Rigid and Intermediate Metal Conduit Fittings Locknuts

advertisement
Rigid and Intermediate Metal Conduit Fittings
Locknuts
140 Series
141AL Series
Application
• To connect externally threaded conduit or connector
to a threadless opening in a box or enclosure
• To effectively bond conduit or connector to box
or enclosure
Features
• Hardened steel/malleable iron/copper-free
aluminum construction
• Tightens without deformation
106 Series
Standard Material
140 Series & 106 Series
3
⁄8" thru 2" steel (hardened) 21⁄2" thru 6"
Malleable Iron
All screws steel
141AL Series
All copper-free aluminum
Standard Finish
All steel and malleable iron locknuts, including electro zinc-plated bonding
screws and chromate coated all-aluminum locknut, degreased
Range
• Locknuts specially designed to:
⁄8" through 6" conduit (All threads straight pipe [NPS]) (140 Series)
⁄2" through 4" conduit (106 Series & 141AL Series)
3
(i) Provide extended reach for clamping on thin boxes
and enclosures
1
(ii) Cut through protective coating on box and enclosure,
thereby ensuring ground continuity
UL (UL File No. E-23018)
CSA [catalog numbers 108, 109, 110 and 111. All 140 Series
except catalog number 140.] (LR-2884, LR-4484)
(iii) Permit tightening from outside
Conforms to
(iv) Prevent loosening under vibration
UL 514B
CSA C22.2 No. 18
NEMA FB1
NFPA 70
Federal Specification replaced by A-A-50553
Federal Standard H-28 (Threads)
• 106 Series provided with a hardened cone point screw
Listed/Certified by
Case Hardened Locknuts
Case hardened locknuts make fittings faster and easier to install. Case
hardened locknuts do not slip or turn, thereby protecting the biting edge.
Case hardened locknuts bite through paint into the enclosure, providing
excellent continuity of ground (typical T&B/Thomas & Betts fitting with case
hardened locknuts successfully passed minimum fault current of 10,000
amps RMS). Case hardened locknuts, when assembled in the intended
manner, will not vibrate loose, thereby ensuring excellent ground continuity.
A-4
www.tnb.com
United States
Tel: 901.252.8000
800.816.7809
Fax: 901.252.1354
Canada
Tel: 450.347.5318
Fax: 450.347.1976
Technical Services
Tel: 888.862.3289
Rigid and Intermediate Metal Conduit Fittings
Available in your choice of steel/malleable
iron or aluminum.
Ensures positive bonding of conduit to box
and prevents loosening due to vibration!
Locknuts
Bonding Locknuts
A
• Steel or malleable iron (steel through 2")
• Can be used anywhere an ordinary locknut is installed
(B) Thickness
• Also can be used for Service Entrance applications
in conformance with code
• Steel from 1⁄4" to 2" and malleable iron from 21⁄2" to 6"
®
• Aluminum 624 in all sizes
• T&B rigid conduit and EMT (thinwall) fittings comply
with Federal Specification A-A-50553
®
DIMENSIONS (IN.)
CAT. NO.
SIZE (IN.)
A
B
†
⁄2
⁄4
1
11⁄4
11⁄2
2
21⁄2
3
31⁄2
4
1 ⁄8
15⁄8
115⁄16
25⁄32
21⁄2
3
313⁄32
413⁄16
429⁄32
57⁄32
.125
.140
.170
.170
.170
.187
.375
.375
.438
.438
106
107†
108
109
110
111
112†
113†
114†
115†
3
1
3
(B) Thickness
®
®
CAT. NO.
UL File No. E-3060
CSA File No. 638
† Not CSA certified.
Available with DURA-PLATE ® Finish.
Provides positive seal against water and oil.
Sealing Locknuts
A
B
C
Molded Santoprene Seal
Color: Blue
• For use with rigid and intermediate metal conduits or fittings
®
®
141SL
142SL
143SL
144SL
145SL
146SL
A
DIMENSIONS (IN.)
B
C
⁄2
3
⁄4
1
11⁄4
11⁄2
2
1.140
1.420
1.770
2.281
2.598
3.175
⁄8
5
⁄32
11
⁄64
11
⁄64
11
⁄64
3
⁄16
⁄4
9
⁄32
9
⁄32
5
⁄16
9
⁄32
7
⁄64
1
SIZE (IN.)
139*
140*
141**
142**
143
144
145
146
147
148
149
150
151
152
153
—
—
141AL
142AL
143AL
144AL
145AL
146AL
147AL
148AL
149AL
150AL
151AL
152AL
153AL
⁄4
⁄8
1
⁄2
3
⁄4
1
11⁄4
11⁄2
2
21⁄2
3
31⁄2
4
41⁄2
5
6
1
3
DIMENSIONS (IN.)
A
B
⁄4
⁄16
17⁄64
13⁄8
111⁄16
25⁄32
21⁄2
3
39⁄16
43⁄16
413⁄16
55⁄16
515⁄16
61⁄2
73⁄4
3
15
⁄64
⁄64
5
⁄32
3
⁄16
13
⁄64
13
⁄64
13
⁄64
7
⁄32
13
⁄32
13
⁄32
15
⁄32
15
⁄32
17
⁄32
17
⁄32
19
⁄32
9
9
**Case hardened locknuts
Aluminum locknuts comply with federal standard of copper-free aluminum;
less than .5% copper.
SIZE (IN.)
1
ALUM.
*Hex shape
• Provides watertight or raintight seal at all enclosures
CAT. NO.
STL. OR M.I.
1
Available with DURA-PLATE ® Finish.
UL File E-23018
CSA File No. 2884
UL File No. E-23018
CSA File No. 2884
United States
Tel: 901.252.8000
800.816.7809
Fax: 901.252.1354
Canada
Tel: 450.347.5318
Fax: 450.347.1976
Technical Services
Tel: 888.862.3289
www.tnb.com
A-5
Rigid and Intermediate Metal Conduit Fittings
Perfect for grounding old work or new!
Bonding & Grounding Wedges
Series 3651
Series 3650
• Provides grounding without a jumper except
in concentric knockouts
Standard Material/Finish
Listed/Certified by
1
⁄2" size Steel/Electro Zinc Plated
3
⁄4" thru 6" size Bronze/Tin Plated
UL File #E3060
CSA File #638
Range
Conforms to
⁄2" thru 6" conduit
UL 467
CSA C22.2 No. 41
NFPA-70
Federal Specification A-A-50552
1
• When jumper is required, it fits under set screw
in grounding wedge
• Update existing installations to meet code requirements for
bonding (NEC Sect. 250-72e) without disconnecting wiring
Grounding Wedges
• For use on new wiring, just loosen bushing, position
wedge and tighten bushing and bonding screw
Application
• To effectively bond terminating fitting or conduit
to a box or enclosure
Features
• Sizes 3⁄4" thru 6" equipped with an additional bonding
screw to install bonding jumper where required
• Can be added to an existing installation without
disconnecting conductors
CAT. NO.
SIZE
3650
3651
3652
3653
3654
3655
3656
3657
3658
3659
3661
3662
⁄2"
⁄4"
1"
11⁄4"
11⁄2"
2"
21⁄2"
3"
31⁄2"
4"
5"
6"
1
3
UL File No. E-3060
Sealing Rings with
Stainless Steel Retainer
B
CAT. NO.
A
Sealing Ring — Santoprene
Thermoplastic Rubber
These sealing rings provide a liquid-tight, dust-tight seal of fitting at enclosures.
5302
5303
5304
5305
5306
5307
5308
5309
5311
NEMA 3R, 4, 6 & 13
A-6
www.tnb.com
United States
Tel: 901.252.8000
800.816.7809
Fax: 901.252.1354
Canada
Tel: 450.347.5318
Fax: 450.347.1976
DIMENSIONS (IN.)
B ± 1/64
CONDUIT SIZE
A
⁄2"
⁄4"
1"
11⁄4"
11⁄2"
2"
21⁄2"
3"
4"
111⁄64
11⁄2
13⁄4
29⁄64
2&
259⁄64
37⁄16
45⁄64
59⁄32
1
3
UL File No. E-13938
Technical Services
Tel: 888.862.3289
CSA File No. 2884
⁄4
⁄16
111⁄64
11⁄2
13⁄4
215⁄64
243⁄64
319⁄64
419⁄64
3
15
Rigid and Intermediate Metal Conduit Fittings
Blackjack® — Grounding Bushing
Innovative design makes installation quicker, easier.
The Blackjack® Grounding Bushing never has
to be threaded onto a conduit. It is simply placed
in position on either a threaded or non-threaded
rigid or IMC conduit, with the grounding lug in
perfect position to accept the grounding wire —
even in tight installations.
It’s as simple as one, two, three!
Compare the installation with conventional
bushings that must be threaded onto the
conduit. In tight areas, you may have to remove
the grounding lug, keep up with the loose parts
and then reattach the lug. Then you still have
to twist and turn the bushing to get the lug
Mounting screw
with nylon locking
in position to accept the grounding wire.
patch has a cone
The Blackjack bushing does away with these
point to lock
needless delays for good, making it the ideal
bushing securely
grounding bushing — and the only logical
in place.
choice for small spaces, corners and multiple
conduit runs. And, because the grounding lug
is an integral part of the bushing, it's designed
not to fall off or get lost.
Integral grounding
lug enhances
ground continuity.
Added ground
wire range taking
reduces inventory.
Accepts copper or
aluminum ground
wires.
Insulating nylon
surface is 150° C
rated and covers
top of bushing,
including lug
corners.
Angle of lug
screw improves
accessibility when
securing
grounding
wire.
Innovative design improves performance.
The Blackjack® bushing provides
superior ground continuity.
The design of the Blackjack bushing has
an integral, cast-on grounding lug for better
ground continuity. This means that the
Blackjack bushing stands up to intense loads.
Reduce inventory.
Because the Blackjack Grounding Bushing
is designed for threaded and non-threaded
conduits, and the ground lugs are designed to
handle an extended range, the number of parts
in inventory is reduced by up to two-thirds
without losing any application coverage.
Secure grip forms
lasting bond.
The Blackjack bushing’s
cone-point mounting screw
bites securely into both
threaded and non-threaded
rigid conduits. And the
Blackjack bushing’s nylon
locking patch is designed
to prevent the screw from
loosening due to vibration.
Insulator surface
features a rounded
design to reduce
drag and prevent
abrasion during
wire pulling.
Cast “threads”
opposite the
mounting
screw tighten
the fit during
installation.
Blackjack® — Conduit Grounding Bushing
Lug Screw:
Range
14-4: Slotted
14-2/0: Slotted
Conduit: 1⁄2" thru 6" threaded or threadless
rigid/IMC
6-4/0: Internal Hex Drive
Wire Range: #14 AWG to 4/0 AWG CU/AL
Standard Material/Finish
Listed/Certified by
Body: Malleable Iron or Aluminum
UL File #E3060
Mounting Screw: ( ⁄2"–2") Stainless Steel,
(21⁄2"–6") Brass
CSA File #LR2884
1
Lug Screw: Stainless Steel
Finish: Zinc Plated or Mechanical Galvanized
Conforms to
UL 514B & U.L. 467
CSA C22.2 No. 18 & CSA C22.2 No. 41
United States
Tel: 901.252.8000
800.816.7809
Fax: 901.252.1354
Canada
Tel: 450.347.5318
Fax: 450.347.1976
Technical Services
Tel: 888.862.3289
www.tnb.com
A-7
Rigid and Intermediate Metal Conduit Fittings
Blackjack® Grounding Bushing Technical Information
Mounting Screw
Nylon Insulator (150º C)
Lug Screw
14-4: Slotted
14-2/0: Slotted
6-4/0: Internal hex drive
ØB
Throat I.D.
C
E
ØA
D
For Threaded and Threadless Rigid and IMC Conduit
CAT. NO.
ZINC PLATED
MALLEABLE IRON
ALUMINUM
BG050-14-20
BG050-14-4
BG075-14-20
BG075-14-4
BG100-14-20
BG100-14-4
BG125-14-20
BG150-14-20
BG200-14-20
BG250-14-20
BG250-6-40
BG300-14-20
BG300-6-40
BG350-14-20
BG350-6-40
BG400-14-20
BG400-6-40
BG500-14-20
BG500-6-40
BG600-14-20
BG600-6-40
BGA050-14-20
BGA050-14-4
BGA075-14-20
BGA075-14-4
BGA100-14-20
BGA100-14-4
BGA125-14-20
BGA150-14-20
BGA200-14-20
BGA250-14-20
BGA250-6-40
BGA300-14-20
BGA300-6-40
BGA350-14-20
BGA350-6-40
BGA400-14-20
BGA400-6-40
BGA500-14-20
BGA500-6-40
BGA600-14-20
BGA600-6-40
CONDUIT
SIZE
ØA
MAX.
ØB MIN.
THROAT I.D.
C
MAX.
D
MAX.
E
MAX.
WIRE
RANGE
⁄2"
⁄2"
3
⁄4"
3
⁄4"
1"
1"
11⁄4"
11⁄2"
2"
21⁄2"
21⁄2"
3"
3"
31⁄2"
31⁄2"
4"
4"
5"
5"
6"
6"
1.251
1.251
1.533
1.533
1.783
1.783
2.220
2.470
2.830
3.418
3.418
4.042
4.042
4.542
4.542
5.042
5.042
6.136
6.136
7.199
7.199
.569
.569
.772
.772
.993
.993
1.319
1.553
2.010
2.412
2.412
3.022
3.022
3.491
3.491
3.975
3.975
4.991
4.991
6.009
6.009
1.181
1.027
1.221
1.030
1.181
1.027
1.181
1.181
1.181
1.181
1.524
1.181
1.524
1.181
1.524
1.181
1.524
1.181
1.524
1.181
1.524
2.134
1.940
2.414
2.168
2.581
2.368
2.987
3.236
3.766
4.341
4.526
4.966
5.139
5.467
5.639
5.966
6.139
7.045
7.207
8.087
8.409
.696
.696
.696
.696
.696
.696
.759
.696
.696
.978
.978
.978
.978
.978
.978
.978
.978
.978
.978
.978
.978
14-2/0
14-4
14-2/0
14-4
14-2/0
14-4
14-2/0
14-2/0
14-2/0
14-2/0
6-4/0
14-2/0
6-4/0
14-2/0
6-4/0
14-2/0
6-4/0
14-2/0
6-4/0
14-2/0
6-4/0
1
1
Suggested Specifications: Insulated grounding and bonding bushing (Series BG050-BG600)
Where code requires bonding and grounding of single or multiple metal conduits, or positive bonding and grounding of metal conduit to the box, enclosure or auxiliary gutter, the end of the
conduit shall be equipped with an insulated metallic grounding and bonding bushing series BG050-14-20 as manufactured by Thomas & Betts.
