-2- PRESSURE MODULAR DIFFERENTIAL PRESSURE TRANSMITTER HART MHDS Operating manual Modular differential pressure transmitter MHDS Overview documents - Technical documentation MHDS - Operating manual MHDS-M (this document) MHDS-M-1 -2- MHDS PRESSURE MODULAR DIFFERENTIAL PRESSURE TRANSMITTER Inhalt: Safety instructions page 3 - icons Mounting page 3 page 4 page 5 page 6 page 7 - mounting, putting into operation - incoming acceptance - storage - identification - scope of delivery - notes for installation - mounting flow measurement - mounting flow measurement - mounting level measurement - mounting level measurement - mounting differential pressure mesurement - mounting differential pressure mesurement - wall- and tube mounting - turning enclosure - check of the mounting Electrical connection page 8 - connection of the device - test signal 4...20 mA page 9 - output (working resistance) - sceening and equipotential bonding - check electrical connection Operation page 9 page 10 page 11 page 12 - on-site display - operating elements - on-site operation (operating elements outside) - on-site operation (operating elements inside) - on-site operation (operating elements inside) Putting into operation page 13 - position adjustment - flow measurement page 14 - level measurement page 15 - level measurement page 16 - differential pressure measurement Input page 17 Dimensions page 17 Process connection page 17 Electronics page 18 HART communication page 18 Technical data page19 MHDS-M-2 HART -2- PRESSURE MODULAR DIFFERENTIAL PRESSURE TRANSMITTER HART MHDS Safety instructions Used icons ! Warning! A non-observance can cause injuries to persons or lead to demolition of the device. ! Attention! A non-observance can cause a faulty operation of the device. i Information! A non-observance can have influence on the operation of the device or cause unintentional reactions of the device. Mounting, putting into operation ! Ther MHDS is a differential pressure transmitter for flow, level and differential pressure measuring. The manufacterer of the device is not liable for defects, which are resulted from incorrect use or use other than that designated. The pressure transmitter meets the state of the art with taking into account the relevant regulations and EC standards. When the use is not appropriate or in accordance with the requirement, from the device can start application-related dangers, eg an escape of fluid when mounted or adjusted wrong. A non-observance of the valid safety regulations for this case of application may cause serious injuries and/or damages. Only personnel with the needed qualification, who is authorised by the operator, is allowed to carry out mounting, electrical connection, putting into operation, operation and maintenance of the pressure transmitter. The specialist staff must have read and understood this operating manual. Instructions , which are included in this manual, have to be followed. Modifications and repairs to the device are permissible only when they are allowed expressly in this documentation. Mounting Before mounting: Acceptance - When receiving the goods check the packaging and the contents for damage - Check the goods for completeness (eg compare delivery note with order data) Storage - The device has to be stored in a dry, clean area and protected against damage from impact - Storage temperature: -40...+85 °C Identification - The type plate shows the maximum working pressure (Pmax = MWP = maximum working pressure). This value refers to a reference temperature of 20 °C. - The allowed pressure values at higher temperatures can be found in the relevant standards. - The test pressure of the device is corresponding with the overload pressure (see table on page 17). - The used abbreviation PS in the Pressure Equipment Directive (97/23/EG) corresponds to the MWP (Maximum working pressure = Pmax) of this device. Details on the type plates (these details can vary) Type: name of the device = MHDS TAG-No: indentification number within the installation Date: date of completion Pmax: = MWP = maximum working pressure) Input: kind of pressure (differential