USD 315 Fire Alarm Request for Proposal Colby, KS SECTION 2 8 31 00 – FIRE ALARM INTEGRATED AUDIO VISUAL EMERGENCY COMMUNICATION SYSTEM PART 1 - GENERAL 1.1 A. 1.2 RELATED DOCUMENTS Drawings and general provisions of the Request For Proposal apply to this Section. SUMMARY A. Contractor shall provide all permits, labor, equipment, materials and services to furnish and install a full functional UL Listed, code compliant, integrated, intelligent addressable fire alarm and emergency communication system. B. BASE BID: FIRE ALARM SYSTEM EXPANSION 1. The Contractor shall expand the existing Notifier NFS-320E Fire Alarm System located in the Intermediary building to provide the fire alarm systems in the Middle School and Primary School as shown on the Drawings 2. This section covers the equipment, devices, cabling and pathways to provide a complete addressable fire alarm system. Section Includes: a. Fire Alarm System 1) Fire Alarm Control Panel 2) Manual fire-alarm boxes 3) System smoke detectors 4) Heat detectors 5) Device guards 6) Magnetic door holders 7) Remote annunciator 8) Addressable interface device 9) Notification Appliances C. ALTERNATE: INTEGRATED EMERGENCY COMMUNICATION SYSTEM 1. The Contractor shall provide an ALTERNATE Bid to modify and expand the existing Notifier NFS-320E Fire Alarm System to include and intelligible Voice Emergency Communication System. All Audio and Audio/Visual Notification Appliances shown on the drawings shall be changed to allow for Intelligible Voice Communication. 2. This section covers the equipment, devices, cabling and pathways to provide a complete addressable fire alarm and integrated emergency communication system. Section Includes: a. Integrated Emergency Communication System 1) Autonomous Control Unit 2) Local Operating Console 3) Fire Alarm Control Interface 4) Notification appliances 5) Audio Amplifiers FIRE ALARM INTEGRATED AUDIO VISUAL EMERGENCY COMMUNICATION SYSTEM 28 31 00 - 1 USD 315 Fire Alarm Request for Proposal Colby, KS 1.3 CODES AND STANDARDS A. The system shall comply with the provisions of the following codes and standards as the codes and standards apply. System shall comply the either the latest version of the codes and standards unless the AHJ has adopted earlier versions B. National Fire Protection Agency (NFPA) 1. NFPA 70 National Electrical Code 2. NFPA 72 National Fire Alarm and Signaling Code 3. NFPA 90A Standards for the Installation of Air-Conditioning and Ventilating Systems 4. NFPA 101 Life Safety Code C. Underwriter’s Laboratories, Inc. 1. UL 864 - Control Units for Fire Protective Signaling Systems. 2. UL 268 - Smoke Detectors for Fire Protective Signaling Systems. 3. UL 268A - Smoke Detectors for Duct Applications. 4. UL 521 - Heat Detectors for Fire Protective Signaling Systems. 5. UL 228 - Door Closers-Holders, With or Without Integral Smoke Detectors. 6. UL 464 - Audible Signaling Appliances. 7. UL 38 - Manually Actuated Signaling Boxes for Use with FireProtective Signaling Systems 8. UL 346 - Waterflow Indicators for Fire Protective Signaling Systems. 9. UL 1971 - Signaling Devices for the Hearing-Impaired. 10. UL-1480 - Speakers for Fire Alarm, Emergency, and Commercial and Professional Use 11. UL 1481 - Power Supplies for Fire Protective Signaling Systems. 12. UL 1711 - Amplifiers for Fire Protective Signaling Systems. 13. UL 1635 - Digital Alarm Communicator System Units 14. UL 2075 – Gas and Vapor Detectors and Sensors 15. UL 2572 - Control and Communication Units for Mass Notification Systems D. International Code Council: 1. International Building Code - 2012 2. International Fire Code - 2012 E. Americans with Disabilities Act (ADA) 1.4 DEFINITIONS A. ACU: Autonomous Control Unit. B. ADA: C. AFF: D. AHJ: E. Approved: Unless otherwise stated, materials, equipment or submittals approved by the Authority or AHJ. Americans with Disabilities Act. Above Finished Floor. Authority Having Jurisdiction. FIRE ALARM INTEGRATED AUDIO VISUAL EMERGENCY COMMUNICATION SYSTEM 28 31 00 - 2 USD 315 Fire Alarm Request for Proposal Colby, KS F. ECS: Emergency Communication System. G. EMT: H. FAAP: Fire Alarm Annunciator Panel I. FACP: J. HLI: K. HVAC: L. IDC: Initiating Device Circuit. M. LCD: Liquid Crystal Display. N. LED: Light Emitting Diode. O. LOC: Local Operating Console. P. NAC: Q. NEMA: National Electrical Manufacturers Association R. NFPA: S. NICET: gies T. NRTL: U. Pathway: Any circuit, conductor, optic fiber, radio carrier, or other means connecting two or more locations. V. PC: W. SLC: X. UL: Y. VESDA: 1.5 A. Fire Alarm Control Panel. High Level Interface. Heating Ventilating and Air Conditioning. Notification Appliance Circuit. National Fire Protection Association. National Institute for Certification in Engineering TechnoloNationally Recognized Testing Laboratory Personal computer. Signaling Line Circuit. Underwriters Laboratories, Inc. Very Early Smoke-Detection Apparatus. SUBMITTALS Product Data: For each type of product, including furnished options and accessories. 1. 2. B. Electrical Metallic Tubing. Include construction details, material descriptions, dimensions, profiles, and finishes. Include rated capacities, operating characteristics, and electrical characteristics. Shop Drawings: FIRE ALARM INTEGRATED AUDIO VISUAL EMERGENCY COMMUNICATION SYSTEM 28 31 00 - 3 USD 315 Fire Alarm Request for Proposal Colby, KS 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. C. Comply with recommendations and requirements in the "Documentation" section of the "Fundamentals" chapter in NFPA 72. Include plans, elevations, sections, details, and attachments to other work. Include details of equipment assemblies. Indicate dimensions, weights, loads, required clearances, method of field assembly, components, and locations. Indicate conductor sizes, indicate termination locations and requirements, and distinguish between factory and field wiring. Detail assembly and support requirements. Include voltage drop calculations for notification-appliance circuits. Include battery-size calculations. Include input/output matrix. Include statement from manufacturer that all equipment and components have been tested as a system and meet all requirements in this Specification and in NFPA 72. Include performance parameters and installation details for each detector. Verify that each duct detector is listed for complete range of air velocity, temperature, and humidity possible when airhandling system is operating. Include floor plans to indicate final outlet locations showing address of each addressable device. Show size and route of cable and conduits and point-to-point wiring diagrams. General Submittal Requirements: 1. 