Grounding and bonding bushings used shall be approved for the purpose and
(i) Shall be of malleable iron/steel/aluminum construction adequately protected
against corrosion.
(ii) Bushing insulator shall be listed or certified for 150° C/302° F application with
a flammability rating of 94V-O. Insulator must be positively locked in place.
Please consult factory for mechanically galvanized.
A-8
www.tnb.com
United States
Tel: 901.252.8000
800.816.7809
Fax: 901.252.1354
Canada
Tel: 450.347.5318
Fax: 450.347.1976
Technical Services
Tel: 888.862.3289
Rigid and Intermediate Metal Conduit Fittings
Threaded Insulated Grounding Bushing
Application
• For quick installation of bonding jumper
to multiple metal conduits (Rigid and IMC)
• Designed to bush conductors and prevent
insulation damage
Features
• Ease of installation, lay in lug design
®
®
• Cast malleable iron body designed to lock insulator
in place within body, reducing common assembly
problem resulting in dislodging of insulator
• Insulator rated for 150° C/302° F application
• Look for the unique T&B blue color, ensuring
the highest quality fitting
Standard Material/Finish
Body:
Electro zinc plated
Lay-In Lug: Aluminum/tin plated
Insulator:
Thermoplastic 150° C/302° F
Application with 94V-0 flammability
Wire Clamping Screw
Lay-In Lug
Insulator
Set Screw (1)
3870 Series
Bushing
Casting
CAT. NO.
3870-TB
3861
3871-TB
3862
3872
3882
3873
3883
3874
3884
3875
3889
3876
3886
3993
3877
3887
3994
3878
3863
3995
3879
3864
3996
3880
3865
3998
3881
3866
3999
CONDUIT BUSHING THROAT
SIZE
DIA.
DIA.
⁄2"
⁄2"
3
⁄4"
3
⁄4"
1"
1"
11⁄4"
11⁄4"
11⁄2"
11⁄2"
2"
2"
21⁄2"
21⁄2"
21⁄2"
3"
3"
3"
31⁄2"
31⁄2"
31⁄2"
4"
4"
4"
5"
5"
5"
6"
6"
6"
1
1
1.125
1.125
1.420
1.420
1.770
1.770
2.190
2.190
2.468
2.468
3.031
3.031
3.516
3.516
3.516
4.234
4.234
4.234
4.781
4.781
4.781
5.328
5.328
5.328
6.328
6.328
6.328
7.406
7.406
7.406
.560
.560
.742
.742
.944
.944
1.242
1.242
1.449
1.449
1.860
1.860
2.222
2.222
2.222
2.761
2.761
2.761
3.193
3.193
3.193
3.623
3.623
3.623
4.542
4.542
4.542
5.458
5.458
5.458
LUG
LENGTH
1.310
1.675
1.310
1.675
1.310
1.675
1.310
1.675
1.310
1.675
1.310
1.675
1.310
1.675
2.230
1.310
1.675
2.230
1.310
1.675
2.230
1.310
1.675
2.230
1.310
1.675
2.230
1.310
1.675
2.230
WIRE
RANGE
SWING BUSHING AWG
RADIUS HEIGHT CU/AL
1.212
1.402
1.360
1.550
1.535
1.725
1.745
1.935
1.884
2.074
2.165
2.355
2.408
2.598
2.928
2.767
2.957
3.287
3.040
3.230
3.560
3.314
3.504
3.834
3.814
4.000
4.334
4.353
4.543
4.875
.657
.657
.660
.660
.735
.735
.735
.735
.770
.770
.770
.770
.940
.940
.940
.975
.975
.975
.975
.975
.975
.980
.980
.980
.985
.985
.985
1.200
1.200
1.200
14-4
8-2/0
14-4
8-2/0
14-4
8-2/0
14-4
8-2/0
14-4
8-2/0
14-4
8-2/0
14-4
8-2/0
6-4/0
14-4
8-2/0
6-4/0
14-4
8-2/0
6-4/0
14-4
8-2/0
6-4/0
14-4
8-2/0
6-4/0
14-4
8-2/0
6-4/0
Temperature rating 150° C
Meets Coast Guard Regulation CG293
Available with DURA-PLATE ® Finish.
United States
Tel: 901.252.8000
800.816.7809
Fax: 901.252.1354
Canada
Tel: 450.347.5318
Fax: 450.347.1976
Technical Services
Tel: 888.862.3289
www.tnb.com
A-9
Rigid and Intermediate Metal Conduit Fittings
Meets and surpasses NEC® requirements!
Insulated Throat Fittings
Locknut-type base improves bonding
and resists loosening under vibration.
• Steel or malleable iron
(steel through 11⁄2")
Metallic Bushings
• Exceeds NEC 373-6C requirements
for protection of ungrounded
connectors at entrance to raceways,
pull boxes and junctions
• Aluminum, steel or malleable
iron (steel through 11⁄2")
• Smoothly rounded shoulder
covers end of conduit
• Recognizable by distinctive trademarked
blue insulating liner in throat
• Broad flange covers knockout hole
• High ribs for easy tightening with fingers
or with wrench
• Reduces wire pulling effort
by as much as 50%
• Temperature rating of 105° C
Nylon insulated
metallic bushings
• Look for the unique T&B blue color,
ensuring the highest quality fitting
• 1⁄2" to 11⁄2" sizes, formed in steel, feature
extra-smooth shoulders
®
®
CAT. NO.
CAT. NO.
STL. OR M.I.
ALUM.
SIZE
1222
1223
1224
1225
1226
1227
1228
1229
1230
1231
1232†
586
587
⁄2"
3
⁄4"
1"
11⁄4"
11⁄2"
2"
21⁄2"
3"
31⁄2"
4"
41⁄2"
5"
6"
1222AL
1223AL
1224AL
1225AL
1226AL
1227AL
1228AL
1229AL
1230AL
1231AL
1232AL†
586AL
587AL
1
DIMENSIONS (IN.)
A
B
11⁄32
19⁄32
119⁄32
115⁄16
23⁄16
211⁄16
33⁄16
327⁄32
47⁄16
47⁄8
—
531⁄32
73⁄16
⁄64
31
⁄64
11
⁄32
21
⁄32
23
⁄32
7
⁄8
1
⁄32
5
⁄16
11⁄16
13⁄32
—
19⁄32
111⁄32
29
† Not CSA Certified
Catalog series 1222 thru 1232, 586 and 587 are available in aluminum. Add suffix
AL to Cat. No. The aluminum series fittings are not CSA certified.
STL. OR M.I.
ALUM.
SIZE
122
123
124
125-TB
126
127
128
129
130-TB
131-TB
132-TB
133-TB
134-TB
122AL
123AL*
124AL**
125AL
126AL
127AL
128AL
129AL
130AL
131AL
—
133AL
134AL
⁄2"
⁄4"
1"
11⁄4"
11⁄2"
2"
21⁄2"
3"
31⁄2"
4"
41⁄2"
5"
6"
DIMENSIONS (IN.)
A
B
11⁄32
11⁄4
19⁄16
129⁄32
25⁄32
221⁄32
33⁄16
327⁄32
43⁄8
415⁄16
57⁄16
6
71⁄4
1
3
* Not UL Listed or CSA Certified
UL File No. E-23018
** Not CSA Certified
CSA File No. 2884
All Plastic Insulating
Bushings
• Impact-resistant plastic insulation
• Ribbed for easy, secure gripping
• UL Listed 105° C
A-10
www.tnb.com
®
®
DIMENSIONS (IN.)
CAT. NO.
SIZE
A
222-TB
223-TB
224
225-TB
226
227
228-TB
229-TB
230-TB
231
232
233
234
⁄2"
3
⁄4"
1"
11⁄4"
11⁄2"
2"
21⁄2"
3"
31⁄2"
4"
41⁄2"
5"
6"
11⁄16
19⁄32
19⁄16
129⁄32
27⁄32
225⁄32
33⁄8
41⁄16
45⁄8
51⁄8
511⁄16
65⁄16
77⁄16
1
UL Rated flame retardant 94V-1
United States
Tel: 901.252.8000
800.816.7809
Fax: 901.252.1354
7
Available with DURA-PLATE ® Finish.
Perfect threads for easy thread-on!
Plastic Insulating Bushings
⁄32
⁄16
1
⁄2
9
⁄16
19
⁄32
5
⁄8
3
⁄4
13
⁄16
15
⁄16
1
15⁄64
13⁄16
11⁄4
13
Canada
Tel: 450.347.5318
Fax: 450.347.1976
Technical Services
Tel: 888.862.3289
B
⁄8
⁄32
9
⁄16
9
⁄16
9
⁄16
5
⁄8
3
⁄4
3
⁄4
7
⁄8
7
⁄8
1
1
1
3
13
Rigid and Intermediate Metal Conduit Fittings
For threadless rigid conduit and intermediate metal conduit.
Insulating Bushing
A
Application
• When assembled to the end of a threadless conduit,
provides a well-rounded insulating surface over which
conductors may be pulled or on which conductors may
bear while in service
B
Features
• Designed to be popped onto, and bush, conduit end
C
• Fast, easy installation without screws
• High-impact thermoplastic constructio
Standard Material
Listed by
High-impact thermoplastic listed for
105° C (221° F) application
UL (UL File No. E-13938)
TRIB-75
CSA (LR-2884, LR-4484)
Flammability Classification 94 V-1
Conforms to
Standard Finish
UL 514B
As molded
NFPA 70
TRIB-100
Range
⁄2" through 4" conduit
1
1. Cut conduit end squarely.
Remove sharp edges and burrs
on inside and outside diameters
by reaming or filing.
TRIB-150
®
®
2. Slip the pop-on bushing over
the end of the conduit.
3. Using the flat surface of any standard utility tool such as an
electrician’s pliers (or a hammer with a block of wood for the larger
sizes), strike the bushing on its top surface using a series of light
blows until the end of the conduit rests against the bushing throat
and conduit stop.
CAT. NO.
SIZE
A
DIMENSIONS (IN.)
B
C
TRIB-50
TRIB-75
TRIB-100
TRIB-125
TRIB-150
TRIB-200
TRIB-250
TRIB-300
TRIB-350
TRIB-400
⁄2"
⁄4"
1"
11⁄4
11⁄2"
2"
21⁄2"
3"
31⁄2"
4"
⁄32
⁄32
1
15⁄16
117⁄32
131⁄32
223⁄64
259⁄64
33⁄8
327⁄32
1 ⁄32
125⁄64
11⁄2
15⁄8
121⁄32
113⁄16
2
27⁄32
25⁄16
213⁄32
11⁄16
11⁄4
19⁄16
159⁄64
211⁄64
211⁄16
31⁄4
329⁄32
429⁄64
5
1
3
19
25
9
I.M.C. sizes 1⁄2" thru 4"
UL Rated flame retardant 94V-1
UL File No. E-13938
CSA File No. 2884
United States
Tel: 901.252.8000
800.816.7809
Fax: 901.252.1354
Canada
Tel: 450.347.5318
Fax: 450.347.1976
Technical Services
Tel: 888.862.3289
www.tnb.com
A-11
Rigid and Intermediate Metal Conduit Fittings
Knockout Bushing
3210 Series
Application
• To bush knockout openings in metal
boxes or enclosures
Listed/Certified by
Features
• One-piece construction designed
to snap in place
Conforms to
• High-impact strength, self extinguishing,
non-dripping (per UL 94) thermoplastic
construction
Provides smooth, rounded
insulation surface for
easy wire pulling!
UL (UL File No. E-3803)
CSA (LR-589,LR-4484)
UL 514B
CSA C22.2 No. 18
NFPA 70-1999 (ANSI)
Standard Material
Thermoplastic rated for 105° C (221° F) application
Standard Finish
As molded
• Quickly snaps into outlet box,
switch box or other enclosure left
vacant by wiring modifications or
maintenance changes
Range
.875" through 2.469" nominal diameter knockout
opening (1⁄2" through 2" trade size knockouts)
• High-impact thermoplastic,
one-piece construction
Wall thickness of box or enclosure
.095" max. up to 1" trade size
• Easily installed by hand
CAT.
NO.
FOR USE IN
KO SIZE*
DIMENSION (IN.)
B
3210
3211
3212
3213
3214
3215
.875
1.109
1.375
1.734
1.984
2.469
.360
.360
.360
.400
.520
.520
* Per UL and NEMA standards. Refer to “Knockout Plugs”
table on next page.
Oxygen index >28°
UL 94V-1
UL File No. E-3803
CSA File No. 589
Capped Bushings
CAT. NO.
SIZE
DIMENSION (IN.)
A
B
• Removable with pliers
1460
1461
1462
1463
1464
1465
⁄2"
⁄4"
1"
11⁄4"
11⁄2"
2"
11⁄32
11⁄4
19⁄16
129⁄32
25⁄32
221⁄32
UL File No. E-23018
CSA File No. 2884
.140" max. 11⁄4" through 2" trade size
• UL Listed 105° C
Makes a workman-like seal against grit, plaster and mischief!
Capped Bushings
• ⁄2" through 1 ⁄4" sizes in steel
1
1
• 11⁄2" and 2" sizes in malleable iron
1
3
⁄32
⁄16
1
⁄2
9
⁄16
19
⁄32
5
⁄8
13
7
Snaps into a regular bushing to
make a UL Listed insulated bushing!
INSULINER® Sleeves
• Converts ordinary bushing to code-approved
insulated bushing without disturbing wiring
• For use with standard rigid conduit, EMT
(thinwall conduit) or any standard bushed outlet
• Especially suited for use with flexible
metallic conduit
• High-dielectric nylon material, rated 105° C
Slip over wires —
insert into bushing —
snaps into place
A-12
www.tnb.com
United States
Tel: 901.252.8000
800.816.7809
Fax: 901.252.1354
Canada
Tel: 450.347.5318
Fax: 450.347.1976
CAT. NO.
SIZE
DIMENSION (IN.)
