MOUNTING INSTRUCTIONS – 4500 Series KNOX-VAULT® POWER SHUTDOWN STATION Dust Cover Read and understand these instructions FULLY before mounting and installing the 4500 Series KNOX-VAULT® POWER SHUTDOWN STATION. Tamper Switch Warning Label ! Use a small level to plumb the vault square. ! Use four(4) Grade 5 or Grade 8 fasteners (carriage bolts, etc.) of 3/8” BOLT HEAD MARKINGS diameter. Units may also be welded into place. Mounting to solid studs or steel supports is required. Grade 5 Fastener Grade 8 Fastener Avoid mounting face 3 Marks on Bolt Head 6 Marks on Bolt Head down from ceiling or overhang area. ! Series 4500 Surface Mount ! ! ! Be sure to caulk the sides and the top between the wall and the vault for water proofing. Use commercial 100% silicone caulk with a typical bead thickness of 1/4”. Leave the bottom open for drainage. IMPORTANT: Clear any material from the interior/bottom of the vault that could obstruct the drain hole. Caulk Top and Sides ONLY Back View Surface Mount Do Not Obstruct Holes ! Series 4500 Surface Mount with optional Tamper Switch Use of a licensed commercial electrician for 4500 Series mounting and electrical installation is required. Raintight or wet location (rigid) conduit and hubs must be used. The KNOX-VAULT will need to be disassembled for mounting. Once KNOX-VAULT has been properly mounted to wall, re-assemble unit in reverse order being sure that electrical for both the shutdown switch and tamper switch have been properly installed and tested. Tamper switch leads and field wiring conductors must be routed separately unless they are both insulated for the maximum voltage involved in either circuit. lock mechanism cover removed or lockout will result. The large plastic washers holding this cover are special and must not be changed to another type. IMPORTANT: When mounting of the KNOX-VAULT is complete, contact your local fire department to inform them the vault is ready for lock up. Wall Surface Mount Caulk back of vault across top and down sides, leaving the bottom open. Be careful not to obstruct the 3 tamper switch wiring holes on surface mount models. Recess Mount Caulk back of flange across top and down both sides before tightening permanently to wall. Door Removal and Adjustment If door must be removed, remove only the top and bottom hinge pin screws. Do NOT remove the three hinge bracket screws as these are factory set for proper door alignment. When replacing the door, adjust hinge pin screws loose enough so that door swings freely. Thread locker (LOCTITE®) must be used on hinge pin screws. Page 1 INSIDE VIEW Rear Tamper Switch Mounting Holes DO NOT USE FOR MOUNTING 7" HIGH Switch housing a screwdriver, remove the (4) mounting 2 Using screws and nylon washers from the power on/ 4 mounting holes are 7/16" diameter off label area metal encasement from vault which 3 Remove contains the electrical switch and NEMA box 7" WIDE cover, being careful not to damage the door tamper switch/plunger assembly located in the upper slot-area of the encasement. 4 5 ALWAYS USE BEST POSSIBLE Using an Allen wrench, remove the (4) mounting bolts for the NEMA electrical enclosure. (Long “T” handled Allen wrench recommended) MOUNTING DESIGN WHEN CONDITIONS ARE DIFFERENT FROM EXAMPLES SHOWN IN Using a Phillips screwdriver, remove the tamper switch assembly. THIS INSTRUCTION. Electrical conduit hole is to be drilled by a qualified, licensed commercial electrician making sure all National and Local Electrical Codes are met. Conduit hole should be drilled so that tamper switch, mounting screws and grounding lug are not compromised. Additionally, use only raintight or wet location conduit and hubs. CAUTION! The KNOX-VAULT door is equipped with a security re-locking device. Do NOT lock vault with the If vault is purchased for private, industrial or commercial use: keys will be sent separately to address requested. Wall 1" No caulking in this area NEMA Enclosure Mounting Holes octagonal lock nut from directly behind the knob. Always mount your KNOX-VAULT to a secure, solid wall, beam or post. A six foot height level is recommended to resist vandalism. Mount the KNOX-VAULT face-up so the hinge is on the right and the small moisture drain hole is on the bottom. 