ELECTRICAL SYMBOLS LEGEND
S
D1
V
1.
VOLUME CONTROL - MOUNT 46" AFF.
2.
WALL MOUNTED FIXTURE - AS ABOVE - MOUNTING HEIGHT AS PER PLANS.
M
DUPLEX MICROPHONE OUTLET - MOUNT 18" AFF.
EXIT LIGHT - CEILING MOUNTED; WALL MOUNT 7'-6" AFF OR ABOVE DOOR SHADED PORTION INDICATES
FACE; WITH DIRECTIONAL ARROW(S) AS INDICATED. FIXTURE TYPE "X" (U.N.O.).
M
DUPLEX MICROPHONE OUTLET - FLOOR MOUNTED.
M
MICROPHONE OUTLET - CEILING MOUNTED FOR CORD HUNG DEVICE.
COMBINATION EXIT LIGHT WITH EMERGENCY LIGHTING HEADS. FIXTURE TYPE "X1" (U.N.O.).
1.
INTERCOM STATION - MOUNT 46" AFF.
IC
LED,FLUORESCENT OR H.I.D. FIXTURE - AS ABOVE - CEILING MOUNTED OR PENDANT MOUNTED
TO HEIGHT INDICATED.
C1
SPEAKER - WALL MOUNT 84" AFF.
GENERAL CONSTRUCTION NOTES:
TC
3.
TIME CLOCK
4.
1a,b
NL
EMERGENCY LIGHT - BATTERY OPERATED - WALL MOUNTED 84" AFF (U.N.O.). FIXTURE TYPE "Y" (U.N.O.).
PUSHBUTTON - MOUNT 46" AFF.
LIGHT POLE WITH SINGLE HEAD LUMINAIRE.
BELL - MOUNT 84" AFF.
LIGHT POLE WITH MULTIPLE HEADS (AS INDICATED).
VOICE OUTLET - MOUNT 18" AFF; W INDICATES WALL MOUNT 46" AFF,
SHADING DENOTES EMERGENCY FIXTURE.
DATA OUTLET - MOUNT 18" AFF.
6.
FIXTURE CIRCUITRY NOTATION:
1 - CIRCUIT NUMBER TO WHICH FIXTURE IS CONNECTED
a,b - LETTER(S) OF SWITCH(ES) CONTROLLING FIXTURE
NL - NIGHT LIGHT (UNSWITCHED CIRCUIT)
DATA OUTLET - 8" ABOVE COUNTER.
7.
5.
FLOOR MOUNTED DATA OUTLET.
WIRING DEVICES
COMBINATION VOICE & DATA OUTLET - MOUNT 18" AFF.
8.
COMBINATION VOICE & DATA OUTLET - 8" ABOVE COUNTER.
9.
S
SINGLE POLE SWITCH - "a" INDICATES SWITCH LEG - MOUNT 46" AFF.
FLOOR MOUNTED COMBINATION VOICE & DATA OUTLET.
WIRELESS ACCESS POINT - CEILING MOUNTED, U.N.O.
a
10.
S
DOUBLE POLE WALL SWITCH - AS ABOVE.
S
THREE-WAY SWITCH - AS ABOVE.
TTB
TELEPHONE TERMINAL BOARD - 3/4" FIRE RETARDANT PLYWOOD, 4' x 8' (U.N.O.).
11.
S
FOUR-WAY SWITCH - AS ABOVE.
TTC
12.
S
TELEPHONE TERMINAL CABINET 24" x 36" x 6" (U.N.O.) WITH FIRE RETARDANT PLYWOOD BACK AND
HINGED DOOR WITH KEY LOCK.
KEY OPERATED SWITCH - AS ABOVE.
S
SWITCH WITH PILOT LIGHT - AS ABOVE.
2
3
4
K
TV
P
T.V. OUTLET - MOUNT 18" AFF U.N.O.
ABBREVIATIONS
S
WALL BOX TIMER SWITCH.
S
FAN CONTROL SWITCH.
AC
ABOVE COUNTER
S
MANUAL MOTOR STARTER WITH OVERLOAD PROTECTION - MOUNT ON SIDE OF UNIT OR AT 46" AFF.
AIC
AMP INTERRUPTING CURRENT
S
OCCUPANCY SENSOR WALL MOUNTED, MOUNT 46" AFF. "2" INDICATES DUAL RELAY.
AFC
AVAILABLE FAULT CURRENT
AFF
ABOVE FINISHED FLOOR.
T
FC
M
OS
14.
S
TS
TIME SWITCH - MOUNT 60" AFF.
PC
PHOTOCELL MOUNTED IN WP OUTLET BOX LOCATED ON ROOF, FACING NORTH, (U.N.O.).
LC
LIGHTING CONTACTOR FOR NUMBER OF CIRCUITS AS INDICATED ON PLAN.
OS
OCCUPANCY SENSOR, CEILING MOUNTED, "2" INDICATES 2 POLE.
EC
ELECTRICAL CONTRACTOR
JUNCTION BOX OR POINT OF CONNECTION - MOUNT 18" AFF OR AT HEIGHT REQUIRED BY RESPECTIVE
EQUIPMENT ITEM MANUFACTURER.
EM
EMERGENCY
J
AFI/AFCI
DUPLEX RECEPTACLE - MOUNT 18" AFF.
DOUBLE DUPLEX RECEPTACLE - AS ABOVE.
SINGLE CONVENIENCE RECEPTACLE - AS ABOVE.
DUPLEX RECEPTACLE AS ABOVE - SPLIT WIRED, TOP HALF SWITCHED.
DUPLEX 8" ABOVE COUNTER OR WALL HUNG LAVATORY.
DOUBLE DUPLEX RECEPTACLE 8" ABOVE COUNTER
CEILING MOUNTED DUPLEX RECEPTACLE, FLUSH IN CEILING (U.N.O.).
FLOOR MOUNTED DUPLEX RECEPTACLE WITH BRASS PLATE AND CARPET FLANGE.
SPECIAL PURPOSE OUTLET - MOUNT 18" AFF. TYPE AS REQUIRED BY RESPECTIVE EQUIPMENT MFR.
COMBINATION POWER & DATA/VOICE FLOOR BOX OR POKE THRU - "FF" INDICATES FURNITURE FEED.
MOTORS AND EQUIPMENT
DISCONNECT SWITCH (FUSED OR NON-FUSED AS INDICATED) - MOUNT 60" AFF. 30/20/3 INDICATES
SWITCH AMPS/FUSE AMPS/POLES.
30/20/3
T
ATS
CATV
ARC FAULT CIRCUIT INTERRUPTER TYPE DEVICE, (U.N.O.)
ELECTRIC WATER COOLER; ROUGH-IN RECEPTACLE INCONSPICUOUSLY; COORDINATE WITH PC
EWH
ELECTRIC WATER HEATER
EX
EXISTING
FLA
FULL LOAD AMPS
FPC
FIRE PROTECTION CONTRACTOR
FSS
FUSIBLE SAFETY SWITCH
GC
GENERAL CONTRACTOR
MFR
MANUFACTURER
MH
MOUNTING HEIGHT
30.
MIN
MINIMUM
31.
NF
NON-FUSED SWITCH
32.
33.
KILOWATT HOUR METER BASE.
TYP
TYPICAL
U.N.O.
UNLESS NOTED OTHERWISE
UPS
UNINTERRUPTABLE POWER SUPPLY
WP
WEATHERPROOF
34.
SEISMIC RESTRAINTS FOR ELECTRICAL SYSTEM COMPONENTS (EARTHQUAKE LOAD RESISTANCE)
SEISMIC USE GROUP ( II )
HORN OR SPEAKER - MOUNT 80" AFF; V DENOTES COMBINATION AUDIBLE/VISUAL APPLIANCE.
(NUMERALS INDICATE CANDELA).
FIRE ALARM MAGNETIC DOOR HOLDER.
F R
INTERFACE RELAY FOR CODE REQUIRED ACTION, OR AS NOTED ON PLANS; SEE SPECIFICATION.
F CM
CONTROL MODULE FOR CODE REQUIRED ACTION; SEE SPECIFICATION.
F MM
MONITOR MODULE FOR CODE REQUIRED ACTION, OR AS NOTED ON PLANS; SEE SPECIFICATION.
T
SPRINKLER TAMPER SWITCH (FURNISHED BY FPC).
F
SPRINKLER FLOW SWITCH (FURNISHED BY FPC).
P
SPRINKLER PRESSURE SWITCH (FURNISHED BY FPC).
RQE
SEISMIC DESIGN CATEGORY ( D )
ANCHORAGE TO
FLOORS, ROOFS, ETC.
NOT
PROVIDED
PROVIDED
SWAY BRACING
NOT
PROVIDED
PROVIDED
LOCATION OF PROFESSIONALLY SEALED
ANCHORAGE AND SWAY BRACING DETAILS
ON CONST.
DOCUMENTS
DRAWING NO. OR
SPEC. SECTION
SUBSEQUENT SUBMITTAL
SHOP DRAWINGS
COMMENTS
SEPARATE
PERMIT & PLANS
42.
X
X
5
N/A, NO EMERGENCY OR STANBY
EQUIPMENT IN THE PROJECT
X
X
X
X
X
OTHER EQUIPMENT & SYSTEM COMPONENTS
NEEDED FOR CONTINUED OPERATION OF
SEISMIC USE GROUP III FACILITIES OR WHOSE
FAILURE COULD IMPAIR THEIR CONTINUED
OPERATION;
N/A, NO SEISMIC USE GROUP III OR
IV IN THE PROJECT
ELECTRICAL ALTERNATE #1:
PROVIDE AN ALTERNATE PRICE ADDER FOR THE FOLLOWING:
- REPLACE EXISTING PANEL 102B WITH A NEW 60 POLE, 1 SECTION, 120/208V, 3 PHASE, 4 WIRE, 225A, 10KAIC, MLO PANELBOARD.
- PROVIDE TEN (10) ADDITIONAL 20A/1 POLE CIRCUIT BREAKERS AS SPARES.
- PROVIDE A 120/208V, 3 PHASE SURGE PROTECTIVE DEVICE AND AN ASSOCIATED 30A/3 POLE CIRCUIT BREAKER FOR THE SPD.
- PROVIDE ALL ASSOCIATED INSTALLATION, LABOR AND COORDINATEION FOR THE ABOVE WORK.
OTHER GENERAL EQUIPMENT & SYSTEM
COMPONENTS;
MOTION DETECTOR
DOOR CONTACT
PANEL BOARD
LIGHTING FIXTURES
CONDUIT AND WIRING
CARD READER/PROX READER
REQUEST TO EXIT
ES
ELECTRIC STRIKE (FURNISHED BY DIVISION 8)
EH
ELECTRIFIED HARDWARE (FURNISHED BY DIVISION 8)
ML
MAGNETIC LOCK (FURNISHED BY DIVISION 8)
GB
GLASS BREAK SENSOR
ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR NECESSARY PERMITS, LICENSES, INSPECTIONS AND
FEES FROM THE LOCAL AUTHORITIES. CONTRACTOR SHALL BE LICENSED BY LOCAL AND/OR STATE AUTHORITIES
HAVING JURISDICTION..
ALL MATERIAL AND WORKMANSHIP SHALL CONFORM TO THE NATIONAL FIRE PROTECTION ASSOCIATION (NFPA),
NATIONAL ELECTRICAL CODE (NEC), INTERNATIONAL BUILDING CODE (IBC) AND OTHER APPLICABLE LOCAL, STATE
AND NATIONAL CODES.
ALL ELECTRICAL MATERIAL USED ON THIS PROJECT SHALL BE "UL" LISTED AND LABELED.
THE ENTIRE ELECTRICAL SYSTEM AND ALL ELECTRICAL EQUIPMENT SHALL BE GROUNDED IN STRICT
ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND AS SHOWN ON THE DRAWINGS. PROVIDE A GROUND
WIRE IN EACH POWER CONDUIT, SIZED PER THE NEC.
CONTRACTOR SHALL BE RESPONSIBLE FOR INSTALLING A COMPLETE SYSTEM PER CONTRACT DRAWINGS AND
ENSURING THAT THE SYSTEM IS OPERATIONAL UPON JOB COMPLETION.
CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING WITH ALL OTHER TRADES AND DISCIPLINES TO AVOID
CONFLICTS AND TO VERIFY ALL EQUIPMENT CONNECTIONS. COORDINATE ALL WIRING DEVICE LOCATIONS AND
ELEVATIONS INDICATED ON THE PLANS WITH THE OWNER, ARCHITECT AND FINAL FURNITURE/EQUIPMENT
LAYOUTS.
CONTRACTOR SHALL GUARANTEE ALL LABOR AND MATERIAL INSTALLED OR FURNISHED UNDER THIS CONTRACT
FOR A PERIOD OF NOT LESS THAN ONE YEAR AFTER FINAL ACCEPTANCE OF THE BUILDING.
MAINTAIN AND VERIFY ELECTRICAL EQUIPMENT CLEARANCES AND WORKING SPACE PER NEC.
PROVIDE ELECTRICAL SYSTEMS IDENTIFICATION AS INDICATED IN THE SPECIFICATIONS AND REQUIRED BY THE
NEC OR NFPA 70E.
IF ANYTHING ON THE PLANS IS NOT IN COMPLIANCE WITH NATIONAL, STATE OR LOCAL CODES, THE ENGINEER
SHALL BE ADVISED BY THE ELECTRICAL CONTRACTOR DURING THE BIDDING PROCESS. THERE ARE TO BE NO
CHANGES TO THE CONTRACT DOCUMENTS WITHOUT WRITTEN PERMISSION FROM THE ENGINEER.
CONTRACTOR SHALL BE RESPONSIBLE FOR ALL MEANS AND METHODS FOR NEW WORK, SAFETY, ETC., IN
ACCORDANCE WITH ALL AUTHORITIES HAVING JURISDICTION. (I.E. OSHA, NEC, ETC.)
THE CONTRACTOR SHALL REFER TO ARCHITECTURAL DRAWINGS FOR PHASING AND SCHEDULING OF THIS
PROJECT. COORDINATE WITH OWNER'S FIELD REPRESENTATIVE.
VERIFY ALL INDICATED DIMENSIONS BY FIELD MEASUREMENTS. NOTIFY ENGINEER OF ANY DISCREPANCIES.
PROVIDE ACCESS PANELS OR DOORS WHERE EQUIPMENT OR DEVICES REQUIRED TO BE ACCESSIBLE ARE
CONCEALED BEHIND INACCESSIBLE SURFACES.
PRIOR TO TURNOVER, THIS CONTRACTOR SHALL REMOVE ALL RUBBISH, DIRT, DEBRIS AND STAINS ON THEIR
WORK OR CAUSED BY THEIR WORK AND SHALL THOROUGHLY CLEAN ALL EQUIPMENT, FIXTURES, DEVICES, ETC.
CONTRACTOR SHALL REPLACE, TOUCH-UP OR REFINISH THE FACTORY FINISH ON EQUIPMENT, FIXTURES,
DEVICES, ETC. MARRED DURING SHIPMENT, INSTALLATION OR CONSTRUCTION.
PANELBOARD CIRCUIT BREAKERS SHALL BE EQUIPPED WITH BOLT-ON TYPE BREAKERS, PHENOLIC NAME TAGS
AND KEYED LOCK AND LATCH. EACH PANEL SHALL BE PROVIDED WITH TWO KEYS WITH ALL PANELS KEYED
ALIKE. ALL CIRCUIT BREAKERS USED TO SWITCH LIGHT FIXTURES SHALL BE TYPE SWD SHALL BE APPROVED FOR
THE PURPOSE. ALL CIRCUIT BREAKERS SERVING HVAC EQUIPMENT SHALL BE HACR TYPE.
ALL CIRCUITS INDICATED ON THESE DRAWINGS ARE 20A, 1P CIRCUIT BREAKERS IN PANELS UNLESS NOTED
OTHERWISE.
THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE PROPER IDENTIFICATION AND LABELING OF ALL
CIRCUIT BREAKERS. EACH PANELBOARD SHALL BE EQUIPPED WITH A TYPE WRITTEN CIRCUIT DIRECTORY. ALL
EXISTING PANELBOARDS THAT HAVE CIRCUITS ALTERED SHALL HAVE A NEW TYPE WRITTEN CIRCUIT DIRECTORY
SHOWING CIRCUIT REVISIONS AND EXISTING CIRCUIT CONDITIONS ON THE NEW DIRECTORY.
MINIMUM WIRE SIZE SHALL BE #12 AWG UNLESS OTHERWISE NOTED. MINIMUM CONDUIT SIZE SHALL BE 1/2"
UNLESS OTHERWISE NOTED. ALL CONDUIT IN SLABS OR EXTERIOR TO BUILDING SHALL BE MINIMUM 1". PROVIDE A
NYLON/POLY PULL CORD IN ALL EMPTY CONDUITS.
ELECTRICAL CONTRACTOR SHALL PROVIDE ALL COPPER CONDUCTORS TYPE THHN OR THWN FOR ALL INTERIOR
BUILDING WIRE. FOR EXTERIOR FEEDERS AND BRANCH CIRCUITS PROVIDE ALL COPPER CONDUCTORS TYPE
XHHW-2.
VOLTAGE DROP MINIMUM WIRE SIZING (20A CIRCUIT) USE: 120V CIRCUIT OVER 100' SHALL BE #10 MINIMUM; 120V
CIRCUIT OVER 175' SHALL BE #8 MINIMUM; 208V CIRCUIT OVER 200' SHALL BE #10 MINIMUM; 277V CIRCUIT OVER
200' SHALL BE #10 MINIMUM. MINIMUM WIRE SIZE FOR ANY 20A BRANCH CIRCUIT SHALL BE #12. FURTHERMORE,
CONSIDER ALL DERATING OF CONDUCTORS AS REQUIRED IN ACCORDANCE WITH THE APPLICABLE NEC.
ELECTRICAL CONTRACTOR SHALL HAVE THE OPTION OF GROUPING HOME RUNS IN ONE CONDUIT, PER THE
REQUIREMENTS OF SECTION 310 OF THE NATIONAL ELECTRICAL CODE. NO MORE THAN FOUR (4) CIRCUITS SHALL
BE ALLOWED TO BE GROUPED AND INSTALLED IN A SINGLE JUNCTION BOX. EC SHALL BE RESPONSIBLE FOR
INCREASING CONDUCTOR SIZE AND DERATING. HOME RUNS WITH MORE THAN THREE CIRCUITS SHALL BE #10
AWG. CONDUCTOR MINIMUM. PROVIDE DEDICATED NEUTRALS FOR EACH PHASE CONDUCTOR AND CONSIDER
THEM AS A CURRENT CARRYING CONDUCTOR FOR DERATING.
ALL HOME RUNS SHALL BE IN EMT CONDUIT. MC CABLE IS PERMITTED ABOVE CEILINGS FROM HOMERUNS TO
FIXTURES AND WIRING DEVICES WITHIN WALLS AND FURRED COLUMNS. REFER TO ELECTRICAL SPECIFICATIONS
FOR MORE DETAILED INFORMATION.
ONLY PVC CONDUIT SHALL BE PERMITTED IN CONCRETE SLAB, EXCEPT FOR GRS ELLS.
WHEN SAW CUTTING FLOOR IS REQUIRED, CONTRACTOR SHALL LIMIT DEPTH TO A MINIMUM. ROUTE NEW
CONDUITS BELOW OR ABOVE EXISTING CONDUITS, WATER PIPES, ETC. CONDUIT SHALL HAVE A MINIMUM OF 1'' OF
CONCRETE COVER. CONTRACTOR SHALL XRAY FLOOR SLAB PRIOR TO ANY SAW CUTTING.
ELECTRICAL CONTRACTOR SHALL ARRANGE WITH THE ELECTRIC, CATV AND TELEPHONE UTILITY COMPANIES FOR
INCOMING SERVICE REQUIREMENTS FROM LANDLORD DEMARC AND INCLUDE ALL COSTS IN BASE BID.
HEATING, VENTILATING, AIR CONDITIONING EQUIPMENT AND PLUMBING EQUIPMENT ALONG WITH ALL OTHER
MISCELLANEOUS EQUIPMENT, MOTORS, AND KITCHEN EQUIPMENT SHALL BE POWERED AS CALLED OUT ON
EQUIPMENT PROVIDER'S SCHEDULES UNLESS OTHERWISE NOTED. EC SHALL PROVIDE DISCONNECTING MEANS
UNLESS SPECIFICALLY NOTED ON EQUIPMENT PROVIDER'S SCHEDULE.
SUPPORT ALL CONDUITS FROM STRUCTURAL WALLS, SLABS, MEMBERS AND ROOF JOISTS. DO NOT SUPPORT
CONDUITS FROM CEILING TIE WIRES, DUCTWORK, PIPING, ROOF DECK OR OTHER NON-STRUCTURAL MEMBERS.
