Models: ACSP-3001-HW
Compact 30A Surge Suppressor - hardwired
Description
This advanced surge suppressor provides the highest current
capacity available in devices of its size to protect multiple
pieces of sensitive electronic equipment on a single circuit. It
features industrial strength “zero failure” technology backed by
a ten year warranty. The compact body has a very low profile
(1.75"H x 6"D x 9"W) and includes two mounting brackets for
easy installation — on a wall behind a flat panel TV, under a
counter, in a rack or just about anywhere. Terminates to 6-ft.
non-metallic flexible whip that can be field-cut to shorter
lengths. A blank plate with knockout allows the 30A receptacle
to be converted to hardwired output if desired.
Includes a 6-ft. non-metallic flexible
whip and mounting brackets.
Features
• ETL Listed, ANSI C62.41 Compliant
• Features (1) 30A outlet
• Conforms to UL1449-3
• Includes blank cover plate with knockout that allows the
30A receptacle to be converted in the field to hardwired
output, if needed
• Low-profile chassis (1.75”H x 6”D x 9”W)
• LEDs provide visual system status
• Suppresses line to neutral with no ground contamination.
• TCR technology defeats surges up to 72,000 amps with zero
failures
• Two mounting brackets allow versatile installation.
• Optional mounting ears are available if standard 19” panel installation is preferred.
• Terminates to 6-ft. non-metallic flexible whip
• 10 year warranty
Optional mounting
ears (ACC-1ME) are
available if standard
19” rackmount installation is preferred.
Mechanical Specifications:
Dimensions:
Weight:
Input Connections:
Output Connections:
Chassis:
Mounting:
Performance Specifications:
Operating Voltage/Current:
Maximum Surge Current:
Initial Clamping Voltage:
Endurance:
Transient Noise Reduction:
Response Time:
Temperature Range:
Protection Mode:
UL1449-2 Adjunct Results:
A & E Specifications
The 30A single-circuit surge suppressor shall be Lowell model
ACSP-3001-HW with one 30A outlet. It shall be ETL Listed and
conform to UL1449 3rd edition. It shall meet ANSI C62.41 and
protect the line to neutral without ground wire contamination. It
shall be capable of protecting electronic equipment from transient voltages, spikes and surges up to 72,000 amps and have
a response time of less than 5 nanoseconds. It shall mount
with mounting brackets (included. It shall include LEDs for visual ground verification and surge diagnostics.
Model No.
Description
ACSP-3001-HW
ACC-1ME
Compact surge suppressor
Mounting Ears
Spec. No. 1127
(rev. 06.04.13)
pg. 1 of 2
Federal GSA specs (1996)
Diagnostic LEDs (surge)**
Applicable Standards:
Safety Agency Approvals:
9"W x 1.75"H x 6"D
5 lbs.
6-ft. non-metallic flexible whip
(1) 30A receptacle
Steel with black powder epoxy finish
(2) brackets
120VAC / 30A, 60Hz
72,000A (exceeds UL1449-3 6000V, 3000A)
205V, UL rating 400V
IEEE C62.41-1991, B3 (C1), Pulses (lifetime):
1kv≥1,000,000; 3kv≥100,000; 6kv≥5000
29dB@100kHz, 70dB@1MHz
Less than 5 nanoseconds
25˚C (77˚F) nominal
Line to neutral, zero ground leakage
1000 surges, 6000 volts, 3000A, C1, and B3
waveforms (IEEE C62.41), NO FAILURES
Grade A, Class 1, Mode 1
Top (green): ON = ground verified
Center (green): ON = protection active
Bottom (red): ON = protection reduced*
UL1449-3, IEEE standard 587-80 A & B, IEEE
standard C62.41-1991, IEC 1000-4-5-1995
(IEC 801-5).
ETL Listed US and Canada
**TCR surge suppression technology provides the assurance of Grade A, Class 1, Mode 1
endurance and performance testing plus visual diagnostic LEDs. The ground verified (green
LED), protection active (green LED) should always be ON and the reduced protection (red
LED) should be OFF. In the unlikely event the red LED illuminates, full suppression capability
is NOT immediately or even necessarily compromised. The red LED indicates the overall life
expectancy of the unit may be reduced. Contact Lowell for repair or replacement under the
unit’s ten year warranty.
Outlets
Amperage
Termination
Over/Under Protection
Remote Control Capable
1
30A
hardwired
No
No
©2013 Lowell Manufacturing Company, 100 Integram Dr., Pacific MO 63069. Phone–800.325.9660
Fax—636.257.6606. Lowell makes every effort to provide accurate information while reserving the right to
change specifications and/or improve manufacturing methods without notification. (lowellmfg.com)
Top / Front Panel Layout
Includes a 6-ft. non-metallic flexible whip
and universal mounting brackets.
Changing from receptacle output to hardwired output
Remove cover, flip over and
remove receptacle plate.
Disconnect receptacle.
Install blank knockout plate
in place of receptacle plate.
Attach conduit with wires to
blank knockout plate or
knockout in side of chassis.
Splice to receptacle wires.
Reassemble.
Installation Options with Mounting Brackets
Surface-mount with
exposed brackets.
Surface-mount with brackets
concealed behind unit.
Mount to rack rail supports or
10-32 tapped rack rail.
Non-metallic flexible whip can be trimmed in the field
Snip reinforcing rib at desired length. Bend
and carefully cut around conduit without cutting wires inside. Remove excess conduit.
Spec. No. 1127
(rev. 06.04.13)
pg. 2 of 2
Snip 2 or 3 ribs around the connector and
remove connector from excess conduit.
Attach connector to shortened
conduit length.
©2013 Lowell Manufacturing Company, 100 Integram Dr., Pacific MO 63069. Phone–800.325.9660
Fax—636.257.6606. Lowell makes every effort to provide accurate information while reserving the right to
change specifications and/or improve manufacturing methods without notification. (lowellmfg.com)