section 26 05 33 - Adroit Construction

advertisement
Consolidated Rental Car Facility
Project No. 1206
Rogue Valley International-Medford Airport
April 2013
SECTION 26 05 33 - RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS
PART 1 GENERAL
1.1
SCOPE
A.
The work under this Section covers all raceway and boxes for electrical systems.
PART 2 PRODUCTS
2.1
MATERIAL AND EQUIPMENT
A.
2.2
2.3
Materials and equipment for this project shall be first quality, new materials, free from
any defects, in first class condition, with ratings as shown on these Drawings.
CONDUIT
A.
Galvanized Rigid Steel Conduit (GRS): Rigid steel conduit including couplings,
elbows, nipples, and other fittings shall be galvanized after fabrication by hot-dipping,
electroplating, or a metalizing process. Conduit bodies and covers shall be of cast
malleable galvanized ferrous materials. Provide covers with gaskets.
B.
Electrical Metallic Tubing (EMT): Electrical metallic tubing, including couplings and
elbows, shall meet the requirements of the NEC and Oregon Electrical Specialty
Code (OESC).
C.
Rigid PVC Conduit (PVC): Rigid polyvinyl chloride (PVC) conduit shall be schedule
40 UL listed for concrete-encased, direct burial underground, and exposed use. PVC
conduit shall be rated 90 degrees C.
D.
Flexible Conduit (flex): Flexible conduit shall be moistureproof flexible steel, polyvinyl
chloride jacketed, UL approved, and shall be Anaconda Sealtite conduit, Electriflex, or
equal. Flexible conduit used in dry, concealed areas for lighting fixtures may be nonmoistureproof flexible steel conduit, Anaconda Type CN, Triangle Tristeel, or equal.
E.
Metal Clad Cable (MC): Factory assembly of one or more insulated circuit
conductors, enclosed in an armor of interlocking sheath. Connectors and fittings
used on MC Cable shall be listed and identified for the cable type.
BOXES
A.
General:
1.
Boxes shall not be smaller than required to meet the minimum requirements
of the National Electrical Code (NEC).
2.
Install boxes in a rigid and satisfactory manner, and support boxes
independently of the conduit.
B.
Sheet Steel Boxes, Small (Up To 4” X 4”):
1.
These boxes shall include sizes up to 4 inches square and ganged switch
boxes.
2.
Sheet steel boxes shall be zinc- or cadmium-plated, and shall be of the onepiece stamped or drawn type, or welded, except when not available in the
size required.
3.
Provide boxes of adequate size without using box extensions.
4.
For hollow masonry construction, provide boxes of sufficient depth so that
RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS
260533 - 1 of 5
Consolidated Rental Car Facility
Project No. 1206
Rogue Valley International-Medford Airport
5.
April 2013
conduit knockouts or hubs are in the masonry void space.
Provide covers and device plates as called out under RACEWAY SYSTEM.
Type to be Used, in the Part, EXECUTION.
C.
Sheet Steel Boxes, Large (Larger Than 4” X 4”):
1.
Boxes shall be 16-gauge sheet steel, minimum, with welded seams.
2.
Boxes shall be NEMA 1, minimum, in dry locations and NEMA 3R, minimum,
in damp and wet locations.
3.
Provide hinged covers on boxes with length or width greater than 24 inches.
Hinges shall be full length, with stainless steel hinge pins. Hinged covers
shall have secure closing provisions. Provide draw-pull catches (two
minimum), three-point latch with a single handle, or clamps on three sides to
clamp the cover.
4.
Finish shall be ANSI 61 gray over a primer and rust inhibitor.
5.
Boxes shall be Hoffman, Tanco, Keystone, Electromate, or equal.
D.
Cast Boxes:
1.
Cast boxes shall be galvanized malleable ferrous metal, gasketed and
watertight, with threaded conduit hubs and mounting lugs. Boxes shall have
a minimum (inside) depth of 2 inches.
2.
Provide stamped steel covers with gaskets and stainless steel or galvanized
steel screws; except provide weatherproof cast covers for switches and
receptacles outdoors and in other wet or damp locations.
3.
Cast boxes shall be Crouse Hinds FD, Appleton FD, or equal.
PART 3 EXECUTION
3.1
RACEWAY SYSTEM
A.
General: Raceway system shall be installed in accordance with the National
Electrical Code (NEC) and Oregon Electrical Specialty Code (OESC). Unless
otherwise specified or indicated, wiring shall consist of insulated conductors installed
in raceways of the types indicated.
B.
Types to be Used: Minimum size conduit shall be 1/2 inch; except 3/4-inch minimum
shall be used for embedded conduit, unless indicated otherwise on the Drawings.
Use the following types of conduit and boxes for the locations listed below, unless
shown otherwise on the Drawings.
1.
Use electrical metallic tubing (EMT) with sheet steel boxes and stamped steel
covers in exposed, interior, dry locations.
2.
Concealed locations: In concealed locations (sheet rock walls, ceilings), use
EMT conduit with sheet steel boxes. Use stamped steel covers and device
plates in dry locations, and use cast weatherproof covers and device plates
with gaskets in wet and damp locations; except use plastic covers and device
plates in dry, finished areas.
3.
EMT may be used in place of PVC in dry, concealed locations, and GRS may
be used as a substitute in any location.
4.
Use liquidtight flexible metal conduit (flex) for the last 18 to 36 inches of
conduit run to a piece of equipment where required to isolate vibration or to
facilitate maintenance or adjustment. Flexible metal conduit (nonmoistureproof) may be used in dry, concealed areas for lighting fixtures.