SUPPORTING OF ELECTRICAL CONDUITS: THE INDIVIDUAL BRANCH CIRCUIT CONDUIT AND ASSOCIATED 4'' X 4''
JUNCTION BOXES MAY BE SUPPORTED FROM FLOOR/ROOF JOISTS. ALL LARGER FEEDER CONDUITS AND/OR
CLUSTER OR GROUPS OF BRANCH CIRCUIT CONDUITS SHALL BE SUPPORTED ON STEEL TRAPEZE WITH STEEL
CHANNEL ATTACHED TO STEEL OR WOOD JOIST/BEAMS WITH PROPER ATTACHMENTS. NO SUPPORT SHALL BE
ATTACHED TO THE ROOF DECK (NO EXCEPTIONS). HANG CONDUIT FROM TOP CHORD OF BAR JOIST WHEN
ATTACHING HOME RUNS TO JOIST.
INTERIOR AND EXTERIOR LIGHT FIXTURES SHALL BE FURNISHED AND INSTALLED AS SHOWN ON THE DRAWINGS
AND AS CALLED OUT IN THE LIGHTING FIXTURE SCHEDULE.
ALL WIRING DEVICES SHALL BE FLUSH MOUNTED, UNLESS NOTED OTHERWISE. ALL CONDUIT SHALL BE RUN
WITHIN WALL CAVITIES, BELOW FLOOR AND ABOVE CEILINGS. SURFACE MOUNTED ELECTRICAL WORK SHALL NOT
BE USED UNLESS SPECIFICALLY NOTED ON THE PLANS.
ALL WALL AND CEILING FIXTURES AND DEVICES SHALL BE INDEPENDENTLY AND SECURELY MOUNTED SO THEY
ARE NOT DEPENDENT ON CEILING FINISH FOR SUPPORT AND CAN NOT BE ROTATED OR DISPLACED. FIXTURES
AND DEVICES MOUNTED IN SUSPENDED ACOUSTICAL CEILING TILE SHALL HAVE CHANNEL SUPPORTS ACROSS
THE MAIN GRID RUNNERS OR GRID SUPPORTS SECURELY ANCHORED SO AS NOT TO CAUSE TILE TO SAG OR SO
FIXTURE OR DEVICE CAN NOT BE LIFTED, ROTATED OR DISPLACED.
ELECTRICAL LIGHT FIXTURES, MECHANICAL AIR DEVICES, FIRE SPRINKLERS, AND SMOKE DETECTORS IN CEILING:
ALL SUBS NEED TO TAKE OTHER DISCIPLINES INTO CONSIDERATION BEFORE STARTING THEIR WORK. ALL ITEMS
THAT NEED TO BE MOVED WILL BE MOVED AT THE SUB'S EXPENSE. FIRE SPRINKLERS MUST BE LOCATED A
MINIMUM OF 30 INCHES FROM ANY SURFACE MOUNTED LIGHT. SMOKE DETECTORS MUST BE MOUNTED NO
CLOSER THAN 3 FEET OF AN AIR DEVICE OR CEILING FAN. FIRE SPRINKLERS, LIGHT FIXTURES, SMOKE
DETECTORS, AND AIR DEVICES ALL TO BE CENTERED DOWN THE HALLWAYS. ELECTRICAL, MECHANICAL, FIRE
SPRINKLER, AND LOW VOLTAGE SUB CONTRACTOR MUST MEET AND DECIDE BEFORE ANYONE STARTS, WHERE
LOCATION OF THESE ITEMS WILL BE LOCATED. IF ITEM NEEDS TO BE MOVED, IT WILL BE AT THE EXPENSE OF THE
SUB CONTRACTOR. COORDINATE WITH ARCHITECT'S REFLECTED CEILING PLAN.
ALL OPENINGS IN FIRE AND/OR SMOKE RATED WALLS, FLOORS, AND PARTITIONS FOR CONDUITS SHALL BE
SEALED WITH RED FIRE RESISTANT FOAM OR PUTTY TO MAINTAIN THE FIRE AND/OR SMOKE RATING. ALL
OPENINGS IN FIRE RATED AND/OR SMOKE WALLS, FLOORS, AND PARTITIONS FOR CABLING SHALL BE SEALED
WITH WIREMOLD FLAMESTOPPER, STI EZ-PATH, HILTI SPEED SLEEVE OR EQUIVALENT.
REFER TO ARCHITECTURAL DRAWINGS FOR EXACT LOCATION OF LIGHT FIXTURES, DIMENSIONAL LOCATION OF
FIXTURES IN DRYWALL CEILING, ETC. LOCATION OF FLOOR BOXES AND RECEPTACLES, INCLUDING MOUNTING
HEIGHTS. ALL RECEPTACLES AND COVER PLATE COLORS SHALL BE APPROVED BY ARCHITECT
OWNER RESERVES THE RIGHT TO RELOCATE ANY LIGHT FIXTURE, RECEPTACLE, ETC., BEFORE BEING INSTALLED
10'-0'' FROM LOCATION AS SHOWN ON PLANS AT NO ADDITIONAL EXPENSE TO THE OWNER.
OUTLETS IN OFFICES SHALL HAVE THEIR WALL LOCATIONS COORDINATED WITH FINAL FURNITURE LAYOUT. GROUP
POWER AND COMMUNICATION OUTLETS SIDE BY SIDE AT SAME HEIGHT.
NO CONDUIT OR CABLES SHALL BE INSTALLED EXPOSED IN FINISHED AREA. NON-CEILING AREA CONDUITS SHALL
BE INSTALLED EXPOSED IN A NEAT WORKMAN LIKE MANNER AND BE PAINTED TO MATCH ADJACENT FINISHES.
ALL MATERIALS, DEVICES, FIXTURES, ETC., THAT ARE REQUIRED FOR THIS PROJECT ARE TO BE FURNISHED AND
INSTALLED BY THE EC, UNLESS SPECIFICALLY INDICATED TO BE FURNISHED AND OR INSTALLED BY OTHERS.
TELEPHONE, IT, AUDIO, VIDEO AND SECURITY CABLE WIRING WILL BE PROVIDED BY OWNERS VENDOR. EC SHALL
COORDINATE AND PROVIDE ALL ROUGH-IN'S AS REQUIRED. LOW VOLTAGE DEVICES HAVE BEEN SHOWN ON THE
PLANS FOR REFERENCE PURPOSES ONLY. ALL LOW VOLTAGE CABLING SHALL BE ROUTED IN CONDUIT FROM
DEVICE/JUNCTION BOX TO ABOVE AN ACCESSIBLE CEILING OR IN ATTIC SPACE; 1" EMT MINIMUM. EC SHALL
PROVIDE J-HOOKS AS REQUIRED, NO MORE THAN 60" O.C.
ALL SIGNAL AND CONTROL CABLES SHALL BE MINIMUM #18 STRANDED COPPER, UNLESS NOTED OTHERWISE. ALL
CONNECTIONS AND SPLICES TO BE MADE BY USE OF ''STA-KON'' CONNECTORS AND TERMINAL STRIPS.
TYPICAL SEISMIC DETAILS ARE PROVIDED ON THE DRAWINGS FOR REFERENCE ONLY. CONTRACTOR SHALL
PROVIDE SHOP DRAWINGS TO THE OWNER'S ENGINEER FOR REVIEW AND APPROVAL PRIOR TO SUBMITTAL TO
THE PLAN REVIEWER. SHOP DRAWINGS SHALL SHOW ALL EQUIPMENT ANCHORAGE TO WALLS/CEILINGS/FLOORS
AND SHALL INCLUDE SIZE OF SEISMIC ANCHOR BOLTS USED FOR EACH SYSTEM. CONTRACTOR SHALL PROVIDE
CALCULATIONS, DETAILS, ETC. - PREPARED BY, SIGNED AND SEALED BY A LICENSED STRUCTURAL ENGINEER.
REFER TO SPECIFICATIONS.
1,2,8,9
1
INTRUSION ALARM PANEL
KEY PAD
40.
41.
EMERGENCY OR STANDBY EQUIPMENT & SYSTEM
COMPONENTS;
EMERGENCY LIGHTING FIXTURES
EXIT SIGNS
38.
39.
FIRE PROTECTION, DETECTION & ALARM
EQUIPMENT & SYSTEM COMPONENTS;
FIRE ALARM WIRING
F DH
CR
LISTING OF EQUIPMENT &
SYSTEM COMPONENTS
VISUAL FLASHER - MOUNT 80" AFF TO BOTTOM OF FLASHER; (NUMERALS INDICATE CANDELA).
EXTERIOR FA BELL - MOUNT 90" AFF.
C
36.
37.
INTRUSION ALARM SYSTEM
The Seal and Signature apply only to the Document to
which they are Affixed, and Expressly Disclaim any
Responsibility for all other Plans, Specifications,
Estimates, Reports, or other Documents or Instruments
relating to or intended to be used for any part or parts of
the Architectural or Engineering Project.
Copyright © 2016 by SSC Engineering, Inc.
35.
FIRE ALARM POWER SUPPLY - MOUNTED 72" A.F.F.
HEAT DETECTOR - CEILING MOUNTED (U.N.O.).
MD
19.
MECHANICAL CONTRACTOR
TEMPERATURE CONTROL CONTRACTOR
H
K
18.
27.
TCC
DUCT MOUNTED SMOKE DETECTOR'S REMOTE ANNUNCIATOR LAMP AND TEST SWITCH-MOUNT ON CEILING,
(U.N.O.).
IAP
17.
26.
DRY-TYPE TRANSFORMER.
F A
F
16.
24.
25.
DUCT MOUNTED SMOKE DETECTOR WITH SAMPLING TUBES.
V
30
15.
MC
RAINTIGHT
SMOKE DETECTOR - CEILING MOUNTED.
F
13.
14.
29.
RT
SD
15
12.
MAXIMUM
EXISTING BRANCH CIRCUIT PANELBOARD.
MANUAL PULL STATION - MOUNT 46" AFF.
F
11.
MAX
PLUMBING CONTRACTOR
F
SD
10.
23.
DACT DIGITAL ALARM COMMUNICATOR TRANSMITTER
FAPS
8.
9.
28.
PC
FIRE ALARM ANNUNCIATOR PANEL - MOUNT TOP 72" AFF.
7.
GROUND FAULT CIRCUIT INTERRUPTER TYPE DEVICE, (U.N.O.)
GFI/GFCI
NEW BRANCH CIRCUIT PANELBOARD - MOUNT TOP 78" AFF.
FAAP
6.
22.
EWC
NOT TO SCALE
FIRE ALARM CONTROL PANEL - MOUNT TOP 72" AFF.
5.
21.
CABLE TELEVISION
NTS
FACP
3.
4.
AUTOMATIC TRANSFER SWITCH
ELECTRIC MOTOR.
FIRE ALARM SYSTEM
2.
20.
DIMMER SWITCH - AS ABOVE, 1000 WATT RATING OR 0-10V AS REQUIRED. MOUNT 46" A.F.F.
D
13.
THE OWNER INTENDS TO VACATE SPECIFIC AREAS OF WORK BEFORE DEMOLITION BEGINS. ALL OTHER AREAS SHALL
REMAIN OCCUPIED AND IN ACTIVE USE. UTILITIES AND SERVICES TO EXISTING ACTIVE AREAS SHALL NOT BE INTERRUPTED
WITHOUT THE OWNER'S APPROVAL AS TO THE TIME AND DURATION. THE OWNER WILL CONTINUE TO OCCUPY THE REST
OF THE EXISTING FACILITIES THROUGHOUT THE CONSTRUCTION OPERATIONS. THE ELECTRICAL CONTRACTOR SHALL SO
ORGANIZE HIS WORK AS TO CAUSE A MINIMUM OF UTILITY INTERRUPTIONS, WHICH SHALL BE SCHEDULED AT THE
CONVENIENCE OF THE OWNER.
ALL ELECTRICAL EQUIPMENT, LIGHTING FIXTURES, SWITCHES, RECEPTACLES, SPECIAL OUTLETS, ETC., WHICH ARE NOTED
TO BE DEMOLISHED, OR ARE SHOWN WITH DASHED LINE SYMBOLS ON THE DEMOLITION PLANS, SHALL BE REMOVED.
ASSOCIATED WIRING AND CONDUIT SHALL BE REMOVED BACK TO THE SOURCE OR EXISTING UPSTREAM DEVICE TO
REMAIN AND MADE SAFE.
REMOVE EQUIPMENT, FIXTURES, DEVICES AND OUTLETS AS SPECIFIED AND SHOWN ON DRAWINGS, AND AS MAY
BECOME NECESSARY BECAUSE OF EXISTING FIELD CONDITIONS. EXAMINE ALL EXISTING WALLS AND CEILING DESIGNATED
FOR REMOVAL TO DETERMINE THE CONDUIT AND WIRING THAT WILL REQUIRE REMOVAL.
FOR EXISTING ELECTRICAL DEVICES IN WALLS TO BE REMOVED, DISCONNECT POWER, REMOVE CONDUCTORS AND CAP
CONDUIT BELOW FLOOR OR ABOVE CEILING AS REQUIRED. DEVICES ARE TO BE REMOVED ALONG WITH WALL BY
GENERAL CONTRACTOR.
FOR EXISTING ELECTRICAL EQUIPMENT, FIXTURES AND DEVICES TO BE REMOVED FROM WALLS WHICH REMAIN,
DISCONNECT POWER, REMOVE CONDUCTORS, REMOVE THE ELECTRICAL ITEM, AND PATCH AND FINISH THE SURFACE AS
REQUIRED TO MATCH THE EXISTING, OR MAKE READY FOR NEW WALL FINISH. PROVIDE BLANK PLATES WHERE NOTED OR
REQUIRED.
EXISTING RECEPTACLES, DEVICES, ETC. TO REMAIN ARE DENOTED BY THIN SOLID LINE OR MAY NOT BE INDICATED AT ALL.
THESE DEVICES SHALL BE EXTENDED TO BE FLUSH WITH NEW FINISH ON EXISTING WALL WHERE REQUIRED.
MAINTAIN CIRCUIT CONTINUITY TO ALL EQUIPMENT, FIXTURES, DEVICES, ETC., TO REMAIN IN USE WHETHER NOTED ON THE
PLANS OR NOT. FIELD VERIFY EXISTING ITEMS TO REMAIN IN USE. WIRING FOR EXISTING CIRCUITS WHICH ARE PARTIALLY
ABANDONED SHALL BE RECONNECTED BY THE ELECTRICAL CONTRACTOR TO SERVICE THE REMAINING OUTLETS ON THE
CIRCUIT.
ALL WIRING FOR A CIRCUIT WHICH IS TO BE REMOVED SHALL BE REMOVED BACK TO THE PANEL WHICH SUPPLIED THE
CIRCUIT.
EXISTING CONDUIT & CONDUCTORS MAY BE REUSED WHERE FEASIBLE. ALL UNUSED CONDUIT MADE EMPTY BY THIS
DEMOLITION SHALL BE REMOVED BY THE ELECTRICAL CONTRACTOR. WHERE CONDUITS EXTENDING OUT OF THE FLOOR
ARE TO BE REMOVED, CUT THE CONDUIT OFF 1/2" BELOW THE FLOOR LINE AND PATCH.
ALL ACTIVE CIRCUITING THAT RUNS THROUGH THIS SPACE, ORIGINATING AND/OR TERMINATING IN OTHER SPACES, SHALL
REMAIN IN PLACE. COORDINATE WITH NEW CEILING WORK FOR RAISED CEILING WHICH MAY REQUIRE CIRCUITING
RELOCATION.
ALL UNUSED TELEPHONE AND DATA CABLES SHALL BE REMOVED. ANY OTHER UNUSED LOW VOLTAGE SYSTEMS CABLES
SHALL ALSO BE REMOVED.
ALL EXISTING EQUIPMENT, LIGHTING FIXTURES, WIRING DEVICES, AND MATERIALS TO BE REMOVED SHALL BECOME THE
PROPERTY OF THE CONTRACTOR AND SHALL BE REMOVED FROM THE PREMISES AND PROPERLY DISPOSED OF IN
ACCORDANCE WITH AUTHORITIES HAVING JURISDICTION, UNLESS OTHERWISE NOTED. ALL ITEMS NOTED THAT THE OWNER
CHOOSES TO KEEP SHALL BE TRANSFERRED TO THEIR STORAGE AREA BY THE ELECTRICAL CONTRACTOR.
FOR ALL EXISTING ELECTRICAL WIRING DEVICES, TELEPHONE, DATA ETC., CONTRACTOR SHALL REMOVE/REINSTALL
COVERPLATES AS REQUIRED TO ALLOW FOR NEW FINISHES.
INFORMATION ON THE EXISTING CONDITIONS PLANS ARE COMPILED FROM EXISTING DRAWINGS AND CASUAL FIELD
OBSERVATIONS AND SHALL BE CONSIDERED APPROXIMATE ONLY. VERIFICATION OF ALL EQUIPMENT, WIRING DEVICES
AND FIXTURES, EITHER SHOWN OR NOT SHOWN ON THESE PLANS, SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR.
NOTIFY ENGINEER IMMEDIATELY IF DISCREPANCIES EXIST.
X
X
X
X
X
X
X
3,8,9
1,4
5,6,7
IT IS THE BASIC INTENET OF THIS CODE BLOCK TO DECLARE WHETHER OR NOT ANCHORAGE AND SWAY BRACING IS REQUIRED ON THE PROJECT. IF SO, TO DECLARE WHETHER OR NOT THE DETAILS ARE SHOWN ON THE
PLANS OR WILL BE SHOWN ON A SUBSEQUENT SUBMISSION. IF SEISMIC RESTRAINT OF A COMPONENT IS NOT REQUIRED BY CODE THIS SHOULD BE STATED IN COMMENTS. IF SEISMIC RESTRAINT, WHICH IS NOT REQUIRED
BY CODE, IS BEING PROVIDED DUE TO OWNER/DESIGNER REQUIREMENTS THIS SHOULD ALSO BE STATED IN THE COMMENTS.
SHOP DRAWINGS NEED TO BE SUBMITTED TO THE COUNTY A MINIMUM OF TWO WEEKS PRIOR TO THE PLANNED INSTALLATION TO ALLOW FOR PLAN REVIEW AND DISTRIBUTION TO THE INSPECTOR. ADDITIONAL TIME
MAY BE NEEDED IF SUCH SUBMISSIONS ARE DEFICIENT.
VIDEO SURVEILLANCE CAMERA
A
DURESS/HOLD UP ALARM
CIRCUITRY DESIGNATIONS
BRANCH CIRCUITRY. CONCEALED IN WALLS OR ABOVE CEILINGS. ARROW INDICATES HOME RUN TO PANEL.
SHORT SLASH MARKS INDICATE "HOT" WIRES, LONG SLASH MARK INDICATES "NEUTRAL" WIRE, LONG SLASH
WITH SOLID CIRCLE INDICATES GREEN GROUNDING CONDUCTOR.
BRANCH CIRCUITRY AS ABOVE, CONCEALED IN FLOOR SLAB OR UNDERGROUND.
BRANCH CIRCUITRY AS ABOVE, EXPOSED ON WALLS OR STRUCTURE.
1. LIGHT FIXTURES LESS THAN 20 POUNDS POWERED WITH FLEXIBLE CABLE LESS THAN 3 FEET, FIXTURE SHALL BE MECHANICALLY ATTATCHED TO CEILING GRID.
2. PENDANT TYPE FIXTURES DO NOT REQUIRE SWAY BRACING WHEN IT CAN SWING AT AN ANGLE OF 45° FROM VERTICAL WITHOUT IMPACTING OTHER COMPONENTS.
3. TABLE 4.4, EXCEPTION FOR IP=1.0, WEIGHT LESS THAN 400 POUNDS.
4. TABLE 4.4, EXCEPTION FOR IP=1.0, WEIGHT LESS THAN 20 POUNDS.
5. TABLE 4.4, EXCEPTION FOR IP=1.0, WEIGHT 5LBS/FT OR LESS.
6. FLEXIBLE CONNECTION REQUIRED BETWEEN EQUIPMENT AND COMPONENTS IF INSTALLATION OTHER THAN MOUNTED TO WALLS AND FLOORS.
7. TABLE 4.4, ITEM 2, D, RIGID STEEL IMC CONDUIT < 1-1/2 INCHES IN DIAMETER, AND EMT OR ALUMINUM CONDUIT < 2 INCHES IN DIAMETER.
8. TYPICAL SEISMIC DETAILS ARE PROVIDED ON THE DRAWINGS FOR REFERENCE ONLY. SHOP DRAWINGS ARE REQUIRED.
9. CONTRACTOR SHALL PROVIDE SHOP DRAWINGS TO THE ENGINEER OF RECORD FOR REVIEW AND APPROVAL PRIOR TO SUBMITTAL TO THE PLAN REVIEWER.
10. ELECTRICAL EQUIPMENT AND COMPONENTS IN SEISMIC DESIGN CATEGORY 'C' WITH Ip = 1.0 ARE EXEMPT FROM SEISMIC RESTRAINTS PER ASCE-7,13.1.4.
CIRCUITRY UP - CIRCUITRY DOWN.
MISCELLANEOUS
SEISMIC RESTRAINTS FOR ELECTRICAL SYSTEM COMPONENTS
NO SCALE
XXX
X-X
MECHANICAL EQUIPMENT ITEM IDENTIFICATION PER EQUIPMENT SCHEDULE ON MECHANICAL DRAWINGS.