2. Submittals shall be approved by authorities having jurisdiction prior to submitting them to Architect. Shop Drawings shall be prepared by persons with the following qualifications: a. b. c. D. Trained and certified by manufacturer in fire-alarm system design. NICET-certified, fire-alarm technician; Level III minimum. Licensed or certified by authorities having jurisdiction. Delegated-Design Submittal: For notification appliances and smoke and heat detectors, in addition to submittals listed above, indicate compliance with performance requirements and design criteria, including analysis data signed and sealed by the qualified professional engineer responsible for their preparation. 1. 2. 3. 4. Drawings showing the location of each notification appliance and smoke and heat detector, ratings of each, and installation details as needed to comply with listing conditions of the device. Design Calculations: Calculate requirements for selecting the spacing and sensitivity of detection, complying with NFPA 72. Calculate spacing and intensities for strobe signals and soundpressure and intelligibility levels for audible appliances. Indicate audible appliances required to produce square wave signal per NFPA 72. Indicate Acoustically Distinguishable Spaces (ADS) per NFPA 72 FIRE ALARM INTEGRATED AUDIO VISUAL EMERGENCY COMMUNICATION SYSTEM 28 31 00 - 4 USD 315 Fire Alarm Request for Proposal Colby, KS 1.6 CLOSEOUT SUBMITTALS A. Operation and Maintenance Data: For fire-alarm systems and components to include in emergency, operation, and maintenance manuals. 1. Comply with the "Records" section of the "Inspection, Testing and Maintenance" chapter in NFPA 72. 2. Provide "Fire Alarm and Emergency Communications System Record of Completion Documents" according to the "Completion Documents" Article in the "Documentation" section of the "Fundamentals" chapter in NFPA 72. 3. Complete wiring diagrams showing connections between all devices and equipment. Each conductor shall be numbered at every junction point with indication of origination and termination points. 4. Riser diagram. 5. Device addresses. 6. Record copy of site-specific software. 7. Provide "Inspection and Testing Form" according to the "Inspection, Testing and Maintenance" chapter in NFPA 72, and include the following: a. Equipment tested. b. Frequency of testing of installed components. c. Frequency of inspection of installed components. d. Requirements and recommendations related to results of maintenance. e. Manufacturer's user training manuals. 8. Manufacturer's required maintenance related to system warranty requirements. 9. Abbreviated operating instructions for mounting at fire-alarm control panel, autonomous control unit, each annunciator and local operating console. B. Software and Firmware Operational Documentation: 1. 2. 3. 1.7 A. Software operating and upgrade manuals. Program Software Backup: On magnetic complete with data files. Device address list. media or compact disk, MAINTENANCE MATERIAL SUBMITTALS Furnish extra materials that match products installed and that are packaged with protective covering for storage and identified with labels describing contents. 1. 2. 3. 4. Lamps for Strobe Units: Quantity equal to 10 percent of amount installed, but no fewer than one unit. Smoke Detectors: Quantity equal to 10 percent of amount of each type installed, but no fewer than one unit of each type. Keys and Tools: One extra set for access to locked or tamperproofed components. Audible and Visual Notification Appliances: One of each type installed. FIRE ALARM INTEGRATED AUDIO VISUAL EMERGENCY COMMUNICATION SYSTEM 28 31 00 - 5 USD 315 Fire Alarm Request for Proposal Colby, KS 1.8 QUALITY ASSURANCE A. Installer Qualifications: Personnel shall be trained and certified by manufacturer for installation of units required for this Project. B. Installer Qualifications: Installation shall certified by NICET fire-alarm Level II technician. C. NFPA Certification: 1.9 A. be by personnel Obtain certification according to NFPA 72. WARRANTY Special Warranty: Manufacturer agrees to repair or replace fire system equipment and components that fail in materials or workmanship within specified warranty period. 1. 2. Warranty Extent: All equipment and components not covered in the Maintenance Service Agreement. Warranty Period: Five years from date of Substantial Completion. PART 2 - PRODUCTS 2.1 SYSTEM DESCRIPTION A. General 1. The supplied system shall be a new UL Listed integrated fire alarm (Base Bid) and emergency communication (Alternate) system that uses independently addressed fire detection devices, input/output control modules, notification appliances, consoles, amplifiers and speakers. 2. All critical systems, sub-systems and circuits shall be monitored for integrity. System faults shall be annunciated 3. Strobes shall be synchronized per NFPA-72 4. Signals shall be prioritized and processed in accordance with UL 2572 as indicated below: a. Special suppression pre discharge alarm (CO2, FM200, or other total flooding gaseous suppression system b. Mass Notification c. Fire Alarm/Life Safety d. Other 5. Operation of any ECS functions by a user shall be indicated at the FACPs, LOCs and FAAPs that the respective ECS system is active. 