DISASSEMBLY AND CONDUIT HOLE INSTRUCTIONS MOUNTING

advertisement
MOUNTING INSTRUCTIONS – 4500 Series KNOX-VAULT® POWER SHUTDOWN STATION
Dust Cover
Read and understand these instructions FULLY
before mounting and installing the
4500 Series KNOX-VAULT® POWER SHUTDOWN STATION.
Tamper
Switch
Warning
Label
!
Use a small level to plumb the vault square.
!
Use four(4) Grade 5 or Grade 8 fasteners (carriage
bolts, etc.) of 3/8”
BOLT HEAD MARKINGS
diameter. Units may
also be welded into
place. Mounting to
solid studs or steel
supports is required.
Grade 5 Fastener
Grade 8 Fastener
Avoid mounting face
3 Marks on Bolt Head
6 Marks on Bolt Head
down from ceiling or
overhang area.
!
Series 4500
Surface Mount
!
!
!
Be sure to caulk the sides and the top between
the wall and the vault for water proofing. Use
commercial 100% silicone caulk with a typical
bead thickness of 1/4”. Leave the bottom open for
drainage. IMPORTANT: Clear any material from the
interior/bottom of the vault that could obstruct the
drain hole.
Caulk Top and Sides ONLY
Back View Surface Mount
Do Not
Obstruct Holes
!
Series 4500
Surface Mount
with optional
Tamper Switch
Use of a licensed commercial electrician for 4500
Series mounting and electrical installation is
required. Raintight or wet location (rigid) conduit
and hubs must be used.
The KNOX-VAULT will need to be disassembled for
mounting. Once KNOX-VAULT has been properly
mounted to wall, re-assemble unit in reverse order
being sure that electrical for both the shutdown
switch and tamper switch have been properly
installed and tested.
Tamper switch leads and field wiring conductors
must be routed separately unless they are both
insulated for the maximum voltage involved in
either circuit.
lock mechanism cover removed or lockout will result.
The large plastic washers holding this cover are special
and must not be changed to another type.
IMPORTANT: When mounting of the KNOX-VAULT is complete,
contact your local fire department to inform them the vault is
ready for lock up.
Wall
Surface Mount
Caulk back of vault across top and down
sides, leaving the bottom open.
Be careful not to obstruct the 3
tamper switch wiring holes on
surface mount models.
Recess Mount
Caulk back of flange
across top and down
both sides before
tightening permanently
to wall.
Door Removal and Adjustment
If door must be removed, remove only the top and bottom hinge
pin screws. Do NOT remove the three hinge bracket screws as
these are factory set for proper door alignment. When replacing
the door, adjust hinge pin screws loose enough so that door
swings freely. Thread locker (LOCTITE®) must be used on hinge
pin screws.
Page 1
INSIDE VIEW
Rear Tamper
Switch
Mounting
Holes
DO NOT USE
FOR MOUNTING
7"
HIGH
Switch housing
a screwdriver, remove the (4) mounting
2 Using
screws and nylon washers from the power on/
4 mounting
holes are 7/16"
diameter
off label area
metal encasement from vault which
3 Remove
contains the electrical switch and NEMA box
7" WIDE
cover, being careful not to damage the door
tamper switch/plunger assembly located in the
upper slot-area of the encasement.
4
5
ALWAYS USE BEST POSSIBLE
Using an Allen wrench, remove the (4)
mounting bolts for the NEMA electrical
enclosure. (Long “T” handled Allen wrench
recommended)
MOUNTING DESIGN WHEN
CONDITIONS ARE DIFFERENT
FROM EXAMPLES SHOWN IN
Using a Phillips screwdriver, remove the tamper
switch assembly.
THIS INSTRUCTION.
Electrical conduit hole is to be drilled by a qualified,
licensed commercial electrician making sure all National
and Local Electrical Codes are met. Conduit hole should
be drilled so that tamper switch, mounting screws and
grounding lug are not compromised. Additionally, use only
raintight or wet location conduit and hubs.
CAUTION! The KNOX-VAULT door is equipped with a
security re-locking device. Do NOT lock vault with the
If vault is purchased for private, industrial or commercial use:
keys will be sent separately to address requested.
Wall
1"
No caulking
in this area
NEMA Enclosure
Mounting Holes
octagonal lock nut from directly behind
the knob.
Always mount your KNOX-VAULT to a secure,
solid wall, beam or post. A six foot height level is
recommended to resist vandalism.
Mount the KNOX-VAULT face-up so the hinge is on
the right and the small moisture drain hole is on
the bottom.
1"
TYP.
a 1-3/8” crescent or adjustable wrench,
1 Using
remove the red selector knob by removing the
MOUNTING PREPARATION GUIDELINES
!