pressure) Supply: voltage supply = 15...45 VDC Output: output signal = 4...20 mA HART Range: measuring range (adjusted) Order number / item number: 200-xxxxx (x = variable) SN: serial number Degree of protection: IP65 MHDS-M-3 MHDS -2- PRESSURE MODULAR DIFFERENTIAL PRESSURE TRANSMITTER HART Mounting (continued) Scope of delivery The delivery includes: - differential pressure transmitter MHDS - mount for wall- and tube mounting - accessories (option) Supplied documents: - this operating manual MHDS-M - option: final inspection and test report - option: factory calibration form - option: operating manual for programming software Mounting - Assembly dimensions see page 17 Notes for installation - Due to the fitting position of the MHDS there may be a zero offset. Example: Although the storage basin is empty the measured value not 0 (zero). It is possible to correct this zero point shift directly on the device by using the keys for configuration or extenally by means of software for configuration. See page 10...12 in this manual or in the manual for the software. - When using a 3-valve or 5-valve manifold, the mounting, putting into operation and maintenance can be done without interrupting the process. - When laying the differential pressure pipes outside, take care of an adequate antifreezing protection, eg with a parallel pipe heating. - You can take from relevant standards (national or international) recommendations about laying of differential pressure pipes (eg DIN 19210). - Tubes for pressure drop have to be layed with a constant gradient of at least 10%. - The enclosure of the electronics can be turned up to 360°. In this way the display of the electronic insert is readable very well. See on page 7, too. - A mount for wall- and tube mounting is included in the delivery. Mounting for flow measurement Flow measurement in liquids A: pitot tube / orifice plate B: stop valve C: 3-valve manifold D: MHDS E: separator F: drain valve Mount the pressure sensor MHDS below the measuring point. In this way the differential pressure pipes are always filled with liquid and possible gas bubble can rise back into the process piping. A B B + D E E F F Separators and drain valves are usefull if the medium contains solid parts. Through this the deposit can be removed. C Flow measurement in gases A: B: C: D: pitot tube / orifice plate stop valve 3-valve manifold MHDS Mount the pressure sensor MHDS above the measuring point. Possible existing condensate can run off into the process piping. D C B + MHDS-M-4 - B A -2- PRESSURE MODULAR DIFFERENTIAL PRESSURE TRANSMITTER HART MHDS Mounting (continued) A: B: C: D: E: F: G: A G Flow measuring in steam pitot tube / orifice plate stop valve 3-valve manifold MHDS separator drain valve condensate trap G B B + D Mount the pressure sensor MHDS below the measuring point. Mount the condensate trap at the same level as the tapping point and the same distance to the MHDS. Fill the differential pressure pipes before putting into operation to the height of condensate traps. E E F F C Mounting for level measurement Level measurement in an open vessel A: B: C: D: E: F: minus is open to atmosphere stop valve vessel MHDS separator drain valve Patm C + min A E Mount the pressure sensor MHDS below the measuring point. In this way the differential pressure pipes are always filled with liquid. Minus is open towards atmosphere D F B Level measurement in a closed vessel A: B: C: D: E: F: vessel stop valve 3-valve manifold MHDS separator drain valve B max A B min Mount the pressure sensor MHDS below the measuring point. In this way the differential pressure pipes are always filled with liquid. Minus has to be connected above the maximum level. Separators and drain valves are usefull if the medium contains solid parts. Through this the deposit can be removed. + D E E F F C MHDS-M-5 MHDS -2- PRESSURE MODULAR DIFFERENTIAL PRESSURE TRANSMITTER HART Mounting (continued) Level measurement in a closed vessel with superimposed steam A: B: C: D: E: F: G: vessel stop valve 3-valve manifold MHDS separator drain valve condensate trap G max B A B min Mount