Test- Machine With Solution Q.1 A Transformer has its maximum efficiency of 99% at 10KVA at 0.9 pf. The Cu-losses at 5 kW and 0.8 pf are (a) 91 W (b) 30.2 W (c) 35.6 W (d) 23.5 W Ans. (c) Exp. At a load S L xS0 10 kVA, S0 Rated & pf cos = 0.9, Maximum efficiency max 0.99 xS 0Cos xS 0Cos Pi x 2PcF Pi & PCF are Iron loss & full load Cu losses. Pi x 2PCF for max 0.99 10 0.9 10 0.9 Pi Pi Pi 0.091kW x S L 10 S0 S0 p i x 2PCF 2 10 0.091 PCF S PCF 9.1 104S2 kW At a load PL 5kW, Cos 0.8 SL x PL 5 6.25 kVA Cos 0.8 S L 6.25 S0 S0 Cu losses = x 2PCF 2 6.25 4 2 9.1 10 S 0 S0 0.0356 kW 35.6W Common Data for Q.2, Q.3 & Q.4 A 10KVA, 1000V/100V Single phase transformer has R1 2, X 1 5, R 2 0.03 and X 2 0.05 Q.2 The secondary terminal voltage (approximately) at 0.707 lag pf when delivering full load current with primary voltage held fixed at 1 kV. (a) 80.3 V (b) 90.4 V (c) 96.2 V (d) 98.5 V Ans. (b) Q.3 Determine the pf of rated load, supplied at 100V such that the terminal ENGINEERS ZONE IES / GATE / PSU 65/C Prateek Market, behind D.D.A Office, Munirka Ph: (011)-26194869, 9873000903, 9899713889 Website: www.qhengineerszone.org 1 Test- Machine With Solution voltage observed on reducing the load to zero is still 100V. (a) 0.89 lead (b) 0.707 lead (c) 0.92 lag Ans. (a) N 1 Exp. Transformation rotio K 2 N1 10 R2 X 2 (d) upf R2 0.03 3 2 2 K 1 10 X2 5 K2 Total resistance referred to primary R 01 R1 R2 2 3 5 X 01 X1 X 2 5 5 10 Rated S0 10 kVA V1 1 kV, V2 100V S0 V1I 1 V2 I 2 I1 10A & I 2 100A Base impedance referred to primary V 1000 Z1B 1 100 I1 10 per unit impedances. R 5 R pu 1 0.05 Z1B 100 X pu X 01 10 0.1 Z1B 100 At rated current & pf Cos (lag), The voltage regulation, VR R puCos X puS in At Cos 0.707 lag 45 Sin 0.707 VR 0.05 0.707 0.1 0.707 0.10605 10.605% Secondary voltage referred to primary V V2 2 10V2 K V V2 V .R 1 V2 0.10605 1000 V2 V2 V2 904.12V V2 90.412V It no-load voltage is equal to full load voltage, i.e. Vnl V fl V .R 0 ENGINEERS ZONE IES / GATE / PSU 65/C Prateek Market, behind D.D.A Office, Munirka Ph: (011)-26194869, 9873000903, 9899713889 Website: www.qhengineerszone.org 2 Test- Machine With Solution At leading pf c o s VR R puCos X puSin 0 tan R pu X pu 0.05 0.5 0.1 26.57 pf Cos 0.895 lead Q.4 Determine the maximum applied voltage on primary side if rated load is delivered at secondary at lag pf (a) 1000 V (b) 988 V (c) 1231 V (d) 1112 V Ans. (d) Exp. At lag pf & rated load VR R puCos X puSin d VR 0 d VR max if tan X pu R pu 0.1 2 0.05 63.45 VR max 0.05 cos 63.45 0.1 sin 63.45 0.112 11.2% V2 100V rated V2 V .R . V2 1000V K V1 V2 V2 VRmax V1max V2 V2 V1max 1000 1000 1112V 0.112 V1max Q.5 consider the following statements regarding Distribution Transformer. 1. It operates at rated load in general. 2. Its magnetising flux m is smaller than the ordinary power transformer of the same rating. 3. Its Iron losses are large as compared to the ordinary power transformer of the same rating. 4. Its size is large as compared to the ordinary power trasformer of same rating. 