03 · AUTOMATION
FIRE DETECTION UNIT ITDAC-14P-4
Fire detection system is one of the most important marine systems, since its functionality is directly connected with the
safety of people and equipment. As such, it must provide reliable notification of fire and warn the responsible persons, in
order to prevent fire spreading and potential catastrophic consequences.
Inelteh's fire detection unit ITDAC-14P-4 features:
• conventional fire detection system
• 4 fire detection lines
• automatic and/or manual alarm output activation
• separate and independent outputs for crew and passengers
• outputs 24V DC - fire bells can be directly connected
• type approved by Croatian Register of Shipping
FIRE DETECTION UNIT
ITDAC-14P-4
SMOKE
DETECTORS
HEAT
DETECTORS
MANUAL CALL
POINTS
IN CASE OF FIRE
BREAK GLASS
ITDAC-14P-4
FIRE DETECTION UNIT
RIJEKA - CROATIA
4 lines
LINE 1
IN CASE OF FIRE
LINE 2
BREAK GLASS
LINE 3
LINE 4
ALARM
ALARM
CREW
PASSENGERS
OUTPUT CONTACT
for VENTILATION
BLOCKING
LINE FAILURE
ALARM OUTPUT
ACTIVATED
24V DC
TEST
POWER
FAILURE
OUTPUT FOR BELLS IN CREW'S AREA
POWER
24V DC
POWER SUPPLY: 24V DC
OUTPUT FOR BELLS IN PASSENGERS' AREA
FIRE DETECTION UNIT ITDAC-14P-4
• power supply: 24V DC (18-32V DC)
• current consumption (without bells): 200mA max.
• number of smoke and heat detectors in single line: 17 max.
• number of manual call points in single line is unlimited
• power failure signalization: LED + buzzer; built-in battery with automatic charging
• output contact for ventilation blocking: Voltage-free contact 5A/250V AC, activated as long as one of fire detectors is in alarm state and/or when
alarm output is manually activated
• alarm output for crew: output 24V DC 1A max; activation: automatically (after 2 min if alarm isn't accepted) and/or manually
• alarm output for passengers: 24V DC 1A max; activation: manually
• flush (IP22, weight: 0.9kg) or bulkhead (IP54, weight: 7kg) mounting
320
300
8
30
CONSOLE
CUT-OUT
300
260
138
138
144
144
DEPTH IS 107mm.
All dimensions are in mm.
ENGINEERING FOR ELECTRONIC EQUIPMENT AND SYSTEMS
7xPG13.5+1xPG16
165
OPTICAL SMOKE DETECTOR
• power supply: 8.5-33V DC
• quick and reliable detection of smoke on the light scatter principle
• performs well in detecting black and white smoke
• with LED indication
• bulkhead mounting or wall mounting (on box with cable glands)
• approved for use in marine environment by GL, DNV, BV, LR, ABS, CCS
• IP protection: according to EN 54-7:2000
HEAT DETECTOR
• for applications where smoke detectors are unsuitable
• in environments that are dirty or smoky under normal conditions
• for temperature 65°C or for temperature 80°C (kitchen)
• power supply: 8.5-33V DC
• quick and reliable sensing of air temperature, using single thermistor
• with LED indication
• bulkhead mounting or wall mounting (on box with cable glands)
• approved for use in marine environment by GL, DNV, BV, LR, ABS, CCS
• IP protection: according to EN 54-7:2000
MANUAL CALL POINT
• conventional, with voltage-free contact and resistor element
• test-key for alarm simulation
• construction: ABS
• spare glass (on request)
• bulkhead mounting
• for indoor (IP42) or outdoor (IP66) use
• weight: 0.36kg (IP42 version) or 0.46kg (IP 66 version)
Optical smoke and heat
detectors, dimensions:
O100
72
220
204
52
O6
IN CASE OF FIRE
120
82
110 (for IP66)
87 (for IP42)
110 (for IP66)
87 (for IP42)
BREAK GLASS
O5
2xPG13.5
2xPG13.5
DEPTH: 53 (for IP42)
or 65 (for IP66)
for wall mounting
DEPTH: 132; WEIGHT: 0.7kg
for bulkhead mounting
WEIGHT: 0.14kg
13
• power supply: 24V DC
• current consumption: 0.3A
• sound pressure: 98dB / 1m
• IP protection: IP66
• weight: 1.6kg
O168
91
BELL CEADEL 165
6.5
DEPTH: 76
All dimensions are in mm.
Ljubljanska cesta 7, HR-51000 Rijeka / Croatia / tel. ++385 51 274 536 / fax 712 122 / inelteh@inelteh.hr / www.inelteh.hr