1 VO2301CE TAPSA CONTROL – EMERGENCY LIGHTING CENTRAL BATTERY UNIT WITH AUTOMATIC SELF-TESTING TK2301C – TK2308CB Product Description TAPSA CONTROL PRODUCT DESCRIPTION Doc. No. : VO2301CBE Rev.4; 19.07.2006 MKo Table of Contents Page 1. Description 1.1. Manufacturer 1.2. Type code 1.3. General description 1.4. Technical data 1.5. Directives and standards applied 4 4 4 4 4 5 2. Operational description 6 2.1. Central-module 2.1.1 The purpose of the central-module 2.1.2. Outputs 2.1.3. Recharging of the batteries 2.1.4. Limits of the mains voltage 2.1.5. Limits of the battery voltage 2.1.6. Alarm relay outputs 2.2. Control-module 2.2.1. Test of luminaires 2.2.2. Battery test 2.2.3. Alarm relay outputs 2.2.4. Operation during mains voltage breakdown 2.3. Optional features 2.3.1. Printer 2.3.2. Basic Central Monitoring unit 2.3.3. LON based Central Monitoring Unit 2.3.4. Remote control by a GSM-phone 2.3.5. Connection to building automation network 2.3.6. Usage via an external PC 6 6 6 7 7 7 8 8 8 8 9 9 9 9 10 10 11 11 11 3. Designing of the system 11 4. Installation of the system 12 5. Comissioning 5.1. Central-module 5.1.1. Setting the charging current 5.2. Control-module 5.2.1. Configuration 5.2.2. Reconfiguration 5.3. Normal mode 5.4. Setting of the internal clock 12 12 13 14 14 14 14 15 6. Using the basic functions 6.1. Central-module 6.2. Control-module 6.3. Printer 16 16 16 17 2 7. Maintenance 7.1. Replacing the batteries 17 8. Disposal 17 Appendixes: Appendix 1. Appendix 2. Appendix 3. Appendix 4. Appendix 5. Appendix 6. Control panel An example of a printed report Mechanical dimensions External connection Block diagram Component layout 3 1. Description 4 1.1. Manufacturer Teknoware Oy Ilmarisentie 8 FIN-15200 Lahti FINLAND 1.2. Type Code TK2301C … TK2308CB (See point 1.4. Technical data) 1.3. General description Tapsa Control is based on Teknoware’s modular Tapsa –central battery unit family for emergency lighting. In normal conditions the central unit takes its power from the 230VAC mains supply recharging the batteries and supplying the maintained luminaire groups with 230VAC voltage. In the case when the mains supply disappears or drops below 180VAC, the unit switches itself to emergency mode. Then the supply is taken from the 24VDC batteries and converted to 230VDC, which is supplied to both maintained and non-maintained luminaire groups. The supply is taken from the batteries as long as the net supply remains down or until the battery voltage drops to the deep discharge protection level of 19,2V. The central unit can supply up to 8 lighting group, depending on the type. The maximum load for each group is 120W. Each group can be connected independently as maintained or non-maintained. In addition to the standard operations described above, the Control-module of the central unit has the following testing and reporting features: - addressed testing of the luminaires and battery - battery capacity testing - external cabling as in a standard central battery unit. No separate data cabling. - self-learning system; luminaires can be added or removed afterwards - indicates the address of the faulty luminaire by LED and group number - short operation test once a day and full duration test twice a year - tests can be started also manually - testing and reporting optionally also with a GSM phone - printed report of the tests by integrated printer (=diary) - the report includes the date of testing, possible faulty luminaires, test duration and the condition of the batteries - possibility for optional connection to external data network, for example LON The batteries are located in a separate container according to EN 50171. All operations regarding the usage of the central unit can be performed from the control panel of it. Control panel has also LEDs for the indication of the status of the central unit and tests. The operations of the panel are described in the appendix 1. 5 1.4. Technical Data Mains supply: 230VAC 50Hz Output voltage: normal mode: 230VAC, emergency mode 230VDC Battery voltage: 24VDC Battery recharging time: 12 h Type of the central unit Input power from the mains supply Outputs TK2301C TK2302C TK2303C TK2304C TK2305C TK2306C TK2307C TK2308C TK2305CB TK2306CB TK2307CB TK2308CB 370 VA 420 VA 540 VA 660 VA 780 VA 900 VA 1020 VA 1140 VA 960 VA 1080 VA 1240 VA 1360 VA 1 x 120 W 2 x 120 W 3 x 120 W 4 x 120 W 5 x 120 W 6 x 120 W 7 x 120 W 8 x 120 W 5 x 120 W 6 x 120 W 7 x 120 W 8 x 120 W Battery capacity with 1h duration (max load) 17 Ah 24 Ah 38 Ah 65 Ah 65 Ah 100 Ah 100 Ah 100 Ah Battery capacity with 3h duration (max load) 24 Ah 65 Ah 65 Ah 100 Ah 150 Ah 150 Ah 200 Ah 200 