5. It gives maximum efficiency at rated load The currect statements are (a) 1, 2 and 3 (b) 3 and 4 (c) only 3 (d) 3, 4 and 5 Ans. (c) ENGINEERS ZONE IES / GATE / PSU 65/C Prateek Market, behind D.D.A Office, Munirka Ph: (011)-26194869, 9873000903, 9899713889 Website: www.qhengineerszone.org 3 Test- Machine With Solution Exp. Distribution transformer operates opproximately 70% of its rated load mostly So max at x 0.7 Pi x 2PCF Pi 0.49PCF while ordinary power transformer operates mostly at its rated load So max at x 1 Pi x 2PCF Pi PCF So Iron loss in distribution transformer are comparatively smaller. So peak flux density Bm in distrebution Transformer is designed to be small. V some for both. f If area of cross-section of core = A m Bm A Magnetising flux m As Bm small so A is large in distribution transormer. Common Data for Q.6 & Q.7 A 500 V/100 V, 10 kVA, T wo winding transformer is to be used as an autotransformer to supply a 100V load from 600V source. Q.6 Its kVA rating as an auto transformer. (a) 12 kVA (b) 8 kVA (c) 60 kVA (d) 48 kVA Ans. (a) Q.7 Its efficiency at rated load and 0.9 pf(lag) is 98% as a 2-winding transformer. Then efficiency as an auto transformer (a) 96.8 % (b) 99.6 % (c) 99.2 % (d) 98.3% Ans. (d) Exp. 10 kVA voltages 500/100 V currents 20 A/100 A Auto transformer as 600V/100V ENGINEERS ZONE IES / GATE / PSU 65/C Prateek Market, behind D.D.A Office, Munirka Ph: (011)-26194869, 9873000903, 9899713889 Website: www.qhengineerszone.org 4 Test- Machine With Solution V1 600V , I1 20 A V2 100V , I 2 120 A Sauto V1I1 V2I 2 12 kVA At rated load x 1 Efficiency of Tw transformer Cos SCos Pi PCF 0.98 10 0.9 10 0.9 Pi PCF Pi PCF 0.184 kW As current & voltages in each winding is same in both two-winding & auto trans former configuration the losses Pi PCF same auto Sauto Cos Sauto Cos Pi PCF 12 0.9 12 0.9 0.184 98.32% Q.8 The value of load resistance for maximum power delivered to R L is (a) 20 Ans. (a) (b) 5 Exp. Transformation Ratio K (c) 12 (d) 1.25 N2 2 N1 ENGINEERS ZONE IES / GATE / PSU 65/C Prateek Market, behind D.D.A Office, Munirka Ph: (011)-26194869, 9873000903, 9899713889 Website: www.qhengineerszone.org 5 Test- Machine With Solution load resistance refarred to primary R R R1L L2 L 4 K For maximum power delivered R1L Z s 3 j 4 5 RL 20 Q.9 A 1:2:4 three winding transformer is connected as shown in figure below The reading of voltmeter (a) 50 V (b) 250 V Ans. (d) Exp. (c) 150 V (d) 350 V OR Using KVL V0 50 100 200 0 V0 350V ENGINEERS ZONE IES / GATE / PSU 65/C Prateek Market, behind D.D.A Office, Munirka Ph: (011)-26194869, 9873000903, 9899713889 Website: www.qhengineerszone.org 6 Test- Machine With Solution Q.10 The efficiency of a 100 kVA transformer at upf is 98% at full as well as half load. The maximum efficiency is obtained at a load (a) 70.7 kVA (b) 50 kVA (c) 90.6 kVA (d) 82.5 kVA Ans. (a) Exp. x S Cos x S Cos Pi x 2PCF Rated So 100 kVA 98% 0.98 pf Cos 1 At full load x 1 1 100 1 0.98 1 100 1 Pi 12 PCF Pi PCF 2.04kW 1 At half full load x 0.5 0.5 100 1 0.98 0.5 100 1 Pi (0.5)2 PCF Pi 0.25PCF 1.02 2 By solving (1) & (2) Pi 0.68kW, PCF 1.36kW For max