PerfectSense
Intelligent Building Occupancy Sensors
PRODUCT SELECTION GUIDE
®
BENEFITS OF PERFECTSENSE
Whether the goal is cost and time-saving installation, building energy efficiency,
certification to national energy code regulation, retrofitting, flexibility, or building
automation, NexLight’s PerfectSense Intelligent Building Occupancy Sensors
meets any application need.
EASY TO DESIGN
Either installed to work independently, or connected to work with a building
network lighting control system, PerfectSense products offer many ways to control
area lighting.
EASY TO INSTALL
All PerfectSense products come with easy to understand installation instructions
and wiring guides to quickly complete the line and low voltage connections. Intelligent out of the box presets provide accurate sensing and detection sensitivities for
most applications, making the installation process even faster.
EASY ENERGY SAVINGS
Cost-effectively save 20-80% of area lighting costs by installing occupancy sensors
throughout a facility. Perhaps the most cost effective controls strategy, occupancy
sensors begin saving energy the day they are installed.
EASY CODE COMPLIANCE
Meet and exceed today’s stringent energy codes and performance requirements
such as ASHRAE 90.1 2010, IECC 2012 and California Title 24 quickly and easily.
EASY SAFETY & SATISFACTION
PerfectSense employs the latest sensing technologies and manufacturing methods
to provide customers with a superior performing product. Backed by a 5-year
limited warranty all products are designed to provide a solution which increases
energy savings while delivering occupant satisfaction.
EASY TO RETROFIT
All PerfectSense products work with every standard commercial lighting load type
from all lighting manufacturers, enabling you to bring savings to every building
application.
VALUABLE TO:
BUILDING PROFESSIONALS, ARCHITECTS, SPECIFIERS, SYSTEM INTEGRATORS, ENGINEERS, AND INSTALLERS.
Flexibility, simplicity, code compliant, environmentally friendly.
BUILDING OWNERS, FACILITY MANAGERS AND PRIVATE CONSUMERS.
Energy savings, cost benefits, flexibility and comfort, simplicity, security.
1
PRODUCT SELECTION MATRIX
General Information and Product Design Guide
Model #
Pages
Operating
Voltage
Page 3-10
Description
Dual Tech Ultrasonic
PIR
Switch Occupancy
Occupancy Sensors
Sensors
Wall Switch
Page
11-18
Page17-30
Small o ces, small and medium conference rooms,
utility / storage rooms
Small o ces, small and medium conference rooms,
lunch/ breakrooms, utility / storage rooms
PS-PWS1277W
11
120/277
PIR Wall Switch 1-Button
PS-PWD1277W
11
120/277
PIR Wall Switch 2-Button
PS-UWS1277W
13
120/277
Ultrasonic Wall Switch 1-Button
Individual restrooms, two-stall restrooms, utility /
storage rooms
PS-UWD1277W
13
120/277
Ultrasonic Wall Switch 2-Button
Individual restrooms, two-stall restrooms, utility /
storage rooms
PS-DWS1277W
15
120/277
Dual Tech Wall Switch 1-Button
Small and executive o ces, small and medium
conference rooms, lunch break rooms
PS-DWD1277W
15
120/277
Dual Tech Wall Switch 2-Button
Small and executive o ces, small and medium
conference rooms, lunch break rooms
PIR
Page17-30
PS-CPS1000
17
24
1000 sq. ft PIR w/ Relay
Ultrasonic
Ceiling Mount Occupancy Sensors
PS-CUS800
19
24
1000 sq. ft 180° view w/ Relay
PS-CUS2000
21
24
2000 sq. ft w/ Relay
PS-DTC24
23
24
1000 sq. ft
PS-DTC24-R
25
24
1000 sq. ft w/ Relay
PS-CDS800
27
24
1000 sq. ft 180° view w/ Relay
PS-CDS2000
29
24
2000 sq. ft w/ Relay
Dual Tech
Typical Applications
Open o ces, restrooms, conference rooms,
hallways, end of aisle
Open o ces, restrooms, conference rooms, large
o ces, hallways
Classrooms, conference rooms, training rooms, large
o ces, computer rooms
Classrooms, conference rooms, training rooms, large
o ces, computer rooms
Classrooms, conference rooms, training rooms, large
o ces, computer rooms
Classrooms, conference rooms, training rooms, large
o ces, computer rooms
Page 31-36
PIR
31
24
Multi-Lens PIR w/ Relay
Ultrasonic
O ces, classrooms, hallways, warehouses, aisleways,
conference rooms
PS-WPS1500
PS-WUS1500
33
24
Ultrasonic w/ Relay
Open o ces, classrooms, restrooms, conference
rooms, large o ces
Dual Tech
Wall Mount Occupancy Sensors
Small o ces, copy rooms, break rooms, library book
stacks, aisleways, small classrooms
PS-WDS1500
35
24
Dual Tech w/ Relay
Classrooms, conference rooms, training rooms, large
o ces, computer rooms
Power Packs
Page 37-42
PS-PP1277
37
120/277
Basic Power Pack
PS-SP24
39
120/277
Auxiliary Power Pack
PS-PP7000X
41
120/277
Heavy Duty Power Pack
Low Voltage Switches
PS-LVSX
Auto On, Auto O
Allows for added loads
Auto On, Auto O , Manual On, Light Hold On, Light
Hold O
Page 43-44
43
24
Common Stand Alone Control Strategies
Low Voltage Series of Switches
Manual On / Off control in any location
Page 45
2
ENERGY CONSERVATION
ENERGY SAVINGS
Occupancy sensors deliver maximum energy savings,
exceeding the savings provided by other control solutions
(i.e. scheduling), by ensuring that lighting is only on when
people are present. NexLight, the world’s top producer of
design built and easy to use lighting control systems,
continues its mission by providing new sensors that save
energy and assist in achieving additional design goals.
100%
Actual Energy Savings By Application
90%
80%
70%
PerfectSense products provide convenient code compliant
Automatic-ON or Manual-ON control and are full of innovative features. Our sensors use Passive Infrared (PIR),
Ultrasonic, and a combination of the two, commonly
referred to as Dual-Technology. Both Automatic-ON and
Manual-ON sensors meet the Automatic-OFF requirement
of all major energy codes, including ASHRAE 90.1 (2007 and
earlier), IECC and California’s Title 24.
ASHRAE 90.1-2010 is now including the requirement for
many spaces to be Manual-ON. A space may use
Automatic-ON control, however the Automatic-ON function cannot turn on more than 50% of the space lighting.
Whichever method your space requires, PerfectSense
offers a complete selection of compliant solutions.
AUTOMATIC-ON + BI-LEVEL CONTROL
60%
50%
40%
30%
20%
20-80%
Energy Savings*
10%
0
Classroom Conference
Room
Private
Office
Restroom
Storage
(*Sources: U.S. EPA, Lighting Research Center & California Energy Commission publications)
EFFICIENCY INCENTIVES
The use of occupancy sensors can assist building owners in
earning Corporate Tax Incentives including credits, deductions, exemptions and rebates based on the equipment
installed. To qualify, a building must meet or exceed the
energy performance required. Visit www.dsireusa.org for
more information and updates for your local area.
SUSTAINABLE BUILDINGS
By designing beyond the requirements of codes, design
teams can provide even greater energy savings and work
toward sustainable building practices. LEED certification
points are awarded with correct application and use of
sensors. The result is another way of providing the community with green and energy efficient buildings.
3
ENERGY CODE COMPLIANCE
Bi-level switching has the potential to save energy by
enabling occupants to use just as much lighting as they
want, and is a requirement by EPAct, California’s Title 24
and ASHRAE 90.1 2010. Bi-level Auto-on control is when
one zone is turned on automatically (by the sensor) and the
other zone must be turned on manually (local switch).
This method of control has been shown to use 52% less
energy* than Automatic-on only. Additionally, many occupants are comfortable working in lower lighting levels. The
result are dramatic energy savings and enhancing occupant comfort. (* Based on California Lighting Technology Center research 2009.)
AUTO-ON TO 50% EXAMPLE
SENSOR TECHNOLOGIES
PerfectSense gives engineers and facility managers more control
options than ever before, offering sensors that are the best fit for
any application. Sensors featuring Passive Infrared, Ultrasonic or
Dual Technology are ideally suited for different applications. Let’s
take a closer look at each type.
PASSIVE INFRARED
Passive Infrared (PIR) technology detects occupancy in the space
by sensing the difference between temperatures of a human body
in motion and the background space. Requiring a line of sight for
detection, PIR sensors feature accurate area coverage cut-offs.
ULTRASONIC
Ultrasonic (US) technology operates by transmitting an ultrasonic
sound wave into the space and measuring the speed at which they
return back to the sensor. Occupant movements change the
frequency of the waves. This means ultrasonic sensors can detect
movement around partitions or indirect line of sight.
DUAL TECHNOLOGY
Dual Technology operates by combining PIR and ultrasonic detection into a single device. This technology increases the accuracy of
detection while decreasing the potential of false ON or false OFF
triggers.
PIR BEST APPLICATIONS:
+ Small offices
+ Warehouses
+ High ceiling locations
+ Library book stacks/aisles
+ Lobby / common areas
+ Computer rooms
ULTRASONIC BEST
APPLICATIONS:
+ Restrooms
+ Open office spaces
+ Enclosed hallways
+ Stairways
DUAL TECHNOLOGY
BEST APPLICATIONS:
+ Classrooms
+ Large conference rooms
+ Large offices
+ Lecture halls
+ Cafeterias
4
APPLICATION EXAMPLES
PRIVATE OFFICES
In private offices, use a PIR or dual tech sensor depending on
room layout and field of view. Take advantage of the integrated
light level feature to keep lights off when sufficient daylight is
present.
REST ROOMS
Lighting in restrooms is best controlled with ultrasonic sensors to
eliminate hundreds or even thousands of hours of unneeded
on-time during a year. A ceiling-mounted ultrasonic senses
motion around restroom stalls for greater coverage area.
OPEN OFFICES
For the open or partitioned office spaces, either the dual tech or
ultrasonic type may be appropriate. Wall mounted or on the
ceiling, expand coverage of large spaces by linking multiple
sensors together to control lighting in a coordinated way. Use
these sensors to cover the area in zones with 10-20% overlap as
illustrated above.
5
CONFERENCE ROOMS
Large conference rooms require detection that will account for
occupants that may be still for long periods of time. Dual technology sensors will be able to detect minor motion to keep lights on
as long as the space is occupied.
CLOSETS / STORAGE
Copy rooms, IT rooms, and janitor’s closets are ideal for occupancy based controls. With a wall or switch mounted PIR sensor,
lights can be shut off just minutes after the occupant leaves
saving hours of wasted lighting energy each day.
CLASSROOMS
Classrooms large and small require the ability to detect minor
motion. Ceiling mounted dual technology sensor models are
preferred to get complete room detection. In larger rooms a
second sensor and power pack could be added for multizone
control.
