BY DAVID P. STOCKTON, JOHN R. BLAND, JR., TODD MCCLANAHAN, JIM WILSON, DAVID L. HARRIS, & PATRICK MCSHANE F IRE SAFETY, FIREWALLS, deluge systems, and fluid containment are some of the fire protection problems users face when installing mineral oil filled transformers. Aging substation infrastructure, environmental protection, and resource sustainability are other growing issues. To address these concerns, natural ester fluids are being utilized for their superior fire, environmental, and life-extension properties. Natural ester fluid offers the highest fire point of any insulating fluid at 360 °C and a flawless fire safety record through ten years and more than 45,000 installations. Natural ester fluid is manufactured IEEE INDUSTRY APPLICATIONS MAGAZINE JAN j FEB 2009 WWW.IEEE.ORG/IAS from seed oil and biodegradable additives, mak- 68 ing it readily biodegradable in the case of a spill. The combination of fire safety and biodegradability typically eliminates the traditional need for Digital Object Identifier 10.1109/MIAS.2008.930887 © PHOTODISC Safety, reliability, and environmental performance of natural ester fluids 1077-2618/09/$25.00©2009 IEEE incorporated less-flammable transfirewalls and deluge systems and can former fluids in 1978. Qualifying reduce spill containment, reporting, fluids must meet a minimum criteand remediation requirements. PropNATURAL ESTER rion of 300 °C open-cup fire point. erties unique to certain seed oils help FLUIDS CAN BE Figure 1 shows the fire and flash to slow down the insulation aging rate points of mineral oil and natural and to stabilize the electrical performREJUVENATED, ester, less-flammable fluids. ance of the transformer [1]. Because of this series of environmenThis article presents information on RECYCLED, AND tal regulations and liability risks involvthe safety, reliability, and environmental ing nonedible oils such as mineral oil, an performance of natural ester transformer READILY extensive research and development profluids by acquainting the readers with gram began in the early 1990s. Rethe history of transformer fluids and DISPOSED. searchers concluded that natural esters also explores how the industry has could be chemically enhanced to overarrived at the current technologies of come the initial barriers of inferior oxidanatural ester fluid. The properties of natural ester fluids are explained and then compared side by tion stability, pour point, permittivity, and viscosity values. According to the IEEE specification, when a new insulaside with conventional mineral oil fluid. This article outlines two refinery case studies. The tion system is developed, it is recommended to test the sysfirst case study is from a refinery in Texas City, where nat- tem following the C57.100 standard, also known as the ural ester transformers were chosen for a new wet gas Lockie method. This method is known as Standard for Thermal scrubber project. The second case study is from a refinery Evaluation of Oil-Immersed Distribution Transformers Life Test in Memphis, Tennessee, where natural ester fluid was [17]. This method uses actual transformers (Figure 2). used to retrofill an in-service, large-power transformer. These two case studies show the applicability of natural ester fluids in new and retrofilled distribution and power class transformers 400 Flash Point 350 300 250 200 150 Mineral Oil Natural Ester Fluid Flash Point 155 330 Fire Point 165 360 1 Transformer fluid flash and fire points. 2 Lockie-accelerated aging transformer test facility. Authorized licensed use limited to: IEEE Xplore. Downloaded on January 7, 2009 at 11:14 from IEEE Xplore. Restrictions apply. IEEE INDUSTRY APPLICATIONS MAGAZINE JAN j FEB 2009 WWW.IEEE.ORG/IAS Temperature (°C) Fire Point History of Transformer Fluids In the United States, the first distribution class transformer was constructed in 1885 and was of dry-type construction; it used air as the dielectric coolant. Although smaller and more efficient mineral oil transformers were patented in 1882 by Elihu Thomson, it was not until 1892 that General Electric produced the first-known liquid-filled transformer. Shortly after 1899, the key mineral properties