.
15. FM
FM GLOBAL.
16. HI
HYDRAULIC INSTITUTE STANDARDS.
17. HVAC
HEATING, VENTILATING AND AIR CONDITIONING.
18. MSS
MANUFACTURERS STANDARDIZATION SOCIETY.
19. NEMA
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION.
20. NFPA
NATIONAL FIRE PROTECTION ASSOCIATION.
21. NFGC
NATIONAL FUEL GAS CODE.
22. NRCA
NATIONAL ROOFING CONTRACTORS ASSOCIATION.
23. NSF
NATIONAL SANITATION FOUNDATION.
24. OSHA
OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION.
25. SMACNA
SHEET METAL AND AIR CONDITIONING CONTRACTORS' NATIONAL ASSOCIATION, INC.
26. TEMA
TUBULAR EXCHANGER MANUFACTURERS ASSOCIATION.
27. TIMA
THERMAL INSULATION MANUFACTURERS ASSOCIATION.
28. UL
UNDERWRITERS LABORATORIES INC.
B.
PROVIDE: TO FURNISH AND INSTALL, COMPLETE AND READY FOR THE INTENDED USE.
C.
FURNISH: SUPPLY AND DELIVER TO THE PROJECT SITE, READY FOR UNPACKING, ASSEMBLY AND INSTALLATION.
D.
INSTALL: INCLUDES UNLOADING, UNPACKING, ASSEMBLING, ERECTING, INSTALLATION, APPLYING, FINISHING, PROTECTING, CLEANING AND
SIMILAR OPERATIONS AT THE PROJECT SITE AS REQUIRED TO COMPLETE ITEMS OF WORK FURNISHED BY OTHERS.
1.10
A.
B.
2.1
A.
B.
MECHANICAL DRAWINGS:
1. THE MECHANICAL DRAWINGS ARE INTENDED TO BE DIAGRAMMATIC AND ARE BASED ON ONE MANUFACTURER'S EQUIPMENT. THEY ARE
NOT INTENDED TO SHOW EVERY ITEM IN ITS EXACT DIMENSIONS, OR DETAILS OF EQUIPMENT OR PROPOSED SYSTEMS LAYOUT. VERIFY
ACTUAL DIMENSIONS OF SYSTEMS (I.E. DUCTS AND PIPING) AND EQUIPMENT PROPOSED TO ASSURE THAT SYSTEMS AND EQUIPMENT WILL
FIT IN AVAILABLE SPACE.
2. INSTALLATION OF ALL MECHANICAL SYSTEMS WITHIN LIMITATIONS IMPOSED BY ARCHITECTURAL, STRUCTURAL, AND ELECTRICAL
REQUIREMENTS. PROVIDE ADEQUATE SPACE FOR MANUFACTURER'S RECOMMENDED MAINTENANCE AND CODE_REQUIRED CLEARANCES.
C.
SUBSTITUTIONS:
1. WHERE MATERIALS OR EQUIPMENT ARE SPECIFIED BY NAME OF MANUFACTURER, SUCH SPECIFICATION TO BE DEEMED TO BE USED FOR
PURPOSES OF ESTABLISHING A STANDARD OF QUALITY FOR THAT PARTICULAR ITEM. MATERIALS OR EQUIPMENT TO CONFORM TO
SPECIFICATIONS AND DRAWINGS IN ALL RESPECTS. MODIFICATION TO EQUIPMENT TO CONFORM TO SPECIFICATIONS OR DRAWINGS IS
REQUIRED IF LISTED MANUFACTURER CANNOT MEET REQUIREMENTS WITH A REGULARLY CATALOGED ITEM. INCLUSION OF A
MANUFACTURER'S NAME AS ACCEPTABLE TO PROVIDE SPECIFIC EQUIPMENT DOES NOT INDICATE THAT MANUFACTURER'S STANDARD
CATALOGUED COMPONENTS WILL PERFORM AS REQUIRED, OR THAT THEY WILL FIT IN ALLOCATED PHYSICAL SPACE FOR EQUIPMENT.
VERIFY THAT EQUIPMENT WHICH IS PROPOSED TO BE PROVIDED WILL FIT IN ALLOCATED PHYSICAL SPACE, WITH ALL REQUIRED
MANUFACTURERS AND CODE REQUIRED CLEARANCES.
2. EQUIPMENT SUBMITTED FOR SUBSTITUTION TO MEET ALL CONTRACT DOCUMENT REQUIREMENTS INCLUDING QUALITY ESTABLISHED BY
BRAND SPECIFIED. INDICATE ALL DEVIATIONS OR NONCOMPLIANCES BY AN ATTACHED LETTER EXPLAINING A PROPOSED CHANGE.
ACCEPTANCE OF SUBMITTED MATERIAL DOES NOT GRANT DEVIATION FROM CONTRACT REQUIREMENTS. ADDITIONAL EXPENSE
RESULTING BY DECISION TO USE SUBSTITUTE MATERIALS MUST BE INCLUDED IN BID SUM AND SHALL INCLUDE ALL COSTS BY OTHER
AFFECTED CRAFTS.
3. VARIATIONS IN EQUIPMENT: IF APPROVED MECHANICAL EQUIPMENT OF OTHER MANUFACTURER REQUIRES MODIFICATION OR ADDITIONS
TO OTHER WORK SHOWN ON DRAWINGS, ARRANGE FOR AND PAY ALL COSTS OF SUCH CHANGES AT NO ADDITIONAL COST TO OWNER.
4. "OR APPROVED": WHERE EQUIPMENT MAKE IS LISTED, FOLLOWED BY PHRASE "OR APPROVED," THIS SHALL REQUIRE SUBMITTAL OF
PROPOSED MAKE PRIOR TO BIDDING FOR REVIEW AND APPROVAL BY ARCHITECT.
ALL MATERIALS AND PRODUCTS USED FOR CONSTRUCTION SHALL BE NEW, OF BEST GRADE AND OF LATEST PRODUCTS AS LISTED IN PRINTED
MANUFACTURER'S CATALOG DATA. ALL ARTICLES OF A KIND ARE STANDARD PRODUCT OF A SINGLE MANUFACTURER. TRADE NAMES AND
MANUFACTURER'S NAMES DENOTE CHARACTER AND QUALITY OF EQUIPMENT DESIRED AND SHALL NOT BE CONSTRUED AS LIMITING
COMPETITION. REFERENCES TO PRODUCT SPECIFICATIONS FOR MATERIALS ARE LISTED ACCORDING TO ACCEPTED BASE STANDARDS. ALL
MATERIALS SHALL MEET LATEST APPROVED VERSIONS OF THESE STANDARDS.
3.1
INSPECTION
A.
3.2
ALL WORK AND MATERIALS SUBJECT TO INSPECTION AT ANY AND ALL TIMES BY ARCHITECT AND/OR OWNER'S REPRESENTATIVE.
SUPERVISION
A.
3.3
CONSTANTLY SUPERVISE WORK COVERED BY THESE SPECIFICATIONS. VERIFY ALL CONDITIONS ON JOB SITE AND LAY OUT WORK
ACCORDINGLY.
EQUIPMENT IDENTIFICATION
A.
3.4
EACH NEW PIECE OF EQUIPMENT SHALL BEAR A PERMANENTLY ATTACHED IDENTIFICATION PLATE, LISTING MANUFACTURER'S NAME,
CAPACITIES, SIZES AND CHARACTERISTICS.
A.
PRIOR TO ACCEPTANCE OF WORK AND DURING TIME DESIGNATED BY ARCHITECT, PROVIDE NECESSARY QUALIFIED PERSONNEL TO OPERATE
SYSTEM FOR PERIOD OF 2 HOURS.
B.
DURING OPERATING PERIOD, FULLY INSTRUCT OWNER'S REPRESENTATIVE IN COMPLETE OPERATIONS, ADJUSTMENT AND MAINTENANCE OF
EACH RESPECTIVE INSTALLATION.
C.