5.
Use MC Cable in concealed interior locations (sheet rock walls, ceilings). Not
to be used for home runs.
6.
Use rigid polyvinyl chloride (PVC) conduit for buried and embedded locations,
except use galvanized rigid steel (GRS) at least 5 feet on both sides of
RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS
260533 - 2 of 5
Consolidated Rental Car Facility
Project No. 1206
Rogue Valley International-Medford Airport
7.
April 2013
penetrations through footings and outside walls, under equipment mounting
pads, where embedded in exterior light pole foundations, and where conduit
changes from underground to exposed or from embedded to exposed.
Use galvanized rigid steel conduit (GRS) outdoors and in wet locations (car
wash bay). Provide cast weatherproof covers and device plates with gaskets
in wet and damp locations.
C.
Boxes:
1.
Provide each outlet in the wiring or raceway systems with a box to suit the
conditions encountered. Provide flush or recessed fixtures with separate
junction boxes when required by the fixture terminal temperature requirements. Boxes used with concealed conduits shall be flush mounted, unless
otherwise indicated on the Drawings.
2.
Install boxes in a rigid and satisfactory manner, and support boxes
independently of the conduit.
D.
Installation:
1.
Conduit system installation shall meet or exceed the requirements of the
NEC. Raceways shall be entirely free of obstructions or shall be replaced.
All conduit shall be reamed, deburred, and cleaned for proper introduction of
wires and cables. Immediately after installation, plug or cap all conduit ends
with watertight and dusttight conduit seals until the time for pulling wires.
2.
Conduit shall be of the greatest practicable single length between joints.
3.
Install conduit, boxes, and fittings outdoors or in other wet locations so as to
prevent water from entering the conduit. Do not run conduit through
equipment foundation pads.
4.
Empty ducts and conduits shall be identified at both ends and shall be
capped and provided with a flat pull tape (Mule Tape, or equal).
5.
For PVC conduit, use factory-made ells where applicable. Use approved
heating methods for forming all other bends. Provide expansion joints as
required by the NEC and Oregon Electrical Specialty Code (OESC) and as
recommended by the manufacturer. When joining PVC conduit to metallic
fittings, use approved PVC terminal adapters. When joining PVC conduit to
rigid steel conduit, use an approved PVC female adapter. PVC conduit joints
shall be solvent-welded with solvent recommended by the conduit
manufacturer. Where PVC conduit is used, a separate grounding conductor
shall be run with the conductors.
6.
Concealed, embedded, and buried conduits shall emerge at right angles and
shall have none of the curved portion of a bend exposed. Embedded and
underground ells shall be galvanized rigid steel conduit.
7.
Where conduit size is 4 inches or less, final connection to motors, wall- or
ceiling-mounted fans, dry transformers, and to other equipment where flexible
connection is desired or required to minimize vibration or to facilitate maintenance or removal of equipment, shall be made with flexible conduit. Length
shall be 18 inches to 36 inches, unless otherwise approved by the Engineer.
8.
Flexible conduit shall not be used as a ground. Where flexible conduit is
used, a separate grounding conductor shall be run with the conductors.
Flexible conduit shall be secured with conduit clamps or equivalent means
except where the flexible conduit is fished and where sections less than 4
feet in length are used in concealed areas for lighting fixtures.
9.
For steel conduit installed underground, wrap the entire length with tape using
1/2-inch overlap. Use PVC-based pressure-sensitive all-weather tape, 20-mil
minimum thickness, as recommended by the manufacturer for corrosion
protection of underground conduits. Tape shall be Scotchwrap 51 or equal.
RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS
260533 - 3 of 5
Consolidated Rental Car Facility
Project No. 1206
Rogue Valley International-Medford Airport
3.2
April 2013
UNDERGROUND AND EMBEDDED CONDUIT
A.
Arrangement and Routing:
1.
Arrange multiple conduit runs substantially in accordance with details shown
on the Drawings.
2.
Make minor changes in location or cross section as necessary to avoid
obstructions or conflicts.
3.
Where piping on other utility systems are encountered or being installed
along a raceway route, maintain a 12-inch minimum vertical separation
between raceways and other systems at crossings. Maintain a 12-inch
minimum separation between raceways and other systems in parallel runs.
Do not place raceways over valves or couplings in other piping systems
which may restrict access.
B.
Except as otherwise indicated, cover for underground and embedded conduit shall be
as tabulated in Table 1, except conduit under building slabs may be just below the
slab. Do not embed conduit in slabs. Conduit installation shall meet the requirements
of the NEC.
TABLE 1
COVER REQUIREMENTS FOR BURIED RACEWAYS
Type of Buried Raceway
Direct-Buried Conduit
Areas of Vehicle
Access (Roads,
Parking Areas, etc.)
36 inches,
with warning
tape 12 inches
above conduit
Other Areas
18 inches,
with warning
tape 12 inches
above conduit
C.
Separate parallel runs of four or more conduits in a single trench or embedded duct
bank with preformed, nonmetallic spacers designed for the purpose. Install spacers
at 6 feet or at intervals not greater than that specified in the NEC for support of the
type of conduit used. Support conduits installed in fill areas suitably to prevent
accidental bending until backfilling is complete.
D.
Trenching and Backfill:
1.
Trench bottoms shall be free of rocks and other hard objects. Bedding
material shall be used for a depth of 3 inches below the conduit or cable, and
bedding material shall be used for the zone 6 inches above the conduit or
cable.
2.
Bedding material shall contain no rocks larger than 3/4 inch in diameter and
shall be free from roots and debris.
3.