Ah The central unit is fitted with a mains voltage fuse F2 10AT (inside the unit TS1), battery fuse F1 and recharging circuit fuse F1 and F2 (on the charger unitTS2/TS2B), which is located on the recharge unit. The battery recharge electronics is fitted with a battery temperature sensor, which controls the temperature compensation of the recharging voltage. Types ending with -B are fitted with twin charger units TS2 and TS2B to allow sufficient charging current for 150Ah and 200Ah batteries. The luminaries which are used with the central unit shall be suitable for both AC- and DC-supply and to enable the automatic testing feature they shall be of Teknoware type that has the type code ending –K or -T. (for example TW77581K) 1.5. Directives and standards The following standards are applied in designing of the Tapsa- Control central battery unit: EN 50171:2001 EN 50172 BS 5266-1: 2005 VDE 0108-100 (DIN EN 50172): 2005 EN 1838 EN 50081:1992 EN 50082-1:1997 Central power supply systems Emergency escape lighting systems Emergency lighting. Code of practice for the emergency lighting of premises Sicherheitsbeleuchtungsanlagen Lighting applications - Emergency lighting Electromagnetic compatibility. Residential, commercial and light industry, generic emission standard Electromagnetic compatibility. Generic immunity standard. Residential, commercial and light industry. The product is designed in full compliance and certified by SGS Fimko and UL Demko according to the following directives and product specific standards 6 Electrical safety and performance: 72/23/EEC, 93/68/EEC EN 50171:2001 Low voltage directive Central power supply systems Electro magnetic compatibility: 89/336/EEC, 92/31/EEC EN 50081:1992 EMC-directive Residential, commercial and light industry, generic emission standard Electromagnetic compatibility, generic immunity standard. Residential, commercial and light industry. EN 50082-1:1997 The company Teknoware is certified by SGS Fimko as follows: Quality: Environment: ISO 9001:2000 ISO 14001:1996 2. Operational description The Tapsa-Control central unit is divided to two operational modules: Central-module and Controlmodule, both in the same central unit. 2.1. Central-module 2.1.1. The purpose of the central-module The function of the central-module in normal mode is to recharge the batteries and supply the maintained emergency lighting groups. During the mains voltage breakdown the central unit supplies both maintained and non-maintained emergency lighting groups with the energy from the batteries. The descriptions of the indicator LEDs in the front panel are given in the appendix 1. 2.1.2. Outputs The output of the Tapsa-Control central unit is divided to max 8 groups. Each of them can be connected to maintained or non-maintained operation by the ”Mode” –connectors as follows: ”Mode” –connection closed: maintained ”Mode” –connection open: non-maintained 2.1.3. Recharging of the batteries 7 After the mains voltage breakdown the batteries are first recharged with a constant current (0.1c) until the voltage reaches 28.8V. After this there is a cyclic charge period where the recharging voltage is changed between 28.8V and 27.0V in the cycles of 4 minutes. These recharging modes last totally 12 hours after which the recharging is continued in a trickle charge mode where the battery voltage is maintained in 27.0V. Display: Mains use -LED is on Recharging -LED is on when the battery voltage is 27V±0.3V, otherwise it is blinking 2.1.4. Limits of the mains voltage When the mans voltage decreases below 180V (still being over 100V), the central unit turns to emergency mode showing the following display. Display: Mains use –LED is blinking Emergency mode -LED is on When the mains voltage drops below 100 V, the central unit turns to emergency mode showing the following display. Display: Emergency mode -LED is on When the mains voltage returns or increases to over 195V, the central turns unit back to normal mode and recharges the batteries as described in the point 2.1.3. Display: Mains use -LED is on Recharging -LED is on when the battery voltage is 27V±0.3V, otherwise it is blinking 2.1.5. Limits of the battery voltage If the battery voltage increases to over 28.8V in normal mode, there is an overvoltage alarm given. Display: Mains use -LED is on Overvoltage -LED is on Recharging –LED is blinking Internal fault –LED is on If the battery voltage drops under 25.2V in normal mode, there is an undervoltage alarm given. Display: Mains use -LED is on Undervoltage -LED is on Recharging -LED is blinking Internal fault –LED is on When the central unit is in emergency mode and the battery voltage decreases below 19.2V, the central unit turns to deep discharge protection mode where the discharging of the batteries is discontinued. Display: Deep discharge -LED is on Internal fault -LED is on Deep discharge –LED remains on until it is reset from the reset/test push-button switch. 