1" TYP. a 1-3/8” crescent or adjustable wrench, 1 Using remove the red selector knob by removing the MOUNTING PREPARATION GUIDELINES ! MOUNTING HOLE LOCATIONS REQUIRED TO MOUNT ALL 4500 SERIES MODELS Hinge WARNING! The complete electrical system should be installed, tested and approved by a licensed commercial electrician before it is placed in operation. ! DISASSEMBLY AND CONDUIT HOLE INSTRUCTIONS INSIDE VIEW Avoid grounding lug area when drilling conduit hole Switch housing Recommended area for conduit hole #4544 Single Lock, Recess Mount shown NEMA Enclosure Mounting Holes All 4500 Series Knox-Vaults are fully tested and listed by Underwriters Laboratories as anti-theft devices. Alarm tamper switches are UL listed as Central Station Alarm Units. UL Electrical Range: Max Voltage of 24 VDC at 50 mA. Electrical Ratings: Main Switch: 24-480VAC, 125VA MAX, PILOT DUTY, PER CONTACT BLOCK Two contact blocks per switch; Double Pole, Double Throw (DPDT) UL 1332 Organic Coatings for Steel Enclosures for Outdoor Use Electrical Equipment Tamper Switch: 24VDC, 50mA, general use UL 508 Industrial Control Equipment Use 75°C wire only UL 1037 Antitheft Alarms and Devices Enclosure Rating: Type 2, 3R UL 1610 Central Station Alarm Units Ambient Air Temperature Rating: -40°C / +65°C -40°F / +149°F Page 2 6 feet above ground mounting height Suggested minimum 6 feet above ground mounting height Suggested minimum Stucco Nut & Washer 7-1/4" 5/16" Lag screws, 4 per stud 5/16" Lag screws, 4 per stud Backboard: 1-1/8" thick plywood or 2 pcs 3/4" ply glued together or 2 pcs 3/4" ply glued together IMPORTANT: Backboard: 1-1/8" thick plywood Rigid conduit to burglar alarm system IMPORTANT: backup plate 1/4" Steel burglar alarm system Rigid conduit to Rigid conduit to 1/4" Steel backup plate shunt trip switch Rigid conduit to shunt trip switch Steel Washer 5/16" Lag screws, 4 per stud 5/16" Lag screws, 4 per stud Steel Washer Interior Interior Wall (need not be present for installation) Wall (need not be present for installation) Stud Nut & Washer • The recommendations and information contained in these instructions are based on Knox Company experience and judgment, but should not be considered to be all-inclusive or covering every application or circumstance which may arise. If any questions arise, contact Knox Company at 1-866-625-4563 for further information or instructions. • Always turn off power at the breaker when assembling or disassembling the 4500 Series Knox Vaults. Installation and maintenance involving the circuit and any other accessory attached to the circuit must be performed by a licensed commercial electrician. The complete electrical system should be installed, tested and approved by a licensed commercial electrician before it is placed in operation. • User is cautioned to observe all recommendations, warnings, and cautions relating to the safety of personnel and equipment, as well as all general and local health and safety laws, codes and procedures. • THE 4500 SERIES KNOX VAULTS MUST BE INSTALLED, OPERATED, AND MAINTAINED BY QUALIFIED PERSONS WHO ARE THOROUGHLY TRAINED AND WHO UNDERSTAND ANY HAZARDS THAT MAY BE INVOLVED. THIS PUBLICATION IS WRITTEN ONLY FOR SUCH QUALIFIED PERSONS AND IS NOT INTENDED TO BE A SUBSTITUTE FOR ADEQUATE TRAINING AND EXPERIENCE IN SAFETY PROCEDURES FOR THIS TYPE OF PRODUCT. KNOX COMPANY IS NOT LIABLE FOR THE MISAPPLICATION OR MISINSTALLATION OF ITS PRODUCTS. 