A
B
422
423
424
425
426
427
428
429
430
431
433
434
⁄2"
⁄4"
1"
11⁄4"
11⁄2"
2"
21⁄2"
3"
31⁄2"
4"
5"
6"
⁄8
⁄16
7
⁄8
1
1
11⁄8
11⁄4
11⁄2
125⁄32
21⁄32
21⁄2
21⁄2
Oxygen index >28°
UL File No. E-23018
Technical Services
Tel: 888.862.3289
1
3
5
11
.025
.025
.025
.030
.030
.030
.040
.040
.055
.055
.070
.070
CSA File No. 589
Rigid and Intermediate Metal Conduit Fittings
Made from flame-retardant, non-dripping thermoplastic, UL rated 105° C!
Knockout Plugs
1451 Series
Application
• To plug unused knockout openings in a box or enclosure
Features
• One-piece construction designed to snap in place
105° C rated by UL Made from
flame retardant, non-dripping
thermoplastic.
• High impact strength self-extinguishing non-dripping
(per UL-94) thermoplastic construction
Standard Material
Wall thickness of box or enclosure
.095" max. up to 1" trade size
Thermoplastic rated for 105° C (221° F) application
Standard Finish
.140" max. through 2" trade size.
As molded
Listed/Certified by
Range
UL (UL File No. E13938)
.875" through 2.469" Nominal Diameter
CSA (LR589)
Knockout opening ( ⁄2" through 2" trade size knockouts)
Conforms to
1
CAT.
NO.
SIZE
DIMENSIONS (IN.)
A
B
1451
1452
1453
1454
1455
1456
⁄2"
⁄4"
1"
11⁄4"
11⁄2"
2"
1.060
1.300
1.590
1.860
2.240
2.740
1
3
.400
.400
.400
.450
.570
.570
Wall thickness of electrical box .095 max.
Meets Coast Guard Regulation CB293.
UL File No. E-13938
CSA File No. 4484
UL 514B
NFPA 70
Eliminates need for separate capped bushing or steel penny and bushing!
Plug, Conduit, Connectors (Push-Penny® Plugs)
Conforms to
Application
• To plug open end of conduit or connector
in order to prevent ingress of trash,
dirt or moisture during construction
and remodeling
Features
• Wide range of applications; can be used
with rigid metal conduit, intermediate
metal conduit, electrical metallic tubing,
all connnectors and all bushings
• Designed to stand up to normal
handling and is functionally
unaffected by moisture
• Economically seal out grout and
plaster from any fitting or raceway
conforming to CSA dimensional
tolerances
• Just push into place
• Pressure holds plug fast against
internal surface of fitting or raceway
• Made of flexible plastic
Standard Material
Polyethylene
Standard Finish
As molded
Listed/Certified by
• Used under a bushing to seal
end of conduit during construction
• Completely salvageable
United States
Tel: 901.252.8000
800.816.7809
Fax: 901.252.1354
CAT. NO.
SIZE
1470
1471
1472
1473
1474
1475
1476*
1477*
1478*
1479*
⁄2"
⁄4"
1"
11⁄4"
11⁄2"
2"
21⁄2"
3"
31⁄2"
4"
1
3
*Not CSA Certified.
CSA File No. 2884
UL not applicable.
CSA (LR2884, LR4484)
Made to fit any bushing!
Pennies — Steel
UL 514B
CSA C22.2 No. 18
NFPA 70
NEMA FB1
CAT. NO.
SIZE
CAT. NO.
SIZE
815-TB
816
817
818
819
820
⁄2"
⁄4"
1"
11⁄4"
11⁄2"
2"
821
822
824
823
21⁄2"
3"
31⁄2"
4"
Canada
Tel: 450.347.5318
Fax: 450.347.1976
1
3
UL not applicable.
CSA File No. 2884
Technical Services
Tel: 888.862.3289
www.tnb.com
A-13
Rigid and Intermediate Metal Conduit Fittings
Bush holes in metal boxes or enclosures!
CHASE® Nipples
CAT. NO.
STL. OR M.I.
841TB
842TB
843TB
844
845
846
847
848
849
850
851
853
854
• 3⁄8" and 1⁄2" sizes in steel
• 3⁄4" to 6" sizes in malleable iron
DIMENSIONS (IN.)
B
ALUM.
SIZE
A
—
842ALTB†
843ALTB
844AL†
845AL†
846AL
847AL
848AL
849AL
850AL
851AL
853AL
854AL
⁄8"
⁄2"
3
⁄4"
1"
11⁄4"
11⁄2"
2"
21⁄2"
3"
31⁄2"
4"
5"
6"
⁄16
1 ⁄16
13⁄8
111⁄16
21⁄32
23⁄8
215⁄16
39⁄16
43⁄8
51⁄8
51⁄8
61⁄2
75⁄8
3
1
⁄16
⁄64
19
⁄32
3
⁄64
25
⁄32
13
⁄16
31
⁄32
11⁄16
11⁄4
15⁄16
15⁄16
15⁄16
13⁄8
15
7
43
9
† Not UL Listed
• 1⁄2" to 6" sizes in copper-free aluminum
Available with DURA-PLATE® Finish.
UL File No. E-23018
CSA File No. 2884
Nylon insulator offers extra protection!
CHASE® Nipples — Nylon-Insulated
• 3⁄8" and 1⁄2" sizes in steel
• 3⁄4" to 6" sizes in malleable iron
• 1⁄2" to 6" sizes in copper-free aluminum
• Look for the unique T&B blue color ensuring
the highest quality fitting available
A-14
www.tnb.com
United States
Tel: 901.252.8000
800.816.7809
Fax: 901.252.1354
CAT. NO.
SIZE
A
DIMENSIONS (IN.)
B
C
1942
1943
1944
1945
1946
1947
1948
1949
1950
1951
1953
1954
⁄2"
3
⁄4"
1"
11⁄4"
11⁄2"
2"
21⁄2"
3"
31⁄2"
4"
5"
6"
19⁄64
13⁄8
111⁄16
21⁄32
23⁄8
215⁄16
39⁄16
43⁄8
51⁄8
51⁄8
63⁄8
75⁄8
⁄16
17
⁄32
21
⁄32
25
⁄32
13
⁄16
31
⁄32
11⁄16
1i
15⁄16
15⁄16
15⁄16
13⁄8
⁄32
⁄32
7
⁄8
11⁄32
13⁄32
111⁄32
17⁄16
119⁄32
125⁄32
113⁄16
113⁄16
17⁄8
1
UL File No. E-23018
CSA File No. 2884
Canada
Tel: 450.347.5318
Fax: 450.347.1976
Technical Services
Tel: 888.862.3289
7
19
23
Rigid and Intermediate Metal Conduit Fittings
For Threaded Rigid Metal Conduit/IMC/PVC Coated Rigid Metal Conduit.
Threaded Hubs (Bullet® Hubs)
Copper-Free Aluminum
Copper free aluminum castings for fittings have a maximum of 0.4%
copper. The most detrimental effect of higher percentage of copper on
aluminum base alloy is its decrease in corrosion resistance.
(A)
Predetermined
Compression
(B)
(C)
Standard Material
370-485 Series
370AL
⁄2" thru 1" Steel
All Copper-Free Aluminum
Body:
1
Locknut:
1
1
21⁄2" thru 6" Malleable Iron
21⁄2" thru 4" Copper-Free
Aluminum
11⁄4" thru 6" Malleable Iron
(E)
(D)
⁄2" thru 2" Steel (hardened)
370 Series
370AL Series
Application
• To connect threaded metal conduit (ferrous rigid/non-ferrous rigid/
PVC coated/or intermediate metal) to a threadless opening in a box
or enclosure in outdoors or indoor location exposed to continuous
or intermittent moisture
Screws:
Steel (hardened)
O-Ring:
Buna N
⁄2" thru 2" Steel (hardened)
Insulator: Nylon
Coating:
PVC
Standard Finish
• To positively bond conduit to box or enclosure
Features
• Rugged steel/malleable iron/copper-free aluminum construction
• Tapered internal threads for water-tight/dust-tight union (A)
• Threads relieved to prevent bottoming of conduit, ensuring
sound assembly (B)
370 Series
370AL Series
Hub; Electro Zinc Plated
As Cast
Chromate Coated
485 Series
PVC — Outside Electro Zinc
Plated Chromate Coated Inside
Locknuts: All Ferrous Locknuts Electro Zinc Plated and Chromate Coated
Screws:
All Electro Zinc Plated and Chromate Coated
• Recessed sealing ring at box end; sealing ring captivated (C)
Range:
• Hardened steel/malleable iron/copper-free aluminum locknuts
designed to provide high-quality ground continuity; extended reach
of locknut permits clamping on thin boxes and enclosures (D)
370 Series
1
370AL & 485 Series
1
⁄2" thru 6" Conduit
⁄2" thru 4" Conduit
All hub threads — straight pipe
• Insulated throat, insulates conductors, prevents abrasion
and thinning of conductor insulation, reduces wire pull effort (E)
All female threads — taper pipe
(NPT)
• Suitable for hazardous location use per following:
(i) Class I Division 2, Class II Division 1 & 2, Class III Division
1 & 2 per NEC 501-4 (b); 502-4 (a) and 503-3 (a)
Listed/Certified by
(ii) Class II Groups E, F, G, & Class III locations per CEC 18-202;
18-252; 18-302; 18-352
CSA (LR-637, LR-23086)
UL (UL File No: E-23018)
(G)
(A)
• PVC coated 485 Series
Conforms to
(i) Protects connector from extremely corrosive surroundings
without affecting integrity of electrical grounding path (F)
(ii) Provided with overlapping sleeve for additional seal (G)
CSA C22.2 No. 18
(B)
NFPA 70
National Electrical Code® states that, “Where practical, dissimilar metals in
contact anywhere in the system shall be avoided to eliminate the possibility
of galvanic action.” The only exceptions, aluminum fittings and enclosures,
are permitted to be used with steel conduit.
Joint Industrial Council (JIC) Electrical Standards also forbid dissimilar
metals in contact for the same reason and require that the fittings for metal
conduit be of malleable iron or ductile iron and have impact strength
comparable to that of the conduit.
United States
Tel: 901.252.8000
800.816.7809
Fax: 901.252.1354
(F)
UL 514B
(G)
NEMA FB-1
JIC EGP1; JIC EMP 1
(C)
Federal Specification
A-A-50553
(D)
(E)
485 Series
Federal Standard H-28 (Threads)
Canada
Tel: 450.347.5318
Fax: 450.347.1976
Technical Services
Tel: 888.862.3289
www.tnb.com
A-15
Rigid and Intermediate Metal Conduit Fittings
Nylon insulated!
Steel/Malleable Iron and Aluminum Hub Connectors*†
®
®
CAT. NO.
STL. OR M.I.
• Aluminum, steel or malleable iron (steel through 1")
• With neoprene O-ring, provides watertight threaded
hub on enclosures
• UL Listed 105° C
• Look for the unique T&B blue color ensuring
the highest quality fitting
370
371
372
373
374
375
376
377
378
379
381
382
ALUM.**
SIZE
370AL
371AL
372AL
373AL
374AL
375AL
376AL
—
—
—
—
—
⁄2"
⁄4
1"
11⁄8"
11⁄2"
2"
21⁄2"
3"
31⁄2"
4"
5"
6"
DIMENSIONS (IN.)
A
B
C
13⁄8
15⁄8
23⁄32
29⁄16
33⁄32
35⁄8
41⁄8
5
59⁄16
63⁄16
8
93⁄16
1
3
* Suitable for hazardous locations use in
Class I, Div. 2; Class II, Div. 2; Class III,
Div. 1 and 2 where general purpose
equipment is specifically permitted per
NEC Section 500-2(a).
11⁄4
11⁄4
13⁄8
15⁄8
15⁄8
15⁄8
17⁄8
21⁄2
21⁄2
21⁄2
31⁄8
31⁄8
⁄4
⁄4
7
⁄8
1
1
1
11⁄8
11⁄2
11⁄2
11⁄2
WALL
THICK
(MAX.)
⁄16
⁄16
5
⁄16
5
⁄16
5
⁄16
5
⁄16
3
⁄8
1
⁄2
1
⁄2
1
⁄2
1
⁄2
1
⁄2
3
5
3
5
† UL Listed rain tight and CSA Certified
watertight and dust tight
Available with DURA-PLATE® Finish.
UL File No. E-23018
For Stl.: CSA File No. 2284
** Aluminum not available with insulated
throat.
For AL.: CSA File No. 0637
PVC coating protects hub in corrosive environments!
PVC-Coated Hub for Rigid Conduit
LOCKNUT
B
PLASTIC
COATING
NFS THREAD
• Steel in 1⁄2" to 11⁄4" sizes
C
A
• Malleable iron from 11⁄2" to 4" sizes
Insulator
Sealing ring
CAT. NO.
Steel or malleable iron (steel thru 11⁄4").
485
486
487
488
489
490
491
492
493
494
CONDUIT SIZE
A
DIMENSIONS (IN.)
B
C
⁄2"
3
⁄4"
1"
11⁄4"
11⁄2"
2"
21⁄2"
3"
31⁄2"
4"
121⁄64
119⁄32
127⁄32
215⁄32
229⁄32
33⁄8
327⁄32
421⁄32
59⁄64
53⁄4
21⁄8
21⁄8
23⁄4
33⁄8
35⁄8
33⁄4
4
45⁄8
413⁄16
49⁄16
17⁄8
21⁄8
23⁄8
31⁄8
31⁄2
4
41⁄2
55⁄8
57⁄8
67⁄16
1
Suitable for hazardous locations use per Class I, Div. 2; Class II, Div. 1 & 2; Class III, Div. 1
& 2 NEC 501-4(b); 502-4(a) (2); 503-3(a) where general purpose equipment is specifically
permitted per NEC Section 500-2(a).
A-16
www.tnb.com
United States
Tel: 901.252.8000
800.816.7809
Fax: 901.252.1354
Canada
Tel: 450.347.5318
Fax: 450.347.1976
Technical Services
Tel: 888.862.3289
Rigid and Intermediate Metal Conduit Fittings
Spacing Chart for Bullet® Hubs
⁄2
⁄4
1
15⁄8
13⁄4
—
—
—
—
—
—
—
—
13⁄4
17⁄8
2
—
—
—
—
—
—
—
1
⁄2
3
⁄4
1
11⁄4
11⁄2
2
21⁄2
3
31⁄2
4
3
17⁄16
—
—
—
—
—
—
—
—
—
1
CENTER TO CENTER SPACING
CONDUIT SIZES (IN.)