the pressure sensor MHDS below the measuring point. In this way the differential pressure pipes are always filled with liquid. Minus has to be connected above the maximum level. Separators and drain valves are usefull if the medium contains solid parts. Through this the deposit can be removed. The condensate trap ensures a constant pressure on minus. + D E E F F C Mounting for differential pressure measurement Differential pressure measurement in fluids A: B: C: D: E: F: filter (example) stop valve 3-valve manifold MHDS separator drain valve Mount the pressure sensor MHDS below the measuring point. In this way the differential pressure pipes are always filled with liquid and possible gas bubble can rise back into the process piping. Separators and drain valves are usefull if the medium contains solid parts. Through this the deposit can be removed. A B B + D E E F F C MHDS-M-6 -2- PRESSURE MODULAR DIFFERENTIAL PRESSURE TRANSMITTER HART MHDS Mounting for differential pressure measurement (continued) Differential pressure measurement in steam and gas A: B: C: D: filter (example) stop valve 3-valve manifold MHDS D Mount the pressure sensor MHDS above the measuring point. Possible existing condensate can run off into the process piping. C - + B B A Wall- and tube mounting 37 Holder made of steel (zinc coated) for mounting the device on walls or tubes is supplied with the device. 109 Supplied parts: holder, fixing clamp with nuts and washers. The holder made of stainless steel can be selected as an option (additional price). When using a valve block, take it’s dimensions into account. i When mounting, please note: - To avoid a scuffing, lubricate the fastening screws with multi-purpose grease before mounting. - In case of tube mounting: fasten the screw nuts of the fastening bow with a torque of at least 30 Nm. 70 8 10 i 70 9 9 Dimensions in mm Turning of enclosure After unscrewing the M6 Allen screw the enclosure can be rotated up to 360°. - release the screw with a 3 mm hexagon key - turn enclosure (up to 360°) - drive in screw again maximum 360° FIELD TERMINALS FIELD TERMINALS 316 316 316 316 Check the mounting After mounting of the transmitter carry out the following check: - Check if all screws are screwed down tight - Check if the screwed covers are screwed up - Check if screw plugs / ventilating valves are screwed down tight MHDS-M-7 -2- MHDS PRESSURE MODULAR DIFFERENTIAL PRESSURE TRANSMITTER HART Electrical connection - the supply voltage has to match the power supply which is given on the type plate. See also on page 3: identification - before connecting the device, switch off the power supply. - screw off the screwed cover of the terminal compartment. - insert the cable via screwed cable gland (specification see below). - carry out the connection according the illustration below. - screw up screwed cover. - switch on power supply. A Z supply S B C D 4...20 mA mA 1+ 2- test signal 3+ E FIELD TERMINALS Electrical connection 4...20 mA HART A: Enclosure B: Voltage supply 15...45 VDC (terminal 1(+) / terminal 2 (-)) C: 4...20 mA test signal between 2- and test point 3+ D: Internal earthing E: External earthing 1+ 2- 3+ Test 4...20 mA The device has a protective system against overvoltage peaks, RF interferences and wrong polarity. Voltage supply: between 15 ....45 VDC Cable entry: screwed cable gland M20x1,5 (metal) Cabel: outer diameter: 6...12 mm cross-sectional area: 0,5...1,5 mm² shielded and twisted 2-wire cable (recommended) Residual ripple: no influence on mA-signal up to 5% within nominal voltage range Tapping the 4...20 mA test signal test signal The 4...20 mA test can be measured without interruption of the low-potential circuit between terminal 3(+) and terminal 2(-). The output current is measured with an ammeter for mA across a diode in the output circuit. 3+ The internal resistance of the ammeter should be less than 0,7 ohms to keep the error of measurement below 0,1%. 