OPERATIONS AND MAINTENANCE DATA: AT TIME OF SYSTEM DEMONSTRATION, DELIVER TO OWNER TWO BOUND COPIES (3_RING BINDER
TYPE) OF OPERATION AND MAINTENANCE MANUALS CONTAINING FOLLOWING MATERIALS:
1. CATALOG DESCRIPTION OF EACH ITEM OF EQUIPMENT ACTUALLY INSTALLED ON JOB.
2. INSTRUCTIONS FOR OPERATION AND MAINTENANCE OF MECHANICAL SYSTEMS COMPOSED OF OPERATING INSTRUCTIONS, MAINTENANCE
INSTRUCTIONS AND MANUFACTURER'S LITERATURE AS FOLLOWS:
a. MAINTENANCE SCHEDULE CHART: PROVIDE AN 8_1/2_ BY 11_INCH TYPEWRITTEN LIST OF EACH ITEM OF INSTALLED EQUIPMENT
REQUIRING INSPECTION, LUBRICATION OR SERVICE, DESCRIBING AND SCHEDULING PERFORMANCE OF SUCH MAINTENANCE.
b. MANUFACTURER'S LITERATURE: PROVIDE COPIES OF MANUFACTURER'S INSTRUCTIONS FOR OPERATION AND MAINTENANCE OF ALL
MECHANICAL EQUIPMENT, INCLUDING REPLACEMENT PARTS LIST WITH NAME AND ADDRESS OF NEAREST DISTRIBUTOR. MARK EACH
COPY WITH EQUIPMENT IDENTIFICATION LABEL AS LISTED IN EQUIPMENT SCHEDULE, I.E. AC_5, EF_10, ETC.
B.
3.6
NOTIFY ARCHITECT AT FOLLOWING STAGES OF CONSTRUCTION SO THAT ARCHITECT MAY, AT HIS OPTION, VISIT SITE FOR REVIEW AND
CONSTRUCTION OBSERVATION:
1. PLUMBING:
a. PRIOR TO COVERING WALLS
b. WHEN CEILING INSTALLATION IS STARTED.
2. HVAC:
a. WHEN DUCT AND PIPE SYSTEMS INSTALLATION STARTS.
b. WHEN INSTALLATION STARTS FOR EACH DIFFERENT MAJOR TYPE OF EQUIPMENT.
c. WHEN CEILING INSTALLATION IS STARTED.
d. WHEN ANY LINES OR DUCTS ARE TO BE PERMANENTLY CONCEALED BY CONSTRUCTION OR INSULATION SYSTEMS.
e. WHEN BALANCING AND TESTING IS STARTED.
OPERATING DURING CHANGEOVER
A.
DURING REMODELING OF AN EXISTING STRUCTURE, OR ADDITION OF A STRUCTURE TO AN EXISTING STRUCTURE, WHILE AN EXISTING
STRUCTURE IS OCCUPIED, PRESENT SERVICES SHALL REMAIN INTACT UNTIL NEW CONSTRUCTION, FACILITIES OR EQUIPMENT IS INSTALLED.
UNLESS OTHERWISE NOTED, WHERE SPECIFICATION REFERS TO SMACNA IN REFERENCE TO SHEET METAL OR FLEXIBLE DUCTWORK
ACCESSORIES, THIS REFERS TO HVAC DUCT CONSTRUCTION STANDARDS, METAL AND FLEXIBLE, LATEST EDITION, AS PUBLISHED BY SMACNA
(SHEET METAL AND AIR CONDITIONING CONTRACTORS NATIONAL ASSOCIATION, INC.).
C.
DO ACTUAL TRANSFER TO NEW SERVICE AT AN OFF_PEAK TIME, AS ARRANGED WITH OWNER. ONCE CHANGEOVER IS STARTED, VIGOROUSLY
PURSUE IT TO ITS COMPLETION, TO KEEP INTERFERENCE TO A MINIMUM.
C.
D.
MEET REQUIREMENTS AS A MINIMUM REQUIREMENT, AND INCLUDE ANY COST NECESSARY TO MEET THESE IN CONTRACT. ALL MACHINERY
AND EQUIPMENT SHALL COMPLY WITH OCCUPATIONAL SAFETY AND HEALTH ACT OF 1970, AS CURRENTLY REVISED, AS INTERPRETED FOR
EQUIPMENT MANUFACTURER REQUIREMENTS. INSTALL ALL EQUIPMENT PROVIDED PER MANUFACTURER RECOMMENDATIONS. SEE "LETTER
OF CONFORMANCE" THIS SECTION.
3.7
3.8
B.
OBTAIN CERTIFICATES OF INSPECTION FROM PUBLIC AHJ AND DELIVER TO OWNER BEFORE FINAL ACCEPTANCE.
C.
EACH TRADE TO CONSULT LOCAL BUILDING DEPARTMENT, UTILITY COMPANIES AND OWNER PRIOR TO COMMENCEMENT OF WORK TO
ASCERTAIN EXISTENCE AND LOCATION OF EXISTING UNDERGROUND UTILITIES. PROTECT EXISTING SERVICE AGAINST DAMAGE AND
INTERRUPTION OF USE, AND REROUTE AS MAY BE NECESSARY TO ACCOMPLISH NEW WORK. INCLUDE COSTS FOR MATERIALS AND
INSTALLATION FOR REROUTING AS SPECIFIED FOR NEW WORK IN BID PRICE.
3.9
B.
A.
3.10
UPON COMPLETION OF WORK AND ADJUSTMENT OF ALL EQUIPMENT, TEST SYSTEMS TO DEMONSTRATE TO OWNER'S REPRESENTATIVE AND
ARCHITECT THAT ALL EQUIPMENT FURNISHED AND INSTALLED OR CONNECTED UNDER PROVISIONS OF THESE SPECIFICATIONS FUNCTIONS
MECHANICALLY IN MANNER REQUIRED.
PIPING AND EQUIPMENT REMOVAL
A.
PIPING AND EQUIPMENT REMOVED AND IDENTIFIED AS SALVAGE BY OWNER TO REMAIN PROPERTY OF OWNER.
B.
COMPLY WITH SITE DEMOLITION PORTION OF SPECIFICATION..
C.
CONTRACTOR TO REMOVE AND DISPOSE OF EXCESS PIPING, DUCTWORK AND EQUIPMENT REMOVED (AND NOT IDENTIFIED BY OWNER AS
SALVAGE).
3.11
CUTTING AND PATCHING
A.
CUTTING AND PATCHING PERFORMED UNDER DIVISION 15 SHALL INCLUDE BUT NOT BE LIMITED TO:
1. SAW CUTTING AND TRENCHING NEW AND EXISTING CONCRETE FLOORS.
2. CUTTING AND PATCHING OF PLASTER OR PARTITIONS.
3. CUTTING AND TRIMMING OPENINGS IN CASE WORK FOR INSTALLATION OR CONNECTION OF PLUMBING FIXTURES. COUNTERTOP
OPENINGS FOR SINKS CUT BY CASEWORK SUPPLIER.
4. CUTTING AND PATCHING OF FINISHED CEILINGS.
THE MECHANICAL EQUIPMENT SHALL BE COMPATIBLE WITH, ACKNOWLEDGE AND ACCOMMODATE, REQUIREMENTS OF OTHER TRADES.
RESOLVE WITHOUT ADDITIONAL COST TO OWNER THOSE DETAILS NECESSARY TO ASSURE THAT MECHANICAL SYSTEMS PROPERLY AND
COMPLETELY FUNCTION TOGETHER WHEN ASSEMBLED AND ACHIEVE ALL REQUIRED PERFORMANCE AND CONFORM TO ALL REQUIREMENTS
OF ALL GOVERNING CODES AND REGULATORY AGENCIES.
B.
PERFORM CUTTING AND PATCHING BY SKILLED CRAFTSMEN IN TRADE OF WORK TO BE PERFORMED. FILL HOLES WHICH ARE CUT OVERSIZED
FOR COMPLETED WORK. REFINISHING SHALL MATCH EXISTING ADJACENT FINISH AND SHALL BE ACCEPTABLE TO ARCHITECT.