ELECTRICAL SHEET LIST
Sheet Number
E0.1
E0.2
E0.3
E1.1
E2.1
Sheet Name
ELECTRICAL SYMBOLS, ABBREVIATIONS & GENERAL NOTES
ELECTRICAL PANEL SCHEDULES
ELECTRICAL DETAILS
ELECTRICAL LIGHTING PLAN
ELECTRICAL POWER & SYSTEMS PLAN
MISSOURI
5017 Washington Place Suite 200
St. Louis, M0 63108
314.361.0000 ph
314.361.9191 fax
IOWA
1000 Melrose Avenue
Iowa City, IA 52246
319.343.7055 ph
hkwarchitects.com
18207 Edison Avenue
Chesterfield, M0 63005
636.530.7770 ph
636.530.7877 fax
Bid Set
LUMINAIRE - AS ABOVE - WALL MOUNTED 84" AFF (U.N.O).
GENERAL DEMOLITION NOTES:
912 Meramec Station Road, Valley Park, MO 63021
BB2
SPEAKER - CEILING MOUNTED.
S
PNC Valley Park
LUMINAIRE - CEILING MOUNTED. ALPHA-NUMERIC DESIGNATION DENOTES TYPE;
SEE LIGHTING FIXTURE SCHEDULE FOR DESCRIPTION.
PNC Bank
AA3
AUXILIARY SYSTEMS
Revision Schedule
No
SSC JOB# 2016123_BID SET - NOT FOR CONSTRUCTION
LIGHTING FIXTURES
Date
Description
April 11, 2016
16.008.00
ELECTRICAL
SYMBOLS,
ABBREVIATIONS
& GENERAL
NOTES
E0.1
Copyright 2016 HKW Architects
Branch Panel: 102B
Location: Elec/Data 105
Supply From:
Mounting: Surface
Enclosure: Type 1
Volts: 120/208 Wye
Phases: 3
Wires: 4
A.I.C. Rating:
Mains Type: MLO
Mains Rating: 225 A
MCB Rating:
Notes:
MISSOURI
5017 Washington Place Suite 200
St. Louis, M0 63108
314.361.0000 ph
314.361.9191 fax
CKT
NOTES
1
--2
2
2
2
2
2
2
2
3
3
3
3
3
3
3
3
3
3
CKT
A
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
Trip
Poles
RTU
35 A
3
------Vestibule, Lobby, and Concierge Lighting 20 A
1
Corridor, Janitor, Restrooms Lighting,...
20 A
1
Off-Stage, Offices, Break, and Cash...
20 A
1
Emergency Lighting
20 A
1
General Receptacles
20 A
1
Exterior PNC Sign
20 A
1
Receptacle - VESTIBULE
20 A
1
Receptacle - OFF STAGE
20 A
1
Receptacle - CONCIERGE
20 A
1
MDF Printer - CONCIERGE
20 A
1
RECEPTACLE - ICI PRINTER
20 A
1
Receptacle - TELLER/CONCIERGE
20 A
1
Receptacle - TELLER/CONCIERGE
20 A
1
Receptacle - TELLER/CONCIERGE
20 A
1
Receptacle - TELLER/CONCIERGE
20 A
1
Receptacle - CASH ROOM
20 A
1
Receptacle - CASH ROOM
20 A
1
Receptacle - CASH ROOM
20 A
1
Total Load:
Total Amps:
B
C
A
B
C
Circuit Description
3360 VA
1280 VA
3360 VA
1280 VA
3360 VA
894 VA
1280 VA
1900 VA
714 VA
400 VA
630 VA
501 VA
360 VA
500 VA
900 VA
1440 VA
200 VA
360 VA
900 VA
1740 VA
720 VA
1200 VA
720 VA
500 VA
1000 VA
720 VA
360 VA
180 VA
180 VA
360 VA
2500 VA
360 VA
180 VA
180 VA
360 VA
360 VA
2000 VA
2000 VA
360 VA
14835 VA
125 A
2100 VA
860 VA
13374 VA
111 A
0 VA
14350 VA
121 A
CKT
Poles
3
--1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
-1
1
Trip
40 A
--20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
25 A
-30 A
20 A
Circuit Description
RTU
--Receptacle TOILET/COUPON
Receptacle - EWC
Receptacle - IT
Receptacle for Diebold
Receptacle - OFFICE
Receptacle - OFFICE
Receptacle - BREAKROOM/JANITOR
Microwave - BREAKROOM Counter
Refrigerator - BREAKROOM
Receptacle - OFF STAGE & DISCOVER
MICR Printer - CONCIERGE Counter
Receptacle - CASH/SECURITY
IT RACK Receptacle
IT RACK Receptacle
EH-1
--
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
Water Heater
40
Spare
42
CKT
NOTES
1
--2
2
2
2
2
2
2
2
2
2
2
3
3,4
3,4
3,5
-3,5
3
IOWA
1000 Melrose Avenue
Iowa City, IA 52246
319.343.7055 ph
hkwarchitects.com
18207 Edison Avenue
Chesterfield, M0 63005
636.530.7770 ph
636.530.7877 fax
Legend:
Load Classification
Lighting
Power
Electric Heat
Other
Receptacle
Connected Load
2145 VA
180 VA
4000 VA
2900 VA
19420 VA
Demand Factor
100.00%
100.00%
100.00%
100.00%
75.75%
Estimated Demand
2145 VA
180 VA
4000 VA
2900 VA
14710 VA
Panel Totals
Total Conn. Load:
Total Est. Demand:
Total Conn. Current:
Total Est. Demand Current:
42565 VA
37855 VA
118 A
105 A
Notes:
ELECTRICAL PANELBOARD NOTES:
Bid Set
PNC Bank
NOTE: EXISTING PANEL SCHEDULE IS NOT LABELED WELL AND ASSUMPTIONS HAVE BEEN MADE FOR RE-USE OF
CIRCUITS. FIELD VERIFY ALL AVAILABLE CIRCUITS AFTER DEMOLITION AND MODIFY CIRCUITING AS REQUIRED.
NOTE CHANGES ON AS BUILT DRAWINGS.
912 Meramec Station Road, Valley Park, MO 63021
EXISTING LOAD TO REMAIN. FIELD VERIFY PANEL LABELING IS ACCURATE PRIOR TO WORK.
EXISTING LOAD TO BE REMOVED. FIELD VERIFY LOAD IS DEMOLISHED AND RE-USE CIRCUIT BREAKER.
NEW BREAKER IN EXISTING SPACE.
VERIFY WITH OWNER'S IT REP PRIOR TO ORDERING.
VERIFY SIZE WITH MC/PC PRIOR TO ORDERING.
PNC Valley Park
1.
2.
3.
4.
5.
Revision Schedule
SSC JOB# 2016123_BID SET - NOT FOR CONSTRUCTION
The Seal and Signature apply only to the Document to
which they are Affixed, and Expressly Disclaim any
Responsibility for all other Plans, Specifications,
Estimates, Reports, or other Documents or Instruments
relating to or intended to be used for any part or parts of
the Architectural or Engineering Project.
Copyright © 2016 by SSC Engineering, Inc.
No
Date
Description
April 11, 2016
16.008.00
ELECTRICAL
PANEL
SCHEDULES
E0.2
Copyright 2016 HKW Architects
MISSOURI
5017 Washington Place Suite 200
St. Louis, M0 63108
314.361.0000 ph
314.361.9191 fax
IOWA
1000 Melrose Avenue
Iowa City, IA 52246
319.343.7055 ph
hkwarchitects.com
18207 Edison Avenue
Chesterfield, M0 63005
636.530.7770 ph
636.530.7877 fax
EXPANSION ANCHOR
1/2"x1-1/4" HEX
HEAD CAP SCREWS
AND N225WO NUTS
5/8" BOLT
B-LINE, B22 CHANNEL
LONGITUDINAL OR
TRANSVERSE BRACE
(9'-4" MAX LENGTH)
NO SCALE
INNER NEOPRENE
BUSHING
TYPE "PB"
EQUIPMENT
SUPPORT LEG
SEISMIC
ANCHOR BOLT
TYPE "SAB"
STEEL WASHER
NEOPRENE
BUSHING
"TYPE Z"
CONCRETE
FLOOR
FIELD TRIM BUSHING
TO MATCH HOLE DEPTH
(2) SEISMIC
CABLE BRACES
PER CABLE
ANCHORED TO
STRUCTURE ABOVE
OUTER
STEEL SLEEVE
SWIVEL
CONNECTION
OVERSIZED HOLE
OUTSIDE
NEOPRENE
ELEMENT
SEISMIC ANCHOR
SLACK 1/8"
GAL. STEEL
AIRCRAFT CABLE
DESIGNER NOTES:
1. REFERENCE SPECIFICATION SECTION 260025, "SEISMIC
RESTRAINTS" ARTICLE FOR ADDITIONAL INFORMATION.
ELONGATED INNER
STEEL SLEEVE
DESIGNER NOTES:
1. THIS IS BASED ON MASON INDUSTRIES INC. TYPE "SCB" BRACE.
2. THIS IS BASED ON MASON INDUSTRIES INC. TYPE "SG" NEOPRENE
ISOLATOR.
The Seal and Signature apply only to the Document to
which they are Affixed, and Expressly Disclaim any
Responsibility for all other Plans, Specifications,
Estimates, Reports, or other Documents or Instruments
relating to or intended to be used for any part or parts of
the Architectural or Engineering Project.
Copyright © 2016 by SSC Engineering, Inc.
3. NORMALLY USED ON FLOOR MOUNTED EQUIPMENT WHICH
GENERATE IT'S OWN VIBRATION.
7
SEISMIC ISOLATOR TYPE "Z1"
NO SCALE
2. REFERENCE SPECIFICATIONS 260025, "VIBRATION AND SEISMIC
CONTROL" FOR ADDITIONAL INFORMATION.
DOES NOT
3. USE THIS DETAIL IN CONJUNCTION WITH TRAPEZE MOUNTED
SEISMIC SUPPORT.
6
SEISMIC SWAY BRACING CABLE ANCHOR
NO SCALE
GENERAL
FASTENED TO
STRUCTURE
ABOVE
MOUNT C-BAR LIGHT
FIXTURE SUPPORT
CHANNEL ON T-BAR
CEILING GRID
SUPPORT BY G.C.
BACK OF
STEEL PANEL
CONCRETE WALL MOUNTED EQUIPMENT SEISMIC
ANCHORAGE
MOUNT ADJUSTABLE
MOUNTING BRACKETS
TO LIGHT FIXTURE
AND C-CHANNEL
RECESSED
TROFFER
CONDUITS:
ADJUSTABLE
MOUNTING
BRACKET
T-BAR
CEILING
GRID
SHEET METAL
SCREWC-BAR
TO T-BAR PLUS
SAME ON DIAGONAL
INSERT #2 TAPPING SCREWS
THRU CLAMP AND TEE BAR
(2 PER CLAMP)
CADDY SFCLT SEISMIC
FIXTURE CLAMP WITH
SELF TAPPING SCREWS
ONE (1) AT EACH
CORNER (TYP. OF 4)
NOTES:
1. BASED ON MASON INDUSTRIES INC. TYPE "PB" NEOPRENE
BUSHING.
NO SCALE
SEISMIC SUPPORTED
TEE BAR CEILING
1. NO BRACING IS REQUIRED IF THE TOP OF THE CONDUIT IS SUSPENDED
12" OR LESS FROM THE SUPPORTING STRUCTURAL MEMBER.
2. ATTACHMENT TO STRUCTURAL MEMBERS SHALL USE DEVICES INCLUDED IN
FEDERAL SPECIFICATION WW--H-171 (MSS SP-58) OR BE BOLTED/WELDED
AS APPROVED BY THE ENGINEER. BRACES SHALL BE CONNECTED TO THE
HANGERS/SUPPORTS FOR CONDUIT.
3. SEE THE SPECIFICATIONS FOR REQUIRED STRENGTH OF BRACING.
4. LATERAL SEISMIC FORCE SHALL BE CONSIDERED TO ACT CONCURRENTLY
WITH THE DEAD LOAD. THE SLENDERNESS RATIO (l/r) OF BRACES SHALL
NOT EXCEED 200, WHERE (l) IS THE LENGTH OF THE BRACE AND (r) IS
THE LEAST RADIUS OF GYRATION, BOTH IN INCHES.
INSIDE NEOPRENE
ELEMENT
5
12GA. SLACK WIRE
OR PENCIL ROD
UP TO STRUCTURE
1. BRACE ALL 2" AND LARGER.
2. TRANSVERSE AND VERTICAL BRACING SHALL OCCUR AT 40' INTERVALS,
MAXIMUM. LONGITUDINAL BRACING SHALL OCCUR AT 80' INTERVALS,
MAXIMUM.
3. AT RISERS, WHEREVER POSSIBLE, SUPPORT THE WEIGHT OF THE RISER
AT A POINT OR POINTS ABOVE THE CENTER OF GRAVITY OF THE RISER.
STEEL DISK
No
4
NOTES FOR SEISMIC BRACING
NO SCALE
3
RECESSED MOUNTED FIXTURE SEISMIC SUPPORT
"SS3B"
NO SCALE
1
RECESSED MOUNTED FIXTURE SEISMIC SUPPORT
"SS4"
NO SCALE
SSC JOB# 2016123_BID SET - NOT FOR CONSTRUCTION
SEISMIC ANCHOR
BOLT
Revision Schedule
CEILING GRID
SUPPORT BY G.C.
SEISMIC ANCHOR AND
ANCHOR BOLT
Bid Set
ATTACHMENT - LATERAL BRACING TO MASONRY OR
CONCRETE
PNC Valley Park
2
PNC Bank
1
912 Meramec Station Road, Valley Park, MO 63021
1
Date
Description
April 11, 2016
16.008.00
ELECTRICAL
DETAILS
E0.3
Copyright 2016 HKW Architects
ELECTRICAL GENERAL NOTES:
1.
2.
3.
Lighting Fixture Schedule
Lamp Details
Lamp
Voltage Lamp Type
120V LED, 3500K INCLUDED
Type
Mark Manufacturer Catalog No.
A
CREE
KR6-13L-35K-120V-10V-RBH*-KR6TA &
KR6T-SSGC-WF
AE
B
BE
C
CE
D
CREE
CREE
CREE
KR6-13L-35K-120V-10V-EB7-RBH*-KR6TA &
KR6T-SSGC-WF
120V
CR22-32L-35K-10V
CR22-32L-35K-10V-EB14
120V
120V
COOPER
4SNLED-LD4-32HL-LN-UNV-L835-CD-1-U-AYC-CH
AIN/SET
COOPER 4SNLED-LD4-32HL-LN-UNV-EL14W-L835-CD-1-U-A
YC-CHAIN/SET
SLOAN LED 701269-WWLPY-MB & MULTIPLE POWER
SUPPLIES & ALL ACCESSOREIS
120V
LED, 3500K INCLUDED
LED, 3500K INCLUDED
LED, 3500K INCLUDED
LED, 3500K INCLUDED
Fixture
Finish
Mounting
RECESSED CLG WHITE
RECESSED CLG WHITE
LAY-IN CLG
LAY-IN CLG
SUSPENDED
WHITE
WHITE
WHITE
Remarks (Type) Description
GENERAL LTG 6" LED DOWNLIGHT WITH 1100 DELIVERED LUMENS, 0-10V DIMMING, SOFT SATIN
GLOW REFLECTOR AND WHITE FLANGE/TRIM; C CHANNEL MOUNTING
ACCESSORY.
GENERAL LTG 6" LED DOWNLIGHT WITH 1100 DELIVERED LUMENS, 0-10V DIMMING, SOFT SATIN
GLOW REFLECTOR AND WHITE FLANGE/TRIM, C-CHANNEL MOUNTING &
EMERGNECY BATTERY BALLAST.
GENERAL LTG 2' X 2' RECESSED LED FIXTURE WITH 3200 DELIVERED LUMENS.
GENERAL LTG 2' X 2' RECESSED LED FIXTURE WITH 3022 DELIVERED LUMENS AND 1400 LUMEN
EMERGENCY BATTERY BALLAST
JANITOR
4' LED STRIP LIGHT WITH 3200 LUMENS AND SEMI-FROST LENS.
120V
LED, 3500K INCLUDED
SUSPENDED
WHITE
IT/ELEC
120V
LED, 4200K INCLUDED
MECHANICAL
FASTNER
WHITE
COVE
X1
EELP
EDGU-1RC-BA-RC-EM-SD
120V
LED
INCLUDED
CEILING
-
-
X2
EELP
EDGU-2RW-BA-RC-EM-SD
120V
LED
INCLUDED
CEILING
-
-
5.
6.
102A
314.361.0000 ph
314.361.9191 fax
ELECTRICAL KEYED NOTES:
319.343.7055 ph
hkwarchitects.com
1
PROVIDE WATTSTOPPER PEANUT LIGHTING CONTROL PANEL #LP8S-8-115 WITH EIGHT RELAY'S,
ASTRONOMICAL TIME CLOCK AND LOW VOLTAGE INPUTS. EC SHALL PROGRAM ACCORDING TO
PNC'S REQUEST, ALL LIGHTS SHALL COME ON 1 HOUR PRIOR TO NORMAL BUSINESS HOURS AND
A ALL LIGHTS TO GO OFF 1 HOUR AFTER NORMAL BUSINESS HOURS (OR AS OTHERWISE
INDICATED BY PNC.)
2
PROVIDE LOW VOLTAGE SWITCH EQUAL TO WATTSTOPPER AS-102-W COMPATIBLE WITH
LIGHTING CONTROL PANEL. COORDINATE SWITCH FINISH WITH ARCHITECTURAL PLANS. SWITCH
SHALL HAVE 2 BUTTONS, TOP BUTTON SHALL TURN ON ALL LIGHTS CONNECTED TO
CONTROLLER, BOTTOM BUTTON SHALL TURN OFF ALL LIGHTS CONTROLLED BY CONTROLLER.
3
PROVIDE CONNECTION TO EXTERIOR SIGN; COORDINATE EXACT LOCATION AND REQUIREMENTS
WITH SIGN INSTALLER. CONNECT SIGN WITH DEDICATED CIRCUIT THRU LIGHTING CONTROLLER.
PROGRAM WITH ASTRONOMICAL CLOCK TO BE ON AT DUSK AND OFF AT DAWN.
4
MOUNT POWER SUPPLY TRANSFORMER ABOVE ACCESSIBLE CEILING.
5
PROVIDE LOW VOLTAGE SWITCH EQUAL TO WATTSTOPPER AS-102-W COMPATIBLE WITH
LIGHTING CONTROL PANEL. COORDINATE SWITCH FINISH WITH ARCHITECTURAL PLANS. SWITCH
SHALL HAVE 2 BUTTONS, TOP BUTTON SHALL TURN ON ALL EXTERIOR SIGN LIGHTS CONNECTED
TO CONTROLLER, BOTTOM BUTTON SHALL TURN OFF ALL EXTERIOR SIGN LIGHTS CONTROLLED
BY CONTROLLER. PROVIDE PERMANENT LABEL READING 'EXTERIOR SIGN LIGHT OVERRIDE'.
6
OCCUPANCY SENSOR SHALL ALSO CONTROL EXHAUST FAN IN ROOM.
7
COORDINATE ROUGH-IN LOCATION WITH T-STAT AND MC.
8
PROVIDE ROUGH-IN FOR ALL SPEAKERS AND VOLUME CONTROLS. PROVIDE WPW #2524WT OR
EQUAL #18G/2C TWISTED PLENUM CABLING FOR SPEAKERS. REVIEW EXACT ROUTING AND
CONNECTIONS WITH SPEAKER INSTALLER PRIOR TO WORK.
18207 Edison Avenue
Chesterfield, M0 63005
636.530.7770 ph
636.530.7877 fax
Concierge
102
AE
B
B
13NL
B
11j
B
11j
BE
11j
B
7LCa
13NL
B
7LCa
B
7LCa
V
13NL
MISSOURI
5017 Washington Place Suite 200
St. Louis, M0 63108
IOWA
1000 Melrose Avenue
Iowa City, IA 52246
CEILING MOUNTED SINGLE FACE LED EDGE LIT EXIT SIGN WITH WHITE HOUSING,
RED PANEL, BATTERY PACK, AND ARROWS AS INDICATED ON DRAWING.
CEILING MOUNTED DOUBLE FACE LED EDGE LIT EXIT SIGN WITH WHITE
HOUSING, RED PANEL, BATTERY PACK, AND ARROWS AS INDICATED ON
DRAWING.
AE
J
4.
4' LED STRIP LIGHT WITH 3200 LUMENS AND SEMI-FROST LENS AND 14W
EMERGENCY BATTERY BALLAST.
LED MODULES TO BE INSTALLED IN COVE; COORDINATE WITH ARCHITECTURAL
PLANS AND DETAILS. PROVIDE ONE 60W POWER SUPPLY PER 25' RUN OR AS
OTHERWISE REQUIRED BY MFR; PROVIDE ALL REQUIRED MOUNTING AND
CONNECTION ACCESSOREIS; MOUNT POWER SUPPLY ABOVE ACCESSIBALE
CEILING.
ATM Vestibule
100
REFER TO SHEET E0.1 FOR SYMBOLS, ABBREVIATIONS AND GENERAL CONSTRUCTION NOTES.