21+ MHDS-M-8 + mA 4...20 mA current loop -2- PRESSURE MODULAR DIFFERENTIAL PRESSURE TRANSMITTER HART MHDS Output (working resistance) Load: RLmax = (U - 15 V) / 0,0228 A RL(max) [ohms] 1333 1111 Voltage supply: 15...45 VDC RLmax: maximum load resistance U: Voltage supply Please note: When using communication via a HART modem, a comunication resistance of minimum 250 ohms has to be taken into account. i 666 222 15 20 30 Resolution: Read cycle time: Damping: 40 45 U[V] current output: 16 bit indication: adjustable (factory setting: 0...100%) HART commands all 200 ms. continuously adjustable from 0 to 160 µA via electronic insert inside the device, hand-held equipment or PC-software. Factory configuration: 0 µA Sceening and equipotential bonding An optimal sceening against disturbances is to achieve if the sceening is connected on both sides ( on the device and in the cabinet). If there are potential equalisation currents possible in the plant, only earth sceening on one side, preferably the transmitter side. Installation of potential matching is not necessary. Check electrical connection After completition of the electrical installation carry out the following check: - Check if the power supply matches the details of the type plates. - Check if the device is connected as shown on page 8. - Check if all screws are screwed down tight. - Check if the screwed covers are screwed up. When switching on the power supply the backlighting of the display in the electronic insert illuminates. Operation On-site display The on-site display is a 3-line display (LCD). Indicated are measured values and dialog texts. Functions: 5-digit measured value display (including sign and decimal point), indication of unit and a bargraph for indication of current. Operating elements Span S P Zero Z F1 Below the type plate there are 2 key button for easy configuration of zero, span, zero offset compensation and reset of the device. The layout of the 2 keys is marked on the enclosure with “S” and “Z” F2 The electronic insert with the display has 3 keys (P, F1, F2) for the configuration of the transmitter. The keys are approachable after screwing off the screwed cover. MHDS-M-9 MHDS -2- PRESSURE MODULAR DIFFERENTIAL PRESSURE TRANSMITTER HART On-site operation (external keys) Below the type plate there are 2 key keys for easy configuration. Configurable are: - Zero (lower range value) - Span (upper range value) - Zero offset compensation - Reset of the device Open the lock Press the keys S and Z for 5 seconds simultaneously. The LCD sceen is showing OPEN when the lock is opened. Input pressure for 4 mA (zero) output Set the input pressure to zero reference level. Press key Z for 2 seconds and the output of the transmitter is 4,000 mA. The LCD sceen is showing LSET. Input pressure for 20 mA (span) output Set the input pressure to span reference level. Press key S for 2 seconds and the output of the transmitter is 20,000 mA. The LCD sceen is showing HSET. Zero offset compensation (compensation of position) Set the input pressure level to zero (pressure value = 0 = atmosphere). Press keys S and Z for 2 seconds simultaneously and the output of the transmitter is 4,000 mA. The LCD sceen is showing PV=0. Note: If pressure value / pressure range is >0,5, the zero offset compensationis not possible. The LCD sceen is showing PVER. Reset Switch off the power of the device. Press keys Z and switch on the power supply again. Go on to press key Z for another 5 seconds. The LCD sceen is showing OK when the transmitter is reset. Note: If pressure value / pressure range is >0,5, the zero offset compensationis not possible. The LCD screen is showing PVER. MHDS-M-10 -2- PRESSURE MODULAR DIFFERENTIAL PRESSURE TRANSMITTER HART On-site operation (internal keys) The display is rotatable for approx. 