Pi x 2PCF x Pi 0.68 0.707 PCF 1.36 S L xS 0 0.707 100 70.7 kVA Q.11 A 4-pole Alternator has 72 slots carrying a 6-phase distributed winding. Each coil has span from 1 to 10. The winding factor for 3rd harmonic is 1 1 cot150 cot150 (a) (b) (c) (d) 0 3 cos15 6 sin150 3 6 Ans. (d) Exp. S 72, P 4, m 6 S 3 SPP q mp P 4 10 S 72 18 3q 3 3 10 Sin 2 2 3 3 10 qSin 3Sin 2 2 Sin K d3 ENGINEERS ZONE IES / GATE / PSU 65/C Prateek Market, behind D.D.A Office, Munirka Ph: (011)-26194869, 9873000903, 9899713889 Website: www.qhengineerszone.org 7 Test- Machine With Solution 1 3 2Sin15 Coil span from 1 to 16 i.e. coil span 16 1 15 slots 15 150 Angle of chording 180 150 30 Pitch factor K P 3 Cos 3 3 30 Cos 2 2 1 2 Winding factor K w Kd3 KP3 1 6sin15 Common Data for Q.12 & Q.13 A 220V, 10 kW, DC shunt motor is operating at a speed of 1000 rpm when taking 11A from supply. Its armature resistance is 2 and field resistance is 220. Q.12 The torque developed by motor (a) 20 Nm (b) 23.2 Nm (c) 19.1 Nm (d) 18 Nm Ans. (c) Q.13 If armature terminals are reversed suddenly and a resistance of 40 is connected in series with armature. The Braking Torque developed is (a) 200 Nm (b) 23.2 Nm (c) 19.1 Nm (d) 230.2 Nm Ans. (c) Exp. Shunt Motor supply V 220V , I 11A V 220 Field current I f R 220 1A f arm current I a I I f 10 A Back emf E V I a Ra 220 10 2 200V E K n N Where K n ZP 60 A ENGINEERS ZONE IES / GATE / PSU 65/C Prateek Market, behind D.D.A Office, Munirka Ph: (011)-26194869, 9873000903, 9899713889 Website: www.qhengineerszone.org 8 Test- Machine With Solution As I f Constant Constant K n E 200 0.2 V rpm N 1000 Toque developed T K a I a Where K a ZP 2 A 30 30 Kn Ia 0.2 10 19.1Nm If arm. terminals are interchanged T Braking current V E 220 200 Ib Ra Rb 2 40 10A Braking torque developed 30 Tb K a I b Kn Ib 30 0.2 10 19.1Nm Q.14 An Isolated Induction Generator without Capacitor Bank can supply the power to (a) 3 Induction motor at no load (b) DC motor through 3 rectifier (c) Overexcited synchronuous motor (d) Under excited synchronuous motor Ans. (c) Exp. Induction gen. can operate only at leading power factor. so load connected should be of leading pf i.e. overexcited syn. motor. Q.15 If the voltage Regulation of a DC generator is –95% approximately. It is (a) DC Shunt Generator (b) DC Series Generator (c) Level Compound Generator (d) Differentially Compound Generator Ans. (b) ENGINEERS ZONE IES / GATE / PSU 65/C Prateek Market, behind D.D.A Office, Munirka Ph: (011)-26194869, 9873000903, 9899713889 Website: www.qhengineerszone.org 9 Test- Machine With Solution Q.16 Match the lists List-I A. DC Shunt Generator B. Level Compound Generator C. Cumulative Compound Generator D. Differential Compound Generator A B C D (a) 3 4 1 2 (b) 2 3 4 1 (c) 3 1 4 2 (d) 4 3 2 1 Ans. (b) 1. 2. 3. 