C.
VERIFY IF EXISTING ROOF IS UNDER WARRANTY. PERFORM ALL WORK TO MAINTAIN WARRANTY.
COORDINATE VARIOUS PORTIONS OF WORK AS TO SCHEDULING, INSTALLATION PROCEDURES, SHOP DRAWINGS AND FINAL INSTALLATION OF
ALL RELATED MATERIALS. PROMPTLY NOTIFY OWNER OF ANY DEFECTS OR IMPERFECTIONS WHICH WILL AFFECT SATISFACTORY COMPLETION
OF THIS WORK.
D.
WHEN MASONRY OR CONCRETE CONSTRUCTION MUST BE PENETRATED, FURNISH AND INSTALL A STEEL PIPE SLEEVE IN OPENING AND GROUT
IN PLACE IN A NEAT MANNER. LEAVE GROUT SURFACE TO MATCH EXISTING FINISH. PROVIDE ESCUTCHEONS. IF SLEEVES ARE NOT PROVIDED,
CORE DRILL ALL PENETRATIONS.
1.7 SUBMITTALS
A.
ADJUST CONTROLS FOR PROPER OPERATION. ADJUST REGULATORS, ETC. OPEN AND CLOSE SHUTOFF AND CONTROL VALVES SEVERAL
TIMES TO ENSURE TIGHT GLANDS. FLUSH PIPING THOROUGHLY AFTER TESTING AND PRIOR TO CONNECTING EQUIPMENT OR FIXTURES.
CLEAN FIXTURES AND ADJUST FAUCETS AND VALVES.
DEMONSTRATION
1.6 COMPATIBILITY AND COORDINATION
A.
COORDINATE DEMOLITION OF EXISTING MECHANICAL SYSTEMS. COORDINATE EXTENT OF DEMOLITION OF MECHANICAL WORK WITH OTHER
TRADES. NO EXTRA COSTS WILL BE APPROVED BY REPLACEMENT OF SYSTEMS DUE TO IMPROPER OR EXCESSIVE DEMOLITION.
ADJUSTING AND CLEANING
A.
1.5 PERMITS AND INSPECTIONS
UNLESS OTHERWISE DISTINCTLY HEREINAFTER SPECIFIED, SUBMIT DRAWINGS AND DOCUMENTS FOR PERMIT REVIEW, APPLY AND PAY FOR
ALL NECESSARY PERMITS AND INSPECTIONS REQUIRED BY ANY PUBLIC AHJ.
SHOP DRAWINGS:
1. UNLESS OTHERWISE APPROVED, PROVIDE ALL MECHANICAL SHOP DRAWINGS AT ONE TIME IN A VINYL COVERED THREE_RING
LOOSE_LEAF BINDER OR ELECTRONICALLY.
2. CLEARLY REFERENCE EACH ITEM BY PAGE AND PARAGRAPH TO APPLICABLE PORTION OF SPECIFICATIONS. WHERE EQUIPMENT IS
DESIGNATED BY NUMBER OR SYMBOL ON DRAWINGS SUBMITTAL SHALL ALSO SHOW THIS NUMBER OR SYMBOL.
3. SPECIFICALLY NOTE ALL SPECIFIED FEATURES AND PERFORMANCE DATA ON SUBMITTAL.
4. CHECK SHOP DRAWINGS FOR SPACE REQUIREMENTS AND CONFORMANCE WITH SPECIFICATIONS AND MARK CORRECTIONS AND
APPROVAL ON ALL SHOP DRAWINGS PRIOR TO SUBMITTAL TO ARCHITECT.
5. THE ENGINEER WILL REVIEW THE ORIGINAL SUBMITTAL AND ONE RESUBMITTAL FOR THE SAME PRODUCT. ADDITIONAL RESUBMITTALS
WILL BE REVIEWED ON AN HOURLY RATE, PAYABLE BY THE CONTRACTOR.
6. PARTIAL SUBMITTALS OR SUBMITTALS NOT PROPERLY FORMATTED AS INDICATED ABOVE, ARE SUBJECT TO RETURN WITHOUT REVIEW
FOR THE CONTRACTOR TO CORRECT
7. SHOP DRAWINGS WILL DEPICT PIPE/DUCT SIZES, ROUTING, MOUNTING DETAIL USED, ELEVATION, COORDINATION WITH OTHER TRADES
AND EXISTING CONDITIONS. EQUIPMENT WILL ALSO BE SHOWN ON THE SHOP DRAWINGS WITH APPROPRIATE CLEARANCES.
A.
COPPER TUBE FOR CONDENSATE PIPING: HARD DRAWN COPPER, TYPES "K," AND "L" CONFORMING TO ASTM B88. FITTINGS SHALL BE
WROUGHT COPPER OR CAST BRONZE SOLDER JOINT FITTINGS CONFORMING TO ANSI B16.22.
2.3 ESCUTCHEONS
A.
BRASS MATERIAL, CHROME PLATED FINISH. SIZE SUFFICIENT TO COVER ALL PIPE OPENINGS THROUGH WALL, FLOOR OR CEILING. SET SCREW
OR SPRING TO SECURE TO PIPE.
2.4 PIPE HANGERS AND SUPPORTS
A.
PIPE HANGER SIZE 3 INCHES AND SMALLER: ADJUSTABLE MALLEABLE IRON, SPLIT RING HANGER, BLACK, UL LISTED. MICHIGAN 111. FIGURE
100 OR 101 APPROVED.
B.
PIPE HANGER LARGER THAN SIZE 3 INCHES: ADJUSTABLE STEEL CLEVIS TYPE HANGER, BLACK, UL LISTED. MICHIGAN 400 OR 415.
C.
RISER CLAMPS: BLACK STEEL CLAMP. MICHIGAN 510. COPPER COATED: MICHIGAN 368.
2.5 ACCESS DOORS
A.
STEEL 24 BY 24 INCHES (OR REQUIRED AND APPROVED SIZE) COMPLETE WITH STEEL FRAME, HINGED LOCKING DOOR AND PRIME COAT FINISH.
MILCOR, KARP, ELMDOR, OR APPROVED. WHERE ACCESS PANELS ARE LOCATED IN FIRE RATED AREAS OF STRUCTURE, RATE ACCORDINGLY.
PART 3 - EXECUTION
3.1 PIPE AND PIPE FITTINGS
A.
INSTALL UNIONS IN NON-FLANGED PIPE CONNECTIONS TO APPARATUS AND ADJACENT TO ALL SCREWED CONTROL VALVES, TRAPS AND
APPURTENANCES REQUIRING REMOVAL FOR SERVICING, SO LOCATED THAT PIPING MAY BE DISCONNECTED WITHOUT DISTURBING GENERAL
SYSTEMS. PROVIDE DIELECTRIC COUPLINGS, UNIONS OR FLANGES BETWEEN GALVANIZED STEEL AND COPPER PIPE OR TUBING.
1. RUN ALL PIPING PARALLEL TO BUILDING STRUCTURE AND SUPPORT IT SUFFICIENTLY TO PREVENT SAGGING.
2. INSTALL ALL PIPING WHERE POSSIBLE SO AS TO VENT AND DRAIN.
3. SUPPORT ALL PIPING INDEPENDENTLY SO THAT ITS WEIGHT IS NOT CARRIED BY EQUIPMENT.
B.
SCREWED JOINTS SHALL HAVE PIPE ENDS REAMED, DOPE OR TAPE APPLIED TO MALE THREADS ONLY, WITH EXCEPTION OF BRASS TO BRASS
JOINTS WHICH SHALL BE MADE WITH TEFLON TAPE ONLY.
C.