11⁄4
11⁄2
2
21⁄8
21⁄4
23⁄8
211⁄16
—
—
—
—
—
—
23⁄8
21⁄2
25⁄8
215⁄16
31⁄8
—
—
—
—
—
2 ⁄2
3
3 ⁄2
4
MIN. SPACE FROM
CENTER OF
BULLET® HUB TO
WALL OF BOX
27⁄8
3
31⁄8
31⁄2
33⁄4
4
41⁄4
—
—
—
35⁄16
31⁄2
35⁄8
4
41⁄8
41⁄2
43⁄4
51⁄8
—
—
31⁄2
33⁄4
37⁄8
41⁄4
43⁄8
43⁄4
5
53⁄8
55⁄8
—
37⁄8
41⁄8
41⁄4
41⁄2
43⁄4
5
53⁄8
53⁄4
6
61⁄4
⁄4
⁄8
11⁄8
13⁄8
15⁄8
17⁄8
21⁄8
25⁄8
27⁄8
31⁄4
1
25⁄8
23⁄4
27⁄8
31⁄4
31⁄2
33⁄4
—
—
—
—
1
3
7
KO
DIAMETERS
(MIN.)
7
⁄8
11⁄8
13⁄8
13⁄4
2
21⁄2
3
35⁄8
41⁄8
45⁄8
Bullet® Hub Connectors — Nylon Insulated
®
CAT. NO.
SIZE
(IN.)
401
402
403
404-TB
405
406-TB
407
408
409
410-TB
⁄2
⁄4
1
11⁄4
11⁄2
2
21⁄2
3
31⁄2
4
PACKAGING
CARTON
STD.
DESCRIPTION
25
25
5
5
2
1
1
1
—
—
1
3
Steel or malleable iron (steel through
1 inch). Used with a neoprene O-ring
to provide a watertight* threaded hub
on enclosures. Supplied with 106 series
bonding locknut. Temperature rating: 105° C.
WT.
PER 100
100
50
25
25
10
5
5
5
1
1
20
26
44
75
100
138
200
375
425
500
*CSA LR2884. Certified watertight and dust tight.
Spacing Chart for Bullet® Sealing Hubs
⁄2
1
⁄2
3
⁄4
1
11⁄4
11⁄2
2
21⁄2
3
31⁄2
4
5
6
1
1 ⁄16
—
—
—
—
—
—
—
—
—
—
—
7
⁄4
1
11⁄4
CENTER TO CENTER SPACING
CONDUIT SIZES
1
1 ⁄2
2
21⁄2
1 ⁄8
13⁄4
—
—
—
—
—
—
—
—
—
—
1 ⁄4
17⁄8
2
—
—
—
—
—
—
—
—
—
2 ⁄8
21⁄4
23⁄8
211⁄16
—
—
—
—
—
—
—
—
2 ⁄8
21⁄2
25⁄8
215⁄16
31⁄8
—
—
—
—
—
—
—
3
5
3
1
3
United States
Tel: 901.252.8000
800.816.7809
Fax: 901.252.1354
2 ⁄8
23⁄4
27⁄8
31⁄4
31⁄2
33⁄4
—
—
—
—
—
—
5
2 ⁄8
3
31⁄8
31⁄2
33⁄4
4
41⁄4
—
—
—
—
—
7
3
31⁄2
4
5
6
3 ⁄16
31⁄2
35⁄8
4
41⁄8
41⁄2
43⁄4
51⁄8
—
—
—
—
31⁄2
33⁄4
37⁄8
41⁄4
43⁄8
43⁄4
5
53⁄8
55⁄8
—
—
—
37⁄8
41⁄8
41⁄4
41⁄2
43⁄4
5
53⁄8
53⁄4
6
61⁄4
—
—
47⁄8
413⁄16
415⁄16
55⁄16
77⁄16
53⁄4
6
63⁄8
63⁄4
71⁄8
8
83⁄4
55⁄16
51⁄2
511⁄16
53⁄4
63⁄16
61⁄2
63⁄4
71⁄8
71⁄2
77⁄8
83⁄4
91⁄2
5
Canada
Tel: 450.347.5318
Fax: 450.347.1976
MIN. SPACE FROM
CENTER OF
KO
BULLET® HUB TO DIAMETERS
WALL OF BOX
(MIN.)
⁄4
⁄8
11⁄8
13⁄8
15⁄8
17⁄8
21⁄8
25⁄8
27⁄8
31⁄4
4
43⁄4
3
7
⁄8
11⁄8
13⁄8
13⁄4
2
21⁄2
3
35⁄8
41⁄8
45⁄8
51⁄2
61⁄2
7
Technical Services
Tel: 888.862.3289
www.tnb.com
A-17
Rigid and Intermediate Metal Conduit Fittings
T&B Hub
®
®
A
Never before has a single hub fit like this one. Designed
for unequalled performance. The innovative engineering
of the T&B® Hub will, quite simply, raise your performance
expectations for threaded hubs. Look for the distinctive
blue color to ensure the quality of a Thomas & Betts fitting.
Locknut Design with peripheral slots and a hexagonal/
angled spline spaced every 30° enables easy application
of torque with wrench or hammer and screwdriver. (See
Figures 2 & 3)
3
Sharper and Deeper Teeth on locknut and body designed
for a more penetrating bite for improved bonding to the
enclosure.
4
Hexagonal/Splined Body Design for fast, easy installation
with wrench or hammer and screwdriver.
5
Precision Machined Tapered Threads designed to create
watertight union.
6
Insulated Throat molded from 105° C rated thermoplastic
with a flammability rating of 94 V-O.
19⁄16
119⁄32
113⁄16
17⁄8
17⁄8
115⁄16
29⁄16
27⁄16
223⁄32
223⁄32
31⁄32
35⁄32
⁄8
⁄32
11⁄16
11⁄16
11⁄16
15⁄32
19⁄16
119⁄32
15⁄8
15⁄8
115⁄16
2
D
E
MAX. PANEL THROAT
THICKNESS DIA.
DIA.
H050-TB
H075-TB
H100-TB
H125-TB
H150-TB
H200-TB
H250-TB
H300-TB
H350-TB
H400-TB
H500-TB
H600-TB
⁄2
3
⁄4
1
11⁄4
11⁄2
2
21⁄2
3
31⁄2
4
5
6
17⁄16
17⁄16
2
23⁄8
23⁄4
31⁄4
33⁄4
43⁄8
5
51⁄2
67⁄8
711⁄16
Material –
Hub and Locknut:
zinc or copper-free aluminum
Insulating Throat:
thermoplastic temp. rating – 105° C
1
⁄16
⁄16
1
⁄4
1
⁄4
1
⁄4
1
⁄4
1
⁄4
1
⁄4
1
⁄4
1
⁄4
1
⁄4
5
⁄16
7
⁄32
⁄32
1
15⁄16
117⁄32
131⁄32
213⁄32
231⁄32
313⁄32
37⁄8
415⁄16
6
3
29
19
3
25
Flammability Rating – 94V-0
Sealing Ring and Groove with innovative profile outperforms
standard O-ring design. Sealing ring is captivated in place
before installation and resists buckling or slipping during
installation. The seal groove is designed for optimum
compression of the sealing ring. The sealing ring is
designed to provide a complete 360° seal, even when
the conduit is not perpendicular with the enclosure.
(See Figure 1)
2
C
CAT. NO.
Sealing Ring:
1
B
TRADE
SIZE
Nitrile (BUNA “N”)
For Aluminum Hubs add suffix A (i.e., H050A). For Chrome-Plated Hubs add suffix CP
(i.e., H050CP). For 316 Stainless Steel Hubs add suffix GRSST (i.e., H050GRSST).
(1⁄2" through 2" only.) Meets NEMA sealing requirements for NEMA 3R, 4 & 13 enclosures.
UL Listed and CSA Certified. CSA Certified for hazardous locations Class II Groups
E.F.G. Class III.
UL File No. E-23018
CSA File No. 4484
Chrome-Plated Hubs (suffix-“CP”) are rated NEMA 4X.
4
5
1
3
22
6
Throat Dia. E
B
D
Fig. 1
Fig. 2
C
Fig. 3
A
A-18
www.tnb.com
United States
Tel: 901.252.8000
800.816.7809
Fax: 901.252.1354
Canada
Tel: 450.347.5318
Fax: 450.347.1976
Technical Services
Tel: 888.862.3289
Rigid and Intermediate Metal Conduit Fittings
T&B Grounding Hub
A
CAT. NO.
TRADE
SIZE
DIA.
⁄2
3
⁄4
1
11⁄4
11⁄2
2
21⁄2
3
31⁄2
4
5
6
17⁄16
17⁄16
2
23⁄8
23⁄4
31⁄4
33⁄4
43⁄8
5
51⁄2
67⁄8
711⁄16
H050GR-TB
H075GR-TB
H100GR-TB
H125GR-TB
H150GR-TB
H200GR-TB
H250GR-TB
H300GR-TB
H350GR-TB
H400GR-TB
H500GR-TB
H600GR-TB
1
Material – Hub and Locknut: zinc or copper-free aluminum
Insulating Throat: thermoplastic temp. rating –
105°C
Flammability Rating – 94V-0
Sealing Ring:
Nitrile (BUNA “N”)
B
C
19⁄16
119⁄32
113⁄16
17⁄8
17⁄8
115⁄16
29⁄16
27⁄16
223⁄32
223⁄32
31⁄32
35⁄32
⁄8
⁄32
11⁄16
11⁄16
11⁄16
15⁄32
19⁄16
119⁄32
15⁄8
15⁄8
115⁄16
2
D
MAX. PANEL
THICKNESS
E
THROAT
DIA.
⁄16
⁄16
1
⁄4
1
⁄4
1
⁄4
1
⁄4
1
⁄4
1
⁄4
1
⁄4
1
⁄4
1
⁄4
5
⁄16
⁄32
⁄32
1
15⁄16
117⁄32
131⁄32
213⁄32
231⁄32
313⁄32
37⁄8
415⁄16
6
7
3
29
3
19
25
For Aluminum Hubs add suffix A (i.e., H050A). For Chrome-Plated
Hubs add suffix CP (i.e., H050CP). For 316 Stainless Steel Hubs
add suffix GRSST (i.e., H050GRSST). (1⁄2" through 2" only.) Meets
NEMA sealing requirements for NEMA 3R, 4 & 13 enclosures.
UL Listed and CSA Certified. CSA Certified for hazardous
locations Class II Groups E.F.G. Class III.
UL File No. E-23018
CSA File No. 4484
Chrome-Plated Hubs (suffix-“CP”) are rated NEMA 4X.
T&B Grounding and
Bonding Locknut
Throat Dia. E
B
A
D
C
A
Grounding Locknut for Hubs
T&B Hub Centerline Spacing Chart
CONDUIT
TRADE SIZE
⁄2"
⁄4"
1"
11⁄4"
11⁄2"
2"
21⁄2"
3"
31⁄2"
4"
5"
6"
Nearest Obstruction
to Center of Hub
1
3
⁄2"
1
19⁄16
143⁄64
127⁄32
21⁄32
27⁄32
215⁄32
223⁄32
31⁄32
311⁄32
319⁄32
4s
411⁄16
27
⁄32
⁄4"
3
125⁄32
161⁄64
29⁄64
221⁄64
237⁄64
2K
39⁄64
321⁄64
345⁄64
3ç
4J
61
⁄64
1" 11⁄4" 11⁄2" 2" 21⁄2" 3"
21⁄8
25⁄16
21⁄2
23⁄4
3
35⁄16
35⁄8
37⁄8
49⁄16
431⁄32
11⁄8
21⁄2
211⁄16
215⁄16
33⁄16
31⁄2
313⁄16
41⁄16
43⁄4
55⁄32
15⁄16
27⁄8
31⁄8
33⁄8
311⁄16
4
41⁄4
415⁄16
511⁄32
11⁄2
33⁄8
35⁄8
315⁄16
41⁄4
41⁄2
53⁄16
519⁄32
13⁄4
37⁄8
43⁄16
41⁄2
43⁄4
57⁄16
527⁄32
2
41⁄2
413⁄16
51⁄16
53⁄4
65⁄32
25⁄16
31⁄2" 4"
51⁄8
53⁄8
61⁄16
615⁄32
25⁄8
5"
6"
55⁄8
65⁄16 7
623⁄32 713⁄32 713⁄16
27⁄8 29⁄16 331⁄32
CAT. NO.
L050GR-TB
L075GR-TB
L100GR-TB
L125GR-TB
L150GR-TB
L200GR-TB
L250GR-TB
L300GR-TB
L350GR-TB
L400GR-TB
L500GR-TB
L600GR-TB
®
®
TRADE
SIZE
A
DIA.
B
HEIGHT
GROUND
SCREW
MAX. CONDUCTOR
SIZE
⁄2
⁄4
1
11⁄4
11⁄2
2
21⁄2
3
31⁄2
4
5
6
11⁄2
111⁄16
2
23⁄8
23⁄4
31⁄4
33⁄4
43⁄8
5
51⁄2
65⁄8
711⁄16
⁄32
⁄32
13
⁄32
15
⁄32
15
⁄32
15
⁄32
11
⁄16
23
⁄32
23
⁄32
23
⁄32
23
⁄32
23
⁄32
#10-32 x 1⁄4"
#10-32 x 1⁄4"
#10-32 x 1⁄4"
1
⁄4-20 x 1⁄4"
1
⁄4-20 x 5⁄16"
1
⁄4-20 x 5⁄16"
1
⁄4-20 x 5⁄16"
1
⁄4-20 x 5⁄16"
1
⁄4-20 x 5⁄16"
1
⁄4-20 x 5⁄16"
3
⁄8-16 x 3⁄8"
3
⁄8-16 x 3⁄8"
#10
#10
#10
#10
#8
#8
#6
#6
#6
#4
#2
#1
1
3
13
13
Material – Locknut: zinc or copper-free aluminum
UL File No. E-3060
For Aluminum Locknuts add suffix A. (i.e., L050GRA)
CSA File No. 4484
For Chrome-Plated Locknuts add suffix CP. (i.e., L050CP). For 316 Stainless Steel Locknuts
add suffix SST (1⁄2" through 2" only.) For Locknut with Lay In Lug add suffix GRL
United States
Tel: 901.252.8000
800.816.7809
Fax: 901.252.1354
Canada
Tel: 450.347.5318
Fax: 450.347.1976
Technical Services
Tel: 888.862.3289
www.tnb.com
A-19
Rigid and Intermediate Metal Conduit Fittings
Raintight for Rigid or Intermediate
Metal Conduit (IMC)
Chase Threaded Conduit Hubs
®
Applications:
• A fitting for connecting junction box to junction box, or junction box
to the conduit system. The resulting connection maintaining ground
continuity is raintight.
