Paducah Tilghman HS Paducah, KY Section 16500 – Sports and Field Related Lighting Requirements .. Table of Contents Part 1 General 1.01 Applicability 1.02 Scope 1.03 System Description Lighting Performance 1.04 Foundation Design 1.05 Structural 1.06 Energy Performance 1.07 Inspection and Verification Part 2 Base Products 2.01 Lighting Equipment Aiming Lamps Enclosures Controls Hardware 2.02 Warranty Part 3 Alternate Products 3.01 Alternate Equipment Requirements Part 4 Optional Items 1 Paducah Tilghman HS Paducah, KY Part 1 General 1.01 APPLICABILITY The General Conditions, Supplementary General Conditions, Mechanical General Provisions, and the applicable requirements to each and every contract, contractor, subcontractor or other persons supplying materials and labor for this project. 1.02 SCOPE OF WORK Furnish and install Turnkey complete lighting system including poles, fixtures, ballast, lamps, etc. as set forth in the following specifications. Installation shall also include the following: 1. Pole excavation, framing and setting 2. Trenching and backfill as needed 3. All conduit,wiring and necessary terminations 4. Fields to be controlled separately by lighting controls located in a central location per owner’s approval 5. All permits and electrical inspections 6. Insurance These specifications are the minimum criteria by which all submitted equipment must meet or exceed. Project is for Fast Pitch Girls Softball to meet current IESNA Requirements. 1.03 SYSTEM PERFORMANCE A. Lighting Performance 1) The minimum lighting performance standards have been established as described below and shall be met by all manufacturers submitting bids. All Lighting designs must be done in accordance with Illuminating Society of North America design standards as published in IESNA RP-6-01. Manufactures must apply the proper tilt factor when computing light level averages. Light Level Averages listed must be shown on all layouts and documents submitted for approval. Only Initial Light Level designs will be accepted “Constant Illumination” designs are currently not recognized by IESNA and will not be accepted as alternative to this specification. 2) Lighting Levels – Target light level after 100 hours average shall be as follows. All Manufactures must meet these light levels after a 100 hour check. Field Softball Infield Softball Outfield Average Footcandles 62.8 37.7 2 Paducah Tilghman HS Paducah, KY B. Uniformity 1) Maximum/minimum ratios and Uniformity Gradiants shall not exceed the following: Field Max / Min Ratios Uniformity Gradiant Softball Infield 1.50 to 1.0 1.40 Softball Outfield 1.9 to 1.0 1.45 C. Field Measurements Actual field foot candle measurements as well as computer generated values shall be measured or computed based on the following: All Manufactures must use the listed amount of Target Points as a minimum with their design. 1.04 Field Softball Infield # Of Target Points 25 Grid Spcing 20’ x 20’ Softball Outfield 84 20’ x 20’ FOUNDATION DESIGN Poles and their foundations are to be designed to withstand 90 MPH based upon AASHTO – LTS 2001 1.05 STRUCTURAL STRENGTH Fixture assembly structural strength: Manufacturer’s submittal shall show wind tunnel testing and data that withstand forces equal to 150 MPH wind levels without structural damage or misalignment of the fixture assembly. 1.06 ENERGY PERFORMANCE A. Manufacturer shall provide a lighting layout showing point by point footcandle levels of playing surface including max/min ratio, average tilt factor, and total energy consumption in kW as required. Manufacturer shall guarantee that equipment conforms to the proposed layout and energy consumption. 1.07 INSPECTION AND VERIFICATION A. All testing will be done with entire facility illuminated. B. Test stations for field measurements of horizontal illumination levels shall cover entire area C. The test cell shall be positioned horizontal 36 inches above the playing surface for all field footcandle readings. 3 Paducah Tilghman HS Paducah, KY D. Testing equipment shall be either a United Technology Model 61 or a Gossen Panalux Electronic 2 or approved equal and shall be identified with last calibration date. E. Manufacturer shall provide a final report from the test results and the results shall contain the identification of test stations by number and location. Part 2: Base Products 2.01 LIGHTING EQUIPMENT A. Description 1) The fixture assemblies shall consist of lamps, reflectors,spill control visors, lamp moguls, adjustable aiming/mounting devices, remote ballast enclosures, galvanized steel pre-wired, pre-aimed, pre-assembled crossarms, with pole clamps and be designated as the Pro-Series PS-45 by Qualite Sports Lighting, Inc., or approved equal. 