DESIGNING WITH OCCUPANCY SENSORS
“Are Occupancy Sensors The Correct Control Strategy For Your Space?”
Understanding daily space usage patterns are essential to
properly apply occupancy sensing in a commercial building
space. If you are able to answer “YES” to some of the following
questions, adding occupancy sensors are a viable control
option.
+ Are there periods of time when the space is unoccupied?
+ Is energy wasted due to lights being left on when no one is
in the space?
Evaluate Space
Needs
Install &
Con gure
Match with Best
Technology
+ Are lights left on after business hours?
+ Is the space used only intermittently?
Layout & Specify
+ Could some or all area lights be turned off during the day?
PerfectSense
®
4 STEP DESIGN PROCESS
1. EVALUATE SPACE NEEDS
The following space characteristics are of particular
importance because of the influence they have when
making a sensor selection:
+ Room / Space dimensions and shape
+ Location of main occupant activity
+ Location of walls, doors, windows and drapes
+ Location of desks / workspaces and orientation with
regard to walls and partitions
+ Ceiling heights, partition heights and locations
+ Location of file cabinets, large furniture, large
equipment or shelves
+ Large objects that could block or alter a sensor
coverage area
+ Available daylight for added light level sensing
+ Make note of high levels of air flow or vibrations
noting the location of HVAC ducts and fans
6
2. MATCH SENSING TECHNOLOGY
Tip: Choose the sensing technology that best meets space needs and characteristics
Occupancy Sensor Technology Selection Matrix
Dual Tech
Ultrasonic
PIR
Technology /
Product Type
Coverage Type
Acceptable Application
Qualities
Unacceptable Application
Qualities
Very low motion levels by
occupants or obstacles
blocking sensor view
Very low motion levels by
occupants or obstacles
blocking sensor view
Wall Switches
Line of sight with
clear cuto
smaller enclosed spaces
Ceiling / Wall
Sensors
Line of sight with
clear cuto
spaces where a sensor has
a view of activity
Wall Switches
No clear cuto
smaller enclosed spaces
High level of air ow
Ceiling / Wall
Sensors
Volumetric in space
with no clear cuto
open spaces, and spaces
with obstacles
High ceilings and high levels
of vibration or air ow
Wall Switches
Complete Coverage
spaces with low or variable
High level of air ow
motion levels by occupants
Ceiling / Wall
Sensors
Complete Coverage
spaces with low or variable
High level of air ow
motion levels by occupants
Common Locations
TIP: Use this reference list to identify the commonly used products for your applications
Location
Passive
Infrared (PIR)
Ultrasonic
Classroom
X
Hallway
Private O ce
X
C
C
X
X
C,WS
Conference Room
X
X
C,WS
Open O ces
X
X
C,WM
X
X
C,WM
X
C,WS
X
C,WM,WS
Lecture Hall
Library
X
X
Rest Room
7
Dual
Sensor Type
Technology
C
Lobby
X
Storage
X
Warehouse
X
Closet
X
X
WS
Cafeteria
X
X
C
X
C= Ceiling Mount
WM= Wall Mount
C,WM,WS
WS
WS= Wall Switch
DESIGNING WITH OCCUPANCY SENSORS
3. LAYOUT & SPECIFICATION
COVERAGE PATTERNS
CHOOSE POWER PACKS
Once the technology is chosen, the next step is to select
the correct coverage size and shape. A typical design
guideline will call for a minimum of 90% coverage area of
the square footage in a room. Each product cut sheet
includes specific coverage area specifications.
Power packs are a necessary component providing
three core purposes to most occupancy sensor projects.
Power packs provide power to low voltage sensors and
other control devices, respond to signals from those
devices and switch their internal relays to control the
connected loads.
It’s important to know the typical use of space. Will occupants be engaged in major motions (walking, using a
forklift) or minor motion (reading, typing). Coverage
changes depending on motion type.
Power packs can also provide advanced features such as
switch inputs, inputs for scheduling, and dimming
control. Before selecting a power pack, consider the
following factors.
NEMA TESTING
Voltage: Pay attention to the input ratings of each
power pack model.
PerfectSense understands the importance in producing
the highest quality products. When it comes to occupancy
sensors, that means producing sensors with consistent
detection while reducing False Triggers. All PerfectSense
products are designed to meet and exceed the quality and
consistency standards set forth in the National Electrical
Manufacturers Association guide publication. The NEMA
guide establishes two testing parameters as major and
minor motion detection. It defines minor motion as the
movement of a person sitting at a desk reaching for a
telephone, turning the pages of a book, opening a file
folder, or picking up a coffee cup. Major motion is defined
as the movement of a person walking in or through a
space.
Low voltage output needs: Typically listed in (mA) be
sure the power pack provides enough current to power
all of the connected devices for that zone.
Relay ratings: Power Packs have specific ratings for
different load types (i.e., incandescent, fluorescent,
motor). Make sure the relay is rated for the type of load
to be controlled and the load being switched does not
exceed the load rating of the power pack.
To protect against the potentially damaging effects of
high inrush current common in newer electronic
ballasts, select power packs with zero crossing circuitry
technology.
Common Features
TIP: Use this reference list to identify the desired features for your applications
Feature
Isolated Relay
Light Level Sensing
Terminal Wiring
Bene t
Enables interfacing with facility HVAC, BMS or monitoring systems
Increased energy savings in areas with signi cant natural light
Simpli ed installation
Manual-ON/Auto-ON
Options to meet code and maximize energy savings in di erent applications
Dual Relays
Enables bi-level switching for increased energy savings and code compliance
Zero Crossing
Reduces stress on sensor relays and increases sensor life
LED Operation
LED indicators will ash when motion is detected with each technology
Low Voltage
Flexibility for installation location and wiring
Line Voltage
No need for power pack device
Adaptive Technology
Monitors activity patterns over time to auto adjust o time for maximized energy savings
Walk-Through Mode
Additional energy savings by turning lights o after brief occupancy
Alerts
Multi-way Capability
Lamp Saver
Test Mode
Audible warning of impending shuto
Facilitates control in spaces with multiple entrances
For bi-level lighting: alternates the load that turns on each time the lights turn on.
Temporary setting used to test coverage area typically expires after 15 minutes
Note: not all sensors contain all features, refer to specification for complete details
8
DESIGNING WITH OCCUPANCY SENSORS
4. INSTALL & CONFIGURE
INSTALL THE SENSOR
During installation contractors should position the sensor
so it has the best view of the entire coverage area, while
minimizing the possibility of false ON and OFF triggers.
Wire sensors according to instructions. This will eliminate
any functional problems or sensor damage. If necessary,
adjust sensor settings such as the sensitivity, time delay or
daylight sensing to match the activity levels of the space
being controlled.
TIP: Wire according
to instructions for
proper power pack
and sensor function
Be sure to increase the off time delay setting for spaces
where minor motion and limited activity will be taking
place to further reduce the risk of false offs. For increased
energy efficiency shorten off time delay settings especially
for areas of high traffic. For restrooms, stairwells or areas
with limited or no natural lighting use caution and set
longer off time delays to ensure occupant safety and security.
TIP: Double check
specified sensor
location prior
to installation
WIRING POWERPACKS
Intelligent power packs provide inputs so that multiple
control devices can be connected. This enables customization of control scenarios for different applications and end
user preferences. Use intelligent power packs when
multi-device, manual switching, and dimming applications are desired.
MOUNTING SENSORS
PerfectSense products fall into three categories of
mounting: Ceiling, Wall, and Wall Switch types. Only
wall mount types may be mounted on both the wall
or the ceiling. This is important for applications where
one of the surfaces may be unsuitable for sensor
installation.
Most occupancy sensors include an integrated daylight
sensor to be used in building spaces that receive daylight.
This function is designed to ensure the occupancy sensors
will keep lights off in occupied spaces, when the natural
daylight coming into the space exceeds the set threshold.
If a space has inadequate natural daylight the occupancy
sensor will turn lighting on.
MOUNTING POWERPACKS
PROGRAMMING AND TESTING
Power packs are often mounted to the outside of a
junction box, placing them in the plenum space, so
make sure the power pack is plenum rated. Smaller
power packs can be installed inside a standard junction box.
9
PHOTOCELL CONTROLS
Make post-installation adjustment as needed. This is not
uncommon and is often due to last minute changes in
placement of furniture or fixtures. A walk test of the detection area is a common method of ensuring the sensor is
located and configured properly for the space.
STAND ALONE VS. NETWORKED SYSTEMS
INTEGRATING SENSORS WITH CONTROLS
Occupancy sensors that operate independently in a space,
are referred to as “stand alone” sensors providing no information of occupancy status to other building systems. To
increase control and energy savings, PerfectSense low
voltage occupancy sensors include isolated Form C relays
to seamlessly integrate with Building Management
Systems (BMS), HVAC (VAV controllers) or NexLight 2-Wire
Lighting Controls Systems. These relays providing real
time occupancy status “intelligence” to other systems,
adding signifcantly to a building wide control strategy and
potential savings. PerfectSense has the industries only
sensor with multiple relay outputs for greater connectivity
to building controls.
NexLight 2-Wire Networked
Lighting Control System
MULTILAYERED CONTROL STRATEGY
For the next level of efficiency, consider combining occupancy sensors with other controls such as lighting control
panels or daylight harvesting controls. A multilayered
control strategy can assist in meeting energy codes and
green sustainability guidelines as well as provide maximized energy savings.
Your Source for Design Built Systems
PANELS | SWITCHES | SENSORS
The images below illustrate an example of how a low
voltage sensor could be networked to a building BMS or
2-Wire lighting control system.
PerfectSense
®
TM
Extreme Reliability
Lighting Control Systems
Room Control with
Manual-On + BMS Status
Networked Room
Control with Manual-On
To CPU
or Panel
1-Button
Low Voltage Switch
2-Wire Switch
A
A
F
B
E
A
to BMS or HVAC
C
A
Ceiling Sensor
Occupancy / Vacancy
Sensor
A
Power Pack
A
2-Wire Panel
To CPU
or Panel
WIRING KEY
A
E
F
Line Voltage Class 1
Low Voltage Class 2
(16awg 3-wire)
Low Voltage Class 2
(16awg 2-wire)
WIRING KEY
A
Line Voltage Class 1
B
Low Voltage Class 2
(NexLight 2-wire Bus)
C
Low Voltage Class 2
(16awg 4-wire*)
* for 50%on/all off commands add one additional wire
See page 45 for Stand-Alone Control Scenarios.
10
PerfectSense
®
Intelligent Building Occupancy Sensors
PS-PWS1277 | PS-PWD1277
Commercial Grade Occupancy Sensor
Passive Infrared (PIR) | Wall Switch | Line Voltage
Overview
•
•
•
•
•
•
•
•
•
•
The Commercial Grade PIR Wall Switch Occupancy Sensor provides automatic control
of loads by detecting motion and ambient light within the detection area.
Sensor features include:
One or Two separate relay circuits for independently switching loads
(typically lighting loads) ON or OFF.