• Suitable for use where the system is normally hosed down
(NEMA 4) for cleaning.
HT, HTZ
Features/Benefits:
• Plastic insulated throat, precision cast and machined
surfaces permit safer wire pulling.
• Chase® design provides maximum space for wiring
in the box.Locking nipple sits flush in the enclosure.
• Captive O-ring fits snugly in groove preventing loss
and fumbling with parts.
• Knurled inner face of locking nipple provides 360 degrees
of locking and bites through box wall to ensure grounding.
• Locking nipple has tightening lugs on two planes for easier
assembly in hard to reach field conditions.
HTGZ
Smoot
conduit
stops
Plastic
insulated
throat
• Grounding hubs have a ground screw located within
the enclosure providing a tamper-proof ground for device.
Precision
machined
threads
• Locking nipple design permits replacement of the box
without disassembling the installation.
Standard Materials:
• HTZ Series: Certified die cast zinc alloy ZAMAK 3.
• HT Series: Die cast aluminum alloy A360 with less
than .004 copper content (copper-free).
• O-ring: Buna N
• Insulating Sleeves: Plastic
Standard Finish:
• Aluminum lacquer finish
Knurled teeth
bite box
Convenient
ground screw
option
Space
saving
design
Captive
O-ring
Compliances:
• UL Listed
• CSA Certified
• Suitable for use in Wet Locations
• NEMA 4
A-20
www.tnb.com
United States
Tel: 901.252.8000
800.816.7809
Fax: 901.252.1354
Canada
Tel: 450.347.5318
Fax: 450.347.1976
Technical Services
Tel: 888.862.3289
Rigid and Intermediate Metal Conduit Fittings
Chase® Hub with Insulated Throat
CAT. NO.
HUB SIZE
STD. PKG.
WT. LBS.
APP. PER 100
HTZ1
HTZ2
HTZ3
HTZ4
HTZ5
HTZ6
HTZ7
HTZ8
HTZ9*
HTZ10*
⁄2"
⁄4"
1"
11⁄4"
11⁄2"
2"
21⁄2"
3"
31⁄2"
4"
25
25
25
10
10
10
5
2
2
2
26
32
45
58
74
93
202
250
300
360
1
3
HTZ
*Made to order item. Consult factory for lead time and minimum quantities.
Chase® Hub with Insulated Throat and Ground Screw
CAT. NO.
HUB SIZE
STD. PKG.
WT. LBS.
APP. PER 100
HTGZ1
HTGZ2
HTGZ3
HTGZ4
HTGZ5
HTGZ6
HTGZ7
HTGZ8
HTGZ9
HTGZ10
⁄2"
⁄4"
1"
11⁄4"
11⁄2"
2"
21⁄2"
3"
31⁄2"
4"
25
25
25
10
10
10
5
2
2
2
22
34
44
61
75
95
204
265
270
360
1
3
HTGZ
Chase® Aluminum Hub with Insulated Throat
CAT. NO.
HT1
HT2
HT3
HT4
HT5
HT6
HT7
HT8
HT9
HT10
HUB SIZE
STD. PKG.
WT. LBS.
APP. PER 100
⁄2"
⁄4"
1"
11⁄4"
11⁄2"
2"
21⁄2"
3"
31⁄2"
4"
25
25
25
10
10
10
5
2
2
2
12
14
20
27
32
44
85
120
138
155
1
3
HT
J
F°
HTZ, HTGZ and HT
HUB
SIZE
A
B
C
⁄2"
3
⁄4"
1"
11⁄4"
11⁄2"
2"
21⁄2"
3"
31⁄2"
4"
13⁄8
13⁄8
119⁄32
123⁄32
13⁄4
125⁄32
21⁄4
221⁄64
223⁄64
23⁄8
113⁄32
121⁄32
17⁄8
25⁄16
25⁄8
35⁄32
245⁄64
45⁄16
413⁄16
55⁄16
⁄4
1
⁄4
1
⁄4
1
⁄4
1
⁄4
1
⁄4
3
⁄8
3
⁄8
3
⁄8
3
⁄8
1
1
PANEL
WIDTH
D
E
⁄16
3
⁄16
3
⁄16
1
⁄4
1
⁄4
1
⁄4
1
⁄4
1
⁄4
1
⁄4
1
⁄4
⁄2–14
3
⁄4–14
1–111⁄2
11⁄4–111⁄2
11⁄2–111⁄2
2–111⁄2
21⁄2–8
3–8
31⁄2–8
4–8
3
1
F
MIN.
G
MAX.
H
O-RING
SIZE
J
60
60
60
60
60
60
45
45
45
45
21
⁄52
13⁄32
15⁄16
143⁄64
129⁄32
23⁄8
27⁄8
31⁄2
4
41⁄2
59
⁄64
111⁄64
122⁄32
151⁄64
213⁄64
221⁄32
35⁄32
349⁄64
47⁄16
463⁄64
214
218
222
225
227
231
236
241
245
248
United States
Tel: 901.252.8000
800.816.7809
Fax: 901.252.1354
Canada
Tel: 450.347.5318
Fax: 450.347.1976
G
MNTG HOLE
B
D
A
E
(THREAD) NPT
C
Technical Services
Tel: 888.862.3289
www.tnb.com
A-21
Rigid and Intermediate Metal Conduit Fittings
T&B Bulkhead Fittings
®
®
CAT. NO.
Bulkhead Fitting
Bulkhead Fitting
Across Flats
Diameter
Thru Bulkhead Fitting
Thread
Nipple Nut
Not Included
Thru Bulkhead Hub
Height
Nipple Nut
Not Included
NPSL THREAD
B
⁄2
⁄4
1
11⁄4
11⁄2
2
21⁄2
3
31⁄2
4
5
6
Thru Bulkhead Fitting
H050TBF
H075TBF
H100TBF
H125TBF
H150TBF
H200TBF
⁄2
⁄4
1
11⁄4
11⁄2
2
Thru Bulkhead Hub
H050TBH
H075TBH
H100TBH
H125TBH
H150TBH
H200TBH
⁄2
⁄4
1
11⁄4
11⁄2
2
1
3
THREAD
HEIGHT
DIAMETER
ACROSS
FLATS
⁄2"
⁄4"
1"
11⁄4"
11⁄2"
2"
21⁄2"
3"
31⁄2"
4"
5"
6"
⁄2"–14"
⁄4"–14"
1"–111⁄2"
11⁄4"–111⁄2"
11⁄2"–111⁄2"
2"–111⁄2"
21⁄2"–8"
3"–8"
31⁄2"–8"
4"–8"
5"-8"
6"–8"
1 ⁄32"
115⁄32"
111⁄16"
125⁄32"
113⁄16"
127⁄32"
29⁄32"
29⁄16"
29⁄16"
29⁄16"
223⁄32"
3"
1 ⁄16"
111⁄16"
2"
23⁄8"
23⁄4"
31⁄4"
33⁄4"
43⁄8"
5"
51⁄2"
65⁄8"
711⁄16"
1"
11⁄4"
117⁄32"
127⁄32"
11⁄8"
25⁄8"
31⁄8"
325⁄32"
49⁄32"
427⁄32"
529⁄32"
71⁄32"
3
A
H050BHD
H075BHD
H100BHD
H125BHD
H150BHD
H200BHD
H250BHD
H300BHD
H350BHD
H400BHD
H500BHD
H600BHD
TRADE
SIZE
1
NPT THREAD
TRADE SIZE (IN.)
1
3
13
Material — Hub, Body and Locknut:
Insulating Throat:
7
1
3
1
3
A (IN.) B (IN.)
⁄4
⁄32
29
⁄32
29
⁄32
29
⁄32
15
⁄16
17⁄32
13⁄16
13⁄8
13⁄8
115⁄32
11⁄2
3
25
⁄2
⁄32
19
⁄32
21
⁄32
21
⁄32
21
⁄32
7
⁄8
29
⁄32
7
⁄8
7
⁄8
7
⁄8
31
⁄32
1
17
Zinc or copper-free aluminum
Thermoplastic temp. rating – 105° C
Flammability Rating – 94V-0
Sealing Ring:
Nitrile (BUNA “N”)
For Aluminum Bulkheads add suffix A.
For Chrome-Plated Bulkheads add suffix CP.
Meets NEMA sealing requirements for
NEMA 3R. 4 & 13 enclosures.
A-22
www.tnb.com
United States
Tel: 901.252.8000
800.816.7809
Fax: 901.252.1354
Canada
Tel: 450.347.5318
Fax: 450.347.1976
Technical Services
Tel: 888.862.3289
CSA Certified for hazardous locations Class
II Groups E.F.G. Class III.
UL File No. E-3060
CSA File No. 4484
Rigid and Intermediate Metal Conduit Fittings
Offset Reducers
®
®
C
TRADE
SIZE
CAT. NO.
B
Height
A
H150-TB075ORGR 11⁄2"–3⁄4"
H150-TB100ORGR 19⁄32"–1"
H150-TB125ORGR 19⁄32"–11⁄4"
H250-TB200ORGR 21⁄2"–2"
Material –
Dia. (Ø)
HEIGHT DIA. (Ø)
121⁄32"
125⁄32"
125⁄32"
21⁄8"
Offset Reducer and Locknut:
Insulating Throat:
23⁄4
23⁄4
23⁄4
33⁄4
A DIA.
B
(IN.)
C
⁄16
11⁄16
11⁄16
13⁄16
⁄32
23
⁄32
23
⁄32
15
⁄16
129⁄32 19⁄32
129⁄32 19⁄16
129⁄32 17⁄8
229⁄32 221⁄32
15
23
D
E
⁄32
⁄32
1
⁄32
3
⁄32
11
7
Zinc or copper-free aluminum
Thermoplastic Temp. Rating – 105° C
Flammability Rating – 94V-0
Dia. (0)
Sealing Ring:
Nitrile (BUNA “N”)
For Aluminum Offset Reducer add suffix A.
For Chrome-Plated Offset Reducer add suffix CP.
Meets NEMA sealing requirements for NEMA 3R. 4 & 13 enclosures.
D
CSA Certified for hazardous locations Class II Groups E.F.G. Class III.
UL File No. E-3060
CSA File No. 4484
E
Capoffs
®
®
B
A
C
Capoff
Height
CAT. NO.
TRADE
SIZE
HEIGHT
DIAMETER
A
B
C
H050CAP
H075CAP
H100CAP
H125CAP
H150CAP
H200CAP
H250CAP
H300CAP
H350CAP
H400CAP
H500CAP
H600CAP
⁄2"
3
⁄4"
1"
11⁄4"
11⁄2"
2"
21⁄2"
3"
31⁄2"
4"
5"
6"
113⁄32"
115⁄32"
111⁄16"
125⁄32"
113⁄16"
127⁄32"
29⁄32"
29⁄16"
29⁄16"
29⁄16"
223⁄32"
3"
17⁄16
111⁄16
2
23⁄8
23⁄4
31⁄4
33⁄4
43⁄8
5
51⁄2
65⁄8
75⁄8
⁄32
19
⁄32
11
⁄16
23
⁄32
23
⁄32
23
⁄32
7
⁄8
7
⁄8
29
⁄32
29
⁄32
29
⁄32
31
⁄32
⁄32
11⁄16
13⁄16
121⁄32
129⁄32
23⁄8
229⁄32
31⁄32
41⁄32
41⁄2
59⁄16
65⁄8
⁄16
⁄16
1
⁄4
1
⁄4
1
⁄4
1
⁄4
1
⁄4
11
⁄32
11
⁄32
11
⁄32
11
⁄32
11
⁄32
1
Material – Capoff and Locknut:
Insulating Throat:
(IN.)
19
27
3
3
zinc or copper-free aluminum
Thermoplastic temp. rating – 105° C
Flammability Rating – 94V-0
Diameter
Sealing Ring:
Nitrile (BUNA “N”)
For Aluminum Capoff add suffix A.
For Chrome-Plated Capoff add suffix CP.
Meets NEMA sealing requirements for NEMA 3R. 4 & 13 enclosures.
CSA Certified for hazardous locations Class II Groups E.F.G. Class III.
UL File No. E-3060
CSA File No. 4484
United States
Tel: 901.252.8000
800.816.7809
Fax: 901.252.1354
Canada
Tel: 450.347.5318
Fax: 450.347.1976
Technical Services
Tel: 888.862.3289
www.tnb.com
A-23
Rigid and Intermediate Metal Conduit Fittings
No disassembly required.
XJG-TB Rigid Conduit Expansion Coupling
Whenever you install a rigid expansion
coupling in a long conduit run, you
normally need three hands, two strong
backs and lots of patience. Now you can
relax. With the no-hassle Rigid Conduit
Expansion Coupling, installation’s just
a few turns and you’re done.
8" Movement
Gland
Nut
The T&B Rigid Conduit Expansion
Coupling features innovations that
provide conveniences to the installer,
saving time and money on the job.
There’s no disassembly needed during
the installation, requiring fewer tools
and less opportunities for lost pieces.
It also features a true internal bonding
jumper, eliminating the need for external
jumpers, so there are fewer parts to buy
and install.
If you need a fitting that can give and
take without a lot of hassle, reach for
T&B’s XJG-TB Rigid Conduit Expansion
Coupling. It’s the latest breakthrough
in the industry’s leading line of conduit
fittings. Contact your local representative
for more information regarding the
XJG-TB Rigid Conduit Expansion Coupling
and the complete line of conduit fittings
from the name you trust for quality design
and manufacturing, Thomas & Betts.
Bonding
Bushing
Internal Bonding
Jumper
Internal Sliding
Bushing (keyed)
1
4" Movement
Slide the fitting onto the
conduit until it stops at the
internal sliding bushing.
Tighten and you’re ready.
No parts to reassemble!
XJG24-TB
2
Innovative Design Makes
Installations Easier.
With a wrench, tighten
the gland nut to compress
the Teflon packing,
creating a raintight seal
around
the conduit.
• No disassembly necessary to install
• Fast, simple, and requires fewer steps
• True Internal Bonding Jumper —
no external grounding strap required
• Tamper-proof internal jumper protected
from the environment
• Exceeds code requirements for long
conduit runs to permit linear movement
A-24
www.tnb.com
United States
Tel: 901.252.8000
800.816.7809
Fax: 901.252.1354
3
Thread the next length of
conduit into the other end
of the fitting and tighten.
You’re done!