were identified, and oil refineries began manufacturing this special transformer mineral oil [2]. For many decades, transformer users have recognized the benefits of liquid-filled transformers in comparison with dry-type transformers: overloadability, contamination resistance, surge protection, efficiency, space savings, noise levels, complete diagnostic capabilities, temperature, and expected life are some of the superior characteristics of these. From 1929 to 1977, polychlorinated biphenyl (PCB)filled transformers were commonly used, promoting fire safety in addition to the common liquid-filled transformer benefits. In 1976, the Toxic Substance Control Act [3] targeted the PCBs with extensive Environmental Protection Agency (EPA) regulation to follow the most recent changes in 1998 [4], [5]. Following a government ban of the further production and commercialization of PCB fluids due to environmental concerns, users turned to mineral oil and less-flammable fluids [6], [7]. Mineral oil, however, did not provide the necessary fire protection. The American National Standards Institute (ANSI) has published a Guide for Substation Fire Protection [8], stating that the minimum recommended distance to a building is 30 ft for mineral-oil-filled transformers greater than 333 kVA because of the increased fire risk. Originally referred to as high fire-point fluids until 1984, the National Electric Code (NEC) formally 69 Normative Annex A of this standard defines a sealed tube aging procedure for testing when it is not practical to test an actual transformer. Using this method, the insulation system must meet a minimum of 50% retained tensile strength for an equivalent of 65,000 h, 25% retained tensile strength for an equivalent of 130,000 h, or a degree of polymerization (DoP) greater than 200 for an equivalent of 150,000 h. Detailed results of this test are shown in a condensed format in Table 1 [18]. MINERAL OIL FIRES CAN PROPAGATE TO NEARBY EQUIPMENT AND BUILDINGS. TABLE 1. TEST PARAMETERS FOR TRANSFORMER-ACCELERATED AGING EVALUATION AND RESULTS [19]. Test Cell A B C 167 175 183 1,302 721 407 21 21 21 Hours 6,510 3,604 2,036 Years equivalent 105 105 105 10,186 6,623 328 271 Target hottest-S pot temperature (°C) Standard required expected life* Years equivalent Standard test method required life** Actual times to failure*** 11,400 þ 1,190 Hours Years equivalent 464 Environmental and sustainable characteristics are increasingly important. Natural ester fluids have been tested for biodegradability and can be classified in the most favorable EPA classifications of ultimately biodegradable and readily biodegradable ester fluids [20], [21]. These fluids have also been tested for acute aquatic toxicity with zero trout mortality through the standard test period of 96 h at 1,000 mg/kg [22], [23]. However, EPA SPCC essentially does not differentiate 100 15,000 75 10,000 25 5,000 0 0 0 1,000 2,000 3,000 4,000 Time at 170 °C (h) Mineral Oil Natural Ester Fluid Degree of Polymerization 20,000 Retained Tensile Strength (% of Unaged) 1,200 Tensile Strength (lb/in2) IEEE INDUSTRY APPLICATIONS MAGAZINE JAN j FEB 2009 WWW.IEEE.ORG/IAS Natural Ester Fluid Properties Environmental Safety Hours 70 Because of the extremely favorable results of this testing, further testing was conducted. Figures 3 and 4 show the significantly slower aging rate of thermally upgraded kraft paper in natural ester fluid when compared with mineral oil. ANSI defines the end of life of a transformer as 25% retained tensile strength for distribution transformers and 50% retained tensile strength for power transformers. Using DoP, end of life is defined as being less than or equal to 200. Both of these figures show the data results from tests performed at 170 °C. It has been estimated that thermally upgraded kraft paper in natural ester fluid will have the same life in an 85 °C temperature rise transformer as that of an identical paper in a 65 °C temperature rise mineral-oil-filled transformer [19]. 1,000 800 600 400 200 0 0 1,000 2,000 Natural Ester Fluid Calculated from IEEE Loading Guide (Error Bars = 1σ) 4 3 Aging rates (as tensile strength) of thermally upgraded paper in natural ester and mineral oil [19]. 