Inductive Components Manufacturing, Inc. URC-24 3-Phase Recloser Control (PN 20001) Operation Manual 3/7/05 REVISION 3.0, MARCH 07, 2005 Operation Manual URC-24 Recloser Control Table of Contents Table of Contents URC-24 Introduction URC-24 Panel Layout URC-24 L.E.D. Description URC-24 Display URC-24 Security Code URC-24 Function Codes URC-24 Editing Keys URC-24 Manual Operation URC-24 Remote/SCADA Functions 1 2 3 5 5 6 6 6 8 9 URC-24 Appendix Location of Ports Port 5 Description SCADA Connector SCADA Cable SCADA Terminal Plate (Optional) URC-24 Wiring Diagram URC-24 Wire Harness Microprocessor Time Current Curves Thermal Demand Metering Quick Check Reference Page 1 10 11 12 13 14 15 16 17 21 22 Revision 3.0, March 07, 2005 Operation Manual URC-24 Recloser Control Introduction The new URC-24 advanced technology UPS and Micro based Recloser Control, was designed expressly as a cost effective retrofit control for McGraw - Edison Form 2, 3, 3A Recloser Controls. It interfaces directly to Kyle three phase vacuum Reclosers. The URC-24 is powered from a micro-controlled un-interruptible power supply and an intelligent battery charger to maximize reliability and reduce maintenance. The URC-24 advanced micro-based programmable controller enables the customer to select the basic hydraulic curves of the Form 2 / 3 series Recloser controls as well as eight additional trip and fault curves to optimize performance. In addition the controller has basic "dry-contact" Supervisory Control And Data Acquisition (SCADA) capability. All of these advanced features are presented at an extremely cost-effective price. The control is covered by a 2 year limited warranty. The control includes detailed instructions designed for utility engineers and technically qualified personnel. It is expressly designed to augment the original three phase vacuum Recloser installation and operation manual from McGraw Edison / Cooper / Kyle Recloser. WARNING: The control must be removed from service and completely de-energized electrically before performing service / maintenance and retrofit to URC-24. Failure to do so can result in severe injury or death. CAUTION: Precautions listed in these instructions are to prevent equipment and component damage and possible injury to persons. Specifically, testing, service and maintenance should be accomplished with the unit disconnected from service, to avoid accidental and un-intended Recloser responses. NOTICE: The implementation and or maintenance of this equipment is to be performed only by fully qualified utility technical personnel. Fully reading and understanding the original Recloser manuals, and the URC-24 3-Phase Recloser Control Operation Manual, will help enable a smooth and successful application and installation of the equipment. The URC-24 is certified by ICMI to work on the following Recloser mechanisms. 15kv type: rxe, we, & vwe 25 kv type: vwve 34.5kv type: rve & vwe Any additional Mechanisms applied to the URC-24 must first be qualified by ICMI engineering. Page 2 Revision 3.0, March 07, 2005 Operation Manual URC-24 Recloser Control URC-24 PANEL LAYOUT 1. METER PANEL 2. 1. 3. 2. 4. 5. 6. 7. 8. 9. 10. CONTROL PANEL Page 3 Revision 3.0, March 07, 2005 Operation Manual URC-24 Recloser Control URC-24 PANEL LAYOUT METER PANEL 1. 50 VOLT DC METER: The 50 VDC Meter is used in conjunction with the meter test button to check the battery voltage. It should read about 25 volts when the test button is pressed. 2. METER TEST BUTTON: The Meter Test Button is used in conjunction with the voltmeter to test battery voltage. Press to test voltage and read voltage on meter. CONTROL PANEL 1. DISPLAY: See Page 5 for details. 2. KEYPAD: See page 5 for details. 3. CONTROL SWITCHES: See page 8 for details. 4. OPEN/CLOSE BUTTONS: See page 8 for details. 5. PROGRAM PORT: Used by ICMI for test purposes. 6. BATTERY DIAGNOSTIC STATUS: See page 5 for details. 7. AC POWER INDICATOR: See page 8 for details. 8. POWER SOURCE INDICATORS: See page 5 (LED Description) for details. 9. OPEN/CLOSE INDICATORS: See page 5 (LED Description) for details. 