180° motion detection using passive infrared (PIR) technology.
Superior lens design to provide high resolution for detecting major and
minor motion.
Advanced logic enhances energy savings and user convenience.
Convenient pushbuttons for manual control.
Automatic adaptive technology adjusts the time delay for maximum energy savings.
Automatic 15 second test mode.
Service Switch (OFF/Auto/ON).
Audible alert 10 seconds before sensor turns loads OFF.
Advanced Lamp Saver mode extends the lamp life in 50/50 bi-level
lighting applications (2 Circuit model only).
PS-PWS1277W
PS-PWD1277W
Specifications
Coverage Area: 1000 sq. ft.
Input:
120–277Vac +/-10% 50/60Hz
Output:
120Vac
- 1000W max. tungsten incandescent load
- 1000VA max. ballast load
- 1/4 hp max. motor load
- No minimum load required
277Vac
- 1800 VA max. ballast load
- No minimum load required
Temperature:
32 to 122°F (0 to 50°C)
Humidity:
0% to 90% RH non-condensing
Time Delay:
Initial Minimum: 5, 10, 15, or 30 minutes
Test mode: 15 seconds
Walk through mode: 2 minutes if no activity is
detected after 30 seconds
11
Phone: 218.828.3700
Compliances:
Light level Adjustment:
Detection:
Audible alert:
Service Switch:
Manual operation:
Lens:
Relay Switching:
Dimensions:
www.nexlight.com
UL and cUL Listed
Title 24 Compliant
FCC part 15 (Class B)
0.5 to 250 footcandles (FC)
180° passive infrared (PIR)
Selectable
OFF/Auto/ON
Pushbutton ON/OFF
Impact resistant
0° +/- 500uS
(H x W x D): 4.1 x 1.7 x 1.9in.
(104 x 44 x 49mm)
Fax: 218.824.1568
Detection Range and Coverage Area
Both models provide major motion detection up to 1000 sq. ft., and minor motion detection up to 300 sq. ft.
NOTE: Coverage area may vary depending upon the shape,
size, and absorbent properties of the room.
Wiring Diagram- 1 Circuit
Order Information- Wall Switch Series
PS - P
W
Technology
D= Dual Tech
U= Ultrasonic
P= Passive Infrared (PIR)
S 1277 X
Power
1277= Line Voltage
Color
Mounting
W= Wall Switch
Circuits
S= Single (1)
D= Dual (2)
W= White
I= Ivory
L= Light Almond
G= Gray
B= Black
Wiring Diagrams- 2 Circuits
Color Reference:
BK = Black
GN = Green
R = Red
BL = Blue
BR = Brown
Phone: 218.828.3700
www.nexlight.com
Fax: 218.824.1568
12
PerfectSense
®
Intelligent Building Occupancy Sensors
PS-UWS1277 | PS-UWD1277
Commercial Grade Occupancy Sensor
Ultrasonic Technology | Wall Switch | Line Voltage
Overview
•
•
•
•
•
•
•
•
•
The Ultrasonic Wall Switch Occupancy Sensor provides automatic control of
lighting by detecting motion and ambient light within the detection area. Sensor
features include:
One or Two separate relay circuits for independently switching loads
(typically lighting loads) ON or OFF
180° motion detection using ultrasonic (US) technology.
Superior ultrasonic transducers provide high resolution for detecting major and
minor motion.
Advanced logic enhances energy savings and user convenience.
Convenient pushbutton for manual control.
Automatic adaptive technology adjusts the time delay for maximum energy
savings.
Automatic 15 second test mode.
Service Switch (OFF/Auto/ON). Audible alert 10 seconds before sensor turns
loads OFF.
Advanced Lamp Saver mode extends the lamp life in 50/50 bi-level lighting
applications (2 Circuit model only).
PS-UWS1277W
PS-UWD1277W
Specifications
Coverage Area: 500 sq. ft.
Input:
120–277Vac +/-10% 50/60Hz
Output:
120Vac
- 1000W max. tungsten incandescent load
- 1000VA max. ballast load
- 1/4 hp max. motor load
- No minimum load required
277Vac
- 1800 VA max. ballast load
- No minimum load required
Temperature:
32 to 122°F (0 to 50°C)
Humidity:
0% to 90% RH non-condensing
Time Delay:
Initial Minimum: 5, 10, 15, or 30 minutes
Test mode: 15 seconds
Walk through mode: 2 minutes if no activity is
detected after 30 seconds
13
Phone: 218.828.3700
Compliances:
Light level Adjustment:
Detection:
Audible alert:
Service Switch:
Manual operation:
Lens:
Ultrasonic Transducer:
Relay Switching:
Dimensions:
www.nexlight.com
UL and cUL Listed
Title 24 Compliant
FCC part 15 (Class B)
0.5 to 250 footcandles (FC)
180° ultrasonic (US)
Selectable
OFF/Auto/ON
Pushbutton ON/OFF
Impact resistant
40kHz
0° +/- 500uS
(H x W x D): 4.1 x 1.7 x 1.9in.
(104 x 44 x 49mm)
Fax: 218.824.1568
Detection Range and Coverage Area
Both models provide major motion detection up to 500 sq. ft., and minor motion detection up to 300 sq. ft.
NOTE: Coverage area may vary depending upon the shape,
size, and absorbent properties of the room.
Wiring Diagram- 1 Circuit
Order Information- Wall Switch Series
PS - U W
S 1277 X
Technology
Power
D= Dual Tech
U= Ultrasonic
P= Passive Infrared (PIR)
1277= Line Voltage
Color
Mounting
W= White
I= Ivory
L= Light Almond
G= Gray
B= Black
W= Wall Switch
Circuits
S= Single (1)
D= Dual (2)
Wiring Diagrams- 2 Circuits
Color Reference:
BK = Black
GN = Green
R = Red
BL = Blue
BR = Brown
Phone: 218.828.3700
www.nexlight.com
Fax: 218.824.1568
14
PerfectSense
®
Intelligent Building Occupancy Sensors
PS-DWS1277 | PS-DWD1277
Commercial Grade Occupancy Sensor
Dual Technology | Wall Switch | Line Voltage
Overview
•
•
•
•
•
•
•
•
•
PS-DWS1277W
The Dual Technology Wall Switch Occupancy Sensor provides automatic control
of lighting by detecting motion and ambient light within the detection area.
Sensor features include:
One or Two separate relay circuits for independently switching loads
(typically lighting loads) ON or OFF
180° motion detection using passive infrared (PIR) and ultrasonic technology.
Superior lens design and ultrasonic transducers to provide high resolution for
detecting major and minor motion.
Advanced logic enhances energy savings and user convenience.
Convenient pushbutton for manual control.
Automatic adaptive technology adjusts the time delay for maximum energy
savings.
Automatic 15 second test mode.
Service Switch (OFF/Auto/ON). Audible alert 10 seconds before sensor turns
loads OFF.
Advanced Lamp Saver mode extends the lamp life in 50/50 bi-level lighting
applications (2 Circuit model only).
PS-DWD1277W
Specifications
Coverage Area: 1000 sq. ft.
Input:
120–277Vac +/-10% 50/60Hz
Output:
120Vac
- 1000W max. tungsten incandescent load
- 1000VA max. ballast load
- 1/4 hp max. motor load
- No minimum load required
277Vac
- 1800 VA max. ballast load
- No minimum load required
Temperature:
32 to 122°F (0 to 50°C)
Humidity:
0% to 90% RH non-condensing
Time Delay:
Initial Minimum: 5, 10, 15, or 30 minutes
Test mode: 15 seconds
Walk through mode: 2 minutes if no activity is
detected after 30 seconds
15
Phone: 218.828.3700
Compliances:
Light level Adjustment:
Detection:
Audible alert:
Service Switch:
Manual operation:
Lens:
Ultrasonic Transducer:
Relay Switching:
Dimensions:
www.nexlight.com
UL and cUL Listed
Title 24 Compliant
FCC part 15 (Class B)
0.5 to 250 footcandles (FC)
180° passive infrared (PIR)
Selectable
OFF/Auto/ON
Pushbutton ON/OFF
Impact resistant
40kHz
0° +/- 500uS
(H x W x D): 4.1 x 1.7 x 1.9in.
(104 x 44 x 49mm)
Fax: 218.824.1568
Detection Range and Coverage Area
Both models provide major motion detection up to 1000 sq. ft., and minor motion detection up to 300 sq. ft.
NOTE: Coverage area may vary depending upon the shape,
size, and absorbent properties of the room.
Wiring Diagram- 1 Circuit
Order Information- Wall Switch Series
PS - D W
Technology
D= Dual Tech
U= Ultrasonic
P= Passive Infrared (PIR)
S 1277 X
Power
1277= Line Voltage
Color
Mounting
W= Wall Switch
Circuits
S= Single (1)
D= Dual (2)
W= White
I= Ivory
L= Light Almond
G= Gray
B= Black
Wiring Diagrams- 2 Circuits
Color Reference:
BK = Black
GN = Green
R = Red
BL = Blue
BR = Brown
Phone: 218.828.3700
www.nexlight.com
Fax: 218.824.1568
16
PerfectSense
®
Intelligent Building Occupancy Sensors
PS-CPS1000
Standard Range 360˚ Sensor
PIR Detection | Ceiling Mount | Low Voltage
Overview
The Ceiling-mounted Passive Infrared (PIR) Occupancy
Sensor accurately detects occupancy and automatically
switches lighting on and off as needed.
This low profile sensor is ceiling mounted for superior
motion detection. With a 360 degree field of view and up
to 1000 square feet of coverage area, the Ceiling-mounted
PIR Occupancy Sensor is ideal for offices, conference rooms
and hallways.
Ceiling-mount sensors also incorporate an integral light
level sensor to prevent lighting from switching On when
sufficient ambient light is present, such as is commonly
found in windowed areas.
Installation and configuration is simple. The sensor readily
mounts to drop ceilings and features front located adjustments for setting sensitivity and time delay. Features an
isolated relay for use with building automation, security
and HVAC systems.
Features
Phone: 218.828.3700
Electrical:
Power Requirements: 24VDC, from powerpack
Current Consumption: 21mA
Isolated Relay: Form C Contacts for Class 2 signaling
1A @24VDC Resistive
Output: 24VDC active high logic control signal
with short circuit protection
Controls:
• 1000 sq. ft. coverage area
• 360 degree field of view
• Light level sensing (from 0.5 to 250 foot-candles)
• Adjustable time delay (pre-set time delays from 15
seconds to 30 minutes)
• Automatic adaptive technology adjusts the time delay for
maximum energy savings.
• Adjustable sensitivity (from 60 to 100%)
• Isolated relay
• Red LED motion indicator blinks to indicate motion
detection
• Adjustment compartment cover equipped with retention
feature
• Manual bypass
• UL®/cUL Listed
• Title 24 Certified
• Meets ASHRAE 90.1 requirements
• Five-year warranty
17
Specifications
Passive Infrared Sensitivity: 600-1000 sq. ft
Adjustable Sensitivity of (60-100% of Max. Coverage)
Time Delay: 15 sec. - 30 min.