8 The central unit can be manually switched to emergency mode also by a remote control switch, if it is fitted. Display: Mains use -LED is blinking Emergency mode -LED is on If the battery is disconnected or it does not accept recharge current, there are the following alarms on the display: Display: Mains use -LED is on Battery fault -LED is on General fault -LED is on 2.1.6. Alarm relay outputs Internal fault alarm Operation alarm - Gives an alarm when an internal fault has been detected. - Gives an alarm when the central unit is in emergency mode. 2.2 Control-module The control-module performs periodically automatic tests for luminaries and batteries. The descriptions of the indicator-LEDs are shown in the Appendix 1. 2.2.1. Test of luminaries The testing of each luminaire is performed automatically once a day at 24.00 o’clock. The test runs as follows: The central unit switches to emergency mode and the “luminaire test” –LED is on during the test. As the test proceeds, the group number in the display runs forward and when an operating luminaire is detected, the corresponding LED turns on. If there is a faulty luminaire detected, the program checks it again before it accepts the situation. When all groups are tested, the program returns to normal mode. If there is a faulty luminaire detected, the corresponding LED remains blinking when the corresponding group number is in the display. Also the “External fault” –LED and the relay output are on. LEDs which indicate luminaries which are ok, are on continuously. The report is printed after the test, if there is a new fault detected. Luminaire test can be started also manually by pressing the “Luminaire test” –button shortly. 2.2.2. Battery test The battery duration test is performed automatically twice a year, on Sunday night 24.00 on weeks 26 and 52 During the battery duration test all emergency luminaries are on and the operation of each of them is checked after each one minute. Display: 9 Battery test running –LED is on Luminaire test –LED is on once a minute when the luminaires are tested. If the specified duration is reached, the test is still continued for ½ hour to get more information of the capacity of the batteries. If the specified duration is not achieved, the test is discontinued and an alarm is given. Display: Battery test running –LED is blinking External fault –LED is on If the luminaire test is running during the stopping of the test, it will be completed though. The result of the battery duration test is printed to all reports during 30 days after the test. Possible battery fault alarm can be reset by pressing the “Battery test” -push button approx. 2 seconds. After the battery replacement the system must always be reconfigured, so that the system knows that battery has been replaced. If the battery fault alarm is just reset, but the batteries are not replaced, there will be a note on that in the next printout (if the panel is fitted with printer) of the luminaire test. Battery test can be started manually by pressing the “Battery test” -push button approx. 2 seconds. LED No.1 and a dot on the number display are turned on. The dot indicates that the system is prepared for the battery test. If the push-buttons are not touched, the battery test starts after approx. 40 seconds. 2.2.3. Alarm relay outputs When the “External fault” –LED is on, the fault alarm relay contact operates. When the battery test or luminaire test is running, the operation alarm relay contact operates. 2.2.4. Operation during mains voltage breakdown When a mains voltage breakdown occurs, the central unit switches to emergency mode. The system measures the length of the breakdown, and if it exceeds the specified battery duration time all LEDs of the control-module are switched off to save battery capacity. Only the dot at the number display remains blinking. The display returns to normal operation once the mains voltage recovers or if one of the push-buttons are pressed. 