10.PANEL FUSE (2AMP): See page 8 for details. Page 4 Revision 3.0, March 07, 2005 Operation Manual URC-24 Recloser Control URC-24 L.E.D. Description A. A. DIAGNOSTIC/STATUS LED- Has three possible states. B. 1. The non-blinking state indicates a good battery. Note: A battery is considered good when the voltage of the series connected two 12V battery combination is determined to be at least 20VDC? C. 2. The blinking state indicates a battery pair that has fallen below approximately 20VDC and AC power is present. The LED blinks at a rate of 1 second on and 1 second off. D. E. 3. The OFF state indicates the battery has fallen below approximately 22VDC and there is no AC power present. B. DC POWER LED- Indicates there is a battery STATUS LED’s C. AC POWER LED- Indicates AC power is present. voltage present. D. OPEN LED- Indicates the Recloser is in the E. CLOSE LED- Indicates the Recloser is in the CLOSE position. OPEN position. DC POWER UP The URC-24 also has the ability to power up with only battery power. First, connect the battery cables to the battery and locate the black momentary switch on the charging board (See pg. 10 for illustration). Next just slide the switch until you see the Diagnostic/Status LED come on. URC-24 Display A. Target Indication: The display will indicate which phase, phases, or ground are involved when the control operates to lockout. The target will reset after the close button has been depressed. B. Status Indication: A micro switch inside the Recloser Mechanism provides open and close status. Lockout will be displayed whenever the control operates to lockout on a fault or whenever the OPEN button is depressed. C. Function Number: This displays the function and its value or setting. Functions 1 through 12 correspond directly to the numbered keys on the keypad. Functions 13 through 19 are also accessed through the keypad. D. Setting: This value is a function code that represents an action that is set in a database under the current function that is displayed. A. B. C. D. URC-24 DISPLAY Page 5 Revision 3.0, March 07, 2005 Operation Manual URC-24 Recloser Control URC-24 KEYPAD The URC-24 keypad is used in conjunction with the display as the user interface to the URC-24. The display is divided into two distinct sections. These sections are referred to as Function Keys and Editing Keys. Function Keys: The function keys can access all 19 functions of the URC-24. Keys 1-12 are used to directly access functions 1-12 as labeled on the keys. To access functions 13-19 keys 1-7 are pressed twice. See functions 13-19 for details. FUNCTION KEYS EDITING KEYS Editing Keys: The editing keys perform specific functions related to the key it self. See below for a description of the function of each editing key. Select: URC-24 KEYPAD The SELECT key is used in conjunction with Keys 9 and 10. To read the number of operations, depress Key 9 (Operations Counter), then press the SELECT key to scroll through and read each phase and ground count. The display will indicate which phase is being read. Actual current on each phase and ground can be read in the same manner. Depress Key 10 (Actual Current), then press the SELECT key to read each phase and ground value. Up & Down Arrows: The Up and Down Arrows are used to change the URC-24 functions after the security code has been entered. The keys are inactive until the security code is entered. Enter: The ENTER key is depressed when a new function value has been selected with the Up and Down Arrows. The security code must be entered first before any change can be made. Security Code: For the function codes to be changed, the security code must be entered first. To do so, depress Enter, 5, 2, and 7, Enter. Note: If a key has not been touched for more than 60 seconds, the display will blank out and the security code will have to be re-entered. URC-24 Function Codes Function 1: FAST SHOTS. Choices range from 0 to 4 fast operations. Fast Operations are high-speed operations but follow a specific time current curve. This curve is selected from Function 4. Function 2: SHOTS TO LOCKOUT. Choices range from 1 to 4. This function selects the total number of operations to lockout. At lockout, reclosers are open and automatic operation ceases. Depressing the CLOSE button or closing remotely via SCADA resets the control system. The number of timedelayed operations is the difference between the number of shots to lockout and the number of fast shots. Function 3: 1ST RECLOSE TIME. Choices for first re-close interval are 2, 3, 5, 10, 15, 30, or 45 seconds. Re-close time is the open or dead time between operations. Function 4: 2ND & 3RD RECLOSE TIME. Press key once to display second re-close time. Press key a second time to display the third re-close time. Choices for both are 2, 3, 5, 10, 15, 30, or 45 seconds. Function 5: PHASE MINIMUM TRIP. This is the actual trip value ranging from 10 to 800 amps, in 10 amp increments up to 300 amps and in 20 amp increments from 300 to 800 amps. Function 6: FAST CURVES. There are 4 different fast curves (A hydraulic and A, N, and R electronic type). These curves are virtually