Canada
Tel: 450.347.5318
Fax: 450.347.1976
Technical Services
Tel: 888.862.3289
Rigid and Intermediate Metal Conduit Fittings
B
C
A
XJG Conduit Expansion Coupling
XJG Conduit Expansion Coupling for EMT
CAT NO.
SIZE
MOVEMENT
A
DIAMETER
B
LENGTH
C
HEIGHT
XJG24-TB
XJG28-TB
XJG34-TB
XJG38-TB
XJG44-TB
XJG48-TB
XJG54-TB
XJG58-TB
XJG64-TB
XJG68-TB
XJG74-TB
XJG78-TB
XJG84-TB
XJG88-TB
XJG94-TB
XJG98-TB
XJG104-TB
XJG108-TB
XJG1208-TB
⁄4"
⁄4"
1"
1"
11⁄4"
11⁄4"
11⁄2"
11⁄2"
2"
2"
21⁄2"
21⁄2"
3"
3"
31⁄2"
31⁄2"
4"
4"
5"
4"
8"
4"
8"
4"
8"
4"
8"
4"
8"
4"
8"
4"
8"
4"
8"
4"
8"
8"
2.43
2.43
2.67
2.67
3.36
3.36
3.36
3.36
3.86
3.86
4.96
4.96
4.96
4.96
6.37
6.37
6.37
6.37
7.99
10.00
14.00
10.00
14.00
10.56
14.56
10.56
14.56
11.25
15.25
12.12
16.12
12.12
16.12
12.87
16.87
12.87
16.87
18.87
2.75
2.75
2.99
2.99
3.68
3.68
3.68
3.68
4.18
4.18
5.25
5.25
5.25
5.25
6.75
6.75
6.75
6.75
8.56
3
3
CAT NO.
SIZE
IN. (MM)
MOVEMENT
IN. (MM)
A
LENGTH IN. (MM)
B
HEIGHT IN. (MM)
XJG24-EMT
XJG28-EMT
XJG34-EMT
XJG38-EMT
XJG44-EMT
XJG48-EMT
XJG54-EMT
XJG58-EMT
XJG64-EMT
XJG68-EMT
XJG74-EMT
XJG78-EMT
XJG84-EMT
XJG88-EMT
XJG94-EMT
XJG98-EMT
XJG28-TB
XJG108-EMT
4" (101.6)
8" (203.2)
4" (101.6)
8" (203.2)
4" (101.6)
8" (203.2)
4" (101.6)
8" (203.2)
4" (101.6)
8" (203.2)
4" (101.6)
8" (203.2)
4" (101.6)
8" (203.2)
4" (101.6)
8" (203.2)
4" (101.6)
8" (203.2)
⁄4" (21)
⁄4" (21)
1" (27)
1" (27)
11⁄4" (35)
11⁄4" (35)
11⁄2" (41)
11⁄2" (41)
2" (53)
2" (53)
21⁄2" (63)
21⁄2" (63)
3" (78)
3" (78)
31⁄2" (91)
31⁄2" (91)
4" (103)
4" (103)
17.39 (441.7)
21.39 (543.3)
17.42 (442.5)
21.42 (544.1)
18.27 (464.1)
22.27 (565.7)
18.69 (474.7)
22.69 (576.3)
19.04 (483.6)
23.04 (585.2)
23.23 (589.9)
27.23 (691.6)
24.09 (611.9)
28.09 (713.5)
28.70 (728.9)
28.70 (728.9)
29.30 (743.9)
29.30 (743.9)
2.75 (69.8)
2.75 (69.8)
2.99 (75.9)
2.99 (75.9)
3.46 (87.88)
3.46 (87.88)
3.68 (93.4)
3.68 (93.4)
4.18 (106.2)
4.18 (106.2)
4.52 (114.8)
4.52 (114.8)
5.25 (133.4)
5.25 (133.4)
6.00 (152.4)
6.00 (152.4)
6.75 (171.5)
6.75 (171.5)
3
3
Please consult Technical Services for special orders and availability of products
not shown in this list.
B
B
Standard Materials / Finish
A
Body . . . . . . . . . . . . . . . . . . . . . . . . .Ductile Iron, available PVC Coated
Internal Bonding Jumper . . . . . . . . .Tinned Copper Braid
Listed / Certified By:
Exterior and Interior Finish . . . . . . .Zinc Plating, Aluminum Acrylic Paint
®
Packing . . . . . . . . . . . . . . . . . . . . . .PTFE/Synthetic Fiber Material
®
UL
(File E23018, Std. 514B)
Suitable for Wet Locations
CSA
(File LR2884, Std. C22.2 No. 18)
(Teflon® Coated)
XJG24-EMT
NEC 250.98
Suggested Specifications
Expansion Fittings for Rigid Steel or Intermediate Metal Conduit
• Fitting shall be raintight after installation.
Where raceways require expansion fittings to compensate for thermal
expansion and contraction and where expansion fittings and telescoping
sections of metal raceway shall be made electrically continuos by bonding
jumpers or other means:
• The fitting shall have an internal bonding jumper constructed of a tinned
copper braid, sized to meet UL fault current test requirements and
comply with bonding requirements — NEC article 250.98
• Fitting will be constructed from malleable or ductile iron with exterior
and interior zinc plating for corrosion protection.
• External bonding jumper shall not be required to comply with NEC
requirements.
• Accepted Manufacturers: Thomas & Betts - XJG-TB Series
• The fitting shall be constructed so that disassembly is not required
during installation.
United States
Tel: 901.252.8000
800.816.7809
Fax: 901.252.1354
Canada
Tel: 450.347.5318
Fax: 450.347.1976
Technical Services
Tel: 888.862.3289
www.tnb.com
A-25
Rigid and Intermediate Metal Conduit Fittings
Threadless Connector/Coupling
(For Threadless Rigid Metal Conduit and Intermediate Metal Conduit)
8123 Series
8130 Series
Standard Material
Application
• To connect and effectively bond threadless
rigid metal conduit/intermediate metal
conduit to a box or enclosure, or to couple
ends of threadless conduit
Body . . . . . . . . . . . . . . . . . . . . . . All Malleable Iron
Features
• Steel/Malleable Iron construction
Locknut . . . . . . 1⁄2" thru 2" Steel (hardened) 2" thru
4" Malleable Iron
• Case-hardened ring bites into conduit
for high-quality continuity and grip
Standard Finish
• Nylon insulator firmly secured in place
protects conductors and reduces wire pulling
effort by as much as 50%; prevents thread
damage in handling
Range
Nut, Gland 1⁄2" to 1" Steel – 11⁄4" to 4" Malleable Iron
Ring . . . . . . . . . . . . . . . . . . . Steel (case hardened)
Insulator . . . . . . . . . . . . . . . . . . . . . . . . . . . . Nylon
Electro Zinc Plated & Chromate Coated
8123 & 8120 Series. . 1⁄2" through 4" Size Conduit
8130 Series . . . . . . . . 1⁄2" through 2" Size Conduit
All hub threads . . . . . . . . . . . . Straight Pipe (NPS)
• Case-hardened steel locknut or malleable iron
locknut designed to provide a positive bond
8120 Series
• Suitable for concrete-tight application
• Capable of carrying ground fault currents up
to 10,000 amps RMS (1⁄2" through 11⁄2" size)
and 20,000 amps RMS (2" and above sizes)
for a duration of current 3 cycles
Conforms to
Listed/Certified by
UL 514B
UL (UL File No: E-23018)
CSA C22.2 No. 18
CSA (LR-2884, LR-4484)
NFPA 70
NEMA FB1
Federal Specification A-A-50553
Federal Standard H-28 (Threads)
Split steel ring with diagonal serrations grips conduit and bites in for positive ground!
Threadless Connectors — Nylon Insulated
• Makes a permanent connection
• Eliminates need for cutting a thread on conduit
• Insulation helps ensure continuity of service by protecting
the conductor at the critical point — the connector bushing
CAT. NO.
• Malleable iron construction
• Look for the unique T&B blue color, ensuring the highest
quality fitting
NYLON
INSUL.
8123
8223
8323
8423
8523
8623
8723-TB
8823
8853
8973
NONINSUL.
CONDUIT
SIZE
A
DIMENSIONS (IN.)
B
C
8121
8221
8321
8421
8521
8621
8721
8821
8851
8971
⁄2"
3
⁄4"
1"
11⁄4"
11⁄2"
2"
21⁄2"
3"
31⁄2"
4"
17⁄32
117⁄32
129⁄32
23⁄8
211⁄16
31⁄4
41⁄8
47⁄8
51⁄2
61⁄32
111⁄16
13⁄4
2
27⁄16
25⁄8
213⁄16
313⁄16
4
41⁄8
47⁄8
11⁄2
11⁄2
9
⁄16
11
⁄16
3
⁄4
27
⁄32
11⁄8
17⁄32
11⁄8
11⁄8
1
Available with DURA-PLATE® Finish.
A-26
www.tnb.com
United States
Tel: 901.252.8000
800.816.7809
Fax: 901.252.1354
Canada
Tel: 450.347.5318
Fax: 450.347.1976
UL File No. E-23018
Technical Services
Tel: 888.862.3289
CSA File No. 2884
Rigid and Intermediate Metal Conduit Fittings
Just tighten with a wrench to make a UL Listed
and CSA Certified concrete-tight connection!
Threadless Couplings
• Eliminates need for conduit threading
• Malleable iron construction
CAT.
NO.
SIZE
A
B
8120
8220
8320
8420
8520
8620
8720
8820
8850
8970
⁄2"
3
⁄4"
1"
11⁄4"
11⁄2"
2"
21⁄2"
3"
31⁄2"
4"
19⁄32
119⁄32
17⁄8
23⁄8
25⁄8
31⁄4
315⁄16
411⁄16
53⁄16
511⁄16
2
25⁄16
211⁄16
213⁄16
35⁄8
313⁄16
53⁄8
51⁄2
51⁄2
51⁄2
DIMENSIONS (IN.)
1
Available with DURA-PLATE® Finish.
UL File No. E-23018
CSA File No. 2884
Ideal for entering enclosure or conduit body at right angles!
Threadless Short Elbows — Nylon Insulated
• Eliminates need to thread conduit
• As with straight couplings, makes a concrete-tight connection
• Malleable iron construction
CAT.
NO.
8130
8131
SIZE
A
DIMENSIONS (IN.)
B
⁄2"
3
⁄4"
111⁄32
15⁄8
11⁄2
13⁄4
1
C
⁄2
⁄16
1
9
Available with DURA-PLATE® Finish.
UL File No. E-23018
CSA File No. 2884
United States
Tel: 901.252.8000
800.816.7809
Fax: 901.252.1354
Canada
Tel: 450.347.5318
Fax: 450.347.1976
Technical Services
Tel: 888.862.3289
www.tnb.com
A-27
Rigid and Intermediate Metal Conduit Fittings
Set Screw Connector/Coupling
(For Threadless Rigid Metal Conduit and Intermediate Metal Conduit)
Application
• To connect and effectively bond threadless
rigid metal conduit or intermediate metal
conduit to a box or enclosure or to couple
ends of threadless conduit
8124 Series
8125 Series
• Coupling provided with positive center stop
Standard Finish
• Suitable for concrete-tight application
Electro Zinc Plated &
Chromate Coated
Features
• Thickwall steel or malleable iron body
• Capable of carrying ground fault currents
up to 10,000 amps RMS (1⁄2" through 11⁄2" size)
and 20,000 amps RMS (2" and above sizes).
Listed/Certified by
• Hardened hex head cup point screw
to provide high-quality bond
Standard Material
• Screw captivated, will not vibrate loose
Body . . . . . . . . . . . . . . . . . . . 1⁄2" thru 2" Steel
21⁄2" thru 4" Malleable Iron
• Nylon insulated throat meets and exceeds
all code requirements for bushing:
Locknut . . . . . . . . . ⁄2" thru 2" Steel (hardened)
21⁄2" thru 4" Malleable Iron
CSA C22.2 No. 18
Screw . . . . . . . . . . . . . . . . . . Steel (hardened)
NEMA FB1
Insulator . . . . . . . . . . . . . . . . . . . . . . . . Nylon
Federal Specification A-A-50553
(i)
CSA (LR-2884, LR-4484)
Prevents thinning of insulation
(ii) Reduces installation effort
1
Conforms to
UL 514B
NFPA 70
Federal Standard H-28 (Threads)
(iii) Prevents first thread damage
Eliminates the need for conduit threading!
CAT.
NO.
Insulated Set-Screw Connector
8125
8225
8325
8425
8525
8625-TB
8725-TB
8825
8855
8975
• Captive hex head screws tighten
down onto conduit for positive holding
strength and ground
• Furnished with insulated throats
to reduce wire-pulling effort by
as much as 50%
UL (UL File No: E-23018)
8125 Series
• Approved concrete-tight
CONDUIT
SIZE
⁄2"
⁄4"
1"
11⁄4"
11⁄2"
2"
21⁄2"
3"
31⁄2"
4"
1
3
DIMENSIONS (IN.)
A
B
13⁄8
11⁄2
13⁄16
2
25⁄16
27⁄16
33⁄8
37⁄16
37⁄8
43⁄16
⁄32
⁄16
35
⁄64
5
⁄8
5
⁄8
11
⁄16
1
1
11⁄16
11⁄8
13
7
Sizes 1⁄2"–2" made of steel. Sizes 21⁄2"–4" are malleable iron.
Available with DURA-PLATE® Finish.
UL File No. E-23018 CSA File No. 2884
No need to thread conduit ends when joining rigid conduit!
Set-Screw Coupling
8124 Series
• Captive hex head screws
provide positive holding
strength and ground continuity
• Approved concrete-tight
CAT.
NO.
8124
8224
8324-TB
8424
8524
8624
8724
8824-TB
8854
8974
CONDUIT
SIZE
DIMENSION (IN.)
A
⁄2"
⁄4"
1"
11⁄4"
11⁄2"
2"
21⁄2"
3"
31⁄2"
4"
21⁄2
211⁄16
227⁄32
3
33⁄8
35⁄8
37⁄8
41⁄4
415⁄16
53⁄8
1
3
Sizes 1⁄2"–2" made of steel; sizes 21⁄2"–4" are malleable iron.
Available with DURA-PLATE® Finish.
UL File No. E-23018 CSA File No. 2884
A-28
www.tnb.com
United States
Tel: 901.252.8000
800.816.7809
Fax: 901.252.1354
Canada
Tel: 450.347.5318
Fax: 450.347.1976
Technical Services
Tel: 888.862.3289
Rigid and Intermediate Metal Conduit Fittings
Smoothly rounded shoulders protect conductor insulation!