Unless otherwise shown on the Drawings, that zone from 6 inches above the
conduit to the top of the trench shall be the material removed from the trench;
except that it shall contain no rocks larger than 6 inches and shall be free of
roots and debris.
4.
Where conduit trenches are located in roads or in structural backfill, the
compaction requirements shall be as required for those areas. Where
conduit trenches are located in an area where backfill material specifications
are more rigid than those of this section, the trench backfill shall meet the
more rigid specification. In any event, trench backfill compaction shall be at
least equal to that of the material adjacent to the trench.
5.
Conduits shall be placed parallel in the bottom of the trench. Where conduits
are required to cross, they shall be separated by a minimum of 3 inches of
bedding material. Where more than one level of conduit are placed in the
RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS
260533 - 4 of 5
Consolidated Rental Car Facility
Project No. 1206
Rogue Valley International-Medford Airport
6.
7.
8.
E.
3.3
April 2013
same trench, they shall be separated by a minimum of 3 inches of bedding
material.
As shown in Table 1, backfill shall include warning tape over the entire length
of the run.
Conduit trenches in areas to be paved or improved under this project shall be
installed and backfilled before the area is paved or improved.
All existing improvements damaged as a result of the Contractor’s operation
shall be reconstructed by the Contractor at no cost to the Owner.
Penetrations:
1.
Penetration of any fire-rated partition shall be protected in accordance with
the Uniform Building Code 709 and 710.
WARNING TAPE
A.
Provide heavy-gauge, yellow plastic tape of 6-inch minimum width for use in trenches
containing electric circuits. Utilize tape made of material resistant to corrosive soil.
Use tape with printed warning that an electric circuit is located below the tape.
B.
Manufacturers and types: ITT Blackburn Type YT or RT, Griffolyn Co. Terra-Tape, or
equal.
END OF SECTION
RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS
260533 - 5 of 5
Consolidated Rental Car Facility
Project No. 1206
Rogue Valley International-Medford Airport
April 2013
SECTION 26 50 00 - LIGHTING
PART 1 GENERAL
1.1
SCOPE
A.
The work under this Section covers all lighting equipment for this project.
PART 2 PRODUCTS
2.1
MATERIAL AND EQUIPMENT
A.
Materials and equipment for this project shall be first quality, new materials, free from
any defects, in first class condition, with ratings as shown on these Drawings.
B.
Lighting fixtures shall be of the types and sizes shown on the Drawings, and shall be
furnished and installed complete with mounting devices and junction boxes where
required.
C.
Linear fluorescent lamps provided as new or replacement shall be TCLP (Toxicity
Characteristic Leaching Procedure) compliant.
PART 3 EXECUTION
3.1
GENERAL
A.
Work shall be performed in a workmanlike manner by craftsmen skilled in the
particular trade. Work shall be performed in accordance with the Drawings,
Specifications, manufacturers’ recommendations, and the best practice of the trade.
Completed work shall present a neat and finished appearance. Reference items
below for specific requirements.
1.
Locations of light fixtures and other electrical system components shown on
Drawings are approximate unless dimensioned. Check for and resolve
conflicts with openings, structural members, and equipment having fixed
locations.
2.
Deliver lamps to the project in their original cartons. After construction of the
total project is completed, wash fixtures, clean lamps, touch up any paint
scratches or chips, remove labels from fixture lenses, and replace noisy
ballasts.
END OF SECTION
LIGHTING
265000 - 1 of 1
Consolidated Rental Car Facility
Project No. 1206
Rogue Valley International-Medford Airport
April 2013
SECTION 28 31 00 – FIRE ALARM SYSTEM
PART 1 GENERAL
1.1
1.2
1.3
WORK INCLUDED
A.
This Specification covers the fire alarm system, complete. Furnish all equipment to
provide a complete, addressable fire alarm system, as specified herein and as shown
on the Drawings. Components not specifically listed in this Section or shown on the
Drawings, but which are required for proper operation of the system, shall be
provided. All work shall be done to the best practices of the industry. All components
shall meet applicable requirements of NEC, NFPA, UL, local requirements, and the
State and local Fire Marshal.
B.
This project covers the fire alarm system for a 8,950 square foot Consolidated Car
Rental Facility.
C.
Principal items required are as follows:
1.
Fire alarm control panel (FACP)
2.
Fire alarm system initiating devices
a. Pull stations
b. Photoelectric smoke detectors
3.
Fire alarm notification devices
a. Horns/strobes
4.
Annunciator
5.
Sprinkler water flow switches
D.
Refer to the Drawings for quantities, descriptions, and part numbers of each item.
E.
Fire alarm, signaling wire, and conduit requirements are shown on the Drawings.
FIRE ALARM SYSTEM FUNCTIONAL REQUIREMENTS
A.
The fire alarm system shall consist of equipment, installation, and programming that
result in a complete and functional system that meets the requirements of the State
and local Fire Marshals.
B.
The system shall monitor devices installed under this contract. See drawings for
quantities and locations of devices.
C.
Operator control of the fire alarm system shall be possible at the FACP. Operator
control includes arming or disarming the system, acknowledging alarms, and
observing system status.
D.
All field circuits shall be supervised. Field circuit failure shall occur on open circuit,
closed circuit, or foreign grounded circuit. On field wiring failure, the operator shall be
able to discern the source of the failure on the control panel. In the event of alarm
system trouble arising from field circuit failure, logic unit failure, or loss of 60-Hz
power, then an alarm shall be reported.
QUALITY ASSURANCE
A.
All equipment and materials used shall be standard components, regularly
manufactured and of the same manufacturer.