6. The system shall provide for the ability of single button activation of Pre-recorded emergency messages 7. The system shall be capable of sending up to 8 simultaneous messages to 8 different zones. B. Fire Alarm-Base Bid 1. Non-coded, UL-certified, non-proprietary addressable system, with multiplexed signal transmission. 2. Automatic sensitivity control of certain smoke detectors. FIRE ALARM INTEGRATED AUDIO VISUAL EMERGENCY COMMUNICATION SYSTEM 28 31 00 - 6 USD 315 Fire Alarm Request for Proposal Colby, KS 3. 4. 5. 6. C. 2.2 A. Alternate: Integrated Communication System – ONE WAY 1. Non-coded, UL-certified, non-proprietary emergency communication system, 2. A library of pre-recorded messages shall be available for the operator at the ACU or LOC. The library shall consist of the following messages a. Lockdown (Security Threat) b. Weather warning c. Fire alarm d. All clear e. Evacuation f. Stand by g. Chemical Emergency h. Test 3. The system shall be capable of live voice paging from any LOC. 4. Upon Alarm activation of the Fire Alarm system the system shall remain in alarm mode until all initiating devices are reset and the fire alarm panel is manually reset. 5. The system may be “silenced” in accordance with NFPA-72 SYSTEMS OPERATIONAL DESCRIPTION Fire-alarm signal initiation shall be by one or more of the following devices: 1. 2. 3. 4. 5. 6. B. All components provided shall be listed for use with the selected system. Batteries shall be supplied to support the system for 24hrs of standby operation followed by 15 minutes of alarm operation at the end of the 24 hour period. Event processing and display shall be prioritized as follows: a. Fire alarms b. Supervisory events c. Trouble events d. Monitoring events Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application. Manual stations. Heat detectors. Smoke detectors. Duct smoke detectors. Carbon monoxide detectors. Automatic sprinkler system water flow. Fire-alarm signal shall initiate the following actions: 1. 2. 3. 4. Continuously operate alarm notification appliances, including voice evacuation notices. Identify alarm and specific initiating device at fire-alarm control unit and remote annunciators. Unlock electric door locks in designated egress paths. Release fire and smoke doors held open by magnetic door holders. FIRE ALARM INTEGRATED AUDIO VISUAL EMERGENCY COMMUNICATION SYSTEM 28 31 00 - 7 USD 315 Fire Alarm Request for Proposal Colby, KS 5. 6. 7. 8. 9. 10. 11. C. Emergency Notification signal initiation shall be by one or more of the following devices: 1. 2. 3. 4. D. Activate emergency communication system. Switch heating, ventilating, and air-conditioning equipment controls to fire-alarm mode. Close smoke dampers in air ducts of designated air-conditioning duct systems. Recall elevators to primary or alternate recall floors. Activate elevator power shunt trip. Activate emergency lighting control. Record events in the system memory. Local Operating Consoles Emergency Push Buttons Fire Alarm System Other Emergency Management Systems Emergency Notification signal shall initiate the following actions: 1. 2. 3. 4. 5. Continuously operate alarm notification appropriate emergency notices. Override Fire Alarm Activate emergency lighting control. Record events in the system memory. Record events by the system printer. appliances, including E. Non-Emergency (General) Notification signal shall initiate the following actions: 1. Operate Audible alarm notification devices for live voice or prerecorded messages 2. Activation will NOT override Fire Alarm F. Supervisory signal initiation shall be by one or more of the following devices and actions: 1. 2. 3. 4. 5. G. Valve supervisory switch. Elevator shunt-trip supervision. Independent fire-detection and -suppression systems. User disabling of zones or individual devices. Loss of communication with any panel on the network. System trouble signal initiation following devices and actions: 1. 2. 3. 4. 5. 6. 7. shall be by one or more of the Open circuits, shorts, and grounds in designated circuits. Opening, tampering with, or removing alarm-initiating and supervisory signal-initiating devices. Loss of communication with any addressable sensor, input module, relay, control module, remote annunciator, printer interface, or Ethernet module. Loss of primary power at fire-alarm control unit. Ground or a single break in internal circuits of fire-alarm control unit. Abnormal ac voltage at fire-alarm control unit. Break in standby battery circuitry. FIRE ALARM INTEGRATED AUDIO VISUAL EMERGENCY COMMUNICATION SYSTEM 28 31 00 - 8 USD 315 Fire Alarm Request for Proposal Colby, KS 8. 9. 10. H. System Supervisory Signal Actions: 1. 2. 2.3 Failure of battery charging. Abnormal position of any switch at fire-alarm control unit or annunciator. Voice signal amplifier failure. Initiate notification appliances. Identify specific device initiating control unit and remote annunciators. the event at fire-alarm FIRE-ALARM CONTROL PANEL (FACP) A. Manufacturers: Notifier – No Substitutions B. General Requirements for Fire-Alarm Control Panel: 1. Field-programmable, microprocessor-based, modular, power-limited design with electronic modules, complying with UL 864. a. b. c. d. 2. 3. System software and programs shall be held in nonvolatile flash, electrically erasable, programmable, read-only memory, retaining the information through failure of primary and secondary power supplies. Include a real-time clock for time annotation of events on the event recorder and printer. Provide communication between the FACP, FACI and remote circuit interface panels, annunciators, and displays. Provide nonvolatile memory for system database, logic, and operating system and event history. The system shall require no manual input to initialize in the event of a complete power down condition. The FACP shall provide a minimum 500event history log. Addressable Initiation Device Circuits: The FACP shall indicate which communication zones have been silenced and shall provide selective silencing of alarm notification appliance by building communication zone. Addressable Control Circuits for Operation of Notification Appliances and Mechanical Equipment: The FACP shall be listed for releasing service. C. The system shall provide off premises communications capability using a Digital Alarm Communications Transmitter (DACT) for sending system events to multiple Central Monitoring Station (CMS) receivers over Ethernet. 