2.3. Optional features 2.3.1. Printer Tapsa Control central unit can be fitted with a printer, which automatically prints the reports in the following cases: - When a new fault is detected for the first time - Once a month The printout of the result of the last test can also be taken manually by pressing the “Print” pushbutton. This report can be attached to the diary of the central unit as a proof of the performed test. 2.3.2. Basic Central Monitoring Unit 10 Teknoware basic central monitoring unit can be used to monitor the basic status of up to 9 Tapsa Control panels. The following operations can be made from the monitoring unit: - Luminaire test - Battery test - Remote control to battery mode The following information can be seen from the monitoring unit - The basic status of each panel (normal mode / emergency mode) - External fault of each panel (one or more failed luminaires) - Internal fault of each panel (failed battery test or other abnormal situation) The basic monitoring system shows addressed (1…9) information from each panel, but not from each luminaire. In a case of luminaire failure, the indication is given on which Tapsa Control panel the luminaire is connected. The detailed address can then be seen from the corresponding Tapsa Control panel. 2.3.3. LON based Central Monitoring Unit using Lonix COBA Software With LON based central monitoring the entire emergency lighting system can be controlled and monitored from a single point. Standard personal computer, which is fitted with a LON-connection and Lonix COBA software, is used as user' s interface. From the user' s interface it is possible to monitor the status of the complete system and start necessary tests either manually or automatically. The status information of the luminaires and central battery units is available with individual addresses and the exact location of the units is shown on the map view. Up to 150 Tapsa Control panels can be fitted to the same network. Central monitoring system allows the user to monitor the status of the system and start the necessary tests. However, the actual emergency mode operation of the central battery units during a mains supply failure is entirely independent on the LON network. 11 In the data transmission the monitoring system utilizes an open architecture LON network. As a core of the software is the COBA building management software developed by Lonix. Due to this the Teknoware central monitoring system can be fully integrated to the building management systems in those buildings where COBA is already used. Alternatively the central monitoring can be built as a standalone system. 2.3.4. Remote control by a GSM-phone The control-module can be fitted with a GSM-modem, which allows a wireless remote control of the testing. The central unit sends the result of the test as an SMS-message to a pre-selected phone number. The results of the automatic tests are sent if a new fault is detected. When the fault indication has been sent to the GSM-phone, the fault indication LED remains on at the display of the central unit. It can be reset by pressing “Fault reset” –push-button. 2.3.5. Connection to building automation network The Control-module has a standard RS232 serial port (1200 baud), which accepts the connection to an external data network (for example EIB, LON, Ethernet) via a suitable connection module. It is possible to transmit the test reports and make the settings of the module through the network. For LON Teknoware can supply a ready installed module with required network variable data. 2.3.6. Usage via an external PC When the central unit is connected to the HyperTerminal of the PC, the operations of the Control module can also be used from the PC’s keyboard. ’!’ - the last test report is printed ’#’ - the luminaire test is performed and test report printed ’%’ – Control-module sends the current settings to the screen and new settings can be done Settings are of mode: yyyy/wk/dd/hh: min/battery duration/autotest/autoprint i.e. 2002/31/4/07:42/2/1/1: Year=2002 / week=31 / day 4(Thursday) / time 07:42 / battery duration 2x30min / auto test ON / auto print ON 3. Designing of the system The data between the Tapsa-Control central unit and the luminaires connected to it is transferred via the power supply wires of the luminaires, which means that there are no separate data cabling needed required. This means that the wiring between the central unit and the emergency luminaires does not differ from an ordinary system. Though, the following points shall be taken into account when designing the system. - The emergency luminaries shall be of Teknoware type which have a letter “K” in the end of their type code. These luminaries are fitted with a data transfer unit which is needed for the data transmission between the luminaries and central. - Each luminaire shall have the address number 1…12 set by the DIP-switches. The addresses can be chosen freely as long as there are no same addresses in the same lighting group. This coding can be pre-set by manufacturer, if the list of the addresses is given when ordering the luminaires (group No. / Luminaire No.). In this case the address No. is marked to each luminaire. 