4. List-II –8% 12% 0% 4% Q.17 A DC generator is supplying rated load at 230V. If the terminal voltage observed on reducing the load to zero is still 230V then it is a (a) Under Compound Generator (b) Differential Compound Generator (c) Series Generator with large number of field turns (d) Level Compound Generator Ans. (d) Q.18 A DC generator is operating at constant speed and constant field excitation. If it is supplying maximum power at a voltage of 220 it’s generated emf is (a) 110 V (b) 220 V (c) 440 V (d) depends upon the armature resistance Ans. (c) Q.19 A DC series motor is driving a load which is propotional to the cube of speed. The total resistance of motor is 2 and motor takes 5A and runs at 1000rpm, when operating from 200V supply. The resistance to be inserted in series with armature to reduce the operating speed to 600rpm, is (Neglect saturation). (a) 10.23 (b) 61.4 (c) 5.2 (d) 2.5 Ans. (b) Exp. DC series motor Total resistance R Ra Rse 2 V 200V At I a 5 A, N 1000rpm back emf E V I a R 200 5 2 190V Flux by series field se I a se K se I a ENGINEERS ZONE IES / GATE / PSU 65/C Prateek Market, behind D.D.A Office, Munirka Ph: (011)-26194869, 9873000903, 9899713889 Website: www.qhengineerszone.org 10 Test- Machine With Solution E K n se N K n K se I a N E 190 Constant K n K se I N 5 1000 a 0.038 V A-rpm Torque T N 3 3 T N 3 T N Torque develope T K ase I a K a K se I a 2 or T Ia2 3 I a N N Ia 2 2 At 3 I a 600 I a 2.32A 5 1000 I a 2.32A E K n K se I a N Let 0.038 2.32 600 52.9V Ra Ra Rext E V I a Ra 52.9 200 2.33 Ra Ra 63.4 Rext 61.4 Q.20 A 5 kW, 220 V, 4-pole, lap connected DC motor has 400 armature conductors. At full load, the flux per pole is 25 mWb and rotational losses are 200W. The armature resistance is 1 . The speed at full load is (a) 1280 rpm (b) 1350 rpm (c) 1160 rpm (d) 1400 rpm Ans. (c) Exp. At full load, Net mechanical output =5 kW Gross power o / p 5000 200 5200W At full load current E V I a Ra 220 I a 1 power output P0 EI a 5200 220 I a I a I a 2 220I a 5200 0 I a 26.9A, 193.1A ENGINEERS ZONE IES / GATE / PSU 65/C Prateek Market, behind D.D.A Office, Munirka Ph: (011)-26194869, 9873000903, 9899713889 Website: www.qhengineerszone.org 11 Test- Machine With Solution So I a 26.9A, (193.1A large so it not considerable E 220 26.9 193.1V ZN P E 60 A Lap connected so number of paralled paths A P 4 0.025 400 N 4 193.1 60 4 Speed N 1158.6rpm Q.21 A DC shunt motor is driving constant power load at rated speed while drawing rated armature current. If the terminal voltage is halved but field current is kept constant, then (approximately). (a) I a gets doubled & N is halved (b) Both I a & N gets doubled (c) I a gets doubled but N remains same (d) I a gets halved & N gets doubled Ans. (a) Exp. Power output P0 EI a constant field current I f = const constant back emf E V I a Ra Let Ra 0 E V P V I a constant V V As P V I a V I a 2 I a 2 I a E V Speed N K K n n V V N N K n 2K n 2 Common Data for Q.22 & Q.23 The stator of a 3 , 4-pole SRIM is connected to 50Hz supply. At the rotor terminals a frequency of 30Hz is required. Q.22 The possible speed (s) of rotor is (are) (a) 600 rpm (b) 2400 rpm (c) 600 or 2400 rpm (d) 600 & 900 rpm Ans. (c) Q.23 For a frequency of 30Hz across rotor terminals (a) Two emfs of equal magnitudes and opposite phase sequence can be obtained (b) Two emfs of