4" Minimum Overlap FRONT VIEW 1/4" Steel Backup Plate Concrete Grout Backfill OPE-KBSPEC-0168-D 1601 W. Deer Valley Road, Phoenix, AZ 85027 800-552-5669 • Fax 623-687-2299 • info@knoxbox.com Issue Date: November 2011 Models 4500 Surface Mount 4500 Recessed Mount 4500 Series KNOX-VAULT® REMOTE ELECTRICAL POWER SHUTDOWN STATION MOUNTING INSTRUCTIONS Backboard: 1-1/8" Thick Plywood or 2 pcs 3/4" ply glued together Keep drain hole clear of backfill grout 10" Circular Bore Hole Solid Concrete Wall SIDE VIEW Wood Spacer Blocks (x2) Minimum 1/4" gap between back of vault and plywood surface Lag screws, 4 per stud (Use flathead screwWall to mount spacer) Concrete IMPORTANT: Wood Spacer Blocks (x2) Backboard: 1-1/8" thick plywood or 2 pcs 3/4" ply glued together head screw to mount spacer) of vault Rigid conduit to and plywood surface burglar alarm system4 per stud (Use flatLag screws, Minimum 1/4" gap between back IMPORTANT: Rigid Conduit to shunt trip switch Backboard: 1-1/8" thick plywood or 3/4"plate ply glued together 1/4" Steel2 pcs backup 1/4" Steel backup plate IMPORTANT: 3/8" Grade 5 or Grade Rigid conduit to8 fastener burglar alarm system Steel Washer shunt trip switch Lag screws, 4 per stud Rigid Conduit to (Use first screw to mount spacer) IMPORTANT: 3/8" Grade 5 or Grade 8 fastener Steel Washer Lag screws, 4 per stud Interior Wall (need not be present for installation) 2x6 / 2x8 Series 4500 Recess Mount in Stud IMPORTANT SAFETY INSTRUCTIONS Page 3 10" Diameter 2x6 / 2x8 Stud 2x6 / 2x8 Stud Interior (Use first screw to mount spacer) Wall (need not be present for installation) 2x6 / 2x8 Stud Nut & Washer2x6 / 2x8 Tamper 2x6 / 2x8 SwitchStud Door 2x6 / 2x8 Stud 2x6 / 2x8 Stud Stucco Wall Series 4500 Recess Mount - TOP DOWN VIEW Stucco Wall Top View Stud Wall To reduce the risk of fire, electric shock, serious injury or death: WARNING! 5 Patch exterior paint if needed. grout through visible voids on all four 4 Force sides of KNOX-VAULT flange with grout bag. 3 Install electrical wiring. electrical conduit and steel backup plate. KNOX-VAULT per RECESS MOUNTING 2 Install TO A STUD WALL diagram above, including 1 Bore 10” diameter hole through solid wall. BACK VIEW Top View Stud Wall When the KNOX-VAULT model includes a tamper switch, set the tamper switch aside until the vault is flush mounted. Wiring should be pulled tight so that attempts to force the vault out of the wall will break the wire or pull the terminals loose. If installing the vault on a thin or hollow wall, use a solid backing (1-1/8 plywood or 3/8” steel plate fastened to solid studs on both sides) for secure mounting. Mounting to solid studs or steel support is always required. Alarm wiring/testing should be performed Door by a qualified alarm installer. For use with recessed/flanged models ® Loctite® all fasteners. All fasteners to be Grade 5 or 8 Recess models are designed for flush mounting. Do NOT mount face down from ceiling Wall or overhang area. Units can be adapted to fit a variety of solid walls or in a concrete wall. Due to it’s depth, there is NO RECESSED MOUNTING KIT available for the 4500 Tamper Series KNOX-VAULT. Do NOT over tighten mounting bolts as this will distort the flange. Switch RECESS MOUNTING IN SOLID CONCRETE WALL Nut & Washer 7-1/4" Wall Tamper Switches Stucco(2) IMPORTANT: 3/8" Grade 5 or Grade 8 fastener Door Stud Wall Tamper Switches Top View(2) Series 4500 Surface Mount - TOP DOWN VIEW Loctite all fasteners. IMPORTANT: 3/8" Grade 5 or All fasteners to be Grade 5 or 8 Grade 8 fastener Door Top View Stud Wall When recess mounting to a stud wall, the interior wall must be reinforced across two studs using thick plywood and steel backplate. RECESS MOUNTING TO A STUD WALL If installing on a thin or hollow wall, use a solid backing (ex: 1/4” steel plate) to properly reinforce for secure mounting. Mounting to solid studs or steel support is required. Alarm wiring/testing should be performed by a qualified alarm installer. Surface models are designed for mounting on a flat wall. Do NOT mount face down from ceiling or overhang area. When the KNOXVAULT model includes tamper switches, set the tamper switches aside until the vault is mounted on the wall. Check to see that the “vault to wall” tamper plunger is properly depressed. If switch plunger does NOT properly depress, adjust the screw on the plunger for the proper length. The 4500 Series Vault is 7-1/4” deep and weighs 31 lbs. When surface mounting to a stud wall, the interior wall must be reinforced across two studs using thick plywood and a steel backup plate. SURFACE MOUNTING TO A STUD WALL