FOR BRAZE TYPE JOINTS, USE FOS-COPPER ROD ON WROUGHT COPPER FITTINGS, OR SILVER BRAZING ALLOY WITH FLUX RECOMMENDED FOR
THAT PARTICULAR ALLOY ON ALL FITTINGS. CLEAN COPPER TUBING AND FITTINGS THOROUGHLY BEFORE APPLYING FLUX. REMOVE ALL
COPPER TUBING BURRS, REAM TO FULL BORE AND TRUE AND ROUND ALL JOINTS. APPLY HEATING UNIFORMLY TO SECURE PENETRATION OF
ROD AND LEAVE A FULL BEAD AROUND ENTIRE CIRCUMFERENCE OF JOINT TO SHOW PROPER PENETRATION AND SEALING. UNDER NO
CIRCUMSTANCES WILL FOS-COPPER BE USED ON CAST FITTINGS. USE SILVER BEARING SOLDER ON REFRIGERANT COPPER PIPING. COMPLY
WITH RECENT CALIFORNIA CODES REGARDING LEAD CONTENT.
3.2 ESCUTCHEONS
INSTALL AT ALL EXPOSED PIPES PASSING THROUGH FLOORS OR WALLS.
A.
GENERAL: PROVIDE ADJUSTABLE HANGERS ON ALL PIPES, COMPLETE WITH ADJUSTERS, SWIVELS, RODS, ETC. SIZE HANGERS TO CLEAR
INSULATION AND GUIDES.
B.
ON HOT PIPE LINES WHERE EXPANSION AND CONTRACTION OCCURS, PROVIDE SWIVEL JOINT AT TOP OR BOTTOM OF HANGER ROD.
C.
PROVIDE HANGER WITHIN 3 FEET OF ALL CHANGES IN DIRECTION.
D.
BRANCHES 5 FEET OR LONGER SHALL HAVE SEPARATE HANGER.
E.
PLUMBERS TAPE: NOT PERMITTED AS PIPE HANGERS.
F.
HANGER SPACING:
1. CAST IRON SOIL PIPE: AT EACH JOINT AND AT INTERVALS NOT TO EXCEED 8 FEET.
2. STEEL PIPE 1 INCH AND SMALLER: 7 FEET.
3. STEEL PIPE 1_1/4 INCHES AND LARGER: 10 FEET.
4. COPPER TUBING 1_1/4 INCHES AND SMALLER: 6 FEET.
5. COPPER TUBING 1_1/2 INCHES AND LARGER: 10 FEET.
3.4 PIPE AND EQUIPMENT IDENTIFICATION
A.
PIPE MARKERS:
1. ADHESIVE PIPE MARKERS OF WIDTH, LETTER SIZE AND BACKGROUND COLOR CONFORMING TO ANSI A13.1.
2. BRADY B350, SETON, ZESTON, OR APPROVED.
3. COORDINATE COLORS WITH ARCHITECT.
B.
NAMEPLATES:
1. ENGRAVED NAMEPLATES, 1/16_INCH THICK, LAMINATED 3_PLY PLASTIC, CENTER PLY WHITE, OUTER PLY BLACK, LETTERS FORMED BY
EXPOSING CENTER PLY. BRADY, SETON, ZESTON, OR APPROVED.
2. SIZE: 3_ BY 5_INCH NAMEPLATE WITH 1/4_INCH HIGH LETTERS.
3. SEE SECTION 15010, EQUIPMENT IDENTIFICATION.
DEMOLITION
A.
WHENEVER THIS SPECIFICATION CALLS FOR MATERIAL, WORKMANSHIP, ARRANGEMENT OR CONSTRUCTION OF HIGHER QUALITY OR CAPACITY
THAN THAT REQUIRED BY GOVERNING CODES, HIGHER QUALITY SHALL TAKE PRECEDENCE.
A.
REFERENCES TO PRODUCT SPECIFICATIONS FOR MATERIALS ARE LISTED ACCORDING TO ACCEPTED BASE STANDARDS. ALL MATERIALS
SHALL MEET LATEST APPROVED VERSIONS OF THESE STANDARDS. COMMERCIAL GRADE PIPING MATERIALS ARE INDICATED FOR REFERENCE.
2.2 PIPING MATERIALS
SHOULD CONTRACTOR FAIL TO NOTIFY ARCHITECT AT TIMES PRESCRIBED ABOVE, IT SHALL BE CONTRACTOR'S RESPONSIBILITY AND COST TO
MAKE DUCTWORK ACCESSIBLE, EXPOSE ANY CONCEALED LINES, OR DEMONSTRATE ACCEPTABILITY OF ANY PART OF SYSTEM. ANY EXTRA
COST CAUSED BY REMOVAL OF SUCH WORK SHALL BE BORNE BY CONTRACTOR.
E.
ALL WORK AND MATERIALS SHALL CONFORM TO PUBLIC UTILITY, LOCAL AND STATE CODES, AND ALL STATE AND OTHER APPLICABLE LAWS
AND REGULATIONS. UPON COMPLETION OF MECHANICAL SYSTEMS INSTALLATION, SUBMIT CERTIFICATES OF INSPECTION BY ALL CODE
AUTHORITIES HAVING JURISDICTION (AHJS).
A.
717 Market Street
Suite 500
San Francisco, CA 94103
TEL
415.489.7240
FAX 415.489.7289
www.interfaceengineering.com
3.3 PIPE HANGERS AND SUPPORTS
A.
PRIOR TO CHANGING OVER TO NEW SERVICE, VERIFY THAT EVERY ITEM IS THOROUGHLY PREPARED. INSTALL ALL NEW PIPING, WIRING, ETC.
TO POINT OF CONNECTION.
B.
2.1 PRODUCT STANDARDS
REVIEW BY ENGINEER
B.
AS A MINIMUM REQUIREMENT, UNLESS OTHERWISE SPECIFIED, ALL WORK SHALL BE IN ACCORDANCE WITH FOLLOWING RULES AND
REGULATIONS AND ANY APPLICABLE LAWS:
1. NFPA.
2. OSHA.
3. STATE OF CALIFORNIA AND LOCAL JURISDICTIONAL REQUIREMENTS.
PROVIDE SHOP DRAWINGS FOR FOLLOWING EQUIPMENT:
1. PIPING MATERIALS.
PART 2 - PRODUCTS
A.
3.5
REGULATORY REQUIREMENTS _ UL AND CSA COMPLIANCE: PROVIDE UNITS WHICH ARE UL AND CSA LISTED.
A.
A.
OPERATING AND MAINTENANCE INSTRUCTIONS
D.
1.4 PERMITS, CODES AND LAWS
1.1 SUBMITTALS
PART 3 - EXECUTION
1.3 QUALITY ASSURANCE
WHERE DRAWINGS OR SPECIFICATIONS ARE AT VARIANCE WITH APPLICABLE CODES GOVERNING WORK, CODE REQUIREMENTS TAKE
PRECEDENCE, AND INCLUDE COSTS NECESSARY TO MEET THESE IN BID PRICE.
INCLUDE MANUFACTURER'S STANDARD PRODUCT WARRANTY, COVERING MECHANICAL EQUIPMENT OPERATION UNDER NORMAL CONDITIONS
AND USE, WHERE INSTALLED, OPERATED AND MAINTAINED IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. PROVIDE PRODUCT
WARRANTY PERIOD TERMINATING 12 MONTHS AFTER SUBSTANTIAL COMPLETION. PROVIDE ADDITIONAL MANUFACTURER'S 5_YEAR
WARRANTY ON ALL REFRIGERANT COMPRESSORS.
MATERIAL
WORK INCLUDED: PROVIDE COMPLETE PLUMBING, HEATING, VENTILATION AND AIR CONDITIONING SYSTEMS AS OUTLINED IN THIS
SPECIFICATION.
A.
GENERAL: PROVIDE WRITTEN WARRANTY ON MECHANICAL WORK, AGREEING TO REPLACE/REPAIR INADEQUATE AND DEFECTIVE MATERIALS
AND QUALITY OF WORK, INCLUDING LEAKAGE, BREAKAGE, IMPROPER ASSEMBLY AND FAILURE TO PERFORM AS REQUIRED FOR A PERIOD OF
ONE YEAR FROM DATE OF OWNER'S ACCEPTANCE. INCLUDE SEPARATE PRODUCT WARRANTIES AS INDICATED (IF ANY) FOR SPECIFIC PARTS
OR PRODUCTS IN WORK. PROVIDE WARRANTY SIGNED BY BOTH INSTALLER AND CONTRACTOR.