FIRE ALARM SYSTEM
283100 - 1 of 12
Consolidated Rental Car Facility
Project No. 1206
Rogue Valley International-Medford Airport
1.4
April 2013
B.
All systems and components shall have been thoroughly tested and proven in actual
use.
C.
All equipment shall be listed by Underwriters’ Laboratories.
D.
Equipment shall be manufactured by the indicated suppliers, or others as allowed by
UL listing. All equipment shall be supplied and warranted by the system installer for
no less than 1 year from date of completion of acceptance testing. Such warranty
shall be required of the installing contractor, even if in excess of original manufacturer
warranties.
E.
Contractor shall demonstrate satisfactory installations of comparable systems within
the immediately preceding 5 years, including references.
F.
Contractor shall demonstrate ability to provide response to affect repair within 4 hours
by factory-certified personnel, during the warranty period.
SUBMITTALS
A.
Product submittals shall be submitted within 30 days after the Notice to Proceed. In
addition, no products shall be fabricated or shipped until the applicable submittals
have been reviewed by the Engineer.
B.
Submittal packages shall be assembled as listed below:
1.
Initial submittal
2.
Fire Marshal-approved submittal
3.
Testing submittals
4.
Operation and maintenance manuals
C.
Initial Submittal: Prior to fabricating or shipping any material, submit the following
information and documentation. This package shall be stand-alone and suitable for
forwarding by the Contractor to the Fire Marshal, following review by the Engineer.
1.
Table of contents.
2.
Description of Project. Include location/address; Owner’s name and
telephone number; and Supplier’s name, address, and telephone number.
3.
Complete components list showing quantities, descriptions, manufacturers,
model numbers, and chosen options.
4.
Manufacturer’s specification sheets on all equipment.
5.
Building floor plan(s) showing all devices, zoning, and room identification.
6.
Interconnection diagram which shows all components and interconnecting
wire and conduit, including existing devices to be revised.
7.
Point-to-point wiring diagram for all items within panel(s).
8.
Panel layout drawings.
9.
Symbol legend for devices shown on submitted drawings.
10.
Elevation views showing device installations.
11.
Identification of type of wiring used.
12.
Details on support and anchorage of equipment.
13.
Detail drawings(s) showing conduit penetrations of fire walls, if any.
14.
Calculations providing that battery requirements are met or exceeded.
Provide calculations which show that required device starting and running
voltages will be within published equipment limits.
15.
Sequence of operations/events: Include detail on arming/disarming, audible
alarming, visual indications, and acknowledge sequencing.
16.
Manufacturer’s installation instructions.
FIRE ALARM SYSTEM
283100 - 2 of 12
Consolidated Rental Car Facility
Project No. 1206
Rogue Valley International-Medford Airport
1.5
1.6
April 2013
D.
Fire Marshal-Approved Submittal: Following review of initial submittal by the
Engineer, arrange for local Fire Marshal review of the approved initial submittal.
Obtain the Fire Marshal’s written approval and submit evidence of approval prior to
proceeding.
E.
Testing submittals are required as specified later in this Section.
F.
Operation and maintenance manual submittals are required as specified later in this
Section.
G.
Should any item which deviates from these Specifications be included, the deviation
shall be clearly indicated and explained at the time of submittal.
H.
Submittals shall be complete, neat, orderly, and indexed. The Contractor shall check
submittals for number of copies, adequate identification, correctness, and compliance
with the Drawings and Specifications, and shall initial all copies.
I.
Revise and resubmit all submittal information until acceptable to the Engineer.
APPROVALS
A.
Obtain all necessary approvals and permits from local Authorities for all materials to
be supplied, methods of installation and system operations, as required herein and by
the local Authorities.
B.
The entire installation, including materials and equipment shall meet or exceed the
minimum standards and requirements of the following:
1.
Underwriters’ Laboratories, Inc., listing service.
2.
NFPA 72 and National Fire Codes.
3.
Codes as accepted and/or modified by the local Authorities:
a.
Oregon Building Code.
b.
Oregon Fire Code.
c.
Oregon Electrical Specialty Code.
4.
American Disabilities Act (ADA).
5.
Underwriters’ Laboratories, UL 1971 for Hearing Impaired.
SYSTEM OPERATION
A.
General Operation:
1.
Alarm Verification Operation
a.
When an alarm condition is detected on an Initiating Device Circuit
which has been programmed for Alarm Verification, the system will
automatically enter the ALARM verification mode. If the alarm
condition is still present after a preset time period of 30 seconds, the
system will automatically enter the alarm mode. If a second alarm
occurs during the verification period, the system will immediately
enter alarm mode. If both smoke detectors and dry contact devices
are connected to the same verified circuit, the smoke detectors will
be verified but not the dry contact devices.
2.
Signal Silence Operation
a.
All Notification Appliance Circuits shall have the option to turn off if
the panel signal silence switch is manually activated.
FIRE ALARM SYSTEM
283100 - 3 of 12
Consolidated Rental Car Facility
Project No. 1206
Rogue Valley International-Medford Airport
1.7
1.8
STARTUP, OPERATING, AND MAINTENANCE SERVICE
A.
The Contractor shall obtain from the manufacturer(s) the services of a competent
representative (manufacturer’s field services representative) having complete
knowledge of proper startup, operation, and maintenance of the equipment, to furnish
technical direction as required.
B.
Operation and maintenance training shall be provided. Not less than 2 hours of
training shall be provided at times scheduled with and convenient to The Owner.
SPARE PARTS
A.
1.9
1.10
April 2013
Provide the following spare equipment:
1.