Light Sensor: 0.5-250 foot candles
Load Rating: Controls Class 2 Power Pack
Housing Material: High-Impact ABS
Color: White
Environment Temperature: 32ºF to 122ºF
Humidity: 0-90% Non Condensing
Installation: See Install Instructions
Dimensions: Diameter 4.5 in
Height 1.75 in
www.nexlight.com
Fax: 218.824.1568
Ordering Information
COVERAGE*
COLOR
NA
360˚ 1000sf
White
40kHz
360˚ 1000sf
White
40kHz
360˚ 1000sf
White
PS-CUS800
40kHz
180˚ 1000sf
White
PS-CDS800
40kHz
180˚ 1000sf
White
PS-CUS2000
40kHz
360˚ 2000sf
White
PS-CDS2000
40kHz
360˚ 2000sf
White
DESCRIPTION
CATALOG #
PIR Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay
PS-CPS1000
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor
PS-DTC24
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay
PS-DTC24-R
Ultrasonic Ceiling Mounted Low Voltage Occupancy Sensor
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay
Ultrasonic Ceiling Mounted Low Voltage Occupancy Sensor w/Relay
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay
OPERATING
FREQUENCY
Power Pack (Required for operation)
*all coverage areas are based on a standard 9 ft mounting height
Detection Range and Coverage Area
PIR Sensor Field of View
Hot
COMMON
CONTROL
RED
BLACK
BLUE
277V
120V
+24v
SENSOR
Neutral
GREEN (N.C.)
YELLOW
(COMMON)
ORANGE (N.O)
Wiring Diagrams
PS-PP1277
Power
Pack
BLACK
WHITE
RED
LOAD
* Control power must be provided by PerfectSense Power Pack PS-PP1277 or an approved equivalent.
Phone: 218.828.3700
www.nexlight.com
Fax: 218.824.1568
18
PerfectSense
®
Intelligent Building Occupancy Sensors
PS-CUS800
Standard Range 180˚ Sensor
Ultrasonic Technology | Ceiling Mount | Low Voltage
Overview
The 180 Degree Ceiling-Mounted Occupancy Sensors
are ideal for use in business and office settings to
accurately detect occupancy and automatically control
lighting.
The ceiling-mount design of these low-profile sensors
allows the greatest possible motion sensitivity. An
adjustment panel is conveniently located on the front of
the sensor, providing ready access to setting controls
after the sensor is installed.
These occupancy sensors are available in the ultrasonic
and dual technology models. The dual technology
model employs passive infrared (PIR) and ultrasonic
technology.
Installation and configuration is simple. The sensor
readily mounts to drop ceilings and features front
located adjustments for setting sensitivity and time
delay. Features an isolated relay for use with building
automation, security and HVAC systems.
Power Requirements: 24VDC, from powerpack
Current Consumption: 30mA
Isolated Relay: Form C Contacts for Class 2 signaling
1A @24VDC Resistive
Output: 24VDC active high logic control signal
with short circuit protection
Passive Infrared Sensitivity: 600-1000 sq. ft
• 1000 sq. ft. coverage area
• 180° degree field of view
• Light level sensing (from 0.5 to 250 foot-candles)
• Adjustable time delay (pre-set time delays from 15
seconds to 30 minutes)
• Automatic adaptive technology adjusts the time delay for
maximum energy savings.
• Adjustable sensitivity (from 60 to 100%)
• Isolated relay
•LED motion indicator
• Adjustment compartment cover equipped with retention
feature
• Manual bypass
• UL®/cUL Listed
• Title 24 Certified
• Meets ASHRAE 90.1 requirements
• Five-year warranty
Phone: 218.828.3700
Electrical:
Controls:
Features
19
Specifications
Adjustable Sensitivity of (60-100% of Max. Coverage)
Time Delay: 15 sec. - 30 min.
Light Sensor: 0.5-250 foot candles
Load Rating: Controls Class 2 Power Pack
Housing Material: High-Impact ABS
Color: White
Environment Temperature: 32ºF to 122ºF
Humidity: 0-90% Non Condensing
Installation: See Install Instructions
Dimensions: Diameter 4.5 in
Height 1.75 in
www.nexlight.com
Fax: 218.824.1568
Ordering Information
COVERAGE*
COLOR
180˚ 1000sf
White
40kHz
180˚ 1000sf
White
NA
360˚ 1000sf
White
PS-DTC24
40kHz
360˚ 1000sf
White
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay
PS-DTC24-R
40kHz
360˚ 1000sf
White
Ultrasonic Ceiling Mounted Low Voltage Occupancy Sensor w/Relay
PS-CUS2000
40kHz
360˚ 2000sf
White
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay
PS-CDS2000
40kHz
360˚ 2000sf
White
DESCRIPTION
CATALOG #
OPERATING
FREQUENCY
Ultrasonic Ceiling Mounted Low Voltage Occupancy Sensor
PS-CUS800
40kHz
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay
PS-CDS800
PIR Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay
PS-CPS1000
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor
Power Pack (Required for operation)
*all coverage areas are based on a standard 9 ft mounting height
Detection Range and Coverage Area
Ultrasonic Sensor Field of View
Hot
+24v
SENSOR
COMMON
CONTROL
RED
BLACK
BLUE
Neutral
277V
120V
GREEN (N.C.)
YELLOW
(COMMON)
ORANGE (N.O)
Wiring Diagrams
PS-PP1277
Power
Pack
BLACK
WHITE
RED
LOAD
* Control power must be provided by PerfectSense Power Pack PS-PP1277 or an approved equivalent.
Phone: 218.828.3700
www.nexlight.com
Fax: 218.824.1568
20
PerfectSense
®
Intelligent Building Occupancy Sensors
PS-CUS2000
Standard Range 360˚ Sensor
Ultrasonic Detection | Ceiling Mount | Low Voltage
Overview
The Ceiling-mounted Ultrasonic Occupancy Sensor
accurately detects occupancy and automatically switches
lighting on and off as needed.
This low profile sensor is ceiling mounted for superior motion
detection. With a 360 degree field of view and up to 2000
square feet of coverage area, the Ceiling-mounted Ultrasonic
Occupancy Sensor is ideal for storage rooms, bathrooms,
conference rooms, classrooms, hallways, and open office
areas.
Ceiling-mount sensors also incorporate an integral light level
sensor to prevent lighting from switching On when sufficient
ambient light is present, such as is commonly found in
windowed areas.
Installation and configuration is simple. The sensor readily
mounts to drop ceilings and features front located adjustments for setting sensitivity and time delay. Features an
isolated relay for use with building automation, security and
HVAC systems.
Power Requirements: 24VDC, from powerpack
Current Consumption: 34mA Nominal (125mA max)
Isolated Relay: Form C Contacts for Class 2 signaling
1A @24VDC Resistive
Output: 24VDC active high logic control signal
with short circuit protection
Adjustable Sensitivity of (60-100% of Max. Coverage)
• 2000 sq. ft. coverage area
• 360 degree field of view
• Light level sensing (from 0.5 to 250 foot-candles)
• Adjustable time delay (pre-set time delays from 15 seconds
to 30 minutes)
• Automatic adaptive technology adjusts the time delay for
maximum energy savings.
• Adjustable sensitivity (from 60 to 100%)
• Isolated relay
• Red LED motion indicator blinks to indicate motion detection
• Adjustment compartment cover equipped with retention
feature
• Manual bypass
• UL®/cUL Listed
• Title 24 Certified
• Meets ASHRAE 90.1 requirements
• Five-year warranty
Phone: 218.828.3700
Electrical:
Controls:
Features
21
Specifications
Time Delay: 15 sec. - 30 min.
Light Sensor: 0.5-250 foot candles
Load Rating: Controls Class 2 Power Pack
Housing Material: High-Impact ABS
Color: White
Environment Temperature: 32ºF to 122ºF
Humidity: 0-90% Non Condensing
Installation: See Install Instructions
Dimensions: Diameter 4.5 in
Height 1.25 in
www.nexlight.com
Fax: 218.824.1568
Ordering Information
COVERAGE*
COLOR
40kHz
360˚ 2000sf
White
PS-CDS2000
40kHz
360˚ 2000sf
White
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor
PS-DTC24
40kHz
360˚ 1000sf
White
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay
PS-DTC24-R
40kHz
360˚ 1000sf
White
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay
PS-CDS800
40kHz
180˚ 1000sf
White
Ultrasonic Ceiling Mounted Low Voltage Occupancy Sensor w/Relay
PS-CUS800
40kHz
180˚ 1000sf
White
PIR Ceiling Mounted Low Voltage Occupancy Sensor w/Relay
PS-CPS1000
NA
360˚ 1000sf
White
DESCRIPTION
CATALOG #
Ultrasonic Ceiling Mounted Low Voltage Occupancy Sensor w/Relay
PS-CUS2000
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay
OPERATING
FREQUENCY
Power Pack (Required for operation)
*all coverage areas are based on a standard 9 ft mounting height
Detection Range and Coverage Area
Field of View (Top)
Hot
+24v
SENSOR
COMMON
CONTROL
RED
BLACK
BLUE
Neutral
277V
120V
Wiring Diagrams
PS-PP1277
Power
Pack
BLACK
WHITE
RED
LOAD
* Control power must be provided by PerfectSense Power Pack PS-PP1277 or an approved equivalent.
Phone: 218.828.3700
www.nexlight.com
Fax: 218.824.1568
22
PerfectSense
®
Intelligent Building Occupancy Sensors
PS-DTC24
Standard Range 360˚ Sensor
Dual Technology | Ceiling Mount | Low Voltage
Overview:
The PS-DTC24 increases area lighting energy efficiency quickly
and easily by combining industry leading Passive Infrared (PIR)
technology with Ultrasonic for superior detection. Factory
preset to deliver significant savings out of the box, this sensor
has additional options to further increase energy savings if
desired. The PerfectSense PS-DTC24 is a low-voltage sensor
that works with PerfectSense class 2 power supply (PSPP1277),
to automatically control lighting. The sensor turns the lights
on and keeps them on when occupancy is detected and will
turn the lights off after the delayed-off time has expired.
Operation:
The sensor first sees motion using the PIR detection and then
activates Ultrasonic to confirm and indicate continued occupancy. The standard factory programming is set to meet the
standards of most common area applications with a 10 minute
off delay time.
Additional Operational Features:
Walk-Through Mode: useful when a room is momentarily
occupied, like a storage area. When a person enters the room,
the lights turn on. If the person leaves the room before the 2.5
minute walk-through timer expires the sensor will turn the
lights off. If the person stays in the room longer than 2.5
minutes the sensor will proceed to standard operation.
Single-Tech Mode: Only one technology is active in this mode.
Dip switch selectable, a user may determine that the space
may only require one technology to properly detect the area.