4. Installation of the system 12 Only a skilled person may perform operations related to installation, initial settings and maintenance of the system. The cabling is identical to a standard emergency lighting system, but when installing the luminaires it must be taken care that each luminaire in the same group has a different address number (1…12). Normally the addresses are pre-set to the luminaires already by the manufacturer and the address is marked to each luminaire. If necessary, the address of a luminaire can be changed by changing the settings of the DIP-switch which is located at the data transfer unit inside the luminaire. There are instructions for the settings of the switch on the label of the unit. Before beginning of the installation, the mains switch and battery fuse of the central shall be set to 0position. The batteries are installed in the separate battery container and they are connected in series (2x12V) to the battery cables + and -. The temperature sensor of the batteries shall be located so that it is close the surface of them, preferably between the batteries. Double-check the correct polarity of the batteries before connection. Connect the mains supply to the connectors L, PE and N. Next connect the lighting groups (see appendix 4, external wiring). The output groups are connected from the “Mode” connectors as maintained or non-maintained groups as follows. ”Mode” –connection closed: maintained group ”Mode” –connection open: non-maintained group The wiring of remote alarm and remote control switch is connected if they are included to the installation. 5. Comissioning Only a skilled person may perform operations related to installation, initial settings and maintenance of the system. 5.1. Central-Module Each Tapsa-Control central and Teknoware luminaries are tested for electrical safety according to the Low Voltage Directive by manufacturer. If there is an insulation resistance test made for the external wiring of the system, the input and outputs of the Tapsa-Control central shall be short-circuited. When the necessary installations and inspections are made, turn the battery switch (automatic fuse) to position I and turn the mains voltage on from the mains switch. Display: “Recharging” –LED is blinking “Mains use” –LED is on 13 5.1.1. Setting the charging current Charging current is set to minimum value as the factory setting. During comissioning the charging current shall be set as follows: TK2301C…TK2308C: Set the current from the DIP -switch of the charging module TS2. The charging current shall be always set according to the ampere hour value (Ah) of the batteries. If the value is incorrectly set, the batteries may get damaged. When all the switches are in OFF -position, the charging current is set for 100Ah batteries. DIP SWITCH SETTING TS2 1 DIP ON 2 DIP ON 3 DIP ON 4 DIP ON ALL OFF Battery capacity 17Ah 24Ah 38Ah 65Ah 100Ah Note: only one DIP switch may be "ON" at the same time. TK2305CB…TK2308CB (fitted with 2 charger units): With two charger units, the actual charging current is the sum of the current of the both charging units TS2 and TS2B. The current of each single unit is set as described for TK2301C…TK2308C above. Whenever possible, it is advisable to set the currents of both units close to each other. The currents shall be set according to the following table: DIP SWITCH SETTING TS2 3 DIP ON 4 DIP ON ALL OFF DIP SWITCH SETTING TS2B 4 DIP ON ALL OFF ALL OFF Outputs Battery capacity 38Ah + 65Ah 65Ah + 100Ah 2 x 100Ah 100Ah 150Ah 200Ah ATTENTION! SET THE CURRENT ALWAYS WITH THE VOLTAGE DISCONNECTED Mark the total load and battery mode duration to the type label which is located inside the panel. 14 5.2. Control-module: The control module does not require programming, but after starting the central-module the automatic configuration of the control-module is started by pressing shortly the “Luminaire test” –push button. During the automatic configuration the control-module learns the luminaries which are connected to the system. Before the configuration has been performed, the control-module gives the following display: Display: Big ” C” blinking on the 7 seg-display (the unit is not configured) ”External fault” -LED is on 5.2.1. Configuration Before the configuration it is advisable to still check that all luminaries are actually working, as the configuration teaches this situation to the control-module. The learned configuration is used as a reference in all tests which take place later. The correctness of the