4,000 Time at 170 °C (h) Mineral Oil Calculated from IEEE Loading Guide (Error Bars = 1σ) 3,000 Aging rates (as DoP) of thermally upgraded paper in natural ester and mineral oil [19]. Authorized licensed use limited to: IEEE Xplore. Downloaded on January 7, 2009 at 11:14 from IEEE Xplore. Restrictions apply. between oils while some state regulations do differentiate. Additionally, natural ester fluids are classified under the Edible Oil Regulatory Reform Act [16]. The complete combustion products are carbon dioxide and water. The fluid can be rejuvenated, recycled, and readily disposed. ANOTHER ADDED FEATURE OF NATURAL ESTER FLUIDS IS THE SOLUBILITY OF WATER IN THE FLUID. Fire Safety because of the proven fire-safety record of less-flammable liquids. Code listing requirements are now equal to or more flexible than those listed for silicone oils [14], [15]. FM Global increased the maximum fluid volume from 1,000 to 10,000 gal of an approved, lessflammable fluid-filled transformer for a given minimum clearance distance that is considered to be equivalent safeguard as firewalls and fire-suppression systems [24]. This change allows the users to lessen the separation distance for both equipment to buildings (Table 2) and equipment to equipment (Table 3). TABLE 3. OUTDOOR LIQUID-INSULATED EQUIPMENT-SEPARATION DISTANCES [24]. Approved Transformer or Equivalent Liquid Approved, lessflammable fluid Unapproved fluid Horizontal Distance, ft (m) (Based on Construction Type) Liquid Volume, gal (m3) 2-h Fire Resistant Noncombustible Vertical Distance, Combustible ft (m) Yes N/A 3 (0.9) 3 (0.9) 3 (0.9) 5 (1.5) No 10,000 (38) 5 (1.5) 5 (1.5) 25 (7.6) 50 (15.2) >10,000 (38) 15 (4.6) 15 (4.6) 25 (7.6) 50 (15.2) 5 (1.5) 15 (4.6) 25 (7.6) 25 (7.6) N/A <500 (1.9) 500–5,000 (1.9–19) 15 (4.6) >5,000 (19) 25 (7.6) 25 (7.6) 50 (15.2) 50 (15.2) 50 (15.2) 100 (30.5) 100 (30.5) Authorized licensed use limited to: IEEE Xplore. Downloaded on January 7, 2009 at 11:14 from IEEE Xplore. Restrictions apply. IEEE INDUSTRY APPLICATIONS MAGAZINE JAN j FEB 2009 WWW.IEEE.ORG/IAS There are a percentage of substation transformer fires that are eventful, often resulting in oil fires that are difficult to extinguish and are very costly to control. These mineral oil fires can also propagate to nearby equipment and buildings, creating a very large problem and risk. It is costly to control the fire, perform Relative Performance the necessary safety and clean-up processes, and repair A commonly occurring problem of transformers using carthe equipment; however, the downtime for these bon-based fluids is the development of coking on conducactions to occur is perhaps the most costly of all. tors and switch contacts. Coking tendency tests indicate These fires can be avoided by using a natural ester, that the natural ester fluid resists coke formation on hot less-flammable dielectric coolant. Factory Mutual (FM) metals [25]. A paper presented at the 2006 IEEE Power Global became the first nationally recognized testing Engineering Society (PES) Transmission and Distribution laboratory (NRTL) to list these less-flammable fluids (T&D) conference showed that stationary contacts had by [9]. Underwriters Laboratories (UL) then, in 1984, far the most stability during accelerated life test when developed a new standard for transformers, combining tested with natural ester [26]. the fire resistance of lessflammable fluids with the transTABLE 2. OUTDOOR LIQUID-INSULATED EQUIPMENT-SEPARATION former-protection schemes [10], DISTANCES [24]. [11]. There are currently ten Approved listings of less-flammable diTransformer Liquid Volume, Distance, electric coolants by FM Global or Equivalent gal (m3) ft (m) Liquid and UL [10], [12]. Yes N/A 3 (0.9) Approved, In 1994, FM Global also less-flammable adopted transformer installation No 10,000 (38) 5 (1.5) fluid guidelines that combined an ap>10,000 (38) 25 (7.6) proved, less-flammable fluid with transformer protection per their Mineral oil or N/A <500 (1.9) 5 (1.5) Approval Standard 3990 [13]. unapproved fluid 5005,000 25 (7.6) FM Global’s initial installation (1.919) requirements based on specific