2) Equipment manufacture must be ISO 9001:2000 certified or provide proof of equal quality control procedures in place. 3) UL Listings shall be provided for the lighting system assemblies including; cross-arm assembly’s internal wiring, aiming brackets, fixture housing and remote ballast enclosures. B. Aiming 1) Each mogul assembly shall be preset in the aimed position at the factory and marked, and shall allow for future field setting without reference to manufacturer’s drawing by use of reference indicators for horizontal and vertical aiming stamped or cast into hardware. 2) Computer Models – Field Light Values Manufacturer shall submit a computer derived lighting scan, with spill control when required, and shall provide the following: a. b. c. d. e. f. Point-by-point horizontal footcandle levels on the playing surface Maximum-to-minimum ratio Number of fixtures Initial lamp lumens Average tilt factor (when applicable) Maintenance factor 4 Paducah Tilghman HS Paducah, KY C. Lamps Lamps shall meet the following specifications: ANSI designation M48, POMB, BT56 1) General Electric MVR1500/SPORT/U, Eye M1500 BSX/60 2) Lamps shall be clear jacketed and may not be painted or capped to alter reflector performance. D. Enclosures 1) Ballast Enclosures Shall be 14ga. (Galvanized) sheet steel (including the door) in accordance with ASTM 653/G90 standards, with a NEMA 3R rating or better with no side openings or screw holes, fully sealing door gasket and factory pre-wired for no more than 2 ballast and include primary power landing lugs and distribution block. Enclosures shall utilize a fulllength door, stainless steel piano hinge, a stainless steel latch and a beaded ¼” silicone gasket. Enclosure shall be powder coated with a minimum thickness of 2.5 mils. and pass the following tests: ASTM D2794 ASTM D522 ASTM D3363 ASTM D3359 ASTM B117 Dir/Rev Impact Flexibility, Mandrel Pencil Hardness Cross Hatch Adhesion 5b (no loss) Salt Spray Enclosures shall not be load-bearing members of the attachment means to the pole. 2) Diagnostic Tester Enclosure 12-1/16” x 8” x 3-1/8” and molded of high-density polyethylene. 3) Cross-arm Junction Box a. A junction box 6”x6”x4” shall be provided on the cross-arm assembly for mating of wiring for non-centrally located ballast. b. It shall be fabricated of galvanized steel in accordance with ASTM 653/G90 standards powder-coated with a minimum thickness of 2.5 mils. and pass the following tests. ASTM D2794 ASTM D522 ASTM D3363 ASTM D3359 ASTM B117 Dir/Rev Impact Flexibility, Mandrel Pencil Hardness Cross Hatch Adhesion 5b (no loss) Salt Spray 4) Disconnect Shall be fabricated of 14ga galvanized sheet steel (including the door) in accordance with ASTM 653/G90 standards, with a NEMA 3R rating or better with no side screw holes and factory pre-wired. Enclosures shall not be load-bearing members of the attachment means to the pole. 5 Paducah Tilghman HS Paducah, KY E. Hardware Ballast Assembly: Shall be high power factor, constant wattage, auto-transformer, ANSI M48 (1500W = 1000W) or M112 and be UL Listed to start lamp to -20 degrees F with inputs for required voltage as supplied in the field. There shall be individual ballast and capacitor for each fixture and no more than 2 ballast per enclosure. Ballast Assembly must be remote located on the pole at 10’ above grade. Safety Chain or Cable: Shall be #12 stainless steel chain or cable. Reflectors: Shall be 25.25” in diameter, available in 5 beam patterns without inserts and of single piece design of minimum .062” spun 3002 aluminum with an Alzak process finish and possess a compressed fiber ring to center the lamp and provide thermal and vibration protection. Filter: Each filter shall have a secured activated charcoal filter to prolong optical performance. Crossarms: Shall be 3” x 2” x 1/8” tubular steel with minimum 14awg. THHN or better and welded to a 6” C-channel support structure. Cross-arms using steel less than 1/8” are unacceptable and length shall not exceed 155”. Crossarms are hot dip galvanized after fabrication and factory pre-wired for system assembly. Over-current Protection: Manufacturer shall supply 30 amp fuse blocks for each ballast circuit rated at 600 volts with appropriately rated time-delay fuses. All wiring on the fixture assembly shall meet national and local electrical codes. Power Disconnect There shall be provided within the system a means of disconnecting electrical power to all equipment at the pole served by the feeder circuit. Power