Five fuses of each type used.
OPERATION AND MAINTENANCE MANUALS
A.
Provide three copies of operation and maintenance manuals. Include the following:
1.
Corrected submittals as required herein.
2.
Record (as-built) wiring diagrams and equipment Drawings.
3.
For all equipment suppliers, list of current names, addresses, and telephone
numbers of those who should be contacted for service, information, and
assistance.
4.
Record (as-built) Contract Drawings marked with red pencil to show work
revisions and raceway and cable where different from the original Drawings.
Prepare by obtaining new, clean sets of Contract Drawings from the
Engineer, and pay all costs for same. Each manual set shall have original
red pencil marks (not copies).
5.
Test reports.
B.
Material shall be clean and filed under dividers with headings in accordance with the
Specification item title.
WARRANTY
A.
The work and materials covered in this Section shall be guaranteed for a period of
1 year from the date of acceptance thereof against defective materials, design, and
workmanship.
PART 2 PRODUCTS
2.1
GENERAL
A.
Provide all first-quality new materials, free from any defects, and suitable for the
intended use and the space provided. Provide materials approved by UL and NFPA
wherever standards have been established by that organization. Materials for the fire
alarm system shall be approved by the Fire Marshal having jurisdiction.
B.
Where two or more units of the same class of material or equipment are required,
provide products of a single manufacturer. Component parts of materials or
equipment need not be products of the same manufacturer.
C.
The systems specified under this Section shall be complete. Furnish and install all
incidental items not specifically shown or specified which are required by good
practice to provide the complete systems specified herein.
FIRE ALARM SYSTEM
283100 - 4 of 12
Consolidated Rental Car Facility
Project No. 1206
Rogue Valley International-Medford Airport
2.2
2.3
April 2013
D.
Wiring shall be brought to master terminal blocks. Arrange wiring neatly cut to proper
length, and remove surplus wire. Bundle wires with tie straps or other suitable
product, and tie down securely. Hinge wiring and wiring that will be subjected to
bending during maintenance or other operations shall be arranged so that any wire
bending or twisting will be around that longitudinal axis of the wire. Where wires or
cables pass through holes or across edges of sheet metal, rubber grommets shall be
installed in order to prevent insulation chafing.
E.
Wiring shall not be spliced or tapped except at device terminals, on terminal blocks,
or at approved “T” connections for SLC loops.
FIRE ALARM SYSTEM COMPONENTS
A.
Refer to the drawings. Prior to purchasing parts, perform a field investigation to verify
site conditions. In the event that model numbers have been superseded, the latest
listed products shall be provided, at comparable or higher functionality.
B.
Provide all components required for a complete and operable system meeting the
requirements in these specifications. The design drawings do not show all required
components.
EQUIPMENT
A.
Fire Alarm Control Panel (FACP):
1.
The system control panel shall be configured with all required components,
modules, etc., to provide for the complete operation of the system. The
system shall also be configured to support six mapnet circuits and support
one remote annunciator. Fire alarm control panel cabinet shall be surface
mounted, red in color. The control panel cabinet shall contain required space
for all components involved, and shall be sized for required expansion to
include spare capacities as indicated within this Specification or construction
Drawings.
2.
FIRE ALARM SYSTEM
System Capacity and General Operation
a.
The control panel shall be capable of expansion as specified above.
b.
The CPU shall provide the following controls and indicators used by
the system operator:
AC POWER
(Green LED)
SYSTEMS ALARM
(Red LED)
SUPERVISORY
(Yellow LED)
SYSTEM TROUBLE
(Yellow LED)
SIGNALS SILENCED
(Yellow LED)
POWER TROUBLE
(Yellow LED)
ACKNOWLEDGE
(Momentary Switch)
SIGNAL SILENCE
(Momentary Switch)
SYSTEM RESET
(Momentary Switch)
DISABLE/ENABLE
(Momentary Switch)
EVACUATION DRILL (Function Key)
(Momentary Switch)
c.
The system shall be fully programmable, configurable, and
expandable in the field without the need for special tools or PROM
programmers, and shall not require replacement of memory ICs.
d.
All programming shall be accomplished through manufacturer’s listed
instructions with all required computer hardware and software
provided to the Owner as specified above.
e.
Entry into program mode, if requiring a special key and/or a special
password, shall be provided to the Owner.
283100 - 5 of 12
Consolidated Rental Car Facility
Project No. 1206
Rogue Valley International-Medford Airport
3.
4.
5.
April 2013
Central Processing Unit Module
a.
The central processing unit (CPU) module will communicate, monitor,
and control all other modules in the panel. Removal, disconnection,
failure, or change of type of any control panel module shall be
detected and reported by the CPU as a module failure. The CPU
shall contain and execute all custom programs for specific action to
be taken if a fire situation is detected in the system. Programming
shall be held in non-volatile memory, and shall not be lost even if
system primary and secondary power failure occurs.
Enclosures
a.
The control panel shall be housed in the manufacturer’s UL-listed
cabinet suitable for surface or semi-flush mounting.
b.
The black box and door shall be constructed of .060 steel with
provisions for electrical conduit connections into the sides and top.
c.
The door shall provide a key lock and shall include a glass or other
transparent opening for viewing of all indicators. For convenience,
the door shall be selectable for either right- or left-hand hinging.
Power Supply
a.
The main power supply for the fire alarm control panel shall provide
all control panel and peripheral device power needs.
b.
All power supplies shall meet current UL 864 Standards and NFPA
requirements for power-limited operation on all notification and
initiating circuits.
c.