330° The electronic insert has 3 keys for configuration. Configurable are: - lower range value - Zero offset compensation (compensation of position) - Reranging starting measuring value - Damping - Fixed current output MHDS - upper range value - Reset - Reranging final measuring value - Unit (mA, mbar, %) Open the lock Press the keys F1 and F2 for 5 seconds simultaneously. The LCD sceen is showing OPEN when the lock is opened. Input pressure for 4 mA (zero) output Set the input pressure to zero reference level. Press key F2 for 2 seconds and the output of the transmitter is 4,000 mA. The LCD sceen is showing LSET. Input pressure for 20 mA (span) output Set the input pressure to span reference level. Press key F1 for 2 seconds and the output of the transmitter is 20,000 mA. The LCD sceen is showing HSET. Zero offset compensation (compensation of position) Set the input pressure level to zero (pressure value = 0 = atmosphere). Press keys F1 and F2 for 2 seconds simultaneously and the output of the transmitter is 4,000 mA. The LCD sceen is showing PV=0. Note: If pressure value / pressure range is >0,5, the zero offset compensationis not possible. The LCD sceen is showing PVER. Reset Switch off the power of the device. Press keys F2 and switch on the power supply again. Go on to press key F2 for another 5 seconds. The LCD sceen is showing OK when the transmitter is reset. Note: If pressure value / pressure range is >0,5, the zero offset compensationis not possible. The LCD screen is showing PVER. MHDS-M-11 MHDS -2- PRESSURE MODULAR DIFFERENTIAL PRESSURE TRANSMITTER HART On-site operation (internal keys) continued Function of the keys: P: select function / store adjusted value F1: change digit or decimal point / select characteristic F2: select digit to be changed or decimal point / confirm selected characteristic key P adjustment lower range value key P Select with F2 the digit to be changed or decimal point Change with F1 the digit or decimal point. key P adjustment upper range value key P Select with F2 the digit to be changed or decimal point Change with F1 the digit or decimal point. key P adjustment damping key P Select with F2 the digit to be changed or decimal point Change with F1 the digit or decimal point. key P adjustment display mode Select with F1 the needed display mode. key P fixed output current key P MHDS-M-12 Select with F1 the desired current. Confirm the selected current with F2 -2- PRESSURE MODULAR DIFFERENTIAL PRESSURE TRANSMITTER HART MHDS Putting into operation Check before putting into operation the mounting and the connection (see also page 7 and 9). Compensation of position (zero offset compensation) Because of the fitting position it is possible that there is a shift of the measured value. When the differential pressure pipes are not connected, the indicated measured value is not 0 or indication is not 0 with an empty vessel. Flow measurement Valves 1 Close valve 1 2 Fill the system with medium Open valves 2, 3, 6, 7 3 4 5 6 Meaning Installation (prefered) 4 medium flows in + If 5 valves are available, clean the differential pressure pipes if necessary. - gases: blow out with compressed air - liquids: by rinsing Close valves 2 and 3 the device is blocked Open valves 8 and 9 blow out / rinse the differential pressure pipes Close valves 8 and 9 close valves after cleaning 2 5 - Y 1 3 X 7 6 + - Deaerate the system Close valves 2 and 3 lead medium into Close valve 3 close negative side Open valve 1 balance of positive and negative side Open valves 4 and 5 and close them again after a short time system is filled with medium and air escapes Compensation of position: Carry out only if the process cannot be blocked and the tie-in points (valves 6 and 7) are at the same geodetic height. Compensation see on pages 10...12. In the other case the compensation of position has to be done in step 7. Set the system into operation Close valve 1 disconnect positive from negative side Open valve 3 connect negative side Now: closed valves: 1, 4, 5, 8, 9 open valves: 2, 3, 6, 7 7 Compensation of position: carry out only if the process can be blocked. In this case step 5 has not to be carried out. (see pages 10...12) 8 Carry out adjustment (see pages 10...12) 6 7 + 4 Z + 8 5 Y Z - 9 1 2 X 3 Above: installation for gases Below: Installation for fluids X: Y: Z: 3-valve manifold MHDS Separator 1: 2; 3: 4, 5: 6, 7: 8, 9: Equalising valve Inlet valves Vent valves Stop valves Drain valves MHDS-M-13 -2- MHDS PRESSURE MODULAR DIFFERENTIAL PRESSURE TRANSMITTER HART Putting into operation (continued) Level measurement (open vessel) Valves Meaning 1 