REFER TO THE ELECTRICAL DETAILS SHEET(S) FOR SEISMIC SUPPORTS OF LIGHTING FIXTURES.
SUSPENDED CEILING SYSTEMS ARE DESIGNED TO SUPPORT THE WEIGHT OF ALL LIGHTING
FIXTURES. THE STRUCTURAL FRAMING SHALL SUPPORT ALL CONDUITS, JUNCTION BOXES, ETC
ABOVE CEILINGS.
EMERGENCY LIGHTING THAT IS SHOWN TO BE SWITCHED, CONNECT EMERGENCY BALLAST
VOLTAGE SENSING LEAD AHEAD OF SWITCH LEG OR OTHER CONTROL DEVICE.
INFORMATION ON THIS SHEET IS COMPILED FROM EXISTING DRAWINGS AND CASUAL FIELD
OBSERVATIONS AND SHALL BE CONSIDERED APPROXIMATE ONLY. VERIFICATION OF ALL
EQUIPMENT AND FIXTURES, EITHER SHOWN OR NOT SHOWN ON THESE PLANS, SHALL BE THE
RESPONSIBILITY OF THE CONTRACTOR.
CONTRACTOR SHALL FIELD VERIFY EXISTING EQUIPMENT AND FIXTURES PRIOR TO STARTING
WORK. NOTIFY ENGINEER IMMEDIATELY IF DISCREPANCIES EXIST.
11j
13NL
11j
8
2
X1
B
7LCa
J
4
B
7LCa
BE
7LCa
A
B
A
7LCb
7LCb
7LCb
B
B
13NL
7LCa
BE
B
7LCa
B
13NL
7LCa
Lobby
119
13
X1
102B
BE
13NL
B
7LCb
B
BE
7LCb
7LCb
B
13NL
B
B
7LCb
D
D
LCP
9
CE
102B
OS
13NL
OS
X1
11
Office
117
S
11
Office
(TYP.) 116
V
B
V
B
11
8
S
13
11
S
11
ELECTRICAL LIGHTING PLAN - DEMOLITION
NORTH
13
OS
9
6
BE
6
BE
9
Revision Schedule
9
11
Self-Serve
Boxes
Coupon Booth Toilet
112
108
114
ELECTRICAL LIGHTING PLAN - RENOVATION
SCALE: 1/8" = 1'-0"
7LCa
No
Customer
Pantry
113
SCALE: 1/8" = 1'-0"
13NL
BE
B
7LCa
B
B
OS
8 (TYP.)
S
BE
7LCa
11
Office
115
B
B
13NL
B
V
11
Office
118
B
Elec/Data
105
V
B
1
LV
BE
11
BE
OS
D
OS
D
OS
B
The Seal and Signature apply only to the Document to
which they are Affixed, and Expressly Disclaim any
Responsibility for all other Plans, Specifications,
Estimates, Reports, or other Documents or Instruments
relating to or intended to be used for any part or parts of
the Architectural or Engineering Project.
Copyright © 2016 by SSC Engineering, Inc.
C
X2
OS
NORTH
5
13
7LCb
OS
J
11
Break Room
109
TS
7LCb
B
Maintenance
104
Janitor
107
B
11
13
B
13NL
7LCb
13
B
X1
7LCb
D
7
S
A
BE
7LCb
11i
13NL
LV
13NL
7LCb
S
A
(TYP.)
17
LCc
7LCb
Toilet
106
Bid Set
AE
7LCb
912 Meramec Station Road, Valley Park, MO 63021
AE
B
Off-Stage
103
PNC Valley Park
13
BE
A
PNC Bank
3
B
J
J
13NL
A
SSC JOB# 2016123_BID SET - NOT FOR CONSTRUCTION
13NL
X1
A
OS
A
i
11i
OS
AE
j
AE
Date
Description
April 11, 2016
16.008.00
ELECTRICAL
LIGHTING PLAN
E1.1
Copyright 2016 HKW Architects
ELECTRICAL KEYED NOTES:
ELECTRICAL GENERAL NOTES:
REFER TO SHEET E0.1 FOR SYMBOLS, ABBREVIATIONS AND GENERAL CONSTRUCTION NOTES.
ALL MECHANICAL, ELECTRICAL, PLUMBING, FIRE PROTECTION, AND HVAC WORK SHALL BE
COORDINATED BY THE CONTRACTOR DOING THE WORK. ANY CORRECTIONS TO ANY OF THE ABOVE
SHALL BE AT THE CONTRACTOR'S EXPENSE.
ALL DISCONNECTS REQUIRED SHALL BE PROVIDED BY THE EC, U.N.O. SEE MECHANICAL & PLUMBING
EQUIPMENT SCHEDULE(S) FOR EQUIPMENT DETAILS AND FOR DISCONNECTS FURNISHED BY OTHERS.
REFER TO MANUFACTURER'S SPECIFICATIONS FOR MECHANICAL & PLUMBING EQUIPMENT
CONNECTION DETAILS. COORDINATE WITH APPLICABLE TRADES.
PROVIDE EQUIPMENT GROUNDING CONDUCTOR IN ALL FEEDERS, SIZED IN ACCORDANCE WITH NEC
ARTICLE 250.122, SEE SPECIFICATIONS.
REFER TO ELECTRICAL DETAILS SHEET(S) FOR ADDITIONAL PHONE AND DATA REQUIREMENTS.
INFORMATION ON THIS SHEET IS COMPILED FROM EXISTING DRAWINGS AND CASUAL FIELD
OBSERVATIONS AND SHALL BE CONSIDERED APPROXIMATE ONLY. VERIFICATION OF ALL EQUIPMENT
AND DEVICES, EITHER SHOWN OR NOT SHOWN ON THESE PLANS, SHALL BE THE RESPONSIBILITY OF
THE CONTRACTOR.
CONTRACTOR SHALL FIELD VERIFY EXISTING EQUIPMENT AND DEVICES PRIOR TO STARTING WORK.
NOTIFY ENGINEER IMMEDIATELY IF DISCREPANCIES EXIST.
THE FIRE ALARM IS A BUILDING WIDE SYSTEM MAINTAINED BY LANDLORD. EC SHALL PERFORM
WORK AS INDICATED. BUT MUST COORDINATE ALL FA WORK WITH LANDLORD.
PRIOR TO ANY SAWCUTTING OF THE FLOOR SLAB, CONTRACTOR SHALL XRAY THE FLOOR TO AVOID
HITTING OTHER UTILITIES OR RE-BAR. COORDINATE EXACT ROUTE TO MINIMIZE DISTURBANCE TO
FLOOR SLAB. REVIEW AND COORDINATE ALL SAWCUTTING WITH LANDLORD PRIOR TO WORK
9.
21
TV
23
28
15
A
13
102A
15
35 33
F
31 29
27
19
20
26
6
TV
26
3
41
12
24 24
6
Lobby
119
10
F
+2 6 "
V
PROVIDE DEDICATED RECEPTACLE FOR DIEBOLD. COORDINATE EXACT REQUIREMENTS AND
LOCATION WITH DIEBOLD.
10
PROVIDE FLOOR BOX EQUAL TO LEGRAND RFB-2-OG WITH COVER; PREPARED WITH DUPLEX
RECEPTACLE AND DATA/VOICE OUTLET. SAW CUT FLOOR TO ACCESSIBLE WALL. PROVIDE
(1) 1" CONDUIT FOR POWER AND (2) 1-1/4" CONDUIT FOR LOW VOLTAGE, ROUTED TO
ACCESSIBLE WALL. PROVIDE BRONZE COVER FPBTCBZ. PATCH AND FILL AS REQUIRED.
XRAY FLOOR PRIOR TO SAWCUTTING.
11
PROVIDE (2) CIRCUITS AT EACH NEW TELLER POSITION. FIELD INSTALL TWO RECEPTACLES
AND TWO DATA J-BOXES AS SHOWN; COORDINATE EXACT LOCATIONS WITH TELLER STATION
INSTALLER PRIOR TO WORK.
12
SAW CUT FLOOR AND PROVIDE (1) 1" POWER FEED AND (2) 1-1/4" LOW VOLTAGE FEEDS PER
TELLER STATION STUBBED THROUGH WALL CAVITY, BELOW SLAB, AND STUBBED UP AT
TELLER CONCIERGE DESK. COORDINATE EXACT LOCATION WITH OWNER'S MILLWORK
PROVIDER PRIOR TO SAWCUTTING.
13
PROVIDE ROUGH-IN FOR SECURITY KEYPAD. KEYPAD TO BE PROVIDED BY OWNER'S
SECURITY CONTRACTOR.
14
DEDICATED RECEPTACLE FOR MFD PRINTER; COORDINATE ELEVATION WITH
ARCHITECTURAL PLANS.
15
DEDICATED RECEPTACLE FOR MICR PRINTER; COORDINATE ELEVATION WITH
ARCHITECTURAL PLANS.
16
EXISTING ELECTRICAL PANEL TO REMAIN. PANEL IS NOT CONNECTED TO AN ELECTRICAL
SERVICE; PANEL IS FOR LANDLORDS FUTURE USE ONLY.
17
PROVIDE CONNECTION TO UNIT HEATER; COORDINATE WITH MC.
18
PROVIDE 10" X 2" X 1/4" COPPER GROUND BUS FOR GROUNDING OF IT EQUIPMENT. PROVIDE
A #6AWG BARE COPPER CONDUCTOR FROM GROUND BUS TO INCOMING ELECTRICAL
EXISTING GROUNDING SYSTEM.
19
RELOCATE FIRE ALARM NOTIFICATION APPLIANCE. COORDINATE ALL WORK WITH
LANDLORDS FIRE ALARM VENDOR. EXTEND WIRING AS REQUIRED. REMOVE, PROTECT AND
RE-INSTALL AS SHOWN.
20
REMOVE DEVICE AND WIRING, MAINTAIN ROUGH-IN. RE-CIRCUIT AS INDICATED ON
RENOVATION PLAN.
21
DISCONNECT EXISTING WATER HEATER ABOVE CEILING; MAINTAIN CONDUIT; PROVIDE NEW #
10 AWG CONDUCTOR TO PANEL AND NEW BREAKER PER MFR. SPECS., AND CONNECT NEW
WATER HEATER.
22
CONTROL EF WITH LIGHTING OCCUPANCY SENSOR. SEE LIGHTING PLAN.
23
PROVIDE CONNECTION TO LINE VOLTAGE THERMOSTAT. COORDINATE EXACT
REQUIREMENTS WITH TCC & MC.
24
PROVIDE NEW DEVICE IN EXISTING ROUGH-IN; PROVIDE NEW WIRING AND WALL PLATE;
COORDINATE FINISH WITH ARCHITECTURAL PLANS.
25
COORDINATE ALL ROUGH-IN WORK ALONG PERIMETER WALLS WITH PNC SECURITY AND
WIRE MESH INSTALLER TO MAINTAIN SECURITY OF WIRE MESH BEING INSTALLED.
26
PROVIDE 4' X 4' FIRE RETARDANT PLYWOOD BACKER BOARD FOR SECURITY CONTRACTOR.
LOCATE 5 DUPLEX RECEPTACLES AT BACKER BOARD, COORDINATE EXACT LOCATION OF
RECEPTACLES WITH DIEBOLD PRIOR TO WORK.
27
PROVIDE DUPLEX AND LOW VOLTAGE ROUGH-IN FOR TV ABOVE ATM. ROUGH-IN SHALL BE
FROM BEHIND IN CASH ROOM; COORDINATE EXACT ROUGH-IN WITH ARCHITECTURAL
DETAILS. IT VENDOR TO PROVIDE DATA CABLES FOR TV AS REQUIRED.
28
PROVIDE DUPLEX AND LOW VOLTAGE ROUGH-IN FOR TV ABOVE TELLER COUNTER;
COORDINATE EXACT LOCATION AND ELEVATIONWITH ARCHITECTURAL DETAILS. IT VENDOR
TO PROVIDE DATA CABLES FOR TV AS REQUIRED.
29
PROVIDE ALTERNATE PRICING AS OUTLINED ON E0.1.
30
PROVIDE AND COORDINATE ROUGH-IN IN EXTERIOR WALL FOR EXTERIOR CAMERA.
24
21
+3 4 "
41
GFI
GFI
22
20
Break Room 23
109
2
DC
EF
8
25
3
12
Janitor+46"
107
20
T
102B
LCP
12
32
14
9
8
18
TGB
5
Elec/Data
105
102B 29
F
V
20
+46"
34
20
ABV CLG
16
16
16
J
GFI
GFI
18
Office
115
A
18
Office
116
A
18
Office
117
A
A
Office
118
16
GFI
GFI
Self-Serve
Boxes
114
Passage
111
+24"
GFI
10
Coupon Booth
112
Toilet
108
25
ELECTRICAL POWER & SYSTEMS PLAN - DEMOLITION
ELECTRICAL POWER & SYSTEMS PLAN - RENOVATION
SCALE: 1/8" = 1'-0"
SCALE: 1/8" = 1'-0"
NORTH
The Seal and Signature apply only to the Document to
which they are Affixed, and Expressly Disclaim any
Responsibility for all other Plans, Specifications,
Estimates, Reports, or other Documents or Instruments
relating to or intended to be used for any part or parts of
the Architectural or Engineering Project.
Copyright © 2016 by SSC Engineering, Inc.
NORTH
9
J
8
GFI
8
REQUIRED ELECTRICAL
CLEARANCE
EF
9
1
18
21
EF
2
Toilet
40
106
8
GFI
22
21
25
Revision Schedule
No
Date
Description
19
15
8
Customer
8 Pantry
113
636.530.7770 ph
636.530.7877 fax
Maintenance
104
26
13 12
15
9
18207 Edison Avenue
Chesterfield, M0 63005
21
21
+46"
19
PROVIDE TWO DEDICATED RECEPTACLES FOR IT RACK; ONE QUAD AND ONE DUPLEX.
COORDINATE LOCATION AND TYPE WITH PNC.
2
26
F
TV 41
20
8
Off-Stage
103
DC
15
DD
K
1
EXISTING FIRE ALARM DEVICE TO REMAIN. PROTECT DURING CONSTRUCTION.
FD
J
23
7
24
15
+67"
23
Concierge
102
11
4
30
23
GFI
F
+24"
15
14
T
DD
37
+67"
TV
36,38
FD
C
15
F
7
+24"
19
27
J
V
1
25
39
+67"
K
EH
20
23
EXISTING DUCT DETECTOR TO BE PROTECTED AND REMAIN. RE-ROUTE WIRING AS
REQUIRED TO ACCOMMODATE NEW WORK.
+24"
+67" J
Cash Room
101
J
16
20
15
26
319.343.7055 ph
hkwarchitects.com
6
15
V
+24" J
ATM Vestibule
100
17
28
IOWA
1000 Melrose Avenue
Iowa City, IA 52246
IT RACK AND CABLE TRAY BY PNC. COORDINATE WITH PNC DURING CONSTRUCTION TO
RESERVE ADEQUATE SPACE. PROVIDE #6 COPPER GROUND CONDUCTOR FROM CABLE
TRAY AND EACH IT RACK TO GROUND BAR.
5
FOR ATM; COORDINATE EXACT
LOCATIONS WITH ATM INSTALLER.
24
314.361.0000 ph
314.361.9191 fax
PROVIDE 3/4" CONDUIT TO ALARM PANEL. PROVIDE ADDITIONAL SEALTITE CONDUIT FROM
JUNCTION BOX TO SAFE.
4
EC SHALL PROVIDE ROUGH-IN'S FOR ALL DATA, VOICE, SOUND, SECURITY, ACCESS CONTROL AND
OTHER LOW VOLTAGE SYSTEMS. LOW VOLTAGE EQUIPMENT HAS BEEN SHOWN FOR REFERENCE
ONLY; COORDINATE EXACT REQUIREMENTS WITH RESPECTIVE TRADES. REFER TO SECURITAS
SECURITY DRAWING 'SEC-1' DATED 03/31/16 FOR MORE DETAILS REGARDING SECURITY ROUGH-IN
REQUIREMENTS. EC SHALL PROVIDE ALL ROUGH-INS; ALL CABLING (OTHER THAN SPEAKER WIRING)
WILL BE FURNISHED BY OTHERS. COORDINATE PRIOR TO CEILING AND DRYWALL BEING INSTALLED.
30
MISSOURI
5017 Washington Place Suite 200
St. Louis, M0 63108
Bid Set
8.
3
PROVIDE DUPLEX AND LOW VOLTAGE ROUGH-IN FOR TWO TV'S; TV'S ARE STACKED
VERTICALLY AND OFFSET HORIZONTALLY; REFER TO ARCHITECTURAL DETAILS FOR MORE
INFORMATION. IT VENDOR TO PROVIDE DATA CABLES FOR TV AS REQUIRED.
912 Meramec Station Road, Valley Park, MO 63021
7.
PROVIDE LOW VOLTAGE TRANSFORMER FOR DOOR BELL CHIME SYSTEM AND MOUNT
ABOVE ACCESSIBLE CEILING.
PNC Valley Park
5.
6.
2
PNC Bank
4.
CONNECT DOOR CHIME TO BUTTON AT REMOTE ENTRY. PROVIDE NUTONE HARDWIRED
DOOR CHIME KIT MODEL BK125WH OR APPROVED EQUAL, (2) DOOR CHIMES, (2)
TRANSFORMERS AND LOW VOLTAGE WIRING PER MANUFACTURER'S RECOMMENDATION TO
OPERATE BOTH CHIMES FROM A SINGLE BUTTON.
9
22
SSC JOB# 2016123_BID SET - NOT FOR CONSTRUCTION
3.
1
+46"
1.
2.
April 11, 2016
16.008.00
ELECTRICAL
POWER &
SYSTEMS
PLAN
E2.1
Copyright 2016 HKW Architects
FIRE PROTECTION BRANCH LINE
FIRE PROTECTION SYMBOLS LEGEND
ANCHORAGE & SWAY BRACING - MECHANICAL SYSTEM COMPONENTS
CONNECTION OF NEW TO EXISTING
Occupancy Category ( II )
RETURN BEND
CONNECTED TO
TOP OF BRANCH
LINE PIPING, TYP.
RETURN
BEND
Seismic Design Category ( D )
ANCHORAGE TO
FLOORS,
ROOFS, ETC.
LISTING OF
EQUIPMENT AND
SYSTEM COMPONENTS
Not Provided
PIPING
SWAY BRACING
Provided
-
LOCATION OF PROFESSIONALLY SEALED
ANCHORAGE
AND SWAY BRACING DETAILS
Not Provided Provided
X
-
Drawing No. or
Spec. Section
X
Shop Drawings
-
BY FPC
COMMENTS
Separate
Permit & Plans
BRACE PIPING
AS REQUIRED IN
NFPA 13 & 14
-
VIBRATION ISOLATION AND SEISMIC RESTRAINT SCHEDULE
PENDENT
SPRINKLER
HEAD
AFF
ABOVE FINISHED FLOOR
BOP
BOTTOM OF PIPE
BRZ
BRONZE
EC
ELECTRICAL CONTRACTOR
ECV
EXTENDED COVERAGE
FPC
FIRE PROTECTION CONTRACTOR
GRVD
GROOVED
HSW
HORIZONTAL SIDEWALL
PC
PND
PENDENT
AMPLIFICATION
FACTOR
QR
QUICK RESPONSE
STND
STANDARD
1.0
THR
THREADED
UPR
UPRIGHT
SPR
SPRINKLER PIPING
EQUIPMENT
TAG
ISOLATION
SPEC.
SEISMIC
RESTRAINT
ISOLATOR
DEFLECTION
IMPORTANCE
FACTOR
SPR-PIPING
SC
YES
-
1.5
2.5
1.
SEE THIS SHEET FOR SYMBOLS AND ABBREVIATIONS.
2.
THESE GENERAL DEMOLITION NOTES APPLY TO ALL DEMOLITION WORK.
3.
DEMOLISH PIPING AND EQUIPMENT SHOWN CROSS HATCHED.
4.
THESE DRAWINGS MAY NOT FULLY DEPICT ALL AS-BUILT CONDITIONS, CONTRACTOR SHALL
FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO SUBMITTING BIDS. NOTIFY THE ENGINEER AT
ONCE SHOULD A DISCREPANCY OR OMISSION BE FOUND.
5.
CONTRACTOR SHALL USE CAUTION WHEN REMOVING PIPING AND EQUIPMENT TO AVOID DAMAGE
TO ELECTRICAL WIRING THAT IS TO REMAIN. NOTIFY GC AND EC IF WIRING IS FOUND ATTACHED
TO PIPING.
6.
PLUMBING CONTRACTOR
COMPONENT
RESPONSE
MODIFICATION
FACTOR
FIRE PROTECTION GENERAL DEMOLITION NOTES:
7.
EXISTING SPRINKLER HEAD
9.
SPRINKLER DEMOLITION WORK: VERIFY EXISTING SERVICES TO REMAIN. ALL NECESSARY CARE
SHALL BE TAKEN DURING DEMOLITION TO PREVENT DAMAGE TO FIRE PROTECTION, PLUMBING,
ELECTRICAL, AND MECHANICAL SYSTEMS TO REMAIN. FIRE PROTECTION SYSTEMS SERVING
OTHER AREAS SHALL PROVIDE FOR UNINTERRUPTED SERVICE TO THOSE AREAS UNLESS PRIOR
WRITTEN APPROVAL IS RECEIVED FROM THE OWNER. COORDINATE ALL SUCH WORK WITH THE
GENERAL CONTRACTOR AND OWNER'S ON SITE REPRESENTATIVE.