heat-release rates have been elimi>5,000 (19) 50 (15.2) nated for this class of material 71 tend to polymerize, causing a Another added feature of natural gradual increase in viscosity. Natural ester fluids is the solubility of water in esters are designed for use in sealed the fluid. Figure 5 shows a solubility THE NATURAL transformers [18]. chart of water in both mineral oil and Natural ester has the tendency natural ester fluids. This allows the ESTER FLUID for thin films of the fluid to polyfluid to remove more moisture away merize on hot surfaces exposed to air from the insulating paper, resulting in RESISTS COKE much more quickly than mineral improved dielectric performance, FORMATION ON oil. These films have excellent elimination of the possibility of vapor dielectric properties but can inhibit bubble formation during sudden overHOT METALS. mechanical operation and increase load, and a reduction in the paper the power factor of the coil, and aging rate. It also reduces or elimishould thus be avoided. This does nates the need for periodic, transnot become an issue unless an former dry-out services. The natural ester maintains higher dielectric strength, impregnated core and coil assembly are removed from especially at cold temperatures, because of its more fa- the fluid and stored for several weeks [25]. Doble Engineering developed the power factor valvorable saturation curve compared with mineral oil (see Figure 5). However, the pour point temperature is signifi- ued oxidation (PFVO) and sludge-free life (SFL) tests to resolve the issue of testing oxidation stability of cantly higher than mineral oil. transformer fluids [28]. 72 The historically based opinions that natural esters did not have sufficient oxidation stability properties were commonly derived from results of tests such as ASTM D 2112 and D 2440. When these test methods are applied to natural esters, they perform very poorly because of the nature of the tests. The tests are used to check the inhibitors used in the mineral oil but are not indicative of inservice performance. The reason for the attention to oxidation stability is due to the degradation products of mineral oil precipitating as sludge. However, natural esters oxidize much differently because of the chemical composition of the fluid. Rather than a sludge precipitant, natural esters 5,000 Water Saturation Point (mg/kg) IEEE INDUSTRY APPLICATIONS MAGAZINE JAN j FEB 2009 WWW.IEEE.ORG/IAS Oxidation Stability 4,000 3,000 2,000 Case Study 1: New Distribution Transformer Installation History or Project Scope Following a fatal explosion at the largest oil refinery in Texas City, Texas, the refinery is currently initiating an extensive maintenance and modernization program. The company’s five-year, US$1 billion focus on the future plan is promoting the highest levels of safety, reliability, and environmental performance in equipment installation and upgrades [29]. One such investment was a wet gas scrubber project to reduce sulfur oxide and nitrogen oxide emissions from the fluid catalytic cracking units, which required ten liquidfilled transformers. The wet gas scrubber being installed was to replace an existing system using an electrostatic precipitator. Earlier, the electrostatic precipitator was using an existing double-ended substation, and the equipment was required to remain in service while the wet gas scrubber system was being installed. This meant that the real estate was at an extreme premium, with very little room to work while installing the new system. Original Specification 1,000 0 20 40 60 80 Temperature (°C) A– Saturation (T ) = 10 · 100 120 B 273 +T Natural Ester Fluid: A = 5.3318, B = 684 From Double Engineering Mineral Oil: A = 7.0895, B = 1,567 From IEEE C57.106 When specifying the transformers for this project, the customer and the electrical contractor extended bid opportunities to multiple equipment manufacturers, specifying mineral oil as a standard, with natural ester fluid as an alternate. Although the consultant was relatively familiar with natural ester products, the customer was not initially aware of the option and the benefits inherent with such a fluid. Findings