PART 2 - PRODUCTS
1.2 SUMMARY
A.
WARRANTY
PART 1 - GENERAL
E.
LOCATE ALL CONCEALED UTILITIES TO ELIMINATE ANY POSSIBLE SERVICE INTERRUPTION OR DAMAGE.
F.
NO EXTRA WILL BE ALLOWED FOR LACK OF PROPER COORDINATION.
3.12
3.5 ACCESS DOORS
A.
INSTALL ACCESS PANELS TO PROVIDE ACCESS TO ALL CONCEALED VALVES, FANS, MOTORS, FIRE DAMPERS, ETC., AND ALL ITEMS NEEDING
SERVICE.
SHEET TITLE
SPECIFICATIONS MECHANICAL
REVISIONS
FIRESTOPPING PENETRATIONS IN FIRE_RATED WALL/FLOOR ASSEMBLIES
A.
3.13
PROVIDE PROPER SIZING WHEN PROVIDING SLEEVES OR CORE_DRILLED HOLES TO ACCOMMODATE PENETRATION. FIRESTOP ALL VOIDS
BETWEEN SLEEVE OR CORE_DRILLED HOLE AND PIPE PASSING THROUGH TO MEET REQUIREMENTS OF ASTM E814.
LETTER OF CONFORMANCE
A.
PROVIDE LETTER AND COPIES OF EXTENDED WARRANTIES WITH A STATEMENT IN LETTER THAT ALL MECHANICAL ITEMS WERE INSTALLED IN
ACCORDANCE WITH MANUFACTURE'S RECOMMENDATIONS. IF MANUFACTURER'S RECOMMENDATIONS FOR INSTALLATION HAVE NOT BEEN
FOLLOWED, CONTRACTOR SHALL SO STATE, GIVE REASONS WHY AND HE SHALL WARN ARCHITECT OF ANY CONDITION WHICH MAY IMPAIR
FUNCTIONING OF APPARATUS OR VOID MANUFACTURER'S WARRANTY. INCLUDE LETTER OF CONFORMANCE AND WARRANTIES IN OPERATING
AND MAINTENANCE MANUALS.
DRAWN BY
CR
CHECKED BY
Jesse M Agosta
1.8 VISITING PREMISES
A.
BEFORE SUBMITTING BID ON WORK, VISIT SITE AND BECOME FAMILIAR WITH ALL VISIBLE EXISTING CONDITIONS. NO ADDITIONAL ALLOWANCE
WILL BE GRANTED DUE TO LACK OF INFORMATION OF VISIBLE EXISTING CONDITIONS.
B.
THE SUBMISSION OF A BID WILL BE CONSIDERED AN ACKNOWLEDGMENT ON PART OF BIDDER OF HIS VISITATION TO SITE.
1111 Jackson Street
Oakland, California
A.
MAINTAIN A WEEKLY UPDATED SET OF AS-CONSTRUCTED DOCUMENTS. AT CONCLUSION OF BUILDING PROJECT, TRANSFER THESE WEEKLY
UPDATED DOCUMENTS TO A RECORD SET OF DRAWINGS.
SECTION 230100 - BASIC MATERIALS AND METHODS
JACKSON CENTER ONE
SECTION 230000 - BASIC MECHANICAL REQUIREMENTS
JOB NO.
2014-0284
DATE
DATE
SHEET NUMBER
M5.1
A.
1.1 QUALITY ASSURANCE
A.
QUALIFICATION OF WORKMEN: USE PROFICIENT JOURNEYMAN INSULATORS AND SUPERVISORS IN EXECUTION OF THIS PORTION OF WORK TO
ENSURE PROPER AND ADEQUATE INSTALLATION OF INSULATION THROUGHOUT.
B.
COMPLIANCE WITH SPECIFICATIONS: AS A MINIMUM, COMPLY WITH APPROPRIATE STATE ENERGY CODE REGULATIONS OR OTHER APPLICABLE
CODES.
1. WHENEVER REQUIRED DURING PROGRESS OF WORK, FURNISH PROOF ACCEPTABLE TO ARCHITECT THAT ITEMS INSTALLED ARE EQUAL TO
OR EXCEED ALL REQUIREMENTS SPECIFIED FOR THIS WORK.
2. IN EVENT SUCH PROOF IS NOT AVAILABLE, OR IS NOT ACCEPTABLE TO ARCHITECT, ARCHITECT MAY REQUIRE CONTRACTOR TO REMOVE
ITEM OR ITEMS AND REPLACE WITH MATERIAL MEETING SPECIFIED REQUIREMENTS AND TO REPAIR ALL DAMAGE CAUSED IN REMOVAL
AND REPLACEMENT, ALL AT NO ADDITIONAL COST TO OWNER.
1.2 SUBMITTALS
A.
2.3 REFRIGERANT PIPING
A.
A.
PROTECTION: USE ALL MEANS NECESSARY TO PROTECT INSULATION MATERIALS BEFORE, DURING AND AFTER INSTALLATION.
B.
REPLACEMENTS: IN EVENT OF DAMAGE, IMMEDIATELY MAKE ALL REPAIRS AND REPLACEMENTS NECESSARY.
1.4 FIRE HAZARD CLASSIFICATION
A.
MAXIMUM FIRE HAZARD CLASSIFICATION OF COMPOSITE INSULATION CONSTRUCTION AS INSTALLED SHALL BE NOT MORE THAN A FLAME
SPREAD OF 25, FUEL CONTRIBUTED OF 50 AND SMOKE DEVELOPED OF 50.
B.
TEST PIPE INSULATION IN ACCORDANCE WITH REQUIREMENTS OF UL "PIPE AND EQUIPMENT COVERINGS R5583 400 8.15".
C.
TEST DUCT INSULATION IN ACCORDANCE WITH ASTM E84 AND BEAR UL LABEL.
MATERIALS TO BE MOLD-, HUMIDITY-, AND EROSION-RESISTANT SURFACE THAT MEETS THE REQUIREMENTS OF UL 181.
A.
ARMACELL, LLC ARMAFLEX, CERTAINTEED, IMCOA, JOHNS MANVILLE, KNAUF, OWENS-CORNING, PPG, OR APPROVED.
FIBERGLASS SECTIONAL PIPE INSULATION: THERMAL CONDUCTIVITY OF 0.24 (BTU/IN)/HR/SQ.FT./DEG. F) AT 75F MEAN TEMPERATURE. MINIMUM
DENSITY OF 1.5 LBS. PER CU.FT. JACKETED WITH WHITE VAPOR BARRIER LAMINATED OF ALUMINUM FOIL AND WHITE KRAFT PAPER
REINFORCED WITH GLASS FIBER STRANDS. JACKET SHALL HAVE FACTORY APPLIED SELF-SEALING LAP.
B.
DUCT LINING: NOT ALLOWED FOR PROJECT.
C.
DUCT WRAP: FIBERGLASS DUCT INSULATION WITH THERMAL CONDUCTIVITY OF 0.23 (BTU/IN)/HR/SQ.FT./DEG. F) AT 75F MEAN TEMPERATURE.
MINIMUM DENSITY OF 1.5 LBS. PER CU.FT. FACTORY APPLIED FLAME RETARDANT FOIL REINFORCED KRAFT VAPOR BARRIER FACING.
D.
PIPE FITTING INSULATION COVERS: PVC PREFORMED MOLDED INSULATION COVERS. ZESTON OR APPROVED.
E.
CALCIUM SILICATE: HYDROUS CALCIUM SILICATE TESTED IN ACCORDANCE WITH ASTM C533 TYPE I WITH A MINIMUM OF 200 PSI AT 5 PERCENT
COMPRESSION.
PART 3 - EXECUTION
3.1 INSULATION THICKNESS
A.