shall be disengaged by the operation of one switch, fused or non fused, or thermal magnetic breaker and be located in an enclosure as provided by the lighting manufacturer and covered under the manufacturer’s warranty. Lightning Protection: All structures shall be equipped with lightning protection meeting standards established by NFPA 780 (National Fire Protection Association) Poles: Shall be direct burial – Concrete Sports Lighting Poles –.Minimum Mounting Height of poles shall be 60’ - NOTE See pole Section for Details on poles Pole Wiring Harnesses: Wiring harness shall be #14 multi-conductor tray cable or single conductors wrapped by an outer protective sleeve with quick connect UL listed terminals. Wiring shall be color coded to each fixture for ease of installation and future maintenance. Harness assembly shall have a stainless steel wire support device with stainless steel support ring for tension relief. 6 Paducah Tilghman HS Paducah, KY 2.02 WARRANTY Warranty The fixture assembly including structural and aiming shall be warranted against movement from the pre-aimed position and defects for ten (10) years. This warranty shall only cover defective parts and workmanship of hardware as supplied from the factory. Any parts found defective shall be replaced free of charge to the customer for the first five (5) years. Lamps shall be warranted for a period of (2) two years; installation and lamps included first year, lamps only for the remainder of the warranty period. Fuses shall not be warranted after installation. 3.01 ALTERNATE EQUIPMENT REQUIREMENTS Alternates Requirements to be submitted at 10 days prior to bid for alternates. No Submittals will be accepted after that date. Failure to provide any of the following information at bid time will be grounds for rejection of bid. Each item listed below shall be provided in the form of clear and concise statements and/or plans and drawings, which can be easily read and clearly interpreted. Each item shall also be clearly numbered to correspond with the following list. All items shall be assembled in the order indicated and secured or bound in a neat and orderly fashion for easy use and reference. 1) Complete photometry reports from a qualified independent testing source. 2) A computer derived lighting layout showing point by point footcandle levels on playing surface. 3) Lighting plan showing focus points, reflector types and aiming. 4) Written statement of initial and maintained average footcandle levels. Levels must meet current IESNA requirements. Constant Illumination designs will not be permitted. 5) Written statement of uniformity ratio. 6) Written statement indicating total kW load. 7) Written guarantee that the lighting design and equipment bid conform to the foot candle and uniformity requirements of these specifications along with written statement of remedy should deficiencies be noted by customer. 8) Written statement of model number and manufacturer for all equipment bid. Statement must also include all options including inserts, shields. 9) A packet of descriptive literature on all equipment for the bid. 7 Paducah Tilghman HS Paducah, KY 10) Written manufacturer’s warranty covering fixture assembly and replacement policy. 11) Written 10 year warranty covering aiming alignment of the fixture assembly. 12) A registered professional engineer, independent of manufacturer, shall verify and stamp wind load certification of the fixture assembly using accepted industry calculation method. 13) Physical testing of assemblies shall include results of actual material properties. 14) Provide UL Listing for luminaire assemblies showing approved for wet locations. 15) A written itemized statement of exceptions and discrepancies to bid specifications if any. If none, so state. SPECIFICATION FOR STATIC CAST, PRESTRESSED CONCRETE POLES SPORTSLIGHTING POLES A. SCOPE 1. This specification addresses design, materials, fabrication, quality assurance, pole requirements, optional pole accessories, and the handling and erection of prestressed static cast concrete poles. 