MOUNTING HOLE LOCATIONS
REQUIRED TO MOUNT ALL
4500 SERIES MODELS
Hinge
WARNING! The complete electrical system should be
installed, tested and approved by a licensed commercial
electrician before it is placed in operation.
!
DISASSEMBLY AND CONDUIT
HOLE INSTRUCTIONS
INSIDE VIEW
Avoid grounding lug area
when drilling conduit hole
Switch housing
Recommended area
for conduit hole
#4544 Single Lock, Recess Mount shown
NEMA Enclosure
Mounting Holes
All 4500 Series Knox-Vaults are fully tested
and listed by Underwriters Laboratories as
anti-theft devices. Alarm tamper switches
are UL listed as Central Station Alarm
Units. UL Electrical Range: Max Voltage of
24 VDC at 50 mA.
Electrical Ratings:
Main Switch: 24-480VAC, 125VA MAX, PILOT DUTY,
PER CONTACT BLOCK
Two contact blocks per switch; Double Pole,
Double Throw (DPDT)
UL 1332 Organic Coatings for Steel Enclosures for Outdoor Use Electrical Equipment
Tamper Switch: 24VDC, 50mA, general use
UL 508 Industrial Control Equipment
Use 75°C wire only
UL 1037 Antitheft Alarms and Devices
Enclosure Rating: Type 2, 3R
UL 1610 Central Station Alarm Units
Ambient Air Temperature Rating: -40°C / +65°C
-40°F / +149°F
Page 2
6 feet above ground
mounting height
Suggested minimum
6 feet above ground
mounting height
Suggested minimum
Stucco
Nut &
Washer
7-1/4"
5/16" Lag screws, 4 per stud
5/16" Lag screws, 4 per stud
Backboard:
1-1/8" thick plywood
or 2 pcs 3/4" ply glued together
or 2 pcs 3/4" ply glued together
IMPORTANT:
Backboard: 1-1/8" thick plywood
Rigid conduit to
burglar alarm
system
IMPORTANT:
backup
plate
1/4" Steel
burglar
alarm
system
Rigid conduit to
Rigid conduit to
1/4"
Steel backup plate
shunt trip
switch
Rigid conduit to
shunt trip switch
Steel Washer
5/16" Lag screws, 4 per stud
5/16" Lag
screws,
4 per stud
Steel
Washer
Interior
Interior Wall (need not be present for installation)
Wall (need not be present for installation)
Stud
Nut &
Washer
• The recommendations and information contained in these instructions are based on Knox Company experience
and judgment, but should not be considered to be all-inclusive or covering every application or circumstance which
may arise. If any questions arise, contact Knox Company at 1-866-625-4563 for further information or instructions.
• Always turn off power at the breaker when assembling or disassembling the 4500 Series Knox Vaults.
Installation and maintenance involving the circuit and any other accessory attached to the circuit must
be performed by a licensed commercial electrician. The complete electrical system should be installed,
tested and approved by a licensed commercial electrician before it is placed in operation.
• User is cautioned to observe all recommendations, warnings, and cautions relating to the safety of personnel and
equipment, as well as all general and local health and safety laws, codes and procedures.
• THE 4500 SERIES KNOX VAULTS MUST BE INSTALLED, OPERATED, AND MAINTAINED BY QUALIFIED PERSONS WHO
ARE THOROUGHLY TRAINED AND WHO UNDERSTAND ANY HAZARDS THAT MAY BE INVOLVED. THIS PUBLICATION
IS WRITTEN ONLY FOR SUCH QUALIFIED PERSONS AND IS NOT INTENDED TO BE A SUBSTITUTE FOR ADEQUATE
TRAINING AND EXPERIENCE IN SAFETY PROCEDURES FOR THIS TYPE OF PRODUCT. KNOX COMPANY IS NOT LIABLE
FOR THE MISAPPLICATION OR MISINSTALLATION OF ITS PRODUCTS.