GENERAL: INSULATION THICKNESS TO BE MINIMUM SPECIFIED OR AS REQUIRED TO MEET STATE ENERGY CODE. MOST STRINGENT SHALL
GOVERN.
B.
DUCTWORK INSIDE BUILDING INSULATION ENVELOPE:
1. DUCT WRAP: COVER SUPPLY DUCTS WITH 1.5_INCH DUCT WRAP EXCEPT WHERE SPECIFIED OR NOTED ON DRAWINGS FOR DUCTS TO BE
LINED OR WHERE FIBERGLASS DUCTBOARD IS USED. DUCT WRAP NOT ALLOWED IN MECHANICAL ROOMS OR WHERE DUCT IS EXPOSED.
TOTAL THERMAL RESISTANCE TO BE AT LEAST 4.0.
D.
A.
INSTALLATION SHALL BE CONTINUOUS THROUGH WALLS, FLOORS, PARTITIONS EXCEPT WHERE NOTED OTHERWISE.
B.
FIBERGLASS SECTIONAL PIPE INSULATION: APPLY INSULATION TO PIPE AND SEAL WITH SELF-SEALING LAP. USE SELF-SEALING BUTT STRIPS
TO SEAL BUTT JOINTS. INSULATE ALL FITTINGS, VALVES AND UNIONS WITH SINGLE OR MULTIPLE LAYERS OF INSULATION AND COVER TO
MATCH PIPE OR USE PREFORMED PVC MOLDED INSULATION COVERS.
C.
DUCT LINERS: NOT ALLOWED ON PROJECT.
D.
DUCT WRAP: COVER SUPPLY AIR DUCTS EXCEPT DUCTS INTERNALLY LINED. WRAP TIGHTLY WITH ALL CIRCUMFERENTIAL JOINTS BUTTED AND
LONGITUDINAL JOINTS OVERLAPPED MINIMUM OF 2 INCHES. ADHERE INSULATION WITH 4_INCH STRIPS OF INSULATING BENDING ADHESIVE AT
8 INCHES ON CENTER. ON DUCTS OVER 24 INCHES WIDE, ADDITIONALLY SECURE INSULATION WITH SUITABLE MECHANICAL FASTENERS AT 18
INCHES ON CENTER. CIRCUMFERENTIAL AND LONGITUDINAL JOINTS STAPLED WITH FLARE STAPLES ON 6_INCH CENTERS AND COVERED WITH
3_INCH-WIDE FOIL REINFORCED TAPE.
CALCIUM SILICATE PIPE INSULATION: INSTALL IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. SEAL CANVAS JACKET TIGHT TO
INSULATION AT LAP JOINTS. INSULATION SHALL BE CONTINUOUS OVER PIPE, FITTINGS AND ALL SUPPORTS OR HANGERS. NO HOLIDAYS OR
GAPS PERMITTED.
F.
INSULATION SHIELDS: PROVIDE FULL SIZE DIAMETER HANGERS AND SHIELDS (18 GAUGE MINIMUM) FOR ALL COLD PIPING. HOT PIPING
HANGERS MAY PENETRATE INSULATION TO CONTACT PIPE DIRECTLY. PROVIDE 18-INCH LONG, NON-COMPRESSIBLE INSULATION SECTION AT
INSULATION SHIELDS FOR LINES 2 INCH AND LARGER (STEAM AND COLD PIPING).
SECTION 15500 - HEATING, VENTILATING AND AIR CONDITIONING
PART 1 - GENERAL
1.1 SUBMITTALS
A.
PROVIDE SHOP DRAWINGS FOR FOLLOWING EQUIPMENT:
1. DIFFUSERS AND GRILLES.
2. AIR CONDITIONING UNITS.
3. DUCT AND PIPE CONSTRUCTION STANDARDS.
4. INSULATION.
1.2 SUMMARY
A.
WORK INCLUDES BUT IS NOT LIMITED TO FOLLOWING MAJOR ITEMS:
1. ALL AIR DISTRIBUTION, HEATING, COOLING, VENTILATION AND EXHAUST SYSTEMS.
2. EQUIPMENT USED FOR DISTRIBUTION OF AIR, INCLUDING FANS, MOTORS, CONTROLS, CONTROL WIRING, FILTERS, DUCTWORK, AIR SUPPLY
OUTLETS, AIR RETURN AND EXHAUST INLETS.
3. ALL OTHER COMPONENTS SPECIFIED AND/OR REQUIRED FOR A COMPLETE OPERATING SYSTEM.
FURNISH, SIZE, INSTALL, AND INSULATE REFRIGERANT PIPE FOR SYSTEM AS REQUIRED BY MANUFACTURER. SUBMIT SHOP DRAWINGS OF
PIPING SYSTEM SHOWING ALL TRAPS, PIPE SIZES, AND ACCESSORIES. PIPE SIZES TO BE AS RECOMMENDED BY UNIT MANUFACTURER.
SUBMIT LINE SIZING CALCULATIONS FOR REVIEW BY ENGINEER.
A.
MANUFACTURER'S PROGRAMMABLE THERMOSTAT.
2.3 TRANSFORMERS
PART 3 - EXECUTION
3.1 SEQUENCE OF OPERATION
E.
AFTER DEHYDRATION, INTRODUCE MANUFACTURER'S RECOMMENDED TYPE AND QUANTITY OF REFRIGERANT INTO SYSTEM THROUGH A
FILTER/DRYER.
A.
TRANSFORMERS SELECTED AND SIZED FOR APPROPRIATE VA CAPACITY AND INSTALLED AND FUSED ACCORDING TO APPLICABLE CODES.
PROVIDE WIRING TO NEAREST SUITABLE POWER SOURCE AS REQUIRED.
A.
PROGRAMMABLE THERMOSTAT SHALL CONTROL CU & FC SYSTEM TO MEET TEMPERATURE SET POINT.
B.
SEE PLANS FOR ADDITIONAL REQUIREMENTS.
717 Market Street
Suite 500
San Francisco, CA 94103
TEL
415.489.7240
FAX 415.489.7289
www.interfaceengineering.com
PART 3 - EXECUTION
3.1 INSPECTION
A.
EXAMINE AREAS AND CONDITIONS UNDER WHICH SPLIT SYSTEM UNITS AND FURNACES ARE TO BE INSTALLED. DO NOT PROCEED WITH WORK
UNTIL UNSATISFACTORY CONDITIONS HAVE BEEN CORRECTED IN MANNER ACCEPTABLE TO INSTALLER.
3.2 INSTALLATION
A.
GENERAL: INSTALL UNITS IN ACCORDANCE WITH MANUFACTURER'S INSTALLATION INSTRUCTIONS, PLUMB AND LEVEL, AND FIRMLY ANCHORED
IN LOCATIONS INDICATED. MAINTAIN MANUFACTURER'S RECOMMENDED AND CODE-REQUIRED ACCESS AND CLEARANCES.
B.
SUPPORT: PROVIDE NEOPRENE VIBRATION ISOLATION PADS FOR FLOOR-MOUNTED EQUIPMENT AND SPRING VIBRATION ISOLATORS FOR
SUSPENDED EQUIPMENT.
C.
DUCTWORK: CONNECT SUPPLY AND RETURN TO UNIT WITH FLEXIBLE DUCT CONNECTIONS. PROVIDE TRANSITIONS TO EXACTLY MATCH UNIT
DUCT CONNECTION SIZE. CONNECT OUTSIDE AIR TO UNIT WITH FLEXIBLE CONNECTIONS.
D.
DRAIN PIPING: RUN FULL SIZE TO CODE APPROVED DISCHARGE LOCATION. PROVIDE TRAP AT DRAIN PAN; CONSTRUCT 1 INCH DEEPER THAN
FAN PRESSURE IN INCHES OF WATER.
E.
SECTION 230593 - TESTING, ADJUSTING AND BALANCING
PART 1 - GENERAL
1.1 SUMMARY
A.