with Natural Ester Fluid 5 One hundred percent water saturation versus temperature of natural ester fluid [26] and mineral oil [27]. Following the receipt of proposals for the liquid-filled transformers, the consultant began reviewing the pricing and options. The natural ester-filled transformers were consistently higher on purchase price. After further investigation, it was found that there were additional benefits in using natural ester-filled transformers Authorized licensed use limited to: IEEE Xplore. Downloaded on January 7, 2009 at 11:14 from IEEE Xplore. Restrictions apply. that would help to justify and offset these purchase costs. Health, Safety, Security, and Environment Because of the company’s increased safety awareness, there were very stringent installation procedures for liquid-filled transformers. According to the health, safety, security, and environment (HSSE) policy, the customer was required to install a deluge system and containment for every new liquidfilled transformer installation. Option 1: Fire Deluge System NATURAL ESTERS ARE DESIGNED FOR USE IN SEALED TRANSFORMERS. The refinery was not amenable to a fire deluge system for several reasons. It is required to test the system periodically. To perform this test, the transformers must be deenergized. Since these are the main power feed transformers for the entire refinery, this was not an option. Additionally, the refinery was concerned about spraying the equipment with water containing chlorine and other additives. Option 2: Firewalls Between Transformers Final Installation and Future Transformers Case Study 2: Retrofilled Power Transformer History or Project Scope The refinery had two existing mineral-oil-filled power transformer units feeding the electrical distribution system. The transformers were base rated 25 MVA, with a maximum rating of 46.6 MVA. The primary voltage was 161 kV delta connected, stepping down to a service voltage of 12.47 kV wye connected. The two transformers had been purchased in 1980. The refinery’s insurance company, FM Global, evaluated the two units and determined that the units were too close to one another. The separation distance was not sufficient for mineral oil transformers. The insurance company presented two options to the refinery: fire deluge system and firewalls between transformers. This option was very carefully evaluated. In the end, it was determined that in the case of a spill and a fire the firewalls would merely channel the propagating fluid fire toward the rest of the substation, further spreading the fire and destroying more equipment. Other Options: Less-Flammable Fluids The plant electrical engineer began researching other methods for fire safety. While researching the FM Global guidelines, it was found that less-flammable fluids can be used to significantly reduce the separation distances between equipment as shown in Table 2. The refinery approached FM Global with the option of retrofilling both the units with an approved natural ester, less-flammable fluid. FM Global readily accepted the option. When discussing this retrofilling option with the transformer original equipment manufacturer (OEM), it was found that the equipment was not required to be derated and that the mineral oil and natural ester fluids are completely compatible. Future Transformers An additional power transformer was purchased for the refinery, and natural ester fluid was specified for the unit. The refinery plans to purchase all future units with natural ester fluids. Conclusions The growing demands for improved fire safety, source material sustainability, environment friendliness, and asset life extension have driven the research and development efforts of natural ester, less-flammable fluid. The majority of performance characteristics of natural ester fluids are far superior to those of conventional mineral oil, including fire safety, material compatibility, electrical and thermal characteristics, and a significant reduction in insulation aging rate. The two case studies presented in this article have shown the applicability of a natural ester fluid in both new and retrofilled power and distribution transformers. In