instantaneous, with Curve 1 being the fastest and Curve 4 the slowest. Refer to time current curve graphs for specific curve data. Curve 5 can be found on page 25. Page 6 Revision 3.0, March 07, 2005 Operation Manual URC-24 Recloser Control Function 7: TIME DELAY CURVE. Nine curves are available. Time delay curves allow for coordination of down line fuses and Reclosers, but also must coordinate with up-line devices. Careful selection should be made. The first three curves emulate hydraulic Recloser curves (types B, C, and D). The next four are more inverse curves and emulate electronic Recloser curves (types B, C, D, or E). All curves used are industry standard Recloser curves. Curve 9 can be found on page 25. Curve 8 is a “hold closed” curve for very specific applications. Function 8: RESET TIME. Choices are 10, 30, 60, 90, 120, and 180 seconds. Reset time begins on successful re-close. Successful re-close occurs when the Recloser closes during a sequence of operations on a fault prior to lockout and the fault current has disappeared (the current has dropped below minimum trip). Function 9: OPERATIONS COUNTER. Displays the number of trip signals the control has sent on each phase and ground. Use select key to read values of each phase or ground. Function 10: ACTUAL CURRENT. Displays line current measured from the internal bushing CT. Use the select key to read values of each phase or ground. Line current sensing is provided from the same C.T. used to sense fault current. DEMAND METERING. See attached document “URC24 Thermal Demand Meter” at the back of manual. Function 11: GROUND MINIMUM TRIP. This is the actual ground trip value ranging from 10 to 400 amps in 5 amp increments up to 150 amps, then in 10 amp increments from 150 to 400 amps to disable tripping on curves. Function 12: DEFINITE GROUND LOCKOUT TIME. Choices range from 1 to 15 Seconds in 1-second increments. Use this function for setting the definite Ground lockout time only. This works in conjunction with Function 17. Function 13: SERIAL NUMBER. Pressing the Function 1 key twice, after entering the security code, will display the serial number of the control. Function 14: OPERATING MODE. Pressing the Function 2 key twice will display the mode number 1: three phase trip, three phase lockout. Function 15: GROUND TRIP OPERATIONS. Depress the Function 3 key twice. Select: “0” - All ground detection off. “1” - One shot to lockout on ground fault. “S2” - Same sequence to lockout as phase. The number of fast and slow operations on ground will be the same as phase. NOTE: Setting the GROUND TRIP BLOCK switch to BLOCK is the same as selecting “0” for Function 15. The NON-RECLOSE switch will also set both ground and phase trip to one shot regardless of settings on Functions 2 or 15. For very unbalanced systems or special applications, ground detection may not be needed. By selecting “0”, the user is assured that ground is off regardless of the GROUND TRIP BLOCK switch position. For other applications, one shot may be required on ground while multiple shots are required on phase. Function 16: THIRD RECLOSE TIME. Depress the Function 4 key twice. See Function 4. Function 17: DEFINITE GROUND LOCKOUT. Depress Function 5 key twice. This key sets the minimum trip level on Definite Time Ground Lockout. Do not confuse Definite Ground Lockout with Ground Minimum trip. Definite time ground Lockout is also available even if ground tripping is selected. The definite time ground lockout level can be set at a value different from the phase or Ground trip levels. Definite time ground lockout provides a third level of Protection. When definite time ground lockout is selected, the control will time on a ground fault. After the preset time has expired, with no operations on phase or ground, all three phases lock out. Normally, the definite time ground lockout value is set below the ground trip value. Definite time ground lockout may be desired in areas prone to high impedance faults as an additional level of protection. To disable Definite Time Ground Lockout, set to 400 amps. This is used in Conjunction with Function 12. Page 7 Revision 3.0, March 07, 2005 Operation Manual URC-24 Recloser Control Function 18: FAST CURVES FOR GROUND. Depress the Function 6 key twice. Choose 1, 2, 3, or 4 which corresponds to A hydraulic type, and A, N, and R electronic type curves. Curve 5 can be found on page 25. Note: curves for ground are same as phase. Function 19: TIME DELAY CURVES FOR GROUND. Depress the Function 7 key twice. Choose a curve from 1 to 9, which corresponds to B, C, or D\ hydraulic type and B, C, D, E, or