WORK INCLUDED: MATERIALS, EQUIPMENT AND LABOR REQUIRED FOR TESTING, ADJUSTING, AND BALANCING WORK REQUIRED BY THIS
SECTION, INCLUDING AIR DISTRIBUTION SYSTEMS, AND ASSOCIATED EQUIPMENT AND APPARATUS. THE WORK CONSISTS OF SETTING SPEED
AND VOLUME (FLOW) ADJUSTMENTS, RECORDING DATA, CONDUCTING TESTS, PREPARING AND SUBMITTING REPORTS, AND RECOMMENDING
MODIFICATIONS TO WORK AS REQUIRED.
B.
RELATED DOCUMENTS: DRAWINGS AND GENERAL PROVISIONS OF CONTRACT, INCLUDING GENERAL AND SUPPLEMENTARY CONDITIONS AND
DIVISION_1 SPECIFICATION SECTIONS, APPLY TO WORK SPECIFIED IN THIS SECTION.
1.2 QUALITY ASSURANCE
A.
START UP: START UP IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. TEST CONTROLS AND DEMONSTRATE COMPLIANCE WITH
REQUIREMENTS. REPLACE DAMAGED OR MALFUNCTIONING CONTROLS AND EQUIPMENT.
3.3 INSTALLATION OF COOLING UNITS
A.
B.
GENERAL: INSTALL UNITS IN ACCORDANCE WITH MANUFACTURER'S INSTALLATION INSTRUCTIONS, PLUMB AND LEVEL, AND FIRMLY ANCHORED
IN LOCATIONS INDICATED. MAINTAIN MANUFACTURER'S RECOMMENDED CLEARANCES.
AIR_COOLED CONDENSING UNITS: CONNECT REFRIGERANT PIPING TO UNIT, RUN PIPING SO AS NOT TO INTERFERE WITH ACCESS TO UNIT.
INSTALL FURNISHED FIELD-MOUNTED ACCESSORIES. VERIFY MANUFACTURER'S REQUIREMENTS AND PROVIDE ACCUMULATION WHEN
REQUIRED DUE TO LENGTH OF REFRIGERANT PIPING.
3.4 INSULATION
A.
INSULATE ALL REFRIGERANT PIPING AS REQUIRED BY MANUFACTURER, CONDENSATE DRAINS, AND ALL OTHER ASSOCIATED
APPURTENANCES.
3.5 FILTERS
A.
INSTALL COMPLETE SETS OF FILTERS BEFORE OPERATION OF SUPPLY FANS. FANS SHALL NOT BE OPERATED WITHOUT FILTERS INSTALLED.
REMOVE COILS FROM UNITS AND CLEAN IF UNITS ARE RUN WITHOUT FILTERS.
B.
PROVIDE TWO SETS OF FILTER CARTRIDGES FOR EACH SUPPLY FAN. CLEAN FILTERS TO BE INSTALLED PRIOR TO SYSTEM BALANCING.
3.6 DUCTWORK
CODES AND STANDARDS:
1. NEBB COMPLIANCE: COMPLY WITH NEBB'S "PROCEDURAL STANDARDS FOR TESTING, ADJUSTING, AND BALANCING OF ENVIRONMENTAL
SYSTEMS" AS APPLICABLE TO MECHANICAL AIR AND HYDRONIC DISTRIBUTION SYSTEMS, AND ASSOCIATED EQUIPMENT AND APPARATUS;
OR COMPLY WITH AABC'S MANUAL MN_1, "AABC NATIONAL STANDARDS," AS APPLICABLE TO EQUIPMENT AND APPARATUS.
2. INDUSTRY STANDARDS: COMPLY WITH ASHRAE RECOMMENDATIONS PERTAINING TO MEASUREMENTS, INSTRUMENTS, AND TESTING,
ADJUSTING AND BALANCING, EXCEPT AS OTHERWISE INDICATED.
1.3 QUALIFICATIONS
A.
WORK OF THIS SECTION SHALL BE PERFORMED BY AN AABC CERTIFIED CONTRACTOR.
PART 2 - PRODUCTS
2.1 TOOLS, EQUIPMENT, INSTRUMENTS
A.
CALIBRATE ALL INSTRUMENTS USED FOR BALANCING WITHIN A PERIOD OF SIX MONTHS AND SUBMIT PROOF OF SUCH CALIBRATION TO
MECHANICAL ENGINEER IF REQUESTED.
2.2 REPORTS AND RECORDS
A.
SUBMIT FIVE COPIES OF COMPLETE BALANCING REPORT ON FORMS SIMILAR IN CONTENT TO STANDARD AABC OR NEBB TEST FORMS.
PROVIDE WITH EACH REPORT A COMPLETE SET OF MARKED BALANCING DRAWINGS SHOWING AIR OPENING NUMBERS THAT CORRESPOND TO
NUMBERING SYSTEM IN BALANCING LOGS.
PART 3 - EXECUTION
3.1 TESTING PROCEDURES _ AIR SYSTEMS
A.
ERECT ALL DUCTWORK IN A FIRST-CLASS MANNER, TRUE TO DIMENSIONS INDICATED, STRAIGHT AND SMOOTH ON INSIDE WITH NEATLY
FINISHED JOINTS LAPPED IN DIRECTION OF AIR TRAVEL. PROPERLY BRACE AND REINFORCE ALL DUCTS WITH STEEL ANGLES OR OTHER
MEMBERS.
A.
IDENTIFY AND LIST SIZE, TYPE AND MANUFACTURER OF ALL AIR HANDLING EQUIPMENT AND AIR DISTRIBUTION DEVICES. USE
MANUFACTURER'S PUBLISHED RATINGS ON ALL EQUIPMENT TO MAKE REQUIRED CALCULATIONS.
B.
ELBOWS: STANDARD CENTERLINE RADIUS SHALL EQUAL 1_1/2 TIMES WIDTH OF DUCT.
B.
TEST, ADJUST AND RECORD FAN RPM TO DELIVER WITHIN PLUS OR MINUS 10 PERCENT OF AIR QUANTITY SPECIFIED. PLUG ALL TEST HOLES.
C.
LOCATE ACCESS DOORS IN DUCTWORK AS REQUIRED FOR SERVICE OF FIRE DAMPERS, AUTOMATIC DAMPERS AND OTHER ITEMS REQUIRING
MAINTENANCE OR INSPECTION. PROVIDE VENTLOCK NO. 100 LATCH WITH NO. 150 HINGES AND FELT GASKETS. MINIMUM SIZE 12X12 OR
EQUIVALENT AREA.
C.
AFTER ALL AIR FLOW MEASUREMENTS HAVE BEEN MADE, MARK FINAL POSITION OF BALANCING DAMPER.
D.
RECORD NAMEPLATE DATA AND ACTUAL RUNNING AMPERES FOR EACH FAN MOTOR.
E.
TEST AND RECORD SYSTEM STATIC PRESSURE, SUCTION AND DISCHARGE.
F.
TEST AND ADJUST SYSTEM FOR DESIGN OUTSIDE AIR AND RETURN AIR.
G.
TEST AND RECORD ENTERING AND LEAVING AIR DRY-BULB TEMPERATURE FOR HEATING CYCLE OF EACH FAN SYSTEM.
H.
TEST, ADJUST AND RECORD EACH DIFFUSER, GRILLE AND REGISTER TO WITHIN 10 PERCENT OF DESIGN REQUIREMENTS. IDENTIFY EACH
GRILLE, DIFFUSER AND REGISTER AS MARKED ON BALANCING DRAWINGS.
D.
E.
DUCT HANGERS AND SUPPORTS: HANG DUCTS UNDER 20 INCHES DIAMETER OR MAXIMUM SIDE DIMENSION WITH GALVANIZED STRIPS OF NO.
16 U.S.S. GAUGE STEEL 1_INCH WIDE AND ALL LARGER DUCTS WITH STEEL ANGLES AND ADJUSTABLE HANGER RODS SIMILAR TO PIPING
HANGERS. ANCHOR ALL DUCTS SECURELY TO BUILDING IN SUCH MANNER AS TO PREVENT TRANSMISSION OF VIBRATION TO STRUCTURE.