2. Poles shall be prestressed concrete manufactured by the static cast process and nominally octagonal, or dodecagonal in cross section with a center void. 3. Design, fabrication, allowable stresses, processes, tolerances and inspection shall conform to codes and standards as follows: a. American Concrete Institute (ACI) - 318 Building Code Requirement for Reinforced Concrete. b. Prestressed Concrete Institute (PCI) - MNL-116 Manual for Quality Control for Plants and Production of Precast Prestressed Concrete Products. c. PCI Guide Specification for Prestressed Concrete Poles. d. American Association of State Highway and Transportation Officials (AASHTO) Standard Specifications for Structural Supports for Highway Signs, Luminaires and Traffic Signals. B. DESIGN 1. Poles shall be designed to conform to the wind loading criteria of the American Association of State Highway and Transportation Officials (AASHTO) publication Standard Specifications for Structural Supports for Highway Signs, Luminaires and Traffic Signals. The geographically appropriate wind speed shall be chosen from the 50 - year Mean Recurrence Interval Isotach Chart as given in this publication. 8 Paducah Tilghman HS Paducah, KY 2. The ultimate structural design shall consider the application of both dead loads, gusted wind loads and secondary moments induced by dead load deflection. The calculated ultimate strength of the pole shall include the appropriate strength reduction coefficients as specified by the AASHTO code for flexural and torsional strength. Applied design loads shall include the appropriate over-capacity factors as specified in the AASHTO code for flexural and torsional loading. All wind loads on fixtures and support arms and cages shall be computed on the basis of the manufacturer’s published EPA (the effective projected area determined by dynamic wind tunnel testing) for those fixtures and support arms and cages. If manufacturer’s published EPA data is not available, then the actual net areas shall be modified by the appropriate wind drag coefficient as set forth in the AASHTO publication. 3. Poles shall be designed such that the forces induced by handling, erection and transportation operations will not exceed the cracking capacity of the pole when handled at the pickup point locations indicated by the pole manufacturer. 4. Pole design shall provide for a 1 point erection location for lifting the pole, including the fixtures and mounting hardware, to the vertical installed position. Two lifting locations will be indicated on the pole showing where the attachment locations are so that the pole can be lifted from the truck and transported in the horizontal position. Equal length slings are to be used for two point lifting and no sportslighting hardware is to be attached to the pole. C. MATERIAL 1. Concrete - The concrete mix shall achieve a minimum 28 day compressive strength of 10,000 p.s.i. Cement shall conform with ASTM-C150. Maximum size aggregate shall be 3/4 inch. Water reducers, retarders, or accelerating admixtures shall conform to ASTM-C494. Water shall be free from foreign materials in amounts harmful to concrete and embedded steel reinforcement. a. The use of Calcium Chloride, other salts or materials releasing chloride is prohibited. b. The use of materials causing pyrite staining or efflorescence due to sulphate is prohibited. c. The total content of chloride ions in the finished concrete mix shall not exceed 0.40 lb. per cubic yard (or approximately 100 PPM). 2. Prestressing Tendon - Prestressing tendon reinforcement shall be uncoated 7-wire, stress relieved strand per ASTM-A416. 3. Spiral Reinforcement - Steel spiral reinforcement shall conform to the requirements of ASTM-A82 and shall be not less than 0.1205 inch in diameter (11 gauge wire). The pitch of the spiral shall not be greater than 4 inches except for a distance of three feet at the tip and the butt end of the pole, where the pitch is to be reduced to 1.5 inches. 4. Hardware - All structural steel attached to the pole, such as lighting arms and lighting cages shall be fabricated from steel conforming to ASTM-A36. The hardware shall be hot-dipped galvanized in accordance with ASTM-A123. Inserts shall be non-corrosive and weather-proof. Bolts, nuts, washers, and other fasteners shall be either stainless steel or hot-dipped galvanized. D. FABRICATION 1. Tolerances, details of reinforcement and concrete finish shall be in accordance with PCI’s “Guide Specification for Prestressed Concrete Poles”. 9 Paducah Tilghman HS Paducah, KY 2. Poles shall be constructed so that wiring and grounding facilities are concealed within the pole. Handholes, wire inlets and outlets, inserts for pole steps (if specified), and ground wire shall be cast into the pole during the manufacturing process. 3. Forms shall be designed to provide a continuous pole taper of 0.180 inches per foot of length. 4. All steel reinforcement, including the spiral wire, shall have a minimum concrete cover of 1.00 inch. 5. Poles shall have a natural form finish, soft gray in color. 