One sensor model can now act as a PIR only, Ultrasonic only or
Dual-tech sensor.
Daylight Sensor: The integrated daylight sensor allows for
ambient light override functionality. If this setting is enabled,
the controlled lighting load will only turn on if the ambient
light present is less than the preset level.
Adaptive Learning: Patented adaptive learning technology will
automatically increase or decrease the off delay time in
response to the occupancy and environmental conditions of
the area over a period of time. For example, if there is
frequent motion detection, the sensor will automatically
shorten the off delay time to better meet the conditions of the
room. This technology also detects false off conditions. If this
happens, the off delay time duration will immediately be
lengthened to avoid future false off conditions.
23
Phone: 218.828.3700
Specifications
Features
360˚ Coverage Pattern
TM
100% Digital Multiview PIR
Dual technology uses PIR + U/S
Superior RF immunity
Adjustable Time Delay (30 sec-30 min)
Single Technology Mode
TM
SmartSense Adapt Mode
Walk Through Mode
Daylight Override Mode
Simple Test Mode
Mounts in drop ceilings and solid ceilings
LED’s provide indication of occupancy sensing
Electrical:
Power Requirements: 24VDC, from powerpack
Current Consumption: 30mA
Output: 24VDC active high logic control signal
with short circuit protection
Wiring Diagram: See Fig. 2
Controls:
Passive Infrared Sensitivity: 0-100% (Factory Set 50%)
Ultrasonic Sensitivity: 0-100% (Factory Set 50%)
Light Sensor: 20-320 LUX (Factory Disables)
Detection Range: See Fig. 1
Load Rating: Controls Class 2 Power Pack
Housing Material: High-Impact ABS
Color: White
Environment Temperature: 14ºF to 122ºF
Humidity: 0-95% Non Condensing
Installation: See Install Instructions
Dimensions: Diameter 4.33 in
Height 2.2 in
Supported with a limited 5-year warranty
Title 24 Compliant
Meets ASHRAE 90.1 requirements
www.nexlight.com
Fax: 218.824.1568
Ordering Information
DESCRIPTION
CATALOG #
OPERATING
FREQUENCY
COVERAGE*
COLOR
White
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor
PS-DTC24
40kHz
360˚ 1000sf
Ultrasonic Ceiling Mounted Low Voltage Occupancy Sensor w/Relay
PS-CUS2000
40kHz
360˚ 2000sf
White
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay
PS-CDS2000
40kHz
360˚ 2000sf
White
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay
PS-DTC24-R
40kHz
360˚ 1000sf
White
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay
PS-CDS800
40kHz
180˚ 1000sf
White
Ultrasonic Ceiling Mounted Low Voltage Occupancy Sensor w/Relay
PS-CUS800
40kHz
180˚ 1000sf
White
PIR Ceiling Mounted Low Voltage Occupancy Sensor w/Relay
PS-CPS1000
NA
360˚ 1000sf
White
Power Pack (Required for operation)
*all coverage areas are based on a standard 9 ft mounting height
Detection Range and Coverage Area
Field of View (Top)
TOP VIEW
SIDE VIEW
38 ft.
0ft
0m
8
2.4
10
3
12
3.7
24 ft.
12 ft.
26 ft.
7.3
5.5
3.7
1.8
0m
1.8
3.7
5.5
7.3
24
18
12
6
0ft
6
12
18
24
DETECTION AREA
PIR Minor Motion
PIR Major Motion
Ultrasonic Minor Motion
Ultrasonic Major Motion
26 ft.
32 ft.
Wiring Diagrams
+24v
SENSOR
COMMON
CONTROL
Phone: 218.828.3700
RED
BLACK
BLUE
Neutral
277V
120V
Hot
PS-PP1277
Power
Pack
www.nexlight.com
BLACK
WHITE
RED
LOAD
Fax: 218.824.1568
24
PerfectSense
®
Intelligent Building Occupancy Sensors
PS-DTC24-R
Standard Range 360˚ Sensor
Dual Technology | Ceiling Mount | Low Voltage
Overview:
The PS-DTC24-R increases area lighting energy efficiency quickly
and easily by combining industry leading Passive Infrared (PIR)
technology with Ultrasonic for superior detection. Provides 2
SPDT 1 Amp, 30 VDC Form C relay contacts for integration with
Nexlight Full 2-Way system and BMS systems. Factory preset to
deliver significant savings out of the box, this sensor has
additional options to further increase energy savings if desired.
The PerfectSense PS-DTC24-R is a low-voltage sensor that works
with PerfectSense class 2 power supply (PSPP1277), to automatically control lighting. The sensor turns the lights on and keeps
them on when occupancy is detected and will turn the lights off
after the delayed-off time has expired.
Features
The sensor first sees motion using the PIR detection and then
activates Ultrasonic to confirm and indicate continued occupancy. The standard factory programming is set to meet the
standards of most common area applications with a 10 minute
off delay time.
360˚ Coverage Pattern
TM
100% Digital Multiview PIR
Dual technology uses PIR + U/S
Superior RF immunity
Adjustable Time Delay (30 sec-30 min)
Single Technology Mode
TM
SmartSense Adapt Mode
Walk Through Mode
Daylight Override Mode
Simple Test Mode
Mounts in drop ceilings and solid ceilings
LED’s provide indication of occupancy sensing
Additional Operational Features:
Electrical:
Operation:
Walk-Through Mode: useful when a room is momentarily occupied, like a storage area. When a person enters the room, the
lights turn on. If the person leaves the room before the 2.5
minute walk-through timer expires the sensor will turn the lights
off. If the person stays in the room longer than 2.5 minutes the
sensor will proceed to standard operation.
Single-Tech Mode: Only one technology is active in this mode.
Dip switch selectable, a user may determine that the space may
only require one technology to properly detect the area. One
sensor model can now act as a PIR only, Ultrasonic only or Dualtech sensor.
Daylight Sensor: The integrated daylight sensor allows for ambient light override functionality. If this setting is enabled, the
controlled lighting load will only turn on if the ambient light
present is less than the preset level.
Adaptive Learning: Patented adaptive learning technology will
automatically increase or decrease the off delay time in response
to the occupancy and environmental conditions of the area over
a period of time. For example, if there is frequent motion detection, the sensor will automatically shorten the off delay time to
better meet the conditions of the room. This technology also
detects false off conditions. If this happens, the off delay time
duration will immediately be lengthened to avoid future false off
conditions.
25
Specifications
Phone: 218.828.3700
Power Requirements: 24VDC, from powerpack
Current Consumption: 30mA
Output: 24VDC active high logic control signal
with short circuit protection
Isolated Relays: 2 SPDT 1 Amp, 30 VDC Form C
Wiring Diagram: See Fig. 2
Controls:
Passive Infrared Sensitivity: 0-100% (Factory Set 50%)
Ultrasonic Sensitivity: 0-100% (Factory Set 50%)
Light Sensor: 20-320 LUX (Factory Disables)
Detection Range: See Fig. 1
Load Rating: Controls Class 2 Power Pack
Housing Material: High-Impact ABS
Color: White
Environment Temperature: 14ºF to 122ºF
Humidity: 0-95% Non Condensing
Installation: See Install Instructions
Dimensions: Diameter 4.33 in
Height 2.2 in
Supported with a limited 5-year warranty
Title 24 Compliant
Meets ASHRAE 90.1 requirements
www.nexlight.com
Fax: 218.824.1568
Ordering Information
DESCRIPTION
CATALOG #
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay
PS-DTC24-R
Ultrasonic Ceiling Mounted Low Voltage Occupancy Sensor w/Relay
PS-CUS2000
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay
PS-CDS2000
COVERAGE*
COLOR
40kHz
360˚ 1000sf
White
40kHz
360˚ 2000sf
White
40kHz
360˚ 2000sf
White
OPERATING
FREQUENCY
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor
PS-DTC24
40kHz
360˚ 1000sf
White
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay
PS-CDS800
40kHz
180˚ 1000sf
White
Ultrasonic Ceiling Mounted Low Voltage Occupancy Sensor w/Relay
PS-CUS800
40kHz
180˚ 1000sf
White
PIR Ceiling Mounted Low Voltage Occupancy Sensor w/Relay
PS-CPS1000
NA
360˚ 1000sf
White
Power Pack (Required for operation)
*all coverage areas are based on a standard 9 ft mounting height
Detection Range and Coverage Area
Field of View (Top)
TOP VIEW
SIDE VIEW
38 ft.
0ft
0m
8
2.4
10
3
12
3.7
24 ft.
12 ft.
26 ft.
7.3
5.5
3.7
1.8
0m
1.8
3.7
5.5
7.3
24
18
12
6
0ft
6
12
18
24
DETECTION AREA
PIR Minor Motion
PIR Major Motion
Ultrasonic Minor Motion
Ultrasonic Major Motion
26 ft.
32 ft.
Hot
+24v
COMMON
CONTROL
PS-PP1277
Power
Pack
BLACK
WHITE
RED
LOAD
NORMALLY
OPEN
COMMON
NORMALLY
CLOSED
SENSOR
RED
BLACK
BLUE
Neutral
277V
120V
NORMALLY
CLOSED
COMMON
NORMALLY
OPEN
Wiring Diagrams
Phone: 218.828.3700
www.nexlight.com
Fax: 218.824.1568
26
PerfectSense
®
Intelligent Building Occupancy Sensors
PS-CDS800
Standard Range 180˚ Sensor
Dual Technology | Ceiling Mount | Low Voltage
Overview
The 180 Degree Ceiling-Mounted Occupancy Sensors are
ideal for use in business and office settings to accurately
detect occupancy and automatically control lighting.
The ceiling-mount design of these low-profile sensors
allows the greatest possible motion sensitivity. An adjustment panel is conveniently located on the front of the
sensor, providing ready access to setting controls after the
sensor is installed.
These occupancy sensors are available in the ultrasonic
and dual technology models. The dual technology model
employs passive infrared (PIR) and ultrasonic technology.
Installation and configuration is simple. The sensor readily
mounts to drop ceilings and features front located adjustments for setting sensitivity and time delay. Features an
isolated relay for use with building automation, security and
HVAC systems.
Power Requirements: 24VDC, from powerpack
Current Consumption: 33mA
Isolated Relay: Form C Contacts for Class 2 signaling
1A @24VDC Resistive
Output: 24VDC active high logic control signal
with short circuit protection
Passive Infrared Sensitivity: 600-1000 sq. ft
• 1000 sq. ft. coverage area
• 180° degree field of view
• Light level sensing (from 0.5 to 250 foot-candles)
• Adjustable time delay (pre-set time delays from 15 seconds
to 30 minutes)
• Automatic adaptive technology adjusts the time delay for
maximum energy savings.