4" Minimum
Overlap
FRONT VIEW
1/4" Steel Backup Plate
Concrete
Grout
Backfill
OPE-KBSPEC-0168-D
1601 W. Deer Valley Road, Phoenix, AZ 85027
800-552-5669 • Fax 623-687-2299 • info@knoxbox.com
Issue Date: November 2011
Models
4500 Surface Mount
4500 Recessed Mount
4500 Series
KNOX-VAULT®
REMOTE ELECTRICAL
POWER SHUTDOWN STATION
MOUNTING INSTRUCTIONS
Backboard: 1-1/8" Thick Plywood or
2 pcs 3/4" ply glued together
Keep drain hole
clear of
backfill grout
10" Circular
Bore Hole
Solid
Concrete Wall
SIDE VIEW
Wood Spacer Blocks (x2)
Minimum 1/4" gap between back
of vault and plywood surface
Lag screws, 4 per stud (Use flathead screwWall
to mount spacer)
Concrete
IMPORTANT:
Wood Spacer Blocks (x2)
Backboard: 1-1/8" thick plywood or
2 pcs 3/4" ply glued together
head screw to mount spacer)
of vault
Rigid conduit
to and plywood surface
burglar alarm
system4 per stud (Use flatLag screws,
Minimum 1/4" gap between back
IMPORTANT:
Rigid Conduit to
shunt trip
switch
Backboard:
1-1/8"
thick plywood or
3/4"plate
ply glued together
1/4" Steel2 pcs
backup
1/4" Steel backup plate
IMPORTANT:
3/8" Grade
5 or
Grade
Rigid
conduit
to8 fastener
burglar alarm system
Steel Washer
shunt trip switch
Lag screws, 4 per stud
Rigid Conduit
to
(Use first screw to mount
spacer)
IMPORTANT:
3/8" Grade 5 or Grade 8 fastener
Steel Washer
Lag screws, 4 per stud
Interior
Wall (need not be present for installation)
2x6 / 2x8
Series 4500
Recess Mount in
Stud
IMPORTANT SAFETY
INSTRUCTIONS
Page 3
10" Diameter
2x6 / 2x8
Stud
2x6 / 2x8
Stud
Interior
(Use first screw to mount spacer)
Wall (need not be present for installation)
2x6 / 2x8
Stud
Nut &
Washer2x6 / 2x8
Tamper
2x6 / 2x8
SwitchStud
Door
2x6 / 2x8
Stud
2x6 / 2x8
Stud
Stucco
Wall
Series 4500 Recess Mount - TOP DOWN VIEW
Stucco
Wall
Top View
Stud Wall
To reduce the risk of fire, electric shock, serious injury or death:
WARNING!
5 Patch exterior paint if needed.
grout through visible voids on all four
4 Force
sides of KNOX-VAULT flange with grout bag.
3 Install electrical wiring.
electrical conduit and steel backup plate.
KNOX-VAULT per RECESS MOUNTING
2 Install
TO A STUD WALL diagram above, including
1
Bore 10” diameter hole through solid wall.
BACK VIEW
Top View
Stud Wall
When the KNOX-VAULT model includes a tamper switch, set the tamper switch aside
until the vault is flush mounted. Wiring should be pulled tight so that attempts to force
the vault out of the wall will break the wire or pull the terminals loose. If installing
the vault on a thin or hollow wall, use a solid backing (1-1/8 plywood or 3/8” steel
plate fastened to solid studs on both sides) for secure mounting. Mounting to solid
studs or steel support is always required. Alarm wiring/testing should be performed
Door
by a qualified alarm installer.
For use with
recessed/flanged
models
®
Loctite® all fasteners.
All fasteners to be Grade 5 or 8
Recess models are designed for flush mounting. Do NOT mount face down from ceiling
Wall
or overhang area. Units can be adapted to fit a variety of solid walls or in a concrete
wall. Due to it’s depth, there is NO RECESSED MOUNTING KIT available for the 4500
Tamper
Series KNOX-VAULT. Do NOT over tighten mounting bolts as this will distort the flange.
Switch
RECESS MOUNTING
IN SOLID CONCRETE WALL
Nut &
Washer
7-1/4"
Wall
Tamper
Switches
Stucco(2)
IMPORTANT: 3/8" Grade 5 or
Grade 8 fastener
Door
Stud Wall
Tamper
Switches
Top View(2)
Series 4500 Surface Mount - TOP DOWN VIEW
Loctite all fasteners.
IMPORTANT:
3/8" Grade 5 or
All fasteners to be Grade 5 or 8
Grade 8 fastener
Door
Top View
Stud Wall
When recess mounting to a stud wall, the interior wall must be reinforced across two
studs using thick plywood and steel backplate.
RECESS MOUNTING
TO A STUD WALL
If installing on a thin or hollow wall, use a solid backing (ex: 1/4” steel
plate) to properly reinforce for secure mounting. Mounting to solid studs
or steel support is required. Alarm wiring/testing should be performed
by a qualified alarm installer.
Surface models are designed for mounting on a flat wall. Do NOT
mount face down from ceiling or overhang area. When the KNOXVAULT model includes tamper switches, set the tamper switches aside
until the vault is mounted on the wall. Check to see that the “vault
to wall” tamper plunger is properly depressed. If switch plunger
does NOT properly depress, adjust the screw on the plunger for the
proper length.
The 4500 Series Vault is 7-1/4” deep and weighs 31 lbs. When surface
mounting to a stud wall, the interior wall must be reinforced across
two studs using thick plywood and a steel backup plate.
SURFACE MOUNTING
TO A STUD WALL