1. Comply with UL 1635. 2. In the event of a fire alarm panel CPU failure during a fire alarm condition, the DACT degrade mode shall transmit a general fire alarm signal to the CMS. D. Alphanumeric Display and System Controls: Arranged for interface between human operator at fire-alarm control unit and addressable system components including annunciation and supervision. Display FIRE ALARM INTEGRATED AUDIO VISUAL EMERGENCY COMMUNICATION SYSTEM 28 31 00 - 9 USD 315 Fire Alarm Request for Proposal Colby, KS alarm, supervisory, and component status messages and the programming and control menu. 1. 2. E. Annunciator and Display: Liquid-crystal type, 80 characters, minimum. Keypad: Arranged to permit entry and execution of programming, display, and control commands. Initiating-Device, Circuits: 1. 2. b. c. 2. 3. 4. One RS 485 port for remote annunciators, Ethernet module, or multi-interface module (printer port). One USB or RS 232 port for PC configuration. One RS 232 port for voice evacuation interface. Initiate audible and visible indication of an "alarmverification" signal at fire-alarm control unit. Activate an approved "alarm-verification" sequence at fire-alarm control unit and detector. Sound general alarm if the alarm is verified. Cancel fire-alarm control unit indication and system reset if the alarm is not verified. Elevator Recall: 1. Elevator recall shall be initiated only by one of the following alarm-initiating devices: a. b. c. 2. 3. Elevator lobby detectors except the lobby detector on the designated floor. Smoke detector in elevator machine room. Smoke detectors in elevator hoistway. Elevator controller shall be programmed to move the cars to the alternate recall floor if lobby detectors located on the designated recall floors are activated. Water-flow alarm connected to sprinkler in an elevator shaft and elevator machine room shall shut down elevators associated with the location without time delay. a. H. Signaling-Line Smoke-Alarm Verification: 1. G. and Install no more than 200 addressable devices on each signalingline circuit. Serial Interfaces: a. F. Notification-Appliance, Water-flow switch associated with the sprinkler in the elevator pit may have a delay to allow elevators to move to the designated floor. Door Controls: Door hold-open devices that are controlled by smoke detectors at doors in smoke-barrier walls shall be connected to firealarm system. FIRE ALARM INTEGRATED AUDIO VISUAL EMERGENCY COMMUNICATION SYSTEM 28 31 00 - 10 USD 315 Fire Alarm Request for Proposal Colby, KS I. 2.4 A. Remote Smoke-Detector Sensitivity Adjustment: Controls shall select specific addressable smoke detectors for adjustment, display their current status and sensitivity settings, and change those settings. Allow controls to be used to program repetitive, time-scheduled, and automated changes in sensitivity of specific detector groups. Record sensitivity adjustments and sensitivity-adjustment schedule changes in system memory, and print out the final adjusted values on system printer. MANUAL FIRE-ALARM BOXES General Requirements for Manual Fire-Alarm Boxes: Comply with UL 38. Boxes shall be finished in red with molded, raised-letter operating instructions in contrasting color; shall show visible indication of operation; and shall be mounted on recessed outlet box. If indicated as surface mounted, provide manufacturer's surface back box. 1. 2. 2.5 A. Double-action mechanism requiring two actions to initiate an alarm, pull-lever type; with integral addressable module arranged to communicate manual-station status (normal, alarm, or trouble) to fire-alarm control unit. Station Reset: Key- or wrench-operated switch. SYSTEM SMOKE DETECTORS General Requirements for System Smoke Detectors: 1. 2. 3. 4. 5. 6. 7. Comply with UL 268; operating at 24-V dc, nominal. Detectors shall be four-wire type. Integral Addressable Module: Arranged to communicate detector status (normal, alarm, or trouble) to fire-alarm control unit. Base Mounting: Detector and associated electronic components shall be mounted in a twist-lock module that connects to a fixed base. Provide terminals in the fixed base for connection to building wiring. Self-Restoring: Detectors do not require resetting or readjustment after actuation to restore them to normal operation. Integral Visual-Indicating Light: LED type, indicating detector has operated and power-on status. Remote Control: Unless otherwise indicated, detectors shall be digital-addressable type, individually monitored at fire-alarm control unit for calibration, sensitivity, and alarm condition and individually adjustable for sensitivity by firealarm control unit. a. b. c. d. Rate-of-rise temperature characteristic of combination smokeand heat-detection units shall be selectable at fire-alarm control unit for 15 or 20 deg F per minute. Fixed-temperature sensing characteristic of combination smoke- and heat-detection units shall be independent of rateof-rise sensing and shall be settable at fire-alarm control unit to operate at 135 or 155 deg F. Multiple levels of detection sensitivity for each sensor. Sensitivity levels based on time of day. FIRE ALARM INTEGRATED AUDIO VISUAL EMERGENCY COMMUNICATION SYSTEM 28 31 00 - 11 USD 315 Fire Alarm Request for Proposal Colby, KS B. Photoelectric Smoke Detectors: 1. 