• Adjustable sensitivity (from 60 to 100%)
• Isolated relay
•LED motion indicator
• Adjustment compartment cover equipped with retention
feature
• Manual bypass
• UL®/cUL Listed
• Title 24 Certified
• Meets ASHRAE 90.1 requirements
• Five-year warranty
Phone: 218.828.3700
Electrical:
Controls:
Features
27
Specifications
Adjustable Sensitivity of (60-100% of Max. Coverage)
Time Delay: 15 sec. - 30 min.
Light Sensor: 0.5-250 foot candles
Load Rating: Controls Class 2 Power Pack
Housing Material: High-Impact ABS
Color: White
Environment Temperature: 32ºF to 122ºF
Humidity: 0-90% Non Condensing
Installation: See Install Instructions
Dimensions: Diameter 4.5 in
Height 1.75 in
www.nexlight.com
Fax: 218.824.1568
Ordering Information
COVERAGE*
COLOR
40kHz
180˚ 1000sf
White
40kHz
360˚ 2000sf
White
PS-CDS2000
40kHz
360˚ 2000sf
White
PS-DTC24
40kHz
360˚ 1000sf
White
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay
PS-DTC24-R
40kHz
360˚ 1000sf
White
Ultrasonic Ceiling Mounted Low Voltage Occupancy Sensor w/Relay
PS-CUS800
40kHz
180˚ 1000sf
White
PIR Ceiling Mounted Low Voltage Occupancy Sensor w/Relay
PS-CPS1000
NA
360˚ 1000sf
White
DESCRIPTION
CATALOG #
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay
PS-CDS800
Ultrasonic Ceiling Mounted Low Voltage Occupancy Sensor w/Relay
PS-CUS2000
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor
OPERATING
FREQUENCY
Power Pack (Required for operation)
*all coverage areas are based on a standard 9 ft mounting height
Detection Range and Coverage Area
Dual Technology Sensor Field of View
Hot
+24v
SENSOR
COMMON
CONTROL
RED
BLACK
BLUE
Neutral
277V
120V
GREEN (N.C.)
YELLOW
(COMMON)
ORANGE (N.O)
Wiring Diagrams
PS-PP1277
Power
Pack
BLACK
WHITE
RED
LOAD
* Control power must be provided by PerfectSense Power Pack PS-PP1277 or an approved equivalent.
Phone: 218.828.3700
www.nexlight.com
Fax: 218.824.1568
28
PerfectSense
®
Intelligent Building Occupancy Sensors
PS-CDS2000
Standard Range 360˚ Sensor
Dual Technology | Ceiling Mount | Low Voltage
Overview
The Ceiling-mounted Dual Tech Occupancy Sensor
accurately detects occupancy and automatically switches
lighting on and off as needed.
This low profile sensor is ceiling mounted for superior
motion detection. With a 360 degree field of view and up
to 2000 square feet of coverage area, the Ceiling-mounted
Occupancy Sensor is ideal for storage rooms, bathrooms,
conference rooms, classrooms, hallways, and open office
areas.
Ceiling-mount sensors also incorporate an integral light
level sensor to prevent lighting from switching On when
sufficient ambient light is present, such as is commonly
found in windowed areas.
Installation and configuration is simple. The sensor readily
mounts to drop ceilings and features front located adjustments for setting sensitivity and time delay. Features an
isolated relay for use with building automation, security
and HVAC systems.
Power Requirements: 24VDC, from powerpack
Current Consumption: 37mA Nominal (125mA max)
Isolated Relay: Form C Contacts for Class 2 signaling
1A @24VDC Resistive
Output: 24VDC active high logic control signal
with short circuit protection
Adjustable Sensitivity of (60-100% of Max. Coverage)
• 2000 sq. ft. coverage area
• 360 degree field of view
• Light level sensing (from 0.5 to 250 foot-candles)
• Adjustable time delay (pre-set time delays from 15
seconds to 30 minutes)
• Automatic adaptive technology adjusts the time delay for
maximum energy savings.
• Adjustable sensitivity (from 60 to 100%)
• Isolated relay
• LED motion indicator
• Adjustment compartment cover equipped with retention
feature
• Manual bypass
• UL®/cUL Listed
• Title 24 Certified
• Meets ASHRAE 90.1 requirements
• Five-year warranty
Phone: 218.828.3700
Electrical:
Controls:
Features
29
Specifications
Time Delay: 15 sec. - 30 min.
Light Sensor: 0.5-250 foot candles
Load Rating: Controls Class 2 Power Pack
Housing Material: High-Impact ABS
Color: White
Environment Temperature: 32ºF to 122ºF
Humidity: 0-90% Non Condensing
Installation: See Install Instructions
Dimensions: Diameter 4.5 in
Height 1.25 in
www.nexlight.com
Fax: 218.824.1568
Ordering Information
COVERAGE*
COLOR
40kHz
360˚ 2000sf
White
PS-CUS2000
40kHz
360˚ 2000sf
White
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor
PS-DTC24
40kHz
360˚ 1000sf
White
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay
PS-DTC24-R
40kHz
360˚ 1000sf
White
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay
PS-CDS800
40kHz
180˚ 1000sf
White
Ultrasonic Ceiling Mounted Low Voltage Occupancy Sensor w/Relay
PS-CUS800
40kHz
180˚ 1000sf
White
PIR Ceiling Mounted Low Voltage Occupancy Sensor w/Relay
PS-CPS1000
NA
360˚ 1000sf
White
DESCRIPTION
CATALOG #
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay
PS-CDS2000
Ultrasonic Ceiling Mounted Low Voltage Occupancy Sensor w/Relay
OPERATING
FREQUENCY
Power Pack (Required for operation)
*all coverage areas are based on a standard 9 ft mounting height
Detection Range and Coverage Area
Field of View (Top)
Hot
+24v
SENSOR
COMMON
CONTROL
RED
BLACK
BLUE
Neutral
277V
120V
GREEN (N.C.)
YELLOW
(COMMON)
ORANGE (N.O)
Wiring Diagrams
PS-PP1277
Power
Pack
BLACK
WHITE
RED
LOAD
* Control power must be provided by PerfectSense Power Pack PS-PP1277 or an approved equivalent.
Phone: 218.828.3700
www.nexlight.com
Fax: 218.824.1568
30
PerfectSense
®
Intelligent Building Occupancy Sensors
PS-WPS1500
Commercial Grade Occupancy Sensor
Wall Mounted | Low Voltage | Passive Infrared
Overview
Wall-Mounted Passive Infrared (PIR) Occupancy Sensor accurately detects occupancy and automatically switches lighting on and off as needed. This sensor is
wall- or ceiling-mounted for superior motion detection.
The PIR Occupancy Sensor has three interchangeable lenses included for custom
coverage patterns. The Wide Angle lens has a 2500 square foot coverage area
when the sensor is mounted 8 feet high, the Long Range lens has a 102 linear foot
coverage area at 10 ft. high and the High Bay lens has a 54 linear foot coverage
area at 30 ft. high. With a 110 degree field of view the Wall-Mounted PIR Occupancy Sensor is ideal for warehouse, business, and office settings.
Wall-mount sensors also incorporate an integral light level sensor to prevent
lighting from switching On when sufficient ambient light is present, such as is
commonly found in windowed areas.
Installation and configuration is simple. The sensor readily mounts to walls as well
as drop ceilings and features front located adjustments for setting sensitivity and
time delay. Features an isolated relay for use with building automation, security,
and HVAC systems.
Specifications
Coverage Areas:
(All 3 lenses included)
Wide Angle: 2500 sq. ft. @ 8 ft. high
Long Range: 102 linear ft. @ 10 ft. high
High Bay: 54 linear ft. @ 30 ft. high
Field of view:
110°
Ambient light level sensing:
0.5 to 250 foot-candles
Adjustable Time Delay:
Pre-set time delays from 15 seconds to 30 minutes
Adjustable sensitivity:
60%-100% independent adjustment for US and PIR
Adaptive Technology:
Automatically adjusts the time delay for maximum energy savings
LED Motion Indicators:
Red=PIR motion indicator
Current Consumption @ 24Vdc*: 21mA Nominal
Isolated Relay:
1A @ 24 Vdc Resistive
Operating Temperature:
32 - 122° F (0 - 50° C)
Maximum Humidity:
90% RH Non-condensing
Standards:
UL®/cUL Listed
FCC: Part 15, Class B
Title 24 Certified
31
Phone: 218.828.3700
www.nexlight.com
Fax: 218.824.1568
PerfectSense
Wall Mount Type
®
Intelligent Building Occupancy Sensors
Detection Range and Coverage Area
PIR (PS-WPS1500)
Wide Angle Lens
Long Range Lens
Wiring Color Table
High Bay Lens
Wiring the Sensor
Wire Color
Function
Black
0 VDC
Red
+24 VDC
Green
Isolated contact NC
Yellow
Isolated contact common
Orange
Isolated contact NO
Blue
Control output
PS-PP1277
*Confirm the Sensor is connected to the Class 2 side of the Power Pack.
Refer to the Power Pack PS-PP1277 Instruction Bulletin for additional information.
Ordering Information
Description
Catalog Number
Wall Mounted Dual Technology Occupancy Sensor
PS-WDS1500
Wall Mounted PIR Technology Occupancy Sensor
PS-WPS1500
Wall Mounted Ultrasonic Technology Occupancy Sensor
PS-WUS1500
Power Pack (required)
PS-PP1277
Phone: 218.828.3700
www.nexlight.com
CLASS 2 DEVICE WIRING ONLY
•
•
Do not reclassify and install as Class
1, 3, or Power and Lighting wiring.
To be connected to a Class 2 power
source only.
• Wiring connections shall be rated
suitable for the wire size employed.
Failure to follow this instruction can
result in personal injury or equipment
or property damage.
Fax: 218.824.1568
32
PerfectSense
®
Intelligent Building Occupancy Sensors
PS-WUS1500
Commercial Grade Occupancy Sensor
Wall Mounted | Low Voltage | Ultrasonic Type
Overview
Wall-mounted Ultrasonic Occupancy Sensor accurately detects occupancy and
automatically switches lighting on and off as needed. This low profile sensor is
wall- or ceiling- mounted for superior motion detection over partitions and other
common obstructions.
With 1000 square feet of coverage area, the Wall-Mounted Ultrasonic Occupancy
Sensor is ideal for storage rooms, hallways, bathrooms, conference rooms,
classrooms and open office areas.
Wall-mount sensors also incorporate an integral light level sensor to prevent
lighting from switching on when sufficient ambient light is present, such as is
commonly found in windowed areas.
Installation and configuration is simple. The sensor readily mounts to walls or drop
ceilings and features front located adjustments for setting sensitivity and time
delay. Features an isolated relay for use with building automation, security and
HVAC systems.