Positive-temperature-coefficient thermistors, circuit breakers, and
other overcurrent protection shall be provided on all power outputs.
The power supply shall provide an integral battery charger for use
with batteries up to 100 AH, or may be used with external battery and
charger systems. Battery arrangement may be configured in the
field.
d.
The main power supply shall continuously monitor all field wires for
Earth Ground conditions and shall have the following LED
indications:
1)
Ground Fault
2)
Battery Fail
3)
AC Power Fail
e.
The power supply shall include provisions to add a battery voltmeter
and ammeter.
B.
Batteries:
1.
Battery shall have sufficient capacity to power the fire alarm system for not
less than 24 hours, plus 90 minutes of alarm upon normal ac power failure.
2.
The batteries are to be completely maintenance free. No liquids are required.
Fluid level checks, refilling, spills, and leakage shall not be required.
3.
If necessary to meet requirements, external battery and charger systems may
be used.
C.
Notification Appliances:
1.
Programmable Electronic Horns
a.
Electronic horns shall be field programmable without the use of
special tools, to provide temporal (Uniform Fire Alarm Signal) slow
whoop, or continuous tone with an output sound level of at least
90 dBA measured at 10 feet from the device.
b.
Shall be flush or surface mounted as shown on Drawings.
2.
Notification Appliances shall be powered from a power supply. The quantity
of power supplies shall be based upon no less than two notification appliance
FIRE ALARM SYSTEM
283100 - 6 of 12
Consolidated Rental Car Facility
Project No. 1206
Rogue Valley International-Medford Airport
3.
D.
April 2013
circuits per floor or as necessary to maintain a maximum calculated point-topoint voltage drop of less than 10% of the normal operating voltage of the
circuit. Voltage drop is subject to field verification during acceptance testing.
Power supply NAC circuits shall be individually monitored for trouble
conditions by the control panel.
All NAC device locations shown on construction documents are considered
as representative locations. The installing contractor is responsible for
providing sufficient audible devices to meet the requirements of NFPA 72 for
a system operating in the public mode and sufficient visible devices to comply
with the provisions of NFPA 72 and ADDAG, at no additional costs to the
Owner.
Additional System Components:
1.
Weatherproof Equipment
a.
Devices mounted in non-standard environments shall be approved
for the use and similar to the specified units.
2.
Waterflow Switches
a.
Waterflow switches shall be an integral, mechanical, non-coded, nonaccumulative retard type.
b.
Waterflow switches shall have an alarm transmission delay time
which is conveniently adjustable from 0 to 60 seconds. Initial settings
shall be 30-45 seconds.
c.
All waterflow switches shall come from a single manufacturer and
series.
d.
Waterflow switches and valve tamper switches shall be provided and
connected under this Section but installed by the fire sprinkler
contractor.
e.
Where possible, locate waterflow switches a minimum of 1 foot from
a fitting which changes the direction of the flow, a minimum of 3 feet
from a valve, and manufacturers listed instructions.
f.
The fire sprinkler system shall be provided with vane-type water flow
switches as necessary to indicate only the floor with water flow
occurring, per NFPA 13.
g.
Any required time delays for water surge shall be provided by the
water flow switch. No delays shall be used by the programming of
the software of the fire alarm control panel.
3.
Sprinkler and Standpipe Valve Supervisory Switches
a.
Any above-ground fire sprinkler control valves shall be provided with
appropriate tamper switches that provide a distinct supervisory alarm
at the control panel and off-site retransmission of the distinct
supervisory alarm.
b.
Each sprinkler system water supply control valve riser, zone control
valve, and standpipe system riser control valve shall be equipped
with a supervisory switch. Standpipe hose valves, and test and drain
valves shall not be equipped with supervisory switches.
c.
The switch shall be mounted so as not to interfere with the normal
operation of the valve, and adjusted to operate within two revolutions
toward the closed position of the valve control, or when the stem has
moved no more than one-fifth of the distance from its normal
position.
d.
The supervisory switch shall be contained in the weatherproof
aluminum housing, which shall provide 3/4-inch conduit entrance and
incorporate the necessary facilities for attachment to the valves.
e.
The switch housing shall be finished in red baked enamel.
f.
The entire installed assembly shall be tamper proof and arranged to
cause a switch operation if the housing cover is removed, or if the
FIRE ALARM SYSTEM
283100 - 7 of 12
Consolidated Rental Car Facility
Project No. 1206
Rogue Valley International-Medford Airport
4.
5.
E.
April 2013
unit is removed from its mounting. The Owner shall be provided
three of any specialized tools used for normal access of the device.
g.
Valve supervisory switches shall be provided and connected under
this Section and installed by fire sprinkler contractor.
Remote Control Relays
a.
DPDT relays, suitable for 24V dc coil operation and with 5-amp
contacts resistive load at 120V ac. One required for each fan and/or
damper to be controlled, and for other devices as noted.
Damper Limit Switches and Control Electric Pneumatic Relays: Supplied and
installed as part of the Mechanical Division of work. All electrical connections
and wiring to the devices shall be provided as part of the work of this Division.
System Components – Addressable Devices:
1.
Addressable Devices – General
a.
Addressable devices shall use the manufacturers address setting
method, such as a dip switch.
b.
Detectors shall be intelligent (analog) and addressable, and shall
connect with two wires to the fire alarm control panel signaling line
circuits.
c.
Addressable smoke and thermal detectors shall provide alarm and
power/polling LEDs. LEDs shall flash under normal conditions,
indicating that the detector is operational and in regular
communication with the control panel, and LEDs shall be placed into
steady illumination by the control panel, indicating that an alarm
condition has been detected. If required, the LED flash shall have
the ability to be removed from the system program. An output
connection shall also be provided in the base to connect an external
remote alarm LED if required.
d.