2. Detector address shall be accessible from fire-alarm control unit and shall be able to identify the detector's location within the system and its sensitivity setting. An operator at fire-alarm control unit, having the designated access level, shall be able to manually access the following for each detector: a. b. c. d. e. C. Duct Smoke Detectors: 1. 2. 3. 4. 5. 6. A. Primary status. Device type. Present average value. Present sensitivity selected. Sensor range (normal, dirty, etc.). Weatherproof Duct Housing Enclosure: NEMA 250, Type 4X; NRTL listed for use with the supplied detector for smoke detection in HVAC system ducts. Each sensor shall have multiple levels of detection sensitivity. Sampling Tubes: Design and dimensions as recommended by manufacturer for specific duct size, air velocity, and installation conditions where applied. Relay Fan Shutdown: Fully programmable relay rated to interrupt fan motor-control circuit. HEAT DETECTORS General Requirements for Heat Detectors: 1. B. Photoelectric type complying with UL 268A. Detector address shall be accessible from fire-alarm control unit and shall be able to identify the detector's location within the system and its sensitivity setting. An operator at fire-alarm control unit, having the designated access level, shall be able to manually access the following for each detector: a. b. c. d. e. 2.6 Primary status. Device type. Present average value. Present sensitivity selected. Sensor range (normal, dirty, etc.). Temperature sensors shall test sensitivity range of the device. Comply with UL 521. for and communicate the Heat Detector, Combination Type: Actuated by either a fixed temperature of 135 deg F or a rate of rise that exceeds 15 deg F per minute unless otherwise indicated. 1. 2. Mounting: Twist-lock base interchangeable with smoke-detector bases. Integral Addressable Module: Arranged to communicate detector status (normal, alarm, or trouble) to fire-alarm control unit. FIRE ALARM INTEGRATED AUDIO VISUAL EMERGENCY COMMUNICATION SYSTEM 28 31 00 - 12 USD 315 Fire Alarm Request for Proposal Colby, KS C. Heat Detector, Fixed-Temperature Type: exceeds a fixed temperature of 190 deg. 1. 2. 2.7 A. Description: Units are equipped for wall or floor mounting as indicated and are complete with matching doorplate. Comply with UL 228 2. 3. 4. 2.8 A. 2.9 A. Electromagnets: Require no more than 3 W to develop 25-lbf holding force. Wall-Mounted Units: Flush mounted unless otherwise indicated. Rating: 24-V ac or dc. Rating: 120-V ac. Material and Finish: Match door hardware. REMOTE ANNUNCIATOR Description: Annunciator functions shall match those of fire-alarm control unit for alarm, supervisory, and trouble indications. Manual switching functions shall match those of fire-alarm control unit, including acknowledging, silencing, resetting, and testing. 1. B. Mounting: Twist-lock base interchangeable with smoke-detector bases. Integral Addressable Module: Arranged to communicate detector status (normal, alarm, or trouble) to fire-alarm control unit. MAGNETIC DOOR HOLDERS 1. B. Actuated by temperature that Mounting: Flush or Surface mount cabinet, NEMA 250, Type 1. Display Type and Functional Performance: Alphanumeric display and LED indicating lights shall match those of fire-alarm control unit. Provide controls to acknowledge, silence, reset, and test functions for alarm, supervisory, and trouble signals. ADDRESSABLE INTERFACE DEVICE General: 1. 2. 3. Include address-setting means on the module. Store an internal identifying code for control identify the module type. Listed for controlling HVAC fan motor controllers. panel use to B. Monitor Module: Microelectronic module providing a system address for alarm-initiating devices for wired applications with normally open contacts. C. Integral Relay: Capable of providing a direct signal to elevator controller to initiate elevator recall and to circuit-breaker shunt trip for power shutdown. 1. Allow the control panel to switch the relay contacts on command. FIRE ALARM INTEGRATED AUDIO VISUAL EMERGENCY COMMUNICATION SYSTEM 28 31 00 - 13 USD 315 Fire Alarm Request for Proposal Colby, KS 2. D. A. Sprinkler 1. Each cuit a. normally closed Waterflow/Tamper Module: Comply with UL 346. module shall provide two (2) supervised Class B input circonfigured as: Normally-Open Alarm Delayed Latching for waterflow switch applications. Normally-Open Active Latching for tamper switch and supervisory applications. DEVICE GUARDS Description: Welded wire mesh of size and shape for the manual station, smoke detector, gong, or other device requiring protection. 1. 2. 2.11 two Operate notification devices. Operate solenoids for use in sprinkler service. b. 2.10 and Control Module: 1. 2. E. Have a minimum of two normally open contacts available for field wiring. Factory fabricated and furnished by device manufacturer. Finish: Paint of color to match the protected device. NOTIFICATION APPLIANCES A. General Requirements for Notification Appliances: Individually addressed, connected to a signaling-line circuit, equipped for mounting as indicated, and with screw terminals for system connections. B. General Requirements for Notification Appliances: Connected to notification-appliance signal circuits, zoned as indicated, equipped for mounting as indicated, and with screw terminals for system connections. 1. Combination Devices: Factory-integrated audible and visible devices in a single-mounting assembly, equipped for mounting as indicated, and with screw terminals for system connections. C. Horns: Electric-vibrating-polarized type, 24-V dc; with provision for housing the operating mechanism behind a grille. Comply with UL 464. Horns shall produce a sound-pressure level of 90 dBA, measured 10 feet from the horn, using the coded signal prescribed in UL 464 test protocol. Provide weather proof rated horns where indicated. D. Visible Notification Appliances: Xenon strobe lights complying with UL 1971, with clear or nominal white polycarbonate lens mounted on an aluminum faceplate. The word "ALERT" is engraved in minimum 1-inch high letters on the lens. 1. Rated Light Output: a. 15/30/75/110 cd, selectable in the field. FIRE ALARM INTEGRATED AUDIO VISUAL EMERGENCY COMMUNICATION SYSTEM 28 31 00 - 14 USD 315 Fire Alarm Request for Proposal Colby, KS 2. 