Specifications
33
Coverage Areas:
Field of view:
Ambient light level sensing:
Adjustable Time Delay:
Adjustable sensitivity:
Adaptive Technology:
LED Motion Indicators:
Current Consumption @ 24Vdc*:
Isolated Relay:
1000 sq. ft. major motion 500 sq. ft. minor motion
NA
0.5 to 250 foot-candles
Pre-set time delays from 15 seconds to 30 minutes
60%-100% independent adjusment for US and PIR
Automatically adjusts the time delay for maximum energy savings
Red=PIR motion indicator
34mA Nominal
1A @ 24 Vdc Resistive
Operating Temperature:
32 - 122ºF (0 - 50ºC)
Maximum Humidity:
Standards:
90% RH Non-condensing
UL®/cUL Listed
FCC: Part 15, Class B
Title 24 Certified
Phone: 218.828.3700
www.nexlight.com
Fax: 218.824.1568
PerfectSense
Wall Mount Type
®
Intelligent Building Occupancy Sensors
Detection Range and Coverage Area
Ultrasonic (PS-WUS1500)
CLASS 2 DEVICE WIRING ONLY
•
•
•
NOTE: Coverage area may vary depending upon the shape,
size, and absorbent properties of the room.
Do not reclassify and install as Class
1, 3, or Power and Lighting wiring.
To be connected to a Class 2 power
source only.
Wiring connections shall be rated
suitable for the wire size employed.
Failure to follow this instruction can
result in personal injury or equipment
or property damage.
Wiring the Sensor
Wiring Color Table
Wire Color
Function
Black
0 VDC
Red
+24 VDC
Green
Isolated contact NC
Yellow
Isolated contact common
Orange
Isolated contact NO
Blue
Control output
PS-PP1277
*Confirm the Sensor is connected to the Class 2 side of the Power Pack.
Refer to the Power Pack PS-PP1277 Instruction Bulletin for additional information.
Ordering Information
Description
Catalog Number
Wall Mounted Dual Technology Occupancy Sensor
PS-WDS1500
Wall Mounted PIR Technology Occupancy Sensor
PS-WPS1500
Wall Mounted Ultrasonic Technology Occupancy Sensor
PS-WUS1500
Power Pack (required)
PS-PP1277
Phone: 218.828.3700
www.nexlight.com
Fax: 218.824.1568
34
PerfectSense
®
Intelligent Building Occupancy Sensors
PS-WDS1500
Commercial Grade Occupancy Sensor
Wall Mounted | Low Voltage | Dual Technology
Overview
The Wall-Mounted Dual Technology Occupancy Sensor employs both passive
infrared (PIR) and ultrasonic technology to accurately detect occupancy and
automatically turn on lighting.
To reduce the occurrence of false on events, this sensor employs PIR technology to detect
major motion. Once lighting has been turned on, it employs highly sensitive PIR and ultrasonic
technology to detect minor motion and keep lighting on while areas remain occupied. When the
room or area is no longer occupied, the sensor turns off lighting after a pre-set time delay.
The low profile sensor is wall-mounted for greatest sensitivity to motion in large areas with
obstructions. With a 110º degree field of view and up to 2500 square feet of coverage area when
mounted at 8 ft. off the ground, the Wall-mounted Dual Technology Occupancy Sensor is ideal
for conference rooms, classrooms, bathrooms, and large office areas.
These wall-mount sensors also incorporate an integral light level sensor to prevent lighting from
switching On when sufficient ambient light is present, such as is commonly found in windowed
areas.
Installation and configuration is simple. The sensor readily mounts to walls and drop ceilings and
features front located adjustments for setting sensitivity and time delay. The sensor also features
an isolated relay for use with building automation and HVAC systems.
Specifications
35
Coverage Area:
2500 sq. ft. @ 8 ft. high
Field of view:
110°
Ambient light level sensing:
0.5 to 250 foot-candles
Adjustable Time Delay:
Pre-set time delays from 15 seconds to 30 minutes
Adjustable sensitivity:
60%-100% independent adjusment for US and PIR
LED Motion Indicators:
Red=PIR Green= Ultrasonic
Manual Bypass:
Switch selectable
Adjusment cover:
Current Consumption @ 24Vdc*:
Isolated Relay:
Front located
37mA Nominal
1A @ 24 Vdc Resistive
Operating Temperature:
32 - 122ºF (0 - 50ºC)
Maximum Humidity:
Standards:
90% RH Non-condensing
UL®/cUL Listed
FCC: Part 15, Class B
Title 24 Certified
Phone: 218.828.3700
www.nexlight.com
Fax: 218.824.1568
PerfectSense
Wall Mount Type
®
Intelligent Building Occupancy Sensors
Detection Range and Coverage Area
Wiring the Sensor
Dual Technology (PS-WDS1500)
PS-PP1277
Wiring Color Table
Wire Color
Function
Black
0 VDC
Red
+24 VDC
Green
Isolated contact NC
Yellow
Isolated contact common
Orange
Isolated contact NO
Blue
Control output
CLASS 2 DEVICE WIRING ONLY
•
•
•
Do not reclassify and install as Class
1, 3, or Power and Lighting wiring.
To be connected to a Class 2 power
source only.
Wiring connections shall be rated
suitable for the wire size employed.
Failure to follow this instruction can
result in personal injury or equipment
or property damage.
*Confirm the Sensor is connected to the Class 2 side of the Power Pack. Refer to the Power Pack
PS-PP1277 Instruction Bulletin for additional information.
Ordering Information
Description
Catalog Number
Wall Mounted Dual Technology Occupancy Sensor
PS-WDS1500
Wall Mounted PIR Technology Occupancy Sensor
PS-WPS1500
Wall Mounted Ultrasonic Technology Occupancy Sensor
PS-WUS1500
Power Pack (required)
PS-PP1277
Phone: 218.828.3700
www.nexlight.com
Fax: 218.824.1568
36
PerfectSense
®
Intelligent Building Occupancy Sensors
PS-PP1277
Commercial Grade Power Pack
Overview
The PerfectSense Power Pack has a line input of 120 or 277 Vac, and a
single-pole, single-throw, relay output for the load. A full wave rectifier
converts the AC line voltage to 24 Vdc to power a low-voltage sensor via
Class 2, plenum-rated wire. The power pack can be mounted inside or
outside of an electrical junction box. Be sure to observe all local codes
when mounting and wiring a powerpack.
Features
•
•
•
•
•
100 mA power output can supply up to three sensors
Single-pole, normally open relay
Rated for plenum use
Relay rated for maximum 15 A tungsten and 20 A ballast loads
Mounts to a standard 4-in. x 4-in. junction box using a 1/2-in., threaded EMT nipple
Specifications
-20°F to 150°F (-29°C to 65°C)
32°F to 104°F (0°C to 40°C)
90% non-condensing
120 or 277 Vac ± 10%, 60 Hz
24 Vdc
Schematic Diagram
Hot
System Diagram
Line voltage
120/277 Vac
Hot
Red
(+24 Vdc)
White
Neutral Relay
Red
37
Voltage selector
Transformer
Black
Load
Phone: 218.828.3700
100 mA nominal
1 hp @ 120 V
120 Vac, 60 Hz
15 A tungsten 1800 W
20 A ballast
277 Vac, 60 Hz
20 A ballast
Black
Line voltage
120/277 Vac
Neutral
White
Control
Blue
(Control)
Control input
Override OFF
Load
www.nexlight.com
+24 Vdc
Common
Red
Black
(Common)
277V
Voltage selector
Output Current:
Horsepower Rating:
Switching Capacity:
120V
Storage Temperature:
Operating Temperature:
Maximum Humidity:
AC Power Input:
Output Voltage:
Blue
Blk
Red
Sensor
Fax: 218.824.1568
PerfectSense
Power Packs
®
Intelligent Building Occupancy Sensors
Installation Instructions
1. Provide separate overcurrent protection in accordance with the
National Electrical Code® and applicable local codes.
2. Use copper wire only.
3. Confirm that the device rating is proper for your application.
4. Set the voltage selector on the front of the unit to either 120 or 277
V, depending on your application. The unit is shipped with the
selector set to 277 V.
5. Mount the power pack to a suitable junction box using the 1/2-in.,
threaded nipple and lock. The power pack is plenum-rated, and can
be mounted to the inside or the outside of a junction box or fixture
in a ceiling plenum.
6. Connect the power pack as shown on previous page. Use approved
wire nuts for electrical connections.
Mounting Examples
Line voltage
Inside
120V
To
sensor
277V
120V
277V
To
sensor
Line voltage
Outside
DANGER
To
sensor
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• The power pack must be installed and serviced only by qualified
electrical personnel.
• Turn off power at the circuit breaker before beginning installation.
• Always use a properly rated voltage sensing device to confirm power is off.
Failure to follow these instructions will result in death or serious injury.
Phone: 218.828.3700
www.nexlight.com
Fax: 218.824.1568
38
PerfectSense
®
Intelligent Building Occupancy Sensors
PS-SP24
Auxiliary Relay Power Pack
Overview
The PerfectSense auxiliary relay is similar to the power pack. The auxiliary
relay does not supply power, but switches lighting and HVAC loads based
on a control signal from the occupancy sensor. Both the power pack and
auxiliary relay are housed in a rugged plenum rated enclosure, and rated
for lighting and HVAC loads, including electronic ballasts. Flexible
mounting scheme allows for installation inside or outside a standard
4”x4”junction box
Features
•
•
•
•
Single-pole, normally open relay
Rated for plenum use
Relay rated for maximum 15 A tungsten and 20 A ballast loads
Mounts to a standard 4-in. x 4-in. junction box using a 1/2-in., threaded EMT nipple
Specifications
Storage Temperature:
Operating Temperature:
Maximum Humidity:
AC Power Input:
Output Voltage:
Standards:
-20°F to 150°F (-29°C to 65°C)
Horsepower Rating:
32°F to 104°F (0°C to 40°C)
Switching Capacity:
90% non-condensing
24Vdc / 36mA
No Power Supply
UL and cUL listed
FCC: Part 15, Home and Office use Class B
System Diagram
39
Phone: 218.828.3700
1 hp @ 120 V
120 Vac, 60 Hz
15 A tungsten 1800 W
20 A ballast
277 Vac, 60 Hz
20 A ballast
Schematic Diagram
www.nexlight.com
Fax: 218.824.1568
PerfectSense
Power Packs
®
Intelligent Building Occupancy Sensors
Installation Instructions
1. Provide separate overcurrent protection in accordance with the
National Electrical Code® and applicable local codes.
2. Use copper wire only.
3. Confirm that the device rating is proper for your application.
4. Mount the power pack to a suitable junction box using the 1/2-in.,
threaded nipple and lock. The power pack is plenum-rated, and can
be mounted to the inside or the outside of a junction box or fixture
in a ceiling plenum.
5. Connect the power pack as shown on previous page. Use approved
wire nuts for electrical connections.
Mounting Examples
Line voltage
Line voltage
To
sensor
To
sensor
Inside
Outside
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• The power pack must be installed and serviced only by qualified
electrical personnel.
• Turn off power at the circuit breaker before beginning installation.
• Always use a properly rated voltage sensing device to confirm power is off.
Failure to follow these instructions will result in death or serious injury.