different magnitude and same sequence ENGINEERS ZONE IES / GATE / PSU 65/C Prateek Market, behind D.D.A Office, Munirka Ph: (011)-26194869, 9873000903, 9899713889 Website: www.qhengineerszone.org 12 Test- Machine With Solution (c) Only one possible emf (d) The emf of any magnitude and sequence Ans. (a) Q.24 A 6-pole, 50Hz, 3 I.M. has a rotor resistance of 0.2 per phase and maximum torque is obtained at a speed of 875rpm while full load speed is 960rpm. The resistance to be added in each rotor phase to obtain 80% of full load troque at starting is (a) 0.16 (b) 0.05 (c) 0.22 (d) 0.192 Ans. (d) Exp. 120 f Ns 1000rpm P speed for Tmax, N m 875rpm So slip sm N s Nm 0.125 Ns Full load speed N fl 960 rpm s fl 0.04 if stator impedence is neglected sm R2 0.125 X2 0.2 0.125 X2 X 2 1.6 T 3 E22R2 / s s R2 2 2 s X 2 At full load & R20 0.2 3E 22 0.2 / 0.04 T fl s 0.2 2 2 1.6 0.04 3E 2 0.18 2 s At starting s 1 & R2 R20 Rext 3E 22 R2 Tst 0.8T fl s R22 X 22 3E22 3E22 R2 0.8 0.18 s R22 1.62 s ENGINEERS ZONE IES / GATE / PSU 65/C Prateek Market, behind D.D.A Office, Munirka Ph: (011)-26194869, 9873000903, 9899713889 Website: www.qhengineerszone.org 13 Test- Machine With Solution R22 R2 0.145 2.56 R22 6.9R2 2.56 0 R2 0.39, 6.5 Higher value 6.5 creates excess power loss So it is not acceptable So R2 0.39 Rext 0.19 Q.25 An alternator has a synchronuous reactance of 20% and neglegible resistance. The pf of rated load at which it gives zero voltage regulation is (a) upf (b) 0.1 lead (c) 0.995 lead (d) 0.99 lag Ans. (c) Exp. Resistance Ra 0 , X s 20% 0.2 pu Rated current = I a , Rated voltage = V V Base impedance Z B I a Xs pu reactance X s Z B Xs Ia I R 0.2 , Ra ( pu ) a a V V zero voltage regulation, i.e. E = V At leading pf X s( pu ) 2 2 E 2 VCos I a Ra V sin I a X s 2 2 I a Ra Ia X s V Cos Sin V V 2 E 2 V 2 Cos R pu 2 2 Sin X pu 1 Cos Sin X pu 2 2 Cos2 Sin 2 2X puSin X 2pu 1 X pu 0.2 0.1 2 2 Cos 0.995 leading Sin Q.26 An alternator has armature resistance of 2% and synchronuous reactance of 20%. The pf at which it gives voltage regulation of 10%. (a) 0.956 lead (b) 0.944 lag (c) 0.823 lag (d) 0.853 lead Ans. (b) Exp. ENGINEERS ZONE IES / GATE / PSU 65/C Prateek Market, behind D.D.A Office, Munirka Ph: (011)-26194869, 9873000903, 9899713889 Website: www.qhengineerszone.org 14 Test- Machine With Solution E V 100 10 V E 1.1V E V , i.e. pf Cos lag V .R. As 2 2 E 2 VCos I a Ra VSin I a X s E 2 V 2 Cos R pu 2 Sin X spu 2 1.12 Cos 0.022 Sin 0.22 1.21 Cos2 Sin 2 0.04Cos 0.0004 0.4Sin 0.04 0.4Sin 0.04Cos 0.1696 Cos 10Sin 4.24 1 RCos , 10 RSin R 10.05 , 84.3ο R Cos Cos Sin Sin 4.24 Cos 0.422 65 149.4 ,19.3 pf angle 90 19.3 Cos 0.944 Q.27 A lossless salient pole synchronuous motor has reluctance along q-axis twice that of along d-axis and operating in such a manner as excitation voltage is equal to the terminal voltage. The ratio of reluctance torque to the electromagnetic torque developed when it is delivering maximum load is (a) 0.5 (b) 0.75 (c) 0.25 (d) 1 Ans. (a) Exp. The power o/p developed EV V 1 1 P Sin Sin 2 Xd 2 X q X d E V , Rq 2Rd N 2 N 