3. 4. 5. 6. 2.12 Mounting: Wall mounted unless otherwise indicated. For units with guards to prevent physical damage, light output ratings shall be determined with guards in place. Flashing shall be in a temporal pattern, synchronized with other units. Strobe Leads: Factory connected to screw terminals. Mounting Faceplate: Factory finished, red. EMERGENCY COMMUNICATION SYSTEM (ONE-WAY) - Alternate A. Manufacturers: B. General Requirements for Emergency Communication System: 1. Field programmable, modular design with all electronic devices complying with UL2572 2. Notifier – No Subsitutions Indicate number of alarm channels for automatic, simultaneous transmission of different announcements to different zones or for manual transmission of announcements by use of the local operating console. Amplifiers shall comply with UL2572. a. 3. C. Allow the application of, and evacuation signal to, indicated number of zones and, at the same time, allow voice paging to the other zones selectively or in any combination. b. Programmable tone and message sequence selection. c. Standard digitally recorded messages for the following: 1) Evacuation 2) Shelter in Place 3) Weather Alert 4) Stand By 5) All Clear 6) Test d. Generate tones to be sequenced with audio messages of type recommended by NFPA 72 and that are compatible with tone patterns of notification-appliance circuits of fire-alarm control unit. ACU, Preamplifiers, amplifiers, and tone generators shall automatically transfer to backup units, on primary equipment failure. AUTONOMOUS CONTROL UNIT (ACU): Comply with UL 2572. 1. General Requirements for ACU a. Interface per NFPA-72 to the FACP through an approved internal/external Fire Alarm Control Interface. b. Upon ACU initiation, ACU shall take precedence over any other actions including LOCs. c. Supervise all Local Operating Consoles, Amplifiers, Preamplifiers and Speaker Circuits. d. Override Fire Alarm under conditions assed as “Priority” over Fire Alarm in the Risk Assessment. e. Combined Fire Alarm/Autonomous Control Unit is acceptable. 2. Status Annunciator: Indicate the status of various voice/alarm speaker zones. FIRE ALARM INTEGRATED AUDIO VISUAL EMERGENCY COMMUNICATION SYSTEM 28 31 00 - 15 USD 315 Fire Alarm Request for Proposal Colby, KS 3. 4. 5. D. 2.13 A. 2.14 ACU shall have push buttons and/or switches to control, at a minimum, the functions as follows: a. Local Silence b. System Test c. System Fault Reset d. Fire Alarm Silence ACU shall be equipped with a microphone that shall allow for initiating of live or pre-recorded page messages. Minimum Two Auxiliary Line Level inputs for audio inputs from other audio source for emergency communication Local Operating Consoles (LOC): The LOC shall utilize standard emergency communication user interface components to provide the ability to operate the Autonomous Control Unit functions from alternate locations within the building. Function shall include initiating all pre-recorded and live page messages. FIRE ALARM CONTROL INTERFACE General: Fire Alarm Control Interface to be listed for connection to the FACP and Comply with UL 864. 1. Primary and secondary power for ACU shall from a 24VDC power source 2. FACI shall monitor all NAC, LOCs, Amplifiers and report faults and alarms to the FACP. 3. Provide and distinctive audible and visual indication to the FACP that the ECS System is active. 4. FACI shall receive alarm indications from FACP and send to ACU. 5. Front Panel Shall include indicators for the following: a. Primary Power Present b. System Fault c. General Alarm d. General Fault e. AC Power Fault f. NAC Fault g. Zone Alarms (up to 8 minimum) AMPLIFERS A. General Requirements for Amplifiers: Integral audio processing to select any digitized audio channel, selectable 25/70Vrm output with a minimum of 20 watt power per paging zone. 1. Programmable channel to channel failover or amplifier to amplifier failover capability. 2. Ability to support EOL monitoring for NAC circuit integrity 3. Ability to store emergency messages in on-board, non-volatile digital memory 4. Ability to report all detected faults internal to amplifier B. Voice/Tone Notification Appliances: 1. 2. Comply with UL 1480 and UL2572 Speakers for Voice Notification: Locate speakers for voice notification to provide the intelligibility requirements of the FIRE ALARM INTEGRATED AUDIO VISUAL EMERGENCY COMMUNICATION SYSTEM 28 31 00 - 16 USD 315 Fire Alarm Request for Proposal Colby, KS 3. 4. 5. 6. 7. "Notification Appliances" and "Emergency Communications Systems" Chapter 24 and Annex D in NFPA 72. High-Range Units: Rated 2 to 15 W. Low-Range Units: Rated 1 to 2 W. Minimum Frequency Speaker Response: 400-4,000 hz Mounting: Surface mounted and bidirectional. Matching Transformers: Tap range matched to acoustical environment of speaker location. PART 3 - EXECUTION A. Examine areas and conditions for compliance with requirements for ventilation, temperature, humidity, and other conditions affecting performance of the Work. 1. Verify that manufacturer's written instructions for environmental conditions have been permanently established in spaces where equipment and wiring are installed, before installation begins. B. Examine roughing-in for electrical connections locations of connections before installation. C. Proceed with installation only after unsatisfactory conditions have been corrected. 3.2 A. EQUIPMENT INSTALLATION COMMUNICATION SYSTEM – FIRE ALARM INTEGRATED to verify AUDIO actual EMERGENCY Comply with NFPA 72, NFPA 101, and requirements of authorities having jurisdiction for installation and testing of fire-alarm equipment. Install all electrical wiring to comply with requirements in NFPA 70 including, but not limited to, Article 760, "Fire Alarm Systems." 