Phone: 218.828.3700
www.nexlight.com
Fax: 218.824.1568
40
PerfectSense
®
Intelligent Building Occupancy Sensors
PS-PP7000X
Heavy Duty Power Pack
Overview
Combines transformer relay functions, occupancy sensor control, and
manual/automatic operation into a single high performance unit. The
PerfectSense Power Pack provides a wide array of switching solutions into a
single unit. With high inrush stability circuitry specifically designed to
handle today’s demanding inrush from electronic ballast loads and offer
unmatched durability. A full wave rectifier converts the AC line voltage to
24 Vdc to power a low-voltage sensor via Class 2, plenum-rated wire. The
power pack can be mounted inside or outside of an electrical junction box.
Be sure to observe all local codes when mounting and wiring a powerpack.
Features
• Extreme durability: exceeds WS-896 Federal Specification duty cycle
requirements for specification grade toggle switches.
• High Inrush Stability circuit designed to handle high inrush electronic
ballast loads, including the latest T5HO and T4 ballasts.
• Zero crossing design for reliability and extended life.
• Mechanical latching relay for dependability and robust for all load types
• Return-to-on design provides fail safe operation in the event of power
loss or malfunction.
• Transformer Relay Function: replaces traditional transformer relays and
provides occupancy sensors control. Ideal for use where code
requirements/jurisdictions prohibit the use of 277V switch legs.
• Manual-ON or Automatic-ON functionality for use in bi-level lighting
control per CEC Title 24 requirements.
• UL 2043 Plenum Rated
• Endurance tested to over 1,000,000 cycles at full load.
• Integrates with low voltage momentary and maintained switches to
control occupancy sensors.
• Conduit adaptor included for low voltage connections.
Specifications
Storage Temperature:
Operating Temperature:
Maximum Humidity:
AC Power Input:
Output Voltage:
41
-20°F to 150°F (-29°C to 65°C)
32°F to 104°F (0°C to 40°C)
90% non-condensing
120 or 277 Vac ± 10%, 60 Hz
24 Vdc
Phone: 218.828.3700
Output Current:
Horsepower Rating:
Switching Capacity:
www.nexlight.com
225 mA nominal
1 hp @ 120 V
120 Vac, 60 Hz;
15 A tungsten 1800 W
20 A ballast
277 Vac, 60 Hz;
20 A ballast
Fax: 218.824.1568
PerfectSense
Power Packs
®
Intelligent Building Occupancy Sensors
Installation Instructions
1. Provide separate overcurrent protection in accordance with the
National Electrical Code® and applicable local codes.
2. Use copper wire only.
3. Confirm that the device rating is proper for your application.
4. Mount the power pack to a suitable junction box using the 1/2-in.,
threaded nipple and lock. The power pack is plenum-rated, and can
be mounted to the inside or the outside of a junction box or fixture
in a ceiling plenum.
5. Connect the power pack as shown on previous page. Use approved
wire nuts for electrical connections.
Bi-Level Switching Diagram
N
Zone 1 – Auto ON
H
Yellow
Orange
Orange/Yellow
Black
Blue
White
White/Blue
Blue
Green
Blue
Brown/White
Local SW 1
Occupancy
Sensor
Auto ON
Brown
Red
Black
+24VDC
Com
LOAD 1
LOAD 2
Zone 2 – Manual ON
Yellow
Orange
Orange/Yellow
Black
Blue
White
White/Blue
Blue
Green
Blue
Brown/White
Local SW 2
Manual ON
Momentary or
Maintained Switches
Brown
Red
Black
Phone: 218.828.3700
Com
www.nexlight.com
Fax: 218.824.1568
42
PerfectSense
®
Intelligent Building Occupancy Sensors
PS-LVSX Series
Low Voltage Switches
Overview
The PerfectSense™ Low Voltage Switches are a series of decorator style push button wall switches that can
be mounted in commercial or residential applications. The low voltage switches are designed to operate with
PerfectSense Occupancy Sensors and NexLight 2-Wire relay panels. All switch models are available in white,
almond, and ivory.
Features






Provide simple momentary push
button control.
LED models provide pilot lights or status
outputs.
Operate on voltage ranges from 5-36 VDC.
Certain models are designed for use with
NexLight 2-Wire relay panels.
Switches fit standard NEMA wall boxes.
Decorator-style enclosure; wall plate
included.
Ordering Information
Part Number
Description
PS-LVS1x
1-button, low voltage switch
PS-LVS1Lx
1-button, low voltage switch with LED
PS-LVS2x
2-button, low voltage switch
PS-LVS2Lx
2-button, low voltage switch with LED
PS-LVS1Rx
1-button NexLight 2-Wire relay panel switch with LED
PS-LVS2Rx
2-button NexLight 2-Wire relay panel switch with LED
x = color code; W for White, L for Light Almond, and I for Ivory.
Phone: 218.828.3700
www.nexlight.com
Fax: 218.824.1568
43
PerfectSense
Low Voltage Switches
Intelligent Building Occupancy Sensors
Low Voltage Switch Wiring
One Switch
PS-LVS1
V OUT
Specifications
Connection type
External wires
Gauge: #22 AWG stranded
Number of conductors/switch:
PS-LVS1: 2
PS-LVS1L: 4
PS-LVS2: 3
PS-LVS2L: 7
PS-LVS1R: 2
PS-LVS2R: 3
Switch Operating Range
5-36VDC
Max current of 50mA @ 36VDC
LED Operating Range
5-36 VDC
Min operating current .150ma @ 5VDC
Min operating current .275ma @ 12VDC
Min operating current .385ma @ 24VDC
Min operating current .470ma @ 36VDC
Conductor temperature rating:
Not specified, select to meet UL Class 2 requirements
Conductor voltage rating:
5 to 36 Volt DC
SW1
V IN
One Switch with LED
V OUT
PS-LVS1L
(+) Anode
SW1
(-) Cathode
V IN
Two Switches
V OUT SW1
®
Conductor length:
6 inches from housing
Temperature
0 – 50 degrees C.
Humidity
Maximum 90% RH non-condensing
PS-LVS2
Low Voltage Relay Panel Switch Wiring
SW1
One Switch
V IN
Two Switches
PS-LVS1R
SW2
V OUT
V OUT SW2
Reverse
Polarity
Switch
V OUT SW1
PS-LVS2R
Reverse
Polarity
Switch
V IN
Two Switches with LEDs
V OUT SW1
PS-LVS2L
SW1
V IN
(+) Anode LED1
Reverse
Polarity
Switch
(-) Cathode LED1
V OUT SW2
V IN
SW2
V OUT SW2
(+) Anode LED2
(-) Cathode LED2
Phone: 218.828.3700
www.nexlight.com
Fax: 218.824.1568
44
PerfectSense
Common Stand Alone Control Strategies
®
Intelligent Building Occupancy Sensors
Auto On / Auto Off
Manual On / Auto Off
1-Button
Low Voltage Switch
A
A
F
E
A
E
A
Ceiling Sensor
Ceiling Sensor
A
Power Pack
A
Power Pack
WIRING KEY
A
E
Line Voltage Class 1
Low Voltage Class 2
(16awg 3-wire)
Auto On / Auto Off is the most basic occupancy control strategy.
Requiring only a standard power pack and low voltage sensor,
the space is controlled based on occupnacy with no manual
override control. Line voltage wall switch sensors may also be
configured to work in this manner. Consult local codes for using
this scenario in approved locations.
WIRING KEY
E
F
Low Voltage Class 2
(16awg 3-wire)
Low Voltage Class 2
(16awg 2-wire)
Manual On / Auto Off is the commonly used method for areas
using a single lighting load. Occupants manually turn lights
onBe sure to use a PS-PP7000X power pack designed to work
with low voltage switches.
Manual On / Auto Off +
Dimming + Daylight Sensor
50% Manual On / Auto Off
2- Button
Low Voltage Switch
A
Line Voltage Class 1
Low Voltage Switch
a
b
A ab
A
1
E
B
A
E
E
A ab
1
Occupancy / Vacancy
Sensor
Occupancy / Vacancy
Sensor
A
A ab
B
1
Daylight Sensor
WIRING KEY
Aab
Line Voltage Class 1
(3-conductor)
E
Low Voltage Class 2
(16awg 3-wire)
50% Manual On / Auto Off requires one lighting load to be
switched on automatically when occupancy is detected by an
occupancy sensor, while a second lighting load can be turned
on manually by the occupant if desired. Both loads can then
be turned off manually or via the occupancy sensor timing
out. Commonly required by building codes (such as California
Title 24), this is an easy and convenient method of delivering
extra energy savings without inconveniencing the occupant.
WIRING KEY
A
Line Voltage Class 1
E
Low Voltage Class 2
(16awg 3-wire)
G
Low Voltage Class 2
(0-10V control wires)
F
Low Voltage Class 2
(16awg 2-wire)
Going above and beyond Manual On / Auto Off can be done
in a number of ways. The addition of photocells for daylight
harvesting and or 0-10v dimming are two of the most
popular choices for enahnced levels of control and energy
savings in locations with large windows, conference rooms, or
open office areas.
45
PerfectSense
Intelligent Building Occupancy Sensors
OUR COMMITMENT TO YOU
We take great pride in designing each of our products with the goal of providing the
highest accuracy detection performance possible in the price range of that product. We
strive to reproduce the consistent performance across all of our products. And we strive
to avoid flashy features and promises of auto-commissioning. While that may sound
initially attractive to the novice, they are not real and not enduring. In addition, we use
only the highest-quality parts and the latest assembly and quality control techniques to
ensure the reliability and long life of our products.
Our reputation rests on our steadfast pursuit of this policy in sensors and lighting control
systems for educational, commercial and industrial applications. At NexLight, we are
committed to investing in research that continually gives rise to new technologies for
improving energy savings and occupant comfort.
When you purchase any product from PerfectSense, we encourage you to compare it, as
we do, to competitive products for long-term performance accuracy. We believe that this
process will enhance your appreciation of the product you select.
With best wishes from all of us at PerfectSense for many years of consistent performance.
HOW TO PURCHASE PERFECTSENSE PRODUCTS
In order to serve you better, PerfectSense products are available through a number of
different sales channels. To get you connected with the right products for your application please contact us directly either by telephone at 218-828-3700, or visit us on the web
at www.NexLight.com for more information.
PerfectSense
®
Intelligent Building Occupancy Sensors
PerfectSense is a trademarked brand of NexLight TEL.: 218-828-3700 FAX: 218-824-1568 WWW.NEXLIGHT.COM
®
PerfectSense
®
Intelligent Building Occupancy Sensors
NexLight Lighting Controls
7877 College Road, Suite 105
Baxter, MN, 56425
1-218-828-3700
www.nexlight.com
Electrical equipment should be installed, operated, serviced and maintained
only by qualified personnel. No responsibility is assumed by NexLight for
any consequences arising out of the use of this material.
© 2013 NexLight Lighting Controls, All Rights Reserved.
Cat# PS.4.13