6. Holes shall be accurately located from the pole tip. Holes shall be sized 1/8 inch larger in diameter than the through-bolt they will accommodate and they shall be aligned perpendicular to the pole axis. Holes shall be either cast during pole fabrication or drilled after pole fabrication. 7. Embedded hardware items shall be accurately set in the forms and shall be secured to prevent their movement during the placement of the concrete. 8. After the pole is removed from the form, all small cavities caused by air bubbles, honey comb spots or other small voids shall be cleaned, saturated with water and then carefully pointed with mortar. A small cavity is defined as exceeding 1/2” but less than 3/4”. Larger cavities not exceeding 2” shall be repaired by opening the cavity sides with a mechanical grinder, cleaning thoroughly and patching with a fast set cement. 9. The end of each prestressed tendon emerging from the pole tip shall be burned back from the pole surface at least 1 inch, cleaned of debris and sealed with an epoxy adhesive. The end of each prestressed tendon emerging from the pole butt shall be epoxy adhesive. 10. Each pole tip shall be covered by an aluminum cap plate. 11. A cast aluminum nameplate shall be cast into the wall of the pole approximately 4 feet above ground line. The nameplate shall identify the pole manufacturer, indicate the overall pole length, and indicate the pole weight. E. QUALITY ASSURANCE 1. Testing shall be in accordance with the applicable provisions of Prestressed Concrete Institute (PCI) MNL-116. 2. Test for compressive strength of concrete cylindrical test specimens shall comply with ASTM C-39. 3. Certified mill tests of the mechanical properties of cement and steel shall be made available upon request. F. POLE REQUIREMENTS 1. Provide drilled through holes for lighting arms and lighting cages as required. 2. Provide a 4” x 10” conduit entrance opening, centered 18” below grade. 3. Provide a 3-1/2” x 10” reinforced handhole frame with cover, 24” above grade. 10 Paducah Tilghman HS Paducah, KY 4. Provide a 2-1/2” x 8” reinforced handhole frame with flush cover located at the lighting arm or lighting cage level for use during installation and maintenance of electrical wiring. 5. Provide a 1-1/2” galvanized pipe coupling wire inlet/outlet, located opposite the handhole at the lighting arm or lighting cage level. 6. Provide an internal wire support directly above each wire inlet/outlet, accessible from the handhole opening. 7. Provide a continuous #2 stranded copper ground wire cast into the pole. The ground wire shall terminate in a brass coupling located at the lighting arm or lighting cage level and a coupling approximately 18” below grade. The brass coupling provides a 1/2” tapped insert at the pole face for grounding of hardware. 8. Provide a 1/2” diameter x 24” long air terminal to be attached to the pole at the top. G. OPTIONAL POLE ACCESSORIES 1. Provide step bolts either 5/8” or 3/4” in diameter, alternately spaced at 18” intervals, 90-120 degrees apart, beginning 10 feet above the ground and continuing to within 18” of the lighting arm or lighting cage level. The top and bottom step locations are to be “doubled” (one step on each side of the pole). 2. Provide a 5/16” diameter galvanized safety cable, complete with pole attachment hardware. 3. Provide a safety belt, complete with sliding “quick-stop” hardware. H. HANDLING & ERECTION 1. Transportation, site handling and erection shall be performed by qualified personnel utilizing adequate equipment and while following acceptable industry methods. 2. Concrete poles shall be lifted and supported during the manufacturing, stock piling, transporting and erection operations only at the lifting or support points, as indicated by the pole manufacturer. 3. The pole manufacturer shall provide information which identifies the pole number, pole length, pole weight, erection attachment location and the two attachment locations to be used for handling the pole while it is hanging in the horizontal position. 4. Prior to unloading the pole, the erection contractor shall review the manufacturer’s information which identifies the erection attachment location and the two attachment locations to be used for handling the pole in the horizontal position. 5. WARNING: SAFETY HAZARD All necessary precautions as required by national and local safety codes for handling and erecting utility poles shall be exercised. Proper clearance from high voltage circuits must be maintained at all times. Due to the presence of longitudinal steel reinforcement within the pole, PRESTRESSED CONCRETE POLES ARE CONSIDERED TO BE CONDUCTORS OF ELECTRICITY. 11