Bushed Elbows
CAT.
NO.
SIZE
A
DIMENSION (IN.)
B
• Non-insulated
460-TB
461TB
462
463
⁄2"
3
⁄4"
1"
11⁄4"
11⁄8
11⁄2
113⁄16
21⁄4
113⁄16
21⁄4
211⁄16
31⁄8
• Malleable iron construction
1
Available with DURA-PLATE® Finish.
UL File No. E 23018.
C
⁄8
⁄8
3
⁄4
3
⁄4
5
5
CSA File No. 2884
Integral insulation ensures a smooth bushing in every fitting!
Short Elbows —
Nylon Insulated
• Malleable iron construction
CAT.
NO.
SIZE
A
DIMENSION (IN.)
B
C
4290
4291
4292
4293
4294
4295
⁄2"
⁄4"
1"
11⁄4"
11⁄2"
2"
1 ⁄32
17⁄16
123⁄32
27⁄32
215⁄32
3
1 ⁄4
15⁄16
19⁄16
21⁄16
23⁄16
29⁄16
⁄2
⁄16
11
⁄16
13
⁄16
13
⁄16
13
⁄16
1
7
3
Available with DURA-PLATE® Finish.
For non-insulated applications
Short Elbows
• Malleable iron construction
1
1
9
Not UL or CSA.
CAT.
NO.
SIZE
A
DIMENSION (IN.)
B
C
4250
4251
4252
4253
4254
4255
⁄2"
3
⁄4"
1"
11⁄4"
11⁄2"
2"
15⁄16
117⁄32
113⁄16
29⁄32
29⁄16
33⁄32
11⁄4
15⁄16
19⁄16
21⁄16
23⁄16
29⁄16
⁄16
⁄2
5
⁄8
11
⁄16
11
⁄16
11
⁄16
1
Available with DURA-PLATE® Finish.
U.L. File #E-23018
7
1
CSA File No. 589
Conduit Nipples —
CAT. NO.
Die-Cast Zinc, 1" Long
A
SIZE
A
B
⁄2"
3
⁄4"
1"
1"
1"
1"
⁄16"
13⁄16"
17⁄16"
HA-211
HA-212
HA-213
1
15
UL File No. E-1275 1⁄2" & 3⁄4" only
B
Offset Nipples — Die-Cast Zinc
A
3⁄4"
B
CAT. NO.
SIZE
A
B
HO-221
HO-222
HO-223
HO-224
HO-225
HO-226
⁄2"
3
⁄4"
1"
11⁄4"
11⁄2"
2"
2.60"
2.62"
2.68"
2.85"
2.88"
3.19"
1.00"
1.32"
1.51"
1.85"
2.08"
2.71"
1
⁄4" offset
3
UL File No. E-1275
United States
Tel: 901.252.8000
800.816.7809
Fax: 901.252.1354
Canada
Tel: 450.347.5318
Fax: 450.347.1976
Technical Services
Tel: 888.862.3289
www.tnb.com
A-29
Rigid and Intermediate Metal Conduit Fittings
Threaded Erickson® 3-Piece Coupling
(For Threaded Rigid Metal Conduit and Intermediate Metal Conduit)
674 Series
675AL Series
With an ERICKSON® coupling, a conduit run
may be completed when neither conduit can
be turned. A conduit run may also be broken
without taking down the whole run. Conduit
joined with ERICKSON® Couplings is rigid and
in line and vibration will not loosen the
connections. Malleable iron.
Standard Material
674 Series
Bushing & Case . . . . . . . . . . . Malleable Iron
Ring . . . . . . . . . . . . . . Steel & Malleable Iron
675AL Series
Application
• To couple and effectively
bond threaded ends of rigid metal
conduit/intermediate metal conduit
where neither length of conduit
can be rotated
Bushing & Case . . . . . . . . . . . . . . Aluminum
Ring . . . . . . . . . . . . . . . . . . . . . . . Aluminum
Standard Finish
674 Series: Electro Zinc Plated & Chromate
Coated
Features
• Malleable Iron/Steel/Copper-free
Aluminum construction
ALUM.*
675AL Series: Degreased
CAT.
NO.
Range
674
675
676
677
678
679
680TB
681
682
683
684
685
686
687
⁄8" thru 6" Conduit (malleable iron)
3
• Free fitting threads ensure easy assembly
⁄2" thru 6" Conduit (aluminum)
1
• Permits conduit coupling
without rotating either conduit
All straight pipe threads (NPS)
• Provides rigid in-line coupling
with high- quality grounding;
will not loosen under vibration
Listings/Compliances
• Suitable for concrete-tight application
NEMA FB1
• Capable of carrying ground fault
currents up to 10,000 amps RMS
(1⁄2" through 11⁄2" size) and up to 20,000
amps RMS (2" and above) (duration of
fault current 3 cycles) (674 series tested)
NFPA 70-1999 (ANSI)
UL 514B
CSA C22.2 No. 18
Federal Specification A-A-50553
Federal Standard H-28 (Threads)
Raintight
CAT.
NO.
SIZE
—
675AL
676AL
677AL
678AL
679AL
680AL
681AL
682AL
683AL
684AL
685AL
686AL
687AL
⁄8"
⁄2"
3
⁄4"
1"
11⁄4"
11⁄2"
2"
21⁄2"
3"
31⁄2"
4"
41⁄2"
5"
6"
DIMENSIONS (IN.)
A
B
11⁄8
115⁄32
19⁄16
129⁄32
23⁄8
25⁄8
37⁄32
331⁄32
47⁄16
5
51⁄2
61⁄4
625⁄32
8
3
1
11⁄8
11⁄4
113⁄32
15⁄8
113⁄16
131⁄32
27⁄32
211⁄16
229⁄32
3
33⁄16
315⁄32
33⁄4
41⁄32
*Copper-Free Aluminum
concrete-tight.
UL Listed and CSA Certified
UL File No. E-23018
CSA File No. 2884
Split Couplings
• Ideal for retrofit installations or in tight areas
• Fast installation
• Neoprene gasket provides a concrete-tight seal.
• Joins threaded conduit even when the conduit
can’t rotate.
• Approved for direct burial
. . . . . . . . . Specifications . . . . . . . . .
•
•
•
•
A-30
T&B’s Split Coupling is a simple method to join threaded
conduits in retrofits or in snug areas. Available in 1⁄2” to 6”.
Material: Malleable Iron
Gasket: Neoprene
Plating: Zinc Plated
Standards: UL Standard 514B, NEMA FB-1
www.tnb.com
1
⁄2" and 3⁄4"
furnished with
one screw
United States
Tel: 901.252.8000
800.816.7809
Fax: 901.252.1354
1" and 6"
furnished with
two screws
Canada
Tel: 450.347.5318
Fax: 450.347.1976
CAT. NO.
TRADE
SIZE
SPCP50
SPCP75
SPCP100
SPCP125
SPCP150
SPCP200
SPCP250
SPCP300
SPCP350
SPCP400
SPCP500
SPCP600
⁄2"
⁄4"
1"
11⁄4"
11⁄2"
2"
21⁄2"
3"
31⁄2"
4"
5"
6"
Technical Services
Tel: 888.862.3289
1
3
DIMENSIONS (IN.)
A
B
C
WEIGHT
PER 100
2"
25⁄16"
25⁄8"
31⁄16"
35⁄16"
313⁄16"
45⁄8"
55⁄16"
61⁄16"
69⁄16"
81⁄16"
91⁄4"
34.4
39.4
60.0
75.0
112.5
112.5
275.0
300.0
425.0
500.0
900.0
1,300.0
11⁄4"
11⁄4"
15⁄8"
15⁄8"
115⁄16"
2"
31⁄16"
31⁄8"
31⁄4"
37⁄16"
37⁄8"
43⁄16"
11⁄4"
11⁄2"
113⁄16"
23⁄16"
27⁄16"
27⁄8"
39⁄16"
41⁄8"
413⁄16"
53⁄8"
69⁄16"
75⁄8"
Rigid and Intermediate Metal Conduit Fittings
The ideal solution for applications requiring longer thread length!
Panel Connector Extensions
• Will combine with any fitting
with a male thread
• Male thread of panel connector
extension is 1" long
• Malleable iron construction
CAT.
NO.
SIZE
A
DIMENSIONS (IN.)
B
C
1440
1441
1442
1443
⁄2"
⁄4"
1"
11⁄4"
1 ⁄4
13⁄8
11⁄4
11⁄4
1 ⁄32
111⁄32
119⁄32
115⁄16
17⁄8
2
115⁄16
15⁄16
1
1
3
3
UL File No. E-23018
CSA File No. 2884
Adapt an outlet hole to the next larger size of conduit!
Male Enlargers*
CAT.
NO.
SIZE
A
DIMENSIONS (IN.)
B
C
1245
1246
1244
1247
⁄2" to ⁄4"
⁄4" to 1"
1" to 11⁄4"
11⁄4" to 11⁄2"
1 ⁄32
111⁄16
21⁄16
25⁄16
1 ⁄16
11⁄4
111⁄32
13⁄8
⁄2
⁄32
1
⁄2
9
⁄16
1
3
13
3
1
1
15
* All items shown in this chart are suitable for use in hazardous locations where general purpose
equipment is specifically permitted by the NEC; Class I, Div. 2; Class II, Div. 1 & 2; Class III,
Div. 1 & 2, NEC 501-4(b); 502-4(a)(b); 503-3(a)(b).
Available with DURA-PLATE® Finish.
UL File No. E-23018
CSA File No. 2884
• Built-in bushing covers
rough ends of conduit
• Malleable iron construction
Adapt any outlet to the next smaller size of conduit!
Female Reducers*
• Hex shoulder for easy wrench tightening
• Malleable iron construction
CAT.
NO.
SIZE
A
1250
1261
1251
1262
1263
1252
1253
1254
1255
1256
1257
1258
⁄4" to 1⁄2"
1" to 1⁄2"
1" to 3⁄4"
11⁄4" to 1⁄2"
11⁄4" to 3⁄4"
11⁄4" to 1"
11⁄2" to 11⁄4"
2" to 11⁄2"
21⁄2" to 2"
3" to 21⁄2"
31⁄2" to 3"
4" to 31⁄2"
11⁄8
17⁄16
13⁄8
113⁄16
113⁄16
13⁄4
2
23⁄8
3
35⁄8
41⁄8
45⁄8
3
DIMENSIONS (IN.)
B
⁄8
21
⁄32
11
⁄16
23
⁄32
23
⁄32
25
⁄32
13
⁄16
13⁄16
11⁄4
11⁄2
19⁄16
19⁄16
5
C
⁄16
⁄16
3
⁄16
3
⁄16
3
⁄16
7
⁄32
1
⁄4
9
⁄32
3
⁄8
1
⁄2
1
⁄2
1
⁄2
3
3
* All items shown in this chart are suitable for use in hazardous locations where general purpose equipment is specifically
permitted by the NEC; Class I, Div. 2; Class II, Div. 1 & 2; Class III, Div. 1 & 2, NEC 501-4(b); 502-4(a) (b); 503-3(a) (b).
Available with DURA-PLATE® Finish.
United States
Tel: 901.252.8000
800.816.7809
Fax: 901.252.1354
Canada
Tel: 450.347.5318
Fax: 450.347.1976
UL File No. E-23018
CSA File No. 2884
Technical Services
Tel: 888.862.3289
www.tnb.com
A-31
Rigid and Intermediate Metal Conduit Fittings
Stainless Steel Pipe Straps
• Higher degree of corrosion resistance than traditionalzinc plated
or hot-dipped galvanized straps
• One and two-hole straps for EMT sizes 1⁄2" through 2"
• One and two-hole straps for Rigid and IMC size 1⁄2" through 4"
• 303 Stainless Steel
TRADE WT. PER
SIZE
100
HOLE
DIA.
STD.
PKG.
1
TS101-SS
⁄2"
2.21
3
TS102-SS
⁄4"
2.49
TS103-SS
1"
3.31
TS104-SS
11⁄4"
3.64
TS105-SS
11⁄2"
3.87
TS106-SS
2"
4.03
One-Hole Rigid/IMC Straps
⁄4"
1
⁄4"
1
⁄4"
11
⁄16"
11
⁄16"
11
⁄16"
25
25
25
10
5
5
HS100-SS
HS101-SS
HS102-SS
HS103-SS
HS104-SS
HS105-SS
HS106-SS
HS107-SS
HS108-SS
HS110-SS
⁄32"
⁄32"
9
⁄32"
9
⁄32"
11
⁄32"
13
⁄32"
13
⁄32"
15
⁄32"
17
⁄32"
17
⁄32"
20
20
20
20
10
10
5
5
5
5
CAT. NO.
One-Hole EMT Straps
Thomas & Betts offers stainless steel pipe straps
to support and securely fasten rigid, IMC and EMT
conduit. One and two-hole stainless steel straps
are ideal for industrial applications such as petrochemical plants, manufacturing plants, pulp and
paper mills, food processing, power plants, refineries
and mining operations. Steel City® stainless steel
pipe straps are also useful in commercial applications
in schools, hospitals, office buildings, airports, casinos
and stadiums. To order, contact your local Thomas
& Betts authorized distributor and ask about the
complete offering of Steel City® straps, clamps
and hangers.
⁄8"
⁄2"
3
⁄4"
1"
11⁄4"
1 1⁄2"
2"
21⁄2"
3"
4"
1
Reduces threaded opening in conduit
bodies or any female threaded fitting!
• Smooth, built-in
bushing completely
covers rough ends
of conduit
• Malleable iron or
steel construction
(steel through 606,
also 614 and 615)
A-32
®
CAT. NO.
STD.
PKG.
1
1
TS901-SS
⁄2"
2.21
3
TS902-SS
⁄4"
3.31
TS903-SS
1"
3.87
TS904-SS
11⁄4"
7.54
TS905-SS
11⁄2"
12.21
TS906-SS
2"
18.23
Two-Hole Rigid/IMC Straps
⁄4"
⁄4"
1
⁄4"
11
⁄16"
11
⁄16"
11
⁄16"
25
25
25
10
5
5
9
9
HS901-SS
HS902-SS
HS903-SS
HS904-SS
HS905-SS
HS906-SS
HS907-SS
HS908-SS
HS909-SS
HS910-SS
⁄32"
⁄32"
9
⁄32"
11
⁄32"
13
⁄32"
13
⁄32"
15
⁄32"
17
⁄32"
17
⁄32"
17
⁄32"
20
20
20
10
10
5
5
5
5
5
Reducing
Washers
ALUM.