1. 2. Devices placed in service before all other trades have completed cleanup shall be replaced. Devices installed but not yet placed in service shall be protected from construction dust, debris, dirt, moisture, and damage according to manufacturer's written storage instructions. B. Install wall-mounted equipment, with tops of cabinets not more than 78 inches above the finished floor. C. Manual Fire-Alarm Boxes: 1. 2. 3. D. Install manual fire-alarm box in the normal path of egress within 60 inches of the exit doorway. Mount manual fire-alarm box on a background of a contrasting color. The operable part of manual fire-alarm box shall be between 42 inches and 48 inches above floor level. All devices shall be mounted at the same height unless otherwise indicated. Smoke- or Heat-Detector Spacing: FIRE ALARM INTEGRATED AUDIO VISUAL EMERGENCY COMMUNICATION SYSTEM 28 31 00 - 17 USD 315 Fire Alarm Request for Proposal Colby, KS 1. 2. 3. 4. 5. 6. Comply with the "Smoke-Sensing Fire Detectors" section in the "Initiating Devices" chapter in NFPA 72, for smoke-detector spacing. Comply with the "Heat-Sensing Fire Detectors" section in the "Initiating Devices" chapter in NFPA 72, for heat-detector spacing. Smooth ceiling spacing shall not exceed 30 feet. Spacing of detectors for irregular areas, for irregular ceiling construction, and for high ceiling areas shall be determined according to Annex A in NFPA 72. HVAC: Locate detectors not closer than 36 inches from air-supply diffuser or return-air opening. Lighting Fixtures: Locate detectors not closer than 12 inches from any part of a lighting fixture and not directly above pendant mounted or indirect lighting. E. Install a cover on each smoke detector that is not placed in service during construction. Cover shall remain in place except during system testing. Remove cover prior to system turnover. F. Duct Smoke Detectors: Comply with NFPA 72 and NFPA 90A. Install sampling tubes so they extend the full width of duct. Tubes more than 36 inches long shall be supported at both ends. 1. Do not install smoke detector in duct smoke-detector housing during construction. Install detector only during system testing and prior to system turnover. G. Elevator Shafts: Coordinate temperature rating and location with sprinkler rating and location. Do not install smoke detectors in sprinklered elevator shafts. H. Remote Status and Alarm Indicators: Install in a visible location near each smoke detector, sprinkler water-flow switch, and valvetamper switch that is not readily visible from normal viewing position. I. Audible Alarm-Indicating Devices: 1. Wall Mount: Install not less than 6 inches below the ceiling. Install speakers on flush-mounted back boxes with the deviceoperating mechanism concealed behind a grille. Install all devices at the same height unless otherwise indicated. 2. Ceiling Mount: Install in ceiling not more than 30’ on center. Install Speakers on flush mounted back boxes with the deviceoperating mechanism concealed behind a grille. J. Visible Alarm-Indicating Devices: Install adjacent to each alarm bell or alarm horn and at least 6 inches below the ceiling. Install all devices at the same height unless otherwise indicated. K. Device Location-Indicating Lights: device they monitor. Locate in public space near the FIRE ALARM INTEGRATED AUDIO VISUAL EMERGENCY COMMUNICATION SYSTEM 28 31 00 - 18 USD 315 Fire Alarm Request for Proposal Colby, KS 3.3 PATHWAYS A. Plenum rated cable shall be used for all pathways except where cabling is in conduit. B. Pathways above recessed accessible locations may be routed exposed. C. Pathways above inaccessible locations shall be installed in EMT. D. Pathways in exposed areas shall be routed in EMT and be painted red enamel. E. Pathways from main fire alarm control panel to each zone/building shall be routed underground to lower level mechanical or electrical room. Initial auxiliary panel(s) shall be located in these rooms. All cabling within the building zone shall be installed as specified above. 3.4 A. 3.5 ZONES Provide a fire alarm zone for each building that is identified on Drawings. Fire alarm activation and notification by zone/building. CABLING A. Power wiring for all systems shall be furnished and installed by the contractor as shown on the drawings and as required by the equipment manufacturer. B. When ceiling voids are used as air return plenums, only U.L. Listed plenum cable shall be used or cables shall be completely routed in conduit. C. All wiring installed in ceiling voids shall be bundled, neatly routed, suspended above the grid system or located in cable tray and labeled with appropriate tags as to service. D. Wire and cable shall be specifically designed to function with equipment supplied. Cable shall be color coded-RED for ease of installation and service, twisted, shielded, and grounded for control of voice circuits and covered with wear-resistant moisture proof protective insulation. Wire shall bear manufacturer's trademark either embossed or printed on cable. 3.6 CONNECTIONS A. For fire-protection systems related to doors in fire-rated walls and partitions and to doors in smoke partitions, verify that hardware and devices are listed for use with installed fire-alarm system before making connections. B. Make addressable connections with a supervised interface device to the following devices and systems. Install the interface device less than FIRE ALARM INTEGRATED AUDIO VISUAL EMERGENCY COMMUNICATION SYSTEM 28 31 00 - 19 USD 315 Fire Alarm Request for Proposal Colby, KS 36 inches from the device controlled. Make an addressable confirmation connection when such feedback is available at the device or system being controlled. 1. 2. 3. 4. 5. 6. 7. 8. 9. 