Hold Closed electronic type respectively. Caution: curve 8, the Hold Closed curve, is for special applications. Curve 9 can be found on page 25. URC-24 MANUAL OPERATION The operating functions consist of the two push buttons and the three toggle switches below the keypad (Shown at bottom of page). The OPEN and CLOSE buttons trip and close all three phases at the same time. By holding the CLOSE button in, the control skips its fast curve and automatically goes to a time delay curve to allow for a cold load pick-up. This prevents the control from using its fast curve to react to the inrush current associated with powering up a cold load. For example, if a control’s minimum trip is set at 100 amps and both it’s time delay and fast curve’s are set at number 1, then the control will trip from an inrush current just over 100 amps. The reason being is the number 1 setting of the fast curve gives the control a .5 second (A hydraulic curve) opportunity to pick any inrush current; however, the time delay curve gives up to 5 seconds (B hydraulic curve). Generally, 5 seconds is enough time for an inrush current to diminish below its minimum trip setting, which in this case would be 100 amps. In short, if the CLOSE button is only pressed momentarily, the control times on its fast curve. By skipping to the delay curve when the CLOSE button is held down, additional time is gained to pick up the load. The Non-Reclose switch in the non-reclose position will put the recloser into single-shot mode. In non-reclose mode, Function 2 (Shots to Lockout) will be ignored and the control will only operate one shot to lockout. The Remote/Local switch is for supervisory control. In the local mode, supervisory signals are ignored. For example, if a supervisory signal is sent to trip the control, the control will not trip when it is in local mode. In remote mode, if that same trip signal were repeated, the control would then trip. In essence, if anything is touched on the control panel other than the keypad while in remote mode, nothing will happen. At the same time, if those same signals were generated from the supervisory system then the control would respond accordingly. For instance, in remote mode, the supervisory system controls whether or not the control is in non-reclose or ground trip block. Likewise, if the control’s non-reclose switch is in non-reclose, the supervisory system can set the control for normal re-closing. In short, this switch determines if the control is going to use the control panel switches as in figure 3 or from SCADA described in the following section. Regardless of whether or not the control is in local or remote, the keypad still determines how the control responds to faults. The Block/Ground Trip switch in the block position will disable the definite time ground lockout and ground trip on curves. In the ground trip position those two features are active. The Power lamp indicates control has power. The Panel Fuse is for protection of the electronics. The Data Port (Not Shown) is used at the factory to program the operating system into the control. This is its only function. URC-24 MANUAL CONTROL AND POWER SECTION Page 8 Revision 3.0, March 07, 2005 Operation Manual URC-24 Recloser Control Remote / SCADA Functions The URC-24 can be operated and monitored remotely. The remote functions are provided by dry type contacts so no protocol or protocol converters are used or required. An optional SCADA cable is available to hard wire a user provided RTU or for direct hardwiring. Also an I.C.M.I. SCADA tester is available for testing the remote functions. The following remote features are available. Lockout: A remote lockout signal will trip and lockout all three phases. L.E.D. Port Non-reclose: A remote signal can change the control to either normal operation or one shot, regardless of the position of the non-reclose switch on the URC-24 control panel. Non-reclose Indication: Provides status back if control is in nonreclose mode. Close: All three phases will close when a remote close signal is sent. If the remote close signal is maintained, cold load pick up or timing on delayed curves only is activated. SCADA Port Ground Trip Block: Both definite time ground lockout and ground tripping on curves can be blocked or unblocked, regardless of the position of the URC-24 control panel ground trip block switch. Ground Trip Block Indication: Provides status back to system if control is in ground trip block mode. Open Indication: Open status of each phase is provided. Close Indication: Close status of each phase is provided. Remote Indication: Provides the supervisory system the status of the remote/local switch on the control panel. If the URC-24 switch is in “Local“, remote functions, other than status, can not be activated. AC Indication: Has three possible states. 