addition to being used in outdoor applications, natural ester fluid-filled transformers are becoming more commonly used indoors because of their proven fire-safety performance and code-compliance options. The largest disadvantage to natural ester fluid-filled transformers is the first cost price differential of Authorized licensed use limited to: IEEE Xplore. Downloaded on January 7, 2009 at 11:14 from IEEE Xplore. Restrictions apply. IEEE INDUSTRY APPLICATIONS MAGAZINE JAN j FEB 2009 WWW.IEEE.ORG/IAS The idea of the alternate natural ester fluids was presented to the customer. During this presentation, items such as fire safety and environmental performance were the biggest decision drivers. With the flawless fire record in more than 45,000 applications over ten years, the HSSE group recognized the safety benefits [25]. Because of this, the group made the decision not to require fire deluge systems for the new natural ester-filled transformers. Equally, the group evaluated the biodegradation properties of the natural esters. After being presented with information showing that the fluid is greater than 99% biodegradable after 21 days, the HSSE group made the decision that containment was not required for these natural ester-filled transformers [20], [21]. After the requirement for tire deluge systems and containment were removed from the natural ester, lessflammable fluid-filled transformers, the prices were reevaluated. The installation cost savings for natural ester-filled transformers easily justified the small purchase price difference. In this application, the natural ester fluid not only met all focus-on-the-future objectives but also reduced the total installation cost of the transformers while saving space on a project where real estate was at a premium. For all future installations of liquid-filled transformers, the refinery has adopted a policy of natural ester, lessflammable fluid-filled transformers. 73 [17] Standard for Thermal Evaluation of Oilapproximately 10–15% more than Immersed Distribution Transformers, ANSI/ the conventional mineral oil. HowIEEE Standard C57.100-1986, 1986. THE NATURAL ever, the fluid offers a significant life [18] C. P. McShane, G. A. Gauger, and J. Lukcycle value for users, justified with sich, ‘‘Fire-resistant natural ester dielecESTER MAINTAINS tric fluid and novel insulation system for the performance advantages of the its use,’’ in Proc. IEEE/IAS Transmission fluid. HIGHER and Distribution Conf., New Orleans, LA, Electrical groups, including mem1999. bers of IEEE Petroleum and Chemical [19] C. P. McShane, ‘‘Vegetable-oil-based dielecDIELECTRIC tric coolants,’’ IEEE Ind. Applicat. Mag., Industry Committee (PCIC), have pp. 34–41, May/June 2002. helped to develop new standards for STRENGTH, [20] Office of Prevention, Pesticides, and natural ester dielectric fluids. An Toxic Substances, ‘‘Fate, transport, and ESPECIALLY AT American Society for Testing and transformation test guidelines: OPPTS Materials (ASTM) standard for the 835.3100 aerobic aquatic degradation,’’ COLD U.S. Environmental Protection Agency, acceptance of new natural ester dielecWashington, DC, EPA Publication, 712tric fluids was issued in 2003 [30]. An TEMPERATURES. C-98-075, Jan. 1998. American National Standard Institute [21] Office of Prevention, Pesticides, and Toxic (ANSI)/IEEE standard guide for the Substances, ‘‘Fate, Transport, and Transformation Test Guidelines: OPPTS 835.3110 acceptance and maintenance of natural ready biodegradation,’’ U.S. Environmental Protection Agency, esters is in the balloting process [31]. As more users adopt Washington, DC, EPA Publication, 712-C-98-076, Jan. 1998. this technology, user groups must also work to help [22] OECD, ‘‘Test no. 203: Fish, acute toxicity test,’’ in OECD Guidelines develop database information, especially for preventative for the Testing of Chemicals, Section 2: Effects on Biotic Systems, Paris maintenance purposes. Cedex, France: Organization for Economic Cooperation and Develop- Acknowledgments We gratefully acknowledge the contributions of Jerry Corkran, John Luksich, Peter Stenborg, Kevin Rapp, Jonathan Piel, Larry Bucholtz, Henry Hecker, Roger