SEAL ALL JOINTS IN DUCTS WITH 3M COMPANY OR JOHNS MANVILLE INDUSTRIAL GRADE PRESSURE SENSITIVE TAPE OR 6_INCH WIDTH OF SIX
OUNCE CANVAS PASTED ON WITH ARABOL. RAY CHEM SHRINK TAPE APPROVED.
3.7 BALANCING
A.
E.
PART 2 - PRODUCTS
TEST PIPING TO ABOVE OPERATING TEMPERATURE AS RECOMMENDED BY THE MANUFACTURER.
REFRIGERATION PIPE: INSULATE LIQUID PIPING WITH 1 INCH FLEXIBLE, ELASTOMERIC INSULATION. PROVIDE UV PROTECTIVE JACKETING FOR
OUTDOOR INSULATION.
3.2 INSTALLATION
WIRING: SHALL BE AS REQUIRED FOR A COMPLETE OPERATING CONTROL SYSTEM, PER STATE AND NATIONAL ELECTRICAL CODES. PROVIDE
NECESSARY RELAYS, TRANSFORMERS, FUSING, SWITCHES AND PILOT LIGHTS. FEED INTERLOCKS AND CONTROL POWER FROM NEAREST
PANEL.
D.
2.2 MATERIAL
A.
A.
INSTALL AND INSULATE ALL REFRIGERANT PIPING PER UNIT MANUFACTURER'S LATEST PUBLISHED RECOMMENDATIONS. SLOPE ALL LINES TO
FACILITATE OIL RETURN TO COMPRESSOR. PROVIDE SUCTION LINE TRAPS PER MANUFACTURER'S RECOMMENDATIONS. INSTALL
REFRIGERANT PIPING AS SHOWN EXCEPT THAT MODIFICATIONS SHALL BE MADE AS RECOMMENDED BY UNIT MANUFACTURER. MAKE SUCH
MODIFICATIONS AT NO COST TO OWNER.
PART 2 - PRODUCTS
2.1 MANUFACTURERS
1.1 SYSTEM DESCRIPTION
C.
1.5 LINING MATERIALS
A.
FABRICATE REFRIGERANT PIPING OF HIGH DEFORMABILITY PIPING TYPE 'L' HARD DRAWN "ACR" TUBING THAT HAS BEEN CLEANED AND CAPPED
FOR REFRIGERATION SERVICE. FITTINGS SHALL BE WROUGHT COPPER , RATED TO MATCH THE PIPING, AND INSTALLED WITH SILVER SOLDER
JOINTS. CAREFULLY CLEAN END OF ALL PIPE AND INSIDE OF ALL FITTINGS BEFORE JOINING. USE NO ACID IN CLEANING OR AS A FLUX IN
SOLDERING JOINTS. BLEED NITROGEN THROUGH ALL PIPING WHILE SOLDERING.
PART 1 - GENERAL
2.1 ROOM THERMOSTATS
B.
PRODUCT DATA: BEFORE INSULATING MATERIALS ARE DELIVERED TO JOB SITE, SUBMIT COMPLETE DATA SHOWING INSULATION MATERIALS
PROPOSED TO BE FURNISHED AND INSTALLED.
1.3 PRODUCT HANDLING
DUCTWORK: CONSTRUCT FROM GALVANIZED SHEET METAL TO CONFORM TO CMC SMACNA, LATEST EDITION, OR LATEST EDITION OF ASHRAE
GUIDE TABLE.
SECTION 230923 - CONTROLS
BALANCING BY CONTRACTOR. BALANCE AIR SYSTEM TO WITHIN PLUS OR MINUS 10 PERCENT OF DESIGN VALUES. PROVIDE A BALANCING
REPORT AT END OF PROJECT. SEE SECTION 15990, TESTING, ADJUSTING AND BALANCING, FOR REQUIREMENTS.
END OF MECHANICAL SPECIFICATIONS
1111 Jackson Street
Oakland, California
PART 1 - GENERAL
2.2 DUCT CONSTRUCTION
JACKSON CENTER ONE
SECTION 230700 - INSULATION
SHEET TITLE
1.3 AIR DISTRIBUTION DUCT SYSTEM
A.
GENERAL: ALL DUCTWORK, INCLUDING COLLARS, REGISTER BOXES, FIRE DAMPERS, EXHAUST FANS, VENTILATION LOUVERS, ROOF VENTS
AND SCREENS, AS WELL AS ALL DAMPERS AND ANY OTHER MISCELLANEOUS ITEMS NOT SPECIFICALLY MENTIONED BUT NECESSARY FOR A
COMPLETE INSTALLATION. APPLY LATEST STANDARDS OF SMACNA AND/OR ASHRAE WITH RESPECT TO SHEET METAL GAUGE AND GENERAL
CONSTRUCTION FOR ROUND AND RECTANGULAR DUCTS.
SPECIFICATIONS MECHANICAL
PART 2 - PRODUCTS
2.1 SPLIT SYSTEM HEAT PUMP
A.
B.
INDOOR AIR-HANDLING UNITS:
1. GENERAL: DRAW-THROUGH DIRECT-EXPANSION HORIZONTAL AND/OR VERTICAL AIR-HANDLING UNIT DESIGNED FOR COOLING ONLY
APPLICATION.
2. COILS: COPPER WITH ALUMINUM MECHANICALLY-BONDED SMOOTH-PLATE FINS.
3. FAN: CENTRIFUGAL, DOUBLE INLET, MOUNTED ON A COMMON SHAFT, STATICALLY AND DYNAMICALLY BALANCED, AND SHALL RUN ON
PERMANENTLY-LUBRICATED BEARINGS
4. CASING: GALVANIZED STEEL. FINISH WITH BAKED ENAMEL.
5. CONDENSATE DRAIN PAN INTERNAL TO UNIT.
6. FILTERS: DISPOSABLE, 1_INCH THICK.
7. MANUFACTURER: MITSUBISH, DAIKKEN, LG OR APPROVED.
OUTDOOR AIR-COOLED CONDENSING UNITS:
1. COILS: SEAMLESS COPPER TUBES WITH COPPER OR ALUMINUM PLATE FINS MECHANICALLY BONDED TO TUBES.
2. FANS: DIRECT DRIVEN, PROPELLER TYPE, ARRANGED FOR VERTICAL DISCHARGE, WITH SAFETY GUARDS. MOTORS: PERMANENTLY
LUBRICATED, ON VIBRATION ISOLATORS.
3. COMPRESSOR: SERVICEABLE HERMETIC DESIGN, WITH EXTERNAL SPRING ISOLATORS, AUTOMATICALLY REVERSIBLE OIL PUMP, LOCATED
IN A SECTION SEPARATED FROM CONDENSER FANS AND COIL. PROVIDE LOW AMBIENT CONTROLS TO 20F. PROVIDE 5_YEAR WARRANTY.
4. CONTROLS: HIGH- AND LOW-PRESSURE CUT-OUT SWITCHES, COMPRESSOR OVERLOAD DEVICES, ANTI-SHORT CYCLE CONTROLS WHICH
SHALL PREVENT COMPRESSOR FROM RESTARTING FOR APPROXIMATELY FIVE MINUTES AFTER SHUTOFF. PROVIDE A TRANSFORMER FOR
CONTROL CIRCUITS.
5. CASING: GALVANIZED STEEL, DESIGNED FOR OUTDOOR INSTALLATION. FINISHED WITH BAKED ENAMEL. PROVIDE OPENINGS FOR POWER
AND REFRIGERANT CONNECTIONS. PANEL: REMOVABLE TO PROVIDE ACCESS FOR SERVICING.
6. CONNECTIONS FOR LIQUID LINE, SUCTION LINE, AND POWER SUPPLY.
7. MANUFACTURER: MITSUBISHI, DAIKEN, LG OR APPROVED.
REVISIONS
DRAWN BY
CR
CHECKED BY
Jesse M Agosta
JOB NO.
2014-0284
DATE
DATE
SHEET NUMBER
M5.2