The fire alarm control panel shall permit detector sensitivity
adjustment through field programming of the system. Sensitivity shall
be automatically adjusted by the panel on a time-of-day basis.
e.
Using software in the FACP, detectors shall automatically
compensate for dust accumulation and other slow environmental
changes that may affect their performance. The detectors shall be
listed by UL as meeting the calibrated sensitivity test requirements of
NFPA 72.
f.
The detectors shall be ceiling-mount and shall include a separate
twist-lock base with tamper proof feature.
g.
The detectors shall provide a test means whereby they will simulate
an alarm condition and report that condition to the control panel.
Such a test may be initiated at the detector itself (by activating a
magnetic switch) or initiated remotely on command from the control
panel.
h.
Detectors shall also store an internal identifying type code that the
control panel shall use to identify the type of device (ION, PHOTO,
THERMAL).
i.
Detectors will operate in an analog fashion, where the detector simply
measures its designed environment variable and transmits the
analog value to the FACP based on real-time measured values. The
FACP software, not the detector, shall make the alarm/normal
decision, thereby allowing the sensitivity of each detector to be set in
the FACP program and allowing the system operator to view the
current analog value of each detector.
j.
Detectors shall provide address-setting means using decimal
switches and shall also store an internal identifying code that the
control panel shall use to identify the type of device. LEDs shall be
FIRE ALARM SYSTEM
283100 - 8 of 12
Consolidated Rental Car Facility
Project No. 1206
Rogue Valley International-Medford Airport
2.
3.
4.
5.
FIRE ALARM SYSTEM
April 2013
provided that shall flash under normal conditions, indicating that the
device is operational and is in regular communication with the control
panel.
Manual Fire Alarm Pull Stations
a.
Manual fire alarm pull stations shall be addressable double-action
break glass type, and on command from the control panel, send data
to the panel representing the state of the manual switch and the
addressable communication module status. They shall use a key
operated test-reset and shall be designed so that after actual
emergency operation, they cannot be restored to the normal use
except by the use of a key.
b.
All operated stations shall have a positive, visual indication of
operation and utilize a key type reset.
c.
Manual stations shall be constructed of Lexan with clearly visible
operating instructions provided on the cover. The word FIRE shall
appear on the front of the stations in raised letters.
Intelligent Photoelectric Smoke Detector
a.
Smoke sensors shall be analog addressable photoelectric type, using
an independent base. The base shall be of a common type from the
manufacturer so as to allow for either smoke or heat sensors to be
installed, without replacement of the base. The detectors shall use
the photoelectric (light-scattering) principle to measure smoke
density and shall, on command from the control panel, send data to
the panel representing the analog level of smoke density.
Addressable Control Module
a.
Addressable control modules shall be provided to supervise and
control the operation of compatible, 24V dc powered, polarized,
audio/visual notification appliances. For fan shutdown and other
auxiliary control functions, the control module may be set to operate
as a dry contract relay.
b.
The control module shall mount in a standard 4-inch-square,
2-1/8-inch-deep electrical box, or to a surface-mounted backbox.
c.
The control module NAC may be wired for Class A/B with up to
1 amp of inductive A/V signal, or 2 amps of resistive A/V signal
operation, or as a dry contact (Form-C) relay. The relay coil shall be
magnetically latched to reduce wiring connection requirements, and
to ensure that 100% of all auxiliary relay or NACs may be energized
at the same time on the same pair of wires.
d.
Audio/visual power shall be provided by a separate supervised power
circuit from the main fire alarm control panel or from a supervised,
UL- listed remote power supply.
e.
The control module shall be suitable for pilot duty applications and
rated for a minimum of 0.6 amps at 30V dc.
Isolator Module
a.
Isolator modules shall be provided to automatically isolate wire-towire short circuits on an SLC Class A or Class B branch and NAC
circuit. The isolator module shall limit the number of modules or
detectors that may be rendered inoperative by a short circuit fault on
the SLC loop segment or branch. At least one isolator module shall
be provided for each SLC loop and each NAC circuit. Location of
module shall be clearly indicated in the shop drawing submittals.
b.
If a wire-to-wire short occurs, the isolator module shall automatically
open-circuit (disconnect) the SLC. When the short circuit condition is
corrected, the isolator module shall automatically reconnect the
isolated section.
c.
The isolator module may require a distinct address-setting, and its
283100 - 9 of 12
Consolidated Rental Car Facility
Project No. 1206
Rogue Valley International-Medford Airport
d.
April 2013
operations shall be totally automatic. It shall not be necessary to
replace or reset an isolator module after its normal operation.
The isolator module shall mount in a standard 4-inch-deep electrical
box or in a surface-mounted backbox. It shall provide a single LED
that shall flash to indicate that the isolator is operational, and shall
illuminate steadily to indicate that a short circuit condition has been
detected and isolated.
PART 3 EXECUTION
3.1
3.2
3.3
GENERAL
A.
Work shall be performed in a workmanlike manner by craftsmen skilled in the
particular trade. Work shall be performed in accordance with the Drawings,
Specifications, manufacturer’s recommendations, and the best practice of the trade.
Completed work shall present a neat and finished appearance.
B.
Coordinate work with the Architect, Owner, and the work of other trades to avoid
conflicts, errors, delays, and unnecessary interference during construction.
PROTECTION DURING CONSTRUCTION
A.