Fill vessel to a level above the lower tap 2 Fill system with medium Open valve 6 3 medium flows in system is filled with medium and air escapes 4 Z 8 Set the system into operation Now: 7 + Deaerate system Open valves 4 and 5 and close them again after a short time 4 Installation (prefered) + Closed valves: 4, 8 Open valve: 6 - Y 6 Carry out adjustment (see pages 10...12) Y: Z: 4, 5: 6: 8: 5 MHDS Separator Vent valves Stop valve Drain valve Level measurement (closed vessel) Valves Meaning 1 Fill vessel to a level above the lower tap 2 System mit Medium auffüllen 3 Installation (prefered) 6 Close valve 1 disconnect positive from negative side Open valves 6 and 7 Open stop valves Vent positive side (if necessary, empty negative side) Open valves 2 and 3 Open valves 4 and 5 and close them again after a short time 7 positive side is filled with fluid + 4 positive side is filled with medium and air escapes Z + Set system into operation Now: 5 MHDS-M-14 2 Closed valves: 1, 4, 5, 8, 9 Open valves: 2, 3, 6, 7 Carry out adjustment (see pages 10...12) Y Z - 1 8 4 - 5 X: Y: Z: 3-valve manifold MHDS Separator 1: 2; 3: 4, 5: 6, 7: 8, 9: Equalising valve Inlet valves Vent valvesl Stop valves Drain valves X 9 3 -2- PRESSURE MODULAR DIFFERENTIAL PRESSURE TRANSMITTER HART MHDS Putting into operation (continued) Level measurement (closed vessel with superimposed steam) Valves Meaning 1 Fill vessel to a level above the lower tap 2 Fill the system with medium Open valves 6 and 7 Installation (prefered) 6 open stop valves Fill the negative differential pressure pipe to a level of the condensate tap 3 4 Deaerate the system medium flows in Open valve 1 balance of posizive and negative side Open valves 4 and 5 and close them again after a short time system is filled with medium and air escapes + 4 Z + Close valve 1 Disconnect positive from negative side Open valve 4 connect negative side Closed valves: 1, 4, 5, 8, 9 open valves: 2, 3, 6, 7 Carry out adjustment (see pages 10...12) - 5 Y Z - 1 8 Set system into operation Now: 5 7 Open valves 2 and 3 2 X: Y: Z: 3-valve manifold MHDS Separator 1: 2; 3: 4, 5: 6, 7: 8, 9: Equalising valve Inlet valve Vent valve Stop valve Drain valve X 9 3 MHDS-M-15 -2- MHDS PRESSURE MODULAR DIFFERENTIAL PRESSURE TRANSMITTER HART Putting into operation (continued) Differential pressure measurement Valves 1 Close valve 1 2 Fill the system with medium Open valves 2, 3, 6, 7 3 4 5 6 Meaning Installation (prefered) 4 medium flows in + If 5 valves are available, clean the differential pressure pipes if necessary. - gases: blow out with compressed air - liquids: by rinsing Close valves 2 and 3 the device is blocked Open valves 8 and 9 blow out / rinse the differential pressure pipes Close valves 8 and 9 close valves after cleaning 2 5 Y 1 3 X 7 6 + - Deaerate the system Close valves 2 and 3 lead medium into Close valve 3 close negative side Open valve 1 balance of positive and negative side Open valves 4 and 5 and close them again after a short time system is filled with medium and air escapes Compensation of position: Carry out only if the process cannot be blocked and the tie-in points (valves 6 and 7) are at the same geodetic height. Compensation see on pages 10...12. In the other case the compensation of position has to be done in step 7. Set the system into operation Close valve 1 disconnect positive from negative side Open valve 3 connect negative side Now: closed valves: 1, 4, 5, 8, 9 open valves: 2, 3, 6, 7 7 Compensation of position: carry out only if the process can be blocked. In this case step 5 has not to be carried out. (see pages 10...12) 8 Carry out adjustment (see pages 10...12) MHDS-M-16 6 7 + 4 Z + 8 5 Y Z - 9 1 2 X 3 Above: installation for gases Below: Installation for fluids X: Y: Z: 3-valve manifold MHDS Separator 1: 2; 3: 4, 5: 6, 7: 8, 9: Equalising valve Inlet valves Vent valves Stop valves Drain valves -2- PRESSURE MODULAR DIFFERENTIAL PRESSURE TRANSMITTER HART MHDS Output Measurand: differential pressure derived from this: flow rate (volumetric- and mass flow) level (level, volume, mass) Measuring ranges: 75 mbar up to 420 bar