FIRE PROTECTION GENERAL RENOVATION NOTES:
NOT TO SCALE
1.
THESE DRAWINGS ARE ACCOMPANIED BY SPECIFICATIONS.
2.
THIS CONTRACTOR SHALL COORDINATE WITH OTHER CONTRACTORS IN THE LOCATION OF ALL
PIPING AND EQUIPMENT TO PREVENT INTERFERENCE.
3.
PROVIDE ALL NECESSARY OFFSETS IN PIPING TO AVOID STRUCTURE.
4.
IN SPACES WITHOUT CEILINGS PROVIDE ROUGH BRONZE UPRIGHT SPRINKLER HEADS. IN SPACES
WITH CEILINGS, REFER TO SPECIFICATIONS FOR SPRINKLER HEAD TYPES. IN DRYWALL CEILINGS,
SPRINKLER HEADS SHALL ALIGN WITH LIGHT FIXTURES AND OTHER CEILING MOUNTED DEVICES.
CONTRACTOR SHALL COORDINATE SPRINKLER HEAD LOCATIONS WITH ARCHITECT'S REFLECTED
CEILING PLAN, AND PROVIDE ADDITIONAL SPRINKLER HEADS WHERE REQUESTED BY ARCHITECT.
4'-0"
1'-0"
1'-0"
LARGE
WASHER
1'-0"
BOTTOM
CHORD OF
JOIST
LOCK NUT
RETAINING
CLIP
1'-0"
1'-0"
1
2'-0"
"C" CLAMP
1'-0"
LARGE
WASHER
4
BOTTOM CHORD
OF JOIST
LOCK NUT
LOCK NUT
5
PROVIDE A SUPPORT ANGLE SPANNING TWO OR MORE JOISTS;
3x3x1/4" SUPPORT ANGLE WHERE JOIST SPACING IS OVER 2'-0"
BUT NOT MORE THAN 4'-0". PROVIDE 2x2x1/4" SUPPORT ANGLE
WHERE JOIST SPACING IS 2'-0" AND UNDER. WHERE LOAD EXCEEDS
500 POUNDS PER HANGER, SEE STRUCTURAL DRAWINGS FOR DETAILING.
2
FIELD WELD STIFFENER TO BAR JOIST TOP AND BOTTOM CHORD.
3
PROVIDE STIFFENER ANGLE WHERE LOAD BEING HUNG EXCEEDS 250 LBS.
4
THIS METHOD ALLOWABLE FOR MAX. 150 LB. LOAD WITHIN 6" OF PANEL
POINT; BEYOND 6" OF PANEL POINT 50 LB. MAX. LOAD ALLOWABLE.
5.
PRIOR TO COMMENCING WORK, APPROVAL SHALL BE RECEIVED FROM THE OWNERS INSURANCE
COMPANY, ENGINEER, FIRE MARSHAL AND OWNER.
5
THIS METHOD ALLOWABLE FOR MAX. 50 LB. LOAD WITHIN 6" OF PANEL
POINT; BEYOND 6" OF PANEL POINT THIS METHOD IS NOT ALLOWED.
6.
UPON COMPLETION, THIS CONTRACTOR SHALL PROVIDE A COMPLETE AND FUNCTIONING SYSTEM.
7.
PROVIDE SEISMIC BRACING AS REQUIRED FOR NEW PIPING.
8.
FIRE PROTECTION CONTRACTOR SHALL PERFORM A FLOW TEST. FLOW TEST RESULTS INCLUDING
DATE OF TEST, LOCATION OF TEST HYDRANT, LOCATION OF FLOW HYDRANT, STATIC PRESSURE,
RESIDUAL PRESSURE AND TEST FLOW GPM SHALL BE SUBMITTED WITH HYDRAULIC
CALCULATIONS.
9.
THE FIRE PROTECTION CONTRACTOR SHALL SUBMIT HYDRAULIC CALCULATIONS AND SHOP
DRAWINGS SIGNED AND SEALED BY A FIRE PROTECTION ENGINEER REGISTERED IN THE STATE
WHERE THE PROJECT IS LOCATED.
HANGER ROD
SPRINKLER HEAD
HANGER ROD
2'-0"
1/2"Ø BOLT
1 SUPPORT ANGLE
1'-0"
A
1'-0"
THIS DETAIL
1-1/2x1-1/2x3/16"
STIFFENER 3
LARGE WASHER
BOTTOM CHORD
OF JOIST
PANEL POINT
1'-0"
LOCK NUT
LOCK NUT
LOCK NUT
319.343.7055 ph
hkwarchitects.com
18207 Edison Avenue
Chesterfield, M0 63005
636.530.7770 ph
636.530.7877 fax
10. THE OWNER WILL BE RESPONSIBLE FOR THE REMOVAL OF ANY ACMs (ASBESTOS CONTAINING
MATERIALS, PCBs OR OTHER HAZARDOUS MATERIALS) PRESENTLY EXISTING WITHIN THE
AREAS AFFECTED BY THE PROJECT SCOPE, THAT WOULD BE REQUIRED TO BE REMOVED FOR
THE WORK. ABATEMENT WORK, IF REQUIRED, IS NOT PART OF THIS CONTRACT.
RETURN BEND PIPING TO WET AND DRY PENDENTS
LOCK NUT
IOWA
1000 Melrose Avenue
Iowa City, IA 52246
WHERE ITEMS ARE REMOVED, UTILITIES AND THE AREA FROM WHICH THE ITEMS HAVE BEEN
REMOVED SHALL BE LEFT IN SUCH A MANNER THAT IS SAFE FOR BOTH PEOPLE AND PROPERTY
ON A DAILY BASIS.
SEE ARCHITECTURAL DRAWINGS FOR ARCHITECTURAL DEMOLITION. REFER TO MEP AND
SPRINKLER DEMOLITION PLANS FOR MEP DEMOLITION.
UPRIGHT SPRINKLER HEAD
DRY PENDENT SPRINKLER HEAD NOTE:
DRY BARREL SHALL BE PROVIDED FOR THE ENTIRE LENGTH OF THE DROP PIPING
FROM THE SPRINKLER HEAD TO THE ELBOW AT THE TOP OF THE RETURN BEND.
DRY PENDENTS SHALL NOT INCLUDE A DRAIN OUTLET IN DROP PIPING.
314.361.0000 ph
314.361.9191 fax
WHEREVER EXISTING EQUIPMENT, PIPING AND EQUIPMENT, ETC., ARE TO BE REMOVED, SUCH
REMOVAL SHALL INCLUDE ALL ANCHORS, HANGERS, FOUNDATIONS, ETC., UNLESS NOTED
OTHERWISE. AFTER REMOVAL; FLOORS, WALLS AND CEILINGS SHALL BE PATCHED AND
FINISHED TO MATCH ADJOINING SURFACES.
8.
PENDENT SPRINKLER HEAD
MISSOURI
5017 Washington Place Suite 200
St. Louis, M0 63108
2'-0"
10. CONTRACTOR SHALL PROVIDE ALL DOCUMENTATION AS REQUIRED BY THE AUTHORITY HAVING
JURISDICTION TO DEMONSTRATE COMPLIANCE WITH NFPA 13.
1'-0"
HANGER ROD
11. PIPING SHALL BE INSTALLED AS HIGH AS POSSIBLE.
2
HANGER ROD
BOTTOM CHORD
OF JOIST
LARGE WASHER
LOCK NUT
SPRINKLER HEAD
6"
NOTE:
ALL PENETRATIONS OF SPRINKLER HEADS IN AN ACCOUSTICAL CEILING
PANEL SHALL BE CENTERED.
1/2"Ø BOLT
6"
B
A
THIS DETAIL
THIS DETAIL
CEILING PANEL PENETRATION DETAIL
TYPICAL JOIST HANGER DETAIL FOR PIPING AND EQUIPMENT
NOT TO SCALE
NOT TO SCALE
1 SUPPORT ANGLE
SECTION
B
13. WHERE PIPING ELEVATION CONFLICTS WITH DUCTWORK, OFFSETS TO FIRE PROTECTION PIPING
SHALL BE UP AND OVER DUCTWORK. WHERE CONFLICTS OCCUR, PIPING SHALL NOT BE ROUTED
DOWN BELOW DUCTWORK WHERE THIS PIPING WOULD BE WITHIN 12" OF CEILING ELEVATION.
14. PROVIDE AUXILIARY DRAINS AS REQUIRED FOR DRAINING TRAPPED SECTIONS OF PIPING. FOR
TRAPPED SECTIONS OF PIPING EXCEEDING 5 GALLONS IN CAPACITY, PROVIDE A HARD-PIPED DRAIN
CONNECTION AND ROUTE BACK TO DRAIN IN SPRINKLER RISER ROOM.
SECTION
THIS DETAIL
N.T.S.
12. PIPING SHALL BE ROUTED A MINIMUM OF 12" ABOVE CEILING.
N.T.S.
15. PIPE ROUTING SHOWN ON DRAWINGS IS FOR REFERENCE ONLY. FIRE PROTECTION CONTRACTOR
SHALL COORDINATE WITH STRUCTURAL DRAWINGS, ELECTRICAL AND MECHANICAL DRAWINGS
FOR LOCATIONS AND ELEVATIONS OF PIPING. NO CHANGE TO THE CONTRACT PRICE WILL BE
ACCEPTED WHERE ALTERNATE PIPING ROUTES ARE REQUIRED.
16. CONTRACTOR SHALL PROVIDE A FIRE WATCH DURING CONSTRUCTION HOURS. COORDINATE WITH
LOCAL FIRE DEPARTMENT FIRE WATCH REQUIREMENTS. OBTAIN A FIRE WATCH INSPECTION
FORM AND LOG INSPECTION TIME PER FIRE DEPARTMENT'S REQUIREMENTS.
THREADED HANGER ROD
TOP CHORD OF JOIST,
TYP. 2 MEMBERS
BRACE PIPE
TOLCO FIGURE 907
SWAY BRACE
ATTACHMENT
NO-THREAD
SWIVEL SWAY
BRACE
ATTACHMENT
PIPE CLAMP FOR
SWAY BRACE
CONCENTRICALLY LOADED BAR JOIST - TOP CHORD
3" MAX
THREADED HANGER ROD
NUT
WASHER
4 WAY EARTHQUAKE BRACE
NO SCALE
LONGITUDINAL EARTHQUAKE BRACE
NO SCALE
Revision Schedule
MIN. 45°-90° TYPICAL
CONCENTRICALLY LOADED BAR JOIST - BOTTOM CHORD
MIN. 45°-90° TYPICAL
SWAY BRACE
ATTACHMENT
CONCENTRICALLY LOADED JOIST ATTACHMENT DETAIL
NOT TO SCALE
BRACE PIPE
SWIVEL
SWAY
BRACE
FITTING
SWIVEL
SWAY
BRACE
FITTING (2)
SWAY BRACE
ATTACHMENT (2)
TYPICAL BAR JOIST AND BEAM HANGER ATTACHMENT NOTES:
1. ADDITIONAL HANGERS SHALL BE REQUIRED TO LIMIT THE LOAD ON EACH STRUCTURAL
MEMBER BELOW THE MAXIMUM LOAD ALLOWED. COORDINATE WITH STRUCTURAL ENGINEER
OF RECORD TO PREVENT OVERLOADING.
The Seal and Signature apply only to the Document to
which they are Affixed, and Expressly Disclaim any
Responsibility for all other Plans, Specifications,
Estimates, Reports, or other Documents or Instruments
relating to or intended to be used for any part or parts of
the Architectural or Engineering Project.
Copyright © 2016 by SSC Engineering, Inc.
2. WHEN MULTIPLE PIPES/DUCTWORK ARE PERPENDICULAR TO JOISTS, HANGERS SHALL BE
STAGGERED SO THAT PIPING/DUCTWORK IS NOT SUPPORTED FROM A SINGLE JOIST.
LATERAL EARTHQUAKE BRACE
NO SCALE
FAST CLAMP RISER BRACE
NO SCALE
GENERAL:
PIPING:
1. NO BRACING IS REQUIRED IF THE TOP OF PIPING IS SUSPENDED 12" OR LESS FROM THE
SUPPORTING STRUCTURAL MEMBER.
1. BRACE ALL PIPES 2-1/2"Ø AND LARGER. IN MECHANICAL ROOMS, BRACE ALL
PIPING 1-1/4"Ø AND LARGER.
3. HANGERS AND SUPPORT COMPONENTS SHALL BE FACTORY FABRICATED OF MATERIALS,
DESIGN, AND MANUFACTURER COMPLYING WITH MSS SP-58 AND MSS SP-69 AND
SPECIFICATION 15010. 210010, 220010 OR 230010. COMPLY WITH LOAD RATINGS FOR EACH
TYPE.
2. WALLS, INCLUDING DRYWALL PARTITIONS, MAY REPLACE REQUIRED TRANSVERSE OR
VERTICAL BRACING FOR PIPING.
2. TRANSVERSE AND VERTICAL BRACING SHALL OCCUR AT 40' INTERVALS,
MAXIMUM. LONGITUDINAL BRACING SHALL OCCUR AT 80' INTERVALS, MAXIMUM.
4. BEAM CLAMPS SHALL COMPLY WITH MSS TYPE 19-23, 25, 27-34. TYPE 19 AND 23 C-CLAMPS
SHALL HAVE LOCKNUTS AND RETAINING DEVICES, FURNISHED BY THE MANUFACTURER.
3. ATTACHMENT TO STRUCTURAL MEMBERS SHALL USE DEVICES INCLUDED IN FEDERAL
SPECIFICATION WW--H-171 (MSS SP-58) OR BE BOLTED/WELDED AS APPROVED BY THE
ENGINEER. BRACES SHALL BE CONNECTED TO THE HANGERS/SUPPORTS FOR PIPING
AND SUSPENDED EQUIPMENT.
3. AT PIPE RISERS, WHEREVER POSSIBLE, SUPPORT THE WEIGHT OF THE RISER
AT A POINT OR POINTS ABOVE THE CENTER OF GRAVITY OF THE RISER.
5. FOR BUILDINGS WITH JOISTS MADE BEFORE 1985, ALL CLAMPS SHALL BE ATTACHED TO THE
UPPER CHORD OF JOISTS.
6. PROVIDE BEAM CLAMPS WITH RETAINING CLIPS FOR INSTALLATIONS WHERE SEISMIC
BRACING IS REQUIRED.
7. HANGERS THAT ARE PART OF A SEISMIC RESTRAINT SHALL BE INSTALLED IN CONTACT WITH
THE PIPE.
8. SUPPORT ANGLES AND STIFFENERS TO BE SUPPLIED AND INSTALLED BY CONTRACTOR.
4. SEE THE SPECIFICATIONS FOR REQUIRED STRENGTH OF BRACING.
5. LATERAL SEISMIC FORCE SHALL BE CONSIDERED TO ACT CONCURRENTLY WITH THE
DEAD LOAD. THE SLENDERNESS RATIO (l/r) OF BRACES SHALL NOT EXCEED 200, WHERE
(l) IS THE LENGTH OF THE BRACE AND (r) IS THE LEAST RADIUS OF GYRATION, BOTH IN
INCHES.
6. SWAY BRACING METHODS SHOWN IN NFPA 13 (SPRINKLER PIPING) MAY BE USED IN LIEU
OF DETAILS SHOWN ON THE DRAWINGS FOR PIPING.
7. BRACE ALL FIRE SUPPRESSION PIPING.
4. DO NOT FASTEN ON RIGID PIPING SYSTEM TO TWO DISSIMILAR PARTS OF
THE BUILDING THAT MAY RESPOND IN A DIFFERENT MODE DURING AN
EARTHQUAKE; FOR EXAMPLE, A WALL AND A ROOF.
5. DO NOT USE BRANCH LINES TO BRACE MAIN LINES.
EQUIPMENT:
1. PROVIDE VIBRATION ISOLATORS & SWAY BRACING FOR ALL SUSPENDED
EQUIPMENT.
2. PROVIDE NEOPRENE WASHER AND PAD FOR ALL PUMPS ANCHORED TO
CONCRETE PADS.
KEYED NOTES:
1
TYPICAL BAR JOIST & BEAM HANGER NOTES
SEISMIC BRACING DETAILS AND NOTES
NOT TO SCALE
NOT TO SCALE
ATTACH TO CONCRETE DECK OR STRUCTURAL MEMBERS VIA
APPROVED ATTACHMENT METHOD, ATTACHMENT TO METAL ROOF
DECK IS PROHIBITED.
FIRE PROTECTION SHEET LIST
Sheet Number
Sheet Name
FP0.1
FIRE PROTECTION NOTES & DETAILS
FP1.1
FIRE PROTECTION PLAN
SSC JOB# 2016123_BID SET - NOT FOR CONSTRUCTION
No
BOTTOM CHORD OF JOIST,
TYP. 2 MEMBERS
Bid Set
SWIVEL
SWAY
BRACE
FITTING
FIRE PROTECTION SYSTEM DELEGATED-DESIGN NOTE:
THE FIRE PROTECTION CONTRACTOR SHALL BE RESPONSIBLE FOR DESIGNING AND
PROVIDING AN AUTOMATIC SPRINKLER SYSTEM BASED ON NFPA 13 REQUIREMENTS, THE
AVAILABLE WATER FLOW AND PRESSURE AT THE SITE, AND IBC REQUIREMENTS FOR A
FULLY SPRINKLERED BUILDING. ALL OCCUPIED AREAS SHALL BE SERVED BY WET-PIPE
AUTOMATIC FIRE PROTECTION SYSTEMS. CONTRACTOR SHALL DESIGN ALL PIPE ROUTING,
COORDINATE WITH STRUCTURAL ELEMENTS AND DETERMINE SPRINKLER HEAD
LOCATIONS AND QUANTITIES REQUIRED. SPRINKLER HEAD LOCATIONS AND PIPING
ROUTING ARE SHOWN FOR REFERENCE ONLY, AS AN AID TO BIDDING AND ARCHITECTURAL
COORDINATION. THE FIRE PROTECTION CONTRACTOR SHALL BE RESPONSIBLE FOR
PERFORMING A FLOW TEST, PROVIDING ENGINEERED SHOP DRAWINGS AND HYDRAULIC
CALCULATIONS SIGNED AND SEALED BY A REGISTERED PROFESSIONAL ENGINEER IN THE
STATE WHERE THE PROJECT IS LOCATED, AND DESIGNING, SIZING AND INSTALLING ALL
PIPING, VALVES, SPRINKLERS, ETC. REQUIRED FOR A COMPLETE, FUNCTIONAL AND CODE
COMPLIANT SYSTEM.
912 Meramec Station Road, Valley Park, MO 63021
MIN. 45°-90° TYPICAL
1
PNC Bank
MIN. 45°-90°
TYPICAL
WASHER
PNC Valley Park
NUT
Date
Description
April 11, 2016
16.008.00
FIRE
PROTECTION
NOTES &
DETAILS
FP0.1
Copyright 2016 HKW Architects
FIRE PROTECTION GENERAL NOTES:
1. REFER TO SHEET FP0.1 FOR SYMBOLS, ABBREVIATIONS AND GENERAL CONSTRUCTION NOTES.
2. ADJACENT TENANT SPACE NOT IN SCOPE.
3. ITEMS SHOWN CROSS HATCHED TO BE REMOVED.
MISSOURI
5017 Washington Place Suite 200
St. Louis, M0 63108
FIRE PROTECTION KEYED NOTES:
314.361.0000 ph
314.361.9191 fax
1
REMOVE SPRINKLER HEADS AND BRANCH PIPING BACK TO MAIN.
2
REMOVE EXISTING SPRINKLER HEAD WITHIN SPACE AND PLUG OUTLET. BRANCH PIPING TO
REMAIN TO SERVE ADJACENT TENANT SPACE.
IOWA
1000 Melrose Avenue
Iowa City, IA 52246
3
EXISTING 2 1/2" CROSS-MAIN AT APPROXIMATELY 14'-2" AFF TO REMAIN.
4
PROVIDE THE DESIGN AND INSTALLATION OF A COMPLETE AND FUNCTIONAL AUTOMATIC FIRE
PROTECTION SYSTEM IN THE AREA INDICATED. FIRE PROTECTION SYSTEM(S) SHALL BE
DESIGNED PER NFPA 13 AND IBC REQUIREMENTS FOR A FULLY SPRINKLER BUILDING. PROVIDE
ALL SPRINKLER HEADS, PIPING, HANGERS, ETC. AND COORDINATE LOCATIONS, PIPE ROUTING,
SCHEDULING, AND ALL OTHER INSTALLATION REQUIREMENTS WITH OTHER TRADES. EXTEND
NEW BRANCH LINES FROM EXISTING CROSS-MAIN OUTLETS. WHERE CROSS MAIN OUTLETS ARE
NOT OF SUFFFICIENT QUANTITY PROVIDE A MECHANICAL TEE, TAP EXISTING SUPPLY MAIN AND
PROVIDE ADDITIONAL BRANCH LINE(S).