2 X , X d Reactances q Rq Rd Xq P Xd 2 V2 V2 Sin Sin 2 Xd 2X d P Torque developed T s T V2 V2 Sin Sin 2 s X d 2 s X d ENGINEERS ZONE IES / GATE / PSU 65/C Prateek Market, behind D.D.A Office, Munirka Ph: (011)-26194869, 9873000903, 9899713889 Website: www.qhengineerszone.org 15 Test- Machine With Solution electromagnetic torque Tem V V2 Sin s X d 2 Reluctance torque Trel 2 X Sin 2 s d Trel Sin 2 Ratue T 2Sin Cos em dP dT 0 or 0 For maximum load d d dP V 2 Cos Cos 2 0 d Xd Cos2 Cos 0 2Cos 2 Cos 1 0 1 1 4 Cos 4 3 1 1 As cos ve 4 2 Trel 1 Tem 2 Q.28 A 3 synchronuous motor, connected to bus, is operating with normal excitation with increase in load 1. Armature current increases 2. pf becomes lagging 3. pf becomes leading 4. load angle increases 5. Reactive power flows from Bus to motor 6. Reactive power flows from motor to Bus from these correct statements are (a) 1, 3, 4 & 6 (b) 2, 4, & 5 (c) 1, 3, & 6 (d) 1, 2, 4 & 5 Ans. (d) Exp. The V curres of syn. motor ENGINEERS ZONE IES / GATE / PSU 65/C Prateek Market, behind D.D.A Office, Munirka Ph: (011)-26194869, 9873000903, 9899713889 Website: www.qhengineerszone.org 16 Test- Machine With Solution At load P1 , I f 01 is nominal excitation (at upf) and current I a 01 If load is increased P2 P1 Current increases I a 02 I a 01 For P2, I f 02 is nominal. But I f in constant at I f 01 so for P2 , I f 01 gives under excited syn. motor, i.e. at lag pf. Syn. motor at lag pf consumes VAR from bus. Q.29 A synchronuous generator fed from bus is delivering half-full load. If an increase in its field current causes a reduction in its armature current, then generator is (a) delivers active power to bus and absorbs reactive power from bus (b) absorbs active power from bus and delivers reactive power to bus (c) absorbs active and reactive power from bus (d) delivers active and reactive power to bus Ans. (a) Exp. Increase in field current causes a reduction in armature current so syn. generator is operating in under excited condition, i.e. at leading pf . Gen. delivering active power to the bus. ENGINEERS ZONE IES / GATE / PSU 65/C Prateek Market, behind D.D.A Office, Munirka Ph: (011)-26194869, 9873000903, 9899713889 Website: www.qhengineerszone.org 17 Test- Machine With Solution At lead pf , generator is supplying -ve VAR to bus hence it is consuming +ve VAR from the bus. Q.30 A 3 lossless cylindrical rotor synchronous motor is connected to bus, it is operating in under excited condition and at constant pf, if load on the motor is increased, the excitation voltage variation is represented by (a) Curve-1 Ans. (a) Exp. For syn. motor (b) Curve-2 (c) Curve-3 (d) Curve-4 E V j I a Xs At lag pf cos i.e I a lags behind V by angle Power P V I a cos V & cos Cosnstant so if load P increases I a increases and locus of phasor E is given by straight line as shown. E is decreasing, reaches a minimum, i.e E min and then increasing continuously. ENGINEERS ZONE IES / GATE / PSU 65/C Prateek Market, behind D.D.A Office, Munirka Ph: (011)-26194869, 9873000903, 9899713889 Website: www.qhengineerszone.org 18