configuration can be also verified afterwards by checking that the amount of luminaries that the control-module indicates for each group corresponds the actual amount of the luminaries in the same group. If some of the luminaries is faulty during the configuration, this luminaire is not recognised and thus left outside the automatic testing. If two or more luminaries in the same group have the same address number, considers the control-module these as a single luminaire and detects the fault only when both are faulty. Configuration is started by pressing the “Luminaire test” -push button shortly. Configuration can last several minutes as the assembly of each group is checked few times before accepting it. Display: “Luminaire Test” -LED is blinking “External fault” -LED is blinking As the configuration process proceeds, the group number on the display increases and when a luminaire is detected, the corresponding LED turns on. The configuration can not be interrupted once it has been started. 5.2.3. Re-configuration If there are luminaries added of removed in the system or generally any modifications made to the installation, the control-module must be always re-configured. Re-configuration can be started by pressing the “Luminaire Test” –push button 5 seconds. During the re-configuration the control-module learns the new set-up of the luminaires. Also now it must be checked that all luminaries are actually operating before starting of the configuration. 5.3. Normal mode When the central has configured itself, it turns to normal mode where the status of the each luminaire group is rotated on the display panel. The status of each group is displayed about 3 seconds. 5.4. Setting of the internal clock 15 The internal clock setting mode is started by pressing the “Battery Test” –push button about 2 seconds after which the LED No. 1 turns on and there is a dot displayed on the number display (if no buttons is touched within 40 seconds, the battery test starts). Now, on the display there is a number which indicates decades of the year (i.e. 2006). The number can be changed by pressing the “Luminaire Test” –push button until the reading is correct. When the number is correct it is accepted by pressing the “Browse” –push button. Now the LED 2. turns on and the last digit of the year (i.e. 2002) can be set again by “Luminaire Test” –push button and accepted by “Browse” –push button. This is continued until all settings are correct. The indications of the LEDs during the clock setting: 1.LED – decades of the year number (i.e. 2006) 2.LED – last digit of the year number (i.e. 2006) 3.LED – first digit of the week number (i.e. 37) 4.LED – last digit of the week number (i.e. 37) 5.LED – day : mon=1, tue=2, wed=3, thu=4, fri=5, sat=6, sun=7 6.LED – first digit of hours (i.e. 13:45) 7.LED – last digit of hours (i.e. 13:45) 8.LED – first digit of minutes (i.e. 13:45) 9.LED – last digit of minutes (i.e. 13:45) 10.LED – specified emergency mode duration (reading x 30min, 30min … 240min) 11.LED – 0 = luminaire test only manually, 1 = luminaire test automatically every night at 24:00 12.LED – 0 = printing of report only manually, 1= printing of report after the test if a new fault has been detected. Note: If you notice that you have made a mistake with the settings, you can return to the start by pressing the “Battery Test” -push button 2 seconds, after which you can go to the faulty point using the “Browse” –button and make the correction. If no buttons is touched, the program returns to normal mode after 40 seconds. Settings can be checked by going to settings-mode by the “Battery Test” – button and browsing using the “Browse” –button. 6. Using the basic functions 16 The Tapsa-Control central battery unit is divided to two operational modules: - Central-module, which takes care of the standard emergency lighting operations, such as recharging of the batteries and supplying the lighting groups. - Control-module, which takes care of the automatic testing operations 6.1. Central-Module After the installation and configuration there are no other operations required from the user except checking of the indicator-LEDs (LH side LED column) regularly. In normal mode with the mains voltage on, are the “Mains Use” and “Recharging” –LEDs on. More specific explanations of the LEDs are in the appendix 1. 