1. The non-blinking state indicates a good battery. Note: A battery is considered good when the double battery combination is at least 20VDC. CT Input Open/Close Output 2. The blinking state. This indicates a battery that has fallen below approximately 20VDC and AC power is present. The LED blinks at a rate of 1 second on and 1 second off. 3. The off state. This indicates when the battery has fallen below approximately 22VDC and there is no AC power present. DC Power Up CPU Acknowledge: Provides input back to system that control is functioning properly. URC-24 IO Port Page 9 Revision 3.0, March 07, 2005 Operation Manual URC-24 Recloser Control APPENDIX Page 10 Revision 3.0, March 07, 2005 Operation Manual Page 11 URC-24 Recloser Control Revision 3.0, March 07, 2005 Operation Manual Page 12 URC-24 Recloser Control Revision 3.0, March 07, 2005 Operation Manual Page 13 URC-24 Recloser Control Revision 3.0, March 07, 2005 Operation Manual URC-24 Recloser Control OPTIONAL TERMINAL PLATE FOR SCADA CONNECTION The photo below depicts the terminal connections for the optional SCADA terminal for the URC-24 Page 14 Revision 3.0, March 07, 2005 Operation Manual URC-24 Recloser Control URC-24 Wiring Diagram Page 15 Revision 3.0, March 07, 2005 Operation Manual URC-24 Recloser Control Misc. Grn 2 Misc. Wht #1 #15 and Misc. Red #14 Page 16 Revision 3.0, March 07, 2005 Operation Manual URC-24 Recloser Control URC-24 Microprocessor based Time Current Curves Control response Time Hydraulic Time Delay Curves Function key #7 Control Response Time Curves B, C, & D: Average response time for one operation; variations +/- 10% or +/- .01 second, whichever is greater. Add the following interrupting time to control response time to obtain average clearing time Recloser Interrupting Type Time RE, RXE 0.040 WE 0.045 VSA 0.025 The above reclosers have been verified to work with the URC-24. Others are likely to work but are not verified. Note: It is known that the URC-24 will not work with "MS" reclosers. URC-24 Curve Time current CURVE CODE 1 B 2 C 3 D Page 17 Revision 3.0, March 07, 2005 Operation Manual URC-24 Recloser Control URC-24 Microprocessor based Time Current Curves Control Response Time Electronic Time Delay Curves Function key #7 Control Response Time Curves B, C, & D: Average response time for one operation; variations +/- 10% or +/- .01 second, whichever is greater. Add the following interrupting time to control response time to obtain average clearing time Recloser Interrupting Type Time RE, RXE 0.040 WE 0.045 VSA 0.025 The above reclosers have been verified to work with the URC-24. Others are likely to work but are not verified. Note: It is known that the URC-24 will not work with "MS" reclosers. URC-24 Curve Time current CURVE CODE 4 B 5 C 6 D 7 Page 18 E Revision 3.0, March 07, 2005 Operation Manual URC-24 Recloser Control URC-24 Microprocessor based Time Current Curves Control Response Time Fast curves Function key #6 Control Response Time Curves A & A*: Maximum response time for one operation; variations negative. Curves N & R: Average response time for one operation; +/- 10% or +/- .01 second, whichever is greater. A* is hydraulic type fast curve. Add the following interrupting time to control response time to obtain average clearing time Recloser Interrupting Type Time RE, RXE 0.040 WE 0.045 VSA 0.025 The above reclosers have been verified to work with the URC-24. Others are likely to work but are not verified. Note: It is known that the URC-24 will not work with "MS" reclosers. URC-24 Curve Time current CURVE CODE 1 A* 2 A 3 N 4 R Page 19 Revision 3.0, March 07, 2005 Operation Manual URC-24 Recloser Control URC-24 Microprocessor based Time Current Curves Average Clearing Time Time Delay Curves Function key #7 Control Response Time Curves 8* & 135: Average response time for one operation; variations +/- 10% or +/- .01 second, whichever is greater. A* is hydraulic type fast curve. Add the following interrupting time to control response time to obtain average clearing time Recloser Interrupting Type Time RE, RXE 0.040 WE 0.045 VSA 0.025 The above reclosers have been verified to work with the URC-24. Others are likely to work but are not verified. Note: It is known that the URC-24 will not work with "MS" reclosers. URC-24 Curve Time current CODE CURVE 9 135 10 8* Page 20 Revision 3.0, March 07, 2005 Operation Manual URC-24 Recloser Control