Carbon Monoxide Gas Detection and Control Systems DESCRIPTION Modular, wall-mounted, multi-point Carbon Monoxide (CO) in vehicle exhaust electronic sensing and control system. QAS-1000-CO APPLICATION To detect, control and alarm Carbon Monoxide (CO) in parking structures and ventilation systems. SPECIFICATIONS Power - Supply - Consumption Type of operation Output Trip/Setpoint setting - Low alarm - High alarm - Auxiliary Differential switching Operating - Manual push button - Time delay switching - Alarm stages - Auxiliary stage - Relay action - Audible alarm - Fail on indication Status LED display (operates without time delay) External sensor - Coverage - Element - Range - Accuracy - Repeatability - Output drift - Signal span - Response time - Life expectancy 120 VAC, +10%/-15%, 50 to 60 Hz 5 VA / point module On/Off; Low Alarm - Stage I High Alarm - Stage II Auxiliary - Stage III for setpoint or fail safe guard 3 DPDT Factory calibrated, user adjustable 50 PPM CO in vehicle exhaust 100 PPM CO in vehicle exhaust Fail-on condition 5 PPM, fixed Power On/Off, audio On/Off Test-activating relays, acknowledgement/reset 30 seconds to 8 hours, selectable in 30 second increments Auxiliary, 2 minutes to 8 hours, selectable in 2 minute increments Latching or non-latching, normally energized or not energized, selectable Various sequence, selectable Various sequence, selectable Power On - Green, Auxiliary - Red Fail - Red, Alarm Low - Yellow, Alarm High - Red 4,000 to 10,000 sq ft (based on ventilation and sensor location) Solid state sensor 0 PPM CO/VE to 500 PPM CO/VE ±10 PPM CO/VE ±2 PPM CO/VE < 2% of full scale/month 1-5 VDC, non-linear, as resistance change < 35 seconds to 90% of step change, at 68°F (20°C) 5 years, normal service Phone (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC INTEC Controls, Inc., P.O. Box 12506, La Jolla, CA 92039 www.inteccontrols.com Specification subject to change without notice. Printed in USA 010125 QAS-1000-CO SPECIFICATIONS (cont.) Adm. ambient temperature - Working - Storage Adm. ambient humidity Operating pressure Wire - Connection - Size Cable entry Sensor wire distance -22°F to 122°F (-30°C to 50°C) -40°F to 122°F (-40°C to 50°C) 0 to 99%, non-condensing Ambient, ±10% Terminal blocks, screw type for lead wire Min. 24 AWG (0.2 mm2), max. 14 AWG (2 mm2) Multiple holes for 1/2 conduit, covered Maximum loop resistance 35 Ohms 22 AWG (0.33 mm2), max. 1,000 ft (300 m) 16 AWG (1.3 mm2), max. 4,000 ft (1,200 m) Common for multiple sensors 18 gauge steel Gray NEMA 1 1.97 x 5.24 x 6.93 in (50 x 133 x 176 mm) Ground wire Housing - Material - Color - Protection - Dimension W x H x D (Module without panel) Listing/approvals CSA, C22.2 - No. 205 UL-recognized DPDT relays CO Panel Control Sensor Module Blank Total Panel Size Module * Qty ** Size Plate W x H x D in (mm) 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 2 2 4 4 8 8 8 8 1 -1 -3 2 1 -- 4.7 x 13.0 x 8.5 (120 x 330 x 215) 4.7 x 13.0 x 8.5 (120 x 330 x 215) 8.5 x 13.0 x 8.5 (215 x 330 x 215) 8.5 x 13.0 x 8.5 (215 x 330 x 215) 17 x 13.0 x 8.5 (430 x 330 x 215) 17 x 13.0 x 8.5 (430 x 330 x 215) 17 x 13.0 x 8.5 (430 x 330 x 215) 17 x 13.0 x 8.5 (430 x 330 x 215) Ship Weight lb (kg) 6.6 6.6 13.2 15.4 22.0 24.2 26.4 28.6 (3) (3) (6) (7) (10) (11) (12) (13) Part Number QAS-1001-CO QAS-1002-CO QAS-1003-CO QAS-1004-CO QAS-1005-CO QAS-1006-CO QAS-1007-CO QAS-1008-CO * Completely installed wall-mounted panel. ** Supplied CO sensor(s) for remote application. On request: Can be supplemented with Diesel exhaust module -- transmitter QTS-1500. Phone (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC INTEC Controls, Inc., P.O. Box 12506, La Jolla, CA 92039 www.inteccontrols.com Specification subject to change without notice. Printed in USA 010125 QAS-1000-CO WIRING DIAGRAM Control System, QAS-1000-CO Ground (–) DPDT Contact Rating 120 VAC (+) 1 x per Panel Module NC Common NO NC Maximum Operating • Voltage • Voltage • Current 250 VAC 30 VDC 5A Load Resistive Inductive 5A 5A 5A 5A 5A 3.5 A 3.5 A 3.5 A 3.5 A 2.5 A 240 VAC 208 VAC 120 VAC 24 VAC 24 VDC Auxiliary Stage III Common NO (– ) Black Sig 1-5 VDC Color (+) Power Red Max. switching Capacity 1250 VA 150 W 875 VA 120 W Sensor Aux. Voltage Output Battery Backup NC Common NO NC High Alarm Stage II Common NO NO Ventilation System Control Common NC NO Low Alarm Stage I Common NC Phone (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC INTEC Controls, Inc., P.O. Box 12506, La Jolla, CA 92039 www.inteccontrols.com Specification subject to change without notice. Printed in USA 010125