SIZE
600TB
601TB
602TB
603TB
604TB
605
606
607
608
609
610
611
612
613
614
615
600ALTB
601ALTB
602ALTB
603ALTB
604ALTB
605AL
606AL
607AL
608AL
609AL
610AL
611AL
612AL
613AL
614AL
615AL
⁄2" to 3⁄8"
3
⁄4" to 1⁄2"
1" to 1⁄2"
1" to 3⁄4"
11⁄4" to 1⁄2"
11⁄4" to 3⁄4"
11⁄4" to 1"
11⁄2" to 1⁄2"
11⁄2" to 3⁄4"
11⁄2" to 1"
11⁄2" to 11⁄4"
2" to 1⁄2"
2" to 3⁄4"
2" to 1"
2" to 11⁄4"
2" to 11⁄2"
1
2.49
3.64
4.15
8.17
17.50
21.37
21.54
25.72
27.27
31.70
3
CAT. NO.
⁄16
⁄16
5
⁄8
5
⁄8
13
⁄16
7
⁄8
15
⁄16
13
⁄16
13
⁄16
15
⁄16
3
⁄4
15
⁄16
15
⁄16
15
⁄16
15
⁄16
7
⁄8
9
9
• Used in pairs
• Interlock to form a rib
that centers washers
and conduit in knockout
• Galvanized steel
construction
3700
3701
3702
3703
3704
3705
3706
3707
3708
3709
3710
3711
3712
3713
3714
3715
3716
3717
3718
SIZE
⁄4" to 3⁄8"
⁄4" to 1⁄2"
1" to 3⁄8"
1" to 1⁄2"
1" to 3⁄4"
11⁄4" to 3⁄8"
11⁄4" to 1⁄2"
11⁄4" to 3⁄4"
11⁄4" to 1"
11⁄2" to 3⁄8"
11⁄2" to 1⁄2"
11⁄2" to 3⁄4"
11⁄2" to 1"
11⁄2" to 11⁄4"
2" to 1⁄2"
2" to 3⁄4"
2" to 1"
2" to 11⁄4"
2" to 11⁄2"
3
3
UL File No. E-23018
UL File No. E-13938
CSA File No. 2884
www.tnb.com
9
9
®
CSA File No. 2884
United States
Tel: 901.252.8000
800.816.7809
Fax: 901.252.1354
1
®
DIMENSION (IN.)
A
STL. ON MI
⁄2"
⁄4"
1"
11⁄4"
11⁄2"
2"
21⁄2"
3"
31⁄2"
4"
1
1
Reduce knockout hole in outlet box!
®
Threaded
Reducers
TRADE WT. PER
SIZE
100
Two-Hole EMT Straps
2.00
2.21
2.49
3.48
3.76
18.22
19.69
67.21
76.45
80.18
3
HOLE
DIA.
CAT. NO.
Canada
Tel: 450.347.5318
Fax: 450.347.1976
Technical Services
Tel: 888.862.3289
DIMENSIONS (IN.)
A
B
13⁄8
13⁄8
15⁄8
15⁄8
15⁄8
2
2
2
2
21⁄4
21⁄4
21⁄4
21⁄4
21⁄4
23⁄4
23⁄4
23⁄4
23⁄4
23⁄4
⁄64
⁄8
45
⁄64
7
⁄8
13⁄32
45
⁄64
7
⁄8
13⁄32
123⁄64
45
⁄64
7
⁄8
13⁄32
123⁄64
123⁄32
7
⁄8
13⁄32
123⁄64
123⁄32
131⁄32
45
7
Rigid and Intermediate Metal Conduit Fittings
1275 Series
1276AL Series
For Rigid Metal Conduit and
Intermediate Metal Conduit
Standard Material
Range
1275 Series . . . . . . 1976AL Series
1275 Series . . . . . . 1276AL Series
Conduit Straps
Malleable Iron . . . . . All copper-free
3
Application
• To support and securely fasten rigid metal conduit
and intermediate metal to the supporting surface
Standard Finish
aluminum
Features
• Rugged malleable iron/copper-free aluminum
construction — snugly fits on the conduit
Listed/Certified by
Hot Dipped . . . As Cast Galvanized
CSA (LR-2884, LR-4484)
Conforms to
A
CSA C22.2 No. 18
Conduit Strap
Conduit
• Galvanized finish 1275 Series
Conduit Spacer
• Copper-free aluminum 1276AL Series
Pipe Straps — Malleable
Iron or Aluminum
Elongated bolt hole makes alignment
easy, even when mounting-surface
holes are off center!
B
A
C
Pipe Straps — Steel
• High reinforcing ribs on each side
increase strength and reduce weight
• Snap-on design
(except for 3⁄8" size)
• Available in malleable iron with hot-dipped
galvanized finish or in copper-free aluminum
®
CAT. NO.
MAL. IRON
ALUM.
SIZE
A
B
C
SCREW
SIZE
1275†
1276†
1277†
1278†
1279†
1280†
1281
1282*
1283*
1284
1285*
1286
1287
1288
1275AL
1276AL†
1277AL†
1278AL†
1279AL†
1280AL
1281AL
1282AL
1283AL
1284AL
1285AL
—
—
—
⁄8"
⁄2"
3
⁄4"
1"
11⁄4"
11⁄2"
2"
21⁄2"
3"
31⁄2"
4"
41⁄2"
5"
6"
17⁄8"
25⁄32"
29⁄16"
3"
33⁄4"
43⁄16"
53⁄16"
515⁄16"
611⁄16"
719⁄32"
85⁄16"
93⁄16"
915⁄16"
111⁄2"
⁄16"
⁄32"
11
⁄16"
3
⁄4"
13
⁄16"
15
⁄16"
11⁄8"
11⁄2"
15⁄8"
13⁄4"
17⁄8"
115⁄16"
2"
27⁄16"
3
⁄4"
11⁄32"
17⁄32"
117⁄32"
17⁄8"
21⁄8"
217⁄64"
23⁄4"
311⁄32"
329⁄32"
413⁄32"
415⁄16"
515⁄32"
617⁄32"
#12
1
⁄4"
1
⁄4"
1
⁄4"
5
⁄16"
3
⁄8"
7
⁄16"
1
⁄2"
1
⁄2"
5
⁄8"
5
⁄8"
5
⁄8"
5
⁄8"
5
⁄8"
11
21
* May be used with EMT of same size.
UL not applicable.
† Not snap-on type.
CSA File No. 2884
C
• Rugged steel
construction
®
CAT. NO.
1210†
1211
1212
1213
1214
1215
1216
CONDUIT
SIZE
A
B
C
⁄8"
⁄2"
3
⁄4"
1"
11⁄4"
11⁄2"
2"
115⁄32
2
25⁄16
313⁄16
231⁄32
323⁄32
47⁄16
⁄4
⁄4
33⁄4
3
⁄4
9
1 ⁄16
113⁄16
25⁄16
⁄16
⁄16
1"
117⁄64
19⁄16
113⁄16
25⁄16
3
1
† Not snap-on type.
PVC-Coated Straps for Rigid Conduit
• Designed to fit each size
of conduit snugly
B
A
• Malleable iron construction
B
A
C
3
3
UL not applicable.
PVC coating offers high corrosion resistance!
• High reinforcing ribs on each side
increase strength and reduce weight
NFPA 70
Supporting Wall
Designed for snug fit on each
size of conduit!
1
conduit 6" conduit
1275 Series . . . . . . 1276AL Series
• Designed to prevent accumulation of moisture
and start of corrosion on vertical run of conduit (A)
3
⁄8" through . . . . . . . 1⁄2" through 6"
CAT. NO.
SIZE
1275CR
1276CR
1277CR
1278CR
1279CR
1280CR
1281CR
⁄8"
1
⁄2"
3
⁄4"
1"
11⁄4"
11⁄2"
2"
3
SCREW
SIZE
⁄4"
⁄4"
1
⁄4"
1
⁄4"
3
⁄8"
3
⁄8"
3
⁄8"
11
1
15
1
CSA File No. 2884
BOLT
SIZE
A
DIMENSIONS (IN.)
B
C
⁄4"
1
⁄4"
1
⁄4"
1
⁄4"
3
⁄8"
3
⁄8"
1
⁄2"
17⁄8
25⁄32
29⁄16
3
33⁄4
43⁄16
53⁄16
⁄16
21
⁄32
11
⁄16
3
⁄4
13
⁄16
15
⁄16
11⁄8
3
⁄4
11⁄32
17⁄32
117⁄32
17⁄8
21⁄8
217⁄64
1
11
UL not applicable.
United States
Tel: 901.252.8000
800.816.7809
Fax: 901.252.1354
Canada
Tel: 450.347.5318
Fax: 450.347.1976
Technical Services
Tel: 888.862.3289
www.tnb.com
A-33
Rigid and Intermediate Metal Conduit Fittings
Conduit Spacers
(For Rigid Metal Conduit, Intermediate Metal
Conduit and Electrical Metallic Tubing)
A
1350 Series
1351 Series
Application
• Provides mounting surface for
conduit where installation requires
air space between conduit and
supporting surface
Standard Material
Features
• Prevents conduit rusting from wall
condensation
1350 Series. . . . . . . . . . . . . . . . 1350AL Series
1350 Series. . . . . . . . . . . . . . . . 1350AL Series
Malleable Iron . . . . . . . . . Copper-free aluminum
Standard Finish
Hot Dipped . . . . . . . . . . . . . As Cast Galvanized
Range
• Spacers can be stacked one atop the
other, facilitating installation and
eliminating expensive conduit
offsetting (A)
B
⁄2" through 6" conduit
1
Listed/Certified by
CSA (LR-2884, LR-4484, LR-4484)
• Designed to cover wide range;
marked with accurate size marking
for proper positioning (B)
Conforms to
• Galvanized finish on 1350 Series
NFPA 70
CSA C22.2 No. 18
• Copper-free aluminum alloy,
1350AL Series
Eliminates the need for costly offset-bending conduit and the possibility
of corrosive moisture traps when conduit is mounted directly to a surface!
Pipe Spacers
• Used with T&B conduit straps to
provide space between conduit
and mounting surface
CAT. NO.
• Premountable and stackable
to eliminate offsetting
• Malleable iron construction with
hot-dipped galvanized finish
MAL. IRON
ALUM.
SIZE
SCREW
SIZE
1350
1351
1352
1353
1354
1350AL
1351AL
1352AL
1353AL
—
1
⁄2", 3⁄4", 1"
11⁄4"-11⁄2"-2"
21⁄2"-3"
31⁄2"-4"
41⁄2"-5"-6"
#7
#12
#12
#14
#16
DIMENSIONS (IN.)
A
B
3"
5"
99⁄16"
79⁄16"
109⁄16"
7
⁄8"
13⁄16"
13⁄4"
2"
29⁄16"
Conforms to NEC SECT. 300-5-c.
UL not applicable.
CSA File Nos. 2884 and 4484.
DIMENSIONS (IN.)
A
B
Prevents conduit rusting
from wall condensation!
Pipe Spacers — PVC Coated
• Eliminates the need for offset-bending of conduit
CAT. NO.
CONDUIT
SIZE
SCREW
SIZE
• Can be stacked for offsets on wall or into outlet box
1350CR
1351CR
1352CR
1353CR
1354CR
1
⁄2"-3⁄4"-1"
11⁄4"-11⁄2"-2"
21⁄2"-3"
31⁄2"-4"
1
4 ⁄2"-5"-6"
#7
#12
#12
#14
#16
• Corrosion-resistant, PVC-coated malleable iron construction
UL not applicable.
A-34
www.tnb.com
United States
Tel: 901.252.8000
800.816.7809
Fax: 901.252.1354
Canada
Tel: 450.347.5318
Fax: 450.347.1976
Conforms to NEC SECT. 300-5-c.
Technical Services
Tel: 888.862.3289
3
5
69⁄16
79⁄16
109⁄16
⁄8
⁄8
3
⁄4
2
29⁄16
7
3
Rigid and Intermediate Metal Conduit Fittings
One-piece fitting couples armored cable or flexible conduit to threaded rigid conduit!
TITE-BITE® Combination Couplings — Armored Cable for Threaded Rigid
• Tite-Bite® wedge holds conduit securely
with a double grip
• When used with a Chase® nipple, this fitting
will connect flexible conduit to outlet boxes,
enabling more wiring space in the box than
the usual connector
CAT. NO.
• UL Listed as a grounding means under NEC 350-5
• Malleable iron construction
DIMENSIONS (IN.)
A
B
SIZE
440
441
442
⁄2"
⁄4"
1"
15⁄8
13⁄4
2
1
3
127⁄32
21⁄8
217⁄32
UL File No. E-23018
CSA File No. 2884
Mount flat against wall, eliminating the need to offset conduit!
Entrance Ells
CAT. NO.
• Designed for a straight pull in either direction
CONDUIT
SIZE
1490
1491
1492
1493
1494
1495
1496
1497
1498
1499
• Carefully bushed
• Make it easy to pull heavy wires without
damage to insulation
• Made of copper-free aluminum
⁄2"
⁄4"
1"
11⁄4"
11⁄2"
2"
21⁄2"
3"
31⁄2"
4"
1
3
UL File No. E-23018.
DIMENSIONS (IN.)
A
C
3
39⁄16
41⁄4
531⁄64
61⁄4
63⁄4
139⁄64
139⁄64
169⁄32
169⁄32
119⁄32
17⁄8
223⁄64
213⁄16
27⁄8
39⁄16
57⁄8
61⁄2
717⁄32
717⁄32
CSA File Nos. 2884 and 589
Adjustable design fits a wide range of flange sizes!
CAT. NO.
Adjustable Beam Clamps
700TB
701
703
• Includes bolts
• Steel construction
DESCRIPTION
Fits Flange 23⁄4"–73⁄8"
Fits Flange 7"–12"
Special Bolt and 3 Nuts
CSA File No. 2884.
Fits any flange, tapered or straight, up to 5⁄8" thick!
Conduit Supports
• For use with standard rigid conduit, EMT or IMC
• Broad hook holds conduit at any desired angle
• Malleable iron construction
CAT. NO.
SIZE
690
691TB
692TB
693TB
⁄2"
⁄4"
1"
11⁄4"
1
3
CSA File No. 2884
United States
Tel: 901.252.8000
800.816.7809
Fax: 901.252.1354
Canada
Tel: 450.347.5318
Fax: 450.347.1976
Technical Services
Tel: 888.862.3289
www.tnb.com
A-35