6.2. Control-Module With basic settings the Control-Module performs the following operations for the luminaries and batteries automatically: - Testing of each luminaire once a day - Testing of the battery duration in emergency mode twice a year If everything is ok, the “External Fault” –LED is not on If there is any fault detected in the tests, the “External Fault” –LED remains on. If there is a battery fault, the “Battery Test Running” -LED is blinking. If there is a luminaire fault, the corresponding LED is blinking when the number of the group in case is in the number display. The group number display can be browsed by the “Browse” –button. Both the luminaire test and battery test can be also started manually as follows: Luminaire test: Press the luminaire test button until the test starts. When the test has started, the “Luminaire Test Running” –LED is continuously on and the number display shows the number of the group which is currently tested. When the test is finished, the “Luminaire Test Running” –LED turns off and the result of the test can be seen from the display panel. Battery test: Press the “Battery Test” –button approx. 2 seconds until the LED 1 and dot on the number display turn on. The battery test starts after 40 seconds delay unless any of the push-buttons is touched. When the battery test starts, the “Battery Test Running” –LED turns on. If the specified duration is not reached remains the “External Fault” – LED on and the “Battery Test Running” –LED blinking. This alarm can be reset by pressing the “Battery Test” –button 2 seconds. Note. The battery test fully discharges the batteries and the maximum duration of it is 30 min over the specified emergency mode duration. The test can be interrupted by pressing the ”Battery Test” –button again. 6.3. Printer 17 When fitted, the printer prints the status report of the system automatically once a month and when a new fault has been detected. The printout of the status after the last test can be also started manually by pressing the ”Print” –button. The report of the test can be attached to the diary of the central as a proof of a performed test. 7. Maintenance In addition to the checks and inspections there is no regular maintenance required for the central battery unit other than changing the batteries when the specified emergency mode duration is no longer achieved. The luminaries shall have their light sources replaced once they have reached the end of their lifetime. Only a skilled person may perform such maintenance operations which require opening the casing of the central or the battery container. 7.1. Replacing the batteries The batteries are replaced as follows: - Remove the cover of the central unit - Turn the battery fuse switch F1 to position 0 - Turn the mains switch S1 to position 0 (the display turns off) - Remove the cover of the battery container - Disconnect the battery cables - Replace the batteries with new ones - Place the battery temperature sensor between the batteries - Connect the battery cables (double-check the polarity and insulation distances) - Install the cover of the battery container - Turn the battery fuse switch F1 to position 1 - Install the cover of the central - Turn the mains switch to position 1 - Configure the system as described in point 5.2.1. (If the configuration interrupts by itself, check the charge level of the batteries) - Set the clock as described in point 5.4. - Print the report and check that the central remains in normal mode according to the point 5.3. 8. Disposal When removing the central system and its components from usage, note the following points in the destruction of them: Batteries and fluorescent lamps are hazardous waste. Metal parts shall be recycled as steel or aluminium waste. Wires, connectors and circuit boards are considered as electronics waste. Plastic parts shall be recycled according to the material markings of them. 18 APPENDIX 1 Control panel: [--- Central-Module ---] [----------------- Control-Module -------------------] Descriptions of the LEDs of the Central-Module: Indication LED: Description: MAINS OPERATION - The central is operating in normal mode from the mains network. - If the LED blinks, the mains voltage is 100V-180V or the central is switched to emergency mode from the remote control switch or the control-module is currently performing the automating test. - The central is in emergency mode running on the battery OFF power - Battery voltage is higher than normally (over 28.8V) OFF BATTERY OPERATION BATTERY OVERVOLTAGE BATTERY UNDERVOLTAGE DEEP DISCHARGE RECHARGE CURRENT LIMIT BATTERY FAULT Normal status on mains use: ON - Battery voltage is lower than normally (under 25,2V) OFF - The deep discharge protection of the battery has operated (the voltage has dropped in emergency mode below 19.2V) - Indicates that the recharging voltage of the battery is on, and it is at correct level (27,0V +-0,3V) - Indicates too high recharging current - Indicates