nominal range range limit upper (URL) [mbar] working range smallest adjustable [mbar] overload [mbar] range limit lower (LRL) [mbar] 75 400 2000 7000 21000 70000 200000 420000 -75 -400 -2000 -7000 -21000 -70000 -200000 -420000 +75 +400 +2000 +7000 +21000 +70000 +200000 +420000 1,5 4 20 70 210 700 2000 4200 130 130 130 130 130 125% of range 125% of range 115% of range [bar] Dimensions Dimensions in mm ~130 113 S 128 Z F2 205 F1 120 P 316 H L 316 view front view side view top Process connection M10 84 mm Pressure connection: 1/4-18 NPT AISI 316L (1.4435) Measuring membrane: stainless steel 1.4435 Mounting: M10 Supplied accessories: 2 ventilating valves AISI 316L (1.4435) H L 1/4-18 NPT 97 mm MHDS-M-17 MHDS -2- PRESSURE MODULAR DIFFERENTIAL PRESSURE TRANSMITTER HART Electronics Electronics - XS1 voltage supply 15...45 V - XS2 connection sensor - XS3 external keys - XS7 display - J1 solder bridge to select sensor supply XS3 VS Z M •• •• W S Z II+ VL4 L3 L2 V+ •• •• •• •• •• XS1 XS7 •• L+ L- T1 J1 v V+S+U-S-T i ••••• XS2 U3 HART Communication HART tool: The HART-Tool is a graphical user interface for the MH series with menu-driven progam for configuration. It can be used for putting into operation, configuration, analysis of signals, data backup and documentation of the device. Operating systems: Windows2000, Windows XP Functions: - Configuration of the devices in on-line operation - Loading and storing the devices data (upload / download) - Linearization of characteristic curve - Documentation of the measuring point Possible HART devices to use: - HART interface (modem) with serial interface of a PC - HART interface (modem) with USB interface of a PC - Hand-held HART communicator MHDS-M-18 -2- PRESSURE MODULAR DIFFERENTIAL PRESSURE TRANSMITTER HART MHDS Technical data Input Differential pressure: 75 mbar / 400 mbar / 2 bar / 7 bar / 21 bar / 70 bar / 200 bar / 420 bar Static pressure: 30...420 bar Output Analog: 4...20 mA, 2-wire, with superimposed communication signal (HART-protocol) Signal range: 3,6...22,8 mA Failure: signal 3,6 mA Accuracy Type 75 mbar: 0,1% of FS up to turn down 5:1 ±(0,1+0,01*URL/URV) for turn down 5:1 to 50:1 Types 400 mbar / 2 bar / 7 bar / 21 bar / 70 bar: 0,075% of FS up to turn down 10:1 ±(0,0751+0,00751*URL/URV) for turn down 10:1 to 100:1 Types 200 bar / 420bar: 0,2% of FS up to turn down 10:1 ±(0,2+0,01*URL/URV) for turn down 10:1 to 100:1 Influences: static pressure: zero: ±0,1%/70 bar - range: ±0,2%/70 bar supply: <0,005% of nominal range/1V vibration: <0,01% of nominal range/g at 200 Hz fitting position: zero drift, to compensate span drift: without temperature: <0,45%/55°C Stability: ±0,1% of nominal range / 1 year Settings Rise-delay time: 5 s Cycle time, update: 0,25 s Damping: 200 ms (without concideration of electronic damping) Filter adjustment: 0...160µA Display Visible range: 32,5x22,5 mm Indication: 5-digits 7-segments, 8 mm height / 8-digits 14-segments, 5 mm height 7 bargraph with resolution 2% Range: -19999...99999 Supply Voltage: 15...45 VDC (current loop) Insulation resistance: >250 MOhm Short circuit-proof: permanent Reverse battery protection: yes (no destruction, no funtion) Overvoltage protection: 500V Environmental conditions Operating temperature: -20...70°C Ambient temperature: -20...70°C Temperature medium: -40...104°C Storing temperature:-40...+85°C Humidity: 5...98% relative humidity Mechanics Material: Enclosure ektronics: diecast aluminium Measuring membrane: stainless steel 1.4435 / option:Hastelloy Ventilating valve, joint pieces: stainless steel 1.4435 O-ring in contact with medium: Viton (FKM, FPM) Flange screws: plain carbon steel, zinc coated Type plate: stainless steel 1.4301 viewing glass: laminated glas Process connection: 1/4-18 NPT Dimensions: see page 7 Protection: degreeIP 65 Weight: approx. 3,8 kg Connection: terminal screw (maximum 1,5 mm²), via srewed cable gland M20x1,5 Principle of measurement: capacitive Standards: IEC 61000-4-3 / Pressure equipment directive 97/23/EG MHDS-M-19 MHDS MHDS-M-20 -2- PRESSURE MODULAR DIFFERENTIAL PRESSURE TRANSMITTER HART Subject to change, version 41-050