5
319.343.7055 ph
hkwarchitects.com
18207 Edison Avenue
Chesterfield, M0 63005
636.530.7770 ph
636.530.7877 fax
TO EXISTING VERTICAL BACKFLOW PREVENTER AND SYSTEM RISER.
4
ATM Vestibule
Off-Stage
Concierge
EXISTING FP
SERVICE MAIN
5
EXISTING 2-1/2" RISER
MAIN
@ 14'-2" AFF
Maintenance
SPR
Janitor
SPR
SPR
Customer
Pantry
3
Office
2
2
2
Office
Office
Office
Self-Serve
Boxes
2
Passage
Coupon Booth
Toilet
Toilet
2
Bid Set
Elec/Data
1
PNC Valley Park
1
PNC Bank
1
1
912 Meramec Station Road, Valley Park, MO 63021
Break Room
Lobby
Revision Schedule
The Seal and Signature apply only to the Document to
which they are Affixed, and Expressly Disclaim any
Responsibility for all other Plans, Specifications,
Estimates, Reports, or other Documents or Instruments
relating to or intended to be used for any part or parts of
the Architectural or Engineering Project.
Copyright © 2016 by SSC Engineering, Inc.
NORTH
FIRE PROTECTION FLOOR PLAN - DEMOLITION
FIRE PROTECTION FLOOR PLAN - RENOVATION
SCALE: 1/8" = 1'-0"
SCALE: 1/8" = 1'-0"
NORTH
SSC JOB# 2016123_BID SET - NOT FOR CONSTRUCTION
No
Date
Description
April 11, 2016
16.008.00
FIRE
PROTECTION
PLAN
FP1.1
Copyright 2016 HKW Architects
CEILING MOUNTED, SQUARE SUPPLY
AIR DIFFUSER 4-WAY UNLESS OTHERWISE INDICATED
(ARROW INDICATES DIRECTION OF THROW)
X - EXISTING
DRAIN
RG
REFRIGERANT HOT GAS
RL
REFRIGERANT LIQUID
RS
REFRIGERANT SUCTION
CEILING MOUNTED RETURN AIR GRILLE
SIDEWALL RETURN GRILLE
HWS
HOT WATER HEATING SUPPLY
SIDEWALL SUPPLY DIFFUSER
HWR
HOT WATER HEATING RETURN
SUPPLY AIR SLOT DIFFUSER
X
PIPE ANCHOR
RECTANGULAR TAP WITH DAMPER (BOTTOM)
CA
COMPRESSED AIR
G
NATURAL GAS
ROUND DUCT SUPPLY UP, DN OR IN SECTION
LPG
LIQUID PROPANE GAS
ROUND DUCT RETURN UP, DN OR IN SECTION
CWS
CHILLED WATER SUPPLY
PIPE DOWN
CWR
CHILLED WATER RETURN
PIPE UP
CHS
CHILLED WATER SUPPLY
TOP CONNECTION
CHR
CHILLED WATER RETURN
BOTTOM CONNECTION
CS
CONDENSER WATER SUPPLY
FLOW DIRECTION
CR
CONDENSER WATER RETURN
LPS
LOW PRESSURE STEAM
MPS
MEDIUM PRESSURE STEAM
HPS
HIGH PRESSURE STEAM
LPC
LOW PRESSURE CONDENSATE
MPC
MEDIUM PRESSURE CONDENSATE
HPC
PD
MANUAL AIR VENT
A
AUTOMATIC AIR VENT
THERMOWELL
PRESSURE GAUGE
HIGH PRESSURE CONDENSATE
STEAM CONDENSATE PUMPED DISCHARGE
LWS
LOOP WATER SUPPLY
LWR
LOOP WATER RETURN
P
PNEUMATIC TUBING
E
ELECTRICAL WIRING
MANIFOLD GAUGE
THERMOMETER
CAPPED OUTLET (UP)
DEMO PIPE OR EQUIPMENT
POINT OF CONNECTION NEW TO EXISTING
DIRT LEG (DN)
OPPOSED BLADE DAMPER
H
HUMIDISTAT
T
THERMOSTAT
DD SD
UNION
PIPE GUIDE
SMOKE DETECTOR (DUCT)
FS
T
FLOW SWITCH
DPS
STEAM TRAP
EXPANSION JOINT
EJ
DIFFERENTIAL PRESSURE SWITCH
REDUCER
PRESSURE SWITCH
BASKET STRAINER
X' - X"
BOTTOM OF DUCT ELEVATION
SUCTION DIFFUSER
24 X 12
OR
24 X 12
RECTANGULAR DUCT (FIRST NUMBER IS SURFACE
STRAINER
SHOWN-DIMENSIONS REPRESENT NET FREE AREA)
GATE VALVE
PS
12"Ø
OR
12"Ø
BALL VALVE
ROUND DUCT
TRIPLE DUTY VALVE
BUTTERFLY VALVE
RECTANGULAR TO ROUND TRANSITION
PRESSURE REDUCING VALVE
18x12
12x12
18x12
CHECK VALVE
TRANSITION
GAS COCK
12x12
R
DUCT WITH LINER
BALANCING VALVE (FLOW CONTROL VALVE)
INCLINED RISE (R) OR DROP (D) ARROW IN DIRECTION OF CHANGE
RPBP - REDUCED PRESSURE BACKFLOW PREVENTER
FLEXIBLE DUCT CONNECTION
DRAIN VALVE W/HOSE THREADED CONN.
SUPPLY AIR UP OR IN SECTION
AIR COOLED CONDENSER
AIR CONDITIONING UNIT
ADJUSTABLE
ABOVE FINISHED FLOOR
AIR HANDLING UNIT
ACCESS PANEL
AIR PRESSURE DROP(IN WC)
AIR SEPARATOR
BOILER
AIR BLENDER
BACKDRAFT DAMPER
BRAKE HORSEPOWER
BRITISH THERMAL UNITS
BOTTOM OF DUCT
BOTTOM OF PIPE
BOTTOM OF STEEL
BACKWATER VALVE
CAPACITY
CENTER TO CENTER
CUBIC FEET PER MINUTE
CHILLER
CHILLED WATER RETURN
CHILLED WATER SUPPLY
CAST IRON
CENTER LINE
CEILING
CLEANOUT
CONNECTION
CHLORINATED POLYVINYL CHLORIDE
CONDENSER WATER RETURN
CONDENSER WATER SUPPLY
CONDENSING UNIT
CABINET UNIT HEATER
CONTROL VALVE
DRAIN
DIAMETER
DRY BULB TEMPERATURE
DISCONNECT
DOWN
DOWNSPOUT
DISHWASHER
DUCT SMOKE DETECTOR SUPPLY
DUCT SMOKE DETECTOR RETURN
EXHAUST AIR DEVICE
EXHAUST AIR
ENTERING AIR TEMPERATURE
ENTERING DRY BULB TEMPERATURE
ENTERING WET BULB TEMPERATURE
ENTERING WATER TEMPERATURE
EFFICIENCY
EXPANSION TANK
ELECTRIC CABINET HEATER
EXHAUST FAN
ELECTRICAL CONTRACTOR
ENERGY MANAGEMENT SYSTEM
EXTERNAL STATIC PRESSURE
EMERGENCY SHUT-OFF VALVE
ELECTRIC UNIT HEATER
ELECTRIC WATER HEATER
EXISTING
EXHAUST
FRESH AIR
FAN COIL UNIT
FLOOR DRAIN
FLOOR HYDRANT
FILTER DRIER
FINISH
FLOOR
FACTORY MOUNTED
FEET PER MINUTE
FEET
FURNISHED
FULL LOAD AMPS
FLAT ON BOTTOM
FLAT ON TOP
FIRE PROTECTION CONTRACTOR
FLOOR SINK
FAN TERMINAL UNIT
GALLONS
GALVANIZED
GREASE INTERCEPTOR
GENERAL CONTRACTOR
GAS UNIT HEATER
GAS WATER HEATER
COLD WATER
HOSE BIBB
HUB DRAIN
HOUR
HORSEPOWER
IE
IN
INST
IRH
LAT
LDB
LWB
LWT
LRA
LPG
LWCO
MAU
MAX
MBH
MC
MCC
MD
MIN
MSB
MV
NO
NC
NO.
NF
NTS
OA
OED
OV
P
PC
POC
PIB
PD
PVC
RA
R-#
RD
RF
RPM
RP
RPBP
RTU
RV
S-#
SA
SD
SF
SW
STL
SG
SP
SPC
SV
TC
TDV
T
TF
TS
TSP
TXV
UH
UR
V
VAV
VD
VFD
VTR
WB
WPD
W.C.
ZD
INVERT ELEVATION
INCHES
INSTALLED
INFRA-RED HEATER
LEAVING AIR TEMPERATURE
LEAVING DRY BULB TEMPERATURE
LEAVING WET BULB TEMPERATURE
LEAVING WATER TEMPERATURE
LOCKED ROTOR AMPS
LIQUID PROPANE GAS
LOW WATER CUT-OFF
MAKE-UP AIR UNIT
MAXIMUM
1000 BTU/HR
MECHANICAL CONTRACTOR
MOTOR CONTROL CENTER
MOTORIZED DAMPER
MINIMUM
MOP SERVICE BASIN
MIXING VALVE
NORMALLY OPEN
NORMALLY CLOSED
NUMBER
NON-FUSED
NOT TO SCALE
OUTSIDE AIR
OPEN END DUCT
OUTLET VELOCITY
PUMP
PLUMBING CONTRACTOR
POINT OF CONNECTION
POWER INDUCTION BOX
PRESSURE DROP
POLYVINYL CHLORIDE
RETURN AIR
RETURN AIR DEVICE
ROOF DRAIN
RELIEF FAN
REVOLUTIONS PER MINUTE
RECIRCULATING PUMP
REDUCED PRESSURE BACK FLOW PREVENTER
ROOF TOP UNIT
RELIEF VALVE
SUPPLY AIR DEVICE
SUPPLY AIR
SMOKE DAMPER
SUPPLY FAN
SWITCH
STEEL
SIGHT GLASS
STATIC PRESSURE
SPRINKLER CONTRACTOR
SOLENOID VALVE
TEMPERATURE CONTROLLER
TRIPLE DUTY VALVE
TRANSFER GRILLE
TRANSFER FAN
TAMPER SWITCH
TOTAL STATIC PRESSURE
THERMAL EXPANSION VALVE
UNIT HEATER (HYDRONIC)
URINAL
VENT
VARIABLE AIR VOLUME BOX
VOLUME DAMPER
VARIABLE FREQUENCY DRIVE
VENT THRU ROOF
WET BULB TEMPERATURE
WATER PRESSURE DROP(FT. H20)
WATER COLUMN
ZONE DAMPER
1.
SEE THIS SHEET FOR SYMBOLS AND ABBREVIATIONS.
2.
THESE GENERAL NOTES APPLY TO ALL DEMOLITION WORK.
3.
REMOVE DUCTS AND EQUIPMENT SHOWN CROSS HATCHED OR DASHED.
4.
CONTRACTOR SHALL USE CAUTION WHEN REMOVING DUCTS TO AVOID DAMAGE TO ELECTRICAL
WIRING THAT IS TO REMAIN. NOTIFY GC AND EC IF WIRING IS FOUND ATTACHED TO DUCTWORK.
5.
WHEREVER EXISTING EQUIPMENT, PIPING, DUCTS, ETC., ARE TO BE REMOVED, SUCH REMOVAL
SHALL INCLUDE ALL ANCHORS, HANGERS, FOUNDATIONS, ETC., UNLESS NOTED OTHERWISE.
AFTER REMOVAL; FLOORS, WALLS AND CEILINGS SHALL BE PATCHED AND FINISHED TO MATCH
ADJOINING SURFACES.
6.
MISSOURI
5017 Washington Place Suite 200
St. Louis, M0 63108
314.361.0000 ph
314.361.9191 fax
IOWA
1000 Melrose Avenue
Iowa City, IA 52246
WHERE ITEMS ARE REMOVED, UTILITIES AND THE AREA FROM WHICH THE ITEMS HAVE BEEN
REMOVED SHALL BE LEFT IN SUCH A MANNER THAT IS SAFE FOR BOTH PEOPLE AND PROPERTY ON
A DAILY BASIS.
319.343.7055 ph
hkwarchitects.com
7.
THESE DRAWINGS MAY NOT FULLY DEPICT ALL AS-BUILT CONDITIONS, CONTRACTOR SHALL FIELD
VERIFY ALL EXISTING CONDITIONS PRIOR TO SUBMITTING BIDS. NOTIFY THE ENGINEER AT ONCE
SHOULD A DISCREPANCY OR OMISSION BE FOUND.
8.
SEE ARCHITECTURAL DRAWINGS FOR ARCHITECTURAL DEMOLITION. REFER TO MEP AND
SPRINKLER DEMOLITION PLANS FOR MEP AND SPRINKLER DEMOLITION.
9.
THE OWNER WILL BE RESPONSIBLE FOR THE REMOVAL OF ANY ACMs (ASBESTOS CONTAINING
MATERIALS, PCBs OR OTHER HAZARDOUS MATERIALS) PRESENTLY EXISTING WITHIN THE AREAS
AFFECTED BY THE PROJECT SCOPE, THAT WOULD BE REQUIRED TO BE REMOVED FOR THE WORK.
ABATEMENT WORK, IF REQUIRED, IS NOT PART OF THIS CONTRACT.
18207 Edison Avenue
Chesterfield, M0 63005
636.530.7770 ph
636.530.7877 fax
MECHANICAL GENERAL RENOVATION NOTES:
1.
SEE THIS SHEET FOR SYMBOLS AND ABBREVIATIONS.
2.
THESE GENERAL NOTES APPLY TO ALL WORK.
3.
DUCT SIZES SHOWN ARE SHEET METAL SIZE AND INCLUDE THE DUCT LINER WHERE LINER IS REQUIRED.
4.
ALL SUPPLY, RETURN, EXHAUST, AND TRANSFER REGISTERS IN ROOMS WITHOUT CEILINGS SHALL BE 9'-0"
AFF UNLESS NOTED OTHERWISE.
5.
REFER TO THE ARCHITECTURAL REFLECTED CEILING PLAN FOR EXACT LOCATION OF CEILING AIR DEVICES.
6.
MAINTAIN 10'-0" MINIMUM BETWEEN OUTSIDE AIR INTAKES AND ALL EXHAUST FANS, FLUES, PLUMBING
VENTS, ETC.
7.
ALL DUCT RUN OUTS TO AIR DEVICES SHALL HAVE A DAMPER WITH A LOCKING QUADRANT IN ADDITION TO
THE DAMPER IN THE NECK OF THE AIR DEVICE.
8.
CONTRACTOR SHALL COORDINATE WITH OTHER TRADES TO PREVENT THE INSTALLATION OF CONDUITS,
PIPING, LIGHTING, OR OTHER OBSTRUCTIONS UNDER OR ADJACENT TO HVAC EQUIPMENT THAT
OBSTRUCTS ACCESS TO COILS, MOTORS, VALVES, FILTERS, ETC., OR OTHER HVAC COMPONENTS NEEDING
MAINTENANCE OR OPERATIONS ACCESS.
9.
FLEXIBLE DUCT LENGTH SHALL NOT EXCEED 3'-0".
10. ALL EXPOSED DUCTS SHALL HAVE PAINT GRIP FINISH FOR PAINTING BY GC. COLOR PER ARCHITECT.
11. THERMOSTATS AND ROOM TEMPERATURE SENSORS SHALL BE MOUNTED AT 4'-0" TO THE TOP OF THE
JUNCTION BOX THAT THE DEVICE IS MOUNTED ON.
12. COORDINATE DUCTWORK WITH ALL SPRINKLER AND PLUMBING PIPING BEFORE COMMENCEMENT OF
WORK.
13. MAINTAIN MINIMUM OF 4'-0" BETWEEN BRANCH TAKE OFFS.
14. LOCATIONS OF NEW EQUIPMENT, DUCTWORK, PIPING, AND ASSOCIATED ITEMS SHOWN ON THE DRAWINGS
ARE SCHEMATIC. CONTRACTOR SHALL FIELD VERIFY EXACT LOCATION AND ELEVATION OF ALL WORK.
PROVIDE OFFSETS, FITTINGS, TRANSITIONS, EXTENSIONS, ETC., REQUIRED FOR A COMPLETE SYSTEM.
15. NO CHANGES IN CONTRACT PRICE WILL BE ALLOWED FOR MINOR CHANGES IN LAYOUT OR LOCATION
REQUIRED TO AVOID INTERFERENCES, OBSTRUCTIONS, ETC. CONTRACT PRICE CHANGES WILL BE
CONSIDERED ONLY FOR CHANGES IN THE SCOPE OF THE PROJECT REQUIREMENTS. ALL SUCH SCOPE
CHANGES AND PRICE REVISIONS MUST BE AUTHORIZED IN WRITING. NOTIFY THE ENGINEER AT ONCE
SHOULD A DISCREPANCY OR OMISSION BE FOUND.
16. ALL UTILITIES SERVING EXISTING AREAS SHALL REMAIN IN SERVICE AT ALL TIMES EXCEPT FOR SHORT
PERIODS OF INTERRUPTION FOR TIE IN OF NEW SERVICES TO EXISTING. ALL INTERRUPTIONS SHALL BE
SCHEDULED WITH OWNER AND SHALL NOT BE SCHEDULED UNTIL NEW SERVICES ARE COMPLETE AND
READY FOR FINAL CONNECTION.
PRESSURE RELIEF VALVE
17. AIR DEVICES SHALL BE SIZED TO MATCH THE CEILING GRID. FURNISH AIR DEVICES FOR EITHER REGULAR
GRID CEILINGS OF FOR NARROW GRID CEILINGS OR FOR BOTH TYPES OF GRID; COORDINATE WITH THE
ARCHITECTURAL REFLECTED CEILING PLANS.
3-WAY AUTOMATIC CONTROL VALVE
18. PROVIDE SUPPLEMENTAL "TEES" FOR THE CEILING GRID WHERE DIFFUSERS ARE A DIFFERENT SIZE THAN
THE CEILING TILES.
2-WAY AUTOMATIC CONTROL VALVE
19. WHERE INSULATION CONTAINING HAZARDOUS MATERIALS HAS BEEN REMOVED FROM DUCTWORK, PIPING,
OR EQUIPMENT, REPLACE IT WITH NEW INSULATION. SEE SPECIFICATIONS FOR TYPE AND THICKNESS.
VOLUME DAMPER
MOTORIZED VALVE
20. GENERALLY PROVIDE DUCT INSULATION FOR SUPPLY, RETURN AND OUTSIDE AIR DUCTS ABOVE CEILINGS.
SEE DETAILS AND DUCT INSULATION SCHEDULE ON PLANS FOR ADDITIONAL REQUIREMENTS. SEE SPECS
230900 AND 230200 FOR A MORE DETAILED DESCRIPTION OF LINING AND INSULATION REQUIREMENTS.
MOTORIZED DAMPER
ANGLE VALVE
21. ALL DUCTS SHALL BE 2" WG PRESSURE CLASS.
RETURN,EXHAUST OR OUTSIDE AIR UP OR IN SECTION
SUPPLY AIR DOWN OR AWAY
RETURN,EXHAUST OR OUTSIDE AIR DOWN OR AWAY
RECTANGULAR ELBOW WITH TURNING VANES
M
M
SV
FIRE DAMPER/SMOKE DAMPER/COMB. FIRE SMOKE DAMPER
SOLENOID VALVE
SPIN-IN FITTING WITH DAMPER (SIDE)
THERMAL EXPANSION VALVE
TEMPERATURE/PRESSURE TEST PLUG
Bid Set
D
EQUIPMENT IDENTIFICATION
ACC
AC
ADJ
AFF
AHU
AP
APD
AS
B
BB
BDD
BHP
BTU
BOD
BOP
BOS
BW
CAP
CC
CFM
CH
CWR
CWS
CI
CL
CLG
CO
CONN
CPVC
CR
CS
CU
CUH
CV
D
DIA
DB
DISC
DN
DS
DW
DSD
DSR
E-#
EA
EAT
EDB
EWB
EWT
EFF
ET
ECH
EF
EC
EMS
ESP
ESV
EUH
EWH
EX
EXH
FA
FCU
FD
FH
FDR
FIN
FLR
FM
FPM
FT
FURN
FLA
FOB
FOT
FPC
FS
FTU
GAL
GALV
GI
GC
GUH
GWH
CW
HB
HD
HR
HP
ROUND TAP WITH DAMPER (BOTTOM)
MECHANICAL GENERAL DEMOLITION NOTES:
912 Meramec Station Road, Valley Park, MO 63021
AHU
1
X - EXISTING
S - SUPPLY
R - RETURN
E - EXHAUST
PNC Valley Park
AIR DEVICE TAG
CFM
S1
#
MECHANICAL ABBREVIATIONS
MECHANICAL SYMBOLS LEGEND (CONT.)
PNC Bank
MECHANICAL SYMBOLS LEGEND
Revision Schedule
No
Date
Description
Seismic Use Group ( II )
LISTING OF
EQUIPMENT AND
SYSTEM COMPONENTS
Seismic Design Category ( D )
ANCHORAGE TO
FLOORS,
ROOFS, ETC.