the condition of the battery and battery circuit OFF ON OFF OFF GROUND LEAKAGE INTERNAL FAULT - Indicates ground leakage if this feature is fitted (optional feature) - General fault indication. Operates if the battery overvoltage, battery undervoltage, deep discharge protection, current limit, battery fault or ground leakage LED is operating. OFF 19 OFF Descriptions of the LEDs of the Control-Module: LED: Number display LEDs 1-12 BATTERY TEST RUNNING LUMINAIRE TEST RUNNING EXTERNAL FAULT Description: Indicates the number of the luminaire group which has its luminaries indicated on the LEDs 1-12 Indicate the status of the luminaries of the group which has its number on the number display: - LED is continuously on: Luminaire is ok - LED is blinking: Luminaire is faulty - LED is off: There is no luminaire in that address - LED is continuously on: Battery test is running - LED is blinking: There is a fault detected in the battery test (in this case also the “EXTERNAL FAULT” –LED is on). - If the LED is continuously on, there is a luminaire test running - LED is continuously on, if there is a fault detected in the battery test or luminaire test. PRINT REPORT - LED is on when on while the report is printed FAULT ALARM - LED remains continuously on, if there has been an external alarm made RESET (relay contact output, SMS via GSM phone etc.) Other operations indicated by the LEDs: ”C” blinking on the The system has not been configured (see point 5. ” Preparing the system for number display use ”) ”LUMINAIRE TEST Configuration is running RUNNING” and ”EXTERNAL FAULT” –LEDs are blinking LED 1 and a dot on - The system is prepared for the battery test. The test starts if no buttons are the number display touched within 40 seconds. - The clock setting mode (see point 5.4 “Clock setting”) Push-buttons RESET / TEST BATTERY TEST LUMINAIRE TEST BROWSE PRINT REPORT FAULT ALARM RESET Resetting of the deep discharge protection alarm / starting of the 8 minutes emergency mode test Starting of the battery test and clock setting mode / Resetting of the Battery fault alarm Starting of the luminaire test / choosing of the setting values Browsing of the luminaire groups / choosing of the setting values Printing of the report from the last test Resetting the external fault alarm –LED 20 APPENDIX 2 An example of a printer report: ------------------------------------------------------------------------------------------------------------------------------ TAPSA CONTROL Teknoware TEST REPORT CENTRAL 04 2002/31/5 11:20 GROUP -> 1 2 3 4 5 6 7 8 LUMINAIRE|................................ 1 | - - - - - - - 2 | - - - - - - - 3 | - - - - - - - 4 | - - - - - - - 5 | - - - - - - - 6 | - - - - - - - 7 | - - - - - - - 8 | - - - - - - - 9 | - - - - - - - 10 | - - - - - - - 11 | - - - - - - - 12 | - - - - - - - LUMINAIRE TEST: OK BATTERY TEST : CENTRAL TEST : OK SETTINGS Emergency duration : 060 min Auto test : ON Auto print : ON Revision : F_ O OK F Fault - Not connected ? Added Checked by: ..../.../.... ........................... -----------------------------------------------------------------------------------------------------------------------------Descriptions: LUMINAIRE TEST: BATTERY TEST: CENTRAL TEST: OK / FAULT OK / FAULT / OK / FAULT SETTINGS Emergency duration: Auto test: Auto print: Rev: O V ? duration, which must be reached for passing the battery test ON - Periodic tests are performed automatically, OFF – test only manually ON – report always after the test. OFF report only manually revisions of the software: Control, IO, central-module Luminaire ok Luminaire faulty Luminaire is not connected A luminaire has been added but the system has not been configured after it APPENDIX 3 Mechanical dimensions Main panel: 21 22 Battery container: TK2310: TK2300: APPENDIX 4 23 External connection (RL1) Contacts are shown as in normal mode. Note! Switching the mains voltage off from the mains switch does remove the voltage from the system, as the battery is still supplying the luminaire groups. Switching off also the battery fuse switch F1 makes the complete unit voltage free. Connectors 12-13 shall be connected together if the remote control switch is not in use. If there is requested a single common alarm output from the central unit, the connectors for the internal and external alarm can be connected parallel. When the “Mode” –connection of the power module TS89401 is closed, is the lighting group that it supplies operates as maintained. When the “Mode” –connection is open, the corresponding group operates as non-maintained. APPENDIX 5 Operational Block diagram 24 APPENDIX 6 Component layout TK230xC 25 TK230xCB 26