3.7 Smoke dampers in air ducts of designated HVAC duct systems. Magnetically held-open doors. Electronically locked doors and access gates. Alarm-initiating connection to elevator recall system and components. Alarm-initiating connection to activate emergency lighting control. Supervisory connections at valve supervisory switches. Supervisory connections at elevator shunt-trip breaker. Supervisory connections at fire-extinguisher locations. Alarm-initiating connection to kitchen hood fire extinguishing system. IDENTIFICATION A. Identify system components, wiring, cabling, and terminals B. Install framed instructions in a location visible from FACP, ACU AND LOCs. 3.8 GROUNDING A. Ground fire-alarm control unit and associated circuits; comply with IEEE 1100. Install a ground wire from main service ground to firealarm control unit. B. Ground shielded cables at the control panel location only. shield at device location. 3.9 Insulate FIELD QUALITY CONTROL A. Field tests shall be witnessed by authorities having jurisdiction. B. Manufacturer's Field Service: Engage a factory-authorized service representative to test and inspect components, assemblies, and equipment installations, including connections. C. Perform tests and inspections. D. Perform the following tests and inspections with the assistance of a factory-authorized service representative: 1. Visual Inspection: a. Conduct visual inspection prior to testing. Inspection shall be based on completed record Drawings and system documentation that is required by the "Completion Documents, Preparation" table in the "Documentation" section of the "Fundamentals" chapter in NFPA 72. FIRE ALARM INTEGRATED AUDIO VISUAL EMERGENCY COMMUNICATION SYSTEM 28 31 00 - 20 USD 315 Fire Alarm Request for Proposal Colby, KS b. 2. 3. 4. 5. 6. Comply with the "Visual Inspection Frequencies" table in the "Inspection" section of the "Inspection, Testing and Maintenance" chapter in NFPA 72; retain the "Initial/Reacceptance" column and list only the installed components. System Testing: Comply with the "Test Methods" table in the "Testing" section of the "Inspection, Testing and Maintenance" chapter in NFPA 72. Test audible appliances for the public operating mode according to manufacturer's written instructions. Perform the test using a portable sound-level meter complying with Type 2 requirements in ANSI S1.4. Test audible appliances for the private operating mode according to manufacturer's written instructions. Test visible appliances for the public operating mode according to manufacturer's written instructions. Factory-authorized service representative shall prepare the "Fire Alarm System Record of Completion" in the "Documentation" section of the "Fundamentals" chapter in NFPA 72 and the "Inspection and Testing Form" in the "Records" section of the "Inspection, Testing and Maintenance" chapter in NFPA 72. E. Reacceptance Testing: Perform reacceptance testing to verify proper operation of added or replaced devices and appliances. F. Fire Alarm Integrated Audio Visual Emergency Communication system will be considered defective if it does not pass tests and inspections. G. Prepare test and inspection reports. H. Maintenance Test and Inspection: Perform tests and inspections listed for weekly, monthly, quarterly, and semiannual periods. Use forms developed for initial tests and inspections. I. Annual Test and Inspection: One year after date of Substantial Completion, test fire-alarm system complying with visual and testing inspection requirements in NFPA 72. Use forms developed for initial tests and inspections. 3.10 A. the MAINTENANCE SERVICE Initial Maintenance Service: Beginning at Substantial Completion, maintenance service shall include 12 months' full maintenance by skilled employees of manufacturer's designated service organization. Include preventive maintenance, repair or replacement of worn or defective components, lubrication, cleaning, and adjusting as required for proper operation. Parts and supplies shall be manufacturer's authorized replacement parts and supplies. 1. Include visual inspections according to the "Visual Inspection Frequencies" table in the "Testing" paragraph of the "Inspection, Testing and Maintenance" chapter in NFPA 72. FIRE ALARM INTEGRATED AUDIO VISUAL EMERGENCY COMMUNICATION SYSTEM 28 31 00 - 21 USD 315 Fire Alarm Request for Proposal Colby, KS 2. 3. 3.11 Perform tests in the "Test Methods" table in the "Testing" paragraph of the "Inspection, Testing and Maintenance" chapter in NFPA 72. Perform tests per the "Testing Frequencies" table in the "Testing" paragraph of the "Inspection, Testing and Maintenance" chapter in NFPA 72. SOFTWARE SERVICE AGREEMENT A. Comply with UL 864 and UL2572. B. Technical Support: Beginning at Substantial Completion, agreement shall include software support for two years. C. Upgrade Service: At Substantial Completion, update software to latest version. Install and program software upgrades that become available within two years from date of Substantial Completion. Upgrading software shall include operating system and new or revised licenses for using software. 1. 3.12 service Upgrade Notice: At least 30 days to allow Owner to schedule access to system and to upgrade computer equipment if necessary. TRAINING A. Engage a factory-authorized service representative to train Owner's maintenance personnel to adjust, operate, and maintain fire alarm integrated audio visual emergency communication system. B. The training shall provide a comprehensive understanding of how to utilize and properly operate all functions of the system. Contractor shall provide a training completion sheet indicating the Owner personnel trained and Owner approval of the training. 1. Training shall be completed in two phases: a. Classroom style training for all authorized personnel operating the Fire Alarm Integrated Audio Visual Emergency Communication System. b. Hands-On Training in which all authorized personnel operating the system shall conduct normal use of the system with the factory authorized service representative. END OF SECTION 28 31 00. FIRE ALARM INTEGRATED AUDIO VISUAL EMERGENCY COMMUNICATION SYSTEM 28 31 00 - 22