Not Provided
Provided
SWAY BRACING
Not Provided
Provided
LOCATION OF PROFESSIONALLY SEALED
ANCHORAGE
AND SWAY BRACING DETAILS
Drawing No. or
Spec. Section
Shop Drawings
COMMENTS
Separate
Permit & Plans
AIR DEVICES
X
X
2
EH-1
X
X
X
12
DUCTWORK
X
4
X
EF-1 (EXHAUST FAN)
X
1.
The Seal and Signature apply only to the Document to
which they are Affixed, and Expressly Disclaim any
Responsibility for all other Plans, Specifications,
Estimates, Reports, or other Documents or Instruments
relating to or intended to be used for any part or parts of
the Architectural or Engineering Project.
Copyright © 2016 by SSC Engineering, Inc.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
X
X
12
TABLE 4.4, ITEM 1, A, EXCEPTION FOR 3 FEET MINIMUM OF FLEX CONNECTION BETWEEN COMPONENTS, MOUNTED 4 FEET OR LESS
ABOVE THE FLOOR LEVEL AND WEIGHS 400 POUNDS OR LESS.
TABLE 4.4, ITEM 1, B, EXCEPTION FOR 3 FEET MINIMUM OF FLEX CONNECTION BETWEEN COMPONENTS AND WEIGHS 20 POUNDS OR LESS.
TABLE 4.4, ITEM 1, B, EXCEPTION FOR LESS THAN 5LB/FT (COPPER PIPING - 2-1/2" OR LESS, SCHEDULE 40 AND 80 CPVC - 3" OR LESS). 3 FOOT FLEX
CONNECTIONS FOR SUSPENDED EQUIPMENT.
TABLE 4.4, ITEM 3, EXCEPTION FOR DUCTWORK "A" (OR "B"). REFER TO INSTALLATION DETAIL ON DRAWING #__.
TABLE 4.4, ITEM 4, EXCEPTION FOR PIPING SUSPENDED FROM HANGERS 12 INCHES OR LESS. REFER TO INSTALLATION DETAIL ON DRAWING #__.
TABLE 4.4, ITEM 4, EXCEPTION FOR DUCTILE PIPING 1" OR LESS (SEISMIC DESIGN CATEGORY D).
DUCTILE PIPING, STEEL, COPPER PIPING AND TUBING JOINED BY WELDING, BRAZING/SOLDERING OR FLANGES. REFER TO TABLE 4.4, ITEM 4.
TABLE 4.4, ITEM 4, EXCEPTION FOR DUCTILE PIPING 3" OR LESS (SEISMIC DESIGN CATEGORY D).
TABLE 4.4, ITEM 5, EXCEPTION FOR EXTERIOR GAS PIPING ON ROOF, 2 PSI OR LESS: SEISMIC SHUT-OFF VALVE OR FLEX CONNECTORS WITHIN 5 FEET
OF THE BEGINNING OF THE RUN, AT CONNECTIONS TO EQUIPMENT AND AT 42 FOOT OR LESS INTERVALS.
COMPONENTS SHALL BE POSITIVELY ATTACHED WITH MECHANICAL FASTENERS.
SEISMIC CALCULATIONS ARE ATTACHED TO SET OF DRAWINGS.
CONTRACTOR SHALL PROVIDE SHOP DRAWINGS TO THE ENGINEER OF RECORD FOR REVIEW AND APPROVAL PRIOR TO SUBMITTAL TO THE PLAN
REVIEWER.
TYPICAL SEISMIC ANCHORAGE (OR SWAY BRACING) IS PROVIDED ON THE DRAWINGS FOR REFERENCE ONLY. SHOP DRAWINGS ARE REQUIRED.
MECHANICAL SHEET LIST
Sheet Number
Sheet Name
M0.1
MECHANICAL SYMBOLS, ABBREVIATIONS & GENERAL NOTES
M0.2
MECHANICAL SCHEDULES & DETAILS
M1.1
MECHANICAL DUCTWORK PLAN
SSC JOB# 2016123_BID SET - NOT FOR CONSTRUCTION
Anchorage & Sway Bracing - Mechanical & Plumbing System Components
April 11, 2016
16.008.00
MECHANICAL
SYMBOLS,
ABBREVIATIONS
& GENERAL
NOTES
M0.1
Copyright 2016 HKW Architects
EXHAUST FAN SCHEDULE
ELECTRIC HEATER SCHEDULE (CEILING)
MARK
MANUFACTURER
EH-1
QMARK
MODEL NO.
CDF548
LOCATION
ATM / VESTIBULE
WATTS
VOLT/PH
REMARKS
4000
208/1
1,2,3
1. UNIT MOUNTED DISCONNECT SWITCH.
2. CEILING MOUNTED.
3. THERMOSTAT TO BE MOUNTED ON WALL. SEE SHEET M1.1 FOR LOCATION.
MARK
MANUFACTURER
MODEL NO.
LOCATION
DRIVE
SERVICE
CFM
SP
RPM
VOLTS/PH
HP
REMARKS
EF-1
BROAN
L150MG
CEILING
DIRECT
JANITOR CLOSET
100
0.350
1,750
120/1
-
1
EF-2
BROAN
L150MG
CEILING
DIRECT
RESTROOM
100
0.350
1,750
120/1
-
1
EF-3
BROAN
L150MG
CEILING
DIRECT
RESTROOM
100
0.350
1,750
120/1
-
1
1. SPEED CONTROLLER AND BACKDRAFT DAMPER.
MISSOURI
5017 Washington Place Suite 200
St. Louis, M0 63108
ROOF TOP UNIT SCHEDULE (EXISTING TO REMAIN)
314.361.0000 ph
314.361.9191 fax
ESP
INCHES
H2O
HEATING INPUT MBH
HP
V/PH
MCA
ELECTRICAL
MARK
MANUFACTURER
MODEL NO.
TONS
CFM
O.A.
CFM
RTU-1
YORK
D2NA060N11025D
5
1,850
260
0.5
135
1.0
208/3
29.5
1
RTU-2
YORK
D1NA048N11025C
4
1,500
100
0.5
135
1.0
208/3
25.9
1
1.
REMARKS
IOWA
1000 Melrose Avenue
Iowa City, IA 52246
319.343.7055 ph
hkwarchitects.com
EXISTING RTU UNIT. NO MODIFCATION OR UPGRADES REQUIRED TO UNIT OR ASSOCIATED GAS PIPING.
18207 Edison Avenue
Chesterfield, M0 63005
AIR DEVICE SCHEDULE
PLAN
MARK
MANUFACTURER
MODEL
MATL.
NECK
SIZE
FRAME
TYPE
PANEL
SIZE
NC
COLOR
REMARKS
S1
KRUEGER
PLQ
STEEL
8"Ø
LAY-IN
24x24
<30
44-BRITISH WHITE
1,2
1,2
S2
KRUEGER
PLQ
STEEL
10"Ø
LAY-IN
24x24
<30
44-BRITISH WHITE
S3
KRUEGER
5810
ALUM
22x22
SURFACE
12x12
<30
10-ALUMICAN
1,2
S4
ACUTHERM
TF-HC
STEEL
8"Ø
LAY-IN
24x24
<30
STANDARD WHITE
1,2,5
T1
KRUEGER
5810
ALUM
22x22
SURFACE
12x12
<30
10-ALUMICAN
1,2
R1
KRUEGER
S80H
STEEL
22x22
LAY-IN
24x24
-
44-BRITISH WHITE
1,2,3,4
636.530.7770 ph
636.530.7877 fax
Bid Set
912 Meramec Station Road, Valley Park, MO 63021
PNC Valley Park
PNC Bank
1. VERIFY ARRANGEMENT WITH CEILING TYPE
2. DAMPERS TO BE RADIAL OPPOSED BLADE
3. DROPPED FACE RETURN GRILLE
4. PROVIDE NECK ADAPTER MATCHING SIZE ON DRAWING
5. VARIABLE VOLUME DIFFUSER. SUPPORTED BY DUCT IN OPEN CEILING.
Revision Schedule
BRANCH
DUCT
SEAL FLEX DUCT
INSULATION TO
RIGID DUCT
INSULATION WITH
DUCT TAPE
EXTERNAL DUCT
INSULATION
SQUARE TO ROUND
TRANSITION
The Seal and Signature apply only to the Document to
which they are Affixed, and Expressly Disclaim any
Responsibility for all other Plans, Specifications,
Estimates, Reports, or other Documents or Instruments
relating to or intended to be used for any part or parts of
the Architectural or Engineering Project.
Copyright © 2016 by SSC Engineering, Inc.
VOLUME DAMPER WITH
LOCKING QUADRANT AND
INSULATION EXTENSION
DRAWBAND
SEE NOTE 2
FLEXIBLE ROUND DUCT,
SEE SPECS
NOTES:
1. THIS DETAIL IS APPLICABLE FOR FELXIBLE ROUND DUCT TAKE-OFFS FROM
BRANCH DUCTS TO DIFFUSERS.
2. FLEXIBLE DUCT INSULATION SHALL TERMINATE AT SIDE OF BRANCH DUCT
SO NO UNISULATED METAL PARTS ARE EXPOSED.
BOTTOM TAP DIFFUSER DETAIL
BRANCH CONNECTION TO DIFFUSER DETAIL
FLEXIBLE DUCT CONNECTION TO BRANCH - INSULATED
SOUND BO0T DETAIL
NOT TO SCALE
NOT TO SCALE
NOT TO SCALE
NOT TO SCALE
SSC JOB# 2016123_BID SET - NOT FOR CONSTRUCTION
No
Date
Description
April 11, 2016
16.008.00
MECHANICAL
SCHEDULES &
DETAILS
M0.2
Copyright 2016 HKW Architects
MECHANICAL GENERAL NOTES:
1. REFER TO SHEET M0.1 FOR SYMBOLS, ABBREVIATIONS AND GENERAL CONSTRUCTION NOTES.
2. ADJACENT TENANT SPACE NOT IN SCOPE.
3. ITEMS SHOWN DASHED OR CROSS HATCHED TO BE DEMOLISHED.
4. MC SHALL PROVIDE COMMISIONING FOR THE HVAC SYSTEM BEFORE SUBSTANTIAL
COMPLETION. CONFIRM CONTROLS OPERATION; RTU OPERATION - FAN, DAMPERS, COOLING
STAGING, HEATING STAGING; EF OPERATION; EH OPERATION. SUBMIT REPORT TO OWNER.
MISSOURI
5017 Washington Place Suite 200
St. Louis, M0 63108
314.361.0000 ph
314.361.9191 fax
-
XS
1
-
XS
1
12"ø
16"ø
9
FD
12"ø
XS
-
XS
-
XS
1
-
XS
RTU
1
-
1X
8"ø 10"ø
1X
100
2
R1
8"ø
S2
T
8"ø
12"x12"
350
S2
-
12"ø
-
1
-
16"ø
XS
XS
1
1
-
350
S1
1
XS
RTU
2X
(ON ROOF)
-
R1
S1
-
100
10"ø
12"ø
XS
10"ø
R1
-
8"ø
Lobby
119
RTU
S1
200
2X
S1
200
(ON
ROOF)
-
1
9
-
XT
XT
-
-
9
3
3
EF
EF
S2
EX
EX
350
8"ø
8"ø
Office
116
S1
Office
118
The Seal and Signature apply only to the Document to
which they are Affixed, and Expressly Disclaim any
Responsibility for all other Plans, Specifications,
Estimates, Reports, or other Documents or Instruments
relating to or intended to be used for any part or parts of
the Architectural or Engineering Project.
Copyright © 2016 by SSC Engineering, Inc.
636.530.7770 ph
636.530.7877 fax
6
12" X 12" TRANSFER DUCT SHALL TRANSITION UP AND TERMINATE IN CEILING PLENUM OF LOBBY.
7
8" TWO-POSITION, 120 VOLT CONTROL DAMPER. LINE VOLTAGE, DUCT MOUNTED THERMOSTAT SHALL
CLOSE DAMPER WHEN SUPPLY AIR ABOVE 80° F.
8
PROVIDE DUCTED SOUND BOOT AT PLENUM RETURN GRILLES, SEE SHEET M0.2.
9
EXISTING WALL TRANSFER GRILLE AT 12' AFF TO BE REMOVED TO ACCOMMODATE NEW LAY-IN
CEILING.
10
NEW WALL TRANSFER GRILLE AT 7' AFF.
11
EXISTING DUCT DETECTOR TO REMAIN.
12
12" x 12" TRANSFER DUCT ABOVE CEILING.
150
-
8"ø
S1
150
6"ø
100
-
EF
S4
Break Room
109
S1
Self-Serve
Boxes
114
8"ø
Elec/Data
105
Janitor
107
12
12"x12"
RTU-1X
Office
115
Maintenance
104
150
T
R1
S1
-
150
S1
150
100
Coupon Booth
112
S1
8"ø
100
Toilet
108
Passage
111
4
Toilet
106
EF
EF
1
2
4
Revision Schedule
T1
No
-
MECHANICAL DUCTWORK PLAN - DEMOLITION
MECHANICAL DUCTWORK PLAN - RENOVATION
SCALE: 1/8" = 1'-0"
SCALE: 1/8" = 1'-0"
NORTH
R1
Off-Stage
103
8"ø
8"ø
8"ø
Office
117
S1
150
8"ø
8 (TYP)
10
NORTH
INSTALL SIDE WALL AIR DEVICE 10' AFF.
R1
Customer
Pantry
113
16"x16"
R1
T
5
3
R1
14"x16"
RTU-2X
18207 Edison Avenue
Chesterfield, M0 63005
S1
R1
1
-
NEW EXHAUST FAN TO CONNECT TO EXISTING CAPPED VENT THROUGH ROOF.
12
8"ø
-
150
1
FD
12
-
10"ø
XS
20"x20"
16"ø
2
T
RTU-2X
RTU-1X
XS
RTU
8"ø
(ON
ROOF)
(ON ROOF)
XS
12"x12"
Concierge
102
8"ø
12"x12"
1
4
4
T1
1
DEMOLISH EXISTING EXHAUST FAN AND DUCT TO EXISTING VENT THROUGH ROOF. VENT THROUGH
ROOF TO REMAIN.
8"ø
S1
6
3
hkwarchitects.com
150
1
5
RELOCATE EXISTING THERMOSTAT TO NEW LOCATION. SEE RENOVATION PLAN.
Bid Set
XS
-
2
912 Meramec Station Road, Valley Park, MO 63021
11
319.343.7055 ph
PNC Valley Park
XT
DEMOLISH EXISTING AIR DEVICE. PATCH DUCT TO REMAIN WHERE APPLICABLE.
PNC Bank
-
150
1
S1
EH-1
ATM Vestibule
T
100
S3
EH
5
350
1
XT
S1
100
20"x20"
9
S1
-
IOWA
1000 Melrose Avenue
Iowa City, IA 52246
SSC JOB# 2016123_BID SET - NOT FOR CONSTRUCTION
4
R1
MECHANICAL KEYED NOTES:
Date
Description
April 11, 2016
16.008.00
MECHANICAL
DUCTWORK
PLAN
M1.1
PLUMBING GENERAL DEMOLITION NOTES:
PLUMBING FIXTURE SCHEDULE
Anchorage & Sway Bracing - Plumbing System Components
MARK
Seismic Use Group ( II )
Seismic Design Category ( D )
ANCHORAGE TO
FLOORS,
ROOFS, ETC.
LISTING OF
EQUIPMENT AND
SYSTEM COMPONENTS
Not Provided
Provided
SWAY BRACING
Not Provided
Provided
LOCATION OF PROFESSIONALLY SEALED
ANCHORAGE
AND SWAY BRACING DETAILS
Drawing No. or
Spec. Section
Shop Drawings
EF-21-318 L/R
2a
VENT PIPING
4.
5.
X
2c
6.
AMERICAN STANDARD "LUCERNE", VITREOUS CHINA, 20-1/2"x18-1/4", WALL-HUNG, FRONT
OVERFLOW LAVATORY, 2-1/8" DIA. HOLES FOR CONCEALED ARMS. SINGLE CENTERSET.
BASYS IR SERIES FAUCET.ONS SINGLE LEVER LAVATORY FAUCET WITH GRID STRAINER DRAIN ASSEMBLY,
SINGLE CENTERSET, 0.5 GPM AERATOR.
LFBV2166
Z1231-SL-79
EWC-1
MCGUIRE OPEN-GRID DRAIN. RUBBER WASHER AND BRASS LOCKNUT. WITH 1-1/2" TAILPIECE.
S-1
ELECTRIC WATER HEATER SCHEDULE
EWH-1
A.O. SMITH
DEL-6
6
10 GPH
HEAT CAP.
REMARKS
100
120V
2500 WATTS
1
ELECTRIC WATER COOLER
MCGUIRE CHROME PLATED, BRASS BODY P-TRAP WITH CLEANOUT, 17 GAUGE TUBULAER WALL BEND, CAST
BRASS SLIP NUTS.
LRADQ2521
HEAT SOURCE
CONCEALED ARM SYSTEM FOR WALL LAVATORY.
8912
LFBV02
°F. RISE
LAV GUARD 2 FAST FIT UNDERSINK PIPING COVERS FOR P-TRAP, ANGLE STOPS, AND SUPPLY COVERS.
ADA COMPLIANT.
ELKAY BI-LEVEL ELECTRIC WATER COOLER WITH BOTTLE FILLING STATION. VANDAL RESIST STREAMSAVER
EZH20 BOTTLE FILLING - WATER COOLER COMBINATION KIT.
SR1912A C
STORAGE GAL. RECOVERY
MCGUIRE CHROME PLATED, BRASS BODY P-TRAP WITH CLEANOUT, 17 GAUGE TUBULAER WALL BEND, CAST
BRASS SLIP NUTS.
8912
9.
THE OWNER WILL BE RESPONSIBLE FOR THE REMOVAL OF ANY ACMs (ASBESTOS
CONTAINING MATERIALS, PCBs OR OTHER HAZARDOUS MATERIALS) PRESENTLY EXISTING
WITHIN THE AREAS AFFECTED BY THE PROJECT SCOPE, THAT WOULD BE REQUIRED TO
BE REMOVED FOR THE WORK. ABATEMENT WORK, IF REQUIRED, IS NOT PART OF THIS
CONTRACT.
18207 Edison Avenue
Chesterfield, M0 63005
636.530.7770 ph
636.530.7877 fax
10. MEP DEMOLITION WORK: VERIFY EXISTING SERVICES TO REMAIN. ALL NECESSARY CARE
SHALL BE TAKEN DURING DEMOLITION TO PREVENT DAMAGE TO PLUMBING, ELECTRICAL,
AND MECHANICAL SYSTEMS TO REMAIN. DUCTWORK, PIPING, ELECTRICAL LINES, AND
PLUMBING SERVING OTHER AREAS SHALL PROVIDE FOR UNINTERRUPTED SERVICE TO
THOSE AREAS UNLESS PRIOR WRITTEN APPROVAL IS RECEIVED FROM THE OWNER.
COORDINATE ALL SUCH WORK WITH THE GENERAL CONTRACTOR AND OWNER'S ON SITE
REPRESENTATIVE.
11. WASTE PIPING TO BE PVC WITH PLENUM WRAP OR CAST-IRON TO BE INSTALLED IN
RETURN AIR PLENUM.
PLUMBING GENERAL RENOVATION NOTES:
CHICAGO FAUCET DECK MOUNTED WIDESPREAD FAUCET WITH BLADE HANDLES, 8" HIGH ARC SWING
SPOUT WITH 1.0 GPM AERATOR (E3JKABCP).
1.
SEE SHEET P0.1 FOR SYMBOLS AND ABBREVIATIONS. THESE GENERAL NOTES APPLY TO ALL WORK.
2.
THESE DRAWINGS MAY NOT FULLY DEPICT ALL AS-BUILT CONDITIONS, CONTRACTOR SHALL FIELD
VERIFY ALL EXISTING CONDITIONS PRIOR TO SUBMITTING BIDS. NOTIFY THE ENGINEER AT ONCE SHOULD
A DISCREPANCY OR OMISSION BE FOUND.
3.
PIPING ON PLANS IS SHOWN FOR GENERAL ARRANGEMENT. SEE DETAILS FOR CONNECTIONS TO UNITS.
4.
WHERE PIPE SIZES ARE NOT SHOWN ON PLANS, SEE SIZES SHOWN ON ISOMETRICS. IF PIPE SIZES ON
PLANS CONFLICT WITH SIZES SHOWN ON ISOMETRIC DIAGRAMS, SIZES ON DIAGRAMS SHALL TAKE
PRECEDENCE.
5.
SLOPE ALL SANITARY PIPES SMALLER THAN 4" AT 1/4" PER FT. AND SANITARY PIPES 4" OR LARGER AT
1/8" PER FT. UNLESS OTHERWISE INDICATED.
6.
CONTRACTOR SHALL COORDINATE WITH OTHER TRADES TO PREVENT THE INSTALLATION OF CONDUITS,
PIPING, LIGHTING, OR OTHER OBSTRUCTIONS UNDER OR ADJACENT TO HVAC EQUIPMENT THAT
OBSTRUCTS ACCESS TO COILS, MOTORS, VALVES, FILTERS, ETC., OR OTHER HVAC COMPONENTS
NEEDING MAINTENANCE OR OPERATIONS ACCESS.