URC24 Thermal Demand Meter The Demand Current values are calculated for phase A, B, C, and Ground. The calculated values are: Instantaneous or Present Demand, High draghand Demand, and Low draghand Demand. The Instantaneous Demand value is a moving integral and is lost with the loss of control power. The High draghand Demand and Low draghand Demand values reflect the highest and lowest Instantaneous Demand values over time. Furthermore, these two values are saved in non-volatile memory and are cleared by the customer. When they are cleared, they immediately take on the Present Demand Value and begin to track the Present Demand’s highs and lows after one Demand Interval. Upon Urc24 power up or Demand Interval change, there will be a 3-minute delay before any Present Demand values will be calculated. Also the High draghand Demand and Low draghand Demand will not be updated during recloser operation. The Demand Interval is selectable between 5 or 15 minutes. The Demand Interval is accessed by depressing Function 8 twice. All Demand values are accessed using the Function 10 button on the Urc24 front panel: to access all values simply keep depressing the 10 button. The default function is the “Actual Current” (rms current flowing through recloser CTs) function denoted by “10” on the Urc24 display. Depressing the 10 button again will bring up the Present Demand value denoted by “P” on the display. Another time will bring up the High draghand Demand value denoted by “H” on the display. And finally again, will bring up the Low draghand Demand value denoted by “L” on the display. To clear the High and Low draghand Demand (to clear is to set the High/Low to the present demand values) simply depress the enter button twice when the display is showing the value you want cleared. The security code must be entered before clearing the High and Low draghand Demand or the values will remain unchanged. This procedure is similar to clearing the operation counter. Page 21 Revision 3.0, March 07, 2005 URC-24 QUICK CHECK REFERENCE CARD Note to installer: Before removing the "old" recloser control record the settings of the "old" control in the "Setting" column of the table below. After the URC-24 is installed, transfer the recorded settings to the URC-24 F.C. 1 2 3 4:2 5 DESCRIPTION Fast Shots Shots to Lock Out First Reclose Time 2nd reclose time Phase Min. Trip RANGE/INTERVAL 0-4 1-4 2, 3, 5, 10, 15, 30, 45 2, 3, 5, 10, 15, 30, 45 10 to 800 amps 6 7 8 9 10* 11 Fast Curves Time Delay Curve Reset Time Ops. Counter Actual Current Gnd. Min. Trip 1-5 1-9 10, 30, 60, 120, 180 n/a n/a 10 to 400 amps 12 13 14 15 Def. Gnd Lockout Time Serial Number Operating Mode Gnd. Trip Operations 1-15 sec n/a n/a 0=all gnd detection off 1=one shot to lockout S2=same seq. as FC 2 3rd Reclose Time 2, 3, 5, 10, 15, 30, 45 Def. Gnd. Lockout amps 10 to 400 amps SETTING INCREMENT 1 1 sec sec 10 amps (up to 300) 20 amps (300-800) 1 1 sec switch phase w/ "select" key switch phase w/ "select" key 5 amps (up to 150) 10 amps (150-400) 1 n/a n/a n/a NOTES None None None None None See manual for curves See manual for curves None Shows ops. on ea. phase Shows amps on ea. phase None Related to F.C. 17 Factory set none none Press appropriate key twice to access F.C. 13-19. Example: for 4:3 sec none FC 13 press 5 amps (up to 150) Related to F.C. 12 17 "1" twice, 10 amps (150-400) For FC 14 Fast Curves (Gnd) 1-5 1 See manual for curves 18 press "2" Time Dly. Curves (Gnd) 1-9 1 See manual for curves 19 twice, ect. Dmd. Time Interval 0 (off), 5, 15 sec Sets time interval for the demand meter d *The Demand Meter is displayed by pressing "10" multiple times press twice for "present", 3 times for "High", 4 times for "low". FUNCTION KEYS: The function keys (1-12) are used to access all functions of the URC-24. Press keys "1" - "12" once to directly access F.C. "1" - "12". Press keys "1"-"10" twice (or more for "d") to access F.C. "13" - "d". EDITING KEYS: Press "Select" switch between phases (A, B, C, & GND) when observing the operations count, current, or demand. Press "Ï" and "Ð" to edit the URC-24 functions after the security code has been entered (inactive until security code is entered). Press "Enter" to accept changes made with the "Ï" and "Ð" keys (inactive until security code is entered). SECURITY CODE: To enter the security code press the keypad keys in the following order "Enter", "5","2", "7", "Enter". Copyright 2007 I.C.M.I. (Inductive Components Mfg., Inc.) 1200 Ferris Rd., Amelia, OH 45102 Phone: (513) 752-4731 Fax: (513) 752-4738 Web: www.icmiinc.com Page 22 Revision 3.0, March 07, 2005