Throughout this Contract, provide protection for materials and equipment against loss
or damage. Protect materials and equipment from the effects of weather. Prior to
installation, store items to be installed in indoor locations.
B.
Following installation, protect materials and equipment from corrosion, physical
damage, and the effects of moisture on insulation. Keep openings in boxes or
equipment closed during construction.
MATERIAL AND EQUIPMENT INSTALLATION
A.
Installation shall be in accordance with the NFPA 72 local and state codes, as shown
on the Drawings, and as recommended by the major equipment manufacturer.
B.
All conduit, junction boxes, conduit supports, and hangers shall be concealed in
finished areas and may be exposed in unfinished areas. Smoke detectors shall not be
installed prior to the system programming and test period. If construction is ongoing
during this period, measures shall be taken to protect smoke detectors from
contamination and physical damage.
C.
Conduit: All conduit and its installation shall be in accordance with Section 26 05 33.
All fire alarm system conduits shall be externally identified at no greater than 20-foot
intervals and at junction boxes by permanent red paint suitable for the purpose. Box
cover shall be red in color. Exposed flexible conduit shall be liquidtight and shall not
exceed 3 feet in length, and shall transition properly into metallic conduit.
D.
Wire and cable: All wiring shall be installed in metal conduit or within equipment.
Conductors shall be installed in accordance with Section 26 05 19. Conductors within
equipment enclosures shall be carefully cabled and laced. Minimum conductor size
for NAC circuits shall be No. 14 AWG, standard copper, THHN insulation, installed
within metallic conduit. Sizing of wire shall be subject to a maximum voltage drop of
10 percent. Conductors for SLC shall be as specified by the control panel
manufacturer. Metallic conduit systems shall be no smaller than 3/4 inch or sized as
to not exceed 40 percent fill per NEC.
FIRE ALARM SYSTEM
283100 - 10 of 12
Consolidated Rental Car Facility
Project No. 1206
Rogue Valley International-Medford Airport
April 2013
E.
Outlet pull and junction boxes shall be painted red on the exterior and shall be
installed in accordance with Section 26 05 33.
F.
Pigtail and/or tapped connection will not be allowed on supervised circuit.
Connections shall be made directly to and from device terminal screws.
G.
All fire detection, alarm system devices, and control panels shall be flush mounted
when located in finished areas, and may be surface mounted when located in
unfinished areas.
H.
Manual Pull Stations shall be suitable for semi-flush mounting on standard single
gang box, and shall be installed not less than 42 inches or more than 48 inches
above the finished floor.
I.
All devices located at exterior or areas subject to damp conditions shall be listed for
outdoor or weatherproof locations. Backboxes for such devices shall be confirmed
with manufacturer and shall be installed per listing requirements.
J.
Installing contractor shall be responsible for coordination meetings with other
appropriate trades to confirm operation of smoke/fire dampers, energy management
systems, access control systems, intrusion systems, elevator, or other fire and life
safety systems prior to and as needed during course of installation.
K.
Installing contractor shall coordinate and shall have programmable attributes of the
fire alarm system reviewed by the State Fire Marshal prior to system programming.
L.
Follow the manufacturer’s installation recommendations unless otherwise indicated.
Follow the Engineer’s decision, at no additional cost to the Owner, wherever any
conflict arises between the manufacturer’s instructions, State or other codes and
regulations, and these Contract Documents. Keep a copy of the manufacturer’s
installation instructions available on the jobsite for review at all times.
M.
Provide phenolic labels on each enclosure, white letters on black background, letters
3/8-inch tall, minimum.
FIRE ALARM SYSTEM
283100 - 11 of 12
Consolidated Rental Car Facility
Project No. 1206
Rogue Valley International-Medford Airport
3.4
TESTING AND REPORTS
A.
3.5
April 2013
Upon completion of the system’s installation, a representative of the system
manufacturer shall conduct a thorough test of the system and submit a written report
to the Authority Having Jurisdiction. The test shall include at least verifying the
following:
1.
Before energizing the cables and wires, check for correct connections and
test for short circuits, ground faults, continuity, and insulation.
2.
Close each sprinkler system control valve, and verify proper supervisory
alarm at the FACP.
3.
Verify activation of all flow switches.
4.
Open initiating device circuits, and verify that the trouble signal actuates.
5.
Open and short notification appliance circuits, and verify that the trouble
signal actuates.
6.
Ground initiating device circuits, and verify response of trouble signals.
7.
Check all alarm notification devices.
8.
Check installation, supervision, and operation of smoke detectors.
9.
Verify that each initiating device alarm signal is properly received and
processed by the fire alarm control panel (Walk Test).
10.
Functional operation of each alarm device and circuit.
11.
Functional operation of each monitored device circuit.
12.
Functional operation of each control circuit.
13.
Supervision and automatic replacement functions for audio amplifier,
preamplifiers and tone generators.
14.
Conduct tests to verify trouble indications for common mode failures, such as
alternating current power failure. Consult the manufacturer’s manual for
other common mode failures, and conduct the described testing procedures.
CUTTING AND PATCHING
A.
Do not cut or notch any structural member or building surface without specific
approval of the Engineer. Avoid any cutting, channeling, chasing, or drilling of floors,
walls, partitions, ceilings, paving, or other surfaces. Use clamps and channel where
required for the installation, support, or anchorage of conduit, raceways, or other
electrical materials and equipment. Following such work, restore surfaces neatly to
new condition using skilled craftsmen of the trades involved, at no additional cost to
the Owner.
END OF SECTION
FIRE ALARM SYSTEM
283100 - 12 of 12
Download