7.
CONTRACTOR SHALL COORDINATE EXACT LOCATION OF FLOOR DRAINS WITH ARCHITECTURAL AND
STRUCTU PLANS.
8.
COORDINATE PLUMBING WITH ALL MECHANICAL DUCTWORK AND PIPING AND SPRINKLER PIPING
BEFORE COMMENCEMENT OF WORK.
9.
LOCATIONS OF NEW FIXTURES, EQUIPMENT, PIPING, AND ASSOCIATED ITEMS SHOWN ON THE
DRAWINGS ARE SCHEMATIC. CONTRACTOR SHALL SEE ARCHITECTURAL PLANS AND FIELD VERIFY
EXACT LOCATION AND ELEVATION OF ALL WORK. PROVIDE OFFSETS, FITTINGS, TRANSITIONS,
EXTENSIONS, ETC., REQUIRED FOR A COMPLETE SYSTEM.
BRASS CRAFT LOOSE KEY, CHROME PLATED ANGLE STOP, WITH 1/2" SWEAT INLET AND 3/8"
O.D. COMPRESSION OUTLET WITH 3/8" x 11-1/2" LONG RISER AND SHALLOW CHROME
PLATED WALL ESCUTCHEON.
MCGUIRE CHROME PLATED, BRASS BODY WITH CLEANOUT, 17 GAUGE TUBULAER WALL BEND, CAST
BRASS SLIP NUTS.
MOP SERVICE BASIN
WSB-1
319.343.7055 ph
hkwarchitects.com
ELKAY, 25"x21.25" STAINLESS STEEL SINGLE BOWL SINK, 6" DEEP, HEAVY DUTY SOUND
GUARD UNDERCOATING. 8" CENTERSET.
MSB-1
MIB1HAAB
WHERE ITEMS ARE REMOVED, UTILITIES AND THE AREA FROM WHICH THE ITEMS HAVE
BEEN REMOVED SHALL BE LEFT IN SUCH A MANNER THAT IS SAFE FOR BOTH PEOPLE AND
PROPERTY ON A DAILY BASIS.
SEE ARCHITECTURAL DRAWINGS FOR ARCHITECTURAL DEMOLITION. REFER TO MEP AND
SPRINKLER DEMOLITION PLANS FOR MEP AND SPRINKLER DEMOLITION.
1. NON-SIMULTANEOUS OPERATION.
T-35
IOWA
1000 Melrose Avenue
Iowa City, IA 52246
SINK
ELKAY 3-1/2" DIAMETER WASTE AND 1-1/2" TAILPIECE.
897-RCF
314.361.0000 ph
314.361.9191 fax
MCGUIRE STOP VALVE, CONVERTIBLE LOOSE KEY HANDLE, LEAD FREE, CHROME PLATED.
LK-18B
EB-54
MISSOURI
5017 Washington Place Suite 200
St. Louis, M0 63108
WHEREVER EXISTING EQUIPMENT, PIPING, ETC., ARE TO BE REMOVED, SUCH REMOVAL
SHALL INCLUDE ALL ANCHORS, HANGERS, FOUNDATIONS, ETC., UNLESS NOTED
OTHERWISE. AFTER REMOVAL, FLOORS, WALLS AND CEILINGS SHALL BE PATCHED AND
FINISHED TO MATCH ADJOINING SURFACES.
8.
MCGUIRE LOOSE KEY CHROME PLATED, COMMERCIAL PATTERN QUARTER TURN BRASS BALL VALVE.
LZSTL8WSVRSK
201-AGN8AE3-317ABCP
MODEL NO.
7.
1
X
TABLE 4.4, ITEM 1, A, lp=1.0, COMPONENT DOES NOT WEIGH MORE THAN 400 POUNDS AND FLEXIBLE CONNECTIONS ARE PROVIDED.
TABLE 4.4, NOTE 2:
a. THE FOLLOWING SANITARY DRAIN, WASTE AND VENT PIPE:
SCHEDULE 40 PVC, 6 INCHES OR LESS IN DIAMETER, SCHEDULE 80 PVC, 4 INCHES OR LESS IN DIAMETER, SERVICE WEIGHT
AND NO HUB CAST IRON, 2 INCHES OR LESS IN DIAMETER.
b. THE FOLLOWING STORM DRAIN PIPE:
SCHEDULE 40 AND 80 PVC, 3 INCHES OR LESS IN DIAMETER, SERVICE WEIGHT AND NO HUB CAST IRON, NOT APPLICABLE.
c. THE FOLLOWING WATER PIPE:
TYPE L AND M COPPER, 2-1/2 INCHES OR LESS IN DIAMETER, SCHEDULE 40 AND 80 CPVC, 3 INCHES OR LESS IN
DIAMETER.
d. FLEXIBLE CONNECTIONS ARE NOT REQUIRED FOR CONNECTIONS TO APPLIANCES OR PLUMBING FIXTURES THAT ARE MOUNTED
TO WALLS OR FLOORS.
CONTRACTOR SHALL PROVIDE SHOP DRAWINGS TO THE ENGINEER OF RECORD FOR REVIEW AND APPROVAL PRIOR TO SUBMITTAL TO THE PLAN
REVIEWER.
SEISMIC DETAILS ARE ATTACHED TO THE SET OF DRAWINGS.
TYPICAL SEISMIC ANCHORAGE (OR SWAY BRACING) IS PROVIDED ON THE DRAWINGS FOR REFERENCE ONLY. SHOP DRAWINGS ARE REQUIRED.
MNFG.
CONTRACTOR SHALL USE CAUTION WHEN REMOVING PIPING, EQUIPMENT AND FIXTURES
TO AVOID DAMAGE TO ELECTRICAL WIRING THAT IS TO REMAIN. NOTIFY GC AND EC IF
WIRING IS FOUND ATTACHED TO PIPING.
WALL HUNG LAVATORY
8912
MARK
THESE DRAWINGS MAY NOT FULLY DEPICT ALL AS-BUILT CONDITIONS, CONTRACTOR
SHALL FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO SUBMITTING BIDS. NOTIFY THE
ENGINEER AT ONCE SHOULD A DISCREPANCY OR OMISSION BE FOUND.
LAV-1
0356.137
#103 E-Z
3.
4.
5.
155A2
1.
2.
DEMOLISH PIPING, FIXTURES, AND EQUIPMENT SHOWN CROSS HATCHED OR DASHED.
GERBER FLOOR MOUNTED TANK TYP VITREOUS CHINA TOILET. ELONGATED BOWL,
ADA COMPLIANT, 1.1 GAL PER FLUSH.
WATER PIPING
X
3.
CHURCH COMMERCIAL WHITE SOLID PLASTIC OPEN FRONT SEAT, LESS COVER.
EFX-375.100.0000
WATER HEATER (LESS THAN
OR EQUAL TO 400 POUNDS)
THESE GENERAL DEMOLITION NOTES APPLY TO ALL DEMOLITION WORK.
9500CT
2a
X
X
2.
Separate
Permit & Plans
X
X
FLOOR MOUNTED WATER CLOSET - ADA
SEE SHEET P0.1 FOR SYMBOLS AND ABBREVIATIONS. SEE RISER DIAGRAMS FOR
ADDITIONAL DEMOLITION DETAILS.
COMMENTS
WASTE PIPING
X
WC-1
DESCRIPTION
1.
Copyright 2016 HKW Architects
STERN WILLIAMS ELFIN ONE PIECE, TERRAZO WITH GREY MARBLE CHIPS 24"x24" WITH 6" HIGH SIDES,
MOP BASIN. DRAIN BODY SHALL BE STAINLESS STEEL OR CHROME PLATED BRASS, CAST INTEGRAL AND
SHALL PROVIDE FOR A CAULK CONNECTION NOT LESS THAN 1" DEEP TO A 3" PIPE. STRAINER SHALL
BE CHROME PLATED BRASS.
CHICAGO WALL MOUNTED, 8" BODY FAUCET WITH ADJUSTABLE ARMS.
STERN WILLIAMS HOSE AND WALL HOOK.
WATER SUPPLY BOX
GUY GRAY WATER SUPPLY BOX, 20 GAUGE STEEL FACEPLATE AND BOX WITH WHITE POWDER COATING,
1/4 TURN VALVE, 1/2" SWEAT CONNECTION, WITH LEAD FREE WATER HAMMER ARRESTER.
10. NO CHANGES IN CONTRACT PRICE WILL BE ALLOWED FOR MINOR CHANGES IN LAYOUT OR LOCATION
REQUIRED TO AVOID INTERFERENCES, OBSTRUCTIONS, ETC. CONTRACT PRICE CHANGES WILL BE
CONSIDERED ONLY FOR CHANGES IN THE SCOPE OF THE PROJECT REQUIREMENTS. ALL SUCH SCOPE
CHANGES AND PRICE REVISIONS MUST BE AUTHORIZED IN WRITING. NOTIFY THE ENGINEER AT ONCE
SHOULD A DISCREPANCY OR OMISSION BE FOUND.
11. PIPING IN EXPOSED LOCATIONS SHALL BE CHROME PLATED UNLESS OTHERWISE INDICATED.
12. CHROME PLATED ESCUTCHEONS SHALL BE PROVIDED AT ALL LOCATIONS WHERE PIPES PENETRATE
WALLS IN EXPOSED LOCATIONS.
13. PROVIDE SEISMIC BRACING AS REQUIRED. SEE SCHEDULE FOR SPECIFICATIONS.
WC
1
FIXTURE TYPE
FIXTURE NUMBER
CONNECTION OF NEW TO EXISTING
D
Bid Set
PLUMBING SYMBOLS LEGEND
PNC Valley Park
PNC Bank
15. SPACES ABOVE CEILINGS ARE RETURN AIR PLENUMS UNLESS OTHERWISE INDICATED ON HVAC PLANS.
PIPING AND INSULATION IN CEILING PLENUMS SHALL HAVE A FLAME SPREAD OF 25 OR LESS AND A
SMOKE DEVELOPED RATING OF 50 OR LESS AS DETERMINED IN ACCORDANCE WITH ASTM STANDARD
E-84.
912 Meramec Station Road, Valley Park, MO 63021
14. ALL UTILITIES SERVING EXISTING AREAS SHALL REMAIN IN SERVICE AT ALL TIMES EXCEPT FOR SHORT
PERIODS OF INTERRUPTION FOR TIE IN OF NEW SERVICES TO EXISTING. ALL INTERRUPTIONS SHALL BE
SCHEDULED WITH OWNER, AND SHALL NOT BE SCHEDULED UNTIL NEW SERVICES ARE COMPLETE AND
READY FOR FINAL CONNECTION.
DRAIN
Revision Schedule
COLD WATER (CW)
No
Date
Description
HOT WATER SUPPLY (HW)
S
SOFT WATER
H
HARD WATER
T
TEMPERED WATER
140
G
GW
W
140 DEGREE HOT WATER
GAS PIPING
GREASE WASTE
SANITARY WASTE ABOVE GRADE
SANITARY VENT
DT
DRAIN TILE
ST
STORM DRAINAGE PIPING ABOVE GRADE
OD
OVERFLOW DRAINAGE PIPING ABOVE GRADE
PIPING BELOW GRADE (SEE PLANS)
PLUMBING TRAP
PIPE TURNING DOWN
PIPE TURNING UP
WATER HAMMER ARRESTER
BALL VALVE
FLOW CONTROL/BALANCE VALVE
PRESSURE RELIEF VALVE
The Seal and Signature apply only to the Document to
which they are Affixed, and Expressly Disclaim any
Responsibility for all other Plans, Specifications,
Estimates, Reports, or other Documents or Instruments
relating to or intended to be used for any part or parts of
the Architectural or Engineering Project.
Copyright © 2016 by SSC Engineering, Inc.
CHECK VALVE
GAS COCK
UNION
PRESSURE GAUGE
STRAINER
REDUCED PRESSURE BACKFLOW PREVENTOR (RPBFP)
TP
TRAP PRIMER
AFF
ABOVE FINISHED FLOOR
NTS
NOT TO SCALE
CI
CAST IRON
CO
CLEAN OUT
THRU-FLOOR
PLUMBING SHEET LIST
Sheet Number
Sheet Name
P0.1
PLUMBING SYMBOLS, ABBREVIATIONS & GENERAL NOTES
P1.1
PLUMBING WASTE & VENT PLAN
P2.1
PLUMBING DOMESTIC PIPING PLAN
SSC JOB# 2016123_BID SET - NOT FOR CONSTRUCTION
HOT WATER RETURN (REC)
April 11, 2016
16.008.00
PLUMBING
SYMBOLS,
ABBREVIATIONS
& GENERAL
NOTES
P0.1
Copyright 2016 HKW Architects
PLUMBING GENERAL NOTES:
1. REFER TO SHEET P0.1 FOR SYMBOLS AND GENERAL NOTES.
2. PRIOR TO ANY SAWCUTTING OF THE FLOOR SLAB, CONTRACTOR SHALL XRAY THE FLOOR TO
AVOID HITTING OTHER UTILITIES OR RE-BAR. COORDINATE EXACT ROUTE TO MINIMIZE
DISTURBANCE TO FLOOR SLAB. REVIEW AND COORDINATE ALL SAWCUTTING WITH LANDLORD
PRIOR TO WORK.
MISSOURI
5017 Washington Place Suite 200
St. Louis, M0 63108
3. EXISTING VENT AND WASTE PIPING FROM EXISTING LAV AND WATER CLOSET IN RESTROOMS
VENTED TO ROOF THROUGH TENANT WALL TO REMAIN.
314.361.0000 ph
314.361.9191 fax
4. ADJACENT TENANT SPACE NOT IN SCOPE.
IOWA
1000 Melrose Avenue
Iowa City, IA 52246
5. ITEMS SHOWN CROSS HATCHED TO BE DEMOLISHED.
PLUMBING DEMOLITION KEYED NOTES:
319.343.7055 ph
hkwarchitects.com
1
EXISTING FLOOR DRAIN TO BE REMOVED. PLUG AND CAP PIPE. PATCH FLOOR TO MATCH
EXISTING FLOOR FINISH.
2
EXISTING MOP SERVICE BASIN TO BE REMOVED. PLUG AND CAP PIPE. PATCH FLOOR TO
MATCH EXISTING FLOOR FINISH.
3
EXISTING VENT THROUGH ROOF.
18207 Edison Avenue
Chesterfield, M0 63005
636.530.7770 ph
636.530.7877 fax
PLUMBING RENOVATION KEYED NOTES:
ATM Vestibule
100
1
4
EXISTING LAVATORY SHALL BE DISCONNECTED AND REMOVED. EXISTING ROUGH-IN SHALL
REMAIN FOR NEW FIXTURE CONNECTIONS.
5
EXISTING WATER CLOSET SHALL BE DISCONNECTED AND REMOVED. EXISTING ROUGH-IN
SHALL REMAIN FOR NEW FIXTURE CONNECTIONS.
6
CUT AND REMOVE EXISTING FLOOR TO INSTALL NEW WASTE PIPE BELOW SLAB. CONNECT
TO EXISTING WASTE PIPING. PATCH FLOOR TO MATCH EXISTING FLOOR FINISH.
Off-Stage
103
Concierge
102
FD
2"
EX
Break Room
109
2"
PNC Bank
1
MSB
1
Janitor
107
Elec/Data
105
2
EWC
5
FD
EX
EX
Customer
Pantry
113
Office
118
LAV
EX
WC
WC
EX
EX
LAV
EX
MSB
Office
117
Office
116
5
Office
115
Self-Serve
Boxes
114
6 3"
1
6 2"
1
WC
Toilet
106
Toilet
108
Revision Schedule
WC
No
Date
Description
1
1
LAV
4
1
FD
EX
3
The Seal and Signature apply only to the Document to
which they are Affixed, and Expressly Disclaim any
Responsibility for all other Plans, Specifications,
Estimates, Reports, or other Documents or Instruments
relating to or intended to be used for any part or parts of
the Architectural or Engineering Project.
Copyright © 2016 by SSC Engineering, Inc.
EX
LAV
EX
NORTH
FD
Passage
111
PLUMBING WASTE & VENT PLAN - DEMOLITION
PLUMBING WASTE & VENT PLAN - RENOVATION
SCALE: 1/8" = 1'-0"
SCALE: 1/8" = 1'-0"
NORTH
3
SSC JOB# 2016123_BID SET - NOT FOR CONSTRUCTION
4
FD
Bid Set
S
Lobby
119
PNC Valley Park
Maintenance
104
912 Meramec Station Road, Valley Park, MO 63021
6
April 11, 2016
16.008.00
PLUMBING
WASTE & VENT
PLAN
P1.1
Copyright 2016 HKW Architects
PLUMBING GENERAL NOTES:
1. REFER TO SHEET P0.1 FOR SYMBOLS AND GENERAL NOTES.
2. ADJACENT TENANT SPACE NOT IN SCOPE.
3. ITEMS SHOWN CROSS HATCHED TO BE DEMOLISHED.
MISSOURI
5017 Washington Place Suite 200
St. Louis, M0 63108
PLUMBING DEMOLITION KEYED NOTES:
1
314.361.0000 ph
314.361.9191 fax
DISCONNECT AND REMOVE EXISTING PLUMBING FIXTURE. REMOVE PIPING ROUGH-IN AND
BRANCH PIPE BACK TO SUPPLY MAIN. CAP AT MAIN.
IOWA
1000 Melrose Avenue
Iowa City, IA 52246
2
DISCONNECT AND REMOVE EXISTING PLUMBING FIXTURE. EXISTING ROUGH-IN TO REMAIN
FOR NEW CONNECT TO NEW PLUMBING FIXTURE.
3
1/2"
hkwarchitects.com
EXISTING ELECTRIC WATER HEATER ABOVE CEILING TO BE REMOVED. CONNECTIONS
BRANCHING INTO ADJACENT SPACE TO BE CAPPED AND REMOVED. CONTRACTOR TO
COORDINATE WITH LANDLORD TO VERIFY WATER SERVICE IS AVAILABLE WITH ADJACENT
TENANT SPACE.
18207 Edison Avenue
Chesterfield, M0 63005
1/2"
1/2"
1/2"
1/2"
1/2"
636.530.7770 ph
636.530.7877 fax
PLUMBING RENOVATION KEYED NOTES:
1/2"
4
S
1/2"
6
1
WB
4
OPTIONAL1/2" COLD WATER PIPE TO SERVE TO COFFEE MAKER. CONTRACTOR TO BID AS
SEPARATE LINE ITEM. SEE ARCHITECTURAL DRAWING FOR MOUNTING HEIGHT.
5
EXISTING PRV VALVE / SPACE MAIN WATER SUPPLY. ACCESS THROUGH RESTROOM
CEILING ACCESS PANEL.
6
2-1/2" MAIN WATER SERVICE TO BUILDING WATER SUPPLY CONNECTION.
7
HOT AND COLD WATER PIPING TO EXISTING WATERCLOSETS AND LAVATORIES TO REMAIN.
8
EXISTING COLD WATER AND HOT WATER TO ADJACENT TENANT. DISCONNECT EXISTING
WATER HEATER PIPING JOINING WITH THE ADJACENT SPACE WATER HEATER. PLUG / CAP
SERVICE TO ADJACENT SPACE.
1
1/2"
1/2"
1/2"
319.343.7055 ph
MSB
2 1/2"
1
7
EWC
1
EWH
1
8
3
PLUMBING DOMESTIC WATER ISOMETRIC
NOT TO SCALE
ATM Vestibule
100
Off-Stage
103
Concierge
102
S
6
Maintenance
104
1/2"
1/2"
Janitor
107
4
Customer
Pantry
WB 113 1/2"
1
1/2"
1
2
2
MSB
1/2"
EX
LAV
EX
WC
EX
EWH
EX
WC
EX
LAV
EX
The Seal and Signature apply only to the Document to
which they are Affixed, and Expressly Disclaim any
Responsibility for all other Plans, Specifications,
Estimates, Reports, or other Documents or Instruments
relating to or intended to be used for any part or parts of
the Architectural or Engineering Project.
Copyright © 2016 by SSC Engineering, Inc.
NORTH
3
Office
118
Office
116
Office
117
2
Office
115
Self-Serve
Boxes
114
MSB
1
EWH
1
EWC
Passage
111
1
7
7
Toilet
106
WC
1
LAV
1
Toilet
108
5
WC
1
LAV
2
1
PLUMBING DOMESTIC WATER PLAN - DEMOLITION
PLUMBING DOMESTIC WATER PLAN - RENOVATION
SCALE: 1/8" = 1'-0"
SCALE: 1/8" = 1'-0"
NORTH
PNC Bank
Elec/Data
105
2 1/2"
Break Room
109
Revision Schedule
7
No
Date
Description
7
SSC JOB# 2016123_BID SET - NOT FOR CONSTRUCTION
Lobby
119
PNC Valley Park
1
Bid Set
FD
912 Meramec Station Road, Valley Park, MO 63021
FD
April 11, 2016
16.008.00
PLUMBING
DOMESTIC
PIPING PLAN
P2.1