Bengtson, Jeff Schneider, Ray Schmidt, Dave Vetterick, and Jim Harrison. IEEE INDUSTRY APPLICATIONS MAGAZINE JAN j FEB 2009 WWW.IEEE.ORG/IAS References [1] (2001, June). Envirotemp FR3 Fluid. Cooper Power Systems Bulletin 00092 [Online]. Available: http://www.cooperpower.com/Library/ pdf/00092.pdf [2] F. M. Clark, Insulating Materials for Design and Engineering Practice. New York: Wiley, 1962. [3] Toxic Substance Control Act. U.S. Public Law 94-469, 1976. [4] PCB Regulations, Environmental Protection Agency, Part 761, 40 CFR, 1979. [5] Disposal of Polychlorinated Biphenyls (PCBs), Environmental Protection Agency, Parts 750-761, 40 CFR, 1998. [6] M. Earley, ‘‘Minimizing the hazards of transformer fires,’’ Fire J., pp. 73–74, Jan./Feb. 1988. [7] D. A. Hallerberg, ‘‘Less-flammable liquids used in transformers,’’ IEEE Ind. Applicat. Mag., vol. 5, pp. 50–55, Jan./Feb. 1999. [8] IEEE Guide for Substation Fire Protection, IEEE Standard 979-1994, 1994. [9] Factory Mutual Approval Guide. Norwood, MA: Factory Mutual Research Corporation, 1979. [10] ‘‘R-temp fluid UL classification marking,’’ in Gas & Oil Equipment Directory. Chicago, IL: Underwriter’s Laboratories, 1984. [11] S. D. Northrup, ‘‘Protection of transformers for prevention of rupture, explosion, and fire,’’ presented at the Edison Electric Institute Transmission and Distribution Conf., Fort Worth, TX, 1985. [12] Factory Mutual Approval Guide. Norwood, MA: Factory Mutual Research Corporation, 1999. [13] Less and Nonflammable Liquid Insulated Transformers, Factory Mutual Research Corporation Approval Standard Class Number 3990. [14] ‘‘Loss prevention data sheet 5-4/14-8,’’ Norwood, MA: Factory Mutual Research Corporation, 1997, revised 1998. [15] NEC Requirement Guidelines, 1999 Code Options for the Installation of Listed Less Flammable Liquid Filled Transformers. Waukesha, WI: Cooper Power Systems, 1999. [16] Edible Oil Regulatory Reform Act, Public Law 104-55, 1995. ment, 1992. [23] ‘‘Final report: Acute trout toxicity testing for two Envirotemp FR3 formulations,’’ GlobalTox Int. Consultants, Guelph, ON, Canada, Dec. 1, 1999. [24] ‘‘5-4 transformers,’’ Section 2.3.1.1.1 Separation Distance, Property Loss Prevention Data Sheets, Factory Mutual Global, May 2003. [25] C. P. McShane, J. Corkran, K. Rapp, and J. Luksich, ‘‘Natural ester dielectric fluid development,’’ presented at the IEEE/PES Transmission Distribution Conf. and Exposition, Dallas, TX, 2006. [26] L. Lewand, ‘‘Laboratory evaluation of several synthetic and agricultural-based dielectric liquids,’’ in Proc. Doble Int. Client Conf., 5th ed. Boston, MA, 2001. [27] IEEE Guide for Acceptance and Maintenance of Insulation Oil in Equipment, IEEE Standard C57.106-2002, 2002. [28] F. S. Oliver, ‘‘Doble power factor valued oxidation tests,’’ in Doble Conf. Minutes, Insulating Fluids, 10-401, pp. 1–9, 1960. [29] BP Investigation Team, ‘‘Fatal accident investigation report, isomerization unit explosion final report,’’ BP North America, Houston, TX, 2005. [30] Standard Specification for Natural (Vegetable Oil) Ester Fluids for Use in Electrical Apparatus, ASTM D 6871-03, 2004. [31] Proposed Standard Guide for Acceptance and Maintenance of Natural Ester Fluids in Transformers, IEEE Standard C57.147. [32] L. Dix and P. Hopkinson, ‘‘Tapchangers for de-energized operation in natural ester, mineral oil, and silicone,’’ presented at the IEEE/PES Transmission and Distribution Conf., Dallas, TX, 2006. David P. Stockton (dstockton@cooperpower.com) and Patrick McShane are with Cooper Power Systems in Waukesha, Wisconsin. John R. Bland, Jr., is with BP Texas City Refinery. Todd McClanahan is with Valero Refining in Memphis, Tennessee. Jim Wilson is with Jacobs in Houston, Texas. David L. Harris is with Waukesha Electric Systems in Wisconsin. McClanahan and Harris are Members of the IEEE. McShane is a Senior Member of the IEEE. This article first appeared as ‘‘Natural Ester Transformer Fluids: Safety, Reliability, and Environmental Performance’’ at the 2007 Petroleum and Chemicals Industry Conference. 74 Authorized licensed use limited to: IEEE Xplore. Downloaded on January 7, 2009 at 11:14 from IEEE Xplore. Restrictions apply.